Bonding, Grounding Bonding, Grounding and the NECand the NEC
Presented by The National Association of Certified Home Inspectors
www.NACHI.org
![Page 2: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/2.jpg)
The New Code …The New Code …
• The 1999 and 2002 editions of the NEC* have now clearly defined the separate and vitally important purposes of groundinggrounding and bondingbonding in making safe electrical installations
*The National Electrical Code (NEC) is a registered trademark of the National Fire Protection Association,
www.nfpa.org.
![Page 3: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/3.jpg)
The New Code …The New Code …
• Section 250-4 establishes new performance requirements which clarify what groundinggrounding and bondingbonding are required to accomplish
![Page 4: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/4.jpg)
The New Code …The New Code …
Section 250-2 introduces and defines the new terms:
• Ground Fault
• Ground Fault Current Path
• Effective Ground Fault Current Path
![Page 5: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/5.jpg)
The New Code …The New Code …
• These new definitions are in addition to the two important definitions in Article 100 which apply to Section 250-2
![Page 6: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/6.jpg)
The New Code …The New Code …
These definitions are:
• Grounded - Connected to earth
• Bonded - The permanent joining of metallic parts to form an electrically conductive path that ensures electrical continuity and the capacity to conduct safely any current likely to be imposed
![Page 7: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/7.jpg)
The New Code …The New Code …
• The importance of groundinggrounding electrical equipment seems to be well understood
• The purpose and intent of bondingbonding to create a low impedance ground fault return path seems to be less understