Bop Operation Manual Qn1 Sec g 04 Tp 005(195) Dang Doc
-
Upload
bui-vanluong -
Category
Documents
-
view
68 -
download
4
Transcript of Bop Operation Manual Qn1 Sec g 04 Tp 005(195) Dang Doc
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2 × 300 MW – Anthracite Coal Fired Power Station
BOP Operation
Manual
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Index
1 Scope ................................................................................................................................................................... 4
2 Specific quoting documents ............................................................................................................................... 4
3 Fuel Oil Unloading and Storage & Supply System Operation Manual ......................................................... 4
3.1 Equipments and general description of fuel oil system and fire fighting system .......................................... 4
3.2 Basic properties and technical specification of fuel oil system..................................................................... 4
3.3 Interlock and protection of system ................................................................................................................ 6
3.4 Startup and shutdown of system ................................................................................................................... 6
3.5 Inspections and notices before startup of fuel oil system.............................................................................. 9
3.6 Operation regulating of fuel oil system (oil supply and unloading)............................................................ 10
3.7 Operation regulating of effluent oil system..................................................................................................11
3.8 Operation Check and maintenance of fuel oil system ................................................................................. 13
3.9 Safety operation cautions of fuel oil system ............................................................................................... 13
3.10 Common fault, judgment and disposal of fuel oil system and equipments ............................................... 15
4 Water Treatment Plant Operation Manual.................................................................................................... 21
4.1 General Description .................................................................................................................................... 21
4.2 Technical Specification ............................................................................................................................... 21
4.3 Operation .................................................................................................................................................... 22
4.4 Common faults, judgment and treatment at the water purification station ................................................. 27
5 Demineralization system Operation Manual ................................................................................................. 28
5.1 General description ..................................................................................................................................... 28
5.2 Technical specification of equipment.......................................................................................................... 29
5.3 Control standard and period of water quality of feed-water treatment system ........................................... 30
5.4 Operation of demineralized equipments ..................................................................................................... 31
5.5 Common faults, judgment and disposal ...................................................................................................... 43
6 Water Steam Supervision System Operation Manual................................................................................... 46
6.1 Technical specification................................................................................................................................ 46
6.2 Chemical supervision during unit operation ............................................................................................... 51
6.3 Chemical protection of standby unit ........................................................................................................... 55
6.4 Operation of the boiler chemical dosing system of the boiler..................................................................... 57
6.5 Reason and treatment of water steam quality deterioration ........................................................................ 59
7 Waste Water Treatment Plant Operation Manual ........................................................................................ 64
7.1 General description of waste water station and system............................................................................... 64
7.2 Technical specification................................................................................................................................ 64
7.3 Operation of waste water treatment equipments ......................................................................................... 66
7.4 Common faults, judgment and Treatment of wastewater station and wastewater system........................... 69
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 1
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
8 Hydrogen Generation Plant Operation Manual............................................................................................ 70
8.1 General descriptions of hydrogen plant and hydrogen system.................................................................... 70
8.2 Technical norms of equipments .................................................................................................................. 70
8.3 Equipments operation ................................................................................................................................. 72
8.4 Common faults, judgment and Treatment of hydrogen station and hydrogen generation system............... 76
8.5 Special safety cautions of hydrogen generation station and hydrogen generation system .......................... 79
9. Circulating Water System & Auxiary Cooling Water System Operation Manual .................................... 80
9.1 Equipment Technical Specification............................................................................................................. 80
9.2 Circulating Water System ........................................................................................................................... 81
9.3 Auxilary Cooling Water System.................................................................................................................. 87
10 ESP System & Deslagging and Ash Handing System Operation Manual ................................................. 90
10.1 Scope .................................................................................................................................................... 90
10.2 Specific quoting documents ................................................................................................................. 91
10.3 Principal specification of system.......................................................................................................... 91
10.4 Startup, operation and maintenance and stop of ESP system ............................................................... 94
10.5 Startup, operation, maintenance and stop of negative-pressure ash removal system ......................... 100
10.6 Startup, operation, maintenance and stop of the hydraulic deslagging system................................... 105
11 FGD and Limestone Supply System Operation Manual............................................................................110
11.1 SCOPE ................................................................................................................................................110
11.2 NORMALIZED DOCUMENT QUOTATION ...................................................................................111
11.3 FGD SYSTEM QUIPMENT SPECIFICATION .................................................................................111
11.4 START-UP OF DESULFURIZATION SYSTEM .............................................................................. 129
11.5 MONITORING AND REGULATION IN FGD SYSTEM OPERATION ......................................... 145
11.6 SHUT DOWN OF THE FGD SYSTEM ............................................................................................ 160
11.7 FGD SYSTEM FAULT AND ACCIDENT HANDLING .................................................................. 164
11.8 OPERATION OF LIMESTONE SUPPLY SYSTEM ........................................................................ 171
11.9 11.9 LIMESTONE HANDLING SYSTEM DESCRIPTION ............................................................ 174
12 Air Compressor System Operation Manual............................................................................................... 176
12.1 Direction for use of control panel....................................................................................................... 176
12.2 Instrument-use air compressor operation ........................................................................................... 176
12.3 Air compressor operation maintain .................................................................................................... 176
12.4 Air compressor shutdown protection.................................................................................................. 177
12.5 Air compressor dryer operation maintain ........................................................................................... 177
13 Fire-fighting System Operation Manual .................................................................................................... 177
13.1 Overview................................................................................................................................................. 177
13.2 Startup mode of fire-fighting pump ........................................................................................................ 177
13.3 Operation mode of fire-fighting pump .................................................................................................... 178
13.4 Chain conditions of fire-fighting pump................................................................................................... 178
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 2
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
13.5 Diesel fire-fighting pump system............................................................................................................ 178
13.6 Descriptions of fault and alarm of diesel engine fire-fighting pump ...................................................... 180
13.7 Descriptions of function buttons ............................................................................................................. 180
13.8 Inspection items in the operation of diesel pump group ......................................................................... 181
13.9 Regular maintenance of diesel pump group ............................................................................................ 181
14 Appendix ....................................................................................................................................................... 182
14.1 Twenty-five Key Requirements to Prevent Serious Accident and Failure in Electric Power Operation
(Chemical Part) Issued by China Grid ............................................................................................................ 182
14.1.1 Prevention from large area corrosion............................................................................................ 182
14.1.2 Prevention from tube explosion of pressure vessel .................................................................... 182
13.1.3 Prevention from motor damage ..................................................................................................... 182
14.2 General Principle of Electrical Part and Pump........................................................................................ 182
14.2.1 Inspection items before power on the motor are as follows: ..................................................... 182
14.2.2 Inspection items during operation of the motor are as follows: ................................................. 182
14.2.3 Inspection items during operation of cables are as follows: ...................................................... 183
13.2.4 General operation requirements of the motor.............................................................................. 184
14.2.5 Measurement Manual of insulation resistance of the motor are as follows: ........................... 184
13.2.6 Operation principle of power failure and supply of the motor: ................................................... 184
14.2.7 Permissible startup times of the motor with squirrel cage type rotor shall be in accordance with
following Manual strictly. ............................................................................................................................. 185
13.2.8 Definition of the motor status: ........................................................................................................ 185
14.2.9 Common faults, judgment and treatment of electrical equipments .......................................... 185
14.2.10 Operation of the water pump........................................................................................................ 187
14.3 General Principle of Chemical Technology Supervision ........................................................................ 189
14.3.1 Guidelines of chemical technology supervision........................................................................... 189
14.3.2 Chemical supervision during startup phase of unit ..................................................................... 190
14.3.3 Normal operation management of the unit ................................................................................... 190
14.3.4 Abnormal quality management of water vapor ............................................................................ 192
14.3.5 Supervision during repair phase of the unit.................................................................................. 193
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 3
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
1 Scope
This teaching material is applicable for technical education of staff engaging in chemical
operation of Quang Ninh 2X300MW Thermal Power Plant in Vietnam, including the operation
principle, start-up, shut-down, operation and maintenance, control and adjustment, accident
disposal of dematerialized water system, water-stem sampling and dosing system, hydrogen
generation system, FGD System and waste water treatment system, as well as the principle,
method and procedures for chemical supervision of water-steam-hydrogen of this thermal power
plant. Staff of Quang Ninh Thermoelectric Co., Ltd. at all levels engaging in chemical operation,
power generation operation, equipment maintenance and production technology management
must be familiar with all the standard and the relevant parts and strictly implement them.
2 Specific quoting documents
DL/T 543-1994 Quality Inspection Standard for Water Treatment Equipment Used in
Power Plant DL/T 561-1995 Guide for Chemical Supervision of Water and Steam in Thermal Power
Plant DL/T 794-2001 Guide for Chemical Cleaning of the boiler in Thermal Power Plant DL/T 5068-1996 Technical Code for Chemical Design of Thermal Power Plant SD 223-1987 Guideline for Lay-up of Thermal Power Equipment in Fossil Fuel Plant DL434-1991 Manual for Implementation of Legal Metering Unit in Chemical Water
Discipline of Power Plant GB12145-1989 Quality Criterion for Water and Steam of Steam Power Equipment and
Thermal Power Unit 3 Fuel Oil Unloading and Storage & Supply System Operation Manual
3.1 Equipments and general description of fuel oil system and fire fighting system
The project is equipped with 2 × 5000 t oil tank, 2 oil unload pumps, 8 oil supply pumps, and 3
scavenge oil pumps, 1 deoiler, 4 fuel oil heaters, 1 drain flash tank, and 1 fuel oil cooler. Fuel oil
system is furnished with oil supply piping and oil return pipe to boiler burner, according to single
header circulating system for oil supply and return to boiler.
The fire fighting systems is equipped with foam tank, various mobile fire fighting apparatuses
and fire water system.
3.2 Basic properties and technical specification of fuel oil system
Model
HSNH1300-54
Quantity
2
Arrange
ment
mode
Indoor,
horizontal
type
Medium Heavy oil, oil
temperature
50
Flow rate
95 m3/h
Lift
80 mH2O
Screw
type oil
unload
pump
Efficienc
y
70%
NPSHr limit value is 6 m,
guaranteed value
is 5.5 m
Speed
1450 r/min
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 4
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Model
YB225M-4(防
爆)
Shaft
power
32.2 KW
Rated
power
45 KW
Motor
Speed 1450 r/min Voltage 400 V AC
Model
32QW12-15
Quantity
2
Arrange
ment
mode
Outdoor
submersibl
e pump
Motor
model
YB90S-4(expl
osion-proof
motor )
Flow rate
10m3/h
Lift
10 mH2O
Efficienc
y 40%
NPSHr
5m
Speed
1450 r/min
Submers
ible
pump for
wastewa
ter with
oil
Rated
power
0.9 KW
Shaft
power
1.1 KW
Voltage
400 V AC
Front
screen of
heavy oil
unload
pump
Type
30 mesh
Model
LY-100
Quantity
1LY-100
Heavy oil
Oil
temperature
25~50
Flow rate
95 m3/h (每)
Piping
design
pressure
0.6 MPa
Screen
paramet
ers
Inlet/outl
et pipe
diameter
DN150
Inlet/outlet
operating
pressure
difference
0.1MPa
Inlet/outl
et alarm
pressure
differenc
e
0.5MPa
Type
Horizontal
type U-tube
Model
ZJRQ-28
Arrange
ment
mode
Horizontal
type
Quantity
1 Inlet oil
temperatur
e
25 Outlet oil
temperat
ure
50
Fuel oil
heater
Fuel oil
flow
95 m3/h(each) Operating
oil
pressure
0.8 MPa Design
oil
pressure
1.5 MPa
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 5
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Heated
steam
operatin
g
temperat
ure
250
Heated
steam
design
temperatur
e
300
Heated
steam
Operatin
g
pressure
0.6 MPa
Heated
steam
design
pressure
1.5 MPa
Max.
heater
pressure
drop
< 5 MLC (On shell
side)
Heater
area
28 m2
Model SMH660R40E6-7W23 Flow rate 26.5 m³/h Oil
supply
pump
Motor model
YB180M-4
Lift
100m
3.3 Interlock and protection of system
Interlock control is carried out by 8 oil supply pumps for fuel oil system together with boiler
combustion system.
3.4 Startup and shutdown of system
3.4.1 Startup operation sequence of heavy oil system
Oil store system can be started if oil temperature of large oil tanks is heated to 75 .
3.4.1.1 Purging and preheating for equipment, and system
(1) Contact foreman, shift supervisor to cooperate, and the foreman is responsible for total
command and contact work.
(2) Purge and preheat operation for oil return system
a) Open primary, secondary oil return valve on #1(#2) oil, close main oil feed valve before
the boiler.
b) Open main heat supply valve in heavy oil system, and open heated steam valve of boiler.
Connect turbine, and turn on tracing steam supply for boiler heavy oil. Slightly open boiler
drain valve, wait until remaining water has been drained up before closing.
c) Inform oil store to open front steam, oil interconnection valve, and open steam purge
valve on oil return header, so as to carry out purge and preheat for oil return system.
d) If the gas is emitted at the top of #1 (#2) oil tank, report it to the foreman. Except oil return
valve on #1, #2 oil tank is open, close all valves in items a, c.
(3) Purge and preheat operation for oil feed system
a) Open oil return valve of pump for #1 (#2) oil tank. Open interconnection valve form oil
supply mains to oil return mains of the pump. Open inlet and outlet valves for
corresponding heaters. Report this to foreman.
b) Close front oil return valve, and open oil feed valve of boiler, then open steam, oil
interconnection valve of boiler, finally open steam purge valve on oil feed mains. Then
inform oil store to start purging and preheating for oil feed system.
c) If the gas is emitted at the top of #1 (#2) oil tank, report it to the foreman. Close
interconnection valve form oil supply mains to oil return mains of the pump and all valves
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 6
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
open in item b. Open oil drain valve of heater.
(4) Purge and preheat operation for large oil tank to pump inlet system
a) Open oil drain valve in pump inlet mains, and open purge valve in outlet mains of oil tank,
in order to carry out purging and preheating.
b) Wait until oil drain valve in pump inlet mains is hot, close all valves open in item a.
(5) Purge and preheat operation for all pump body, filter, and pump oil return system
a) Open inlet valve of first, second-stage oil supply pump, and open oil drain valve at
corresponding filter inlet, then open steam purge valve for first, second-stage oil supply
pump, in order to carry out purging and preheating for all pumps and filters.
b) Wait until oil drain valves for all filters is very hot, open partial circulating valves for first,
second-stage oil supply pump, and open oil return valves for first, second-stage oil
supply pump, and close inlet valves for first, second-stage oil supply pump, then close
outlet valves and oil drain valves for corresponding filters, in order to carry out purging
and preheating for oil return system.
c) Wait until oil return valve is very hot, close all opened valves. By now, purge and preheat
operations before startup of all system, equipment are completed, and report it to the
foreman.
3.4.1.2 Startup operation
(1) open the following valves: oil supply valve on #1 (#2) oil tank, inlet valves on first,
second-stage oil supply pump to be started and outlet, inlet valves for corresponding filters; oil
return valve on #1 (#2) oil tank.
(2) Make an overall, carefully pre-startup inspection for first, second-stage oil supply pumps to be
started.
(3) Close start switches for second, first-stage oil supply pumps to be started respectively, and
start second, first-stage oil supply pumps respectively.
(4) When outlet pressure for first, second-stage oil supply pumps reaches 3.5MPA, slowly open
partial circulating valve up to fully open. At this time, ensurethat outlet pressure is stable, and
maintain partial circulation for 30 minutes under normal condition.
(5) If partial circulating operation is normal and stable within 30 minutes, report it to the foreman
and open the following valves: outlet, inlet valves for corresponding heaters, steam valves and
drain valves for corresponding heaters, and main oil feed valve of boiler. Close oil drain valve
of #1 (#2) heater.
(6) Slightly open outlet bypass valve for first, second-stage oil supply pumps, and close partial
circulating valve a little bit, to pressurize the oil feed pipeline.
(7) When front heavy oil pressure reaches 3.0-3.3 MPA, contact attendant in the oil store to
observe the current change, and slightly open front oil return valve successively. At this time,
ensure that pump current does not exceed the specified value by closing partial circulating
valve of the pump, fully opening outlet valve of oil supply pump, and closing outlet bypass
valve, high speed oil return valve of boiler and interconnection valve from oil supply mains to
oil return mains of the pump etc., then maintain stable operation for 30 minutes.
(8) Adjust heated steam valve on #1 (#2) oil tank. Control the oil outlet temperature in the oil store
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 7
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
between 80 and 90 degree, and control the oil supply temperature between 100 and 120
degree.
(9) According to the current of oil supply pump, open inlet valves of all standby pumps, and
slightly open outlet bypass valves of all standby pumps successively, in order to prepare for
warm-up of cylinder.
(10) Adjust positions of interlock switches for all pumps. Two primary, secondary pumps operate,
and two primary, secondary pumps serve as standby. Report it to foreman.
By now, startup operations for oil store are completed.
3.4.2 Operation sequence for full shutdown of heavy oil system
3.4.2.1 After boiler shutdown, immediately start to operate as soon as receiving a stop command
form the foreman.
3.4.2.2 Parallel off interlocking of standby pump, and stop operation of oil supply pump, and then
report it to foreman.
3.4.2.3 Purge operation for oil return system
a) Stop oil supply pump and start to operate as soon as receiving a notice form the oil store.
b) Close main oil feed valve before the boiler, and open front steam, oil interconnection valve
and oil return valve, then open purge valve in oil return header. Inform the oil store.
c) If the gas is emitted at the top of #1 (#2) oil tank for 5 minutes, report it to foreman.
d) After receiving a notice form the attendant, the foreman shall close all valves opened in item
b.
3.4.2.4 Purge operation for system & equipment before oil supply pump
a) Shut down oil supply pump and report it to the foreman, then start to operate.
b) Close the following valves: oil supply valve on #1 (#2) oil tank, outlet valves for first,
second-stage oil supply pumps and bypass valve, as well as partial circulating valves for first,
second-stage oil supply pumps.
c) Open the following valves: oil drain valve in inlet mains for first, second-stage oil supply
pumps, inlet valves and oil drain valves for first, second-stage oil supply pumps, oil drain valve
of filter for first, second-stage oil supply pump, and steam purge valve in first, second-stage oil
supply and outlet mains, as well as steam purge valve for first, second-stage oil supply pump.
Start to purge.
d) If oil drain valves is very hot after purging for 10 minutes, close all valves opened in item c.
3.4.2.5 Purge operation for oil feed system, pump outlet and pump’s oil return system & equipment
a) Start to operate as soon as operation of item 3 is finished.
b) Open the following valves: main oil feed valve before the boiler, front steam, oil
interconnection valve, steam purge valve in oil feed mains. Inform the oil store to open the
interconnection valve from oil supply mains to oil return mains of the pump, and then start to
purge.
c) If the gas is emitted at the top of #1 (#2) oil tank, open the following valves
Outlet valves and bypass valves for first, second-stage oil supply pumps, partial circulating
valve for first, second-stage oil supply pump and steam purge valve, and main oil return valve of
the pump, as well as oil drain valve of heater. Start to purge. If main oil return valve of the pump
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 8
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
and oil drain valve of heater is very hot after 15 minutes, report it to the foreman, and close valves
opened in items b, and c.
3. 4.2.6 Release parallel operation of #1 (#2) oil tank and heated steam valve for corresponding
heater, and fully open drain valve, and close valves of all system, then close main steam feed
valve for oil store steam. Report it to the foreman.
3.4.2.7 Make a detailed record for operation, and timely report equipment defects occurred during
operation to the foreman, and register the defects.
3.4.2.8 Totally check positions of all system, equipment and valves, in order to prevent items
missing.
3.5 Inspections and notices before startup of fuel oil system
3.5.1 Inspection before oil unloading
3.5.1.1 Check oil levels in two oil tanks and remaining oil amount, and make a detailed record.
3.5.1.2 Purging the whole oil unloading system
1) Open oil drain valve in oil unloading mains, and open oil drain valve in the oil unloading pipe
in front of oil unload pump, then open interconnection valve between oil unloading mains and
steam mains, in order to purge for oil unloading mains.
2) Upon completion of purging, close steam, oil interconnection valve, and close two oil drain
valve opened.
3) Open outlet valve of the pump, and close inlet valve of the pump, and open oil valve on #1 (or
#2) oil tank, then open steam purge valve for oil unload pump, so as to purge oil unloading
system.
4) Wait until steam is emitted at the tank top, close steam purge valve.
3.5.1.3 Check valve positions in the system:
1) If the oil is discharged by a steam operated pump, open outlet, inlet valves, and close all
purge valves, and feed oil to all lubrication parts, then drain remaining water in the cylinder.
2) If the oil is discharged by an electrically driven pump, open outlet, inlet valves, and close all
purge valves, and open cooling water and adjust properly, then check that manually-operated
turning is normal.
3.5.1.4 Check oil unloading rubber pipe connection for fastness and oil leakage, and prepare a
small oil bucket for leaked oil.
3.5.2 Prestartup inspection of heavy oil system:
3.5.2.1 Major and minor repairs for all oil store system and equipment are completed, and the work
sheets are handled and finished.
3.5.2.2 Check to see if the gear pump rotates flexibly before operation(gently turn by hand).
3.5.2.3 Check to see if the power pack is normal and rotational direction of the motor is correct.
3.5.2.4 Whether the pipe sizes at oil inlet and outlet meet the requirements, and whether oil
suction height and the lift exceed specified requirements or not.
3.5.2.5 Check to see if all fasteners are secure (including inlet and outlet pipe connections).
3.5.2.6 When inserting the oil tank before startup, the oil inlet pipe cannot be too high, in order to
prevent air from interfusing; the oil pipe cannot be inserted to tank bottom, in order to prevent oil
from being suck up due to closed nozzle.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 9
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3.5.2.7 All valves in the system are complete, and their marks are correct and located in close
positions.
3.5.2.8 All equipments are complete, and entire, and operating power source for oil supply pump is
switched on; all instruments are complete, and entire, and their power source is switched on, and
indicated correctly. All operating handles, and light signals are complete, entire and convenient.
3.5.2.9 Contact the foreman to start the boiler, and slowly open main steam supply valve in oil
store up to fully open.
3.5.2.10 Slightly open steam heating valve and drain valve on oil tank. Wait until remaining water
in the steam system has been drained up, fully open steam heating valve and drain valve, to heat
the large oil tank.
3.5.3 Maintenance and safety of the machine
3.5.3.1 Grounding device shall be provided to prevent getting wound due to creepage.
3.5.3.2 Frequently check fasteners for looseness, and if sound of gear pump is normal.
3.5.3.3 Oil inlet shall be equipped with a strainer, in order to prevent scrap iron and laree impurities
from sucking into the pump, abrading gears or seizing the gear pump.
3.5.3.4 Oil seals are wearing parts. If oil leakage occurs in the drive shaft, the oil seal shall be
replaced.
3.5.3.5 Ball bearing is used by the oil pump. If it is worn, noise of the gear pump is serious, and its
output will be reduced, so the bearing shall be replaced.
3.5.3.6 After maintenance of the gears, the axial clearance, concentricity of the pump shall be
controlled strictly during reassembly. The tolerance cannot be exceeded, otherwise it cannot
operate normally.
3.5.3.7 It is strictly prohibited to operate the gear pump at a place where ambient temperature is
extremely high (over allowable motor temperature)or at the open air.
3.6 Operation regulating of fuel oil system (oil supply and unloading)
3.6.1 Operation sequence of oil unloading system
3.6.1.1 Check heating temperature of oil tank truck for propriety, specific requirements are as
follows:
Oil type heating temperature
#100 heavy oil 60-70 degree
#200 heavy oil 70-80 degree
3.6.1.2 Open steam inlet valve on steam operated oil unload pump, to allow the steam operated
pump to run slowly.
3.6.1.3 Open oil unloading valves at upper and lower parts of oil tanker. If oil leakage is found in oil
unloading joint, then the joint shall be tightened by a copper spanner. If a little of leaked oil persists,
a small oil bucket can be used to hold it. If oil leaked amount is larger, then close oil unloading
valves at upper and lower parts of the oil tanker. Contact maintenance personnel to replace rubber
gasket on oil unloading joint. Restart to unload oil after replacing.
3.6.1.4 Open the oil unloading valve from oil unloading rubber pipe to the main piping, and then
start to unload oil.
3.6.1.5 If oil pumping of steam operated pump is normal, slowly open the steam inlet valve wider,
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 10
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
to accelerate unloading speed. Based on the feature of dry absorption capability of steam
operated pump, begin with steam operated pump to unload oil, and wait until steam operated
pump is operated normally, then start motorized oil unload pump to unload oil quickly. After oil
unloading is completed, stop motorized oil unload pump, pump out residual oil at bottom of oil tank
truck by the steam operated pump.
3.6.1.6 Wait until residual oil at bottom of the oil tank truck has been removed, then stop steam
operated oil unload pump, and close heated steam valve in the oil tank truck, then remove the
heating coupling.
3.6.1.7 Close inlet valves of all pumps, and open oil drain valves in front of all pumps and oil drain
valve in oil unloading pipeline, and then open interconnection valve form the steam mains to oil
unloading mains, in order to carry out purging. Open steam purge valve and oil drain valve at
outlets of all pumps, to carry out purging.
3.6.1.8 After oil unloading rubber pipe has been purged, close upper and lower unloading valve on
the oil tank truck, and close oil unloading valve from oil unloading rubber pipe to the mains.
Contact maintenance personnel to remove the oil unloading coupling.
3.6.1.9 after the steam is emitted at the top of the oil store and oil unloading mains has been
purged, close steam and oil interconnection valve, and close all purge valves and oil drain valves,
then the purging is completed, finally close oil unloading valve in the oil store.
3.7 Operation regulating of effluent oil system
3.7.1 Specification
3.7.2 Pre-operation inspection of effluent oil system
1) Check to see if connecting pipelines in the system are correct, and if all instruments are intact,
and if power source of electric control box is normal.
2) Close primary drain outlet, and secondary drain outlet on the device.
3) During initial use, open water injection valve above oil collecting chamber of oily sewage
vacuum separator and water injection valve above oil collecting chamber of effluent oil
absorber, and all vent valves. Inject industry water to the vacuum separator and effluent oil
absorber respectively, until they are full. Then close all water injection valves, drain valves,
vent valves.
4) Check oil content of oily sewage in oily sewage pool. If floating oil thickness reaches 5 mm,
start floating oil absorber, otherwise start the vacuum separator.
3.7.3 Operation of effluent oil system
3.7.3.1 Switch on power source of control box, place changeover switch in “Local”, “Automatic”
positions. Press Start button, and press start switch on the vacuum separator or floating oil
absorber (according to floating oil thickness), then the system enters into automatic operating
state.
3.7.3.2 When the level of water pool reaches a high position< start position>, the vacuum
separator or floating oil absorber will automatically start. As soon as the separated oil returns to oil
collecting tank, the purified water from the vacuum separator is discharged to an underground
drain, and the separated water from the floating oil absorber returns to the oily sewage pool.
3.7.3.3 If oil level in oil collecting tank reaches a high position, the oil transfer pump will automatic
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 11
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
start, and the recovered oil is transferred to an oil tank of the system. If the level reaches stop
position, the oil transfer pump stops.
3.7.34 The drain pipes is connected with a online monitor in parallel(for its operation mode and
maintenance, see the Instruction). The set value of oil concentration in drained water for online
detection is 5 ppm/l. If effluent oil concentration is higher than the value, an automatic alarm is
given, and motorized drainage valve is closed. Drainage to underground drain is forbidden. Water
return valve is open, the effluent is returned to the oily sewage pool for another treatment.
3.7.3.5 The whole system operates automatically, and oily sewage is automatically separated. If
the level in oily sewage pool reaches to a low position<stop position>, the system shut down.
3.7.3.6 If remote control or local manual control is required, place the changeover switch to the
corresponding position, and then remote automatic control or local manual control can be affected
by the system.
3.7.3.7 If differential pressure controller or safety valve operates, the system will raise an alarm.
Shut down and clean up or replace macromolecule filter element.
3.7.3.8 Check if rotational direction of the pump is correct, and check all meters and instruments
for intactness.
3.7.3.9 Close primary drain outlet, and secondary drain outlet on the device.
3.7.3.10 Open the valve at drainage outlet and vent valve at the top of macromolecular adsorption
chamber.
3.7.3.11 Vacuum chamber, oil collecting chamber and inlet pipeline in the machine are filled with
clean tap water.
3.7.3.12 Turn oil drain switch to Automatic position.
3.7.3.13 Press start butt on the electric control box of the machine, motorized screw pump starts to
pump water.
3.7.3.14 If the ambient temperature is low or oil viscosity is large, open the heater.
3.7.3.15 After the oil-water separator is operated normally, observe operating conditions of all
motors at any moment. In case of abnormality, shut down and check.
3.7.3.16 inlet piping in the machine shall be free from air leakage; otherwise suction ability for the
machine would be affected, and even resulting in maloperation of the machine. If a motor-driven
plunger pump has always been kept operating state, while the screw pump does not work, then
shut down and repair the parts leaked, and fill the device with clean water, then restart the
machine.
3.7.3.17 If the gauge glass in oil collecting chamber of the machine is filled with oil, while the
plunger pump for oil drain does not operate automatically, but it can be started when oil drain
pump is turned to Manual position; it is likely to be the unction of oil level electrode. Shut own and
remove the level electrode. Clean up the surface before restarting the machine.
3.7.3.18 If spring loaded safety valve is open(i.e. value of pressure gauge ≥ 0.25 MPa), shut down
and replace filter element in macromolecular adsorption chamber.
3.7.3.19 If the device is out of service for a long time, the water in the device shall be drained and
cut off the power source of the equipment, and motional parts of the pump shall be filled with some
lubrication oil.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 12
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3.8 Operation Check and maintenance of fuel oil system
3.8.1 Maintenance and check during normal operation of oil supply pump
3.8.1.1 Temperature of oil supply pump for operating and all bearing of the motor, vibration, axial
hunting does not exceed specified value.
3.8.1.2 Lubrication oil for all bearings is sufficient, and oil quality is good. Oil type shall meet the
requirements. For bearings with an oil cup, tighten two turns and fill oil in each shift.
3.8.1.3 Cooling water for all bearings is expedite, unblocked, and water flow rate is adequate.
3.8.1.4 Current, pressure for the operating pumps are stable, and oil supply temperature is normal.
3.8.1.5 All gauges are complete, their indications are correct.
3.8.1.6 Valves for all systems are complete and entire. Marks are correct. Switch positions are
correct. There are no signs of oil leakage, steam leakage.
3.8.1.7 Warm-up temperature of standby pump is normal, and positions of all linkage switches
are correct.
3.8.1.8 Isolation for equipments and systems to be repaired is correct, and safety measures are
complete.
3.8.1.9 Operation and standby for all oil tanks are normal. Temperature in oil store meets the
requirements.
3.8.1.10 cooling water return for all operating, standby pumps is unblocked. All equipments and
the ground shall be clean.
3.8.1.11 If steam operated pump runs stably during oil unloading, there are no signs of abnormal
sound and water hammer in the cylinder; steam connections operate normally, all connection
parts are secure and complete, and periodically discharge the accumulated water in the cylinder.
3.8.1.12 All filters are put into operation, and operated normally, without plugging phenomena.
3.8.1.13 The heater is operated normally, free from oil leakage, steam leakage phenomena.
3.8.1.14 Oil level in effluent oil basin keeps at a low position, free from abnormal change.
3.8.1.15 Lightings in the site, in particular, the lightings for all oil tanks are OK.
3.8.1.16 Various fire fighting apparatuses in the oil store shall keep intact, and be placed at
designated place in order.
3.8.1.17 The used waste cotton yarn and garbage shall be placed in a designated box, and
periodic cleaning shall be made for them. It is forbidden to stack waste cotton yarn garbage in the
garbage yard at discretion.
3.8.1.18 No fire is allowed in the oil store. If electric arc welding job is to be carried out, special
work sheet must be prepared, and take corresponding safety measures.
3.8.1.19 Weeds, and garbages in the oil store shall be removed periodically.
3.8.1.20Usually, the oil store shall be tidy, clean, and sanitary.
3.9 Safety operation cautions of fuel oil system
3.9.1 Notices when operating of oil supply pump
3.9.1.1 Before operation, contact the foreman, and shift supervisor to come to an agreement.
3.9.1.2 Once switching is completed, timely report operating conditions to the foreman.
3.9.1.3 If stopping of the operating pump is defective, timely report it to the foreman, and contact
maintenance personnel to remove it or note down the defects.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 13
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3.9.1.4 Shift record shall be made, and current operation and standby mode shall be clearly told.
3.9.2 Notices when startup of heavy oil system
3.9.2.1 Before operation, an overall, earnest, careful inspection operation shall be performed to all
equipments, so as to know everything fairly well.
3.9.2.2 Earnestly review operation ticket. Earnestly operate step by step. Valves not yet opened
must be opened, and valves not yet closed must be closed, in order to prevent back flow of oil and
steam, and running, emitting of heavy oil due to maloperation.
3.9.2.3 After operation is completed, an overall, earnest inspection shall be performed to all oil,
steam systems, equipments, in order to prevent running, emitting of oil, steam due to missing,
maloperation, hidden trouble of the equipment.
3.9.2.4 This job is leaded by operation director or operation technician in the workshop, and
operation foreman is responsible for uniform command. All operating personnel shall strictly
execute the command and perform necessary contact and report works.
3.9.3 Notices when full shutdown of heavy oil system
3.9.3.1 This operation is leaded by an operation director or operation technician, and operation
foreman is responsible for uniform command and contact works. The whole operation is required
to be completed within 60 – 70 minutes.
3.9.3.2 Make sure to earnestly review the operation tickets before operation, and acquaint with
operation sequences, steps and actual positions of all valves, in order to avoid delaying time due
to sheer ignorance.
3.9.3.3 After every operation is carried out, review shall be made to prevent back flow, running,
and emitting of oil and steam due to maloperation.
3.9.3.4 It is required to coordinate the contact between senior staff and junior staff, and strictly,
earnestly execute the command, and obey uniform command. All operating personnel must
contact each other and make necessary report works.
3.9.4 Operation, maintenance and notices for effluent oil system
3.9.4.1 Conditions of all instruments, meters, and indicator lights shall be observed carefully during
operation. Whether level height indicated is identical with the actual height, and whether the
indicator lights are matched with actual operating equipments. In case of any abnormality, shut
down and check.
3.9.4.2 Carefully observe if the levels of oil collecting chamber in oily sewage vacuum separator
and oil collecting chamber in floating oil absorber are stable. If the level drops, it means that
leakage is occurred in suction pipeline in the system, shut down and clean.
3.9.4.3 If water pump and oil drain pump are switched frequently, it means that the electrode bar in
the oil collecting chamber is failed. Shut down, and remove the electrode bar and clean up its
surface, then put it into service.
3.9.4.4 There must be no foreign matter, impurities in the oily sewage poor. If so, shut down and
clean them up. Meanwhile, oil amount at inlet of vacuum separation purifier for oily sewage shall
be less than 500—100 mg/l. Otherwise, oil absorption saturation of macromolecular filter element
would be accelerated, and service lifetime of the filter element would be shorted, and even
resulting in overstandard of drainage.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 14
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3.9.4.5 When online concentration monitor gives a signal which means that oil concentration is too
high, shut down and check. If digital indication is unstable, shut down and clean the detection
elements.
3.9.4.6 If differential pressure controller or pressure or safety valve operates, shut down and clean
up or replace macromolecular filter element. Open right cover plate on the macromolecular
adsorption chamber. Screw off the screws to fasten the filter element. Grasp the filter element with
hand, and draw it out by rotating two turns toward one direction. After the filter element is removed,
cut off 2 – 3 layers with a knife blade, and strip off the outer layer of filter element being cut off.
After washing in the clean water and drying, reinstall the filter element to macromolecular
adsorption chamber. After reinstalling in reverse order of disassembly, it can be put into service. If
the filter element removed cannot be used after cleaning, replacing a new filter element is
necessary.
3.9.4.7 If the device is out of service for a long time, it is required to drain the water in the device,
and cut off power source of the equipment. Motional parts of the pump shall be filled with some
lubrication oil.
3.10 Common fault, judgment and disposal of fuel oil system and equipments
3.10.1 Liquid cannot be drained out or displacement is low
a) Possible cause
1) Pump body is not filled with oil.
2) Oil suction height exceeds vacuum height.
3) Air leaked in oil suction pipeline.
4) Rotational direction is wrong.
5) Oil pipe blocked or other faults.
6) Rotational speed of oil pump is low.
7) Safety valve is open.
8) Cone tightness of safety valve is poor.
b) Remedy:
1) Fill the place where the vacuum pressure gauge is connected with oil.
2) Raise oil suction surface.
3) Check all connections.
4) Reconnect the motor.
5) Check and eliminate the fault.
6) Check and rectify with a tachometer.
7) Adjust the spring pressure of safety valve.
8) Regrind with fine paste.
3.10.2 Liquid leaked in oil pump
a) a) Possible cause
1) Packing gland not compacted.
2) Sealing ring has been used for a long time and worn.
3) Misalignment of sealing ring and not corrected.
4) Oil leaked in some washers .
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 15
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
b) Remedy:
5) Tighten nuts.
6) Replace.
7) Remove and smoothly tighten nuts.
8) Replace.
3.10.3 Power required by the motor is too big
a) Possible cause
1) Viscosity of sucked liquid is too big.
2) Discharge pressure is too high.
3) Resistance of discharge pipeline is too big.
4) Running of rotary parts is obstructed, resulting in intense heat due to friction.
b) Remedy:
1) Preheat or reduce discharge pressure.
2) Reduce discharge pressure.
3) Check and eliminate the fault.
4) Remove, check and rectify.
3.10.4 Oil supply pump tripped
a) Possible cause
1) Power supply system failed.
2) Mechanical part of pump body damaged.
3) Pump shaft locked.
4) Overload.
b) Remedy:
If linkage pump does not put into service, immediately start standby pump to guarantee the oil
pressure. Inform local patrol operator to check the circumstance, and contact maintenance
personnel to repair.
3.10.5 Vaporization of oil supply pump
a) Possible cause
1) Oil level in oil tank is too low.
2) Flush valve not closed.
3) Fine filter plugged.
4) Inlet temperature is high.
b) b) Remedy
1) Immediately transit operation.
2) Stop failed pump, put into standby pump, check all valves; contact maintenance
personnel to repair if necessary.
3.10.6 Oil pump evacuated
a) Possible cause
1) Oil level in oil tank is too low.
2) Air entered into the pump.
b) Remedy
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 16
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
1) Immediately transit operation.
2) Contact maintenance personnel to repair air leakage point.
3.10.7 Oil supply pressure raised
a) Possible cause
1) Oil return valve is closed a little bit or valve head fallen off.
2) Front linkage valve operated.
3) Oil consumption decreased suddenly.
b) Remedy
1) Check oil return valve, contact maintenance personnel to repair if necessary.
2) Contact shift supervisor to find out the cause.
3.10.8 Low oil supply pressure
a) Possible cause
1) Opening of oil return valve is too big.
2) Oil consumption of boiler increased.
3) Oil supply pipeline leaked.
4) Air admitted to suction inlet.
5) Pump speed is low.
6) Suction pipeline plugged.
7) Impeller channel plugged.
8) Impeller damaged or seal ring worn.
b) Remedy
1) Adjust oil return valve.
2) Immediately link to start standby pump.
3) Contact maintenance personnel to repair.
3.10.9 Bearing leaked
a) Possible cause
1) Gasket of shaft sleeve damaged.
2) Gasket not flat or too hard.
b) Remedy: contact maintenance personnel to repair.
3.10.10 Oil tank caught fire
a) Possible cause
1) Outside open fire.
2) Improper hot work measures.
3) Spark caused due to static electricity.
b) Remedy: immediately dial fire telephone; start foam tank, and extinguish the fire with fire
fighting apparatus; release parallel operation of an oil tank if it catches fire.
3.10.11 Pump cannot pump oil
a) Possible cause
1) Rotational direction of the motor is wrong.
2) Enclosed impeller channel or suction pipeline blocked.
3) Centerline of the impeller not immersed by fuel oil.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 17
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
b) Remedy
1) Change rotational direction.
2) Remove blocked part.
3) Adjust immersed height.
3.10.12 Flow rate not enough
a) Possible cause
1) Impeller corroded and worn seriously.
2) Seal ring worn, corrode seriously.
3) Rotational speed not enough.
4) Clearance between open impeller and casing cover is too big.
5) Suction inlet or discharge outlet plugged.
b) Remedy
1) Replace impeller.
2) Replace seal ring.
3) Increase rotational speed.
4) Replace impeller.
5) Eliminate blocked part.
3.10.13 Lift not enough
a) Possible cause
1) Oil delivered containing air.
2) Impeller corroded, worn seriously.
3) Clearance between open impeller and casing cover is too big.
b) Remedy
1) Decrease liquid temperature, eliminate gas.
2) Replace impeller.
3) Readjust clearance.
3.10.14 Excessive power
a) Possible cause
1) Process exceeds service range.
2) Specific gravity of the medium is too big.
3) Mechanical friction occurred.
b) Remedy
1) Operate the pump within service range.
2) Replace large power motor.
3) Find out the cause, and replace worn parts.
3.10.15 Bearing damage and overheat
a) Possible cause
1) Bearing damaged.
2) Bearing clearance too big.
3) Lubrication oil quality unqualified or short of oil.
4) Misalignment between pump and motor.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 18
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
b) Remedy
1) Switch oil supply pump, and inform maintenance personnel to repair.
3.10.16 Noise and vibration
a) Possible cause
1) Misalignment between pump shaft and motor shaft.
2) Liquid delivered containing gas.
3) Rotor unbalanced.
4) Seal ring worn excessively.
5) Coupling bolt loosened.
b) Remedy
1) Adjust concentricity.
2) Decrease liquid temperature, and eliminate gas.
3) Replace parts.
4) Replace seal ring.
5) Tighten various bolts.
3.10.17 Large start load of oil pump
a) Possible cause
1) Due to large thrust clearance of oil pump, thrust function of thrust disk and balance disc is
lost, leading to friction between movable and stationary parts, and excessive start load,
and even that oil pump cannot be started.
b) Remedy
1) Stop pump and repair
3.10.18 Faults of mechanical part
a) Possible cause
1) Oil level in oil tank is too low.
2) Air entered into oil inlet pipeline.
3) Packing worn seriously.
4) Oil filter plugged.
b) Remedy
1) After linkage pump is put into service automatically, close operation switch to transit
operation, then stop oil filter and corresponding pump, and start standby pump.
3.10.19 Motor overload
a) Possible cause
1) Misalignment.
2) Specific gravity became larger.
3) Friction occurred in rotating parts.
4) Device resistance become lower, operation point leans to large flow rate.
b) Remedy
1) Align opposite wheels.
2) Change operating process.
3) Repair frictionized portion.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 19
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
4) Check pressures in suction and discharge pipelines and original changes.
3.10.20 Auxiliary power interrupted
a) Possible cause
1) Power supply system for auxiliary power failed.
b) Remedy
1) Contact shift supervisor to restore power source, and pull the oil pump switch to stop
position, then release interlocking switch.
3.10.21 Faults of electrical part
a) Possible cause
1) Motor is smoking or catches fire.
2) There is abnormal sound or burnt smell in the motor.
3) Spark occurred in a switch.
4) Motor current exceeds rating.
5) Intensive vibration occurred in a motor.
6) Motor tripped.
b) Remedy
1) Rapidly cut off power source for the motor, and start standby motor.
3.10.22 Fuel oil screen plugged
a) Possible cause
1) There is impurity in the oil.
b) Remedy
2) Switch oil filter, and clean.
3.10.23 Abnormal sound in delivery pump
a) Possible cause
1) Idle running of pump.
2) Screws worn seriously.
3) Pump bearing damaged.
4) There is mechanical impurity in the pump.
b) Remedy
1) Shut down and check inlet pipeline of pump for blocking, and air leakage.
2) Shut down and inform maintenance personnel to repair.
3) Shut down and inform maintenance personnel to repair.
4) Shut down and inform maintenance personnel to repair.
3.10.24 V-belt slipped
a) Possible cause
1) Belt tensions not enough.
2) Pump load is too big.
3) There is oil stain on the pulleys.
b) Remedy
1) Shut own and inform maintenance personnel to repair.
2) Check outlet pipeline for unblocking.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 20
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3) Shut down and remove.
3.10.25 High oil content of blowdown water
a) Possible cause
1) Failure of separator’s adsorption material.
2) The shell not full-flow.
3) Serious oil pollution in each stage.
b) Remedy
1) Regenerate or replace adsorption material.
2) Exhaust gas up to full-flow of the shell.
3) Back wash or clean and perform blowdown.
4 Water Treatment Plant Operation Manual
4.1 General Description
The water purification station system is designed on basis of 4×300MW unit capacity, and the
equipments will be erected in stages. The water amount treated within the capacity of 4×300MW
Power Unit is about 350 m3/h and the equivalent in this 2 × 300MW project will be approx. 200
m3/h. The mechanical acceleration clarifier will be arranged in accordance with capacity of
4×300MW unit, Two sets of mechanical acceleration clarifier and two sets of filter tank with 200%
capacity will be established for this 2×300MW project, and matched with dosing systems of
coagulant, coagulant and sodium hypochlorite.
4.2 Technical Specification
Equipment name Major technical parameter Unit Qty Remark Raw water booster
pump
Q=200m3/h, H=15m
N=15kW, V=400V
Set
2
One is in operation
and the other is for
standby General service
pump
Q=180m3/h, H=65m
N=75kW, V=400V
Set 2
One is in operation
and the other is for
standby Mechanical
acceleration
clarification tank
Q=200m3/h, inlet silt content
≤5kg/m3
Effluent turbidity:≤20PPM
Set 2
One is in operation
and the other is for
standby Clear water lift
pump
Q=200m3/h, H=35m
N=37kW, V=400V
Set 2
One is in operation
and the other is for
standby Filter chamber
Q=200m3/h, inlet turbidity :≤20PPM
Outlet turbidity:≤3PPM
Set 2
One is in operation
and the other is for
standby Lift pump of filtered
water
Q=190m3/h, H=35m
N=37kW, V=400V
Set 2
One is in operation
and the other is for
standby Electric fire-fighting
pump Q=600m3/h, H=110m
N=315kW, V=6.60kV Set
1 One is in operation
and the other is for
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 21
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
standby Fire-fighting pump
driven by diesel fuel
Q=600m3/h, H=110m
N=315kW
Set 1
One is in operation
and the other is for
standby Fire-fighting
pressure stabilizer
Q=21m3/h, H=110m
Set 1
One is in operation
and the other is for
standby Industrial water
pump
Q=110m3/h, H=60m
N=55kW, V=400V
Set 2
One is in operation
and the other is for
standby Living water pump
Q=130m3/h, H=45m
N=37kW, V=400V
Set 2
One is in operation
and the other is for
standby Living frequency
conversion feed
water device
Total feed water volume
Q=0~160m3/h, H=70m
Set 1
Two are in operation
and one is for standby,
each pump has
Q=80m3/h, H=70m,
N=30kW and V=400V. Active carbon filter
backwashing pump
Q=300m3/h, H=30m
N=45kW, V=400V
Set 2
One is in operation
and the other is for
standby Coagulant metering
pump
Q=0-85l/h, H=70m
N=0.25kW, V=400V
Set 2
One is in operation
and the other is for
standby Coagulant aid
metering pump
Q=0-400l/h, H=50m
N=0.37kW, V=400V
Set 2
One is in operation
and the other is for
standby Agitation tank Set 2 Living water
chlorination
equipment
Effective chlorination amount :9.5g/h
Set 1
Cleaning station
chlorination
equipment
Effective chlorination amount :700g/h
Set 1
Filter chamber
backwashing pump
Q=350m3/h, H=35m
N=55kW, V=400V
Set 2
One is in operation
and the other is for
standby 4.3 Operation
4.3.1 Control of Operation Parameters
Water
sample
Item
Unit
Control
standard Time
interval
Remark
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 22
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Alkalinity mmol/l — 8h
Turbidity mg/l — 8h
Raw water
Electroconductivity μs/cm — 8h Settling ratio 5min% 10-20% 4h Water out of
classification
tank
Turbidity
mg/l
≤10
4h
Turbidity mg/l ≤5 4h
Residual chlorine mg/l ≤0.1 4
Water out of
gravity filter
chamber Pressure
difference
MPa
≤0.05
4
4.3.2 Startup and shutdown of mechanical agitating clarifier
4.3.2.1 Preparatory work for mechanical agitation clarification tank prior to startup
1) The dosage in the coagulant and coagulant aid solution tank is adequate and the liquid level
is 1/2 high above the solution pool.
2) There should be no debris inside the clarification tank and the manholes are closed.
3) Sampling tubes and washing pipes should be smooth.
4) The agitator should be filled with lubricant, and its oil level is normal and is in good standby.
5) The bottom discharge valve, middle discharge valve, water exit valve, sampling valve and
rinsing water valve of the clarification tank should be closed.
4.3.2.2 Startup of Mechanical agitation clarification tank
1) Start the raw water booster pump, open the exit valve after the pressure is stable, operate the
coagulant and coagulant aid chemical dosing system, and regulate the effluent flow and
dosage according to the needs, the preliminary water discharge is 100-200T/H, and the
quantity of the coagulant and coagulant aid is 1 to 1.5 times the normal amount.
2) Start the mud scraper of the clarification tank, which is operating when lubricant can not be
interrupted.
3) When the impeller of the agitator is immersed into water, start the agitator of the clarification
tank, adjust the rotation speed to 4.8-14.5 r/min and the hoist speed to 120-1200 r/min, and
check whether the agitator is in normal operation; when a circulation is created, fine mud can
be input if sludge is loose with small particles in the first reaction room.
4) When the clarification tank begins to output water, the effluent water should be drained into
trench if it is unqualified; when the effluent water from the clarification tank is qualified
(Turbidity is less than 10mg/L), water can only flow into the clarification tank, and meanwhile
water flow rate slowly increases, there is in general 30 tons of flow in every 10 minutes and
the coagulant is appropriately adjusted to the normal (200-250T/H).
5) When the effluent water quality of the clarification tank is poor, the reasons should be
determined rapidly and the timely treatment should be completed.
6) The sewage on the bottom of the clarification tank prior to startup should be disposed once,
and then the tank is started according to the steps above.
4.3.2.3 Stoppage of mechanical agitation clarification tank
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 23
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
1) Close the water exit valve of the raw water booster pump, disable the raw water booster pump,
stop inputting water into the clarification tank, stop the coagulant and coagulant aid chemical
dosing system and stop the agitator and mud scraper finally.
2) When the clarification tank stops for a short term (less than 72H), the agitator can continue
running to drain mud appropriately, and the sludge formation maintains not to sediment to
prevent blades from being damaged.
3) When the clarification tank stops for a long term (more than 72H) or is overhauled, the sludge
in the clarification tank should be dumped before the agitator stops running.
4.3.3 Startup and stoppage of Gravity filter chamber
4.3.3.1 Inspection r prior to startup of the gravity filter chambe
1) The inside of the chemical pool should be clean and have no debris.
2) There should be no debris or manhole leakage inside the filter chamber.
3) Water purification blower should be in the standby.
4.3.3.2 Startup of Gravity filter chamber
1) When the effluent turbidity of the clarification tank is less than 10 mg/L, water is allowed to
enter the gravity filter chamber.
2) Open the water inlet valve of the gravity filter chamber and the positive discharge valve of the
gravity filter chamber, and wash the valve positively and open the positive discharge valve
until the effluent turbidity of the gravity filter chamber is less than 5 mg/L, and input water into
the chemical pool through opening the water inlet valve of the chemical pool.
3) Monitor the effluent turbidity of the gravity filter chamber is not more than 5 mg/L and the
residual chlorine in the chemical water is not more than 0.1 mg/L.
4.3.3.4 Stoppage of the gravity filter chamber
1) Stop inputting water into the gravity filter chamber from the clarification tank and close the
water inlet valve of the gravity filter chamber.
2) If the gravity filter chamber stops for overhaul, open the pollution discharge valve at the
bottom of the gravity filter chamber and drain the internal water.
4.3.3.5 Air scrub of Gravity filter chamber
1) Air scrub and backwashing of gravity filter chamber: close the water inlet valve and exhaust
valve of the gravity filter chamber, open the reverse discharge valve and connecting butterfly
valve of the gravity filter chamber and backwash the filter material.
2) Air scrub and waterdrainage of gravity filter chamber: close the reverse discharge valve and
connecting butterfly valve, open the drainage valve, and drain to 100mm above the filter layer
by gravity.
3) Air scrub and air inflow of gravity filter chamber: close the drainage valve, open the front
drainage valve of air inflow and air exit valve and emptying valve of water purification blower
in order to enable smooth exhaust in the air scrub, and air scrub the filter layer.
4) Air scrub, air inflow and backwashing of gravity filter chamber: open the connecting butterfly
valve and close the reverse discharge valve, water from the clean water area at the upper part
of the bulkhead flows into the water separation chamber and filter area via a connecting pipe,
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 24
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
and is drained into the gutter from the backwashing pipe via a backwashing drainage valve
(that is, drainage backwashing + Air scrub).
5) Air scrub and backwashing of gravity filter chamber: close the compressed air valve and
blower exit valve and conduct backwashing.
6) Drainage before air scrub and operation of the gravity filter chamber: drain some water that
are unqualified in the preliminary filteration. Close the backwashing drainage valve and the
connecting butterfly valve, open the water inlet valve and drainage valve prior to operation,
drain the preliminarily filtered water, and then close the drainage valve prior to operation.
Open the connecting butterfly valve, and the filter chamber goes into the normal operation.
4.3.4 Operation of chemical dosing system
4.3.4.1 Overview of chemical dosing system
The distance between the chemical dosing room at the cleaning station and the chemical
dosing point is about 30 meters and the water pressure on the chemical dosing point is about 0.15
MPa. A set of coagulant chemical dosing system, a set of coagulant aid chemical dosing system, a
set of sodium hypochlorite chemical dosing system of clarification tank and a set of living water
sodium hypochlorite chemical dosing system are set up.
1) Coagulant dosing: the dosage of PAC is 10 to 20 mg/l and the preparation concentration is
5% to 10%;
2) Coagulant aid dosing: the dosage of solid polyacrylamide (PAM) is 1 to 2 mg/l and the
preparation concentration is 1%, and the dosage concentration is 0.1 to 0.2%;
3) Germicide dosing: sodium hypochlorite (generated from 4% saturated saline solution by
electrolysis). The inlet dosage of the clarification tank si 1.0 to 2.0 mg/L; the dosage of living
water is no more than 1.0 mg/L, and the largest dosage is about 5 g/l and the water pressure
on the dosage point is 0.10MPa.
4.3.4.2 Startup and shutdown of chemical dosing system
4.3.4.2.1 Startup of chemical dosing system
1) The liquid level of coagulant and coagulant aid solution is higher than the 1m.
2) The liquid level of sodium hypochlorite system metering tank is higher than 40 cm, dosage in
the granulated salt storage room is adequate and living water is normal.
3) Check that the metering pump and its motor meet the inspection standard in the General
Clauses.
4) Open the first and second manual dosage oulet valve of coagulant and coagulant aid solution
tank and the living water inlet valve of sodium hypochlorite metering system.
5) Open the inlet and exit valve of the metering pump, start the coagulant and coagulant aid
metering pump and sodium hypochlorite chemical dosing system, and check whether the inlet
pressure is normal.
4.3.4.2.2 Shutdown of chemical dosing system
1) Press “Stop” button at CRT or local metering pump, and close the inlet and exit valve of the
metering pump and the first and second exit valve of the solution pool.
2) Press the raw water pump at CRT or “Stop” button of the domestic water pump and stop the
raw water pump or domestic water pump and then close the water inlet and exit valve.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 25
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
4.3.5 Inspection and adjustment during operation
4.3.5.1 Operation, maintenance and attentions of Chemical clarification tank
1) Under the supervision projects and time interval provided, the effluent quality of the
clarification tank should be measured and the results are recorded in the operation
statements.
2) According to the effluent quality the dosage supervision and adjustment should be done.
3) The sludge settling ratio of the second reaction chamber is controlled at 10 to 20% (5 min).
4) Under the sludge settling ratio of the second reaction chamber, the sewage disposal time
interval (one-time sewage disposal every 8H for two minutes) is determined, sludge running
and missing phenomena are not allowed, sewage disposal at the bottom is done once every
day shift and the discharge capacity is determined according to the effluent quality of the
clarification tank and the height of sludge.
5) Stabilize the operating conditions of the clarification tank, and the change scope of the flow is
generally not more than 10% of the original flow each 10 minutes.
6) The oil level of the agitator is strictly controlled and the oil dosage should not exceed the
maximum oil level line and should not be less than the minimum oil level line when it is in
operation.
7) The following matters should be paid attention to in the operation of the agitator:
a) Current should have no unusual fluctuations.
b) The agitator should operate in balance, without abnormal vibration and noise.
c) The oil temperature of the reducer should generally not exceed 30.
d) There should not be obvious leakage at each seal part.
8) When adjusting the startup height of the agitator impeller, it is strictly controlled in the scope of
the upper and lower stop line of the scale and nuts must be locked in the process of
adjustment.
4.3.5.2 Operation, maintenance and attentions of gravity filter chamber
1) Air scrub is carried out when the filter chamber runs for 20 hours.
2) Air scrub is carried out when the effluent quality of the filter chamber deteriorates markedly.
3) Air scrub is carried out when the effluent flow of the filter chamber changes little.
4) Air scrub is carried out when the effluent quality of the filter chamber exceeds the standard.
4.3.5.3 Operation, maintenance and attentions of chemical dosing system
1) The liquid level of the coagulant and coagulant aid solution pool is more than 20cm, and a
prescription if filled if it is less than 20 cm.
2) Check whether the dosage in the granulated salt storage room of sodium hypochlorite
chemical dosing system is adequate, and the liquid level of the measuring tank is above
20cm.
3) Check whether the sodium hypochlorite generator is working normally.
4) The outlet pressure of the metering pump is more than the water pressure of the dosing point,
the pressure gauge pointer swings, and there is no leakage phenomenon at the connection
between the pipeline and flange.
5) Check the metering pump and motor body according to the General Clauses.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 26
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
6) If the metering pump fails, the system is switched and another metering pump is put into
operation.
4.4 Common faults, judgment and treatment at the water purification station
4.4.1 Reasons for deteriorated effluent quality of the clarification tank and treatment
S/N Reason Treatment 1 Inadequate or excessive dosage. Stop the filter chamber, drain the effluent of the
clarification tank to the trench, and adjust the
dosage immediately 2 Slagblanket rises as the sludge is not
timely discharged Stop the filter chamber, drain the effluent of the
clarification tank to the trench and dispose
sewage immediately. 3 The flow of the clarification tank is too
big; the lifting load speed of the
clarification tank is over 50 t/h.
Stop the filter chamber, drain the effluent of the
clarification tank to the trench and reduce the
flow. 4 The original water temperature
increases too fast, by 1 to 2 hourly. Stop the filter chamber, drain the effluent of the
clarification tank to the trench and adjust the
system to stabilize temperature and flow. 5 There is mud on the bottom of the
clarification tank due to its long-term
operation.
Drain and wash the clarification tank
6 Inlet water contains air. Clean the pump mesh timely, to prevent pump
flange from leaking. 7 Not clean the clarification tank regularly Clean the clarification tank regularly 4.4.2 All pretreatment rotation equipment trips
Possible reasons: the power supply of MCC cabinet fails and the chemical water fails.
Treatment methods:
1) Report to the leader on duty and professionals and make records.
2) Take inspection and treatment by contacting the centralized control through the leader on
duty.
3) Close the operation switch of the outrage equipment.
4) Put the original operating system into operation again after the power supply is restored.
4.4.3 Sludge in the clarification tank circulates badly and drifts, and sludge formation is in chaos
S/N Reason Treatment 1 The rotation speed of the agitator is
improper, resulting in abnormal
circulation.
Temporarily reduce the rotation speed and wait
for 1 to 2 hours, and recover the rotation speed
after the water is clarified; the rotation speed
may be too high if the clarified water
deteriorates again, but often because of low
rotation speed, the stirring effect changes bad. 2 Due to high turbidity of the raw water,
the impeller runs at low-speed and the
Adjust the rotation speed and eliminate
accumulated silt (sewage) at the lower part of
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 27
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
sludge accumulates at the recycling part the enrichment room and outside cover. 4.4.4 Water yield of the clarification tank in operation declines seriously and the water level can not
be maintained
S/N Reason Treatment 1 The sewage valve is not closed or
seriously leaks after it is opened. Close the sewage valve or make maintenance
2 Raw water booster pump runs
abnormally Check whether the current of the raw water
booster pump is normal.
4.4.5 Water quality of the clarification tank blanches
S/N Reason Treatment 1 Excessive dosage Adjust the dosage. 2 Excessive spoil disposal capacity Control the spoil disposal capacity 4.4.6 Alum floats on the clarification tank
S/N Reason Treatment 1 Too big initial flow Reduce the flow 2 Sudden increase in load in operation Adjust the load balance 3 Excessive dosage Control the dosage 4 Too fast rotation speed of the agitator Adjust the rotation speed of the agitator 5 Suddenly declining temperature Reduce the output 6 Inadequate spoil disposal Control the normal spoil disposal 7 Spoil disposal washing valve not closed Close the spoil disposal washing valve 4.4.7 Unqualified effluent turbidity of the filter chamber
S/N Reason Treatment 1 Big turbidity of inlet water Adjust and treat water quality of the clarification
tank 2 Too big load Reduce the load 3 Too long operation time Backwash and strengthen the air scrub 4 Backwash by halves Backwash thoroughly 5 Bias of filter material and water hat
damaged Maintenance
5 Demineralization system Operation Manual
5.1 General description
The normal output of the feed-water treatment system equipment of the boiler is 240 t/h and
the largest output is 290 t/h. The feed-water treatment system of the boiler is set to two columns of
unit first-class desalination (2 sets of 60 t/h activated carbon filter → 1 set of 120 t/h reverse flow
cation exchanger → 1 set of 120 t/h for decarbonizer → 10 m3 middle water tank →reverse flow
anion exchanger) → 2 sets of 120 t/h mixed bed.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 28
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL
5.2 Technical specification of equipment
Equipment
output
Filling
S/N
Equipment
name
Qty
Nominal
diameter Normal
Max.
Model
Height
Grain
diameter
mm 1
Activated
carbon filter
4
DN2800
60
73
2.0m
0.8~1.6
2
Strong acid
cation
exchanger
2
DN2500
120
145
001X7
1.6m
0.315-1.25
3
Decarbonizer
and blower
2
DN1600
120
Multi-plane
ball
H=1600mm
4
Middle water
tank
2
V=10 m3
5
strong acid
anion
exchanger
2
DN2500
120
145
D202II
2.5m
0.315-1.25
6
Mixed bed
2
DN2000
120
150
MB001X7
MB201X7
Cation
=500mm
Anion
=1000mm
0.7-1.25
0.7-1.25
7
Hydrochloric
acid storage
tank
2
V=25 m3
8
Alkali storage
tank
2
V=25 m3
9
Hydrochloric
acid metering
box(cation)
1
V=1.6m3
10
Hydrochloric
acid metering
box(Mixed)
1
V=1.0m3
11
Alkali metering box(anion)
1
V=1.6m3
12
Alkali metering box(Mixed)
1
V=1.0m3
13
Acid mist absorber (with
filling)
2
DN500
14 Hydrochloric 1 Cation 2.6t/h(0.4mpa)
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 29
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Equipment
output
Filling
S/N
Equipment
name
Qty
Nominal
diameter Normal
Max.
Model
Height
Grain
diameter
mm acid metering
box(cation) bed
15
Hydrochloric
acid metering
box(Mixed)
1
Mixed
bed
1.0t/h(0.4mpa)
16
Alkali metering pump(cation)
1
Anion
bed
2.0t/h(0.4mpa)
17
Alkali metering pump(mixed)
1
Mixed 1.0t/h(0.4mpa)
18 Resin trapper 2 Mixed 19 Safety shower 2
20
Compressed
air tank
2
V=8.0m3
5.3 Control standard and period of water quality of feed-water treatment system
S/N
Name of
water
sample
Analysis item
Symbol
Unit
Control
standard
Supervision
time
Remark
Residual chlorine Cl- mg/L ≌ 0 4h
Oxygen
consumption
CODMn
mg/L
≤1.5
System
assessment
1
Outlet water
of active
carbon filter
Turbidity
mg/L
≤0.2
2h
Backwash
when
exceeding
the
standard sodion
Na+ μg/L
≤100
2h
2
Outlet
water of
cation
exchanger
Acidity
SD
mmol/L
Stable
4h
Increase
the number
of tests
when
putting into
operation
and being
close to
failure
3 Outlet Electroconductivity DD μs/cm ≤5 2h Ditto
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 30
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
water of
anion
exchanger
silicon dioxide
SiO2
μg/L
≤100
2h
Electroconductivity DD μs/cm ≤0.2 2h 4
Outlet water
of mixed ion
exchanger
silicon dioxide
SiO2
μg/L
≤20
2h
Ditto
5
Deionization
water tank
Electroconductivity
DD
μs/cm
≤0.2
2h
Ditto
5.4 Operation of demineralized equipments
5.4.1 Startup and shutdown
5.4.1.1 Startup of desalination system
5.4.1.1.1 Preparation before operation of demineralized equipments
1) The water level of the clean pool is one second above and the raw water pump is in good
standby status.
2) The manual inlet valve and outlet valve of the activated carbon filter, cation bed, anion bed
and mixed bed are opened, the emptying valve at the bottom of the resin trapper is closed,
the exit valve is opened, and all the pneumatic valves are closed and display the same as the
CRT; The one-time valves of flow gauge, sodium gauge and conductance meter are closed,
with intact appearance and zero indication; the on-site control cabinet power supply and gas
source are connected, the green valve indicator light is on and the air pressure is 0.4 to 0.8
MPa.
3) The manual inlet valve of the decarbonization valve is opened, the power supply of the
decarbonization fan is connected and is in good standby status, the liaison valve of the middle
water tank is opened, the emptying valve at the bottom is closed, the entrance valve of the
middle water pump is opened, and the outlet valve is closed, meeting the general inspection
standards.
4) The manual inlet valve and outlet valve of the desalination tank are opened and the emptying
valve at the bottom is closed.
5) The desalination pump meets the general inspection standards, and the manual inlet and
outlet valve are opened.
5.4.1.1.2 Commissioning operations of desalination equipments
1) Start the raw water pump, open its outlet valve and supply water to the activated carbon filter.
2) Commissioning of the activated carbon filter: open the water inlet valve and exhaust valve of
the activated carbon filter, fill water into the activated carbon filter, and open the conventional
well-flushing effluent valve and close the exhaust valve after water flows out of the exhaust
pipe; when turbidity is less than 0.2 mg/L, the conventional well-flushing is qualified, open the
effluent valve and close the conventional well-flushing effluent valve.
3) Commissioning of the cation bed: open the water inlet valve and air valve of the same series
cation bed, fill water into the cation bed, and open the conventional well-flushing effluent valve
and close the air valve for conventional well-flushing after water flows out of the air valve of
the cation bed; when the Na+ is less than 100 ug / L, the conventional well-flushing is qualified,
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 31
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
start the decarbonization fan, open the effluent valve, close the positive discharge valve and
fill water into the middle water tank; when the liquid level in the middle water tank reaches two
thirds above, start the middle water pump, open its outlet valve and send water to the cation
bed.
4) Commissioning of the anion bed: open the water inlet valve and air valve of the same series
anion bed, open the positive discharge valve and close the air valve after water flows out of
the air valve; when DD is less than 5us/cm and SiO2 is less than 100ug/L, the conventional
well-flushing is qualified, open the effluent valve and close the positive discharge valve and fill
water into the mixed bed.
5) Commissioning of the mixed bed: open the water inlet valve and the air valve of the mixed
bed and fill water into the mixed bed; after water flows out of the air valve, open the positive
discharge valve and close the air valve for conventional well-flushing; when DD is less than
0.2us/cm and SiO2 is less than 20ug/L, the conventional well-flushing is qualified; open the
effluent valve and close the positive discharge valve, and send water into the desalination
water tank.
5.4.1.2 Stoppage of the desalination system
1) Stop the raw water pump and close its inlet and outlet valve.
2) Close the pneumatic water inlet valve and the effluent pneumatic valve of the activated
carbon filter.
3) Close the pneumatic water inlet valve and the effluent pneumatic valve of the cation bed, and
stop the decarbonization fan.
4) Stop the middle water pump and close its inlet and outlet valve.
5) Close the pneumatic water inlet valve and the effluent pneumatic valve of the anion bed.
6) Close the pneumatic water inlet valve and the effluent pneumatic valve of the mixed bed as
well as the water inlet valve of the desalination tank.
7) Open the exhaust valves of all equipments, and close all exhaust valves after pressure relief.
8) According to the water level of the chemical pool, decide whether to close the water inlet valve
of the clean water pool.
5.4.2 Inspection and adjustment of the desalination system in operation
1) There is water leakage at the connection between the pipeline and flange, the position of the
valve switch is correct, the effluent residual chlorine and turbidity of the activated carbon filter
is qualified, and the outlet Na+ of the cation bed is less than 100 ug/L, the outlet DD of the
anion bed is less than 5us/cm, the outlet DD of the mixed bed is less than 0.2us/cm and SiO2
is less than 20ug/L.
2) The decarbonization fan has no abnormal sound, with normal vibration and temperature; the
desalination water pump and the middle pump meet the inspection standards of general rules.
3) When the equipment is close to failure, increase the number of tests, prevent the unqualified
water from being sent out.
4) Check whether there is resin inside the resin trapper, stop the mixed bed in time if resin is
found, and record the defects and contact the relevant personnel for maintenance treatment.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 32
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
5) Stop the failed equipment timely and regenerate; if two sets of equipments are put into
operation at the same time, adjust the operating conditions of the equipments reasonably,
avoiding two sets of equipments from failing at the same time.
6) When the cation bed Na is more than 100 ug/L, the cation bed fails; when the effluent
electroconductivity of the anion bed is more than 5us/cm or SiO2 is more than 100ug/L, the
anion bed fails and regeneration should be conducted. Check that the pressure difference of
the switch in operation is less than 0.15Mpa, or else decommissioning, regeneration.
7) Analyze the alkalinity of raw water every 2h, the effluent turbidity of the activated carbon filter
and the effluent acidity of the cation bed; when sea water back flows, strengthen the analysis,
measure once every 1h and analyze chlorine every 4h once.
8) Check that the water level of each water tank is above one second height of liquid level.
9) Check that all on-line meters display normally and one-time meter has no discontinuous flow
or leakage.
a) When the mixed bed is put into operation, input the electroconductivity meter: open the
water sample inlet valve of the electroconductivity meter to maintain flow 200 ml/min
around; observe that the water flow should be continuous, stable and have no
disconnected flow and air from the liquid discharge pipe, and input the power supply of
the corresponding electroconductivity meter.
b) When stopping the mixed bed of anion bed, stop the electroconductivity meter: stop the
power supply of the corresponding electroconductivity meter and close the water sample
inlet valve of the electroconductivity meter.
c) When putting the anion bed into operation, put the sodium meter into operation: open the
manual entrance valve of the sodium meter, pull out the black adjustment knob to
regulate the flow rate to be 40 ml/min, and then reset the adjustment knob. Open the
power switch at the bottom of the sodium meter.
d) When putting the cation bed into operation, put the sodium meter into operation:
disconnect the power switch at the bottom of the sodium meter, push in the switch valve
of the flow tank so that the flow tank is full of water and generates siphon phenomenon.
Close the manual sampling entrance valve of the sodium meter.
5.4.3 Backwashing activated carbon filter of activated carbon filter
5.4.3.1 Preparations for backwashing the active carbon filter
1) The clean water tank maintains a high water level, the activated carbon backwashing pump is
provided with startup conditions and the entrance valve is opened.
2) Check whether the backwashing entrance valve of the operating or standby active carbon bed
is closed tightly.
3) Roots blower is in good standby status.
5.4.3.2 Backwashing operation must be carried out if the active carbon filter in operation meets the
following conditions
1) It is put into operaton for the first time or starts after long-term suspension.
2) The inlet and outlet pressure difference is up to 0.1MPa.
3) The effluent quality exceeds the standard.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 33
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
4) The activated carbon filter operates continuously for 80 hours.
If stopping for over 24 hours, backwashing should be carried out before stopping.
5.4.3.3 Backwashing steps of active carbon filter
1) Stopping: close the water outlet and inlet valve of the filter, open the exhaust valve and close
it after pressure relief for 30s.
2) Drainage: open the exhaust valve and positive discharge valve of the filter, and close the
positive discharge valve when the water level drops to the sight glass center.
3) Air scrub: open the air inlet valve of the filter, start the Roots blower, adjust the air flow to 10
to15 m3/min and scrub for 5 to 10 min.
4) Backwashing: stop the Roots blower, close the air inlet valve and exhaust valve of the filter,
start the backwashing pump, open the exit valve of the pump, open the backwashing influent
valve and backwashing drainage valve of the filter slowly; when the filter is filled with water,
increase flow gradually and control water intensity at 13 to 16l/m2s, until the drained water is
clarified and transparent, stop the backwashing pump and close the backwashing drainage
valve and water inlet valve.
5) Positive washing: open the water inlet valve and the exhaust valve of the filter; after water
flows out of the air valve (about 60s), open the positive washing drainage valve, and the flow
rate is 5 m/h (flow is 40 m3/h), take the positive washing until the water is clarified and
transparent, and then close the water inlet valve and positive discharge valve of the filter and
turn into operation or standby.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 34
Rev.: A
SEC QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW TURBINE & AUXILIARIES OPERATION MANUAL
Table for Operation steps of the activated carbon filter
Control parameter Operation methods
Influe
nt
valve
Efflue
nt
valve
Backwas
hing
influent
valve
Backwas
hing
drainage
valve
Exha
ust
valve
Positiv
e
washi
ng
draina
ge
valve
Air
inle
t
valv
e
Root
s
blow
er
backwash
ing pump
Flo
w 3
m /
h
Rever
se
water
streng
th
l/m2.s
Air
scrub
streng
th
l/m2.s
Tim
e
min
Flo
w
rate
m.h -1
Pre-commissi
oning
5
Commissio
ning Operation <10 Drainage 5-8
Air scrub
Scrubbing
10-15 5-1
0
Back washing 13-16 5 Back
washing Positive
washing 5-1
0
<10
Note: means that the valve starts or the pump operates
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005
Page 35
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
TURBINE & AUXILIARIES OPERATION MANUAL
5.4.4 Regeneration of demineralized equipments
5.4.4.1 Regeneration of one stage desalination equipment
5.4.4.1.1 Preparations for regeneration
1) There is sufficient desalination water in the desalination water tank, and check that all the
water pumps are in good standby status.
2) Adjust the flow and pressure of the operating desalination equipment to ensure making water,
and check that all the related valves of desalination equipment in operation and acid-base
system are closed.
3) The compressed air storage tank is intact and the pressure is around 0.6MPa.
4) Acid and alkali metering box for the anion and cation mixed bed is provided with acid-base
fluid for regenerating a bed body, the high level acid and alkaline storage tank have enough
acid and alkali, and the acid and alkali metering pump and regeneration system are in good
standby status.
5) The acid and alkali concentration are in good standby status.
6) The waste liquid tank is in a low liquid level.
7) Check that all valves of the regeneration system are flexibly used.
8) Close the inlet and outlet valve of the on-line chemical monitoring instruments of the
regeneration equipment, cut off the power supply, and the rest meters are in good operation.
5.4.4.1.2 Regeneration operation of one stage demineralization equipment
1) Small backwashing
Start the self-use desalination water pump, open the small anion (cation) backwashing
influent valve and backwashing drainage valve, backwash for about 10 minutes and control the
backwashing flow, so that resin expands at most and it is suitable that the backwashing height of
resin is up to the peephole middle. After the effluent is clarified, stop small backwashing.
2) Waterdrainage
Stop the self-use desalination water pump, close the small backwashing influent valve and
the backwashing drainage valve, settle the pressure resin layer of resin for five minutes, and then
open the air valve and middle discharge valve to drain water until there is no water in the pressure
resin layer. Close the air valve, and check whether resin falls off when draining.
3) Fill acid (base)
Open the manual regenerated liquid inlet valve and pneumatic valve of the cation (anion) bed,
start the self-use desalination water pump and acid (base) metering pump, open the jet influent
valve of the cation (anion) bed to pre-spray, adjust the cation (anion) bed flow and control it at
15m3/h around; after the flow is stable, open the acid (base) outlet valve of the metering tank,
adjust the acid concentration to be 2% to 2.5% and the alkali concentration to be 1.5% to 2%, fill
2.0m3 acid into the cation bed and fill 2.4 m3 base into the anion bed.
4) Replace
After filling acid (base), stop the acid (base) metering pump, close the exit valve of the acid
(base) metering tank, remain the original flow to replace for about one hour until the acidity of the
middle waste discharge from the cation bed is less than 10 mmol/l and DD of the middle waste
discharge from the anion bed is less than 100 to150us/cm, stop the regeneration water pump and
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005
Page 36
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
SEC BOP OPERATION MANUAL
stop replacing, stop the self-use desalination water pump, and close the manual valve at the mixer
outlet and the acid (base) inlet valve of the bed body
5) Small positive washing
Open the manual influent valve, influent pneumatic valve and air valve of the cation bed and
put the activated carbon filter into operation; after water flows out of the air valve of the bed body,
open the middle discharge valve, close the air valve, wash the cation (anion) bed positively slightly,
and control the flow at 100/h for eight minutes.
6) Positive washing
Open the positive discharge valve of the cation (anion) bed, close the effluent pneumatic
valve of the cation (anion) bed, wash the cation (anion) resin positively, control the flow at 120 t/h,
open the one-time sampling valve of instrument, and take positive washing until Na+ in the cation
bed effluent is no less than 100 ug/L; the anion bed effluent DD ≤ 5 us / cm and SiO2 ≤ 100 ug/L,
and the qualified positive washing water is put into opeaiton or for standby.
7) Large backwashing the cation (anion) bed
a) Start the self-use desalination water pump, open its exit valve, open the backwashing
influent valve and backwashing drainage valve of the cation (anion) bed, and adjust the
backwashing flow from small to large as large as possible when no resin falls off.
b) After the drained water is clarified, reduce the flow gradually so that resin can naturally
settle.
c) After backwashing, stop the self-use water pump, close all the valves above, and open
the emptying valve and middle discharge valve of the cation (anion) bed.
d) Drain the cation (anion) bed to the middle discharge and conduct regeneration according
to the regeneration operation steps of the cation (anion) bed.
Note: large backwashing the cation (anion) bed after it is newly put into operation,
maintenance or long-cycle operation, and then the amount of the regenerated anti-acid (base) is 2
times the normal amount.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 37
Rev.: A
SEC QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW TURBINE & AUXILIARIES OPERATION MANUAL
Table for regeneration operation sequence of the cation (anion) ion switch:
Cation bed valve Pump fan Flow
rt/h
Influent
valve
Backwashing
valve
Large
backwashing
influent
valve
Small
backwashing
influent
valve
Postitive
discharge
valve
Middle
discharge
valve
Effluent
valve
Mixer
outlet
valve
Acid inlet
valve of
regenerated
liquid
Metering
tank
outlet
valve
Exhaust
valve
Raw
water
pump
Self-use
desalination
water pump
Acid
metering
pump
g
age
tive
g
Note: means that the valve starts or the pump operates
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005
Page 38
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
TURBINE & AUXILIARIES OPERATION MANUAL
5.4.4.2 Regeneration operation of two-stage desalination equipment (mixed bed)
5.4.4.2.1. Preparations for regeneration
1) The operation desk and on-site electromagnetic valve box have been supplied with power
and gas, and the atmospheric pressure is 0.4 MPa above.
2) The acid-base system is in good standby status, and the acid-alkali metering box is provided
with enough acid-base solution.
3) The self-use desalination pump, alkali metering pump and middle water pump are in the good
standby status.
4) All the acid-base entrance valves of the mixed bed system should be closed, and the inlet and
outlet manual and pneumatic valves of the renewable mixed bed are closed.
5) The flow of the equipment in operation is properly adjusted to ensure the water level of the
renewable water and desalination water tank.
6) Various meters are provided with commissioning and operation conditions.
7) The sampling primary valve of the mixed bed outlet electroconductivity and silicon meter
should be closed.
5.4.4.2.2. Regeneration operation
1) Waterdrainage
Close the manual influent valve and influent pneumatic valve, and stop the mixed bed. Open
the positive washing drainage valve and exhaust valve, drain until the second peephole of resin
layer can be seen, close the positive washing drainage valve, and prevent siphon when draining.
2) Air scrub
Open the backwashing effluent valve and air inlet valve, adjust the air pressure at 0.10Mpa to
0.15Mpa, scrub for five minutes and then close the air inlet valve.
3) Backwashing delamination
Open the backwashing influent valve and backwashing drainage valve of the mixed bed, start
the self-use desalination pump, open its outlet valve, backwash the mixed bed, and control the
flow at 50t/h for 15 min. When the anion and cation resin are obviously separated, close the
backwashing influent valve and backwashing drainage valve.
Note: resin should settle stably after delamination. If the water backwashing delamination is
poor, soak it into the alkali, and delaminate again.
4) Waterdrainage
Open the positive washing drainage valve and exhaust valve for drainage, and close them
after draining to around 200 mm above resin.
5) Fill the acid and alkali
Open the regenerated acid liquid manual inlet valve and pneumatic valve of the mixed bed,
the regenerated alkali liquid manual inlet valve, pneumatic valve, middle drainage valve, the
influent pneumatic valve and effluent manual valve of the acid (base) mixer, start the self-use
desalination water pump, open the exit valve of the pump slowly and adjust the flow of
regenerated acid liquid to be 8m3/h and the flow of regenerated alkali liquid to be 9m3/h (the
temperature about 40 ); Open the exit valve of the acid (base) metering box, start the acid (base)
metering pump, open the exit valve of the acid (base) metering pump, and adjust the acid
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005
Page 39
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
SEC BOP OPERATION MANUAL
concentration to be 3%; open the manual outlet valve and pneumatic valve of the alkali metering
box, adjust the alkali concentration to be 3%, and fill 0.8m3 acid and 0.8 m3 alkali into the mixed bed respectively.
6) Replacement
After filling the regulated acid (alkali), close the acid outlet valve of the acid metering tank of
the mixed bed, stop the acid metering pump and the alkali outlet valve of the alkali metering box,
stop the alkali metering pump and maintain the flow to replace for 60 min; when replacing to the
drainage neutral, the middle drainage DD is less than 20μs/cm and the replacement ends.
7) Positive washing after replacement
After replacement, stop the self-use demineralization water pump, close the middle drainage
valve of the mixed bed, the manual regenerated acid liquid inlet valve and pneumatic valve of the
mixed bed, the manual regenerated alkali liquid inlet valve and pneumatic valve of the mixed bed,
the influent pneumatic valve and the manual effluent valve of the acid (base) mixer; put the
one-stage desalination equipment into operation, open the influent valve and positive discharge
valve of the mixed bed, and wash the resin of the mixed bed positively. When the
electroconductivity of the positive washing drainage is less than 10μs/cm, the positive washing
ends.
8) Waterdrainage
After replacement, the positive washing is qualified; close the influent valve of the mixed bed,
open the exhaust valve and the positive washing drainage valve of the mixed bed, and drain water
up to 200mm the resin surface, close the positive washing drainage valve, and prevent siphon
when draining.
9) Mix resin
Open the backwashing effluent valve and exhaust valve, manual air inlet valve and pneumatic
air inlet valve of the mixed bed to mix resin for about five minutes, and after the air pressure is 0.1
MPa and it is mixed evenly, close the manual inlet valve and pneumatic valve, wash the drainage
valve fully positively quickly, open the influent valve to drop resin rapidly, and prevent the layered
resin in settlement, for about 30s.
10) Positive washing
After resin drops, adjust the positive washing drainage valve to wash the mixed bed slowly,
and after the exhaust valve drains, close the exhaust valve and wash the mixed bed positively until
the mixed bed effluent DD is less than 0.2us/cm and SiO2 is less than 20ug/L; if the water quality
of the drainage water does not meet the requirements, re-wash the mixed resin positively.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 40
Rev.: A
SEC QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW TURBINE & AUXILIARIES OPERATION MANUAL
5.4.4.2.3. Table for operating procedures of desalination mixed bed equipment
Alkali
Acid
Back t
drainage
valve
Backwashing
influent valve
Positive
drainage
valve
Effluent
valve
Influent
valve
of
alkali
mixer
Alkali
inlet
valve
outlet
valve of
the
alkali
metering
box
Influent
valve
of acid
mixer
Acid
inlet
valve
outlet
valve of
the acid
metering
tank
Air
inlet
valve
Exhaust
valve
Middle
discharge
valve
Acid
metering
pump
Alkali
metering
pump
Self-use
Ti demineralization
mwater pump
15
5
Note: means that the valve starts or the pump operates
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005
Page 41
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
TURBINE & AUXILIARIES OPERATION MANUAL
5.4.5 Operations of water supply acid-base system
5.4.5.1. Preparations for dumping acid and alkali
1) Make clear delivery receipts and ask the relevant information clearly after tankers come, to
prevent mixed dumping acid-base.
2) Inform the lab technicians of the laboratory class to take samples for testing.
3) Wear acid-proof suits, rubber boots, protective masks, gloves and gas masks.
4) Record liquid level of high pH level tanker.
5) Prepare water and anti-acid-base burn liquid at the dumping acid-base site, and safety
shower pedal is not blocked and there is sufficient water pressure on the pipe.
6) The acid-base pipeline is not leaked, valve switch is flexible, liquid level indicator is precise,
and the acid mist absorber is normal.
5.4.5.2 Operations of dumping acid (base)
1) When an acid (base) tanker comes to the site, the acid (base) transport hose on the tanker is
butt jointed with the dumping acid (base) pump entrance.
2) The dumping acid (base) delivery pump is powered on and the local indicator light is on.
3) Open slowly the acid outlet valve of the acid (base) tanker.
4) Start the dumping acid (base) delivery pump, and input acid into the high level acid (base)
tank.
5) After dumping acid (base), stop the dumping acid (base) delivery pump, close the pump exit
valve, the acid outlet valve of the acid (base) tanker and the acid inlet valve of the high level
acid (base) tanker, and meanwhile remove the hose connected and clean the ground.
6) Record the acid (base) concentration, quantity, liquid level of high level acid tank and acid
tanker number in the handover sheet.
5.4.5.3 Attentions to dumping acid (base)
1) When connecting the hose, the fixed bolts connected with the flange must be tightened to
prevent leakage when dumping acid (base).
2) When removing the hose, take careful and confirm that no residual pressure exists in the
hose, to prevent residual acid (base) liquid from splashing.
3) When dumping acid (base), wear ant-acid (base) suits, rubber boots, protective masks,
gloves and other protective equipment surely and open the air inlet valve of low level storage
tank slowly.
4) When being splashed by acid (base) liquid, wash with plenty of water or in safety water
shower immediately, and conduct treatment in accordance with the medical protective
provisions of the “Rules of work of electric job security".
5.4.5.4 Operations of filling acid (base) into the metering tank
1) The high level acid (base) tank has enough acid (base) solution.
2) The acid (base) metering tank exit valve and emptying valve have been closed.
3) Acid mist absorber is normal.
4) Pay attention to observing the liquid level of the metering tank at the exit valve of high level
acid (base) tank and acid (base) metering tank inlet acid (base) valve, to prevent overflow.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005
Page 42
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
5) Stop filling acid (base) into the acid (base) metering tank, close the exit valve of the high level
acid (base) tank and the inlet acid (base) of the acid (base) metering tank, and pay attention
to closing to prevent overflow.
Note: when filling acid (base) into the metering tank, the site must be supervised.
5.4.6 Discharge waste liquid from the water treatment waste liquid tank
5.4.6.1 Preparations
1) Waste liquid pump and Roots blower are in good standby status.
2) Self-control air source pressure is 0.4 to 0.8 Mpa.
3) Valves and pipelines are not leaked.
5.4.6.2 Discharge waste liquid from the water treatment waste liquid tank
1) When the wastewater tank is at a high level, start the Roots blower, open the air inlet valve of
the waste liquid tank, stir the air in the waste liquid tank, stop the Roots blower after 5 minutes,
and close the air inlet valve of the wastewater tank.
2) Start the waste liquid pump, open its exit valve and transmit wastewater to the wastewater
treatment station.
3) When the waste liquid tank is at a low level, stop the wastewater pump and close its exit
valve.
5.5 Common faults, judgment and disposal
5.5.1 Analysis of abnormal reasons and treatment principle of water quality of the desalination
water tank
Analysis of abnormal reasons: first: check rapidly whether the online DD or silicon meter fail
or it is caused by the not timely monitoring of the operator, confirm that the meter is accurate, and
then check whether the medicine for test is overdue or fails or a wrong medicine is used, after all
are confirmed to be accurate; 2: sample and test the water quality of the desalination water tank
and the condensation water tank of the unit, drain the unqualified water, and put the standby
desalination water equipment into operation; third: analyze whether the operating equipment has
the following circumstances when being contaminated: 1. the effluent of the anion bed is seriously
deteriorated, impacting the effluent of the mixed bed, thus the water quality is deteriorated; 2. the
mixed bed not regenerated well is put into operation for fails, as is timely not monitored to stop it; 3.
the effluent of the mixed bed flows back or the backwashing valve is not sealed or the air valve is
not sealed, resulting in resin delamination so that the effluent of the mixed bed is deteriorated; 4.
the acid inlet valve or the alkali inlet valve or the backwashing water inlet valve of the operating
equipment is not sealed, the equipment is regenerated to cause the operating equipment being
contaminated; 5. resin contaminated and aged causes the effluent being deteriorated; 6. the
effluent resin trapper of the mixed bed is damaged, causing resin to enter into the thermal system
to be decomposited. Against these possible causes, analyze and eliminate them and find reasons
for treatment.
Treatment principle: first, if the desalination water tank is contaminated, stop filling water into
the condensation water tank of the unit immediately, thus causing the contaminated desalination
system of the desalination water tank to operate and regenerate possibly, and meanwhile close
the effluent valve of a group of desalination water tanks in operation; at the same time, view
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 43
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
immediately whether there is a change in the indicator of the water vapor system of the unit, and
stop filling water into the unit immediately if the water supply and boiler water indicators change,
drain all water out of the condensation water tank of the unit, and then fill water into the
condensation water tank of the unit with the standby desalination water tank, fill a lot of water in
the unit until the indicator is normal, and meanwhile resume the operation of the standby water
desalination equipment as soon as possible; if PH of the boiler water is low, add sodium hydroxide
and neutralize it; if the quality of the boiler water is poor and the water changed can not be
qualified, when it is up to “Class 3” processing value, report to the leadership about application for
stopping the boiler and draining the boiler water. If the water supply and boiler water indicator has
not changed, suspend to fill water into the unit, confirm the water quality of the desalination water
tank and condensation water tank of the unit, drain the unqualified water, and restore fill water into
the unit after the water quality is ok. Second, take corresponding measures for six possible
reasons: 1. isolate the contaminated anion bed and regenerate it so that it can be normal; 2.
isolate the contaminated mixed bed and regenerate it so that it can be normal; 3. eliminate the
reasons for the mixed bed delamination, re-mix resin and positively wash or re-regenerate; 4.
check the leakage valve, and stop the renewable water into the operating equipment, 5. replace
the contaminated and aged resin, and do not put the equipment into operation before replacement;
6. maintain the effluent resin trapper of the mixed bed, and do not leak resin into thermal system.
5.5.2 Effluent water from the cation bed has hardness
S/N Reason Treatment 1 The depth of the cation bed fails or
regeneration is bad Stop and maintain
2 Load is over allowable value Recover the normal flow 5.5.3 Electroconductivity of one stage demineralization water is big
S/N Reason Treatment 1 The cation bed fails and effluent water
quality is poor Stop the series and put standby series into
operation 2 The efficiency of the decarbonation fan
is low. Contact the maintenance personnel
3 The anion bed fails Stop regenerationand put backup bed into
operation 4 The periodic output amount of fabricated
water from the cation and anion bed is
too low and the influent water quality
changes.
Check water quality
5 The periodic output amount of fabricated
water from the cation and anion bed is
too low and the influent device is
damaged, and current bias occurs
Contact the maintenance personnel
6 The periodic output amount of fabricated
water from the cation and anion bed is
Strengthen backwashing, and conduct
maintenance and treat
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 44
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
too low and the backwashing water
volume is insufficient and resin surface
is not level
7 The periodic output amount of fabricated
water from the cation and anion bed is
too low and the amount of acid base is
insufficient or concentration is too low
during regeneration.
Increase the amount of acid base and improve
concentration during regeneration.
8 The periodic output amount of fabricated
water from the cation and anion bed is
too low and resin is reduced
Supplement resin
9 The periodic output amount of fabricated
water from the cation and anion bed is
too low and the resin is polluted
Clean resin and recover
5.5.4 The cation and anion resin backwashing delamination of the mixed bed is not obvious
S/N Reason Treatment 1 Backwashing delamination is
misoperated Conduct backwashing delamination operation
according to the provision of Manual 2 Proportion of cation and anion resin
does not meet the provision Conduct backwashing delamination operation
according to the provision of Manual 3 Resin is not fully ineffective Leach with NaOH solution or immerse resin,
and then re-delaminate. 4 Resin is polluted Clean resin or recover 5 Cation and anion resin cluster or have
bubble Increase backwashing flow and leach with
NaOH 5.5.5 Active carbon falls off when the active carbon bed is backwashed
S/N Reason Treatment 1 Too big backwashing flow Adjust the opening of the backwashing water
entrance valve, and control backwashing flow
strictly 2 Control the backwashing water flow
unstably Open the backwashing entrance valve slowly
3 The drainage valve damaged Stop and maintain 5.5.6 Resin in the mixed bed in operation falls off
S/N Reason Treatment 1 The effluent water hat of the mixed bed
is unqualified or damaged Replace the effluent water hat
2 The water hat installed does not meet
the requirements Contact the maintenance personnel,
investigate the cause and re-install 5.5.7 Quartz sand or resin in the cation or anion bed in conventional well-flushing or operation is
taken out
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 45 Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
S/N Reason Treatment 1 Confused layers at the bottom of switch Stop and maintain 2 Unqualified granularity of quartz sand
cushion causes uneven water
distribution
Change quartz sand cushion with qualified
granularity
5.5.8 Decarburizator has low efficiency
S/N Reason Treatment 1 Fan turns reversely Contact the electrical personnel for
maintenance 2 Inadequate wind pressure and force Contact the maintenance personnel or change
the fan 3 Too much flow Reduce inlet flow 4 Inadquate or too much filling Supplement or reduce filling 5 Water inlet device is damaged or is
provided with uneven water Contact the maintenance personnel to treat
6 Water Steam Supervision System Operation Manual
6.1 Technical specification
6.1.1 Water-vapor sampling system equipment
Parameter of
sampling point
Instrument disposition
Name of sampling
point Pressure
MPa Temper ature
CC
SC
pH
O2
SiO2
N2
H4
M
Condensate pump
outlet
2.8
42
Deaerator outlet pipe
0.8
170
Deaerator inlet pipe
0.8
170
Economizer inlet
20
291
Economizer outlet
20
291
Boiler water(left)
20
360
Boiler water(right)
20
360
Saturated steam
(left)
20
360
Saturated steam
(right)
20
360
Superheated steam
17.5
541
Closed clod water 0.4
50
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 46
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Parameter of
sampling point
Instrument disposition
Name of sampling
point Pressure
MPa Temper ature
CC
SC
pH
O2
SiO2
N2
H4
M
Reheater steam
5
541
Boiler sewage
disposal tank
0.423
153
Low-pressure heater
drainage
0.423
133.5
High-pressure heater
drainage
1.755
181.8
Boiler feedwater
0.2
50
Condenser hotwell 1
Condenser hotwell
21
Note: is the sampling points and instruments set, and is manual sampling points set
is to set a block of meter and all sampling points operate alternately.
Water-vaport on-line instrument:
S/N
Name
Specification and model
Unit
Qty
Manufacturer
1
Conductance meter
DDG-5188
Set
7×2
Shanghai Lihe
2
Hydrogen conductance
meter
DDG-5188
Set 5×2
Shanghai Lihe
3
Acidity meter
PHG-5288 Set
6×2
Shanghai Lihe
4
Oxygen meter
9182
Set 3×2
POLYMETRON
COMPANY 5
Silicon meter
(four-channel)
9210
Set 1×2
POLYMETRON
COMPANY 6
Hydrazine meter
9186
Set
1×2
POLYMETRON
COMPANY
6.1.2 Chemical dosing system equipment
S/N
Name
Model and specification
Unit
Qty
Remark
1
Ammonia solution
tank V=1.0m3,φ1000
Set
2
Material:1Cr18Ni9Ti
with motor agitating
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 47
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
device N=1.1kW
2
Feed-water
ammonification
metering pump
Q=58l/h
Set 3
Frequency conversion,
hydraulic pressure
diaphragm 3
Condensated water
ammonification
metering pump
Q=22l/h
Set 3
Frequency conversion,
hydraulic pressure
diaphragm 4
Hydrazine solution
tank
V=1.0m3,φ1000 Set
2
Material:1Cr18Ni9Ti
with motor agitating
device N=1.1kW 5
Feed-water
hydrazination
metering pump
Q=58l/h
Set 3
Frequency conversion,
hydraulic pressure
diaphragm 6
Closed cooling water
hydrazination
metering pump
Q=22l/h
Set 2
Hydraulic pressure
diaphragm
7
Phosphate solution
tank
V=1.0m3,φ1000 Set
2
Material:1Cr18Ni9Ti
with motor agitating
device N=1.1kW 6.1.3 Vapor-quality control standard
1) Condensated water quality standard
Control standard
Item
Unit Startup
Normal
Expected
value
Time interval
(H)
Remark
Hardness μmol/L ≈0 ≈0 ≈0 24
Positive KWH μs/cm ≤1.0 ≤0.3 ≤0.15 2 Dissolved
oxygen
μg/L
≤50
≤30
≤30
2
Read the online meter
once per 2h and manual
meter once per 24h Sodium μg/L ≤20 ≤10 ≤5 Assessment Ditto silicon dioxide μg/L ≤30 ≤20 ≤5 Ditto Iron μg/L ≤50 ≤20 ≤10
Copper μg/L ≤20 ≤5 ≤3 2) Feed-water quality standard
Control standard
Item
Unit Startup
Normal
Expected
value
Time interval
(H)
Remark
Total hardness μmol/L ≈0 ≈0 ≈0 24
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 48
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
silicon dioxide
μg/L
≤30
≤20
≤10
2
Read the online meter
once per 2h and manual
meter once per 24h dissolved
oxygen
μg/L
≤30
≤7
≤7
2
Read the online meter
once per 2h and manual
meter once per 24h
Chemical
deoxidant
μg/L
-
10-50
10-30
2
PH
9.0-9.6
9.0-9.6
9.0-9.6
2
First-class
ammonification 9.0-9.6 Positive KWH μs/cm ≤0.65 ≤0.3 ≤0.15 2 Iron
μg/L
≤50
≤20
≤10
Startup or
assessment
Copper
μg/L
-
≤5
≤3
Startup or
assessment
3) Boiler water quality standard
Control standard
Item
Unit Startup
Normal
Expected
value
Time
interval
(H)
Remark
silicon dioxide
μg/L
Silicon
cleaning
requireme
nt
≤250
≤100
2
Read the online meter
once per 2h and manua
meter once per 24h
PH(25)
9-10
9-10
9.3-9.5
2
Read the online meter
once per 2h and manual
meter once per 24h phosphateradica
l
mg/L
0.5-3.0
0.5-3.0
0.5-1.5
2
Read the online meter
once per 2h and manual
meter once per 24h Conductivity
μs/cm
-
≤60
≤20
-
Read the online meter
once per 2h and manual
meter once per 24h 4) Steam quality standard
Control standard
Item
Unit Startup
Normal
Expected
value
Time
interval
(H)
Remark
Cation
conductance
μs/cm
≈0
≈0
≈0
2
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 49
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Sodium
μg/L
≤20
≤10
≤5
2
Read the online meter
once per 2h and
manual meter once per
24h
silicon dioxide
μg/L
≤30
≤20
≤10
2
Read the online meter
once per 2h and
manual meter once per
24h
Iron
μg/L
≤50
≤20
≤10
Startup
and
assessme
nt
Copper
μg/L
≤15
≤5
≤3
Startup
and
assessme
nt
5) Cooling water quality standard of generator stator
Item
Unit
Control standard
Expected
value
Time
interval
(H)
Remark
PH
≥6.8
7.0-8.0
2
Read the online
meter once per 2h
and manual meter
once per 24h Hardness μmol/L ≈0 ≈0 24
Electroconductivity
μs/cm
<1.5
<1.0
2
Read the online
meter once per 2h
and manual meter
once per 24h Copper μg/L ≤40 ≤30 Assessment 6) Closed circulating cooling water
Item
Unit
Control
standard
Expected
value Time interval
(H)
Remark
PH
8-9
8-9
2
Read the online
meter once per 2h
and manual meter
once per 24h
Electroconductivity
μs/cm
≤30
≤20
2
Read the online
meter once per 2h
and manual meter
once per 24h
Date 2008-09-16
No. : QN1-SEC-G-04-TP-005
Page 50
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
6.2 Chemical supervision during unit operation
6.2.1 Chemical supervision at initial startup stage
6.2.1.1 Preparations for startup
1) Prepare analytical instruments and chemical medicines before the start of the units, clean the
instruments and prepare sufficient medicines.
2) Prepare adequate and qualified demineralized water.
3) Check that the steam-water sampling device, dosing equipment and chemical instrument
should be intact and in good standby status, and the closed cooling water system is in normal
use.
4) The dosing pump should be provided with above two thirds lubricant and all dosing pumps are
in good standby status.
5) Check whether the sampling cooling water should be sufficient, and open all the cooling water
inlet valves of samplers and observe whether the cooling water pressure is normal; defects
found will be timely processed.
6) Check that the liquid level of the phosphate metering tank, ammonia metering tank and
hydrazine metering tank should be higher than two thirds, or else it should be dosed.
7) Open the exit valve of the liquid medicine metering tank and the entrance valve of the
phosphate pump, ammonia metering pump and ammonia metering pump.
8) Contact the centralized control operator to open the primary continuous sewage disposal,
sampling and dosing valve.
9) Contact the maintenance thermal-control personnel to prepare for putting the chemical
instruments into operation prior to startup.
6.2.1.2 Chemical monitoring when starting
1) When the unit start, the leader on duty shall timely notify the chemical principal, who arranges
the opening of the cooling water entrance valve of the water-steam sampler of the unit and
observes that the cooling water pressure is normal, and contacts promptly to maintain and
treat the defects found.
2) When the unit begins to start, contact the centralized control operator to open the primary
sampling, dosing and continuous sewage disposal valve; after it has been verified that all the
primary valves are opened, adjust the cooling water volume of each sampler, adjust the
sampling water flow to wash the samplers; after the samplers are clean, adjust the manual
sampling water flow at 500 ml/min, and maintain stable flow and adjust the sampling water
temperature at 25 to 30.
3) Wash the condenser with water: when water flows into the condenser, after starting the
condensate pump, the leader on duty notices the chemical principal to begin washing the
condenser. The chemical principal starts the condensated water ammonification pump to
ammonify condensated water, and adjusts the condensated water pH at 8.8 to 9.3. Wash it
until the condensated water hardness is close to 0 μmol/L, iron content is no more than 50
μg/L and SiO2 content is no more than 30 μg/L, and thus the condenser washed is qualified,
as is reported to the leader on duty. The leader on duty can not conduct the next step until
receiving the chemical water quality report.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 51
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
4) Wash the deaerator with water: when starting to fill water into the deaerator, the leader on
duty notices the chemical principal to begin washing the deaerator, and coordinates at the
same time to put the deaerator heater into operation in order to ensure the deoxidization
effect. Chemical operator starts the feedwater ammonification pump and hydrazine pump to
add ammonification and pump into the feedwater, maintaining feedwater pH of 8.8 to 9.3 and
deaerator content of 10 to 50 μg/L. Monitor water samples of the rear sampling point of the
deaerator, and if the hardness is close to 0 μmol/L, iron content is no more than 50 μg/L, SiO2
content is no more than 30 μg/L and dissolved oxygen is no more than 30 μg/L, the deaerator
washed is qualified, as is reported to the leader on duty. The leader on duty can not conduct
the next step until receiving the chemical water quality report.
5) Wash the boiler with water in cold status: when the boiler is filled with water, the leader on
duty notices the chemical principal to fill water into the boiler, and the chemical principal starts
the phosphate dosing pump to dose into the steam drum and opens the continuous and
intermittent blowdown of the boiler. The chemical principal blows down samples of the
water-steam sampling devices and inputs the manual sampling system, and analyzes the
boiler water pH, phosphate content, iron content and SiO2 content. Control the boiler water
pH at 9.0 to10.0 and phosphate radical at 0.5 to 3.0mg/L; when the iron content is no more
than 50 μg/L and SiO2 content is no more than 30 μg/kg, the leader on duty is reported about
the qualified boiler washed in cold status. The leader on duty can not conduct the next step
until receiving the chemical water quality report.
6) Wash the boiler with water in hot status: after the boiler is ignited, the leader on duty notices
the chemical principal that the boiler has been ignited, and the continuous and intermittent
blowdown of the boiler maintain fully open, so that the boiler water is clarified as soon as
possible. Test chemically the boiler water pH, phosphate radical, iron content and SiO2
content, and control the boiler water pH at 9.0 to 10.0, phosphate radical at 0.5 to 3.0mg/L,
iron no more than 300 μg/L and SiO2 content no more than 300 μg/kg; test the iron content,
SiO2 content, copper content and sodium content in steam; when SiO2 content in steam is
more than 30μg/kg, iron content is more than 50 μg/L, copper content is more than 15 μg/L
and sodium content is more than 20 μg/L, the leader on duty is reported about the qualified
steam and rolling can be done. The leader on duty can not conduct the next step until
receiving the chemical water quality report.
7) Recycling requirements of condensated water after the steam turbine is rolled: the leader on
duty notices the chemical principal that the steam turbine has been rolled, and requests at this
time that the condensated water in the steam turbine can not be recovered and must be
discharged from the condenser; after the condensated water of the steam turbine is clear and
transparent visually outside, test the condensated water hardness, iron content and copper
content by sampling; when the condensated water hardness of the steam turbine is close to
0μmol/L, iron content is no more than 50 μg/L, copper content is no more than 15μg/L and
SiO2 content is no more than 20μg/L, the leader on duty is reported that the condensated
water can be recycled .
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 52
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
8) Wash silicon in the boiler by heating and lifting pressure: begin washing silicon when the main
steam pressure of the boiler rises to 7.5MPa. While washing silicon, monitor the boiler water
pH, phosphate content, iron content and SiO2 content at the same time, and control the boiler
water pH at 9.0 to 10.0, phosphate radical at 0.5-3.0mg/L, iron no more than 300 μg/L and
SiO2 following the requirements of washing silicon; when the SiO2 content in the boiler water
is up to the next pressure level allowable SiO2 content, pressure can continue to rise, and
silicon is washed according to the circular manner of “lifting pressure - lifting load –
decreasing pressure (to the point higher than the starting value of the previous lifting pressure)
– lowering the boiler water concentration (increasing the boiler blowdown and improving water
purity) - lifting pressure” until reaching the rated pressure. SiO2 content of the boiler water and
SiO2 content and pressure of steam are correspondingly shown in the table as follows:
Steam drum pressure
(MPa) 7.5-
10.0 10.0-
12.5 12.5-
15.0 15.0-
16.0 16.0-
17.0 17.0-
18.4 SiO2 content of the boiler water (μg/L)
3000
1500
500
400
300
250
SiO2 content of steam
(μg/L)
30
30
30
30
30
30-20
In the process of lifting pressure of the boiler, the SiO2 content of the boiler water and steam is
continuously analyzed. After SiO2 content of the boiler water and steam is qualified, the leader
on duty is timely reported, in order to adjust the operating conditions of the boiler to conduct
the next parameter pressure.
9) After the end of washing silicon, analyze chemically comprehensively the steam, boiler water,
feedwater and condensated water quality, and adjust dosage or sewage disposal in
accordance with water quality; the water quality indexes of the water-vapor system are up to
the normal value standards within eight hours when the units are parallel in; contact the
leader on duty to make timely adjustment if failing in meeting the standards.
10) Contact the thermal-control personnel to put related chemical instruments into operation (but
the pH scale must be input after the constant temperature system works) and do a good job in
detailed records when starting them.
6.2.2 Chemical supervision during normal operation stage of generating units
1) Patrol inspect and read the online instrument once every two hours, conduct a manual
laboratory test every day, investigate the reasons timely if the water vapor quality is
unqualified, check and confirm the experiment, increase in the number of analysis if the
experiment is correct, and strengthen water supply, correct the boiler water, contact the
centralized control personnel, adjust the operating conditions, and report to the chief and
leader on duty. Treat the problems related and make records in accordance with the vapor
quality deterioration third-class treatment principle and methods.
2) According to water-vapor quality, notice the centralized control personnel to adjust the
continuous blowdown of the boiler and ward the blowdown work regularly.
3) According to analysis conditions of water quality, adjust timely the amount of ammonia,
deoxidant and phosphate, guarantee that their content is qualified and at the same time
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 53
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
maintain the minimum level of chemical dosage. Chemical dosage should be uniform and
continuous as far as possible.
4) When the dissolved oxygen in the deaerator water and condensed water exceeds the
standard, strengthen supervision and make operating records, control the deaerator content,
and at the same time contact the centralized control personnel to adjust and treat.
5) Check the dosing equipment in operation every two hours once, treat the problems found
timely, or contact the maintenance personnel to eliminate them.
6) Adjust the temperature and flwo of samples in the allowed range and contact promptly the
maintenance personnel to treat the flaws.
7) Wash the sampling water of the high-temperature water-vapor sampling bracket to dispose
sewage at 10:00 every Monday once.
8) During the operation of the units, monitor the leakage of the condenser closely. When the
hardness or conductivity of the condensated water exceeds the standards, increase the
number of analysis, control the boiler water pH and phosphate radical within the qualified
scope, strengthen the sewage disposal, report to the chief and leader on duty and make
records.
9) The continuous blowdown of the boiler should be adjusted based on the control standard of
the boiler water and blowdown rate, avoiding too big blowdown rate from affecting economy
and too small blowdown rate from affecting the steam quality. The regular blowdown of the
boiler under normal circumstances is conducted once every morning shift daily; when the
boiler water concentration is over 50% of the normal value, the boiler water is turbid and the
quality of feedwater is bad, the number of blowdown should be increased.
10) Check the quantity of testing medicines and prepare the dosage for weekend on day shift
every Friday.
6.2.3 Chemical monitoring of the boiler during stoppage stage
1) After the generating unit stops, the chemical person on duty should stop the corresponding
water-vapor chemical monitoring instruments, close the corresponding water-vapor sampling
valve and sampling cooler, cooling water inlet and outlet valve. Pay attention to purging the
remaining water in various sampling pipes, to prevent the sampling system from being
corroded and blocked. When the thermal equipments stop or are backupped, maintain them
according to the relevant provisions of stoppage (backup) maintenance.
2) After the generating unit operates normally in a short term, protect the boiler from corrosion by
maintaining feedwater pressure, and purge the remaining vapor inside the pipeline connected
the steam turbine body for anti-corrosion of the steam turbine after stopping so that the
cylinder keeps dry.
3) When the generating unit is partly repaired or stops for not more than 30 days, protect it by
using the method that hot boiler discharges water and waste heat is used for drying.
4) When the generating unit is overhauled or stops for more than 30 days, protect it by stopping
using octadecyl amine.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 54
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
6.3 Chemical protection of standby unit
In order to prevent the thermal equipment from being corroded during stoppage (standby)
period and ensure the secure and economic operation of the unit, according to “Manual for
chemical supervision” and “Rules of anti-corrosion for thermal stoppage (standby) equipment in
thermal power plants”, it is necessary to take effectiveanti-corrosion protection measures for the
thermal equipment during the stoppage to prevent the boiler, heater, steam turbine and other
equipment from being corroded and damaged, and the protection measures are specially
prepared as follows combined with the actual situation of the company:
6.3.1 Anti-corrosion protection methods
6.3.1.1 Ammonia – deoxidant comined passivation + water discharged from hot boiler and waste
heat for drying
1) Scope of use
The method applies to the circumstance under which the unit stops for less than a week.
2) Technical points
Using feedwater and condensated water chemical dosing system to inject ammonia and
deoxidant to the system two hours before the boiler stops, improve PH value and deoxidant
concentration and form protective membrane under the high temperature, and then the boiler
discharges hot water and is dried by waste heat.
3) Operating methods
Using feedwater and condensated water chemical dosing system to inject ammonia and
deoxidant (acetone oxime in the first and second stage and hydrazine in the third) to the system
two hours before the boiler stops; PH is up to 9.5 to 10.0 at the entrance to the economizer, the
deoxidant concentration is 30 to 50 mg/L and the deaerator concentration of the boiler water is
200 to 400 mg/L. In the process of stopping the boiler, maintain two hours when the steam drum
pressure declines to 4.0 MPa and then continue to release pressure; when the steam drum
pressure declines to 0.5 to 0.7 MPa (135MW generating unit) and 0.6 to 0 .9 MPa (300MW
generating unit), discharge the boiler water rapidly. In the course of discharging water, open fully
the air valve, exhaust valve and water drain valve, and ventilate and discharge moisture in the
boiler naturally. After the end of discharging water, close the air valve, exhaust valve and water
drain valve and seal up the boiler.
4) Attentions
While the boiler release pressure and drains water, control strictly that the temperature of the
upper and lower wall of the steam drum does not exceed the allowable value.
6.3.1.2. Adding octadecylamine and water discharged from hot boiler and waste heat for drying
1) Scope of use
The method applies to the circumstance under which the unit stops for more than a week.
2) Technical points
When the unit stops, add octadecylamine into the thermal system, and it is volatile at a high
temperature to form steam after it enters into the boiler, thus full of the boiler, steam turbine and
the whole thermal system. A layer of hydrophobic octadecylamine protective film forms on the
metal surface of all parts of the thermal system, to separate the metal from the air, thereby
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 55
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
preventing the metal from being corroded by water, oxygen and carbon dioxide in the atmosphere
during the stoppage of the equipment, protecting the equipment.
3) Operating methods
a) Using special rapid dosing device of octadecylamine emulsion and connect its outlet hose
to the outlet pipe of the hydrazine pump.
b) Dosing: 10% pure octadecylamine emulsion 200 kg/time, (135MW generating unit),
400kg/time (300 MW generating unit).
c) When the main steam temperature drops to 500 below and it is estimated that it is about
1.5 to 2 hours before the main steam valve is closed after the unit stops (usually, it is
estimated under the power level in the coal powder warehouse), and the leader on duty
notices the chemical principal to begin to dose (at this time feedwater flow is suppressed
as much as possible. Superheated steam temperature can be adjusted at 400 to 500 and can not be higher than 500 , and the water level of the steam drum is controlled at
low water level).
d) Chemical dosing is under control completed generally for about 30 minutes. After dosing,
wash the dosing box and pump with water, open the dosing pump for 10 minutes, and
wash the dosing pipeline.
e) Report to the leader on duty after dosing, and the generating unit should systematically
circulate for 1 to 1.5 hours before downtime after completion of dosing.
f) Stop the boiler and hot boiler discharges water: when the steam drum pressure drops to
0.5 to 0.7MPa (135MW generating unit) and 0.6 to 0 .9 MPa (300MW generating unit) in
the process of stopping the boiler, discharge the boiler water quickly. In the course of
discharging water, open fully the air valve, exhaust valve and water drain valve, ventilate
and discharge the moisture from the boiler naturally. After discharging water, close the air
valve, exhaust valve and water drain valve and seal up the boiler.
4) Attentions
a) While the boiler releases pressure and drains water, control strictly that the temperature of
the upper and lower wall of the steam drum does not exceed the allowable value.
b) Since dosing, begin to record PH and conductivity meter of feedwater, boiler water,
superheated steam and condensated water, and make a record every five minutes
(usually, the conductivity increases slightly but PH does not change)l if conductivity and
PH are significantly abnormal, conduct manual re-testing immediately by sampling.
c) Record the boiler operation parameters (load, feedwater flow, main steam temperature
and water level of steam drum) during dosing every five minutes.
d) After beginning to dose, pay attention to water samples at the sampling points. When there
is white turbidity in water samples, dosing is normal, or else the dosing liquid has not
completely entered into the system and the chemical dosing system (including the
feedwater system) should be timely inspected.
e) There is no foreign body in the liquid when dosing, and massive octadecylamine should be
stirred up and scattered to prevent the pump from being blocked.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 56
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
6.4 Operation of the boiler chemical dosing system of the boiler
6.4.1 Phosphatizing the boiler water
6.4.1.1 Preparations for phosphatizing
1) Check that the relevant valves of all equipments of the phosphatizing system are switched off.
2) Check that the system is in good standby status.
6.4.1.2. Preparation of phosphate solution
1) Around 1% Na3PO4 • 12 H2O and Na2HPO4 • 12 H2O or NaOH are respectively prepared in
the phosphate solution tank, and a mixed solution is generally not prepared.
2) Weigh appropriate solid Linsuansanna, Na2HPO4 or sodium hydroxide once, pour into the
phosphate solution tank and co-ordination phosphate solution tank, open the inlet valve of the
deionization water, and close the inlet valve after the water level is up to a certain height, start
and stir the motor so that liquid in the solution tank is fully dissolved and mixed evenly before
stopping the stirring motor.
3) If phosphate is easily not dissolved, open the heating device so that the solution temperature is up to 50 to 60, and then open the stirring motor to stir until the solution is dissolved
completely.
6.4.1.3. Phosphate dosing steps
1) Contact the centralized control personnel to open the primary boiler water dosing valve.
2) Open the exit valve of the metering tank.
3) Open the inlet and outlet valve of the metering pump.
6.4.1.4. Manually start and stop the dosing pump
1) Switch the design metering pump to the “on-site” shift, start the dosing pump, and adjust the
dosage of the dosing pump according to needs.
2) Check that the motor, gearbox and all rotating parts have no abnormal noise and pressure
gauge is slightly higher than the steam drum pressure, and the dosing pump can not leave
after the pressure is normal.
3) Stoppage of the dosing pump: stop the dosing pump and close the exit valve of the dosing
pump.
6.4.1.5. Automatic dosing operation
1) Switch the phosphate dosing pump and coordination phosphate dosing pump control knobs
to “Programmed-control” shift and switch the frequency converter to “Input”.
2) In ”Soft hand” state of the CRT, start the dosing pump and adjust the pump frequency
manually on the CRT.
3) In the “Automatic" state of the CRT, phosphate dosing pump and coordination phosphate
dosing pump enter into the automatic dosing state according to the phosphate radical
concentration of the boiler water and automatically start and stop, and coordinate dosing.
4) Stoppage of the pump: in the “Soft hand" state of the CRT, press the dosing stop switch to
end the stopping the pump.
6.4.1.6. Automatic phosphate dosing exists
When the automatic dosing fails, it can be switched to the manual dosing; switch the pump in
the system to the “Soft hand" state of the CRT, and switch the control knob on the start and stop
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 57
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
button of the CRT or the on-site switch box to “on-site” to start and stop the dosing pump on the
site.
6.4.2 Feedwater and condensated water ammonification treatment
6.4.2.1. Preparations for ammonification
1) Check that the relevant valves of all ammonification system equipments are switched off.
2) Check that the system is in good standby status.
6.4.2.2. Preparation of ammonia solution
1) Open the water inlet valve of ammonia solution metering tank, and close the water inlet valve
when the water level reaches a certain level.
2) Open the ammonia inlet valve of the ammonia metering tank, ammonia filling inlet valve and
ammonia bottle outlet valve to fill ammonia, pay attention to the pressure display (for example,
the ammonia bottle outlet valve should be immediately closed to change the ammonia bottle
filled with ammonia liquid if no pressure), close the ammonia bottle outlet valve, ammonia
filling inlet valve and ammonia inlet valve of the ammonia metering tank after filing sufficient
amount of ammonia.
6.4.2.3. Manually start and stop the dosing pump
1) Contact the centralized control personnel to open the primary ammonification valve.
2) Open the exit valve of the ammonia metering tank and the entrance and exit valve of the
ammonia pump, switch the dosing metering pump to the “on-site” shift, start the dosing pump,
and adjust the dosing pump stroke in accordance with needs to adjust dosage.
3) Check that the motor, gearbox and all rotating parts have no abnormal sound, and the dosing
pump can leave after the pressure is normal.
4) Stoppage of the dosing pump: stop the dosing pump and close the exit valve of it.
6.4.2.4. Automatic dosing operation
1) Switch the ammonia pump control knob to the “Programmed-control" shift and switch the
frequency converter to “Input”.
2) In ”Soft hand” state of the CRT, start the dosing pump and adjust the pump frequency
manually on the CRT.
3) In the “Automatic" state of the CRT, phosphate dosing pump enters into the automatic dosing
state according to the feedwater pump, closed cooling water and condensed water pH value.
4) Stoppage of the pump: in the “Soft hand" state of the CRT, press the dosing stop switch to
end the stopping the pump.
6.4.2.5. Automatic phosphate dosing exists
When the automatic dosing fails, it can be switched to the manual dosing; switch the pump in
the system to the “Soft hand" state of the CRT, and switch the control knob on the start and stop
button of the CRT or the on-site switch box to “on-site” to start and stop the dosing pump on the
site.
6.4.3 Water and closed cold water hydrazination
6.4.3.1. Preparations for hydrazination
1) Check that the relevant valves of all ammonification system equipments are switched off.
2) Check that the system is in good standby status.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 58
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
6.4.3.2. Preparation of the ammonia solution
1) Check whether the connecting pipe is connected with the hydrazine metering pump liquid
pump well, and insert the pump inlet pipe into the hydrazine storage barrel.
2) Open the entrance valve of the hydrazine metering tank, start the hydrazine self-suction pump,
and inject appropriate hydrazine to the hydrazine metering tank.
3) Stop the hydrazine metering pump liquid pump, and close the entrance valve of the hydrazine
metering tank.
4) Open the water inlet valve of the hydrazine solution metering tank, and close the water inlet
valve when the water level reaches two thirds liquid level.
5) Start the agitator to stir until the solution is evenly mixed before stopping preparation.
6.4.3.3. Manually start and stop the dosing pump
1) Contact the centralized control personnel to open the primary hydrazination valve.
2) Open the exit valve of the hydrazine metering tank and the entrance and exit valve of the
hydrazine pump, switch the dosing metering pump to the “on-site” shift, start the dosing pump,
and adjust the dosing pump stroke in accordance with needs to adjust dosage.
3) Check that the motor, gearbox and all rotating parts have no abnormal sound, and the dosing
pump can leave after the pressure is normal.
4) Stoppage of the dosing pump: stop the dosing pump and close the exit valve of it.
6.4.3.4. Automatic dosing operation
1) Switch the hydrazine dosing pump control knob to the “Programmed-control" shift and switch
the frequency converter to “Input”.
2) In ”Soft hand” state of the CRT, start the dosing pump and adjust the pump frequency
manually on the CRT.
3) In the “Automatic" state of the CRT, hydrazine dosing pump enters into the automatic dosing
state according to the feedwater flow to change frequence automatically.
4) Stoppage of the pump: in the “Soft hand" state of the CRT, press the dosing stop switch to
end the stopping the pump.
6.4.3.5. Automatic hydrazine dosing exits
When the automatic dosing fails, it can be switched to the manual dosing; switch the pump in
the system to the “Soft hand" state of the CRT, and switch the control knob on the start and stop
button of the CRT or the on-site switch box to “on-site” to start and stop the dosing pump on the
site.
6.5 Reason and treatment of water steam quality deterioration
6.5.1 Water-vapor cracking treatment principle
1) When the water-vapor quality is deteriorated, strengthen the analysis, first of all check
whether our own analysis and determination are right and the sampling containers are clean,
identify whether the water-vapor samples are correct and representative, and then analyze
whether the drugs used go bad and whether calculation methods are accurate and correct.
2) After determining that the analysis is accurate, report to the chief and the leader on duty
timely to propose the chemical supervision and treatment advices.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 59
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3) For the deterioration in the water-vapor quality, the persons on duty make records on the
extent, reasons, and treatment processes and results of water-vapor deterioration. If there are
accidents resulted from chemical reasons, chemical professional staff should be organized to
conduct accident analysis and timely treatment, to restore water-vapor standard value as
soon as possible.
6.5.2 Tertiary treatment principle
The key chemical indexes of the boiler feedwater, boiler water and condensated water are
processed according to the tertiary treatment values, and the meaning of tertiary treatment values
are as follows:
First treatment value - 2 times the normal value, with the possibility of accumulated impurities
and corrosion, it should be restored to the normal value within 72 hours.
Secondary treatment value - 2 times first treatment value, the accumulated impurities and
corrosion will surely occur and it should be restored to the normal value within 24 hours.
Tertiary treatment value - more than the secondary treatment value, experience has shown
that corrosion will be rapidly carried out and the boiler should stop in four hours.
In every level of the non-normal treatment methods, if it can yet not return to the normal within
the required time, a higher level of treatment method should be taken. In the steam drum boiler,
one of the methods for restoration of the normal value is relieve pressure in operation.
When the water-vapor quality is abnormal, the contents in the table below shall be
implemented:
Treatment value Water sample
Item
Normal value
First class Second class Third class
Sodium μg/L ≤10 10~20 20~35 >35 Condensated
water Electroconductivity
μs/cm
≤0.3 0.3~0.4 0.4~0.5 >0.5
Copper 8.8~9.3 <8.8 or >9.3
pH(25) No
copper 9.0~9.6
<9.0 or >9.6
<8.0
~
Electroconductivity
μs/cm
≤0.3 0.3~0.4 0.4~0.65 >0.65
Feedwater
Dissolved oxygen
μg/L
≤ 7 >7 >20 ~
Boiler water PH (25) 9~10 <9.0 <8.5 <8.0
If feedwater PH is less than 7.0 or condensated water sodium is more than 400 ug/l, the machine
should be immediately shut down Note: when there is abnormal water quality, CL-, Na+, conductivity and alkalinity in the boiler
water should also be determined in order to identify the reasons and take corresponding
measures.
6.5.3 Feedwater turbidity
S/N Reason Treatment
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 60
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
1 The condensated water, drainage and
supply water of feed water are turbid Identify the polluted water source, cut off the
pollution source and treat the water source. 6.5.4 Unqualified dissolved oxygen in feedwater
S/N Reason Treatment 1 The deaerator operates abnormally Adjust the operation of the deaerator 2 The internal device of the deaerator fails Contact the maintenance personnel to treat the
failure. 3 Too much replenished water in the
deaerator Reduce the instantaneous replenished water
and balance replenishment 4 The sampler is not sealed Contact the maintenance personnel to treat
timely 6.5.5 Unqualified silicon content and sodium content(or conductivity)in feedwater
S/N Reason Treatment 1 The silicon content and sodium content
in the condensated water, drainage and
supply water of feed water are
unqualified
Identify the unqualified water source, cut off
the pollution source and treat the water source.
2 When the continuous blowdown
expansion tank is put into operation,
steam with water of the deaerator goes
into it.
Adjust the operation of the continuous
blowdown expansion tank
6.5.6 Unqualified iron and copper content in feedwater
S/N Reason Treatment 1 In the early stage when the generating
unit starts, the water-vapor system has
high copper and iron content.
Change water and increase the sewage
disposal capacity
2 The iron and copper content in drainage
are high. Identify the drainage with high iron and copper
content and remove them. 3 pH controlled too lowly Improve the feedwater pH. 4 Feedwater system is corrided Strengthen ammoniation treatment and do a
good job in antisepticise. 6.5.7 Unqualified feedwater pH
S/N Reason Treatment 1 Too high or low ammonification volume Detect the ammonia solution concentration and
make appropriate adjustment of
ammonification volume. 2 The ammonification system fails Check and contact the maintenance personnel
to eliminate the failure. 3 The pH of condensated water and
feedwater comprising supply water is
Identify the water source with abnormal pH,
and treat the water source.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 61
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
normal
6.5.8 Unqualified condensated water hardness or conductivity
S/N Reason Treatment 1 The condenser leaks Check and block leakage 2 The replenished water in the condenser
is unqualified Change qualified water
3 Unqualified reclaimed drainage water Cut off pollution source and treat the water
source 6.5.9 Unqualified dissolved oxygen in condensated water
S/N Reason Treatment 1 Vacuum part of the condenser leaks. Investigate and block leakage 2 The undercooling degree of the
condenser is too bid. Adjust the under cooling degree of the
condenser 3 Air goes into the condensated water
pump in operation. Activate the standby pump and maintain the
defective pump. 4 Excessive condensated water
replenishing capacity Strengthen the readjustment and balance
water replenishing to prevent water
replenishing capacity from fluctuating. 6.5.10 Silicon and sodium content of steam exceed the standard
S/N Reason Treatment 1 Silicon and sodium content of the boiler
water exceed the standard Increase the discharge capacity of the boiler
2 The operating conditions of the boiler
are instable, steam drum water level is
high and the load changes greatly.
Report to the leader on duty and adjust the
operating conditions of the boiler.
3 The steam-water separator has flaws or
low efficiency. Eliminate defects and improve the separative
efficiency 4 Too big dosing concentration or too fast
dosing. Strengthen sewage disposal and adjust the
chemical dosing situation. 5 Desuperheater water quality is bad. Improve the desuperheater water quality 6.5.11 Boiler water is turbid visually outside
S/N Reason Treatment 1 Turbid feedwater or too big hardness Identify polluted water source, cut off it and
treat water source, to carry the boiler sewage
disposal until clarification 2 The sewage of the boiler is not disposed
for long time or the discharge capacity is
not enough.
Implement the boiler sewage disposal
3 The new period or the initial stage of the
maintenance boiler put into operation. Increase the discharge capacity of the boiler
until water quality is qualified. 6.5.12 Silicon content and sodium content (or conductivity) of the heater water are unqualified
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 62
Rev.: A
4
4
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
S/N Reason Treatment 1 Feedwater quality is poor Identify polluted water source, cut off it and
treat water source, and adjust the operation of
the continuous sewage disposal expansion
tank of the boiler. 2 Boiler sewage is not normal. Increase the discharge capacity of the boiler or
eliminate the defects of the sewage disposal
device. 6.5.13 The boiler water PO 3-
is higher than the standard
S/N Reason Treatment 1 Too big phosphate solution
concentration Dilute phosphate concentration
2 The outlet liaison valve of the dosing
pump is not closed tightly so that
phosphate is added into another boiler.
Check whether outlet liaison valve of the pump
is opened or closed correctly.
3 The operating conditions of the boiler
change drastically and the concentration
rate of the heater water is high.
Adjust the operating conditions of the boiler
and strengthen the sewage.
4 Hidden phosphate is dissolved. Strengthen supervision and increase the
sewage. 6.5.14 The boiler water PO 3-
is lower than the standard
S/N Reason Treatment 1 Low phosphate solution concentration Increase phosphate concentration 2 Solution tank has no liquid medicine or
the dosage pump does not work Investigate the cause, and eliminate defects
3 The outlet liaison valve of the pump is
loose or opened wrongly. Check whether the outlet liaison valve of the
pump is closed tightly or is opened correctly. 4 The condenser seriously leaks, the
condensated water is badly treated,
causing large feedwater hardness.
Investigate and block the leakage of the
condenser and increase the dosage.
5 Too much discharge capacity Reduce discharge capacity 6 The operating conditions of the boiler
change drastically and phosphate
temporarily disappears.
Adjust the operating conditions of the boiler to
prevent phosphate from disappearing
temporarily. 6.5.15 The boiler water pH is lower than the standard
S/N Reason Treatment 1 Inadequate phosphate dosage Increase phosphate dosage 2 Acid water enters into the boiler Investigate the cause, and eliminate the source
of acid water and add NaOH into acid water to
adjust pH.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 63
Rev.: A
4
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
3 Sewage volume is too much. Adjust the discharge capacity 4 Organic matter mixed in feedwater Investigate the cause and eliminate organic
matter 5 Lower ammonia content of feedwater Add ammonia content of feedwater to the
applicable scope 6.5.16 The boiler water pH declines sharply and PO 3-
is basically normal
S/N Reason Treatment 1 Acid water enters into the boiler Identify the source of acidic water quickly,
eliminate acid water to enter into the boiler, and
strengthen the regular discharge and open the
continuous blowdown volume. Add NaOH and
Na3PO4 mixture to the boiler so that the boiler
water pH returns to the normal as soon as
possible. 2 The condenser leaks Contact relevant departments to investigate the
leakage of the condenser. 6.5.17 Unqualified conductivity, copper and pH in cooling water of generator
S/N Reason Treatment 1 The generator cooling water system is
corrided seriously. Taking antisepsis measures.
2 The cooling system maintained is
cleaned incompletely Exchange the qualified cooling water and input
small mixed bed. 7 Waste Water Treatment Plant Operation Manual
7.1 General description of waste water station and system
7.1.1 Waste Water Disposal System Flow
Waste Water→ Waste Water Pool →Ph Adjusting Box→ Coagulation Pool →Clarification
Pool→ Clear Water Tank→ Activated Carbon Filter→ Neutralization Pool → Outlet Water Pool→
Ash Handling System→ Sludge Pool→ Concentrate Pool →Ash Slurry Pool
Chemical feed devise and compress air system is also included.
7.1.2 Requirement of effluent quality of wastewater treatment system
No. Parameter Unit Limited value 1 Temperature 40 2 pH - 5.5~9 3 BOD5 mg/l 50 4 COD mg/l 100 5 SS mg/l 100 6 Mineral Oil mg/l 1 7.2 Technical specification
S/N Name Parameter Unit Qty Remark
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 64
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
1
Generating unit drain
tank
V=200m3 Set
1
2
Drain pump of
generating unit drain
tank
Q=150t/h,P=0.4MPa Set
2
3 Roots blower Q=8.68 m3/min,P=0.06MPa Set 2 4 Roots blower Q=30m3/min,P=0.06MPa Set 2
5
Irregular wastewater
tank V=1500m3,25×18×4 Set
1
6
Irregular wastewater
tank discharge pump Q=100t/h,P=0.2MPa Set
2 N=15kW
7 Wastewater tank V=1500m3,25×18×4 Set 1 8 Wastewater pump Q=100t/h,P=0.3MPa Set 2 N=22kW 9 pH adjustment pump V=50m3,5×3×4 Set 1 10 Flocculation tank V=50m3,5×3×4 Set 1
11
Clarification tank
Q=100t/h , 9800mm
diameter Set
1
12 Sludge sump V=20m3,4×3×4 Set 1 13 Sludge discharge pump Q=10t/h,P=0.3MPa Set 2 14 Clarification pool V=150m3,6×8×4 Set 1
15
Clarification water
delivery pump Q=100t/h,P=0.3MPa Set
2 N=22kW
16
Activated carbon filter
2000mm filling and 3200mm
diameter Set
2
17 Neutralizing tank V=100m3,5×5×4 Set 1 18 Outlet pool V=200m3,5×10×4 Set 1 19 Bckwashing pump Q=200t/h,P=0.3MPa Set 2 N=55kW 20 Output pump Q=100t/h,P=0.3MPa Set 2 N=22kW 21 Unloading alkali pump Q=10t/h,P=0.2MPa Set 1 N=4kW
22
Sodium hydroxide
storage tank
V=10m3 PCS
1
23 Alkali metering pump Q=100L/h,P=0.5MPa Set 2 24 Unloading acid pump Q=100t/h,P=0.3MPa Set 1 N=4kW 25 Acid storage tank V=10m3 PCS 1 26 Acid metering pump Q=20L/h,P=0.5MPa Set 2 27 Oxidant metering tank V=3m3 PCS 1
28 Oxidant metering pump Q=300L/h,P=0.5MPa Set 2 29 FeCL3 dissolution tank V=20m3 PCS 1 30 FeCL3 delivery pump Q=10t/h,P=0.2MPa Set 1 N=4kW 31 FeCL3 metering tank V=1m3 PCS 2
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 65
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
32 FeCL3 metering pump Q=20L/h,P=0.5MPa Set 2 33
Wastewater delivery
pump Q=100t/h,P=0.2MPa Set
2 N=15kW
7.3 Operation of waste water treatment equipments
7.3.1 Operation of chemical dosing system
7.3.1.1 General
Waste water station chemical feed system include a set of oxidant dosing system, a set of
coagulant aid dosing system, a set of hydrochloric acid dosing system and a set of sodium
hydroxide dosing system.
1) Oxidant dosing: bleaching powder, significant chlorine 10%, adjusts waste liquid pool COD
less than 80 mg/L.
To locate dosing point at unfrequent waste water pool and waste water pool in order to
sterilize.
2) Coagulant aid dosing: Iron(Ⅲ ) chloride(FeCl3),clarification pool inlet dosage 27 to 63mg/l,
turbid degree of outlet water less than 20 mg/L.
To locate dosing point at inlet water pipe of Clarification Pool in order to coagulation and
clarification disposal, and remove the suspend substance and colloid.
3) Hydrochloric acid dosing: 30% technical hydrochloric acid, dosage 0 to 0.20kg/m3,
4) Sodium hydroxide dosing: 30% to 40% sodium hydroxide, dosage 0 to 0.60 kg/m3,pH value
control 6~9.
7.3.1.2 Source of wastewater
1) Pickling waste liquid of the boiler
2) Drainage from backwashing the filter and regenerated wastewater of ion exchanger
3) Wastewater from washing the air preheater
4) Industrial wastewater
7.3.2 Wastewater treatment method and procedure
7.3.2.1. Operation of the water pump
1) Inspection before startup
a) Clean the water pump body and its surrounding, where there is no sundries to obstruct
operation of the water pump.
b) Guarantee sufficient liquid level in the pool.
c) Open the inlet valve of the pressure gauge of the water pump and check if the indicator of
the pressure gauge is normal or not.
d) Check if there is full of liquid in the water pump or not or it is required to open exhaust
valve of the water pump and inject liquid into the water pump.
2) Startup of the water pump
a) Close the outlet valve of the water pump.
b) Power on the water pump for startup.
c) Check if operation of pump is normal or not and open outlet valve of the water pump to
check if flow of the water pump and indicator of the pressure gauge are within regulated
scope.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 66
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
d) Variation of pressure and flow of the water pump shall meet manual when flow changes.
3) Shutdown of the water pump
a) Close outlet valve of the water pump and stop the water pump.
b) Close the water inlet and outlet valve and isolate the power supply and then hang an
alarm board according to the manual when stopping the pump for repair.
7.3.2.2 Startup and shutdown of Roots blower
1) Inspection before startup
a) Check if there are sundries which may obstruct operation of the water pump around the
blower.
b) Check if the pressure gauge and amperemeter are normal or not.
c) Check if the pipeline valves of Roots blower are opened or not.
2) Startup of Roots blower
a) Open the air outlet and exhaust valves of Roots blower.
b) Power on the blower for startup and operate for about 0.5 minute. Open air inlet valve of
wastewater storage pool which needs air inlet and close exhaust valve of blower.
c) Check if operation of blower is normal or not after operation.
d) Check if indicators of the pressure gauge and amperemeter are within regulated scope or
not.
e) It is only required to start up another blower after opening air inlet valve of wastewater
storage pool which needs air inlet if one blower is already in operation.
3) Shutdown of Roots blower
a) Open exhaust valve of blower and close corresponding air inlet valve of wastewater
storage pool.
b) Stop Roots blower and close air outlet and exhaust valves of blower.
7.3.2.3 Startup and shutdown of the dosing metering pump (acid, alkali, flocculating agent and
oxidation pump)
1) Inspection before startup
a) Clean the water pump and surrounding environment to remove sundries which may
obstruct operation of the water pump.
b) Guarantee sufficient liquid level in the metering tank.
c) Open inlet valve of the pressure gauge of the water pump to check if indicator of the
pressure gauge is normal or not.
2) Startup of the dosing pump
a) Open inlet and outlet valves of the water pump.
b) Power on the water pump for startup.
c) Check if operation of the water pump is normal and indicator of the pressure gauge of the
water pump is within regulated scope or not.
3) Shutdown of the dosing pump
a) Power off the dosing pump.
b) Close water inlet and outlet valves and isolate the power supply and then hang an alarm
board according to the manual when stopping the water pump for repair.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 67
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
7.3.2.4 Operation of the wastewater treatment system
1) Inspection before startup
a) Check if the wastewater treatment system is powered on or not.
b) Check if pumps and blowers are in good standby status or not.
c) Guarantee sufficient liquid medicine, acid and alkali in every dosing box.
d) Check if the irregular wastewater Treatment basin, wastewater Treatment basin, PH
adjustment box, flocculation tank, clarification tank, concentrated tank, neutralizing tank
and water outlet pool are in good standby status or not.
e) Check if ampere meter, pressure gauge, flow meter and every chemical measurement
instrument are in good standby status or not.
f) Check if the activated carbon filter is in good standby status or not.
2) Irregular wastewater treatment operation of the drainage tank of the unit
a) Open air inlet valve of irregular wastewater Treatment basin and start up drainage pump
of drainage tank of the unit.
b) Open the water inlet valve of the wastewater Treatment basin and close the irregular
wastewater Treatment basin when irregular wastewater Treatment basin has a high
liquid level.
c) Start up one Roots blower for aeration for about 20 hours and open the dosing valve then
start up the dosing pump of the deoxidizer to adjust the dosage so that COD of
wastewater can be less than 80ppm when one of irregular wastewater Treatment basins
has a high liquid level.
d) Open the water outlet valve of the wastewater Treatment basin and start up the
wastewater pump so that wastewater can pass through PH adjustment tank, flocculation
tank, activated carbon filter, neutralizing tank and water outlet pool and so on in
sequence. PH adjustment tank and final neutralizing tank shall monitor values according
to on-line PH meter and acid and alkaline system can charge and adjust automatically.
e) Start up water outlet pump to store the water in water storage box of the ash removal
system after the water quality meets the drainage standard.
f) Sludge in the clarification pool is drained to the concentrated tank, and start up drainage
pump of the concentrated tank to drain sludge to the sludge pool of the ash removal
system at the same time.
3) Constant wastewater treatment operation of drainage tank of the unit and water supply
treatment system of the boiler
a) Open the water inlet valve of the wastewater Treatment basin when there is wastewater
in the drainage tank of the unit and water supply treatment system of the boiler.
b) Open water outlet valve of wastewater Treatment pool and start up wastewater pump
when liquid level of the waste liquid tank is high. Wastewater will pass through PH
adjustment tank, flocculation tank, clarification tank, activated carbon filter, neutralizing
tank and water outlet pool and so on in sequence. The acid and alkaline system can be
automatically adjusted by dosing in the PH adjustment tank and final neutralizing tank
according to the monitoring values of on-line PH meter
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 68
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
c) Start up the water outlet pump to drain to the ash system water storage tank after the
water quality meets the drainage standard.
d) Sludge in the clarification tank is drained into the concentrated tank, and start up
drainage pump of the concentrated tank to drain sludge to the sludge pool of the ash
removal system at the same time.
4) Operation and supervision of the wastewater treatment equipment
a) Sample and analyze turbidity, COD, BOD5 and PH before drainage of treated
wastewater and wastewater can not be drained until every indicator is qualified.
b) Strengthen inspection of every rotary mechanical equipment during operation of the
wastewater equipment.
c) Inspect and supervise PH valve of the drainage constantly during operation of
equipments.
d) Ensure that the liquid level of acid and alkaline metering tank and solution tank and
others is more than one third, and prepare it in a timely manner if it is insufficient.
e) Check if cooling water of every pump is smooth or not.
f) Idler running of every mechanical mixer is strictly prohibited when there is no liquid.
g) Backwash when inlet and outlet pressure difference of the activated carbon filter is more
than 0.1MPa according to the manual in the water generation manual.
7.4 Common faults, judgment and Treatment of wastewater station and wastewater system
1) Unqualified pH of water outlet of wastewater station
a) Reason: On-line PH meter fails. Treatment: Contact a thermal control person for repair. b)
Reason: Acid can not be added due to abnormal acid dosing pump. Treatment: Contact
the relevant person for repair.
c) Reason: Alkali can not be added due to abnormal alkali dosing pump. Treatment:
Contact the relevant person for repair.
d) Reason: Excessive or insufficient acid or alkali dosage. Treatment: Adjust acid or alkali
dosage.
2) Unqualified turbidity or chromaticity of water outlet of wastewater station
a) Reason: Large drainage quantity and poor quality of wastewater of desulphurization
specialty. Treatment: Dilute and circulate until water is qualified.
b) Reason: Abnormal sludge scraped from flocculation tank and clarification tank.
Treatment: Contact an electrical repairer.
c) Reason: Sludge in flocculation tank and clarification tank can not be discharged.
Treatment: Wash pipelines with industrial water and contact the relevant person for
repair.
d) Reason: The dosing pump of flocculation tank is dosed abnormally. Treatment: Adjust
dosage of coagulating agent.
e) Reason: The dosing pump of coagulant aid is dosed abnormally. Treatment: Adjust
dosage of coagulant.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 69
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Serial No.
Item
Unit
Data
Remark
8.2.1
Hydrogen generator
1) Hydrogen treatment quantity
3
8.4
2)
Working pressure
MPa
0.7
3)
Purity of outlet hydrogen %
99. 8
4)
Purity of outlet oxygen %
99.5
5) Humidity of outlet hydrogen
3 mg/m ≤0.049gH2O/N.Cu.m3
6) Temperature of outlet hydrogen
35
7) Requirements of cooling water
Cooling water quantity m3/h
2.64
PH value
≈7
Soluble solids
ppm
1
8 Hydrogen Generation Plant Operation Manual
8.1 General descriptions of hydrogen plant and hydrogen system
8.1.1 General descriptions of hydrogen generation system
The system includes auxiliary hydrogen generation and supply equipments of 4X300MW
Project of Vietnam Quang Ning Power Plant. It consists of three sets of HM water electrolysis and
hydrogen generation equipments of 8.4m3/h, three sets of medium-pressure and high-pressure
compressor systems, three sets of medium-pressure drying systems, one set of closed cooling
water device, medium-pressure cache equipment, high-pressure storage equipment, hydrogen
distribution device and auxiliary water tank, vacuumization device, nitrogen system and control
system used for blowing and cleaning.
8.1.2 Operational principle
Water will be decomposed to hydrogen and oxgyen when DC passes through potassium
hydroxide solution and its chemical reaction is as follows:
Cathode:
Anode:
Power-on:
2H2O +2e → H2↑+ 2OH-
2OH--2e → H2O + 1/2O2↑
2H2O = 2H2↑+ O2↑
In general, electrolyte used in the HM system is KOH solution whose weight ratio is 25% and
the corresponding specific gravity is 1.236(20).
8.2 Technical norms of equipments
Nm /h
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 70
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Serial No.
Item
Unit
Data
Remark
Rigidity ( Calculated by CaCO3)
ppm
1
8.2.2
Busbar
1)
Working pressure
MPa
0.7
2)
Quantity
Set
1
3)
Producer
Beijing CEC
8.2.3
Pure water tank
1)
Volume m3
0.219
2)
Outer diameter
mm
2700*1800*2270
3)
Quantity
Box
1
4)
Producer China Power New Energy Group
8.2.4
Hydrogen compressor
1) Hydrogen generation quantity
3 0.8~20
2)
Inlet pressure
MPa
1.0
3)
Outlet pressure
MPa 5.0 -15.0
4)
Working temperature
-36—50
5)
Working voltage
V(DC)
380
6)
Outline dimension
mm
550×300×700
7)
Quantity
Compressor
6
8)
Producer
Beijing Tiangao Company
8.2.5
Storage tank
1)
Type
Vertical
2)
Design pressure
MPa
15.5
3)
Working pressure
MPa
14.0
4)
Design temperature
50
5)
Working temperature
-36~50
6)
Volume m3
0.51
Nm /h
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 71
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Serial No.
Item
Unit
Data
Remark
7)
Diameter
mm
457
8)
Wall thickness
mm
22
9)
Total height
mm
3810
10)
Material
16MnR
11)
Quantity
Tank
27
12)
Producer Kaiyuan Chemical Machine Co., Ltd
8.2.6 Desalinated water & cooling device
1)
Model
CLZ-100
2) Closed cooling water flow:
T/h
10
3) Industrial cooling water flow:
T/h
25
4) Closed cooling water pressure:
MPa
0.2-0.6
5) Volume of reflux water tank:
3
1.4
6) Power:
kW
8
7)
Quantity
Set
1
m
8.3 Equipments operation
8.3.1 Startup and shutdown of hydrogen plant and hydrogen system
8.3.1.1 Startup and shutdown of hydrogen generation equipment
8.3.1.1.1 Preparation before startup of the hydrogen generator
1) Carry out hydrostatic test of 1.5MPa and airtight test of 1.0MPa for 30 minutes respectively
before startup of the inspected hydrogen generation equipment system and electrolytic tank,
and check if there is no leakage or not with soap solution; tests are qualified if there are no
bubbles and pressure drop of the pressure gauge.
2) Measure insulation degree of every part with 500V Meg-ohmmeter before startup of the
repaired the electrolytic tank and treat instantly if there is any unconformity until it is qualified.
3) Clean electrolytic tank, pure water tank, pressure adjuster, washer and separator with
condensation water and analyze water quality.
4) Check if valves and switches in all systems are flexible and pressure gauge is normal or not.
5) Prepare for sufficient nitrogen cylinders, carbon dioxide cylinders and potassium hydroxide
and potassium dichromate and so on for replacement.
6) Clean the maintenance equipments and the electrolytic tank to guarantee there is no seeper
on the ground.
7) Inject electrolyte and take inspection.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 72
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
8) Open water inlet valve of water supply pump to inject water.
8.3.1.1.2 Startup of the hydrogen generator
1) It is required to adopt equipment power and water supply during operation of the system.
2) Close the main loop breaker connected to the power supply to receive power energy, and the
programmable controller must be in operation mode.
3) Turn on control switch of the power contactor to power on two control loops of the generator
and power supply.
4) Press touch switch of “Alarm to reset” on the parking screen and then “Generator is ready” is
displayed; the system will begin to run after pressing touch switch of “startup/reset”.
5) Blow and clean the pipe valve system at the side of the generator oxygen by blowing and
cleaning with nitrogen for 30 seconds after operation of the system; the pipe valve system has
also been pre-pressed to the required pre-pressure with the development of blowing and
cleaning. When the hydrogen pressure begins to rise, the oxygen pressure will rise
correspondingly and maintain a pressure difference of 3Psi to 10Ps on the “blowing and
cleaning screen of the generator; when the hydrogen pressure reaches 20Psig (namely,
1.4kg/cm2), the pre-pressure period of 15 minutes begins and the countdown of 900 seconds
is shown on the “pre-pressure” screen.
8.3.1.1.3 Shutdown of the hydrogen generator
1) From operation to standby: Internal pressure of the system will begin to rise due to no air
supply, and air will not be generated when pressure reaches 115Psig (namely, 8.1kg/cm2). 6#
lamp on controller module of 2# slot will be off. The system will remain pressure and be in
standby status and be ready for air supply according to nees. Touch screen will display
“Generator is in standby status” of hydrogen and oxygen pressure, and air will be generated
again when internal pressure of the system drops to the rated system pressure.
2) Shutdown: Hydrogen generator will stop automatically by contacting “Generator has stopped.”;
press the pressure release switch to release pressure automatically if releasing pressure
3) Automatic shutdown and protection of the unit:
Shutdown conditions Alarm input Setting point
High temperature of KOH
High liquid level of KOH LS2
Low liquid level of KOH LS1 90 seconds
Low flow of KOH FS1 10l/min
High hydrogen pressure PT1 120Psig
Low hydrogen pressure PT1 120Psig
High oxygen pressure PT12 115Psig
Low oxygen pressure PT12 39Psig
Low differential pressure PT1-PT2 3Psig
Low pre-pressure PT1 5Psig
High temperature pressure in oxygen TC3-TC4 200 Power alarm
Low water supply resistance FQM 200Ω-cm
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 73
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
External alarm
Power failure PLC
High ambient temperature
TC4
50Low ambient temperature TC4 5 Drying circulation trouble PT3, PT4 Drying & blow-cleaning trouble PT3, PT4
8.3.1.2 Startup and shutdown of the diaphragm compressor
8.3.1.2.1 Prepare before boot-strap
1) Clean equipments;
2) Check if all valves are closed tightly or not;
3) Check if the pointer of the pressure gauge returns to “zero position” or not;
4) Check if lubricating oil in crankcase is qualified or not. Check if oil level is between the upper
and lower scribed lines of the oil leveler or not.
8.3.1.2.2 Startup
1) Open the valve of the exhaust pipe, and turn to open bypass vent pipe if there is air pressure
in the externally connected pipeline;
2) Rotate the fly wheel for several circles;
3) Start up the diaphragm compressor so that rotary speed of the crankcase can reach the rated
rotary speed, when the oil pressure in the oil cylinder will rise gradually to 3.6 MPa to 3.8
MPa;
4) Open the valve of the air inlet pipe slightly and then close the air release valve of the exhaust
pipeline quickly;
5) Operate under low load for ten minutes and then operate under full load.
8.3.1.2.2 Shutdown
1) Close valves of the air inlet or exhaust pipeline in sequence;
2) Stop the diaphragm compressor;
3) Open the air release valve of the exhaust pipes to release air pressure in every cylinder;
4) Open meter valve below oil-pressure gauge and release oil pressure in every cylinder;
5) Close all valves tightly.
Note: Diaphragm compressor can not be started or stopped frequently. In general, the interval
between shutdown and boot-strap shall be not less than 2 hours (and it can be shortened properly
if the ambient temperature is less than 10).
8.3.2 Adjustment in operation of hydrogen plant and hydrogen system
8.3.2.1. Adjustment in operation of the hydrogen generator
1) Indicator of ampere meter shall be 50A to 280A according to user demand during operation
period; the corresponding voltage shall be determined according to the specification of the
electrolytic tank and several operation factors. Voltage of the electrolytic tank shall be within
the scope of following table.
Voltage of the electrolytic tank at 250A
Specification of the electrolytic tank Voltage scope
HM 50 54-65
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 74
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
HM 100 108-125 HM 125 135-160 HM 150 162-190 HM 200 215-250
2) KOH temperature without heat exchanger (TC1) shall be within permissible KOH temperature
control scope during operation of the system. The temperature regulator shall control the
initially prepared program according to proportion so that KOH temperature can be 64.
Temperature regulator (BV1) will be opened or closed according to demand. The valve
position and temperature of electrolyte can be monitored on screen of “temperature control
valve position” which is selected from “system information” of the display.
3) Water supply system is replenished with water intermittently and supply water flows to a
storage tank periodically during the ordinary operation, as shown 3# input lamp of 1# slot and
1# and 3# output lamps of 2# slot which are all on. Water supply shall be shown by injection
image of touch display for 30 seconds. Water supply frequency depends on consumption rate
and it changes with air outlet and electrolytic rate. Water quality monitor shall indicate the
permissible green lamp for the minimum electric resistivity of 200Ω-cm.
4) Temperature rise of hydrogen in oxygen during operation of the generator and under almost full load shall be less than 20. It will increase greatly when the system is in standby mode.
Sensor of hydrogen in oxygen needs a constant oxygen flow of 100CC/min.
5) The pressure gauge of at least one drier shall be under pressure during ordinary operation.
Drier program can be monitored by pressing touch switch of “drier program” on the screen
which displays “Generator is in operation”. 4# output lamp of 6 # slot module shall be on
before switchover of drying except pre-pressure period for 30 minutes to indicate that
blow-cleaning valve of the drier is on. 2# or 3# lamp shall be on according to the program
timing to indicate that the heater of the drier is in operation.
6) Data and working days shall be assigned to the generator so that documents can verify the
daily operation data. The recorded data can provide useful information to daily maintenance
and general diagnosis of operation problems, and such information shall be recorded within
24 hours.
8.3.2.2 Adjustment in operation of the diaphragm compressor
Take the subsection and boost lifting pressure and turn to trial operation under rated
exhaust pressure gradually after normal operation without load. It is required to lift the suction
pressure in sections and then lift the exhaust pressure gradually. (Please refer to Table 2 for
details.)
Table 2
Serial No. Suction pressure, MPa Exhaust pressure, MPa Operation period, min 1 0 1.0 10 2 0.4 2.5 10 3 0.7 3.2 80 8.3.2.2.1. Operation and adjustment:
1) Inspection of oil supply pump Oil supply pump will operate normally by touching oil exit pipe manually or it is required to find
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 75
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
out reasons in Table 5. 2) Removal of gas in pressure measurement pipes in the oil cylinder
Unscrew the tightening bolt on the meter valve slightly, and screw down tightening the bolt if there are no bubbles in fluids to flow out of the oil pipe. 3) Adjustment of oil-pressure gauge of the oil cylinder
Pointer of the oil-pressure gauge of the oil cylinder shall swing slightly and the swinging scope is suggested to be between two minimum scales. Handle of the meter valve can be screwed or unscrewed for adjustment due to excessive or insufficient amplitude of the swing. 4) Lifting pressure
Boost suction or exhaust pressure in sections according to requirements in the table. Oil pressure will rise correspondingly after the exhaust pressure rises, and it shall be always
higher than the exhaust pressure by 10% to 20%. Note: Oil pressure will not decline due to effect of the check valve below, and the oil-pressure
gauge will not drop when the exhaust pressure drops, and at the time the actual valve can be gained by operation according to the above (3). 5) Thermal stable status
Operate continuously for 60 minutes when the suction or exhaust pressure can reach the rated pressure so that the machine can be in the thermal stable status to facilitate inspection and find out problems. 8.3.2.2.2. Water quality requirements of the cooling water of the diaphragm compressor are as
follows:
1) The suspended matter content of organic and mechanical sundries shall be less than
100mg/L and the oil content can be less than 5mg/L; 2) Cooling water is almost neutral. That is, PH indicator of hydrogen ion is suggested to be
between 6.5 and 9.5;
3) It has thermal stability and the temporary rigidity is less than 10°. (Note: rigidity 1° is equivalent to 10mg CaO or 7.19mg MgO in every liter of water.)
It is required to filter and purify if the water quality can not meet the above requirements. Urban drinking water is permitted to use as the cooling water. Inspect and clean the oil filter when the oil pressure is less than 0.15MPa, and then inspect
the gear pump if there is still no effect. 8.3.2.2.3. Items to be inspected itinerantly during operation as follows:
1) Check if the operation of the suction valve, exhaust valve, oil supply pump, pressure
regulation valve and gear pump and others is normal or not;
2) Check if there is leakage from the oil or air pipeline or not;
3) Check if the connecting rod bearing, copper bush, bearing and plunger and others are
overheated or not;
4) Oil temperature of the crankcase shall not exceed 70;
5) Exhaust temperature can not exceed 140,
It is required to stop for inspection instantly if there is any abnormal equipment.
8.4 Common faults, judgment and Treatment of hydrogen station and hydrogen generation
system
8.4.1 Treatment under emergent conditions
8.4.1.1 Cut off the silicon rectifier power quickly for treatment if there is any emergent condition.
1) Short-circuit, fire-fighting and fulmination of the electrolytic tank
2) The pressure of the hydrogen generation system rises rapidly and is invalid after adjustment
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 76
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3) Severe leakage of gas or alkali of hydrogen generation system
4) Severe scorched flavor and short-circuit of the silicon rectifier
5) Circulation shutdown of the electrolyte
8.4.1.2 Fire and explosion in the hydrogenation station
It is required to cut off DC and AC power supply of the silicon rectifier instantly and solve
problems if there is any emergent condition. Record the Treatment result on the operation log after
the event happens; and report it to the chemical worker and leader on duty.
8.4.2 Treatment of common troubles during operation
8.4.2.1 Unqualified purity of hydrogen and oxygen
Reason Treatment Diaphragm ruptured Severe electro corrosion which may cause
corrosion and perforation of pole plate
Overhaul the electrolytic tank if it exceeds the
overhaul term.
Large water level difference of pressure
adjuster of hydrogen and oxygen Adjust hydrogen or oxygen discharge vale to
guarantee normal water level. Too dirty electrolyte or too low concentration
of electrolyte in electrolytic tank Re-fabrication of electrolyte
Deposits in electrolytic tank Shutdown and backwashing of electrolytic tank 8.4.2.2 The maximum current of the electrolytic tank only rises to 220A.
Reason Treatment One-phase quick fuser is fused. Notify the electrical maintenance personnel to
replace quick fuser. One phase of silicon rectifier fails. Electrical maintenance personnel shall find out
trouble points and solve problems and record in
guard records. 8.4.2.3 Severe leakage of alkali and gas from the electrolytic tank
Reason Treatment Frequent startup, expansion or uneven
shrinkage Strengthen operation and supervision and
prevent alkaline liquid from splitting and hurting
people The electrolytic tank has operated for a long
time to damage leakproofness Reduce startup times and decrease load slowly
Corrosion on the surface of pole plate or
diaphragm frame Damaged insulation cushion Ruptured coil spring
Replace insulation cushion, pole plate,
diaphragm frame and coil spring and so on
during overhaul and shutdown
8.4.2.4 Sudden shutdown of electrolytic tank
Reason Treatment Power failure caused by vibration of connecting
points of mercury relay of silicon rectifier blower
Inspect silicon rectifier then start up it for
operation if there are no other troubles. Sudden power failure of the plant Contact integrated control guard for power
Date 2008-09-16
No. : QN1-SEC-G-04-TP-005
Page 77
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
supply. Trouble of silicon rectifier and protection motion Notify the electrical maintenance personnel to
solve problems. 8.4.2.5 Large temperature difference of positive and negative poles and hydrogen-oxygen outlet of
electrolytic tank
Reason Treatment Jammed filter and unsmooth circulation of acid
and alkali Clean or close inlet and outlet valves of filter
and open bypass valve for operation Jammed air outlet pipe or alkaline liquid hole of
electrolytic tank Stopping the tank for backwashing
Uneven opening of cooling water of
hydrogen-oxygen separator Check if concentration of alkaline liquid is
normal or not. Too high or low concentration of electrolyte Adjust water inlet quantity of cooling water of
hydrogen-oxygen separator. 8.4.2.6 Water tank which is full of water
Reason Treatment Misuse of water inlet valve of water tank Check if outlet valve of hydrogen pressure
regulator is closed or not and remove water in
the U-type pipe. Internal leakage of water inlet valve of the water
supply tank Close main valve of condensing water and
open water inlet valve and blowdown valve of
water tank to release partial condensing water
in the water tank. Hydrogen system pressure is more than
pressure in water tank Inspect water inlet valve if there is leakage in
the valve. 8.4.2.7. System pressure is more than pressure of hydrogen storage tank by 0.003MPa of gauge
pressure
Reason Treatment Jammed valve or pipe before hydrogen storage
tank Dredge jammed pipe valves
Frozen outdoor valve or pipe to hydrogen
storage tank Unfreeze outdoor pipe valves by steam
Jammed float connecting rod of pressure
regulator Fluctuate water level of pressure regulator for
several times Large reserve pressure of the check valve Correct and evaluate pressure difference of the
check valve again 8.4.2.8. Unbalanced water levels of hydrogen and oxygen sides before startup of electrolytic tank
Reason Treatment Leakage of hydrogen or oxygen system Find out leakage positions carefully and solve
problems.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 78
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Automatic water supply valve of water tank is
not closed tightly with internal leakage. Open automatic water supply valve again to
check if it is closed tightly or not. Take
measures to start up the electrolytic tank
normally and adjust balanced water levels of
two sides. 8.4.2.9. Variable pressure of hydrogen system during operation and noise in the hydrogen cooler
Reason Treatment Check if drainage quantity of blowdown valve
on the bottom of the hydrogen cooler exceeds
the normal scope. Check if there are bubbles in industrial water
from peephole of cooling water of cooler or not. Check if there is no noise in the cooler or not by
ears.
Stop the electrolytic tank instantly if there are
any phenomena, and release the system
pressure to 0.02MPa and replace H2 system by
N2.
The hydrogen cooler is sinked in industrial
water for severe corrosion and perforation. Detach and overhaul the hydrogen cooler and
replace the serpent-type pipe. 8.5 Special safety cautions of hydrogen generation station and hydrogen generation
system
1) Repair and maintain relevant devices and instruments of hydrogen generation station
periodically to guarantee normal operation so as to ensure that purity and humidity of
hydrogen can meet requirements.
2) Fireworks of equipments with hydrogen in and out of hydrogen supply station are strictly
prohibited. It is strictly prohibited to place inflammables and explosives. It is required to hang
an alarm board with “No smoking” and enclosure around the hydrogen storage tank (namely,
within 10m) and prepare for necessary firefighting equipments in the hydrogen supply station.
3) Irrelevant people are strictly prohibited to enter into the hydrogen supply station.
4) Fire operation or jobs with spark is strictly prohibited in the hydrogen supply station. Staff can
not wear shoes with nails. Measure hydrogen content in advance if it is required to weld or
carry out fire operation to validate that hydrogen content in the air within work area is less
than 1% and the staff can not work until examination and approval of the chief engineer.
Unfreeze pipe valves or other equipments in the hydrogen supply station by steam or hot
water and it is strictly prohibited to fire. Check if there is hydrogen leakage of every connecting
pipe or not by instruments or soap water and it is strictly prohibited to inspect by fire.
5) Partition repair part and connecting part and install a tight block plate then replace the
hydrogen by air before repair of hydrogen storage equipments (including pipe system) and
hydrogen-cooled system of generator.
6) Open valves on equipments evenly and slowly when discharging hydrogen with pressure or
dumping hydrogen to release gas slowly and it is strictly prohibited to release gas rapidly to
avoid spontaneous combustion caused by friction.
7) Erect gas bottles on the support vertically and avoid heat and direct solar radiation. Coat
white on the surface of storage tank and inspect safety valve on the hydrogen storage tank
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 79
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
periodically to guarantee excellent motion.
8) It is required to cut off electrical equipments and power instantly to release system pressure
and extinguish fire by carbon dioxide when hydrogen supply station. Extinguish fire by carbon
dioxide and caulk leakage by asbestos cloth to guarantee no hydrogen emission or preclude
gas source by other methods if fire is caused by hydrogen leakage.
9) It is strictly prohibited to use tools which may cause spark and it is suggested to use tools
which are made of copper during repair and operation of hydrogen system.
10) Hydrogen supply station shall adopt explosion-proof electrical devices.
11) Mixed hydrogen and oxygen has explosion danger and upper limit is 96% of hydrogen and
4% of oxygen and lower limit is 5% of hydrogen and 95% of oxygen.
12) It is not allowed to repair equipments in the hydrogen supply station during operation and it is
required to stop equipments then repair according to relevant manual if they must be repaired.
13) Operators are not suggested to wear work clothes which are made of synthetic fiber and wool.
14) Freshmen shall be familiar with system operation of hydrogen supply station and they can not
work individually until passing examinations.
15) Door of hydrogen supply station shall be closed constantly and operators shall submit kindling
and register before entering into the hydrogen supply station.
9. Circulating Water System & Auxiary Cooling Water System Operation Manual
9.1 Equipment Technical Specification
NUMBER
NUMBER
NAME
MODEL AND
SPECIFICATION
UNIT
1# 2#
MANUFACTURE
REMARK
CLOSED CYCLE
COOLING
WATER PUMP
MODEL NUMBER:
20SAP-10
Q=2000m3/h
H=45mH2O
SET 2 2 CHANGSHA
WATER PUMP
CO.,LTD
1
MOTOR MODEL NUMBER:
YKK4504-6
400kW 6600V
980rpm
SET 2 2 SUPPLIED
WITH
PUMP
2 CLOSED CYCLE
COOLING
WATER COOLER
MODEL NUMBER:
SJ-1530-1
HEAT EXCHANGE
AREA: 1580m2
SET 2 2 SHANGHAI
POWER
EQUIPMENT
CO.,LTD
3 CLOSED CYCLE
COOLING
WATER
EXPANSION
TANK
VOLUME: 30m3 SET 1 1 JINAN
PRESSURE
VESSEL
CO.,LTD
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 80
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
NUMBER
NUMBER
NAME
MODEL AND
SPECIFICATION
UNIT
1# 2#
MANUFACTURE
REMARK
OPEN CYCLE
WATER PUMP MODEL NUMBER:
28SAP-25
Q=3600m3/h
H=12mH2O
SET 2 2 CHANGSHA
WATER PUMP
CO.,LTD
4
MOTOR MODEL NUMBER:
Y2-355L2-10
160kW 400V
590rpm
SET 2 2 SUPPLIED
WITH
PUMP
CIRCULATING
WATER PIT
BLOWDOWN
PUMP
MODEL NUMBER:
50CYL25-8
25 m3/h 8mH2O
SET 2 2 ZHENGJIANG
CHANGKAI
MECHANICAL
EQUIPMENT
CO.,LTD
5
MOTOR MODEL NUMBER:
Y2100L2-4
3kW 400V
1450rpm
SET 2 2 SUPPLIED
WITH
PUMP
9.2 Circulating Water System
9.2.1 Inspection and Adjustment before Startup
a) Examination and repair is complete, working order form is filled; safety measures have
removed and site has cleaned completely;
b) C&I group shall be informed to apply operating power source and gauge power for
circulating water pump control panel; to check the gauges operate normally.
c) Motor insulation of circulating water pump and hydraulic control butterfly valve oil pump
are qualified; interlock protection test is qualified.
d) Open the water filling valve of cooling water manifold.
e) Open water inlet valve of condenser cooling water.
f) Open water outlet valve of condenser cooling water
g) Close outlet/inlet drain valve of condenser circulating water..
h) Open vent valve of inlet water chamber and then it shall be closed after continuous water
discharging.
i) Cooling water shall be opened to circulating water pump A&B and electromotor cooling
water inlet valve, and then to adjust the opening of valves (rubber bearing shall be filled
with water for 20mins washing in the first startup).
j) To adjust lube cooling water pressure of circulating water pump A&B until achieving
normal condition.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 81
Rev.: A
k) Lube oil level and quality of Motor bearing of circulating water pump A&B is normal with oil temperature not less than 15; oil level of hydraulic control butterfly valve shall be at
1/2~1/3,
l) Interlock switching of circulating water pump set at “CUTTOFF” position, and then power
supply will be provided to circulating water pump. Circulating water pump protection shall
be put into service.
9.2.2 Startup of Circulating Water Pump
a) Operate rotary filter screen continuously, pressure difference before/after filter screen
shall be <100mm.
b) Circulating pump is provided with startup condition.
c) Press “SEQUENCE STARTUP” button of circulating water pump.
d) Hydraulic control butterfly valve at the outlet is opening gradually, and then circulating
water pump starts up when the valve opens to 15º.
e) Hydraulic control butterfly valve at the outlet opens keep opening and will be fully open in
25s.
f) Current, circulating water manifold pressure and pump and electromotor bearing of
circulating water pump are normal;
g) When the pressure difference before/after rotary filter screen is <100mm, then filter
screen can be shutdown if no sundries being filtered off.
9.2.3 Circulating Water Pump Shutdown
a) Press “SEQUENCE STARTUP” button of circulating water pump
b) Hydraulic control butterfly valve at the outlet is closing gradually, and then circulating
water pump shutdown when the valve closes to 15º.
c) Hydraulic control butterfly valve at the outlet opens keep closing without circulating water
pump inversion.
d) Idle circulating water pump will be on standby or maintained according to the actual
situation.
9.2.4 Circulating Water Pump Shifting
a) Standby circulating water is provided with startup condition.
b) Startup standby circulating water pump according to startup sequence of circulating water
pump; attention shall be paid to the pressure changing of circulating manifold.
c) Standby pump starts normally;
d) Operating pump shall be stopped according to the shutdown sequence of circulating
water pump; attention shall be paid to the pressure changing of circulating manifold;
pump shall not operate inversely after shutdown.
e) Idle circulating water pump will be on standby or maintained according to the actual
situation.
9.2.5 Operating Maintenance of Circulating Water Pump
a) Pump current and water outlet pressure is normal during operating.
b) Lube oil level of from bearing on the circulating water pump Motor is at 1/2-2/3; oil quality
and cooling water flux is normal;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 82
Rev.: A
c) Water level difference before/after filter screen of cleaning machine shall be less than
400mm.
d) Bearing temperature of running circulating water pump electromotor shall not be higher
than 70(alarm warning at 70, protection will act at 80); thrust bush temperature
shall not be higher than 75(alarm warning at 95); winding temperature of Motor
stator winding shall not be higher than 80(alarm warning at 110 and protection will
act at 120)
e) Upper and lower shaft vibration of running circulating water pump Motor shall not be
larger than 0.06mm.
f) Adjustment shall be carried out when the cooling water pressure decreases to 0.1MPa.
9.2.6 Startup and Shutdown of Rotary Filter Screen
a) All gauges completed and power is available normally;
b) Lube oil quality of lube components is qualified; lube level is normal;
c) Tightness degree of chain is appropriate, main axis is level;
d) Alarm device is available;
e) Rotary filter screen shall be accepted by manual inching test and no-load test before
operation.
f) Auto startup of rotary filter screen
1) Flushing water pump will startup automatically when the water level difference
before/after the filter screen achieved 100mm(adjustable); to open motorized valve of
flushing water, the rotary filter screen will startup automatically after 10s(adjustable)
2) Rotary filter screen will be shut down after 15mins (adjustable) continuous flushing
and the water level difference before/after the rotary filter screen lower than 50mm;
and then close to close motorized valve of flushing water, finally to shutdown flushing
water pump.
3) If the water level difference is still more then 50mm within the specified 15 mins
flushing time, the flushing will be go on until the water level difference before/after the
rotary filter screen lower than 50mm.Meanwhile, alarm signal will be sent to the
shifting room(or control room).
4) If the water source is clean which results in the water level difference before/after filter
screen cannot achieves 100mm, rotary filter screen and flushing water pump will be
operated 15min(adjustable) automatically each 8 hours; 1-1.5 rounds will be applied
to each operation flushing.
5) Alarm signal will be sent to control room immediately when the water level
before/after filter screen achieves or more than 400mm.
g) Rotary Filter Screen Startup in Manual Way:
1) When the rotary filter screen fails to operate, manual running will be applied; manual
running shall be carried out twice during each shift according to the start up sequence
of: flush pump – electric valve – filter screen, shutdown will base on the sequence of
filter screen – electric valve – flush pump;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 83
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
2) Manual way will apply when the rotary filter screen meet the startup condition with
large filter screen differential pressure;
3) Flushing water pump starts up by opening the outlet manual valve and the electric
valve of corresponding rotary filter screen water source; pump outlet pressure is
0.3~0.5 MPa;
4) Switching sets at manual position, then startup rotary filter screen to check if the
rotation parts is operating normally; attention shall be paid to the operating sound and
vibration as well as heating of each parts; relevant flushing water will be provided and
drained to sewer tunnel outlet;
5) Rotary filter screen operates stably without blockage and serious twist;
6) Sewage in the cleaning groove shall be removed by flushing water.
h) Rotary Filter Screen Shutdown:
1) Rotary filter screen can be shutdown when the pressure difference is small;
2) Cutoff the power for Motor, power gauge shown “zero”;
3) Rotary filter screen stops operating without abnormity;
4) Shutdown flush pump.
i) Operating Maintenance of Rotary Filter Screen
1) Sewage cleaning shall be carried out in time according to the original water; sewage
cleaning shall be strengthen continuously; for the cleaning water source, filter screen
shall be runned 1-1.5 round in each 8 hours;
2) Nozzel shall be checked and cleaned termly to improve cleaning quality;
3) Safety device shall be inspected frequently to ensre safety operation;
4) According to the alarm signal for chain loosening, chain shall be calibrated in time;
5) Inspection and repair shall be carried out if the chain or screen plate being blocked
during operating;
9.2.7 Condenser Rubber Ball Cleaning System
a) Ensure circulating water system and outlet siphon are normal, and outlet/inlet water valve
of condenser is open;
b) Ensure the differential pressure before/after ball collector is normal, then operator
records the vacuum, TTD/DCA and temperature increasing of condenser;
c) Check the rotor plate of rubber ball cleaning pump to ensure normal bearing oil level and
quality.
d) Overall inspection of condenser;
e) Rubber collector A&B set at ball collecting position;
f) Add 700 balls with φ29 into ball chamber A&B respectively;
g) Open water inlet/outlet valve of rubber ball pump, water outlet valve and vent valve of ball
chamber;
h) Apply rubber ball cleaning procedure and startup rubber ball pump; vent valve of ball
chamber will be closed automatically after water drain off;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 84
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
i) Water outlet valve of ball chamber shall be opened adequately and screen plate of ball
chamber shall be opened; rubber balls shall be checked to ensure they are into main
system completely;
j) Screen plate of ball chamber sets at “balls collecting” position after 24 hours operation;
balls collecting time will be 30 mins;
k) Close outlet valve of rubber ball pump, and then shutdown the pump and the water outlet
valve of ball chamber;
l) Water drain and vent valve of ball chamber will be opened for water drain and pressure
releasing; hand hole will be opened to count the rubber after complete water draining;
ball return rate shall be more than 95%;
m) Ball collector on water outlet pipe of circulating water shall set at “FLUSHING” position
after cleaning according to the real situation.
9.2.7.1 Condenser Isolation Cleaning and Leakage Checking (Half)
a) Ball cleaning device of the part to be shutdown shall finish ball collecting, balls stop
running, then ball cleaning procedure will be exited; meanwhile power for rubber ball
pump will be cut of;
b) Shifting engineer is informed to loading down below 75% according to the unit vacuum
situation;
c) Water inlet/outlet of condenser circulating water operated side shall be opened properly;
d) Close isolation valve from shutdown side to vacuum pump inlet;
e) Close condenser exhaust vacuum isolation valve of shutdown side;
f) Close inlet/outlet valve of condenser shutdown side and to open drain valves on
inlet/outlet pipe;
g) Vent valve of condenser shutdown side shall be opened adequately to destroy its outlet
siphoning;
h) Drain valve of condenser shutdown side water chamber shall be opened for water drain
and pressure releasing;
i) Cutoff the power for the following devices:
1) condenser pump inlet/outlet electric valves
2) Rubber ball pump.
3) Electric inlet/outlet valve of rubber ball pump.
j) After water pressure decreased to zero, manhole of shutdown side shall be opened
slowly for cleaning and leakage checking; condenser vacuum shall be checking during
isolation procedure, If vacuum drops, operation shall be stopped immediately to recover
the vacuum;
9.2.8 Condenser Recovery after Isolation Cleaning.
a) Condenser overhaul is complete; personnel leave site complete, tools and waste are
removed completely; holes and valves are closed, and then power shall be provided to
the following devices:
1) Inlet/outlet electric valves of condensers.
2) Rubber ball pump.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 85
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3) Rubber ball pump inlet/outlet electric valve.
b) Close all drain valves of condensate circulating water.
c) Circulating water outlet valve opens 10%
d) Open condenser water inlet valve gradually;
e) Vent valve on circulating water inlet/outlet pipes shall be closed after water is drain off;
f) Open electric valve of circulating water outlet gradually;
g) Water outlet valve on two sides of condenser circulating water shall be adjusted to
ensure average water temperature;
h) Condenser vacuum valve of shutdown side shall be opened slowly to adequate opening
after water side of condenser circulating water working normally;
i) Open water inlet valve of water chamber vacuum pump; to open the isolation valve form
reported water chamber to inlet of water chamber vacuum pump according to the actual
need;
j) Unit load will be recovered according to the condenser vacuum if necessary, or to carry
out cleaning of the other side;
k) Condenser rubber cleaning device procedure can be applied according to the actual
need.
9.2.9 9.2.9 chlorine feeding system of circulating water
9.2.9.1 Adjusting the Dosing Flow
9.2.9.1.1 Increasing the dosing flow
a) Open the flap
b) Turn hand wheel slowly to the left
c) Close the flap
9.2.9.1.2 Decreasing the dosing flow
a) Open the flap
b) Turn hand wheel slowly to the right
c) Close the flap
9.2.9.2 Switching between Automatic and Manual Adjusting of the Dosing Flow
9.2.9.2.1 Switching from manual to automatic adjusting of the dosing flow
a) Open the flap
b) Turn hand wheel totally to the right
c) Press hand wheel upwards until upper limit is reached
d) Close the flap
9.2.9.2.2 Switching from automatic to manual adjusting of the dosing flow
a) Open the flap
b) Pull hand wheel down
c) Close the flap
9.2.9.3 Switching on
9.2.9.3.1 Close rate valve
9.2.9.3.2 Close shut-off valve at the injection unit
9.2.9.3.3 Open motive water valves
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 86
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
9.2.9.3.4Switch on booster pump
9.2.9.3.5 Open valve of the gas container
9.2.9.3.6 Slowly open the rate valve until the desired gas flow is displayed by the measuring tube
9.2.9.4 Switching off
9.2.9.4.1 Emergency Stop
a) Put on safety equipment!
b) Immediately close all container valves
c) Let the plant run until all parts are evacuated from the dosing medium
d) Swith off the plant as described in the following
9.2.9.4.2 Short-term Stop(up to 6 hours)
a) Close rate valve
b) Switch off booster pump
c) Close motive water valves
d) Close shut-off valve at the injection unit
9.2.9.4.3 Long-term Stop While the plant is still running:
a) Close all container valves
b) Let the plant run until the measuring tube shows no more gas flow
c) Close rate valve
d) Switch off booster pump
e) Close motive water valves
f) Close shut-off valve at the injection unit
9.3 Auxilary Cooling Water System
9.3.1 Open Cooling Water System
9.3.1.1 Startup of Open Circulating Cooling Water Pump
a) Inspection and repair for opened cooling water system have completed; working order
form is finished; safety measures is removed; Construction site is cleaning; C&I
instrument are complete, instruction valves are open. Oil level of bearing shall be at
1/2-2/3 with normal quality.
b) Confirm that the circulating water system operates normally.
c) Clean the filter screen of opened circulating cooling watr , and then to close the drain
valve.
d) Open water inlet valve of opened circulating cooling water pump.
e) The vent valve of open circulating cooling water pump shall be opened, and then it shall
be closed after air exhausting completely.
f) Open water outlet valve of opened circulating cooling water pump.
g) Open the inlet/outlet valve of closed water heat exchanger which to be started (two sets
operating and one set standby in total 3 heater exchangers A, B and C); to open water
side vent valve of closed water heat exchanger, and then it shall be closed after water
drain off continuously.
h) Power will be supplied to opened circulating cooling water pump after insulation of Motor
is qualified; Motor power shall be provided to the test position for the first startup after
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 87
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
overhaul, and switch static open/close test is accepted; Motor operates normally without
coupling.
i) Close outlet valve of opened pump and the cooling water control switch; if water pump
and Motor operate in good condition, outlet valve of open circulating water will be
opened.
j) Bypass electric valve shall be opened before opened circulating cooling water pump
shutdown.
9.3.1.2 Shutdown of opened circulating cooling water pump
a) Bypass operates in good condition
b) Close outlet valve of open circulating cooling water pump slowly, and then open
circulating cooling water pump shall be shutdown if the closed heat exchanger operates
normally.
c) If opened circulating cooling water pump need to be shutdown or bypass need to be
closed, the system shall be checked to ensure that no system users operate.
9.3.1.3 Operation Maintenance of Open Circulating Cooling Water Pump
a) Current and outlet water pressure of operating pump are normal.
b) Motor, bearing temperature and gland water return shall be normal;
c) Operating pump and Motor bearing vibration shall be normal;
d) No alarm warning for pressure difference of opened circulating water filter screen; filter
screen shall be cleaned termly according to the working requirement;
e) When opened circulating water pump tripped or pressure decreased to 0.18MPa, bypass
operation shall be adjusted to ensure normal working condition for closed circulating
water heat exchanger. In the normal operation, a group of device will be standby while
the other group puts into service.
9.3.2 Closed Cooling Water System
9.3.2.1 Startup of Closed Circulating Cooling Water Pump
a) Inspection and repair have completed; working order form is finished; safety measures is
removed; Construction site is cleaning; C&I marks is complete, instruction valves are
open; the inlet/outlet valve of Motor cooler shall be closed if no pressure in the Motor.
b) to open the isolation valve form condensate transferpump to closed expansion water tank,
to close inlet valve of closed water pump; drain valve shall be opened to wash the
expansion water tank, and then water level of expansion water tank shall be filled to the
overflow pipe after water is qualified, and then to closed the tank. Condensate is
accepted to apply in the above procedure, but condensate shall not used as make-up
water during normal operation to avoid water quality affected by different water.
c) Vent valve after closed circulating water outlet valve shall be closed after water is
draining off continuously.
d) Open the water inlet valve of closed cooling water pump A&B
e) to open the van valve of closed circulating water pump A &B, and then close after air
exhausting completely; pressure difference before/after closed pump inlet filter is normal;
f) Open water outlet valve of closed cooling water pump A&B.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 88
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
g) Sampling valve before water outlet valve of closed cooling water pump A&B shall be
closed.
h) Open closed inlet/outlet valve, pressure governor valve and front/back electric butterfly
valve of two heat exchangers; close drain valve and vent valve.
i) At least a group of cooler is put into service.
j) Power will be supplied to opened circulating cooling water pump after insulation of Motor
is qualified; Motor power shall be provided to the test position for the first startup after
overhaul, and switch static open/close test and interlock loop test is accepted; Motor
operates normally without coupling.
k) Controlling switch of closed circulating water pump shall be closed to check if the water
pump and Motor operate normally.
l) Standby pump interlock shall be set at “INPUT” position.
9.3.2.2 Shutdown of Closed Cooling Water Pump
a) Shifting engineer, shifting personnel of Chemical, FGD and boiler group shall be informed
before closed circulating pump shutdown.
b) Interlock of standby closed circulating cooling water pump shall be cutoff.
c) Closed circulating cooling water pump shutdown without inversion operation, or the water
outlet valve of inversed operate water pump shall be closed immediately; startup is
forbidden when water pump is inversion operating to avoid equipment damage.
d) If both the closed circulating cooling water pumps need to be shutdown, the system shall
be checked to ensure that no any user; if cooling water is required by chemical and FGD,
it shall be provided from adjacent units.
9.3.2.3 Closed Heat Exchanger Shifting (e.g.: Operation changed from A to B)
a) Closed water pressure, water level of water tank shall be recorded and shifting engineer
shall be informed before closed heat exchanger shifting;
b) Close bottom water drain valve of closed heat exchanger B;
c) Open water inlet valve of closed heat exchanger B slightly for water filling.
d) Vent valve of closed heat exchanger B opens slightly, and it shall be closed when water
comes out.
e) Water inlet valve of closed heat exchanger B opens slowly to observe water level
changing of closed water tank.
f) Open cooling water inlet valve of closed heat exchanger B.
g) Cooling water side vent valve of closed heat exchanger B is closed.
h) Cooling water side drain valve of closed heat exchanger B is closed.
i) Open cooling water outlet valve of closed heat exchanger B.
j) Water outlet valve of closed heat exchanger B shall be opened slowly and attention shall
be paid to the closed water pressure changing.
k) Cooling water outlet vale of closed heat exchanger B shall be adjusted to maintain the temperature of closed water less than 38.
l) Water inlet valve of closed heat exchanger A shall be closed slowly and attention shall be
paid to the changing of closed water pressure.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 89
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
m) Close water outlet valve of closed heat exchanger A.
n) Close cooling water inlet valve of closed heat exchanger A. o)
Close cooling water outlet valve of closed heat exchanger A.
p) Open the cooling water drain valve on two ends of closed heat exchanger A.
q) Shifting engineer inform chemical group to test the hardness of closed water.
r) To record the shifting time of closed heat exchanger.
9.3.2.4 Operation Maintenance of Closed Circulating Cooling Water Pump
a) Water level of expansion water tank is normal; water level adjustment system of
expansion water tank shall put into service.
b) Outlet pressure of operating pump shall not be less than 0.5MPa.
c) Operating pump current and outlet water pressure are normal.
d) Motor and bearing temperature of operating pump is normal;
e) Motor and bearing vibration of operating pump is normal;
f) When closed circulating cooling water pump trips or manifold pressure of closed
circulating cooling water decreased to 0.3MPa, standby closed circulating cooling water
pump will startup automatically and alarm warning;
g) When water level of water tank achieves 1800mm, High water level switch will act to
alarm at control room; when water level of water tank decreased to 1500mm, low water
level switch will act to alarm, meanwhile, water makeup governor valve of expansion
water tank will be fully open; when water level of water tank decreased to 500, LL water
level switch will act to alarm in the control room.
h) After closed cooling water pump trips, and standby cooling water pump fails to act in 3
secs. Shutdown protection pump will startup automatically; water source of shutdown
protection pump is induced from condensate storage tank; attention shall be pay to the
water level, if shutdown protection pump fails to startup or trips automatically after startup,
manual cooling water inlet valve from expansion water tank and boiler-water circulating
pump. Meanwhile, attention shall be paid to other temperature changing.
10 ESP System & Deslagging and Ash Handing System Operation Manual
10.1Scope
The standard provides for the principles, methods and steps of startup, stop, operation and
maintenance, control and adjustment, maintenance, trouble removal and others of gas
electrostatic precipitator (ESP), deslagging and ash removal system in Vietnam Quang Ninh
Thermal Power Co., Ltd. 2 × 300MW generating units. Personnel at all levels engaging in ESP and
ash system operation, equipment maintenance and production technology management of
Vietnam Quang Ninh Thermal Power Co., Ltd. 2 × 300MW generating units must be familiar with
all or relevant parts of the standard and strictly implement them.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 90
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.2 Specific quoting documents
The provisions contained in the following standards and adopted by the manual are the
provisions of the manual. When the manual is promulgated, all the shown standards are valid. All
the standards will be revised, and all parties using the manual should explore the possibility of
using the following standards with the latest versions and their latest versions apply to the manual.
S/N Symbol of standard Name of Standard 01
No. 277 electricity safety
(1994) Rules of work of electric job security(thermal-mechanical
part) 02
DL408-91
Rules of work of electric job security (Power plant and substation electrical part)
03
Technical agreements and equipment data of Quang Ninh
Power Plant 10.3Principal specification of system
10.3.1 Overview
Vietnam Quang Ninh Thermal Power Co., Ltd. 2 × 300MW generating units are provided with
double-arched W flame single hearth and one-time middle reheating, forced circulation and
sub-critical steam drum furnace. Solid deslagging method is used and ash residue at the furnace
bottom is discharged to a residue slurry tank via slag crusher and hydraulic ejector. ESP uses
double-room four-electric-field electrostatic precipitator and negative pressure ash removal system.
The fly ash collected from the air heater, economizer and ESP is delivered to large ash silos (the
volume of each of two ash silos is 2500 m3), and dry ash is further mixed through ash
and water and sent to the residue slurry tank, and then is transported to the ash yard by mortar
pump (meanwhile dry ash retains the way of comprehensive utilization).
Each generating unit consists of two negative pressure delivery subsystems. Four separate
subsystems (1A, 1B, 2A and 2B) can at the same time automatically (or manually) run and sent
out the ash in their respective ESP ash buckets, economizer ash bucket and air preheater bucket
through the negative pressure fan. The production systems of three negative pressure fans of
each generating unit run the necessary vacuum, of which two run and the other one is for standby.
The two ash silos can at the same time receive ash from four transportation subsystems. Four
subsystems include their respective independent and specialized pipeline and respective ash silos,
and each generating unit contains two pipelines.
ESP ash bucket is provided with a gasification system, which transports continuous and
stable compressed air provided by the ash bucket gasification fan and heated to the ESP ash
bucket, enabling ash in the ash bucket to remain dry and flow, so that ash in the ash bucket can
smoothly flow to the pipeline while the fly ash system is running.
The dust collection equipment is installed on the top of the ash silo and includes 2 sets of bag
filter dust collectors, each of which is equipped with two gas lock valves. The bag filter dust
collector includes an automatic injection bag filter attached with relevant instruments. The bag
filter can filter fly ash and prevent dust from entering into the negative pressure fan.
The ash collected in the bag collectors in the role of their own gravity goes into the ash silos
through four air lock valves (each ash collector is equipped with two air lock valves). The air lock
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 91
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
valve is used to ensure the fly ash falls smoothly into the ash silos but the system in operation will
not be interrupted. Ash is temporarily stored in the ash silos until fly ash is discharged and finally
handled through the unloading devices.
A ventilation filter is arranged on top of each fly ash silo. Air is replaced out when the system
runs and the ash silos discharge ash is filtered and then discharged into the atmosphere by the
ventilation filter.
Each fly ash silo is equipped with an air chute. The air chute can evenly distribute the
gasification air in the silo and cause ash to flow toward the discharge mouth. Gasification air is
from three sets of ash silo gasification fans and is heated by air circulation heater installed on the
gasification pipeline to make the gasification air keep dry. The ash silo gasification device is
designed to the continuous operation mode.
10.3.2 Technical specification of major equipment
10.3.2.1 Electrostatic precipitator
1 Model 2
Quantity
Set / furnace
2
3 Distance between
the same poles mm
450/400
4 Number of channel PCS 2×21/2×24 5 Number of electric
field PCS
4
6 Height of electric
field m
15
7 Type of anode
plate
480C
8 Length of electric
field m 4.55(Single electric field)
9
Type of cathode
wires
BS Barbed Wires of the first and second electric field;
high chrome high nickel stainless steel spiral line of the
third and fourth electric field 10 Cathode vibration
type
Lateral transmission vibration
12 Anion vibration
type
Lateral transmission vibration D of the top transmission
13 Groove type polar
plate system Set/set
14 Electric field wind
speed m/s
15 Number of ash
buckets pcs/electric
field
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 92
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
16 Number of power
supply regions pcs/electric
field
17 Design pressure Pa 18 Body resistance Pa 19 efficiency of dust
collection %
20 Manufacturer Shanghai Metallurgical Mining Machinery Plant 1 Model/specification GGAJ02—1.2A/72kV 2 Quantity set/set 3 3 AC input voltage V 380 4 AC input current A 271 5 AC input power kVA 6 DC output voltage kV 72 7 DC output current A 1.2 8 DC output power kW 9
Rectifier system Single-phase full-wave bridge type, negative
high-pressure output 10 Cooling pattern 11 Manufacturer Fujian Longking Environmental Protection Co.Ltd.
1
Girder electric
heater
2
Ceramics axis
electric heater
3
Ash bucket electric
heater
4
Ash bucket level
gage
10.3.2.2 Negative pressure fan
S/N
Item name
Unit
Design data
1 Model BK9020 2 Maximum
working
pressure
kpa
-49
3 Flow m3/min 69 4 Quantity Set 3 5 Motor model QA280M4A 6 Motor power kW 90 7 Rated current A 8 Rated voltage V 400
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 93
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
9 Manufacturer China Diamond Power Machine (Hubei) Co. Inc. 10.3.2.3 Combination bag type ash collector
S/N
Item name
Unit
Design data
1 Model DMD250 2 Filter area m2 90 3 Efficiency of
dust collection %
99.95
9 Manufacturer China Diamond Power Machine (Hubei) Co. Inc. 10.4Startup, operation and maintenance and stop of ESP system
10.4.1 Interlocking and Protection
10.4.1.1 If the security interlocking key of the ESP is disconnected, the silicon rectifier transformer
of the corresponding electric field can not be put into operation; when the ESP runs, if the
interlocking key is disconnected, the silicon rectifier transformer of the corresponding electric
field will trip.
10.4.1.2 If the lock switch of the switch cabinet valve of the silicon rectifier transformer is
disconnected, the silicon rectifier transformer of the corresponding electric field can not be
put into operation; when the ESP runs, if the lock switch is disconnected, the silicon rectifier
transformer of the corresponding electric field will trip.
10.4.1.3 Silicon rectifier transformer is provided with gas protection: light gas alarm and heavy gas
tripping.
10.4.1.4 Silicon rectifier transformer is provided with the oil temperature protection, and it will alarm if the oil temperature is more than 80 (ambient temperature +30 to 40 ) and it will
trip if the oil temperature is more than 85 (as is commissioned and set on the site). Alarm
oil temperature signal is in parallel connected with light gas signal and tripping oil
temperature signal is in parallel connected with heavy gas signal.
10.4.1.5 Silicon rectifier transformer is provided with input over-current, load open circuit, load
short circuit, SCR short circuit, SCR open circuit and partial excition protection.
10.4.2 Preparation and inspection of pre-operation
10.4.2.1 ESP body and relevant electrical parts are all repaired, all components fully inspected
are qualified, the inside is clean without person, debris and others, manholes are closed
and locked tightly, mechanical and electrical work sheets are ended, and the idle load
pressure build-up test is qualified.
10.4.2.2 All the equipment parts are complete, equipment signs are clear and correct, all
manholes are sealed well, heating devices of girders, insulators and ohters are intact, and
each part provides complete thermal insulation.
10.4.2.3 All the temporary grounding wires inside the electric field are disassembled and the ESP
body is grounded well.
10.4.2.4 The grounding resistance of the ESP body should be no more than 1Ω, and the shells of
all electric field, low-voltage distribution devices, control cabinets and motors as well as
high-voltage isolation switch grounding ends and others must be reliably grounded.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 94
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.4.2.5 The motor connections of all the rotating equipment are correct firm with complete
appearance, and the direction is right after commissioning; the local switch is at the
“cabinet” posiiton and the power switch in the control cabinet is closed.
10.4.2.6 The oil of all the rotating equipment (including reducers) is qualified, the oil level is
normal, there is no oil leakage, the protection covers are intact, the arming pins are firmly
connected, and the transmission mechanisms do not fall off..
10.4.2.7 The rectifier transformers have no oil infiltration or leakage, the oil is qualified, the oil
level is normal, the silica gel inside the respirator is blue, high and low-voltage cables are
not damaged, high-voltage cable joints have no flashover traces, and the grounding wires of
transformer shells are complete and firmly.
10.4.2.8 The isolation switch of the rectifier transformer is at the closing position of “electric field”
and contacts well, cabinet valves are well locked, insulation porcelain pieces are clean
without crack and discharge traces, and damping resistors do not fall off and fracture; ash
bucket ;evel switches, insulators, porcelain axis electric heaters and their temperature
measurement devices are installed firmly and connections are intact.
10.4.2.9 The switches of high-voltage control cabinets and low-voltage control cabinets as well as
meters are complete and integral, all brakes are operated flexibly, indicaiton locations are
correct, connections do not fall off, and the power supply of low-voltage busbar at the PC
section is turned on.
10.4.2.10 The security interlocking cabinet keys inside the low-voltage cabinets are complete and
are placed to “Turn-on”, the low-voltage power switch and the power control switch of the
control cabinet are closed, the “control the power switch” button on each control cabinet
panel is pressed, and then the low-voltage power and power control indicator lights on the
panel are on. (Operate intelligent monitoring instruments of control cabinets in No. 3 to 6
generating units: close the power supply of all electric field intelligent monitoring
instruments, and the intelligent monitoring instruments after completion of their
self-inspection should show “CCCC”; check whehter all parameters of the intelligent
monitoring instruments are set up correctly, and “sparks setting” operation mode under
normal circumstances should be used in the high-voltage electic field.)
10.4.2.11 The insulation resistance of high-voltage coil, rectifier component and high-voltage
ceramic casing in the high-voltage electic field. tested with 2500V megohm meter is no less
than 1000MΩ, the insulation resistance of the electric field is no less than 500MΩ; the
insulation resistance of the vibration motor, electric heater and their cables (380V and
below electrical equipment) tested with 500V megohm meter is no less than 0.5MΩ, and
the insulation resistance of the low-voltage coils and low-voltage ceramic casing of the
silicon rectifier transformer is no less than 300MΩ.
10.4.2.12 The dust removal transformer and dust removal PC section operate normally.
10.4.2.13 The fly ash system is in the standby status, ash bucket electric heater, ash bucket
gasification fan and ash bucket level meter all can work properly.
10.4.2.14 ESP stairs and platform are solid and clean, with adequate lighting and complete fire
prevention facilities.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 95
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.4.2.15 The upper PC of the system operation control is normally put into operation.
10.4.2.16 All the remote monitoring equipment (meters) are intact, the measured values are
correct and the alarm system is intact.
10.4.3 Commissioning and operation of the ESP
10.4.3.1 The ESP operates in priority in the PC and can also be operated on the control cabinet
on the site, and the switch of the on-site control cabinet is placed at the “on-site” position in
the implementation process of the on-site operations of the on-site control cabinet.
10.4.3.2 Close the switches of the power supply and the control power supply inside the
high-voltage control cabinet and low-voltage control cabinet, and the power switches of
electric heater and vibration motor inside the low-voltage cabinet, and th indicator lights
show correctly without warning and it is confirmed that all the set parameters are right.
10.4.3.3 Before the boiler is ignited, ceramics axis, insulator (porcelain sleeve), girder, ash bucket
and others are input for heating in 12 to 24 hours (18 to 24 hours optional in the rainy
season mostly and 12 to 18 hours optional in the dry season), and the electrostatic
precipitator body and the ash bucket are preheated.
10.4.3.4 Before the boiler is ignited, input all the electric field ash bucket gasification fans in 2 to 4
hours, and put the vibration motor into operation in 1 to 0.5 hours.
10.4.3.5 After the boiler with coal dust input operates stably (usually, there are two sets of milling
systems of the boiler in operation, there are not more than four oil guns for fuel, and the inlet
gas temperature of the ESP under normal circumstances should be more than 110 and
the minimum should be not less than 95), the leader on duty notices the ESP to be put
into operation. When operating the on-site control cabinet, press the “Reset” button, and
then press the Startup button to commission and operate the high-voltage electric field (the
electric field is input in order according to the inverse direction of flue gas flow direction, and
300MW generating unit ESP is first input into Ⅳ electric field and then into Ⅲ , Ⅱ , Ⅰ electric field). If there is still oil gun in operation in the boiler burning, boost in the “Manual”
mode, and adjust the secondary voltage to 40kV in operation; after the withdrawal of all oil
guns for the boiler burning, the secondary voltage is adjusted to the normal best state and
the operation switch is set to “Automatic” position. After each field is put into operation, a
period of time to observe and stability (5 to 10 minutes) should be provided, to verify
whether their work is normal, and the problems found should be timely examined, analyzed
and treated.
10.4.3.6 Adjust the operating mode and setting values of high-voltage parameters according to
the secondary voltage and current value, the operating conditions of the boiler and load of
the generating unit .
10.4.4 Stop the ESP
10.4.4.1 While the boiler stops, after the oil gun is put into operation, when the exhaust gas
temperature drops to below 100 , the operation of high voltage electric field can be
gradually cease.
10.4.4.2 After stopping the ESP upon the command of the leader on duty, start to stop the
high-voltage electric field, and operate in priority the upper PC and also operate the on-site
control cabinet.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 96
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.4.4.3 When stopping the high-voltage electric field in the inverse direction of flue gas flow
likewise, that is, start with the last electric field in series to stop it. In the process of stopping,
adjust first the secondary voltage and current to the minimum, and then stop it.
10.4.4.4 When stopping on the on-site control cabinet, adjust first the secondary voltage and
current to the minimum, press “Reset” button on the control panel and then press the
“Shutdown” button.
10.4.4.5 Shut off the main circuit switch of the high-voltage control cabinet.
10.4.4.6 Under normal circumstances, after the high-voltage field stops, maintain the vibration
device to continue to operate for four to eight hours and then stop it.
10.4.4.7 If the boiler stops in two days and the ESP is not repaired, the girder, cermics axis and
other heating devices will not stop. If they need to be disabled due to maintenance or other
inspections, testing and so on, stop them according to the normal stop operation and take
the power outage and other related security measures.
10.4.4.8 If the boiler has stopped for more than two days, the heating device should be suspended
and the power switches and the control power switches and others of all branches of the
low-voltage cabinet are disconnected.
10.4.5 Inspection in operation and contents of maintenance
10.4.5.1 The vibration device is installed firmly and its anchor bolts are not loose; the motor is in
normal operation, turns correctly and has no abnormal sound; the motor surface temperature
can not exceed the ambient temperature 45, its vibration is no more than 0.08mm, and the
fan is in normal operation; the maximum motor bearing temperature is not allowed to be
more than the ambient temperature 45 ; the reducer lubricates well, with adequate
lubricant, and no oil permeability exists on all vent caps and oil discharge mouthes.
10.4.5.2 The arming pins of the transmission mechanism are intact, shift forks are not fractured,
and the vibration sound inside the ESP is normal.
10.4.5.3 Each manhole of ESP body, insulator room valve and vibration axis penetration body
should be closed and seamless, and the ash bucket outputs ash normally.
10.4.5.4 Check that the on-site control cabinet of the vibration motor is normal and under
emergency circumstances, stop the vibration motor through the on-site cabinet control
switch.
10.4.5.5 After the anode vibration motor stops, the corresponding electric field continues to run for
a peirod time that should not exceed 24h.
10.4.5.6 After the cathode vibration motor stops, when the secondary current is less than 100mA,
it should be suspended, and the corresponding electric field continues to run for a peirod
time that should not exceed seven days.
10.4.5.7 The oil level of the high-voltage silicon rectifier transformer is one second to two thirds,
and oil is transparent without debris and oil leakage; the transformer has no abnormal sound
and smell, no abnormal increase in oil temperature occurs, silica gel inside the respirator is
blue, the isolation brake is in the electric field, the red indicator light is on, and the ceramic
casing has no climbing electricity and discharge phenomenon.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 97
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.4.5.8 The primary and secondary voltage and current of the high-voltage cabinet should be
lower than the rated values, otherwise they should be adjusted or the reasons are identified
and eliminated.
10.4.5.9 The operating indicator light of the high-voltage cabinet control panel is on, with no fault
alarm, and the cooling fan of the high-voltage cabinet SCR operates normally.
10.4.5.10 The vibration motor of the low-voltage cabinet and electric heater have no fault alarm,
and the displayed temperature value of the electric heater is in the set scope.
4.5.11 There is no abnormal sound, smell and smoke phenomena in the cabinet, each meter and
indicator right show normally, the switch position is correct, and the cabinet valve is locked.
10.4.6 Operation of ESP and Attentions to Maintenance
10.4.6.1 ESP uses high-voltage DC power supply, so the relevant provisions of “Safety” should be
strictly enforced in the process of operation and maintenance, with particular attention to
personal safety and equipment.
10.4.6.2 The rectifier transformer is not put into operation in the boiler-fuel stage and can be
appropriately input in the co-combustion of coal oil stage when the fuel is very little.
10.4.6.3 Before commissioning and operating the high-voltage electric field, the temperature of the
ceramics axis, insulator and others heated should be more than the smoke dew point
(normally 70 to 80) temperature of 20 to 30 and the inlet smoke temperature of the ESP
exceeds 95 (less than 160 ).
10.4.6.4 It is prohibited in operation that the manholes of the ESP body, ceremics axis and
insulator room are opened and the isolation switches must be locked; it is prohibited in the
operating process of the rectifier transformer to operate the high voltage isolation switch or
directly cut off the power supply.
10.4.6.5 If the operations inside the ESP are necessary, the operations must be conducted after the boiler stops and cools down, the outlet temperature of the ESP drops to below 40, the
ESP body is reliably grounded by inspection, and the power off and other security measures
are prepared and it is confirmed that the content of the internal toxic gas meets labor
protection requirements. If it is urgent to operate the ESP inside, after the boiler stops for
eight hours, open the manhole of ESP body and start a guide ventilatorto speed up the
cooling.
10.4.7 Common faults and trouble shooting of ESP
10.4.7.1 The primary and secondary voltmeter and ammeter of ESP have no significant display
values
-- Reasons
The power supply of the power circuit of the rectifier transformer is disconnected;
The automatic adjustor is powered off.
-- Treatment
Check the power circuit;
Check the control power supply of the automatic adjustor.
10.4.7.2 The primary voltage of the ESP is very low, its current is large, its secondary voltage is
close to zero and the secondary current is very large
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 98
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
-- Reasons
The high-voltage isolation switch is placed on the “Ground”;
High-voltage cable is broken down or terminal joint insulator is damaged to cause short
circuit;
The electric field ash bucket is seriously accumulated with dust to cause short-circuit between
the anode and the cathode;
The broken cathode line causes short circuit;
The rotational ceramics axis of the cathode vibration device is damaged or the ceramics axis
box is seriously accumulated with dust, causing short circuit to earth;
The damping resistor at the top of electric field falls off to the ground;
There is a metal foreign body between two poles to cause short circuit;
The high-voltage insulator is damaged or quartz casing is condensed or has ash, causing the
short circuit.
-- Treatment
The high-voltage isolation switch is placed on the “Electric field” position;
Treat or replace cables and terminal joints;
Reduce the fouling inside the ash bucket as soon as possible;
Stop the boiler and treat the broken line;
Replace the rotation axis or remove the fouling;
Restore or replace the damping resistor;
Stop the boiler and treat the foreign body;
Replace the damaged insulation porcelain pieces, remove the fouling and improve the
heating temperature.
10.4.7.3 The secondary voltage of the ESP is normal and its secondary current is small
-- Reasons
Corona is closed;
The vibration effect is bad, resulting in weighty corona line or anode plate with too thick
fouling.
-- Treatment
Understand the boiler load, and observe whether it is relieved in low load;
Input the continuous vibration or adjust the vibration cycle.
10.4.7.4 The switch inside the ESP control cabinet trips or trips again after it is closed
-- Reasons
There is a foreign body in the electric field, causing double-pole short circuit;
The cathode line is broken or components fall off, causing double-pole short circuit;
The ash bucket is full of ash, causing the cathode short-circuit to earth;
The heating device of the insulator room at the top of the cathode fails or thermal insulation is
bad, causing the insulator surface to be condensated and flashover resulted from
insulation;
The fouling surface on the insulator at the top of the cathode discharges and is broken down.
-- Treatment
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 99
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Stop the boiler and treat the debris;
Stop the boiler and treat the broken line or components;
Reduce the fouling inside the ash bucket;
Restore thermal insulation or heating devices;
Swab the insulator.
10.4.7.5 Light and heavy gas alarm happen in the gas relay of ESP rectifier transformer
-- Reasons
Rectifier transformer fails inside
-- Treatment
Check whether the abnormal temperature of the outage rectifier transformer rises, check and
confirm the nature of the gas inside the gas relay, and inform the maintenance staff to
check and test insulating oil.
10.5Startup, operation, maintenance and stop of negative-pressure ash removal system
10.5.1 Interlocking and permision conditions
Before the system vacuum breaker valve is closed, the system must form a single and
smooth negative pressure air flow channel.
While the system is running, only an ash bucket material transport valve (H-type valve) is
allowed to be opened.
Before the ash removal procedures of the system ash transport pipeline start, all H-type
valves must be closed.
Before the negative pressure fan is allowed to commence, there must be a single and smooth
transport channel to form.
Before H-type valve is allowed to be opened in automatic ash transport mode during the
operation, the value of negative pressure the system must meet the minimum allowable
transmission value of PSML.
Before the upper valve of the gas lock valve is allowed to be opened, the lower valve of the
gas lock valve must be fully closed.
Before the lower valve of the gas lock valve is allowed to be opened, the upper valve of the
gas lock valve must be fully closed.
If the ash warehouse provides the alarm condition of “the material level of the ash warehouse
is high”, the system associated with the ash warehouse could not be activated. However,
when the relevant ash warehouse provides the alarm condition of “the material level of
the ash warehouse is high” after the system has begun to operate, the system continues
to run (only alarm).
Before the electric gasification air heater of the ash bucket (the ash warehouse) is put into
operation, the gasification fan of the corresponding ash bucket (the ash) must have been
put into operation normally.
Before the electric gasification air heater of the ash bucket (the ash warehouse) commences,
it must be ensured that the outlet pipeline valve has been opened and a smooth air flow
channel has formed.
10.5.2 Inspection and preparation before commissioning and operation
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 100
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
The maintenance of all equipment of the negative pressure pneumatic ash removal system is
all over, and the work sheet ends and passes the acceptance.
Check whether there is no debris inside the ash bucket.
Check that the appearance of the on-site control box is intact and the switches and buttons in
the disc are complete and are operated flexibly.
Contact a heat engineer to connect the PLC program-controlled power supply of the ash
removal system, and the indicator light shows correctly, without alarm.
Check that the pneumatic and manual valves for all instruments are at the full position, and
adjust the gas pressure for the instruments to be 0.4 to 0.6 Mpa.
Click, open and close all pneumatic valves on the CRT one by one, and observe that the
actual location is consistent with the position of the CRT and the on-site control panel on
the site and the pneumatic implementing mechanism switch is flexible and in place and is
not jammed.
Check that the appearance of the bag-type dust collector is intact, the outlet mesh grid is
intact, the general compressed air valve is open, the pressure is about 0.6Mpa, without
air leakage phenomenon, the power switch inside the on-site control cabinet is closed,
the indicator light shows right and all the switches are flexible.
The manhole of the ash warehouse is closed, the appearance of the vacuum pressure
release valve is intact, the connections of the level meter and material level switch do not
fall off, the indication is correct, and the CRT has no wrong alarm.
The inlet and outlet manual valve of the gas storage cylinder in the ash warehouse are both
opened, and the pressure is 0.4 to 0.6 Mpa. The pneumatic and manual valve of the
pneumatic valve at the top of the ash warehouse for the electromagnetic valve control
cabinet is opened, the switch location is right and the control power supply is closed.
Open the manual dry ash valves of each ash bucket to the full open status.
Open the manual isolation valve of each branch pipeline of the gasification fan of the ash
bucket to the full open status.
Deliver the power supply of the gasification fan, ash warehouse and gasification fan heater of
the ash bucket, and gasification fan heater of the ash warehouse.
Check and set the temperature (120) of the gasification fan electric heater of the ash bucket
(the ash warehouse) correctly, and set the control mode of the heater to the position of
“Remote control”.
10.5.3 Startup of the gasification system of the ash bucket and air warehouse
10.5.3.1 Check and confirm that the isolation valve of each branch of the ash bucket (the ash
warehouse) gasification fan has been opened.
10.5.3.2 Open the outlet pneumatic valve of the gasification fan of the ash bucket (the ash
warehouse) until the “Full open” feedback signal is sent out.
10.5.3.3 Start the gasification fan of the ash bucket (the ash warehouse).
10.5.3.4 Delay three minutes and then start the gasification fan electric heater of the ash bucket
(the ash warehouse).
10.5.4 Commissioning and operation of the negative pressure ash removal system
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 101
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.5.4.1 Start the ventilation filter of the ash warehouse.
10.5.4.2 Complete the following options based on the operating control station CRT of the ash
removal system:
• Select the ash bucket of each ESP, air preheater and economizer until “COLLECT” status is
through the BYPASS - COLLECT selection button)
• Select the ash removal subsystem A and B to AUTO status (relative MANUAL)
• According to the standby status of the negative pressure dedusting fan, select two fans on
work.
10.5.4.3 Press “START” button of the system
10.5.4.4 Observe that the system should run in accordance with the following procedures:
10.5.4.4.1 The filter dust collector of the ash warehouse A begins to circulate, and its impulse
control timer is excited (powered on) so that the bag-type filter starts to work. The upper
and lower valve of the corresponding air lock valve combined with the balance valve begin
to open and close circulatorily. At the same time the fluidization electromagnetic valve of
the filter dust collector is excited (powered on) and is open. When the lower valve of the air
lock valve is open, its fluidization electromagnetic valve is excited and is open, and the
fluidization electromagnetic valve is de-excited (powered off) and is closed when the lower
valve is closed.
10.5.4.4.2 The opening/closure of the following system isolation valve can form a separate ash
transport channel and vacuum channel through the filter dust collector A:
The vacuum fan isolation valve is adjusted to the correct channel.
The first branch pipe isolation valve of the ESP ash bucket is opened.
•Check the procedure logic and make sure that the ash warehouse is not in the high material
level, and a separate smooth transport channel has been established (through the limit
switch of the valve).
The vacuum breaker valve is excited (powered on) and is closed.
10.5.4.4.3 Startup of vacuum fan A.
10.5.4.4.4 When all the ash bucket relief valves (H-type valves) are closed after the fan
commences, the vacuum degree of the system will rise. When the vacuum degree reaches
the set point PSML, PLC will send signals so that the most remote ash bucket relief valves
(H-type valves) in the first column of the ESP ash bucket are opened.
If it can not reach the set point of PSML in the scheduled time, it will send a warning signal
“low vacuum” (FLY ASH SYSTEM VACUUM LOW). The phenomenon is likely resulted
from the vacuum leakage of the pipeline system or an H-type valve not closed.
When the H-type valve is opened after receiving the signal, the timer begins to work. In the
scheduled time, the vacuum degree of the system must decline to the set point PSL
below, otherwise it will trigger the “high vacuum” alarm (FLY ASH SYSTEM VACUUM
HIGH). (Usually, the time set by the timer is determined based on the time for dumping
the entire ash bucket). Before the end of the timer delay, if the vacuum degree of the
system declines to the PSL below, the timer returns to zero (reset).
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 102
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
When the ash in the ash bucket is discharged into the flying ash pipeline, the vacuum degree
of the system will increase to the set point PSH, and at the time, the E-type valve that is
currently open receives the signal and is closed to prevent the pipeline from over load.
When the H-type valve is closed, as no more ash is discharged into the pipeline, the
vacuum degree of the system will gradually drop to PSMH, and at this time, the H-type
valve receives the signal and is re-opened.
As ash in the ash bucket is gradually discharged, the vacuum degree of the system will
gradually decline. When the vacuum degree of the system declines to the set point of
PSL, the ash bucket is basically emptied, and thus the H-type valve of the ash bucket
receives the signal and is closed. The closure of the H-type valve leads to the vacuum
degree of the system to rise again, when the vacuum degree reaches the set point of
PSML, PLC sends signals to open the H-type valve of the selected next ash bucket in the
ash collection order.
10.5.4.4.5 Repeat the operation order in the above steps from C to E for every ash bucket in the
column.
10.5.4.4.6 When the vacuum degree of the system declines to PSL in the operation process of the
chosen last ash bucket in the column, or the fourth ash bucket, its H-type valve is closed.
10.5.4.4.7 The branch pipe isolation valve of the ash bucket in the second row receives signals
and is opened, and meanwhile branch pipe isolation valve of the ash bucket in the row that
has completed ash output receives signals and is closed.
10.5.4.4.8 The order of ash output and the operation process of the ash bucket in the second row
are completely the same as the ash bucket of the row completed.
10.5.5 Inspection of the negative pressure ash removal system in operation
10.5.5.1 The gasification fan and vacuum fan of the ash bucket (the ash wareshoue) are in normal
operation, without abnormal sound, the vibration is less than 0.08mm, the bearing
temperature is less than 80 , and belts slack appropriately, without fault; oil of the
lubricating parts is good, transparent and colorless, the oil level is one third to two thirds,
without oil leakage.
10.5.5.2 The combination faces of all air pipelines and pipeline flanges have no air or ash leakage.
10.5.5.3 Ammeter three-phase of the electric heater control cabinet is uniform, the voltage is
around 380V, the indicator light is right and can automatically start and stop according to the
set temperature, there is no burnt flavour inside the cabinet, and the SCR cooling fan is in
normal operation.
10.5.5.4 The ash transport pipeline has no vacuum leakage and each ash bucket discharges ash
normally;
10.5.5.5 The compressed air pressure of the system is normal, withotu air leakage phenomenon,
all the pressure gauges show correctly, the pneumatic valve operates flexibly and is not
jammed, and the on-site switch position is the same as the indicated on the CRT and on-site
disc;
10.5.5.6 Check the ash discharge pressure curve of each ash bucket timely, analyze the ash
discharge status, and confirm the alarm in the larm column after it is analyzed.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 103
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.5.5.7 The electromagnetic valve of the bag-type dust collector works properly, the effect of
pulse vibration is good, and the air exhaust does not output ash.
10.5.5.8 The on-site state of all remote control equipment and valves are consistent with the CRT.
10.5.6 The negative pressure ash removal system stops normally:
10.5.6.1 The pulse injection timer of the filter dust collector still remains the working condition, and
the upper and lower valve of the corresponding air lock valve continue to circulate for a
scheduled period of time to ensure that the filter bag is clean and the filter dust collector is
completely emptied.
10.5.6.2 After a delay for cleaning the transmission pipeline, the running vacuum fan receives
signals and stops. Before the fan stops (about 2 seconds), the corresponding vacuum
breaker valve is powered off and is opened.
10.5.6.3 The branch pipe isolation valve of the ash bucket and the isolation valve of the fan are
closed.
10.5.6.4 The operating process of ash removal ends.
10.5.7 Common faults and trouble shooting of negative pressure ash removal system
When there is an alarm signal, press (ACK) button first of all; after eliminating the alarm
situations, press (RESET) to remove the alarm display. (For the critical alarm signal of the
system, the system must be reset before it is allowed to restart.)
10.5.7.1 Low vacuum of fly ash system
Reason: A “low vacuum” alarm signal lasts more than 30 seconds. The possible reason is that
the material transport valve of the ash bucket can not be closed or the pipeline is
damaged.
System response: the system stops at the current ash bucket because the vacuum degree of
the system fails to rise to PSML, it can not be transferred to the next ash bucket.
Treatment: check whether H-type valve of the current ash bucket moves normally, and find
the leakage point and eliminate it
10.5.7.2 High vacuum of fly ash system
Reason: the vacuum value continues to maintain the set point of PSMH for more than 15
minutes. The possible reason is that the ash bucket is blocked or the material transport
valve of the ash bucket can not be opened.
System response: the system stops at the current ash bucket because the vacuum degree of
the system fails to decline to PSL, the current H-type valve maintains open.
Treatment: switch the status of the ash bucket to the BYPASS status, and check whether the
manual lower ash valve of the ash bucket is opened, and treat the blocked ash of the ash
bucket.
10.5.7.3 High temperature outlet of negative pressure fan A (B)
Reason: the outlet temperature of the negative pressure fan is high, and the possible reasons
include the bad lubrication or the fan has mechanical failure.
System response: the transportation system is shut down
Treatment: the system is put into operation again after switching the standby fan
10.5.7.4 High pressure difference of filter dust collector A (B or C)
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 104
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Reason: the differential pressure switch senses the high differential pressure inside and
outside the cloth bag, and three times of this situation within 10 minutes appear
continuously. Possible reason is that the cloth bag is blocked or the cloth bag cleaning
equipment fails.
System response: when the cloth bag dust collector alarms for the first time due to the high
differential pressure of the cloth bag, the current H-type valve should be closed and the
system vacuum breaker valve is powered off and is opened. The “on demand” ash
removal control procedures of the filter dust collector continue to operate, and the air lock
valve below the dust collector runs circulatorily for a scheduled period of time (about two
minutes). The vacuum breaker valve is powered on and is closed, and the current H-type
valve is re-opened so that the system resumes operating. If the dust collector cloth bag
has high differential pressure for three times continuously within 10 minutes, an alarm
signal appears, and the system starts to stop normally. (After cleaning the pipeline,
before the system stops, the pulse injection control procedures of the filter dust collector
and the circulation procedures of the air lock valve continue to run for 5 to 10 minutes).
Treatment: check the pulse electromagnetic valve of the cloth bag dust collector and check
the pressure of the gas source for the cloth bag dust collector.
10.5.7.5 The cloth bag A (B) of the filter dust collector is broken
Reason: the determined significant changes in dust grain flow are detected by the dust
monitor installed on the front air inlet mother tube at the entrance of the negative
pressure fan and this situation continues for a scheduled period of time. The reason is
usually that the cloth bag of the filter dust collector is damaged or the cloth bag falls off.
System response: the system alarms.
Treatment: stop the system to check the cloth bag dust collector and calibrate the dust
detector.
10.6Startup, operation, maintenance and stop of the hydraulic deslagging system
10.6.1 Interlocking and protection
10.6.1.1 After the slag crusher is overload, it stops and sends out fault alarm signal.
10.6.1.2 A, B slag bucket of each boiler are at the same time not allowed to discharge slag, and
two boilers discharge slag alternately.
10.6.1.3 When the liquid level of the front buffer tank of the slurry pump of No.1, 2 generating unit
(the front tansfer warehouse of the slurry pump for No. 3 to 6 generating unit) is “too low”
value, the operation pump stops; when it is “low” value, the slurry pump is locked and is
allowed not to start. If the high-pressure pump at this time is in operation, the water
replenishing valve is opened; when it is the normal value, the water replenishing valve is
closed, and when it is high value, the slurry pump should be start or continue to run; when
the liquid level of the front buffer of the slurry pump is “low” value and the high-pressure
water pump does not run, the water replenishing valve is not closed. (No. 3 to 6 generating
unit is yet not provided wih logical chain, so the “low” value is 1.5m in the actual operation
and the “too low” value is provided by 0.5m)
10.6.1.4 When the liquid level of the front buffer tank of the slurry pump of No.1, 2 generating unit
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 105
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
is “too low” value, the washing valve of the slurry pump is opened, the inlet valve is closed,
and the slurry pump stops and the washing valve is closed after washing for some time.
10.6.1.5 When the high, medium and low-pressure water pump begin to be put into operation, the
electric bypass valve is opened first automatically, the bypass valve is closed after the pump
operates stably, and when the pressure of the mother tube is high in the course of running,
the bypass valve is opened to relieve pressure.
10.6.1.6 The overflow pump and sewage discharge pump start under the “high water level” signal
sent by the liquid level meter, and they stop when it is “low water level " signal.
10.6.1.7 When the water storage tank sends “low water level” signal, the water replenishing
electric valve is opened to supply water to the water storage tank, until the water level is
normal before the water replenishing electric valve is closed.
10.6.2 Preparation and inspection prior to commissioning and operation
10.6.2.1 Confirm that the maintenance of all the equipment of the system is all over and the work
sheets are ended and pass the acceptance.
10.6.2.2 The manholes of the slag bucket are closed tight, overflow pipes are smooth, there is no
slag deposition in the overflow water tank, each manual valve of water seal slot and sight
glass washing valve are opened, the slag discharge gate and each aerodynamic nozzle
vavle are closed, sight glass is intact, and all the pipelines are connected tightly.
10.6.2.3 The water storage tank for controlling the slag discharge valve of the slag bucket is filled
with water by 15 to 25cm, and its water inlet valve, overflow water valve,and the water
discharge valve at the bottom and the control emptying valve at the top are all closed,
without water and air leakage.
10.6.2.4 The appearance of the slag crusher is intact, the anchor bolts are connected tightly, the
shaft seal water is normal, the oil level of the reducer is one second to two thirds, and oil
quality is good, without oil permeability and leakage, the transmission chain is appropriate
elastic with good lubrication, the shield is solidly installed, the hydraulic injector is smooth,
and the inlet and outlet flange are connected tightly.
10.6.2.5 The liquid level of the water storage tank is normal and the liquid level indicator shows
correctly.
10.6.2.6 The anchor bolts of high and medium pressure water pumps are connected tightly, the
inlet manual valve and bypass manual valve are open, the shaft seal water and bearing
cooling water are appropriately adjusted, the oil level is one second to two thirds, and the oil
quality is good, without oil permeability and leakage, and the coupling shield is installed
firmly.
10.6.2.7 The anchor bolts of low-pressure water pumps are connected tightly, the inlet manual
valve and bypass manual valve are open, the bearing lubricant is good, the belt is intact and
is appropriately elastic, and the shield is installed firmly.
10.6.2.8 Start a slag bucket cooling water pump to supply the corresponding the water seal groove
at the bottom of the boiler with water before 1h when the boiler is ignited.
10.6.2.9 The anchor bolts of the overflow pumps are connected tightly, the bearing lubricant is
good, the belt is intact and is elastic appropriately, the shield is installed firmly, and the shaft
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 106
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
seal water is appropriately adjusted.
10.6.2.10 There are no big blocks of slag deposition, debris and others inside the slag bucket
buffer pool (transfer warehouse), and the liquid level shows correctly.
10.6.2.11 The anchor bolts of the slurry pump are connected tightly, the inlet manual valve and
outlet manual valve are open, the shaft seal water and bearing cooling water are
appropriately adjusted, the oil level is one second to two thirds, and the oil quality is good,
without oil permeability and leakage, and the coupling shield is installed firmly.
10.6.2.12 Contact a heat engineer to connect the PLC power supply, open the pneumatic and
manual valve of the slag bucket for the electromagnetic on-site cabinet instrument, close the
control power supply, and the indicator light shows correctly and the switch is placed at the
“Remote” position.
10.6.2.13 Close the power supply inside the on-site control cabinet of the slag crusher, and the
indicator light shows correctly and the switch is placed at the “Remote” position.
10.6.2.14The air pressure of the instrument is 0.4 to 0.6 Mpa, all the pressure transmitting
instruments and pressure switches are input, the pressure gauge is intact, the pneumatic
valve and electric valve switches are flexible and the feedback signals are correct.
10.6.2.15 The ash water recycling system is in good standby status.
10.6.3 Startup and stop of slag bucket cooling water pump
10.6.3.1 Operation steps of starting the slag bucket cooling water pump
10.6.3.1.1 According to the operating conditions of the generating units, open the general electric
valve of the low-pressure water replenishment and the manual valve of each branch line
(appropriate opening).
10.6.3.1.2 Open the electric bypass valve of the low-pressure water pump.
10.6.3.1.3 Press “Start” button of the low-pressure water pump, observe that the outlet pressure
gauge of the low pressure water pump is normal, and open the electric valve of the
low-pressure water pump.
10.6.3.1.4 After the low-pressure water pump works normally, close the electric bypass valve of
the low-pressure water pump, and adjust the electric outlet valve according to the water
replenishing status of the boiler water seal.
10.6.3.2 Operation steps of switching slag bucket cooling water pump (switching the high and
medium pressure water pump by reference to the operation steps)
10.6.3.2.1 Report to the leader on duty before switching.
10.6.3.2.2 Start the standby pump.
10.6.3.2.3 Open the exit valve of the standby pump and close the exit valve of the operating pump,
and at this time pay attention to the changes in the outlet mother tube pressure and the
overflow water.
10.6.3.2.4 Stop the original operating pump after the startup pump is operating normally.
10.6.3.3 Operation steps of stopping the slag bucket cooling water pump
10.6.3.3.1 Stop the slag bucket cooling water pump when the leader on duty orders to stop the
slag bucket cooling water pump.
10.6.3.3.2 Press “Stop” button of the low-pressure water pump to stop it.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 107
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.6.3.3.3 Close the inlet and outlet valve, and shaft seal water and bearing cooling water.after the
low-pressure water pump stops
10.6.4 Startup and stop of overflow pump
10.6.4.1 Operation steps of starting the overflow pump
10.6.4.1.1 Check whether the overflow pump and its motor have the startup conditions, connect
the power supply and confirm the power current and the control power supply are normal.
10.6.4.1.2 Confirm that the slag bucket cooling water pump is running normally, the overflow of the
water seal slag discharge groove is normal and the water level of the overflow water tank
is normal.
10.6.4.1.3 When the water level of the overflow water tank is high, start the overflow pump on the
CRT, open the electric outlet valve of the overflow pump in the interlocking or manual
mode, and confirm on the site that the overflow pump starts normally. (When the water
level “high” signal of the overflow water tank is sent, the overflow pump should be
interlocked and start automatically)
10.6.4.1.4 After the overflow pump is running, pay attention to the changes in the outlet pressure
of the overflow pump and the water level of the overflow water tank.
10.6.4.2 Operation steps of stopping the overflow pump
10.6.4.2.1 When confirming that the water level of the overflow water tank is low, the overflow
pump can be suspended. (When the overflow water tank sends a “low water level” signal,
the overflow pump should chain and automatically stop, and the electric inlet valve will
shut down automatically).
10.6.4.2.2 Press “stop” button of the overflow pump on the CRT to stop operating the overflow
pump, and close its electric outlet valve.
10.6.4.2.3 If the overflow pump stops for a long time and there is no water in the overflow water
tank, close the manual water valve of shaft seal of the overflow pump.
10.6.5 Startup and stop of deslagging water pump
10.6.5.1 Operation steps of starting the deslagging water pumps
10.6.5.1.1 Check whether the liquid level of the water storage tank is normal;
10.6.5.1.2 Check that the deslagging water pump and its motor are provided with startup
conditions, connect the power supply, and confirm that the power supply and the control
power supply are normal.
10.6.5.1.3 Open the electric bypass valve of high-pressure water pump.
10.6.5.1.4 Press “Start” button of the deslagging water pump on the CRT, observe the outlet
pressure gauge of the deslagging water pump shows normally, and open the electric outlet
valve of the deslagging water pump, when the changes in the outlet pressure of the
deslagging water pump and the water level of the water storage tank should be paid
attention to.
10.6.5.1.5 Close the electric bypass valve of the deslagging water pump after opening the inlet
and outlet valve of the slag discharge hydraulic ejector.
10.6.5.2 Operation steps of stopping the deslagging water pump
10.6.5.2.1 Confirm that the slag discharge out of the slag bucket ends.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 108
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
10.6.5.2.2 Press “Stop” button of the deslagging water pump on the CRT
10.6.5.2.3 Close the electric outlet valve of the deslagging water pump
10.6.5.2.4 Confirm that the deslagging water pump stops running.
10.6.5.2.5 Close the shaft seal water valve and bearing cooling water valve of the deslagging
water pump.
10.6.6 Operations of slag bucket slag discharge
10.6.6.1 Place the switches of the electromagnetic valve control cabinet and slag crusher on-site
control cabinet to “Remote” position.
10.6.6.2 Open the outlet pneumatic valve of the hydraulic ejector.
10.6.6.3 Open the inlet pneumatic valve of the hydraulic ejector.
10.6.6.4 Start the deslagging water pump.
10.6.6.5 Start the front-wall slant nozzle of the slag bucket.
10.6.6.6 Start the slag crusher and open the back dilution valve of the slag gate and the slag
discharge gate.
10.6.6.7 When slag in the slag bucket is emptied basically (time to be determined after
commissioning) , close the front-wall slant flush valve of the slag bucket, open the outer slant
flush valve, rinse it for 2 to 3 minutes and then close it, open the lower oblique flush valve
inside the slag bucket for 2 to 3 minutes and then close it, open the upper oblique flush valve
inside the slag bucket for 2 to 3 minutes and then close it, open the front-wall slant flush
valve of the slag bucket for 2 to 3 minutes and then close it, and open the emergency flush
valve of slag bucket gate for 1 to 2 minutes and then close it.
10.6.6.8 Close the slag discharge gate. Open the upper oblique flush valve inside the slag bucket
to inject water to the slag bucket for 20 minutes and then close it.
10.6.6.9 Stop the slag crusher.
10.6.6.10 Open the outlet pneumatic valve of the hydraulic injector of another slag bucket.
10.6.6.11 Open the inlet pneumatic valve of the hydraulic injector of another slag bucket.
10.6.6.12 Repeat Item 6.6.5 to 6.6.9 and discharge slag out of another slag bucket
10.6.6.13 Stop the deslagging water pump after the end of discharging slag out of the slag bucket
10.6.6.14 Close the inlet valve of the hydraulic injector.
10.6.6.15 Close the outlet valve of the hydraulic injector.
10.6.7 Startup and stop of slurry pump
6.7.1 Operation steps of starting the slurry pump
10.6.7.1.1 Check that the liquid level of the slurry buffer tank or transfer warehouse is normal, and
wash the slurry pumps of No. 1 and No.2 generating unit and close the electric valve.
10.6.7.1.2 Confirm that the slurry pump and its motor are provided with startup conditions, connect
the power supply, and confirm the power supply and the control power supply are normal.
10.6.7.1.3 Start the inlet valve of the slurry pump, press “Startup” button of the slurry pump and
observe that the outlet pressure gauge of the slurry pump shows normally (more than
0.4Mpa), and open the exit valve of the slurry pump (but a slurry pump should be avoided
from transporting to two slag pipes at the same time, and two slurry pumps are
prohibited to transport to a slag pipe at the same time), when the changes in the outlet
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 109
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
pressure of the slurry pump and the water level of the slurry buffer tank should be paid
attention to.
10.6.7.1.4 The inspection on concentration of slag water, size of slag grain, pressure of slag pipe
and others of the slurry pump during operation should be strengthened to prevent the
slurry pump from being jammed, overflowing or the slag pipe from being blocked as well
as unusual situations from occurring.
6.7.2 Operation steps of stopping the slurry pump
10.6.7.2.1 When it is confirmed that sediment in the slag bucket at the bottom of the furnace or in
the slurry buffer tank has been transported cleanly, the desulfurization and ash warehouse
stop discharging gypsum (mortar) and the liquid level of the slurry buffer tank or transfer
warehouse reduces to the low value, open the backwashing valve at the entrance to the
slurry pump, close the inlet valve of the slurry pump and rinse the slag pipe for 15 minutes.
10.6.7.2.2 Press “Stop” button of the slurry pump to stop operating the slurry pump.
10.6.7.2.3 Close the outlet valve of the slurry pump.
10.6.8 Inspection of commission and operation and contents of maintenance
10.6.8.1 All the slag buckets, pipelines and valves have no water leakage, the fire holes are not
ruptured, and the positions of the valves are correct.
10.6.8.2 There is no abnormal sound from the slag crusher in operation, shaft seal is supplied with water normally, vibration is less than 0.08mm, bearing temperature is no more than 80,
and the chain transmission is normal.
10.6.8.3 Water storage tank provides normal liquid level and has no water or gas leakage
phenomenon.
10.6.8.4 The outlet pressure of the hydraulic ejector in the process of discharging slag increases
abnormally, the water output of the slag pipe becomes small, the slag discharge gate of the
slag bucket should be timely closed and the slag pipe is washed.
10.6.8.5 The liquid level of the water storage tank and slurry buffer tank is normal, the float valve
sends signal right in time, and water supply is input in a timely manner.
10.6.8.6 The sound of the water pump is normal in operation, and the pump body does no leak and the shaft seal drips normal. Bearing temperature does not exceed 80, vibration is less
than 0.08mm, water of the shaft seal is properly adjusted, the belt does not skid or is not
broken, and the outlet pressure is normal.
10.6.8.7 The indicator lights of all on-site control cabinets are right, the air pressure for instruments
is 0.4 to 0.6Mpa, the pipeline does not leak, and all the pressure gauges and pressure
transmitting instruments are input normally.
11 FGD and Limestone Supply System Operation Manual
11.1 SCOPE
This standard prescribes the principle, method and procedure for the start up, shut down,
operation & maintenance, control & regulation, dead status upkeep, accident handling and so on
of the 2x300MW power generation unit flue gas desulfurization (FGD) system in Vietnam
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 110
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Guangning Power Corporation, Ltd. The 2x300MW power generation unit FGD system operation,
equipment maintenance and production technical management staff at all levels engaged in
Vietnam Guangning Power Corporation, Ltd. must acquaint themselves with entire or related parts
and carry through strictly.
11.2 NORMALIZED DOCUMENT QUOTATION
The terms in the documents listed below become the terms of this standard through quotation.
For every dated quotated documents, all subsequent revision sheets or versions shall not be
applicable. However, it is encouraged that all parties who come into agreement on this standard
can investigate the workablity of the latest versions of these documents. For every undated
qutoted documents, the latest version shall be applicable under this standard.
S. No. Standard Code Name Standard Title 01
DL277-94
Working Regulation of Power Safety (Thermal Mechnical
Part) 02
DL408-91
Working Regulation of Power Safety (Power Station and
Substation Electrical Part) 03
Shanghai Shichuan Island Guangning Desulfurization
System Operation And Maintenance Manual 11.3FGD SYSTEM QUIPMENT SPECIFICATION
11.3.1 General
Vietnam Guangning first phase 2x300MW coal firing generation units consist of 2 sets of
subcritical drum boiler with controlled circulation, single drum, one regenerative stage, “W” flame
combustion (middle storage, hot air powder feeding, third air not entering the furnace), balanced
ventilation, solid deslag, open arrangement and complete steel suppension structure. The raw flue
gas shall be dedusted by ESP. The FGD is set at the furnace rear area after the ID fan. The
limestone-gypsum wet full flue gas desulfurization method shall be used under BMCR operation
conditions by FGD project. The design efficiency is 93% and the guarantee desulfurization
efficiency is not less than 90%. Desulfurization process shall use limestone-gypsum wet
desulfurization method. The spray empty absorber towers are adopted. One absorber tower is set
for each boiler.
The wet milling proposal is used in limestone preparation system which is design into two sets.
One set of the milling machine shall meet the 100% limestone consumption requirement by 2
boilers under BMCR operation conditions.
The Gas-Gas-Heater (GGH) is used.
The monitoring and control of FGD are set in Ash Control Building. One DCS system is
adopted for control of 2 boilers’ FGD and common systems.
The desulfurization sewage treatment system is not given in this project temporarily. The
desulfurization sewage is discharged into the plant ash slurry reservoir directly.
11.3.2 Project Design Conditions
11.3.2.1 Boiler Survey
11.3.2.1.1 Major design parameters for boiler
Equipment Parameter Unit Value
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 111
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Type SUBCRITICAL NATURAL CIRCULATION, “W” FLAME, DRUM BOILER
MCR t/h 996.33 Quantity set 2
Boiler
Actual coal consumption t/h 130~145 Quantity (per boiler) set 2 Type DOUBLE ROOM FOUR
FIELDS ESP
Deduster
efficiency % >99.1 Type Static blade adjustable axial
draft type Quantity (per boiler) set 2 Air quantity (T.B) m3/s 258.7
ID fan
Air pressure (T.B) Pa height m 200 Inner diameter at outlet m 4600
chimney Internal anticorrosive material
11.3.2.1.2 Parameters for flue gas and its ducting
Item Unit Value Flue gas speed (design flow) m/s ﹤ID fan outlet flue duct dimension (steel structure) m×m R=4500 ID fan outlet flue duct central line elevation m 2.9 11.3.2.1.3 Flue gas parameters at FGD system inlet
Boiler BMCR Operation Conditions Flue Gas Analysis (Design coal, Standard conditions, Actual O2)
Item Unit Dry basis Wet basis Remark CO2 Vol% 13.26 12.57 α=1.477 O2 Vol% 6.85 6.49 N2 Vol% 79.84 75.67
SO2 Vol% 0.06 0.053 H2O Vol% 4.98 5.2176
Boiler BMCR Operation Conditions Flue Gas Parameters Design coal remark
Nm3/s Dry basis, α=1.447
Nm3/s Wet basis, α=1.447
Nm3/h Standard conditions, Dry basis, α=1.4
ID fan outlet flue gas quantity(BMCR)
Nm3/h Standard conditions, Wet basis, α=1.4
ID fan outlet flue gas temperature
ID fan outlet flue gas pressure
Pa BMCR Operation Conditions
ID fan outlet flue gas quantity and temperature under different loads Item Unit RO 75%RO 65%RO 30%RO
ID fan outlet dry flue gas quantity
Nm3/h
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 112
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
ID fan outlet wet flue gas quantity
Nm3/h
ID fan outlet flue gas temperature
Boiler BMCR Operation Conditions Flue Gas Pollutant Analysis(Standard conditions, Dry basis, 6%O2)
Item Unit Design coal Min Max SO2 mg/Nm3 934 573 1504 SO3 mg/Nm3
Cl(HCl) mg/Nm3 F(HF) mg/Nm3
Soot (ID fan outlet) mg/Nm3 400 400 400 11.3.2.2 Fuel
No. Components Symbol Unit Range Data Design Data I Heating values
High heating value HHV kcal/kg 4680 - 5300 4980 Low heating value LHV kcal/kg 4490 - 5157 4790 Proximate analysis 1 Total moisture (as received) War % 5.55 - 12.0 9.00 2 Surface moisture Ws % 4.81 - 9.88 7.63 3 Inherent moisture Win % 0.78 - 2.35 1.48 4 Air-dried moisture Wad % 0.80 - 2.41 1.39 5 Fixed carbon (as received) Cf
ar % 49.54 - 63.15 53.68 6 Volatile matter (as received) Var % 5.82 - 8.61 6.83 7 Ash content (dry) Ad % 28.0 - 37.36 33.5 8 Ash content (as received) Aar % 25.48 - 34.0 30.49
To tal 100.00 Ultimate analysis
1 Carbon (as received) Car % 46.83 - 63.75 54.62 2 Hydrogen (as received) Har % 2.56 - 2.97 2.62 3 Oxygen (as received) Oar % 1.66 - 2.68 2.09 4 Nitrogen (as received) Nar % 0.73 - 0.86 0.77 5 Sulphur (as received) Sar
or % 0.27 - 0.66 0.41 6 Ash (as received) Aar % 25.48 – 34.0 30.49 7 Moisture (as received) War % 5.55 - 12.0 9.00
Total 100.00 Physical criteria 1 Hardgrove Grindability Index - 45 - 70 47 2 Dust coal particle size
(0-15mm) 100
+10 mm size % 6.16 - 17.5 10.53 5-10 mm size % 9.89 - 18.3 14.22
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 113
Rev.: A
Item Value Colour: No Smell: No
CO2 (Concentration): 2.64 mg/l
Date 2008-09-16
No. : QN1-SEC-G-04-TP-005
Page 114
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
No. Components Symbol Unit Range Data Design Data 2.5-5 mm size % 15.60 - 21.71 18.62 1.25-2.5 mm size % 8.73 - 13.76 10.97 0.63-1.25 mm size % 12.36 - 18.13 14.89 0.315-0.63 mm size % 6.80 - 14.45 10.02 - 0.315 mm size % 11.47 - 31.47 20.77 3 Density - 0.92 - 1.10 1.00 4 Angel of repose degree 33 - 39 37 No. Components Symbol Unit Range Data Design Data
Ash content 1 SiO2 % 57.60 - 64.10 62.83 2 Al2O3 % 23.3 - 28.64 24.76 3 Fe2O3 % 4.26 - 6.16 5.41 4 V2O5 % 0.018 - 0.028 0.026 5 TiO2 % 0.50 - 0.91 0.68 6 CaO % 0.30 - 0.77 0.44 7 MgO % 0.67 - 1.42 1.11 8 K2O % 3.35 - 4.70 3.64 9 Na2O % 0.15 - 0.55 0.48 10 P2O5 % 0.19 - 0.30 0.24 11 SO3 % 0.251 - 0.481 0.341 12 MnO % 0.006 - 0.050 0.043 13 Others % 0.00 0.00
Total 100.00 1 Ash density g/cm3 0.224 - 0.370 0.291 2 Ash resistivity (for reference
only) R Ωcm 301x102 -
603x102 525x102
Ash Fusibility
1 Initial deformation temperature T1 0C 1210 - 1280 1250 2 Hemispherical softening
temperature T2 0C 1430 - 1600 1570
3 Fluid temperature T3 0C 1530 - 1600 1600 11.3.2.3 Water Conditions
The process water comes from plant industrial water with temperature less than 35 and
pressure of 0.2~0.5MPa(g). The cooling water sources from the process water and circles within
the process system. It is not returned. The quantity is included in the process water. The industrial
water analysis is as follows:
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Item Value Total hardness: 0.10 me/l
Total Cation: 0.17 mol/l Total Anion: 0.175 mol/l
SiO2: 1.80 mg/l Total sludge: 50 mg/l
Mean Corrosiveness: Weak 11.3.2.4 Limestone Conditions
Parameter Unit Value CaCO3 content wt % 92 – 95
Analysis:
MgO Fe2
O3
SiO2
Al2 O3
wt %
wt %
wt %
wt %
0.19 - 2
0.1 - 1.2
0.16 - 0.6
0.14 - 2.0 Bond work index KWh/Mt 10 (estimated)
Solid limestone (dense) Kg/m3 2400 - 2600 Solid limestone size mm 0 - 20 or more
11.3.2.5 FGD Design Guarantee Value
11.3.2.5.1 Once the FGD is in commercial operation, the FGD utilization ratio shall be not
less than 98% of the boiler ESP operating time, the definition is as the below
formula:
A − B
Utilization ratio = A
×100%
Here: A- hours with FGD device in-operation conditions
B- forced shut down hours with FGD’s causes
11.3.2.5.2 Desulfurization efficiency, SO2 emission density
Under the conditions of no excessive limestone, process water and power consumptionns,
firing the coal provided by client (sulfur 0.27%-0.66%) and handling complete flue gas under
BMCR operation comditions, the guarantee desulfurization effciency is over 90% so that the FGD
outlet SO2 density shall not exceed max permissible density 150mg/Nm3 (Dry basis, 6%O2).
11.3.2.5.3 FGD gypsum slurry quality
Item Unit Value
- purity mass-%dry 90
- pH / 5.5~7.5
- density mg/m3 1
- smell / Nil
- average particle diameter / 40μ
- MgO(water soluble) mass-%dry 0.021
- Na2O(water soluble) mass-%dry 0.035
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 115
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Item Unit Value
- K2O mass-%dry 0.07
- Cl(water soluble) mass-%dry 0.01
- CaSO3·1/2H2O(as SO2) mass-%dry 0.35
- (Oxidable organics)
- soot mass-%dry 1.32
-Al2O3 mass-%dry 0.26
-Fe2O3 mass-%dry 0.10
-SiO2 mass-%dry 0.70
-CaCO3 mass-%dry 2.9
-K2O mass-%dry 0.07
11.3.2.5.4 Flue gas emission
When the coal sulfur content comes up to 200% of the design value, the polutant emission
density shall not exceed:
SO2: 150 mg/Nm3(Dry basis)
HCl: 1 mg/D.Nm3
Soot: <100mg/Nm3(Dry basis)
11.3.2.5.5 Limestone consumption
Ca:S≤1.03
When S content = 0.66%, average limestone consumption≤5.7 t/h.
When S content = 0.41%, average limestone consumption≤3.3t/h.
11.3.2.5.6 Water consumption
Max: 100 t/h (When S content = 0.66%)
Normal: 80 t/h (When S content = 0.41%)
11.3.2.5.7 Steam consumption
Under the boiler rated loading and worst conditions, FGD maximum steam consumption is 5.5
t/h. The superheated steam used by desulfurization island comes from the main power house with
quality of: 1.2Mpa, 300.
11.3.2.5.8 Power consumption
The desulfurization island total power consumption is 5800 Kw.
11.3.2.5.9 Flue gas temperature at chimney inlet and mist content at mist eliminator outlet
The chimney inlet flue gas temperature is not less than 82 (boiler BMCR operation
conditions), the water drop carried by the flue gas shound be less than 100mg/Nm3(dry).
11.3.3 Production Process
11.3.3.1 The FGD system consists of the following subsystems:
Sorbent Preparation and Supply System;
Flue Gas System;
So2 Absorbing System;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 116
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Common System;
Electrical System.
11.3.3.2 FGD System Process Flow
11.3.3.2.1 Absorber
The flue gas exhausted by ID fan flows into the bottom of the absorber under the function of
boost fans, to the top, to mix with the suspension of sorbent. The slurry is delivered to the top of
the absorber via slurry pipe and spray section by the recirculation pump, the slurry is sprayed out
to be specified droplets by atomization nozzle, and dispersed in the circulating reaction pool by the
self weight. The droplets absorb the acidity content in the flue gas, such as SO2, SO3, HF and HCl,
etc. During the process that gas passes through absorber and absorbs the acidity content, it is
vaporized by the water in slurry to saturation condition, and cooled to the adiabatic saturation
temperature.
Upon the spray section in the absorber, two-stage mist eliminator is arranged to separate the
slurry droplets in the gas. The separate droplets drop to the slurry pool by its self weight. It is easy
for the slurry droplets to paste on the flakes of mist eliminator, so it is necessary to wash the flakes
of mist eliminator periodically to ensure the smooth transfer of gas in the mist eliminator. In the
mean time, the washing water makes up most of the lost water being carried away by gas.
Fresh limestone slurry must be fed in the absorber to make up the consumed limestone. At
the same time, the outgrowth (most is gypsum) should also be discharged to control the
concentration of absorption slurry.
The absorber is divided basically to three sections:
Absorption Section
The absorption section is from the surface of circulation slurry to the bottom of mist eliminator.
In this section, some acidity content is absorbed, most is SO2, SO3; SO2 is absorbed to be HSO3-,
further to be oxidized SO42-, then react with limestone to be gypsum.
Circulation Slurry Tank
The circulation slurry tank is section from the absorber bottom to the surface of slurry pool, the
depth of slurry pool is 6.0M under normal condition.
The function of circulation slurry pool:
Oxidize sulfite to be sulfate
Dissolve the fresh limestone slurry
The sulfate reacts with the dissolved limestone to be gypsum
Gypsum crystal formation
The slurry pool is large enough to meet the requirement of the formation of favorable gypsum
crystal (CaSO4υ2H2O).The slurry is discharged to gypsum tank by absorber bleed pump.
3 sets of agitators are arranged in the absorber to avoid the sediment of slurry. The agitators
undertake not only the function of agitation, but also the function of air dispersion.
Flue gas Section
On the upper part of the absorber, the flue gas passes through the two-stage roof type mist
eliminator to minimize the droplets. The start-up of washing program for mist eliminator is
controlled by the slurry level.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 117
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.3.3.2.2 The oxidization air
Three sets of oxidization fans are adopted for two absorbers, 2 working 1 stand by. The
oxidization fan is Roots fan. Three sets of mixers are set per absorber. The oxidization air is fed
into the absorber slurry reservoir through the front nozzles. And then the mixers shall distribute the
bubbles equally in the reservoir. The oxidization air can be well distributed among the slurry, so
that the SO3 can be oxidized into SO4.
11.3.3.2.3 Flue gas reheat system
During the desulfurization, the flue gas is cooled to adiabatic saturated temperature by
circulating slurry. The flue gas is reheated before entry into the existing chimney to prevent the
condensation in the chimney. The flue gas reheat system major equipments include gas gas
heater (GGH) and its auxiliaries.
Gas gas heater (GGH)
To use the heat of the untreated flue gas from the boiler, one set of rotary GGH is adopted.
The clean flue gas at the absorber outlet is heated by this device. The flue gas uplift floatage in
and at the outlet of the chimney is increased so that it can prevent the chimney corrosion bought
by condensate maximumly. The GGH device has increased the power consumption and
maintenance expense of the FGD, but it is a must.
The philosophy of GGH (like air preheater) is as follows: The heating components
circumvolve slowly through original gas and clean gas. They absorb the heat energy from original
gas when it is on the original gas side, and transfer the heat to the clean gas when they rotate to
the clean gas side. The clean gas is isolated from original gas by seal plate. The two streams pass
through the section bodies on rotor separately. The two gas streams flow in reverse directions.
The GGH has higher and stricter requirements than boiler air preheater in aspects of sealing,
leakage, flue gas contacting surface anti-corrosion, sweeping and etc.
The anti-leakage control system is arranged to bring the leakage of original gas to clean gas
down to the minimum. That is to say some clean gas is extracted and charged to the heating
elements between clean gas and original gas. Because the pressure of seal gas is higher than
original gas, the leakage of original gas to clean gas is prevented maximumly.
Auxiliaries for reheater
The reheater is mate with one set of cleaning device for removing the dust on the heating
surface. The steam and pressure water is used as cleaning medium in the device.
The steam sweeping is in use under normal operation. When the device is operating up to
some time (preliminary fixed as five days, or according to the pressure drop between the GGH
inlet & outlet), the HP water is used. After the system stop operation, the LP water is used.
11.3.3.2.4 Boost fan system
To compensate the pressure lost because of the absorber, GGH and flue duct, the boost fan
is installed at the upriver of the original flue gas side. The boost fan is of static blade axial fan.
11.3.3.2.5 Flue gas duct system
There is main flue gas duct connection between the flue gas duct system and boiler ID fan
outlet. There is bypass flue gas damper set at the section connecting main flue gas duct and
chimney. FGD device is equipped with independent flue duct system, consisting of:
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 118
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Original flue gas duct, from the main flue gas duct with original flue gas damper to the
absorber inlet through boost fan.
Clean flue gas duct, from the absorber outlet, GGH, through main flue gas duct with clean flue
gas damper, to the chimney.
Partial original flue gas duct and all clean flue gas duct is lined with anti-corrosion (glass scale)
protection.
The flue gas duct system is equipped with double layer damper. The damper sealing fan
system will provide sealing air to these dampers to fulfill zero leakage.
11.3.3.2.6 Limestone storage, milling and slurry supply system
The limestone (0-20mm) is transported to the site by truck. Two unloading fuel hoppers are
used in this project. Heavy grating is set at each unloading fuel hopper to prevent large size
material from entering the downriver equipment. One set of dedusting system is adopted to
eliminate the dust in the unloading room and around to the minimum.
The limestone is conveyed on the ripple belt conveyor through the bottom of the unloading
hopper by the vibrating feeder and then fed into the two limestone storage silo. The conveying
system is designed to be of close negative pressure which can decrease the fly ash to the
minimum.
One scale weighing fuel feeder is set at the bottom of the limestone silo which sends the
limestone particle. There is air locking device at the milling fuel adding hole.
The limestone preparation system shall be two sets (one working one stand by). Each set is
equipped with one scale weighing feeder, one wet miller with slurry tank, two slurry pumps and
one group of limestone swirling machine. The scale weighing feeder sends the middle silo
limestone particle into the wet miller for milling. Single wet miller is of 75% FDG-BMCR. The
limestone slurry after milling overflows into the wet milling slurry tank. Then it is centrifuged in
limestone swirling machine with fineness of 90% of the particle can pass through screen of 0.045
(325) and quality of smooth overflow into the buffer tank. The unqualified particle returns to the wet
milling for remilling through the bottom of the swirling machine. The limestone slurry preparation
system automatically make limestone and water into 30% density slurry which is sent into
absorber through two stage pumps (buffer pump and slurry supply pump).
11.3.3.2.7 Process water system
The process water system is mainly used for absorber mist eliminator cleaning (absorber
make up), pipe cleaning, GGH HP & LP cleaning. The process water for FGD comes from the
plant industrial water system. 1x150m3 water tank as middle storage tank supplies continuous
make up water to maintain the normal operation of the system. The FGD island industrial water
and process water system shall common pump delivery and network system.
In FGD system, the major process water consumption includes flue gas evaporation, waste
water drainage and etc.
11.3.3.2.8 Industrial water system
The industrial water is mainly for high quality consumer, including milling oil station cooling,
pump mechanical sealing water, rotary equipment bearing cooling water and so on. The water
supply system is the same as in process water system.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 119
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Most part of the industrial water is circulating within the FGD system.
11.3.3.2.9 Instrument air system
There is one set of instrument air tank for two units in the FGD island which is mainly used for
bypass flue gas damper actuator and instrument cleaning in FGD island.
11.3.3.2.10 Auxiliary steam system
The auxiliary steam is of GGH cleaning with steam. The auxiliary steam comes from the plant
hot and cool section.
11.3.3.2.11 Vent, discharge system
The vent system consists of emergency slurry tank, ground channel and pit. When FGD in
normal operation, the overflow slurry or water and water shall be collected in the pit and then sent.
Emergency is used for storage of the slurry during the absorber overhauling and for
emergency storage.
After FGD system into operation, the cleaning of the absorber and connecting network among
all parts of the water drainage system will be done manually. Therefore, there will be few times in
actual application.
All overflow water in the system, except of the life sewage, will be recovered into the system.
The discharge system mainly consists of gypsum discharge pump, absorbing area pit pump,
emergency slurry return pump. When the circulating slurry PH and density in the absorber reaches
the discharge requirements, the gypsum discharge pump will start and discharge part of the slurry
into the reservoir.
11.3.4 Major equipment specifications
11.3.4.1 Boost fan
Item Parameters
Type
Remark
1. Equipment type TB BMCR ECR
- Fan efficiency 86.3% 85.7%
- Axial power 1999kW 1489kW - Fan total weight(exclusive of motor)
75000kg
- Fan speed 480r/min
- Shell material Q235 - Blade material
16MnR
Spraying nickel based carbon wolfram
- Front/rear guide plate material
Q235/Q345
Spraying nickel based carbon wolfram
- Wheel hub material 16MnR
- Axis material 35CrMo
2. Motor type YKK series
- Rated power 2100kW
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 120
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
- Rated voltage 6kV
- Rated voltage 480r/min
- Shell protection degree IP54
- Cooling mode Air-air cooling
3. Gearbox type Nil
4. Coupling type Form13 series
11.3.4.2 GGH
Type
Item
Type
Remark
1.GGH proper design
parameters:
⑴ Type Rotary GGH
⑵ Speed(working/cleaning) 1.2/0.6rpm
⑶ Effective anti-leak system
type Double channel sealing structure, low
leaking system
⑷ Pressure drop
Raw flue gas terminal (design value):
462Pa
Clean flue gas terminal (design value):
450Pa
⑸ Heat exchange element
Material Low carbon steel+enamel
Heat exchange surface 23500 m2(both sides)
Total height 780 mm
⑹ Shell
Material Q235-A
Lining material and thickness Scale resin, 1.5~2.0mm
⑺ Rotor
Main shaft material CORTEN
Cubicle frame material CORTEN
⑻ Motor and its driven device
Motor capacity 15KW
Rotary power consumption (shaft
power consumption)
11.6KW
Rated voltage 380V
Motor rated speed 1500rpm
Cooling mode Oil-bath
Gear box mode Gear driven
Gear box model B4VV09 or related model of indicated FLENDER
Date 2008-09-16
No. : QN1-SEC-G-04-TP-005
Page 121
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Type
Item
Type
Remark
brand
Coupling type Flexible coupling
Coupling model Undetermined
⑼ Sealing pad
Material 316L.TEFLON
⑽ Guiding bearing SKF Bearing type and model
Double row rolling
bearing/23060(CCK/W33 )
Lubrication mode Oil-bath
⑾ Supporting bearing SKF
Bearing type and model Thrust rolling bearing/29488E
Lubrication mode Oil-bath
2.Soot blower and its air
compressing system
⑴ Soot blower
Operating duty Online intermittent operation
Installation quantity 2X2
Installation location Raw flue gas upper and lower
Air consumption 5.5t/hr
LP water consumption 45t/h
LP water pressure 0.3~0.5Mpa
3.Sealing fan
Type and model Centrifugal fan /GMB16
Quantity 2X2
Flow 7500 Nm3/hr
Pressure 5000Pa
Shell/impeller material Carbon Steel/Carbon Steel
Medium Air
Motor type
Motor capacity 18.5kw
Motor insulation degree F(check as per B)
Motor protection degree IP55
4. Purifying fan
Type and model HMB 40
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 122
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Type
Item
Type
Remark
Quantity 1X2
Flow 63000Nm3/hr
Pressure 6500Pa
Shell/impeller material 316L
Medium Clean flue gas
Motor type
Motor capacity 185kw
Motor insulation degree F(check as per B)
Motor protection degree IF55
5.HP flush water pump
Type and model Ram pump GP5136
Quantity 1
Flow 160 L/min
Pressure 13Mpa
Shell/impeller material Cast steel/cast steel
Motor type
Motor capacity 50KW
Motor insulation degree F(check as per B)
Motor protection degree IP54
Inlet screen type and material Cylinder/stainless steel
11.3.4.3 Slurry circulating pump
Item Unit -Quantity set (3+1)×2
-Type Centrifugal pump -Shell material Anticorrosive alloy or lining rubber
-Impeller material Anticorrosive alloy -Anti abrasion material Anticorrosive alloy or carborundum
-Axis capacity kW 225/255/285/315 -Motor rated power kW 260/300/330/370
-Suction screen Yes/no Yes -Suction side pressure kPa 52
-Head kPa 15/17/19/21 -Volume flow m3/h 4254
-Solid content in medium % 20 -Sealing system type Mechanical sealing
-Sealing medium SiC
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 123
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
-Suction side valve material
Spheroidal graphite cast iron+EPDM/stainless
steel 11.3.4.4 Absorber
-Absorber type Spray tower -Flow direction(direct/reverse) Reverse
-Flue gas quantity before absorber (standard conditions, wet basis, Actual O2)
Nm 3/h 1,258,254
-Flue gas quantity after absorber (standard conditions, wet basis, Actual O2)
Nm3/h 1,304,741
-Design pressure Pa 5000 -Stop time for slurry circulation min 2.5 -Time for all slurry discharge h 13.4
-Flue gas speed m/s 3.94 -Time for flue gas in the absorber s 2.9
-Chemical measure ratio CaCO3/removed SO2 mol/mol 1.03 -Slurry reservoir solid content: Min/Max Wt% 15/25
-Slurry Cl content g/l <20 -Slurry pH 4.5~6.0
-Absorbing area diameter in absorber(or length x width)
m 11.6
-Absorbing area height in absorber m 7.5 -Slurry reservoir diameter(or length x width) m 11.6
-Slurry reservoir height m 5.3 -Slurry reservoir level normal/max/min m 4.8/5.3/5.8
-Slurry reservoir capacity m3 560 -Total height of absorber m 28.2
-Material ·Absorber shell/internal lining Carbon steel/1.4529
·Inlet flue gas duct material/thickness/length -/mm/m C276 clad plate/2/6.8 ·Spray layer/nozzle FRP/SiSic ·Mixer shaft/impeller DIN1.4529/DIN1.4529
·Oxidization air duct/nozzle DIN1.4529 -Spray layer number/layer space 4/2.0
-Nozzle number per layer 68 -Nozzle type Screw /air awl
-Mixer or mixing device quantity pic/tower 3 -Mixer or mixing device power kW 22
-Mixer specific power kW/m3 0.11 -Oxidization air nozzle quantity 3
-Absorber insulation ·Thickness mm ·Material
·External layer material ·Flue gas resistance in absorber(including mist
eliminator) Pa 1190
Mist eliminator -Location Inside tower
-Stage number Two -Height 3.65
-material polypropylene -Mist eliminator cleaning nozzle number pic/tower 420
Date 2008-09-16
No. : QN1-SEC-G-04-TP-005
Page 124
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
-Nozzle pressure Pa 0.2×10^6 -Nozzle material polypropylene
-Nozzle flow l/min 63 -Cleaning mode(constant/intermittent) intermittent -Average cleaning water consumption m3/h·set 1
-Instantaneous max cleaning water consumption m3/h·set 26.46 -Flue gas resistance in mist eliminator Pa 190
11.3.4.5 Oxidization fan
-Quantity set 1×2+1 -Type Roots -Head kPa 88
-Shaft power kW 113 -Motor rated power kW 128 -Inlet flow (per set) Nm3/h 3364
-Flow allowance % 10 -Outlet oxidization air temperature 130
- Fan inlet strainer type Sound absorbing pipe type - Fan inlet & outlet silencer type Sound absorbing pipe type
11.3.4.6 Slurry discharge pump
-Quantity Set (1+1)×2 -Type Centrifugal pump
-Shell material Anticorrosive alloy or lining
rubber -Impeller material Anticorrosive alloy
-Anti-abrasion material Anticorrosive alloy -Shaft power kW 7.7
-Motor rated power kW 11 -Suction side screen Yes/no Yes
-Suction side pressure kPa 50 -Head kPa 40
-Volume flow m3/h 60 -Sealing type Mechanical sealing
-With/without sealing material SiC 11.3.4.7 Limestone silo
-Quantity pic 1 -Effective volume m3 90
-Material Carbon steel -Height m 7
-Diameter m 5 -Anti-abrasion material 16Mn
-Discharge type Screw unloading -Discharge outlet Quantity 1+1
-Limestone silo top deduster Type/Quantity -/set Silo top type/1 11.3.4.8 Metal separator
-Quantity set 2 -Type Electromagnetic
11.3.4.9 Crusher
-Quantity set 2
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 125
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
-Type Hammer type -Capacity t/h 10~15
-Inlet particle size mm 80 -Outlet particle size mm ﹤
-Shaft power kW 22 -Motor power kW 30
11.3.4.10 Scale weighing belt conveyor
-Quantity set 2 -Capacity t/h 5~15 -Accuracy % 0.5
-Motor power kW 3.7 11.3.4.11 Wet type ball miller
-Quantity 2 -Type Wet type horizontal ball miller
-Rating per set % 100 -Handling capacity per set t/h 7
-Shell size m×m 2.5x7.5 -Anti-abrasion component Rubber lining
-Shaft power kW -Motor rated power kW 380
-Output size mm/% 0.63/90 11.3.4.12 Gypsum slurry cyclone
Gypsum slurry cyclone -Cyclone Quantity 1×2
-Cyclone Quantity per set -Standby Cyclone Quantity 1×2
-Cyclone material Carbon steel+Rubber lining/ polyurethane
-Feeding material solid content % 30 -Overflow solid content % 20
-Bottom flow solid content % 35 11.3.4.13 Gypsum miller slurry circulation tank
-Quantity set 2 -Effective volume m3 50
-Material Carbon steel -Anti-corrosion material Rubber lining
-Mixer Quantity set 1 -Mixer Material (Impeller/shaft) Carbon steel Rubber lining
-Mixer power kW 5.5 11.3.4.14 Miller slurry circulation pump
-Quantity set 1+3 -Type Centrifugal pump -Head kPa 200
-Capacity m3/h 90 -Medium solid content % 30
-Sealing type Mechanical sealing -shaft power kW 6.5
-Motor rated power kW 7.5 11.3.4.15 Limestone slurry reservoir
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 126
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
-Quantity set 1 -Effective volume m3 200
-Diameter m 6.77 -Height m 6
-Anti-corrosion material Synthetic resin -Mixer Quantity set 1
-Mixer material (Impeller /shaft) Rubber lining -Mixer power kW 22
11.3.4.16 Limestone slurry pump
-Quantity Set 2+2 -Type Centrifugal pump
-Shell /Impeller Material Anticorrosive alloy or lining rubber / Anticorrosive alloy
-Suction side pressure kPa 30 -Head kPa 450
-Capacity m3/h 30 -Medium solid content % 20
-Sealing type Mechanical sealing -Sealing material SiC
-Shaft power kW 6.5 -Motor rated power kW 7.5
11.3.4.17 Process water tank
-Quantity Set 1 -Effective volume m3 100
-Diameter m 5.8 -Height m 4.5
-Material Carbon steel+Synthetic resin lining
11.3.4.18 Process water pump
-Quantity set 1+1 -Type Centrifugal pump
-Shell material Spheroidal graphite cast iron -Impeller material Spheroidal graphite cast iron
-Shaft power kW 26 -Motor rated power kW 30
-Suction screen Yes/no No -Suction side pressure kPa 30
-Head kPa 400 -Volume flow m3/h 120 -Sealing type Mechanical sealing
-Sealing material SiC 11.3.4.19 Mist eliminator cleaning pump
-Quantity set 1×2 -Type Centrifugal pump
-Shell material Cast iron -Impeller material Cast iron
-Shaft power kW 30 -Motor rated power kW 45
-Suction screen Yes/no Yes
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 127
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
-Suction side pressure kPa 42 -Head kPa 60
-Volume flow m3/h 156 -Sealing type Mechanical sealing
-Sealing material SiC 11.3.4.20 Emergency slurry reservoir
-Quantity set 1 -Effective volume m3 560
-Diameter m 9 -Height m 9
-Anti-corrosion material Synthetic resin -Mixer Quantity set 1
-Mixer material (Impeller /shaft) Anticorrosive alloy or carbon steel+lining rubber / Anticorrosive alloy
-Mixer power kW 22 11.3.4.21 Emergency slurry return pump
-Quantity set 1 -Type Centrifugal pump
-Shell /Impeller material Anticorrosive alloy or carbon steel+lining rubber / Anticorrosive alloy
-Suction side pressure kPa 520 -Head kPa 200 -Flow m3/h 60
-Medium solid content % 20 -Sealing type Mechanical
-Sealing material SiC/alloy -Shaft power kW 6.5
-Motor rated power kW 7.5 11.3.4.22 Absorber water discharge pit
-Quantity set 1×2 -Effective volume m3 17
-material Concrete -anti-corrosion material Synthetic resin lining
-Mixer Quantity set 1 -Mixer material (Impeller /shaft) Anticorrosive alloy or carbon
steel+lining rubber / Anticorrosive alloy
-Mixer power kW 3.7 11.3.4.23 Absorber water discharge pit pump
-Quantity set 4 -Type Vertical pump -Head kPa 200
-Capacity m3/h 60 -Shaft power kW 4.8
-Motor rated power kW 5.5 11.3.4.24 Limestone slurry preparation area water discharge pit
-Quantity set 1 -Effective volume m3 17
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 128
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
-Material Concrete -anti-corrosion material Synthetic resin lining
-Mixer Quantity set 1 -Mixer material (Impeller/shaft) Anticorrosive alloy or carbon
steel+lining rubber / Anticorrosive alloy
-Mixer power kW 2.2 11.3.4.25 Limestone slurry preparation area water discharge pit pump
-Quantity set 1 -Type Vertical -Head kPa 300
-Capacity m3/h 30 -Shaft power kW 3.0
-Motor rated power kW 3.7 11.3.4.26 Instrument air tank
-Quantity set 1 -Volume m3 3
-Diameter m 1.4 -Height m 2.8
-Working pressure MPa 1 11.3.4.27 Miscellaneous use air tank
-Quantity set 1 -Volume m3 4
-Diameter m 1.6 -Height m 2.8
-Working pressure MPa 1 11.4START-UP OF DESULFURIZATION SYSTEM
11.4.1 Acceptance and test after maintenance
11.4.1.1 Acceptance after overhaul
11.4.1.1.1 After overhaul of the desulfurization devices, institute responsible for the overhaul
work should offer overhaul summary, acceptance report, deviation report of the
equipment and detailed explanation to the operation department.
11.4.1.1.2 The operation department should organize its managing and operating personnel
to attend the overhaul acceptance above level 2; to attend every stand-alone and
system pre-commissioning of main and auxiliary equipment, and record various
primary data, confirm the data is right in the range regulated by the specification; to
attend pre-commissioning, test and confirm the DCS control system is in right
logical relation while having normal protection and interlock movement.
11.4.1.1.3 The entire acceptance file before start-up should be kept in generating department
as file materials.
11.4.1.2 Inspection and acceptance after overhaul
11.4.1.2.1 Once the overhaul work finished, overhaul personnel and tools should be
evacuated from the operating field, safeguard measures cancelled, false work
cancelled, no sundries can be saw on the equipment, ambient environment,
passway and the lighting should be satisfying.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 129
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.4.1.2.2 Foundation bolts and coupling wheel screw of rotating equipment should be
tightened, hood of the coupling wheel should be complete and tightly installed;
qualified lubrication, oil level is above oil gauge’s centerline but between the upper
limit red line and lower limit red line, no leakage in the oil system, clear and
complete oil gauge and oil level mirror, try the oil tank heater and confirm it’s in
normal operating; clear, unblocked and controlled shaft cooling water; complete
inlet/outlet damper(valve) with flexible switches on close position; complete and
tight grounding of the motor; and no things around is to interfere the start-up.
11.4.1.2.3 No deviation for the equipment’s appearance, good insulation, correct and clear
equipment’s name plate, color ring on the pipe, rotating direction and medium’s
flowing direction.
11.4.1.2.4 Inspect the flue duct, absorber, mist eliminator, each water tank and pit, reservoir,
boost fan, GGH, and make sure it is clean inside without foreign matters & medium
along with intact anti-corrosion layer. After inspection, manhole and vent valve is
tightly closed.
11.4.1.2.5 All manual, pneumatic, motorized air doors and valve should be tight, flexible in
switch, complete in travel and of no leakage on dynamic & static sealing area. The
local switch indications of all pneumatic and motorized valves are in line with the
displays of DCS, which are at the off position.
11.4.1.2.6 The tightness of al mechanical driven V shape belt is appropriate.
11.4.1.2.7 Upon the completion of DCS commissioning, the configuration parameters are
correct and all instrument power supply is put in use. All automatic, protection and
alarming device is correctly launched after commissioning. The installation of local
instruments and testing point finishes with firm wiring and correct position. The
measuring and testing of transmitters and transformers are in normal conditions.
All testing data and acceptance procedures are complete.
11.4.1.2.8 The local control cabinet is in normal operation and the indication light testing is in
order.
11.4.1.2.9 The gauges for distribution device are complete, intact and verified. The terminal,
plug and socket are of no abnormal looseness and mobilization.
11.4.1.2.10 All switches and contactors are of clear and correct switch-in & off indication. They
are qualified in switch-in & off testing with switch at testing positions.
11.4.1.3 Testing after overhaul
11.4.1.3.1 Trial operation of mechanical equipment
z The trial operation of mechanical equipment is to confirm that there is no abnormal
condition before the formal operation of the FGD system. The inspection and
measuring of the current, vibration, temperature and sound of the motor and
mechanical equipments as well as the performance of the design values are done in
this trial operation. Any abnormal conditions are to be eliminated before normal
start-up. At the same time of trial operation , the inspection and testing for equipment
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 130
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
start up, shut down, interlock procedure, sequence, time, alarm and trip preset
values shall be done.
z Before trial operation of all mechanical equipments, the motors should be
independently operated for 1-4 hours with unfastened coupling connecting screw.
After confirmation on correction of its vibration, temperature rise, current and
direction, the coupling connecting screw should be connected. The rotor is in normal
operation under related torque without stuck, unsmooth or abnormal sounds. The
insulation resistance should be confirmed qualified before trail operation and power
supply of the motors.
z The trial operation of conveyor belt and feeder should be conducted with no load.
The trial operation of steel ball crusher should be done in phased manner from no
load to full load gradually as per the requirements in the manual and the retightening
of its steel tiles should be done by the installation workers during the process.
z The trial operation of the rotary machinery should continuously operate for 1-4 hours
in principles. The operation can be extended if the person in charge thinks it is
necessary, but the reasons and results for doing the same should be clearly noted
down.
z During the trial operation period, the engaged equipments should be regularly
inspected, measured and recorded: motor current (on/off load), bearing temperature,
bearing vibration, noise, inlet & outlet pressure, rotary speed, current & its flow curve
generated by damper (air door, valve) open degree variation, equipment interlock,
alarm & protection, and to confirm whether they are in the normal value range.
z The remote control of all air door, damper, pneumatic & motorized valve should be
agile in action and properly switched to on/off positions.
z During the trial operation, the thermal control persons should inspect, check and
modify the travel & torque of motorized actuator; the accordance between the actual
open degree of valve & air door damper and the display on DCS screen; the
correctness of interlock logic; the correctness of protection action.
z During the trial operation, the electrical persons should observe and inspect the
operation conditions of the transformer, switches & motors, record all data; examine
and check the protection setting, electrical interlock & emergency switch.
11.4.1.3.2 Preparation before equipment trial operation
z Examine & test the start up/shut down circuit, interlock circuit and control circuit to
make sure they are in normal conditions; the testing of overload relay and earthing
relay drivers is done;
z Test the insulation resistance of motors & cables and supply the power after
resistors’ qualification;
z Supply power for the thermal instruments & meters and check whether they are in
normal operation;
z The cleaning work of miscellaneous and instrument air pipes is done, and the
internal & external obstacle are completely removed;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 131
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
z The water tank and reservoir is internally clean with industrial water fed at indicated
level (above permitted start up level), confirm the accordance between the level
gauge and actual testing value, and no leakage;
z The lubrication oil for all rotary equipments are qualified in testing; the lubrication oil
level for all equipments is normal; all cooling water can go smoothly; the oil
temperature of start up oil tank heater or start up oil cooler is in the prescriptive
range;
z The on/off speed correction of pneumatic valve regulated by speed controller is
done; its operation normality is confirmed by using manual switch;
z For belt driven equipments, the adjustment & correction of the capstan and the
follower is done; the qualified belt has been installed; the belt tightness is suitable;
the tightness should be measured again and adjusted after completion of the
machinery’s trial operation;
z The control relay has been set to standard values.
11.4.1.3.3 Matters to be taken care in trial operation
z When start the rotary equipments, besides the regular protection measures, the
commissioning persons should stand at the shaft direction position of the
equipments to avoid accidental injury.
z In the specific time period, the start up times of HV motors can not exceed the
provision in the regulation. The on load start up times of AC motors should be in line
with the products technical regulation. If there is no clear regulation in products’
technical conditions, the following Manual shall be followed:
z The start up can be done twice in cold state, with interval not less than 5 mins.
z The start up can be done once in hot state; when in accident handling & the start up
time for big motors is less than 2-3s, it can be restarted again.
z Prevent the body and the tools from contact with the rotary parts.
z Before the trial operation, the handling preparative proposals for abnormal interlock
or protection action conditions should be though over carefully to insure the
equipment and personal safety.
z The trial operation should be stopped when after start up obvious abnormal
conditions and high possibility of equipment damage & personal injury occur. During
the machinery trial operation, if there are abnormal sounds or vibration or
temperature rise, the measures such as inspection, retighten foundation bolts,
appropriate addition or change of lubrication oil and so on should be done, under the
premises of personal & equipment safety and the monitoring of the progress should
be kept on. If it is still abnormal, the fault equipment should be stopped. The
equipment can not restart for trial operation until the reasons are found out and the
problem is solved.
z After the completion of the trial operation, all left medium in equipment and pipes
should be discharged as much as possible. If the equipments shall not be in
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 132
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
operation right after trial operation, the power supply of motors and other electrical
equipments should be cut off and necessary maintenance is to be done.
11.4.1.3.4 Testing items for equipments’ trial operation
z The time period from start-up to back and the current value under no-load and load
changing conditions of the large-scale HP motors and equipments should be
measured and recorded when start-up for the first time. The start-up, operation and
shut down of the motors and equipments should follow the orders of the personnel
who measure the current.
z Inspect and record interlocking action sequence and time of equipments; inspect
and test the alarm and interlock protection setting value; inspect and test emergency
button.
z Check whether the current value is in the regulated range; whether the vibration and
temperature rise of the machinery and motors is in the regulated range; whether the
noise is normal; whether there is peculiar smell, leakage of gas or fluid; whether the
changes of the water level of the water tank and pond is in the regulated range;
whether the operation of the motorized or pneumatic valves are normal; record with
details.
11.4.1.3.5 Normal operation standard of motors and mechanical equipments
z The operation time of motors and mechanical equipments is 1-4 hours, during which:
bearing temperature rise: gliding bearing temperature should not exceed 80;
rolling bearing temperature should not exceed 95.
z No unexpected noise should occur during the operation of the machinery; machinery
vibration should be in the normal range.
Synchronous speed
(r/min) 3000 1500 1000 750 and below
Double amplitude value
(mm) 0.05 0.085 0.10 0.12
z The motor’s operation current should exceed the rated value on the name plate.
z If there is specific regulation of the above parameters from the manufacturers, then
these Manual will be followed.
11.4.1.4 Simulative test of water circulation
11.4.1.4.1 Aim of the water circulation test: using water instead of limestone slurry and
gypsum slurry, simulative operations will be carried out to all equipments of FGD
system, inspecting and confirming the system rigour and stability, as well as the
desulfurization control system, start-up and shut down sequence, related interlock
and protection, so that the potential equipment defects and errors might occur after
formal start up of FGD system can be discovered in advance.
11.4.1.4.2 The scope of water circulation tests: equipments and systems for handling
limestone slurry and gypsum slurry.
11.4.1.4.3 The qualified standard for water circulation test:
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 133
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
z To conduct preliminary modifications for control system and confirm the correctness
of the logic relationship;
z To confirm the control system, its start-up & shutdown operation sequence, related
working parameters, interlocks and protection in normal conditions;
z The equipments are in normal operation without leakage and the system is water
balanced;
z To confirm the flow characteristic curve of all control valves.
11.4.1.4.4 The preparation of water circulation test
z Sufficient qualified water source;
z DCS system is qualified with application conditions;
z All instruments correction, testing & interlock, protection examinations are
completed;
z The trial operation of all pumps and mixers machinery related to water circulation are
accomplished;
z The dampers of original and clean flue gas are insulated from the control system;
z The water circulation system is qualified with all start-up conditions.
11.4.1.4.5 Matters to be taken care of during water circulation test:
z The water circulation tests should not influence the boiler safety operation. The
bypass damper fixings should be all open. The dampers of original and clean flue
gas should be closed. Its sealing fans should be operating. The FGD system is
insulated from the boiler flue gas system.
z The levels of absorber, limestone slurry tank and filtrate tank should be closed
monitored during water circulation tests. Due to different liquid densities, the level
displayed by DCS might be a little bit higher than the actual level in absorber and
other equipments. The operating personnel should master the actual level of the
absorber in line with various situations.
11.4.1.4.6 The start-up operation of water circulation tests and operations requiring water
circulation tests:
z Injecting the water till normal level for the following equipments:
Equipment name Unit Absorber m Limestone slurry reservoir m Industrial water tank m Gypsum buffer tank m Filtrate tank m
z When there is no system and equipment fault, maintenance, cleaning signals, all
liquid levels are in line with start up requirements, all inlet and outlet doors are at the
pre-start state, individual equipment can meet the start up requirements after
inspection, the following equipments will be started in DCS system:
Industrial water pump;
Absorber mixer;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 134
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Filtrate tank mixer;
Limestone slurry tank mixer;
Absorber pit mixer;
Gypsum slurry buffer tank mixer;
Absorber gypsum discharge pump;
Gypsum eddy station charge pump;
Sewage eddy station charge pump;
Absorber slurry discharge pump;
Absorber slurry circulation pump;
z The control room operators should get the permission from the local inspection and
side station monitoring personnel before start up the above equipments in
sequence.
z After the normal start up completion of each equipment, the related inlet & outlet
doors should be opened and stopped at the required positions through automatic or
manual remote operation. Until inspectors’ confirmation on the successful start up
and normal operation of this equipment, can the start up of the next equipment be
arranged.
z After all equipments normal start up, the operating conditions at every positions
should be regulated so that the flow, water level and pressure correspond to the
system water balance requirements and the machinery is in sound operation.
z After completion of the testing, the testing equipments should be stopped one by
one in the sequence which is reverse of the start up and the related valves should be
closed.
z Each characteristic curve and words obtained in the testing should be recorded and
kept in files.
11.4.1.5 Major equipment emergency button test
11.4.1.5.1 After the overhaul of FGD system, the emergency buttons of each major
equipment in FGD system shall be tested to examine and ensure the operation
withdrawals under emergency conditions.
11.4.1.5.2 Test procedure:
z Pull the switches of the engaged equipments to the testing positions;
z Enforce all related conditions in DCS manual manner to meet the start up
requirements of the testing equipments;
z Close the switches of all individual 6KV equipments on CRT;
z Press the emergency button close to the equipment;
z Observe the equipment switch which should be normally disjunct;
z Resume all related forced conditions in testing to the normal original state.
11.4.1.6 Flue gas test
11.4.1.6.1 Test purpose
z The initial flue gas test is to conduct simulative operation of all equipments in flue
gas system and absorber system, inspecting and confirming the system rigour and
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 135
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
equipment reliability as per the design requirments, as well as onece more
examination of the desulfurization control system, start-up and shut down sequence,
related interlock and protection, so that the potential equipment defects and errors
might occurr after formal start up of FGD system can be discovdered in advance.
Particularly, a preliminary estimation of each flue gas damper’s reliability, fexibility,
rigour & influence to the boiler & unit and the standardrization & check of each
instrument testing point as well as a comparison with the design values can be done
through the test, making good preparation for the system commissioning and normal
placing in operation in future.
11.4.1.6.2 Test conditions
z FGD system has passed the water circulation test: each tank, reservoir, pipe, valve
and all equipments are qualified without leakage, and environment, passage,
illumination and communication conditions can meet with the requirements;
z Each equipment in FGD system has been proved to be qualified in individual tests;
z Each subsystem in FGD system instruments, control sequence, thermal signals,
interlock protections has been installed well and tested to be qualified;
z Common systems can be normal operating and standby, including water, power,
steam, air and etc;
z The absorber is ready with gypsum slurry; the limestone slurry reservoir is ready
with enough slurry of qualified density;
z The FGD system has been proved to be qualified in “emergency shut down” button
test.
11.4.1.6.3 Test procedure
z Report to the operating manager and obtain the permission;
z Start cleaning pump, compressing air system, GGH system with its sealing fans
successively;
z Start gypsum discharge pump and limestone slurry pump for circulation;
z Start slurry circulation pumps (two sets at least) and oxidization air system;
z Close the evacuation door on the top of the absorber and open the clean flue gas
damper;
z Start the original flue gas damper;
z Start the boost fan;
z Adjust the boost fan guiding blades, and slowly close the bypass damper door
depending on the situations;
z Put mist eliminator cleaning, PH device cleaning and limestone slurry feeding
system in service.
11.4.1.6.4 Test items
z Inspect, measure and correct the site obtained values with the display values on
CRT including flue gas system inlet oxygen content, SO2, flue gas temperature, flue
gas flow, dust content, inlet pressure and etc;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 136
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
z Inspect, measure and correct the site obtained values with the display values on
CRT including flue gas system outlet oxygen content, SO2, flue gas temperature,
pressure differential & temperature between GGH original flue gas side & clean flue
gas side, GGH outlet pressure and etc;
z Inspect, measure and correct the site obtained values with the display values on
CRT including slurry PH in the absorber, process water consumption, limestone
consumption, power consumption, the influence of open degrees of all damper
doors & boost fan guiding blades to the boiler & desulfurization system and etc;
z Dynamically verify the bypass damper door quick open function when the boost fan
trip.
11.4.1.6.5 Matters to be taken care of in the test
z Conduct accident anticipations and measures to keep the accidents away for the
boost fan, inlet & outlet damper doors of FGD system; the boiler operating personnel
should conduct accident anticipations when the testing bypass damper door is
closed, and the test personnel should take other measures to ensure the quick open
action of the bypass damper door;
z Adjust slowly the boost fan guiding blades to reduce the negative influence on boiler
negative pressure;
z Record the site measured and control displayed parameters on time;
z Reinforce the going-around inspection and monitoring of the system trial operation;
z Each characteristic curve and words obtained in the testing should be recorded and
kept in files.
11.4.2 Inspection and preparation before start up of FGD system
11.4.2.1 Cold standby state start up: when desulfurization device in operation for the first time
after installation, or long time shut down for overhaul or other reasons, all the chemical
tanks are without absorbent and water, all the mechanical equipments are out of
operation, and all the operations start from “OFF” state.
11.4.2.2 Hot standby state start up: when desulfurization device experiences short time shut
down for debugging maintenance or other reasons, flue gas removing system is not in
operation, and the other systems are under start-up operation of standby or operating
state.
11.4.2.3 Inspection before start up of FGD system
11.4.2.3.1 After confirming the accomplishment of the maintenance and operation orders,
safety measures are removed; field sundries be cleared up with unblock passages,
sufficient illumination, safe & stable handrails & stairs, clean channels, floors &
equipments, and complete covers.
11.4.2.3.2 For each rotary equipment, the oil level is normal with good quality oil, clear &
intact oil gauge & oil level mirror and no leakage; the cooling water is unblocked
and the water temperature is normal.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 137
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.4.2.3.3 All signs and marks for the revisions of the equipment name, serial number, color
ring, medium flow direction, due to the maintenance, changes of the equipments or
system, or other reasons, should be clear, intact and correct.
11.4.2.3.4 Inner space of the flue duct, earth pit, channel, tanks, towers, bunkers and GGH
should be cleaned already; intact anti-corrosion layer; no left over; manholes are
closed after inspection; intact insulation of the flue duct and the pipes.
11.4.2.3.5 Put the DCS system in operation and the power supply for each instrument in
operation; the parameters are correct in each group and state; the measuring
indications and regulating actions are normal; field testing points, instruments,
transmitters and sensors are in good operation state and at the right positions.
11.4.2.3.6 Measure the insulation resistance of the electrical equipment and supply the power
after a qualified test result.
11.4.2.3.7 Mechanical and electrical equipment having normal appearances with foundation
bolts, motor connection and grounding wiring in safe and stable state, complete
shield, normal installation of connector and fasteners.
11.4.2.3.8 Normal air compressing system of FGD system with pressure of 0.5--0.8MPa.
Make sure that all the steam source doors of the start up actuators are at open
position.
11.4.2.3.9 Switches of air doors and valves should be flexible and on the right position.
Inspect each air door and valve of every system according to the requirements
before the start up of the FGD system, and then adjust the doors & valves to the
specified position.
11.4.2.4 The following conditions should be satisfied before the start up of the FGD system:
11.4.2.4.1 Qualified crystal seeds have been injected into the absorber.
11.4.2.4.2 The limestone slurry preparation system is under normal operation and can
produce qualified limestone slurry.
11.4.2.4.3 The unit is under normal operation with ESP, whose outlet flue gas turbialty can
meet the requirements of the FGD system.
11.4.2.4.4 The water level of the process water tank is normal and can guarantee the
constant water supply of the process water.
11.4.2.5 Absorber slurry crystal seeds make up & install conditions and slurry charge method:
11.4.2.5.1 The process water pump can work properly and the process water tank is filled
with water. The commissioning of each protection and interlock in process water
system has completed. To check whether the absorber level gauge is at the
pre-start up position.
11.4.2.5.2 Inspect the inside of absorber, emergency slurry reservoir (tank) and its water
discharge pit is clean without sundries. Each manhole is tightly closed. The
evacuation valve door to the earth pit is closed. Suitable screen (over 6mm can not
pass) is installed at the emergency slurry reservoir earth pit inlet to prevent the
entry of caking gypsum or sundries. Instruments should be prepared
simultaneously including measuring bottle, density meter, gablock and etc. The
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 138
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
trail operation of emergency slurry tank discharge pit pump and emergency slurry
tank discharge pump have been finished. The commissioning of protection and
interlock has completed.
11.4.2.5.3 The air pressure of the compressing air tank is normal. The commissioning of each
manual and pneumatic door has been completed and doors can work properly.
11.4.2.5.4 The trial operation of slurry circulation pump, gypsum discharge pump and
oxidization fan have completed. The commissioning of the protection and interlock
has finished. All mixers have accomplished the trial operation.
11.4.2.5.5 The clean industrial water is injected into the emergency slurry reservoir from the
absorber up to around 4 meters. The emergency slurry reservoir mixer should be
started.
11.4.2.5.6 Check the valve from the gypsum slurry discharge pump to ash slag front reservoir
is closed, the absorber earth pit pump outlet manual door is closed, the valve to
emergency slurry reservoir is closed and the circulation pipe manual door of the
gypsum slurry discharge pump is open.
11.4.2.5.7 The gypsum crystal seed which is 10% of the gypsum is fed into the emergency
slurry reservoir uniformly to keep the density of slurry at around 10%.
11.4.2.5.8 Start the gypsum slurry discharge pump, open the valve from the gypsum
discharge pump to emergency slurry reservoir and inject water into the emergency
slurry reservoir slowly.
11.4.2.5.9 Check the valve from the emergency slurry pump to the ash slag reservoir is
closed and the shaft sealing water is normally put into service.
11.4.2.5.10 Start the emergency slurry pump, open the outlet door manually and inject the
gypsum crystal seed slurry into the absorber.
11.4.2.5.11 When the absorber level is above 3 meters, the 4 mixers should be started
successively.
11.4.2.5.12 Inject the water continuously and inject the gypsum crystal seeds uniformly at the
rate of 10% gypsum into the emergency slurry reservoir, keeping the slurry density
at around 10%. Maintain the emergency reservoir level higher than the trip position
of mixer and emergency slurry pump until the absorber level reaches 9.63 m, then
stop injecting the gypsum crystal seeds & emergency slurry pump and close its
outlet door.
11.4.2.5.13 Discharge the gypsum crystal seeds in the emergency slurry pump pipe
completely and conduct reverse cleaning when necessary.
11.4.2.6 The FGD system whole set start up
11.4.2.6.1 To shorten the start up time as much as possible, several function groups should
be started in parallel and operated under standby state. The FGD system device
should be put in service as per the following order: (If the system starts after a
short time shut down and the process water pump and mist eliminator cleaning
water pump do not stop during the short shut down, the related steps can be
skipped.)
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 139
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
Special name KKS Action
Limestone slurry supply system drawing 06019S-J-03-13 (absorber area slurry supply pipe part) Limestone slurry non return valve
*HTK71 AA901
The switch should be
flexible Limestone slurry regulating valve up stream
isolation valve
*HTK71 AA501
Open
Limestone slurry regulating valve down stream
isolation valve
*HTK71 AA502
Open
Limestone slurry regulating valve bypass
orifice plate inlet isolation valve
*HTK71 AA503
Close
Limestone slurry regulating valve bypass
orifice plate outlet isolation valve
*HTK71 AA504
Close
Slurry supply pipe outlet to circulation pipe 2#
inlet isolation valve
*HTK71 AA510
Open (circulation pump in operation)
Slurry supply pipe outlet to circulation pipe 1#
inlet isolation valve
*HTK71 AA511
Open (circulation pump in operation)
Limestone slurry to circulation pipe 2# inlet
isolation valve
*HTK71 AA520
Open (circulation pump in operation)
Limestone slurry o circulation pipe 1# inlet
isolation valve
*HTK71 AA521
Open (circulation pump in operation)
Absorber system drawing 06019S-J-03-02 & 06019S-J-03-03 Absorber level gauge cleaning isolation valve
*HTD10 AA213
*HTD10 AA214
*HTD10 AA214
Close
Close
Close
Absorber level gauge isolation valve
*HTD10 AA303
*HTD10 AA304
*HTD10 AA305
Open
Open
Open
Absorber evacuation valve *HTD10 AA202 Close
Absorber evacuation tank cleaning valve *HTD10 AA203 Close Absorber lower mixer cleaning pipes isolation
valve
*HTD10 AA204
*HTD10 AA205
*HTD10 AA206
Close
Close
Close
z Process water pump;
z Mist eliminator cleaning water pump;
z Absorber slurry circulation pump;
z Flue gas duct;
z Oxidization fan;
z Limestone slurry conveying system.
11.4.2.6.2 The positions of the related manual valves should be checked as per the following
table before put the system in service:
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 140
Rev.: A
Special name KKS 号 Position
FGD process water inlet master valve Open
Process water tank water discharge valve Close
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Special name KKS Action Absorber low position mixer cleaning pipe
isolation valve
*HTD10 AA204
*HTD10 AA205
*HTD10 AA206
Close
Close
Close Mist eliminator pressure differential measuring
pipe isolation valve *HTD10 AA301
*HTD10 AA302 Open
Open Mist eliminator pressure differential measuring
pipe cleaning pipe isolation valve *HTD10 AA211
*HTD10 AA212 Close
Close
Gypsum slurry sampling valve *HTL11 AA401 Close
Absorber to gypsum slurry buffer tank *HTL11 AA501 Open
Absorber to emergency tank isolation valve *HTL13 AA501 Close
Gypsum slurry PH value measuring bypass
outlet manual valve
*HTL30 AA501
Open
PH gauge 1 cleaning pipe inlet isolation valve
PH gauge 2 cleaning pipe inlet isolation valve *HTL30 AA511
*HTL30 AA512
Open
Circulation pump inlet pipe pressure gauge
isolation valve
*HTF11 CP301
*HTF12 CP301
*HTF13 CP301
Open
Circulation pump outlet pipe pressure gauge
isolation valve
*HTF11 CP510
*HTF12 CP510
*HTF13 CP510
Open
Oxidization air system 06019S-J-03-10
#1 oxidization fan outlet manual valve *HTG11 AA510 Open
#2 oxidization fan outlet manual valve *HTG12 AA510 Open
#1 oxidization fan outlet non return valve *HTG11 AA901 Flexible open
#2 oxidization fan outlet non return valve *HTG12 AA901 Flexible open
Oxidization air main pipe to absorber manual
valve *HTG50 AA501 Open
Oxidization air main pipe to GGH dry manual
valve *HTG51 AA501 Close
Instrument valves for each pressure,
temperature gauges Open
11.4.2.6.3 Put the process water system in service
z Check and ensure the process water tank is not less than 3.0 m;
z Check the related system valves is at the required positions as per the following
table:
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 141
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Special name KKS 号 Position
#1 process water pump inlet isolation valve Open
#2 process water pump inlet isolation valve Open
#1 process water pump inlet isolation valve Open
#2 emergency process water pump inlet isolation
valve Open
#1 process water pump outlet isolation valve Open
#2 process water pump outlet isolation valve Open
#1 process water pump outlet isolation valve Open
#2 emergency process water pump outlet isolation
valve Open
Master water supply valve to emergency slurry tank
area Open
Emergency slurry return pump cleaning valve Close
Emergency slurry mixer cleaning valve Close
Emergency slurry tank area ground cleaning valve Close
Turn-off valve of water supply to Limestone slurry
tank area Open
Mater valve of other water supply to milling &
preparation workshop Open
Master water valve at dehydration process building
first floor Open
Water supply valve for vacuum pump unit groups Open
Desulfurization sewage treatment system
hydrochloric room water valve Close
Desulfurization sewage treatment dosing unit area
master water valve Close
Cleaning valve at neutralization, coagulation aids
and precipitation tank Close
Mater cleaning valve at gypsum eddy station sewage
eddy pump Open
Master water valve for absorber area slurry pump,
mixers and etc Close
Cleaning turn-off valve to GGH LP water Close
Cleaning turn-off valve to absorber mist eliminator Close
Water supply valve to GGH HP cleaning water pump Open
z Start #1 or #2 process water pump;
z Put the standby pump interlock in service;
11.4.2.6.4 Start up of mist eliminator cleaning water pump:
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 142
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
z Check and ensure the process water tank is not less than 3.0 m;
z Check the related valves is at the required positions as per the following table:
Special name KKS Position
#1 mist eliminator cleaning water pump inlet isolation valve Open
#2 mist eliminator cleaning water pump inlet isolation valve Open
#1 mist eliminator cleaning water pump outlet isolation valve Open
#2 mist eliminator cleaning water pump outlet isolation valve Open
#1 mist eliminator cleaning water pump inlet isolation valve evacuation
valve Close
#2 mist eliminator cleaning water pump inlet isolation valve evacuation
valve Close
Master door from mist eliminator cleaning water pump to #1 FGD mist
eliminator Open
Master door from mist eliminator cleaning water pump to #1 FGD mist
eliminator Open
z Start #1 or #2 mist eliminator cleaning water pump;
z Put the standby pump interlock in service;
11.4.2.6.5 Put the absorber slurry circulation pump in service:
z Check and ensure the absorber level is not less than 5.0m;
z Check and ensure the start up interval with other 6Kv equipment in the system is
over 60s;
z Invoke the slurry circulation pump start up function group or operate as per the
following sequence:
a) Close the slurry circulation pump evacuation door and ensure the action
completeness;
b) Start the slurry circulation pump inlet motorized door and ensure the action
completeness;
c) Start the slurry circulation pump in 60s delay manner and observe the current which
should return to the normal value in time.
11.4.2.6.6 Put the flue gas system equipment in service:
z The following conditions have to be fulfilled before put the flue gas system in service:
a) The boiler ESP has been put in service normally;
b) The boiler ID fan is operating normally;
c) The boiler combustion is normal without heavy oil aiding;
d) The limestone slurry preparation system can normally supply the limestone slurry
continuously;
e) The absorber system has qualified conditions for put in service and 2 sets or above
slurry circulation pump is in operation.
z Invoke the flue gas system start up function group or operate as per the following
sequence:
z Start the GGH sealing fan;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 143
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
z Start the GGH major or standby driven motor and wait for the return of signal for
normal GGH speed;
z Open the low leakage fan inlet damper;
z Close the low leakage fan outlet damper;
z Start the low leakage fan;
z Open the low leakage fan outlet damper;
z Put the GGH rotor low speed signal interlock in service;
z Open the clean flue gas damper;
z Close the motorised absorber evacuation buffer fly valve;
z Open the original flue gas damper;
z Put the boost fan static blade actuator at the manual position and adjust its open
degree to less than 10%;
z Check and ensure the following start up permission conditions are fulfilled:
a) The clean flue gas damper is open;
b) The original flue gas damper is open;
c) GGH is in normal operation with speed not less than 0.75 r/min;
d) 2 sets or above slurry circulation pumps are in operation;
e) The temperature of boost fan bearing is less than 70;
f) The temperature of boost fan main motor bearing 1# and 2# is less than 75;
g) The main motor winding temperature is normal;
z Start 1# or 2# bearing cooling fan;
z Start boost fan main motor;
z Increase the open degree of static blade manually depending on the boost fan inlet
negative pressure situation after return of boost fan main motor current;
z Close the bypass damper gradually and adjust the open degree of static blade
manually to maintain the boost fan inlet pressure around -200Pa;
z Set the boost fan pressure close circuit control setting value (bypass damper
pressure differential is zero or the boost fan inlet pressure is -200Pa) and put the
boost fan static blade automatic control mode in service.
11.4.2.6.7 Put the oxidization fan in service
z Check and confirm all manual valves on air duct from the oxidization fan outlet to
absorber are open;
z Open the oxidization fan bypass unloading valve;
z Open the oxidization fan sound arresting covering fan;
z Start the oxidization fan and observe the current to return in 20-6S normally;
z Close the oxidization fan bypass unloading valve.
11.4.2.6.8 Put the limestone slurry supply system in service
z Check the related valves is at the required positions as per the following table:
Special name KKS Position
Isolation valve before limestone slurry supply pipe density gauge Open
Isolation valve after limestone slurry supply pipe density gauge Open
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 144
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Special name KKS Position
Limestone slurry supply pipe density gauge bypass valve Close
Limestone slurry supply pipe density gauge valve group evacuation
valve Close
Isolation valve before absorber slurry charge regulating door group Open
Isolation valve after absorber slurry charge regulating door group Open
Absorber slurry charge regulating door group bypass valve Close
Absorber slurry charge regulating door group evacuation valve Open
Primary door for all measuring instruments Open
z Close the motorized evacuation valve at the limestone slurry pump inlet;
z Set the open degree of the absorber slurry charging regulation door below 30%
manually;
z Close the motorized cleaning valve on the limestone slurry pump outlet pipe;
z Start the limestone slurry pump;
z Start the limestone slurry pump outlet motorized door;
z Put the standby limestone slurry pump interlock in service;
z Set the absorber slurry PH automatic control setting value at 5.6 and put the
absorber gypsum slurry PH valve close circuit control.
11.5MONITORING AND REGULATION IN FGD SYSTEM OPERATION
11.5.1 Major purpose and task of monitoring and regulation
The major purpose and task of monitoring and regulation is to ensure the continuous steay
operation of the FGD system, the qualified desulfurization efficiency, the long term application life
of the equipments, the safe operation of the equipments under accident conditions, and maintain
the FGD system in favourable working conditions through corrrect monitoring and regulation of the
FGD system and the equipments.
11.5.2 Crucial control parameters and limitations in the FGD system
11.5.2.1 Absorber inlet flue gas density control
As per the design requirement, the soot density at the FGD system inlet should be controlled
below 370mg/Nm3, (i.e. the dust content of the flue gas at the inlet). If the dust content is too high,
the system working conditions shall deteriorate and the SO2 absorbing efficiency shall decrease
with occurrence of abnormal conditions such as the belt conveyor dehydration difficulty,
influencing the quality and utility value of the desulfurization gypsum. Therefore, the dust content
variation should be strictly watched over in operation regulation. When the system dust content
gose above the normal scale seriouly, the unit operating personnel should be contacted in time
and the operation of the FGD system should be stopped without delay.
11.5.2.2 Fan inlet air pressure control
To ensure the safe and steady operation of the boiler, the flue gas presssure is controlled by
regulating the open degree of the boost fan guiding blades and the boost fan inlet pressure
stablization is maintained. In order to obtain the better dynamic features, the boiler loading and ID
fan situatin singals are led in as subsidiary signals. During the process of putting the FGD flue gas
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 145
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
in service, the open degrees of the flue gas bypass damper door and the boost fan guding blades
should be controlled coordinately, maintaining the pressure stablization at the boost fan inlet.
When the bypass damper door is closed to certain degree, the preesure control close circuit will be
put in service and the bypass damper door will be closed. In the operation process, the boost fan
inlet pressure should be closely watched over. If there is big variation in boost fan inlet pressure,
the open degree of the boost fan moving blades should be manually regulated in good time to
keep the boost fan inlet pressure stable.
11.5.2.3 Absorber slurry PH control
The PH value of the absorber slurry should be controlled within the specific arange. If it is very
low, the slurry will lose the absorbing capability, influencing the SO2 removing rate and by product
desulfurization gypsum quality. Simultaneously, high PH value will bring the consequences of
scaling and jam to the system. The stability of PH is maintained by the online dynamic regulating
the open degree of the limestone slurry regulation door to control the limestone slurry supply
quantity. The best PH value for single circuit absorber is controlled between 4.5 and 5.8.
11.5.2.4 Absorber level control
The absorber level varies due to the changes in factors such as the control of the absorber
limestone slurry supply quantity, the gypsum slurry discharge quantity, the flue gas inlet quantity
and etc. Based on the measured level value, the filtrate pipe regulation valve and the time interval
for mist eliminator cleanings are controlled to keep the level stable. The level of absorer should be
controlled at 13.5±0.5m. If the level is at14.00m or above, the operation is forbidden to avoiding
GGH heat exchange surface pollution by gypsum slurry overflowing through the absorber inlet
glue gas duct.
11.5.2.5 Absorber gypsum slurry density control
The density of the absorber gypsum slurry should be controlled within the specific range. If
the density is too low, it will result in the slurry gypsum crystalization difficulty and belt dehydration
difficulty. If the density is too high, the system abrasion, the slurry circulation pump power
consumption and risks of system scaling will be increased. The FGD absorber density should be
controlled between 1050—1150Kg/m3. The absorber gypsum slurry density is controlled through
regulation of the gypsum slurry quantity discharged to the ash and slag system.
When the density of the absorber gypsum slurry reaches 1100Kg/m3, check and confirm
the ash and slag system is ready with necessary conditions to receive gypsum slurry;
To control the absorber gypsum slurry discharge quantity through regulating the open
degree of the slurry discharge pneumatic door from the absorber to the front slurry
reservoir by absorber gypsum slurry density close circuit control or manual control, and
keep the absorber gypsum slurry density relatively stabilize at 1050—1150Kg/m3.
11.5.2.6 Absorber slurry Chloridion content control
To protect and reduce the corrosion of the equipment and system pipes, ensure the normal
operation of the FGD sewage system and maintain the suitable sewage discharge quantity, the
asborber slurry Chloridion content should be controlled below 10000ppm. When the Cloridion is
relatively high, the slurry discharge quanaity to the ash and slag system should be increased and
the absorber level should be maintain by increasing the absorber process water make up quantity.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 146
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.5.2.7 To ensure the limestone reaction activity, the CaO ore of good quality and qualified
fineness is generally used.
11.5.2.8 The SO2 content in outlet flue gas should be strictly watched over. When deviation
occurs, comprehensive analysis of the boiler loading, inlet SO2 density, circulation
pump operation conditions and slurry PH should be conducted and suitable counter
measurement should be adopted.
Comparison Table of Parameters and Power Consumption
Influencing SO2 Desulfurization Efficiency
Value SO2 desulfurization
efficiency Power consumption
Absorber circulating
flow ↑ ↑ ↑
PH ↑ ↑ = CaCO3 in absorber ↑ ↑ = Limestone activity ↑ ↑ = Flue gas flow ↑ ↓ ↑ SO2 density at FGD
inlet ↑ ↓ =
Cl content in flue gas ↑ ↓ = 11.5.3 Major operation control parameters limitation
11.5.3.1 Flue gas system
Range KKS
Specification
From To
Unit
Operatin
g value
Min/Max
Valu
e
Action
*HTA10
CP001
Boost fan up stream
untreated flue gas
pressure
-40
40
mbar
-5
*HTA10
CP002
Boost fan up stream
untreated flue gas
pressure
-40
40
mbar
-5
*HTA10
CP003
Boost fan up stream
untreated flue gas
pressure
-40
40
mbar
-5
*HTA10
CP901
Boost fan up stream
untreated flue gas logic
pressure (two values out
of 3)
> Max
XXX
X
Bypass
protectio
n start up
*HNA50
AA601
*HTA10
CT001
FGD device up stream
untreated flue gas
temperature
0
350
< 180
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 147
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Range KKS
Specification
From To
Unit
Operatin
g value
Min/Max
Valu
e
Action
*HTA10
CT002
FGD device up stream
untreated flue gas
temperature
0
350
< 180
*HTA10
CT003
FGD device up stream
untreated flue gas
temperature
0
350
< 180
*HTA10
CT901
FGD device up stream
untreated flue gas logic
temperature (two values
out of 3)
0
350
< 180
> Max1
140
>Max 2
180
Bypass
damper
protectio
n start up
*HNA50
AA601
<Min1
120
Bypass
damper
protectio
n start up
*HNA50
AA111
>Min1
120
Sending
out
signals
for
starting
up of
treated
flue gas
damper
*HTA50
AA601 <Min 2 110
*HTA20
CQ001
FGD device up stream
untreated flue gas SO2
content
0
5000
mg/m3
dry
basis
<3605
>Max1
3605
*HTA20
CQ002 FGD device up stream
untreated flue gas O2
0
21
%
6-8
Date 2008-09-16
No. : QN1-SEC-G-04-TP-005
Page 148
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Range KKS
Specification
From To
Unit
Operatin
g value
Min/Max
Valu
e
Action
content
*HTA30
CT001
Absorber (inlet) up
stream untreated flue gas
temperature
0
200
<120
Max1
125
Failure
alarm *HTA50
CP001 FGD device down stream
treated flue gas pressure
-10
40
mbar
+5
*HTA50
CP002 FGD device down stream
treated flue gas pressure
-10
40
mbar
+5
*HTA50
CP003 FGD device down stream
treated flue gas pressure
-10
40
mbar
+5
*HTA50
CP901
Absorber down stream
treated flue gas logic
temperature (two values
out of 3)
> Max 1
10
> Max2 40
*HTA50
CQ001
FGD device down stream
treated flue gas SO2
content
0
500 mg/m3
dry
basis
<150
*HTA50
CQ002
FGD device down stream
treated flue gas NOX
content
0
1000
mg/m3
dry
basis
<1000
*HTA50
CQ003
FGD device down stream
treated flue gas O2
content
0
21
% dry
basis
7
*HTA50
CQ004
FGD device down stream
treated flue gas ash
content
0
200 mg/m3
dry
basis
<50
> Max1
50
*HTA50
CM001
FGD device down stream
treated flue gas moisture
content
0
100
%
<12
*HTA50
CT010 Down stream treated flue
gas temperature
0
200
>=80
*HUD10
CS901
GGH rotary body speed
<0.7 rpm
rpm
< Min1
0.2
FGD
device
flue gas
pipe
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 149
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Range KKS
Specification
From To
Unit
Operatin
g value
Min/Max
Valu
e
Action
failure
*HTAOO
EG001
*HUD10
CS902
GGH rotary body speed
<1.2 rpm
rpm
< Min1
0.7
Flue gas
ready to
receive
*HTA00
EG002 11.5.3.2 Boost fan
Range KKS
Specification
From To
Unit
Operatin
g value
Min/Ma
x Valu
e
Action
*HTC10
AA001 Boost fan static blade
actuator
0
100
%
>max1 5 Warning
>max2 10 Alarm <min1 -15 Warning
*HTA10
CP901
(see flue gas
system)
Boost fan inlet pressure
-40
+40
mbar
<min2 -18 Alarm >max1 30 Warning
>max2 35 Alarm <min1 -5 Warning
*HTC10
CP001
Boost fan outlet
pressure
-40
+40
mbar
<min2 -10 Alarm <min1 40 Alarm
*HTC10
CF901
Flue gas flow signa
calculated from the
pressure differential of
*HTC10 CP003
0
150
%
40-120
>max1
120
Alarm
>max1 85 Alarm *HTC10
CT001 Boost fan front bearing
temperature
-25
120
oC
<70
>max2 95 Trip
>max1 85 Alarm *HTC10
CT002 Boost fan front bearing
temperature
-25
120
oC
<70
>max2 95 Trip
>max1 85 Alarm *HTC10
CT011 Boost fan middle bearing
temperature
-25
120
oC
<70
>max2 95 Trip >max1 85 Alarm *HTC10
CT012 Boost fan middle bearing
temperature
-25
120
oC
<70
>max2 95 Alarm >max1 85 Alarm *HTC10
CT051 Boost fan rear bearing
temperature
-25
120
oC
<70
>max2 95 Alarm >max1 85 Trip *HTC10
CT052 Boost fan rear bearing
temperature
-25
120
oC
<70
>max2 95 Alarm
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 150
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Range KKS
Specification
From To
Unit
Operatin
g value
Min/Ma
x Valu
e
Action
>max1 75 Trip *HTC10
CT031 Boost fan motor front
bearing temperature
-25
120
oC
<70
>max2 80 Alarm >max1 75 Alarm *HTC10
CT032 Boost fan motor front
bearing temperature
-25
120
oC
<70
>max2 80 Trip >max1 75 Trip *HTC10
CT031 Boost fan motor rear
bearing temperature
-25
120
oC
<70
>max2 80 Alarm >max1 75 Alarm *HTC10
CT032 Boost fan motor rear
bearing temperature
-25
120
oC
<70
>max2 80 Trip >max1 125 Alarm *HTC10
CT021 Boost fan motor stator
winding temperature
oC
<125 >max2 130 Trip >max1 125 Alarm *HTC10
CT022 Boost fan motor stator
winding temperature
oC
<125 >max2 130 Trip >max1 125 Alarm *HTC10
CT023 Boost fan motor stator
winding temperature
oC
<125 >max2 130 Trip >max1 125 Alarm *HTC10
CT024 Boost fan motor stator
winding temperature
<125 >max2 130 Trip >max1 125 Alarm *HTC10
CT025 Boost fan motor stator
winding temperature
<125 >max2 130 Trip >max1 125 Alarm *HTC10
CT026 Boost fan motor stator
winding temperature
<125 >max2 130 Alarm >max1 6.3 Trip *HTC10
CY301 Boost fan bearing
vibration value
mm/s
<5 >max2 7.1 Alarm >max1 6.3 Alarm *HTC10
CY302 Boost fan bearing
vibration value
mm/s
<5 >max2 7.1 Trip
*HTC10
CP301
Boost fan surging alarm
Signal
spark
Alarm60S
unrelease
d Trip 11.5.3.3 GGH
KKS
Specification
Range
Unit
Operatin
g value
Less/mo
re than
Value
Action
*HUD10
CS901
GGH rotor speed
*HUD10 CS001~003 (2
out of 3)
0~2
rpm
1~1.5 Normal
operating
speed
GGH speed<0.2rpm
<Min1
0.2 Alarm,
stop rotor
driver GGH speed <0.7rpm <Min1 0.7 Stop HP
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 151
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
KKS
Specification
Range
Unit
Operatin
g value Less/mo
re than
Value
Action
water
cleaning
procedure
GGH speed <1.0rpm <Min1 1.0 Alarm
*HUD10
CT001 Guiding bearing
lubricating oil temperature
0~ 200
60 >Max1
Alarm
>Max2
*HUD10
CT002 Supporting bearing
lubricating oil temperature
0
>Max1
>Max2
*HUG01
CP001
Cleaning steam pressure
bar
10
<Min1
6 Stop
steam
cleaning *HUG20
CT001 Cleaning steam drainage
discharge temperature
300
<Min1
250
3HUQ01
CP002
HP cleaning water pump
up stream pressure
bar
<Min1
5
Stop HP
water
cleaning
procedure
3HUQ01
CP005
HP cleaning water pump
outlet pressure
bar
>Max1
100
Stop HP
water
cleaning
procedure
*HUW01
CP001 Positive pressure sealing
fan down stream pressure
mbar
11.5.3.4 Absorber
Range KKS
Specification
From To
Unit
Operatin
g value Min/Ma
x
Value
Action
>MAX2
14300
Absorber
inlet PO,
2 out of 3
*HTD10
CL001
1# absorber level
13500
<MIN4
10000
Upper
mixer PO,
2 out of 3
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 152
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
<MIN7
3000
Circulatio
n pump
PO, 2 out
of 3
<MIN9
1800 Mixer PO,
2 out of 3
<MIN1
1
1200
Gypsum
discharge
pump
PO, 2 out
of 3
>MAX2
14300
Absorber
inlet PO,
2 out of 3
<MIN4
10000
Upper
mixer PO,
2 out of 3
<MIN7
3000
Circulatio
n pump
PO, 2 out
of 3
<MIN9
1800 Mixer PO,
2 out of 3
*HTD10
CL002
2# absorber level
13500
<MIN1
1
1200
Gypsum
discharge
pump
PO, 2 out
of 3
>MAX2
14300
Absorber
inlet PO,
2 out of 3
<MIN4
10000
Upper
mixer PO,
2 out of 3
<MIN7
3000
Circulatio
n pump
PO, 2 out
of 3
*HTD10
CL003
3# absorber level
13500
<MIN9
1800
Mixer PO,
2 out of 3
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 153
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
<MIN1
1
1200
Gypsum
discharge
pump
PO, 2 out
of 3
>MAX1
14000
Alarm,
mist
eliminator
sequence
group
control
stop
>MIN1
X Stand by
signal
<MIN2
12700
Close
circuit
control
start up
cleaning
<MIN3
10500
Alarm,
upper
mixer PO
>MIN3
10500
Release
connectin
g upper
mixer
>MIN5
3500
Release
connectin
g
circulatio
n pump
<MIN6
3000
Alarm
circulatio
n pump
PO
<MIN8
1900 Alarm
mixer PO
*HTD10
CL901
Absorber logic
level
>MIN8
1900 Release
connectin
g mixer
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 154
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
>MIN9
1800
Release
connectin
g gypsum
discharge
pump
<MIN1
0
1700
Alarm
gypsum
discharge
pump PO 11.5.3.5 Limestone slurry supply system
Range
KKS
Specification Fro
m
To
Unit
Operatin
g value
Less/Mor
e than
Valu
e
Action
0HTK60
CL901 Limestone
slurry tank
level
0 500
0 MM 2000-4
500 More
than 480
0 High level alarm
More
than 450
0 Unconditional
start slurry
preparation
terminal
procedure More
than 420
0 Conditional start
slurry preparation
procedure More
than 300
0 Conditional start
slurry preparation
terminal
procedure Less
than 200
0 Start slurry
preparation
procedure Less
than 180
0 Low level alarm
More
than 150
0 Allowing mixer
start up More
than 150
0 Allowing
limestone slurry
pump start up Less
than 100
0 Stop mixer, alarm
limestone slurry
pump stop
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 155
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Less
than 400 Stop limestone
slurry pump 11.5.3.6 Process water system
Range KKS
Specification
From To
Unit
Operating
value
Min/Max
Value
Action
0HTQ10
CL901 Process water
tank level mm Continuous
>Max1
5800 High level
alarm
>Max2
5500 Make up
valve close
(0HTQ10
AA101)
<MIN1
3000 Make up
valve open
(0HTQ10
AA101)
>MIN1
3000 Allowing
process water
pump
activation
<MIN2 2000 Low level
alarm
<MIN3
1000 Stop all
process water
pumps 0HTQ15
AA091 Process water
return pressure
stabilizing valve
MPa 0.65
*HTQ50
AA090 Absorber mist
eliminating
cleaning pressure
relief valve
MPa 0.21
11.5.3.7 Emergency slurry system
Range KKS
Specification
From To
Unit
Operatin
value g
Min/Max
Value
Action
Emergency slurry tank 0HTT10
CL001 Emergency
slurry tank
level
mm 13500 >MAX1 13000 High level
alarm
Date 2008-09-16
No. : QN1-SEC-G-04-TP-005
Page 156
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Range KKS
Specification
From To
Unit
Operatin
value g
Min/Max
Value
Action
Emergency
slurry tank
level
mm >MIN1 3000 Allowing mixer
activation
mm <MIN2 2000 Alarm mixer
termination mm <MIN3 1800 Stop mixer mm <MIN4 1200 Alarm
emergency
discharge
pump
termination mm <MIN5 1000 Stop
emergency
discharge
pump Absorber earth pit
*HTT41
CL001 Absorber
earth pit level mm 1300 >MAX2 2800 High level
alarm mm >MAX1 2300 Allowing earth
pit pump
activation mm >MIN1 1400 Allowing mixer
activation mm <MIN2 1300 Stop earth pit
pump (level
protection) mm <MIN3 1100 Stop mixer mm <MIN4 500 Stop earth pit
pump
protection Unloading room earth pit
0HTT51
CL001 Unloading
room earth pit
level
mm 700 >MAX2 800 High level
alarm
mm >MAX1 600 Activated
earth pit pump
mm >MIN1 200 Stop earth pit
pump 11.5.4 Inspection in FGD system operation
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 157
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Equipment name Inspection item and requirements Boost fan and its
auxiliaries For all rotary parts, current, vibration and sound are normal; machinery
and motor bearing temperatures are normal; cooling water flow and
temperature are normal; lubricating (hydraulic) oil pressure,
temperature, quality and level are normal; all connectings, including
guiding blade actuator and air dampers, are firm without deformation,
bending and rip; no leakage points; CRT displays of outlet pressure and
flue gas flow are normal. Sealing fan For all rotary parts, current, vibration and sound are normal; machinery
and motor bearing temperatures are normal; outlet pressure value is
normal; inlet screen is clean. Oxidization fan and all
types of pumps For all rotary parts, current, vibration and sound are normal; machinery
and motor bearing temperatures are normal; cooling water flow and
temperature are normal; lubricating (hydraulic) oil pressure,
temperature, quality and level are normal; driven belt tightness is
suitable, without distortion and abrasion is within the normal standard;
inlet and outlet pressure are normal; non return valve and pipes have
no self-sustained oscillation or syntony appearance; inlet strainer is
clean; all connectings are firm without deformation and bending; all
valves are at the right positions; no leakage points. Mixer For all rotary parts, current, vibration and sound are normal; machinery
and motor bearing temperatures are normal; lubricating oil level is
normal and quality is good; all connecting bolts and nuts are firm; no
leakage points. Hydraulic cyclone Without blockage; open degrees of valves are normal; inlet flow is
normal; no leakage points. Gypsum separator and
vacuum dehydration
belt
For all rotary parts, current, vibration and sound are normal; machinery
and motor bearing temperatures are normal; gypsum conveying
conditions and the gypsum lump thickness are normal; the open
degrees of valves and the solenoid valve action frequency are normal;
the roller and its driven device works normally; the filter cloth is without
blockage, broken holes or rip; cleaning conveying nozzle is without
blockage conditions; water cleaning filter cloth is clean; the vacuum
conditions is suitable; the gypsum splattering conditions are normal;
local instruments indications are right; no leakage points. Rotary heat exchanger
(GGH) For all rotary parts, current, vibration and sound are normal; machinery
and motor bearing temperatures are normal; the cleaning water
pressure is normal; lubricating oil level and quality are normal; sealing
air pressure is normal; no leakage points. Dampers with sealing
device The open degree of dampers are right, drivers for air cylinder are
normal; sealing air pressure and flow is normal; sealing components
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 158
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
are without leakage. Absorber Absorber level is within the normal range; current, vibration and sound
of rotary parts, including circulation pump, mixer and so on, are normal;
machinery and motor bearing temperatures are normal; the open
degrees of valves and automatic valves are normal; PH gauge pipe is
without blockage; there is no abnormal vibration and sound in the area;
local instruments indications are right; no leakage points. All water tanks and
slurry tanks All water tank levels are within the normal range; the open degrees of
valves and instrument valves are right; there is no abnormal vibration
and sound in pipes; equipments and its auxiliaries in the system area
are without leakage. Silo The level gauge indications of limestone lump bunker and powder
bunker are right; all instruments indications are within the normal range;
the valve open degrees and pipe vibration are normal; the fluidizing
device works properly; no leakage points. CRT All indication values are within the design range; all interlocks and
protections are normally put in service; no alarm signals; the operators
on duty records on time. 11.5.5 Maintenance During the FGD System Operation
11.5.5.1 GGH Cleaning.
To prevent the scaling inside GGH, the online cleaning must be adopted to GGH when the
pressure difference enlarges in a faster speed or exceeds the designed value. During the normal
operation of GGH (rotary proper of GGH: rotating speed n≈1.5), the steam cleaning should be
carried out every 8 hours and the entire process (1 time) lasts for about 2.3 hours. The process is
manually started by operators.
When pressure difference (∆P) of GGH rises to ~1.5 P under clean conditions, alarms shall
reminder the operators to start-up HP water cleaning.
The intending frequency of HP water cleaning: during the normal operation of GGH, the
system shall be cleaned once a week, or during the GGH system shut down process. The entire
process lasts for about 9 hours. This process can only be manually adopted upon the operator’s
request.
The process is to be automatically accomplished by GGH soot blowing local control cabinet
(including feedback of fault signal), and only remote “start” and “stop” signal will be issued by the
operator.
11.5.5.1.1GGH steam cleaning
Check and confirm the start-up conditions of GGH steam cleaning are fulfilled (not
interlocked).
¾ GGH system is in operation and the rotor speed n≈1.5 (min 1). ¾ Upper and lower soot blowers are at the outer side. ¾ Air valve is closed. ¾ HP nozzle cleaning valve is open.
Invoke GGH steam cleaning start-up function group to start GGH steam cleaning.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 159
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.5.5.1.2GGH HP water cleaning
Check and confirm the GGH water cleaning conditions are fulfilled (not interlocked).
¾ GGH system is in operation.
¾ HP pump is not in operation.
¾ Chief water valve is closed.
Invoke GGH HP water cleaning group to start GGH HP water cleaning.
HP water cleaning procedure specification:
¾ During the HP water cleaning, GGH rotating speed is changed to low rotating
speed of 0.75n.
¾ Start HP water cleaning procedure, which is controlled by soot blower control
cabinet and the “start” & “stop” signals are sent out by DCS.
Monitoring of HP water cleaning.
¾ The HP water procedure should be stopped when the following signals
occurring:
HP water pressure P>100 bar (3HUQ10 CP310), max 1.
11.5.5.2 PH gauge’s cleaning and correction
11.5.5.2.1Absorbing tower has two PH gauges, clean them alternately in the specific sequence.
When the fault value and large warp alarm occur, it is necessary to start the
cleaning device manually. The PH gauges should not be in operation during the
cleaning.
11.5.5.2.2The results of manual analysis and online measurement should be compared at least
once a week, and the online PH gauge should be adjusted when there is
difference in the comparison.
11.5.5.3 Cleaning of oxidization air pipe
11.5.5.3.1To prevent blockage, every oxidization air pipe is equipped with a cleaning pipe, and
every oxidization air pipe should be cleaned sequently every week.
11.5.5.3.2Each oxidization air pipe should be cleaned as per the following procedure:
Check if the cleaning water pump is in normal operation.
Slowly close separate valve of branch oxidization air pipe, wait until the oxidization air
pipe pressure gauge turns to ZERO.
Open the cleaning water separate valve of the oxidization air pipe, clean it and monitor
the pressure gauge.
Close the cleaning water separate valve of the oxidization air pipe after the cleaning.
Slowly open the cleaning water separate valve of the oxidization air pipe.
11.5.5.4 The complete discharge and cleaning of the centrifugal pump for limestone and
gypsum slurry transportation and the pipes after shut down
11.5.5.5 Periodic test for bypass damper door
11.6SHUT DOWN OF THE FGD SYSTEM
Due to periodic overhaul or tear of the system, the FGD system will shut down after
transacting the shut down procedure. Only after the operator manager’s approval can the FGD
system be shut down. During the shut down process, the relative operations especially the flue
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 160
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
gas system should be operated in stable order by closely contacting the operators, so as to
guarantee the boiler safe operation and safe shut down of the FGD system. The methods of the
equipments putting in service vary due to the different shut down methods of the FGD system.
11.6.1 Preparation before shut down of the FGD system
11.6.1.1 As each slurry pump is to be cleared and cleaned after shut down of the FGD system,
the water level of absorber should be lower properly to keep the normal low level
operations of the absorber discharge pit and emergency slurry reservoir.
11.6.1.2 Before shut down of FGD system, GGH should be cleaned by online steam or HP
water.
11.6.2 FGD system from operating state to hot standby state
The shut down of FGD system means that the FGD system changes from the operating state
to the hot standby state; or after shut down of the boiler, the FGD system changes from the
operating state to the hot standby state. This operation is accomplished by running flue gas
system stop function group and absorber’s stop function group, or by the remote sequent control
of FGD system centralized controller.
11.6.2.1 Discuss with operator manager and chief operator to request for shut down of this unit’s
FGD system. After receiving the approval of the operator manager, invoke the flue gas
system stop function group and absorber stop function group or manually stop the FGD
system as per the following procedures:
11.6.2.2 Open the bypass damper
z Manually open the bypass damper, add 5% extent for each time. Add with the
same extent till 50% opening of the damper when the booster air fan’s inlet
pressure reaches to a stable state.
z Change the booster air fan’s automatic control to manually controlling state.
z Add 5% extent to the opening of bypass damper while manually reducing boost
fan’s static blade opening. After maintaining the boost fan’s inlet pressure, add
bypass damper’s opening to 100% by adding 5% opening extent.
11.6.2.3 Stop the boost fan
z Make sure that the bypass damper opens to 100%.
z Close the booster’s static blade until the opening is under 10%.
z Stop the operation of boost fan’s main motor.
11.6.2.4 Close the original flue gas damper
11.6.2.5 Close the clean flue gas damper
11.6.2.6 Start 1 set damper airproof fan
z Start damper airproof fan
z Start the electrical door at damper airproof fan’s inlet
11.6.2.7 Open the drainage door at the top of absorber
11.6.2.8 Shut down the GGH low leakage fan
z Close the electrical door at outlet of low leakage fan
z Shut down the low leakage fan
z Close the electrical door at inlet of low leakage fan
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 161
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.6.2.9 Close the limestone slurry feeding door to opening 0.
11.6.2.10 Shut down the absorber’s slurry circulation pump by sequence
z Make sure that the conditions for slurry circulation pump’s shut down are
fulfilled(boost fan is shut down, original flue gas damper and clean flue gas
damper are closed)
z Shut down the slurry circulation pump
z Close the electrical door at slurry circulation pump inlet after a 120s delay.
z Make sure that the water level at absorber’s drainage pit is not high.
z Start the drainage electrical door at the shut down slurry circulation pump’s inlet
z Close the drainage electrical door at the shut down slurry circulation pump’s
inlet after a 300s delay.
11.6.2.11 Shut down the oxidation fan
z Open the bypass discharge valve of oxidation fan
z Shut down the oxidation fan
z Close the bypass discharge valve of oxidation fan
z Shut down the sound proof fan of oxidation fan
z Close the main humid adding door of oxidation air
11.6.2.12 Stop the gypsum slurry’s PH gauge at absorber
z Close the manual sampling door for PH measuring of gypsum slurry at
absorber.
z Open the drainage door at PH measuring slot’s bottom of gypsum slurry and
drain the gypsum slurry inside.
z Open the measuring loop of PH measuring of gypsum slurry and flush the
manual door for 5 minutes.
z Close the drainage door at PH measuring slot’s bottom of gypsum slurry and
drain the gypsum slurry inside
z Close the gypsum slurry’s PH measuring loop and flush the manual door after
treatment liquid is fulfilled in the PH measuring slot’s bottom of gypsum slurry.
11.6.2.13 Shut down GGH
z Cancel the low rotating speed interlock of GGH stand by motor
z Stop the GGH driven device
z Stop GGH sealing fan
11.6.2.14 Shut down the limestone slurry pump
z Shut down the limestone slurry pump
z Open the flush door of limestone slurry feeding pipe and flush the feeding pump
11.6.2.15 Main equipments’ state under hot and stand by state of FGD system
System Description of main auxiliaries State Boost fan Stopped Original flue gas damper door of FGD Closed Clean flue gas damper door of FGD Closed
Absorber system
Bypass flue gas damper door of FGD Open
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 162
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
System Description of main auxiliaries State Absorber ventilation door Open Absorber circulation pump Stopped Gypsum drainage pump In operation Absorber mixer In operation Oxidation fan Stopped Absorber PH control Manually Mist remover flush system Stopped Absorber water level control Automatic Damper airproof fan In operation Absorber pit pump According to the pit water level
Absorber pit mixer According to the pit water level Soot blower Stopped Main and supplement drive motor Stopped GGH airproof fan Stopped GGH low leakage fan Stopped Low leakage fan inlet door Adjusted to corresponding
position GGH soot blower airproof fan Stopped Limestone slurry pump In operation Limestone slurry tank mixer In operation Limestone slurry tank feedwater flow
control Automatic
Limestone slurry tank’s water level
control Automatic
Milling district pit pump According to Milling district’s pit
water level
GGH system
Milling district pit mixer According to Milling district’s pit
water level Flush water system In operation Closed cooling water system In operation
Multi use air system In operation
Auxiliary system
Instrument air system In operation Emergency slurry pool mixer According to the emergency
slurry pool’s water level
Emergency slurry
pool Emergency slurry pump Stopped
11.6.3 FGD system changes from hot standby state to cold standby state
When the FGD system requires overhaul and the shut down mood need to be changed into
cold standby state, it demands that each system should shut down, drain the slurry from tanks and
pools into emergency slurry pool for storage and keep the emergency pool mixer on running.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 163
Rev.: A
11.6.4 Matter to be taken care of after shut down of the FGD system
11.6.4.1 All the gypsum, limestone slurry transporting pump and pipe should be drained and
flushed after the shut down operation
11.6.4.2 Mixers of tanks containing slurry should maintain constant operation mood.
11.7 FGD SYSTEM FAULT AND ACCIDENT HANDLING
11.7.1 FGD system fault and general principles for accident treatments
11.7.1.1 When FGD system has faults or emergencies, the operator manager and chief operator
should lead all the operators to deal with the accidents according to Manual. Otherwise it’s
harmful to personnel and equipments’ safety; all the orders should be followed.
11.7.1.2 When FGD system has faults or emergencies, the operators should report to chief
operator, operator manager and relative leaders, and adopt effective and doable methods
to prevent the accidents extend, restrict the accidents’ scope, clear up the causations and
resume the operation of the FGD system. Under emergency conditions, the treatment
comes first and then report to the leaders.
11.7.1.3 The main equipments of FGD system should be stopped and treated when they can not
fulfill the operation conditions and can threaten operators and equipments safety.
11.7.1.4 The operators should immediately and positively adopt solutions by personal experience
and judge for accidents not listed in this specification.
11.7.1.5 After treating accidents, the operators should record the time, accident, treatment
process and solutions on the duty relay recording notebook and submit the raw report to
the safety department of the plant.
11.7.1.6 When the accident occurred during the duty relay time, duty deliver that has not finished
duty relay should go on for work and treat the accidents with duty relay personnel. The
duty can only be relayed when the accident treatment is over or stopped for a rest time.
11.7.1.7 When noticing the FGD system’s flue gas system shut down due to accidents, check if
the bypass damper door is automatically opened or press the quick open button on the
bypass damper, then report to operator manager and contact boiler operators to ensure
the safety operation of boiler.
11.7.1.8 The consideration equipment scope of FGD system’s accident treating does not only
including the main equipments and systems inside the FGD system, but also the effects to
the other service systems; take the possible secondary pollutions into consideration and
avoid them.
11.7.2 Emergency shut down of the FGD system
11.7.2.1 Emergency shut down conditions of FGD system
The FGD system should be immediately shut down when comes to the following conditions. If
the system can not be shut down, the bypass damper should be opened manually and shut down
the FGD system.
z Boost fan trips
z Less than 2 sets of operating slurry circulation pumps in operation
z Flue gas temperature at inlet of boost fan is over 180
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 164
Rev.: A
z Operating original flue gas damper or clean flue gas damper are closed due to
faults
z Boiler MFT
z ESP fault trips or less than 2 flue gas channels are flowing to electric field.
z GGH operation motor trips and the stand by drive motor can not be connected
to start, leading to the shut down of GGH.
11.7.3 FGD system shut down due to not emergent faults
The FGD system should be shut down when comes to the following conditions, but the
department leader’s agreement is the precondition.
z 2 sets of absorber mixers out of operation
z Operators should shut down the FGD system when the soot concentration at
the inlet of FGD system.
z The limestone slurry producing equipments and feeding system can not supply
slurry to the absorber, and PH value of slurry insider the tower is under 4.0 and
keep on dropping.
z Density of gypsum exceeds 1200Kg/ m3 and can not be reverted to normal in
short time.
z The accidents occur at producing field and control room threaten personnel’s
and equipments’ safety.
z FGD system’s controlling system can not monitor the faults.
z GGH pressure difference can not be treated by the operators and keeps on
enlarging.
11.7.4 System’s common fault treatment
The following should be carried out when the DCS alarms for faults:
z Make sure of the operation state of FGD system;
z Find out the causes of alarming;
z Adjusting operation should be done to remove the fault.
z Revert and back to operation, resume the FGD system to normal operation.
11.7.4.1 Causations and solutions for the decreasing efficiency of FGD system:
Causations Appearance and analyzing results Solutions Limestone slurry’s
supply can be fulfilled
inside the absorber
Low control level of PH value Improve the PH control level
properly and increase the
limestone slurry’s supply Not exact data for PH
online measuring,
which leads to low
measuring(control
value) of actual PH
level inside the
absorber
Compare the test result with online
measuring value manually to find out the
existing difference
Mark the PH gauge
comparatively and periodically.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 165
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
Blockage inside the
spraying pipes or
nozzles
Slurry circulation pump’s flow(current)
decreases and outlet pressure increases Deal when shut down
Flue gas flow
increases
Online measuring indicates the increasing
of flow and each section’s resistance of
the flue gas system increases at the
same time
Add a spray coat if possible
Density of SO2 inside
flue gas increases
Flue gas online measuring indicates that
the density of SO2 increases and the
boiler’s coal consumption increases
Add a spray coat if possible
Quality of slurry turns
down and the
densities of Cl, dust
and heavy metal are
too high
Enlarge the sewage drainage
flow
Measuring value of
online measuring
gauge is not exact
due to faults, which
leads to wrong
calculation of FGD
efficiency
SO2 value at the inlet of online measuring
absorber is different(less) with SO2 value
contained inside the coal; SO2 value at
the outlet of online measuring absorber is
larger than the actual value.
Calibrate the online gauges
11.7.4.2 Tripping during boost fan’s operation
z Appearance
¾ --Boost fan’s current on the DCS screen turns to “0”, inlet pressure turns to
positive, and motor’s screen turns from red to green.
¾ --Bypass damper opens automatically, inlet and outlet dampers close
automatically, ventilation damper of absorber opens automatically, and boiler’s
induced fan may have short time positive pressure.
¾ --FGD system shut down automatically.
z Treatment process
¾ --Make sure the flue gas bypass damper is already open, or open it by
other means. --Report to operator manager and chief manager of centralized
control about the boost fan’s tripping.
¾ --Check whether the operation of absorber’s circulation pump, oil temperature of
boost fan’s bearing and motor’s bearing and the fan’s vibration are normal. Make
sure if they are the causations for the tripping.
¾ --Check the operation of electrical and thermal protection and compare with the
field equipments’ operation, then contact the maintaining personnel to check the
validity of the protecting operation and reset the protection after handling the
problems, check the insulating resistance of the boost fan’s motor, booster motor
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 166
Rev.: A
proper and oil station, make sure of the causation of tripping and deal with it.
¾ --Check the overall equipments of FGD system and turn them into hot standby
state.
¾ --If the causation of the fault can be found and treated in short time, then restart
the FGD system.
11.7.4.3 Blackout of treatment liquid
z Appearance
¾ Treatment liquid sends out alarm signals
¾ Blackout of treatment water at production fields.
z Treatment procedure
¾ Check the operation state of operating pump, and if there is abnormality, start the
stand by pump (start the coupling pumps when the treatment liquid pressure is
under 300 kpa).
¾ Check the water level of the treatment liquid tank and make sure that the makeup
water of treatment liquid is normal;
¾ When the blackout can not be renewed for a short time, then request the long
time shut down of FGD system;
¾ Drain the slurry pipe, try to renew the water source as soon as possible, then
flush the pipe and restart the FGD system.
11.7.4.4 Large GGH pressure difference
z Appearance
¾ Alarming for large GGH pressure difference
Treatment procedure
¾ Increase the times of soot blowing and reduce the time space of soot blowing.
¾ Start HP water pump when the treatments above are of no effect.
¾ Reduce the opening of the boost fan, reduce the system’s air flow and renew the
system after treating to normal state.
11.7.4.5 Complete shut down of slurry circulation pumps
z Appearance
¾ Complete shut down the operating slurry circulation pumps, switch of the DCS
system turns to green, current changes into ZERO and alarm rings.
¾ Shut down of FGD system.
z Treatment procedure
¾ Make sure that the boost fan is tripped, manually stop the boost fan when
necessary and shut down the FGD system;
¾ Check if the absorber level is in the normal scope;
¾ Contact the thermal control personnel and check if there are abnormal conditions
in absorber level control system, the level indicator is right or not, and clean or
correct the level indicator depending on the actual conditions;
¾ Send a notice to the electrical maintenance personnel to check whether the slurry
circulation pump motor, cable and switch cabinet are in normal operation; check
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 167
Rev.: A
whether the electrical protection is in action;
¾ After eliminating the defects, restart up.
11.7.4.6 Abnormal in absorber level
z Cause
¾ Absorber level gauge out of order or metering error;
¾ Absorber slurry circulation pipe leakage;
¾ All valves which is connected to the absorber inside leakage;
¾ Absorber leakage;
¾ Absorber level control module failure;
¾ Mist eliminator cleaning water cutoff or nozzle blockage.
z Treatment procedure
¾ Check and adjust the level gauge indication;
¾ Check and repair the leaking pipe;
¾ Check the valves’ inside leakage conditions, and change the related leaking
valves;
¾ Check the discharging doors at the absorber proper and the bottom.
11.7.4.7 Accident trip of the FGD flue gas system
z Appearance
¾ DCS alarm signal sent out;
¾ Boost fan trip;
¾ Bypass damper open, original and clean flue gas damper door close;
z Cause
¾ Boost fan failure trip;
¾ GGH driven motor speed less than 0.5r/min;
¾ Less than 2 sets of absorber circulation pumps in operation;
¾ Clean flue gas damper closed;
¾ The FGD system main power supply failure trip.
z Treatment procedure
¾ Closely adjust and monitor each slurry tank and absorber slurry level,
consistency and density after the FGD system trip;
¾ If the FGD system main power supply trip, then it should be treated as equipment
shut down;
¾ After finding out the failure causes and eliminating the defects, restore the FGD
system operation.
11.7.4.8 FGD system other defects causes and treatment methods
Defect type Defect cause Treatment methods
Limestone slurry
density decrease
1. Limestone powder feeder
blockage
2. Powder bridging in the
powder bunker
3. Valve control out of order
1. Clean up the powder feeder
2. Adopt all clean up measurements, to
increase the powder bunker discharge
quantity
3. Inspect and repair the valves
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 168
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
4. Limestone slurry tank over
water feeding 4. Inspect relative pipes and valves
Limestone slurry
flow decrease
1. Valve blockage
2. Relative valve out of order
3. Flow gauge out of order
4. Limestone slurry pump failure
5. Relative valve can not open or
close to the right positions
1. Clean up the pipe
2. Inspect, clean and repair the relative
valves
3. Inspect or change the flow gauge
4. Change to stand by pump
5. Inspect and correct the valves Inexact PH gauge
indication
1.PH gauge slurry supply
quantity is not enough
2.PH gauge slurry supply mixed
with cleaning water
3. Gauge not correct
1. Inspect and correct the valves, and
inspect whether the slurry discharge valves
are at the right positions
2. The cleaning water valve has leakage or
not, examine by cleaning and comparison
with the standard liquid Absorber outlet
SO2 density
increase
1. Absorber circulation slurry
quantity decrease
2. Limestone slurry quantity
decrease
3. Limestone slurry density
decrease
4. Gauge not correct
1. Contact the centralized control operating
manager, to know the boiler operation
adjusting conditions and coal combustion
analysis;
2. Inspect the circulation slurry pump
operation conditions and put 1 more
circulation slurry pump in service when
necessary;
3. Inspect and restore the limestone slurry
density;
4. Correct the gauge. Absorber inlet flue
gas temperature
high
1.GGH rotation not in good
conditions
2.GGH blockage
3. FGD system inlet flue gas
temperature high
1. Treat after find out the reasons
2. Check the pressure differential and treat
3. Contact to conduct boiler modification
GGH outlet flue
gas temperature
high
All absorber circulation pumps
shut down
The temperature rises to the specific value.
GGH outlet flue
gas temperature
low
1.GGH blockage
2. FGD system inlet flue gas
temperature low
1. Check the pressure differential and treat
2. Contact to conduct boiler modification
when it is lower than the specific value Mist eliminator
pressure
differential high
1. Elements blockage
2. Gauge not correct
1. Inspect the blockage, adjust mist
eliminator cleaning flow and time intervals
2. Correct the pressure gauge Oxidization air flow
abnormal 1. Pipe or oxidization fan inlet
blockage 1. Inspect the oxidization fan inlet filter and
clean the air duct up to the absorber
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 169
Rev.: A
SEC
QUANG NINH THERMAL POWER JOINT STOCK COMPANY
2×300 MW BOP OPERATION MANUAL
2. Oxidization fan failure or pipe
leakage 2. Inspect the oxidization fan or pipe
Limestone silo
fluidizing fan
output pressure
low
1. Inlet filter blockage
Inspect the inlet filter, clean or change
11.7.4.9 The FGD system shall shut down due to failure interlock when with the following
conditions:
11.7.4.9.1There are less than 2 absorber slurry circulation pumps in operation;
11.7.4.9.2The FGD system inlet temperature is over the maximum value permitted;
11.7.4.9.3The inlet temperature is below the minimum value permitted;
11.7.4.9.4The boost fan is not in operation;
11.7.4.9.5The GGH is not in operation;
11.7.4.9.6Boiler MFT (2 boilers MFT of 2 boilers +1 absorber or boiler MFT of 1 boiler+1
absorber);
11.7.4.9.7The main power supply fails.
11.7.4.10 The FGD system shall shut down due to the non interlock failure when with the
following conditions, and the approval of the department leaders should be obtained
before the shut down:
11.7.4.10.1 The operators should shut down the system when 2 sets out of 4 absorber mixers are
shut down;
11.7.4.10.2 The operators should shut down the system when the FGD system inlet soot density is over 300mg/Nm3.
11.7.4.10.3 The operators should shut down the system when original damper for 2boilers+1absorber or 1boiler+1absorber is closed;
11.7.4.10.4 The operators should shut down the system when the clean flue gas damper is not open thoroughly.
11.7.4.10.5 When the FGD system outlet flue gas temperature is less than 80 and the adjustment is not effective, the operators should shut down the system after obtaining the approval.
11.7.4.10.6 The instrument air system failure and the pressure can not be kept; when it can not meet the FGD system’s requirements, the operators should shut down the system;
11.7.4.10.7 The system should be shut down when the FGD system parameters are seriously deteriorating and can not maintain the normal operation;
11.7.4.10.8 When accidents happen at the site and in the control room, and personal and equipments safety are in danger, the system should be shut down;
11.7.4.10.9 When the control system of the FGD system fails and can not conduct the normal monitoring, the system should be shut down;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 170
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.7.4.10.10 When the GGH pressure differential is high, and continuously increase after ineffective treatment conducted by the operators, the system should be shut down.
11.8 OPERATION OF LIMESTONE SUPPLY SYSTEM
11.8.1 Start up of the limestone preparation system
11.8.1.1 To choose the start up of the wet miller LP lubricating oil pump on the local control panel,
and set the interlock of wet miller LP lubricating oil pump A & B when the lubricating oil
pressure is more than 0.4MPa.
11.8.1.2 Start the wet miller spray fan.
11.8.1.3 Start the wet miller ejecting oil pump.
11.8.1.4 Start the wet miller gear box oil pump; if the oil pressure is over 0.5bar, start after a time
delay of 120s.
11.8.1.5 Start wet miller LP oil pump (jacking); if the oil pressure (is over 3.0MPa) does not
establish, then wet miller can refuse to start.
11.8.1.6 The wet miller main motor can only start after the wet miller slow driven device trips.
11.8.1.7 Start the limestone miller process water inlet motorized door, and set the wet miller inlet
water recovery regulation door at the automatic mode to mix water as per the limestone
quantity so that the wet miller slurry density can be controlled.
11.8.1.8 Start the scale feeder, when the limestone quantity is around 12t, lower the feeder at the
setting necessary quantity after half an hour. (Considering that: at the initial stage of start
up, the wet miller is on zero load, and large quantities of materials are needed to
counteract the grinding consumption between the steel balls.)
11.8.1.9 Start the wet miller slurry tank mixer.
11.8.1.10 Add materials and water into the wet miller to control the wet miller recirculation
slurry tank (through level mode) at the setting value of 1500mm; (stabilization at this level
is a little bit inclined to the upper limit).
11.8.1.11 Start wet miller slurry recirculation pump, adjust the frequency up to 40-50Hz, and
regulate the limestone slurry eddy station inlet pressure.
11.8.1.11.1 Choose the wet miller recirculation pump A or B, (please pay attention to the
corresponding relationship).
11.8.1.11.2 Invoke the wet miller recirculation pump cleaning sub function group.
11.8.1.11.3 Open the wet miller recirculation inlet door, close the wet miller slurry pump outlet door
and manually close the discharge door.
11.8.1.11.4 Open the process water cleaning door.
11.8.1.11.5 A time delay of 300s.
11.8.1.11.6 Close the wet miller slurry inlet door.
11.8.1.11.7 Open the wet miller slurry outlet door.
11.8.1.11.8 A time delay of 300s.
11.8.1.11.9 Close the wet miller slurry pump outlet door, close the process water cleaning door;
control the outlet pressure (the setting value is around 200kPa) to discharge to the
limestone slurry eddy station (close the outlet door initially and open the overflow
outlet after the fineness is qualified).
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 171
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.8.1.12 Send the samplings for chemical examination.
11.8.1.13 After the start up of the wet miller slurry pump, open the wet miller slurry pump outlet
door, adjusting the frequency up to 50Hz, so that the limestone slurry eddy station inlet
pressure can be regulated over 200kPa or 2 eddy in the limestone slurry eddy station are
in operation.
11.8.1.14 The slurry enters the buffer tank after pass the chemical examination with qualified
results.
11.8.1.15 After confirmation of slurry tank level reaches 5.5m, start all slurry supply pumps to
supply slurry to the each absorber.
11.8.2 Upkeep of the wet miller
11.8.2.1 During the long time shut down, the bowl shall cool and shrink gradually, and the journal
will slip on the bearing bushing. To reduce the friction and the axial tensile force induced by
the bowl shrink, the LP oil pump should automatically supply oil for 3mins in every other
30mins after 24hr shut down so that a certain oil membrane thickness can be maintained
between the journal and the bearing bushing.
11.8.2.2 During the shut down in winter, the cooling water in the water cooler should be
discharged entirely to avoid pipe frozen and split.
11.8.2.3 Generally, the material feeding should be stopped before shut down and stop the wet
miller operation as soon as possible.
11.8.2.4 If the wet miller will shut down for a long time, the steel balls should be spilled out to
prevent the bowl from deformation.
11.8.2.5 The operators should comply with and pay attention to the following matters during
normal operation:
11.8.2.6 The wet miller can not operate for long without feeding so as not to damage the lining
plate and consume the medium (otherwise there should be water in the milling bowl).
11.8.2.7 To feed equally is the one of the most important conditions for the wet miller to achieve
the most working efficiency, so that the operators should ensure the feeding equality of the
materials.
11.8.2.8 To exam the friction conditions of the lining plate and the medium inside the wet miller
bowl, change the lining plates which has been worn and split in time, to screw and
exchange the bolts which are not firm and fractured to prevent bowl from being worn out.
11.8.2.9 Inspect and ensure from time to time each lubricating point (including the main shaft
bearing sealing ring) has enough and clean lubricating oil (fat); to clean the oil station
return oil strainer once every month at least; to examine the lubricating oil quality every
half a year and replace by the new oil when necessary.
11.8.2.10 To inspect the wet miller big & small gears mesh conditions and the junction bolt
tightness, and there is no abnormal vibration and sounds in gear box operation.
11.8.2.11 To regulate the steel ball quantity and stage configuration based on the milling
materials and products granularity requirements; to add steel balls into the wet miller in
time so as to keep the best state of the steel balls in the wet miller; the steel balls added
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 172
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
should be of the maximum size of the initial adding (but if there is long time without adding
new balls, smaller size balls can be added).
11.8.2.12 The protective cover for wet miller coupling & clutch and other safety protection
device should be intact and caution boards should be hung at the dangerous area.
11.8.2.13 Any proper disassembly or maintenance work is forbidden when the wet miller is in
operation. When it is necessary to enter the bowl, the operation order sheet should be
applied & issued, the safety measurements have been strictly followed and the monitoring
measurements have been handled well.
11.8.2.14 During the inspection and maintenance of the wet miller and its auxiliaries, the LP
illumination equipments should be used. When conduct welding to the parts on the wet
miller, necessary earthing protection should be noticed to avoid current burning gear
surface and bearing bushing surface.
11.8.2.15 The cooling water temperature and flow for the main shaft and each oil station
should be meeting with the requirements that the bushing temperature does not exceed
the permitted temperature and can be adjusted appropriately.
11.8.2.16 Periodic inspection Manual should be worked out during the application procedure,
and the equipments maintenance should be conducted.
11.8.2.17 To upkeep the equipments carefully, clean the ambience, and ensure there is no
water leakage, slurry leakage, oil pollution, screw untightness and sundries next to the
equipments.
11.8.3 Shut down of the limestone preparation system
11.8.3.1 Stop the scale feeder.
11.8.3.2 Adjust the setting values of the 2 recover water doors at the wet miller inlet and slurry
tank to 0m3/h and then close the doors.
11.8.3.3 Adjust the wet miller recirculation slurry tank to the normal and maintain the wet miller
slurry pump operate for some time to dilute the pipe density.
11.8.3.4 To adjust the wet miller slurry tank level to the low position and ensure the wet miller
inside materials decrease obviously.
11.8.3.5 Start P oil pump (jacking oil pump with establishment of oil pressure), stop wet miller and
then stop the jacking oil pump after 3-5min.
11.8.3.6 Stop the wet miller big gear ejecting oil pump and spray fan.
11.8.3.7 Stop the bearing lubricating system. (Keep the lubricating oil system in operation in
winter)
11.8.3.8 Invoke the cleaning function group when shut down the wet miller recirculation pump:
11.8.3.8.1Stop the wet miller recirculation pump.
11.8.3.8.2Close the wet miller recirculation pump outlet door.
11.8.3.8.3Open the wet miller recirculation pump cleaning door.
11.8.3.8.4Close the wet miller recirculation pump cleaning door and close the inlet door.
11.8.3.8.5Confirm the limestone eddy station is clean after cleaning. In 10.5.3.3 the wet miller
slurry discharge dilatation has been conducted, but manual cleaning shall be
conducted again when necessary.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 173
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
11.8.3.8.6The limestone slurry reservoir mixer can shut down only when the tank level is at 2.0m,
otherwise it can not be stopped.
11.911.9 LIMESTONE HANDLING SYSTEM DESCRIPTION
Limestone with particle size of 5-20mm will be supplied by the Owner through barges of
100-200T capacity near to the plant limestone unloading station. The limestone consumption
for both phases (4x300 MW) has been assessed as about 120,000 t/year. The scope of work
start from Limestone unloading from the barge, conveying to Limestone storage shed
(common for 4 Units), further conveying to limestone Silo.
The limestone supply system shall include but not be limited to the following: Common
unloading facility (4 Units) at jetty complete with bucketed rotary crane of capacity not less
than 70 T/Hr with bucket of capacity 2 m3. One (1) limestone storage shed having storage
capacity of twelve (12) days (about 6000 tons) consumption with the worst sulfur coal at
BMCR for 4 Units. Bridge type grab crane with the capacity of 60 T/Hr will be provided for the
limestone storage shed. One (1) 100% duty limestone supply conveyor system common for 4
Units. The specification of belt conveyor from unloading station to limestone storage shed and
to the limestone Silo is of width B=500mm, speed v=1.0m/s, capacity 60t/h, All Conveyors will
be one streams,. For the flow diagram of limestone handling system see DWG
F4091S-M0104-02.
11.9.1 Startup of limestone belt conveyor
11.9.1.1 All belt conveyors are started in reverse flow sequence.
11.9.1.2 The changeover switch on local control & operating box is place at Local position,
interlock switch is place at correct Interlock position, startup of belt conveyor is strictly
prohibited without turning on interlock.
11.9.1.3 Ring the alarm bell before startup. After 30 seconds, startup operations are
performed by pressing Start button. If the startup is failure, the reason shall be found out
immediately. Startup again is permitted only after the fault is removed. Interval between two
operations must not be less than 15 minutes.
11.9.1.4 After limestone loading is finished, press Stop buttons on various belt conveyors
in forward limestone flow sequence to stop the belt conveyors.
11.9.1.5 On-load start or stop of belt conveyor is forbidden except for special condition.
11.9.1.6 If the belt conveyor is stopped due to tripping, the reason shall be found out.
Startup again is permitted only after the fault is removed. Press Start button, the
conveyor will operate and operating indicator is illuminated after sound-light alarm
device sounds for 30 seconds.
11.9.2 Shutdown of limestone belt conveyor
11. 9.2.1 Shutdown operations may be performed only if shutdown instruction has been
received after local test is finished.
11.9.2.2 Press Stop button, the belt conveyor will stop, stop indicator is illuminated .
11.9.2.3 After confirming the stop of belt conveyor, place the selector switch on local control
box at Remote Control position.
11.9.2.4 After confirming the test run of belt conveyor is satisfactory, equipments are ready
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 174
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
for operation.
11.9.3 Notices for operation
11. 9.3.1 During operation of the equipments, any maintenance and defect elimination jobs
must not be carried out.
11.9.3.2 During operation, changes in current indicator of all operational equipment shall be
monitored closely, the limit must not exceeded.
11.9.3.3 During operation of the equipments, care shall be taken to watch operating
conditions of all rotational equipments, and oil level in reduction gearbox shall be
normal. Temperature shall be ≤75,vibration ≤0.01mm,all bearing temperatures
≤85. If the above data is approached or reached, the shift supervisor shall be
reported promptly to take preventive measures.
11.9.3.4 The belt conveyor shall be free from serious misalignment, slippage, tearing etc. All
idler and roller shall be flexible in rotation, free from jamming and abnormal sound.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 175
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
12 Air Compressor System Operation Manual
12.1 Direction for use of control panel
1) Θ—startup button —stop button
The three indicator lamp indicates: ο---operating ο---fault ο---power supply
The operating indicator lamp and power indicator lamp are on in normal operation, and
the fault indicator lamp is on when fault happens in operation.
2) Emergency button: the red button below the display panel
a) Press the button when fault appears to emergently stop the air compressor; the fault
lamp is on;
b) The reset screen appears when the emergency button is pulled out; press F3 to
reset.
3) Modify the high/low limit of the pressure
a) Press F1 and the main menu (meau) screen appears;
b) When the main menu appear after pressing F1 button, press the down arrow until
the Modify Params appears; press the horizontal arrow until Parameters appears,
and then press the horizontal arrow again to modify the low limit of the pressure.
c) Press F2 button to carry out modification; use up and down arrow to modify the low
limit, and press F1 to confirm; then press F1 to return. The high limit is preset by the
manufacturer, and is not allowed to be modified.
d) Continuously press the F1 button can return to the main menu (meau) screen, and
F3 button can also be pressed to reset
4) Press F1 button and up, low and horizontal arrow for browsing the main menu, check the
startup times, operation time, oil temperature, differential pressure and other parameters.
12.2 Instrument-use air compressor operation
1) The high limit of pressure of No.1 to four air compressor is set as 0.8MPa, and the low
limits are set as 0.7MPa, 0.69MPa, 0.68MPa and 0.67MPa in sequence.
2) In normal operation and conditions, No.1 air compressor (with the high limit of 0.8MPa
and the low limit of 0.7MPa) and No. 2 air compressor (with the high limit of 0.8Mpa and
the low limit of 0.69MPa) are in operation, and the No.3 and No. 4 air compressor are in
reserve. No. 1 air compressor will automatically stop when the system compress air
pressure is higher than 0.8Mpa; when the system compress air pressure is lower than
0.8Mp, No.1 air compressor is automatically started; when the system compress air
pressure is lowered to 0.69Mpa, No.2 air compressor is started and operates in
synchronization with No.1 air compressor; and the rest may be deduced by analogy.
12.3 Air compressor operation maintain
1) Check the room temperature and the ventilation before starting the air compressor, and
the room temperature should be less than or equal to 46 degrees Celsius.
2) Check whether the oil level is normal or not, and whether the automatic water discharge
valve is open or not.
3) Check oil leakage inside the air compressor and whether the machine has abnormal
noise or not after the air compressor is started.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 176
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
4) Frequently open the manual water discharge valve and check discharge water content
and oil content.
5) Periodically clean the filter according to the differential pressure (not more than 0.08Mpa)
in the air compressor.
6) The red emergency shutting down button should not be pressed randomly unless
emergency happens.
7) When the air compressor is shut down, the outlet valve of the air compressor should be
closed, the manual water discharge valve should be opened and the remained water
inside the air compressor should be drained completely.
12.4 Air compressor shutdown protection
1) Main motor overload protection.
2) Emergent shutdown protection.
3) Fan overloads protection.
4) High oil temperature protection (alarms at 100 degrees Celsius and shut down at 110
degrees Celsius).
12.5 Air compressor dryer operation maintain
1) Dryer startup and shutdown operation
a) Switch the startup-shutdown position to the startup position, and when the dryer is
normally started, the local operation indicator lamp is on (green).
b) When trying to stop the dryer, switch the startup-shutdown position to the shutdown
position while the pressure of the two dryer tank is balanced as much as possible,
and then the dryer is shutdown..
2) Dryer maintenance
a) The dryer should be started or shutdown at pressurized conditions.
b) The filter indicated P8P is used for dedust; the filter indicated P8C is used for oil
removal.
c) The dryer filter should be periodically blowdown; the cartridge of the filter should be
replaced when the differential pressure gauge is more than 0.1MPa (the gauge
shows red color)
d) In the operation process of the dryer, the dryer tank has pressure, while the
regeneration tank is pressure free. The two tanks are shifted every five minutes.
13 Fire-fighting System Operation Manual
13.1 Overview
Fire-fighting water system comprises a fire-fighting pump, stabilized pressure pump,
fire-fighting pool, high and low pressure fire-fighting pipe network, invalve and outvalve fire-fighting
hydrants, sprinkler extinguishment facilities and others, and also provides foam fire-fighting water
to the oil depot region. Fire-fighting pump only provides high-pressure fire-fighting water.
13.2 Startup mode of fire-fighting pump
In addition to the self startup according to the chain conditions, the fire-fighting pump can start
and stop by the remote controller of the CRT in the chemical control room (the switch of the
fire-fighting pump of the local control panel is placed on the remote control position) and can also
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 177
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
start and stop on the site (the switch of the fire-fighting pump of the local control panel is placed on
the local position).
13.3 Operation mode of fire-fighting pump
At present the operation mode of the fire-fighting pump is that the stabilized pressure pump
operates for a long term to maintain the pressure of the high and low pressure fire-fighting pipe
network (the stabilized pressure pump is switched per week regularly), and the fire-fighting pump
will automatically start and stop according to the chain conditions when the pressure of the
fire-fighting pipe network declines.
13.4 Chain conditions of fire-fighting pump
1) The pressure of the fire-fighting system is maintained at 1.06 MPa (adjustable) by the
fire-fighting atmospheric pressure stabilizer.
2) When the pressure of the high-pressure fire-fighting pipe network is less than 0.8Mpa
(adjustable), the electric fire-fighting pump is input.
3) When the electric fire-fighting pump fails, the diesel fire-fighting pump is automatically input.
4) When the pressure of the high-pressure fire-fighting pipe network is more than 1.06Mpa, the
fire-fighting pump stops.
5) When the liquid level of the fire-fighting pool is below 1.5 m, two fire-fighting pumps and two
stabilized pressure pumps stop.
13.5 Diesel fire-fighting pump system
Diesel fire-fighting pump body includes a diesel engine, heat exchanger, expansion water
tank, cooling pipeline, flexible coupler, water pump, diesel tank, storage batteries and control
panel and other equipments. Water pump is connected with the diesel engine through the flexible
coupler directly.
13.5.1 Preparations for operation and use
1) Make preparations for operating and using the supporting equipment of the diesel engine
pumping group, such as: oil, water and electricity are in the proper state.
2) Ensure that all cable connections are correct and various switches of the control screen are in
the correct position before operation.
13.5.2 Startup of diesel fire-fighting pump
1) The diesel fire-fighting pump control panel is powered on
2) After the preparatory work is completed, turn on the “Power” switch on the panel (DC control
power supply, or switch from zero position to manual or automatic position), when the DC
control circuit of the diesel engine is powered on, the “power” indicator light is on, and at the
same time the monitor will display the rotation speed, water temperature, oil temperature and
pressure of the diesel engine.
3) Start the diesel fire-fighting pump manually
a) Place the “Manual\automatical” switch on the panel to the “Manual” position, when the
diesel pump group enters into the manual control state.
b) Preheating: when the weather is cold, the pump is preheated prior to startup, the
preheating switch is connected, the preheating indicator light is on, the cooling water of
the diesel engine begins heating, and there is a temperature switch of the water heater,
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 178
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
and the water temperature can be controlled to a certain range. The diesel engine
stops heating if the preheating switch is disconnected.
c) “EDC” power supply: press “EDC Power Supply” button before starting the pumping
group, when “EDC power supply” indicator light is on and an electric spraying controller
is powered on. (Note: the follow-up operations will not be conducted only until “EDC
power supply” indicator light is on)
d) Startup: press “No.1 Battery Startup” button of the diesel engine, and the startup
contact of No.1 Battery is pulled in, when the No.1 Battery provides power supply; if the
No.1Battery lacks of electricity, press the “No.2 Battery Startup” button, when the No. 2
Battery starts and the contact is connected, the No.2 Battery provides power supply, a
motor starts to drive the diesel engine to rotate, and then the operation light is on after
the diesel engine starts successfully. The startup button can be released at this time, a
second startup operation is conducted after the interval of 5 to 10 seconds, and the
appropriate inspection should be carried out if three consecutive startups fail.
e) Speedup: press the “Speedup” button after the diesel engine starts, and the diesel
engine will operate at high speed, and the rotation speed of the diesel engine through
the potentiometer of the screen is adjusted to operate in the rated state or the
necessary rotation speed.
f) Idle speed: press the “Idle speed” button to allow the diesel engine to operate at idle
speed.
g) Stop: press the “Stop” button after it operates at idle speed for three minutes, and
the“Stop” light is on, the diesel engine stop and then the button is released.
13.5.3 Automatic control of diesel fire-fighting pump
1) The control panel automatically works if “Manual/automatic” switch is placed on “Automatic”
position.
2) In the automatic mode, the controller gives out “No.1 Battery Startup” order of diesel engine
when there is automatic startup signal, and meanwhile EDC power supply is automatically
connected so that the diesel engine starts, the controller can give out three consecutive “No.1
Battery Startup” orders if it fails to start, the controller gives out “No.2 Battery Startup” order to
activate the diesel engine if it is not successful in the three times, the controller can give out
three consecutive “No.2 Battery Startup” orders if the activiation fails, and the controller gives
out sound and light alarm signal due to failing in activiation if the activiation is unsuccessful.
After the activiation is successful, the controller will control the diesel engine to run at idling
speed for about five seconds, and then give out idle speed order, so that the diesel engine
operates at the rated rotation speed.
3) During operation of the diesel engine, the controller will give out idle speed order if it receives
automatic shutdown signal, to make the diesel engine run at idle speed for about three
minutes, and then the controller will give out shutdown order so that the diesel engine stops
completely.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 179
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
13.6 Descriptions of fault and alarm of diesel engine fire-fighting pump
1) In operation, if the cooling water temperature, oil temperature, oil pressure and rotation speed
of the diesel engine are beyond the limits, the control panel will give out sound and light alarm
signal and the alarm signal light will give out flashing bright, and at the same time a flashing
LED on the corresponding digital display corresponding to the overranging parameters is also
on, indicating the parameters are beyond the limits. After pressing “Silencer” button, the
sound alarm signal disappears, the light alarm signal is converted to matt indication and
always maintains until the parameters have resumed to the normal. When the overranging
parameters are up to the stopping values, the controller will give out sound and light alarm
signal while giving out stopping signal so that the diesel engine stops emergently due to
failure. At this time, the sound alarm signal can be eliminated by pressing “Silencer” button; as
the light alarm signal has memory function, it will remain until the failure is eliminated, and it
will disappear after pressing “Reset” button.
2) In standby, the alarm signal of a storage battery with low voltage is given out if the voltage of
the storage battery is low.
3) In operation, the sound and light alarm signal of the liquid level is given out if the liquid level is
low.
4) In standby, the alarm signal of charging failure is given out if the charger has no DC
rechargeable power output.
13.7 Descriptions of function buttons
1) “Reset”: When there is fault alarm and the diesel engine stops working, the diesel engine fails
and need be ruled out; press first “Reset” button after the person on duty troubleshoots when
re-starting the generating unit, so that the control screen undoes the alarm signal and is in the
alarm state. In addition, when the control power supply is just connected or the diesel engine
starts, if there are any unusual characters to appear on the digital display, the control panel is
not working properly, this is usually caused by excessively low voltage of the control power
supply, and the control screen can work properly by pressing the “Reset” button. Note: it is
prohibited to press the “Reset” button during normal operation of the diesel engine.
2) “Self-check”: press the “Self-check” button, when the control screen implements the
self-check program. The control screen will simulate the change in the parameters of all
working conditions in the self-check process, and a sound and light alarm and stopping signal
is given out when reaching the overranging alarm and stopping value, and the sound and light
alarm signal can be eliminated by pressing the “Silencer” button and thus light alarm becomes
smooth light. Accordingly, users can check whether the overranging fixed value is correct and
the protection functions meet the requirements.
3) “Silencer”: the control screen can shown a sound and light alarm signal after there are all
kinds of faults. The sound alarm disappears after pressing the “Silencer” button, and all the
light alarms turn into smooth light and continues to work normally.
4) “Time”: when pressing the “Time” button, the total operation time will be shown on the location
of speed display and the original speed display will restore after several seconds.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 180
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
13.8 Inspection items in the operation of diesel pump group
1) Check whether the connecting studs of the diesel engine, water pump and public base are
loose;
2) Check whether the connecting studs and screws of all connecting parts are loose;
3) Check whether the liquid level of the fuel tank is normal and there is leakage in the system;
4) Check whether the liquid level of the oil pan maintains the normal;
5) Check whether the lubrication pre-heating device works normally;
6) Check whether the pressure of the lubrication pre-supply pump in operation is normal;
7) Check whether the water level height of the expansion water tank is normal;
8) Check whether the cooling water preheating device works normally;
9) Check whether there is leakage phenomenon in the cooling water system;
10) Check whether the storage battery starts normally, its voltage is adequate and the charging
device works properly;
13.9 Regular maintenance of diesel pump group
1) Regular maintenance
a) Start the machine once every two weeks and operate it for 15 minutes to check whether
the machine set and all devices maintain still a good state, and conduct a simulation
test of the automated devices to check whether they maintain still a good state.
b) Pay attention to heat preservation of diesel engine and water pump in the cold season
to prevent the equipment from being frozen badly due to low water temperature.. The
room temperature should maintain 5 above.
c) Before the storage battery is used for the first time, it is charged after the battery liquid
is filled.
d) Check the voltage of the diesel engine for starting the battery and the height of storage
battery electrolyte. Maintain the storage battery, storage battery terminals and wiring to
be clean and contact well.
e) Check the siliencer and exhaust pipeline, remove carbon deposition and prevent sparks
from generating.
f) Check whether the water pump packing seal is worn, and replace it timely if necessary.
Check whether the lubricating resin of the water pump is consumed.
g) The fuel storage tank should always be full as much as possible but be definitely not
less than 50% of the fuel tank capacity. When refueling, it should be ensured that
moisture content and impurities are excluded.
2) Switching and maintenance mode
a) When it can not automatically be put into operation and the fire-fighting water is
required for fire, the startup mode should first be switched to the manual mode. The
pump selection switch turns to the pump to be activated and then the startup button is
pressed.
b) Trial run # 1 and # 2 electrical fire-fighting pump every Monday on day shift. Trial run
the diesel fire-fighting pump on the 10th and 25th day monthly.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 181
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
14 Appendix
14.1 Twenty-five Key Requirements to Prevent Serious Accident and Failure in Electric
Power Operation (Chemical Part) Issued by China Grid
14.1.1 Prevention from large area corrosion
1) Be in accordance with “Quality Criterion of Water and Steam for Generating Unit and Steam
Power Equipment” (GB12145—1999), “Guide for Chemical Supervision of Water and Steam
in Thermal Power Plants” (DL/T561—1995), “Opinions of Corrosion of The condenser Copper
Alloy Tube of Thermal Power Plant” and “Correction Measures and Requirements to Prevent
Corrosion of the boiler Structure in Power Plant” and other relevant Manual strictly and
strengthen chemical supervision.
2) Unqualified water is strictly prohibited to enter into the boiler and unqualified steam is strictly
prohibited to mix. Acid wash water-cooled wall in a timely manner if deposit can meet pickling
requirements to avoid corrosion or hydrogen brittleness. Stop and protect boiler according to
requirements of “Guide for Lay-up of Thermal Power Equipment in Fossil Fuel Power Plant”
(SD—223—1987) to avoid shutdown and corrosion of furnace tubes.
14.1.2 Prevention from tube explosion of pressure vessel
Color of gas bottles in use is strictly prohibited to change to avoid misuse. Take measures to
not dump gas bottles and place steel cylinders containing liquid chlorine horizontally and
temperature of locations to place liquid chlorine or ammonia shall meet requirements.
13.1.3 Prevention from motor damage
Water quality of water-internal-cooling generator shall be within regulated scope and it is
allowed to add corrosion inhibitor in water during operation of units whose power is equal to or less
than 125MW to slow up copper tubes but PH value must be more than 7.0.
14.2 General Principle of Electrical Part and Pump
14.2.1 Inspection items before power on the motor are as follows:
1) Inspect integrity of electrical loop and equipments with terminated work order and put them
into protection devices.
2) Fix connecting wires of the motor and cable shell firmly.
3) Fix protective cover of cable head of the motor and blower cover firmly.
4) Check if there is oil in the startup device of wire wound the motor with normal oil level or not.
5) Guarantee no water in the cold air chamber if the motor is cooled by air.
6) The motor and mechanical equipments shall be intact without startup obstacle so that they
can meet startup conditions.
7) Guarantee sufficient oil in the bearing oil level and cover then place the oil system into
operation if it belongs to reinforced lubrication. It is also required to open cooling water if
bearing is cooled by water.
8) Supply cooling water if the motor is cooled by air cooler.
14.2.2 Inspection items during operation of the motor are as follows:
1) Fix connecting wires of shell and protective cover of cable head firmly.
2) Check if there is spark for slip ring or commuter of DC the motor and cover protective cover of
commuter and slip ring and handle of slip ring can not exceed dangerous mark.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 182
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
3) Guarantee no obstacle in ventilation hole of the motor and normal operation of air cooler
without water leakage.
4) Guarantee no accumulated ash and water on the motor and remove sundries such as ash,
powder and water vapor and so on which may enter into the motor and startup devices in a
timely manner.
5) Monitor and compare temperature of the motor shell and bearing under the same ambient
temperature and find out reasons if there is abnormal temperature rise and take measures to
strengthen ventilation and monitoring and reduce load if necessary. The maximum monitoring
temperature of the motor coil and iron core can not exceed the temperature under any
circumstance according to the Manual of manufacturer and it can not exceed 105 and
temperature rise can not exceed 65 if there are no Manual of manufacturer. The maximum
temperature of sliding bearing can not exceed 80 (and temperature rise can not exceed
40) and that of rolling bearing can not exceed 100(and temperature rise can not exceed
60).
6) In general, the motor shall operate within variation scope of -5% to +10% of rated
voltage with constant rated output (which is between 5.7kV and 6.6kV and voltage is
between 360V and 420V). Unbalanced value of voltage in phases during operation under
rated output can not exceed 5% and pay attention to heating and vibration and so on of the
motor during unbalanced operation period of voltage.
7) Current of the motor can not exceed +5% of rated value during normal operation and
guards shall strive to reduce it to rated current within 15 minutes if it is exceeded by +5% to
+10%.
8) Measured amplitude of every bearing during operation of the motor can not exceed following
values:
Rated rotary speed
(r/min)
3000
1500
1000
750 and below
Amplitude
(dual-amplitude)(mm)
0.05
0.085
0.10
0.12
14.2.3 Inspection items during operation of cables are as follows:
1) Guarantee intact cover plate of cable trench and no water, oil or other sundries in the cable
trench.
2) Check if pavement with laid cables is normal or not. Check if stakes are intact without
excavation trace or not.
3) It is not allowed to pile rubbles, slag, building materials, lumpish matters, acid or alkaline
excrement or stack swallow hole and so on along cable lines.
4) Check if cable head is not heated without casing rupture and discharging trace or not.
5) Guarantee intact ventilation, drainage and lighting facilities and so on in cable trench or cable
channel and check if fire prevention facilities are intact or not.
6) Temperature of cable sheath can not exceed permissible normal value and load current can
not exceed permissible value.
7) Pay attention to water level of cable trench in summer or thunder storm season.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 183
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
13.2.4 General operation requirements of the motor
1) Guards of mechanical equipments driven by every motor shall master power supply mode of
the motor and operation mode of relay protection and automatic device.
2) Every motor shall have rated nameplate of original manufacturer on the shell and repair
personnel shall supplement nameplates in a timely manner if they are lost.
3) Paint on shell of the motor, ventilation pipes and metallic structure and name and enumerate
equipments according to the unit.
4) The motor and machines shall have arrow marks to indicate rotation direction.
5) Outgoing lines of the motor and cable heads and exposed rotary parts shall have firm barrier
or protective guard.
6) Shell of the motor and startup device shall be grounded according to the Manual of “Technical
Specifications of Grounding” and it is strictly prohibited to work on grounding body of the
motor in operation.
7) Standby the motor shall be started at any time and it is required to prepare for periodic chart of
shifting operation or trial operation of the motor. Every guard shall operate the motor
according to periodic chart of shifting operation or trial operation strictly.
8) The motor with normal switchover and startup conditions shall be started according to
switchover cycle and measure insulation resistance if volume of the motor without startup
conditions is more than 50kW and it is stopped for 10 consecutive days or it is necessary to
measure insulation resistance before startup. (There is no need to measure insulation
resistance with normal heater input of the motor with moisture-proof heater but repair
personnel must measure insulation resistance after repairing the motor or cables.)
9) Put standby the motor into trial operation for every 10 days to prevent it from being affected
with damp if it is installed in wet locations.
14.2.5 Measurement Manual of insulation resistance of the motor are as follows:
1) Insulation of high-voltage the motor shall be measured by magneto-ohmmeter of 2500V and
insulation resistance can not be less than 1 mega ohm for every 1000V and that of
low-voltage the motor whose voltage is equal to or less than 380V shall be measured by
magneto-ohmmeter of 500V and insulation resistance can not be less than 0.5 mega ohm for
every 1000V. (Insulation resistance of DC the motor can not be less than 0.5 mega ohm.)
2) Insulation resistance of the motor must be measured under cold standby status of loop.
3) Insulation resistance must be measured after the motor is affected with damp, smoked by
steam or poured by water.
13.2.6 Operation principle of power failure and supply of the motor:
1) Supply power to the motor by primary loop and operate according to sequence of power knife
switch and switch and operate according to reverse sequence during power failure.
2) Check if control fuse is placed in its accurate position or not during power supply. That is,
check if green lamp is on or not then take control fuse down during power failure.
3) Selection switch shall be in remote control position according to operation mode of switch
panel of the motor.
4) It is strictly prohibited to use gauge and indicator light as the only judgment basis of opened or
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 184
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
closed switch.
5) Close knife switch and inspect whether blade is in closing or opening position if applicable.
6) Remote operators can not start the motor until contacting local guards if its knife switch is
closed remotely. Local guard shall keep the motor until its rotary speed can increase to rated
rotary speed. Monitor startup process according to ampere meter if applicable and inspect the
motor body according to detailed conditions after startup.
14.2.7 Permissible startup times of the motor with squirrel cage type rotor shall be in accordance
with following Manual strictly.
1) The motor whose volume is equal to or more than 100kW is allowed to start up twice
continuously under cold condition and once under hot condition.
2) The motor whose volume is less than 100kW is allowed to start up for three times
continuously under cold condition and twice under hot condition.
3) Startup times of the motor with accident treatment whose startup time is not more than 3
seconds can be increased by one.
13.2.8 Definition of the motor status:
1) Cold condition means that stalling time of the motor is equal to or more than 30 minutes.
2) Thermal condition means that stalling time or attenuation time of startup current of the motor
is less than 30 minutes.
3) Attentions to startup of motors as follows:
4) Start up the motor one by one and it is usually not allowed to start up two or more the motors
with large volume on one bus at the same time. It is required to contact integration control
personnel to adjust bus voltage before startup of the motor with large volume.
5) It is strictly prohibited to close the knife switch again under normal conditions if switch can not
be closed or before finding out tripping reasons during startup of the motor. It is required to
open power switch of the motor and find out reasons if startup time exceeds general startup
time of the motor and current has not been attenuated to normal value.
6) Open power switch of the motor and find out reasons instantly if the motor has noise without
rotation or it can not reach normal rotary speed after closing knife switch of the motor.
14.2.9 Common faults, judgment and treatment of electrical equipments
14.2.9.1 Stop the motor instantly if there is any circumstance:
1) Instant personal injury caused by accident of the motor if necessary;
2) Strongly vibrated or damaged motor or mechanical parts;
3) Fired or scorched motor;
4) Rapid temperature rise of the motor or bearing which has exceeded limit and rapid declination
of rotary speed;
5) The motor. flooded
14.2.9.2 The motor does not start up
1) Possible reasons
a) Inaccurate position of conversion switch;
b) Inaccurate interlocked position under program control status;
c) No reposition after protection motion of the motor;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 185
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
d) Power failure or broken fuse protector;
e) Damaged contact point of AC contactor which can not be suction.
2) Treatment method
a) Turn interlocked switch to the correct position.
b) Ask local personnel to check if the motor is excellent or not.
c) Supply power after resetting for thermo-couple motion.
d) Ask repair personnel to inspect and treat for other electrical protection motions.
e) Replace fuse or supply power again.
f) Find out reasons and remove mechanical faults.
14.2.9.3 Trip during operation of the motor
1) Possible reasons
a) Excessive current and over load;
b) Failure of startup switch;
c) Unclosed outlet valve or excessive opening;
d) Broken phase of three phases of grounding wires;
e) Abrasive or jammed rotary parts;
f) Friction between impeller and pump shell;
g) Bent shaft and damaged bearing;
h) Vane jammed by sundries;
i) Power failure.
2) Treatment method
a) Startup of standby motor;
b) Load adjustment;
c) Repair and treatment.
14.2.9.4 Larger noise during operation of the motor
1) Possible reasons
a) Single-phase operation;
b) Unbalanced three-phase current of the motor;
c) Uneven air gap between stator and rotor of the motor;
d) Collision or sundries between blower and cover;
e) The motor is installed roughly or loose foot screw;
f) Bearing problem.
2) Treatment method: Stop operation instantly and contact repair personnel for treatment.
14.2.9.5 Excessive temperature rise of the motor or burnt winding
1) Possible reasons
a) Overload for a long time;
b) Trouble of heat engine;
c) Broken one-phase fuse;
d) Poor ventilation and heat elimination;
e) Local short-circuit or grounding of stator winding;
f) Other reasons such as inflexible driving mechanism;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 186
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
2) Treatment method: Stop operation instantly and contact repair personnel for treatment.
14.2.9.6 Heated bearing of the motor
1) Possible reasons
a) Incorrect installation and excessive vibration;
b) Inconsistent gap between crankshaft, bearing and end cover or improper installation and
excessive axial float.
c) Poor lubrication or incorrect oil quality.
2) Treatment method: Stop operation instantly and contact repair personnel for treatment.
14.2.9.7 Air switch of main power which can not be closed
1) Possible reasons
a) Emergency stop button not reset;
b) Damage trip coil or not voltage;
c) Damaged tripping mechanism not reset.
2) Treatment method: Contact repair personnel for treatment.
14.2.9.8 Large noise after closing knife switch of main power switch
1) Possible reasons
a) Insufficient voltage of trip coil;
b) Unadjusted tripper and excessive gap between suctioned armature iron;
c) Obstacle to armature iron after tightening switch cover.
2) Treatment method: Contact repair personnel for treatment.
13.2.9.9 Noise after suctioning contactor
1) Possible reasons
a) Insufficient suction of coil;
b) Poor suction problems such as blocked armature iron or inaccurate alignment;
c) Ruptured short-circuit ring;
d) Excessive axial offset.
2) Treatment method: Contact repair personnel for treatment.
14.2.9.10 Electric leakage of shell
1) Possible reasons
a) Low insulation resistance of the motor;
b) Rupture or aging of outgoing lines or connection between connecting plug and shell;
c) Damaged bottom plate of terminal or local connection in the winding;
d) Poor grounding of shell.
2) Treatment method: Contact repair personnel for treatment.
14.2.10 Operation of the water pump
14.2.10.1 Inspection before startup of the water pump
1) Finish repair and work order with written records for repair equipments.
2) Supply power to electrical valve of pump inlet and guarantee intact valve and normal
operation without leakage.
3) Guarantee intact water pump without foreign matters which may obstacle operation.
4) Check if manual segregation valve is in correct position or not according to conditions of the
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 187
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
water pump.
5) Check if bearings can be connected firmly with intact protective cover and firm fixation without
loss foot screw or not.
6) Guarantee intact gauges in pump outlet and manual valve of the pressure gauge is in closed
position and indicators of flow and pressure converters are zero.
7) Guarantee firm supply of water supply pipes of the water pump and intact insulation layer.
8) Bearing oil level of the water pump shall be between 1/2 and 2/3 and oil shall be transparent
without sundries.
9) Guarantee sufficient lighting on the site and excellent ventilation and complete fire prevention
measures.
14.2.10.2 Operation during operation of the water pump
1) Guarantee normal operation sound and excellent integrity during operation of the water pump
without leakage of the water pump.
2) Bearing temperature of the water pump can not exceed ambient temperature which is 35 and the maximum temperature can not exceed 85 and vibration shall be less than 0.08mm.
Flange temperature shall be the same to that of pump body and drainage pipes shall be
smooth after dripping water for 10 to 20 drips for every minute.
3) Guarantee firm tightening piece and intact protective cover and foundation bolt can not be
loose.
4) Operation of remote and local gauges shall be normal and pressure shall be within the scope
of regulated pressure and current is less than rated value. Flow shall be within the regulated
scope and flow, pressure and current shall correspond mutually.
5) Guarantee correct position and indication of every valve ad excellent appearance of valve
without water leakage or misplacement.
6) Guarantee normal operation of pressure and flow converters and correct fixation of
connecting wires without water leakage.
7) Guarantee no inversion for standby pump.
8) Erect support of water supply pipes without distortion or deformation of expansion joints and
guarantee excellent insulation layer without water leakage for system pipes.
14.2.10.3 Common faults, judgment and treatment of the water pump
14.2.10.3.1 Abnormal sound of the water pump
1) Possible reasons
a) Damaged impeller, bearing or loss rotary parts.
b) Foreign matters suctioned into the water pump.
c) Operation under overload.
2) Treatment method
a) Integral load;
b) Stop the water pump and contract repair personnel for treatment.
14.2.10.3.2 Large vibration of the water pump
1) Possible reasons
a) Air in the water pump or insufficient opening of outlet valve;
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 188
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
b) Loose foot screw;
c) Unbalanced motor and axial line and severely abrasive bearing and rotary parts.
d) Loose or damaged parts of rotary parts;
e) Operation under overload.
2) Treatment method
a) Remove air in the water pump and open the valve of large opening;
b) Operate under reduced load;
c) Contact repair personnel for treatment.
14.2.10.3.3 No water outlet or reduce water supply quantity of the water pump
1) Possible reasons
a) Non-hermetic water absorption pipes with air;
b) Unexhausted air in the water pump;
c) Jammed water passageways;
d) Low rotary speed and reverse direction of the motor;
e) Damaged impeller key;
f) Water source problems (such as low water level and so on);
g) High pressure of main pipe and little water consumption;
h) Unopened inlet valve or shed core.
2) Treatment method
a) Gas-tight pipes;
b) Startup again after exhausting air;
c) Inspection and dredging of passageways;
d) Inspection of power lines;
e) Repair and treatment;
f) Sufficient water source;
g) Some pumps are out of operation;
h) Open the inlet valve or contact repair personnel for repair.
14.2.10.3.4 Overheated bearing or with noise
1) Possible reasons
a) Poor quality or low oil level;
b) Improper gap between bearings;
c) Abrasive bearing;
d) High oil level;
e) Operation under overload.
2) Treatment method
a) Turn down outlet valve and reduce the load;
b) Stop the water pump and replace or add oil;
c) Contact repair personnel for repair.
14.3 General Principle of Chemical Technology Supervision
14.3.1 Guidelines of chemical technology supervision
Chemical supervision is one of important links to guarantee safe, economic and stable
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 189
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
operation of power supply equipments and its main task is to take detection measures which can
adapt power generation development and scientific management method in a timely manner to
strength quality supervision of water, steam, gasoline, hydrogen and fuel and so on to avoid and
slow up corrosion, scale, salt accumulation and inferior oil quality during operation, shutdown and
standby period of thermodynamic equipments. It is required to find out latent troubles of oil-filled
electrical equipments in a timely manner and strengthen fuel supervision to coordinate with
economic and safe combustion of the boiler to increase efficiency of the unit and find out and solve
hidden troubles caused by chemical problems in a timely manner to avoid occurrence of
accidents.
1) Insist in guideline of “precaution primary and quality first” and realistic and scientific attitude
for chemical supervision and research continuously and take new technology to enhance
supervision level.
2) Be in accordance with relevant Manual of management during system design, installation,
debugging, operation and repair phases for chemical supervision to guarantee health unit.
14.3.2 Chemical supervision during startup phase of unit
1) Operation department shall wash the condenser, water supply system and boiler in sections
by desalinated water of regulated PH value after adding ammonia and chemical deoxidizer
before startup of the unit. Next system can not be washed until every washed section is
qualified and ignition is not allowed until water quality of the boiler is qualified. Carry out
hydrostatic test after repairing boiler and it is required to use chemical desalinated water of a
certain quantity of ammonia and deoxidizer.
2) Wash samplers during startup of the unit and adjust flow according to the Manual so that
sample flow can be between 500 mL/min and 700 mL/min and temperature shall be less than
30.
3) Add deoxidizer for heating and adjust steam exhausting opening during startup of the unit to
guarantee qualified oxygen dissolved in the water supplied to boiler.
4) Strengthen sewage treatment and charging treatment during startup of the unit and
unqualified condensing water and drained water can not be recycled and unqualified steam
can not be washed and rotated. Strengthen sewage treatment treatment after startup of the
boiler if the boiler water is turbid and take measures such as limiting load, reducing pressure
and replacing water and so on if necessary until boiler water is clear.
5) Wash silicon according to requirements strictly when boosting the pressure of the boiler and
pressure of silicon dioxide in boiler water can not be boosted until meeting requirements of
next phase. Reduce pressure for operation if silicon dioxide in boiler water exceeds limit.
6) Startup time shall be calculated according to startup standard from watering of the unit to 8
hours after synchronization and result after 8 hours shall be recorded into the operation data
for statistics of chemical specialty.
14.3.3 Normal operation management of the unit
1) Please refer to the manual for quality supervision items of water vapor and control standard
and times of operation unit and water treatment system and add analysis times and items
according to detailed conditions if there is abnormal operation or during startup of the unit.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 190
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
2) Chemical operator shall fill in the daily chemical operation report every day and report it to
supervisor and chemical engineer after manual analysis and confirmation of items which
exceed the standard. Contact chemical examination group for validation if chemical operation
can not define accuracy of chemical examination result and chemical examination group shall
examine water supply and water vapor systems once every week and report it to chemical
operator and engineer if standard is exceeded so that chemical operator can treat and report
it to supervisor for treatment if unit operation needs coordination. Definite the technical
disclosure of requirements which can not be treated by the construction team with next
construction team and make records at the same time. It is required to report it to chemical
engineer, assistant branch manager and manager when it reaching the primary treatment
value and report it to chemical engineer, assistant branch manager, manager and vice
general operation engineer when it reaching the secondary treatment value and report it to
chemical engineer, assistant branch manager, manager, vice general operation engineer and
vice general production manager when it reaching the tertiary treatment value and people of
various levels shall treat according to treatment principle of abnormal water vapor in three
levels.
3) Wash sampler periodically during operation and sample periodically to remove copper and
iron according to the Manual.
4) Strengthen quality supervision of drained water and returned water and it can not enter into
the system directly without treatment. It is required to control water vapor loss in the plant and
it shall meet following requirements.
5) 300MW Unit Not more than 1.5% of rated evaporation rate
6) 135MW Unit Not more than 2.0% of rated evaporation rate
7) Take effective measures scientifically to enhance boiler water quality and reduce blow-down
rate but it can not be less than 0.3% by considering various indicators of energy-saving
supervision and chemical technological supervision comprehensively.
8) Water and vapor quality standard issued by electricity authority refers to controlled limit value
(namely, normal value) to maintain reliable and stable operation for a long time. 50% to 70%
of limit value shall be regarded as the control value of actual operation in accordance with
Manual of electricity authority to guarantee safe and economic operation of the unit on the
basis of enhanced integral level of the equipments.
9) Switch over operation equipments periodically and notify defects of equipments to
maintenance department for treatment in a timely manner to ensure that equipments can
operate normally at any time.
10) Fossil-fired power plant must have necessary on-line chemical instruments to enhance
reliability, timeliness and continuity of quality supervision of water vapor. Supplied water and
boiler water shall have PH, conductivity and phosphate radical tables and supplied water
(namely, water outlet of deoxidizer) and condensing water shall have dissolved oxygen table
and supplied water and condensing water shall have conductivity table (of hydrogen sensing).
Main stream shall have silicon and sodium tables and supplied water shall have conductivity
table (of hydrogen sensing). Prepare for other instruments one after the other according to
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 191
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
detailed conditions and instruments used in the laboratory shall meet requirements in
“Compilation of Testing Methods, Standards and Manual of Water Vapor of Fossil-fired Power
Plant” and they shall be examined periodically and used within the period of validity.
11) Analyze technology and economy of chemical specialty and save medicines to reduce
material consumption.
14.3.4 Abnormal quality management of water vapor
Report deteriorated water vapor quality to leaders in a timely manner and find out reasons
for treatment and treat according to following tertiary treatment principle if water vapor continues
to deteriorate.
That is, the primary treatment begins from deteriorated water vapor quality (which exceeds
the standard) and abnormal conditions shall be restored within 72 hours. Secondary treatment
shall be restored within 24 hours and tertiary treatment shall be restored within 4 hours. Stop the
boiler for treatment instantly if deteriorated water vapor quality can not be restored normally on
time. It is required to take measures of a higher level for abnormal treatment method if
deteriorated water vapor quality can not be restored normally within regulated time. Normal
values of drum boiler can be restored by pressure drop and it is required to stop boiler
emergently when PH of the boiler water is less than 7.0 and sodium content in the condensing
water is more than 400μg/L.
Tertiary treatment value is as follows:
Treatment value Water sample
Item
Normal value
Primary Secondary Tertiary Sodium: μg/L ≤10 10~20 20~35 >35
Condensing water Electric
conductivity: μs/cm
≤0.3 0.3~0.4 0.4~0.5 >0.5
With
copper8.8~9.3
<8.8 or >9.3
pH(25) Without
copper9.0~9.6
<9.0 or >9.6
<8.0
~
Electric
conductivity:μs/cm
≤0.3 0.3~0.4 0.4~0.65 >0.65
Supplied water
Dissolved oxygen:
μg/L
≤ 7 >7 >20 ~
Boiler water PH (25) 9~10 <9.0 <8.5 <8.0
Stop boiler instantly when PH of supplied water is less than 7.0 or sodium content in condensing
water is more than 400ug/l.
Note: Measure Cl-, Na+, conductivity and alkalinity of the boiler water when water quality is
abnormal to find out reasons and take measures for treatment.
12) Chemical specialty shall analyze accuracy of data and representation of sample firstly when
abnormal water vapor quality can reach the “primary treatment value” and report it to
supervisor instantly after comprehensive analysis and confirmation. Supervisor shall organize
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 192
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
investigation and notify corresponding departments for treatment. (Ask integration control
personnel for system adjustment and ask maintenance department to solve equipment
problems.) In the meanwhile, it is required to add testing times and strengthen supervision
until it can be qualified. Supervisor shall report it to division heads and chemical supervision
engineer if abnormal water vapor quality can not be qualified after treatment of the staff.
13) Report detailed conditions to supervisor, chemical supervision engineer and relevant division
heads in a timely manner after confirmation of chemical specialty that water quality of
supplied water, boiler water or condensing water can reach secondary treatment value with
impossibility of restoration. The supervisor shall take corresponding measures for treatment
according to the detailed conditions of the unit and report it to leaders of the company if
abnormal water quality can not be qualified after treatment of the staff.
14) Report it to supervisor, chemical supervision engineer and relevant department managers
instantly when water quality of supplied water, boiler water or condensing water can reach the
“tertiary treatment value”, the supervisor and chemical supervision engineer shall report it to
leaders of the company at the same time and above people shall rush to the site instantly after
receiving the report and leaders of the company shall command uniformly and take emergent
measures.
15) Report it to the supervisor, chemical supervision engineer and relevant department managers
instantly if the condenser leaks or quality of condensing water or supplied water can exceed
the standard. Supervisor and chemical supervision engineer shall report it to leaders of the
company at the same time and above people shall rush to the site instantly after receiving the
report. Leaders of the company shall command uniformly and caulk in a timely manner and
strengthen sewage treatment of the boiler and monitor variation of PH value of the boiler
water. It is necessary to take measures such as reducing pressure and limiting load even
emergent shutdown measures to protect equipments and avoid accidents if the condenser
continues to leak and water quality deteriorates rapidly.
16) Stop equipments emergently for treatment without request if there are accidents which may
endanger safety of people and equipments and report it to relevant leaders instantly after the
event.
14.3.5 Supervision during repair phase of the unit
1) Responsible person of chemical supervision shall propose inspection items and requirements
with regard to water vapor quality before repairing thermodynamic equipments and inspect,
record, sample and analyze them with relevant personnel after inspection and disassembly of
equipments for comprehensive judgment and propose correction opinions by aiming to
existing problems. Sediments in the equipments can not be removed and it is not allowed to
repair in such parts before inspection of chemical supervision.
2) Inspect scale and corrosion of deoxidizer, economizer, water-cooled wall, super-heater,
impeller of turbine, baffle and copper tube of condensing tube and measure scale quantity.
3) Antisepsis management during shutdown and standby phase of the unit
4) Take corresponding antisepsis measures during overhaul, minor overhaul, temporary
inspection or standby periods of the unit and record detailed operation methods in the
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 193
Rev.: A
QUANG NINH THERMAL POWER JOINT STOCK COMPANY 2×300 MW
BOP OPERATION MANUAL SEC
integration control and chemical manuals. Record antisepsis date, method and supervision
control indicators and operation department shall be responsible for it is discharging water by
hot boiler with protection of ammonia injection and hydrazine and nitrogen-filling protection
operation and equipment maintenance department shall be responsible for system installation.
5) Take antisepsis measures for equipments to prevent steam, water and oil in adjacent boiler or
public system from mixing and entering into the standby unit.
Date 2008-09-16 No. : QN1-SEC-G-04-TP-005 Page 194
Rev.: A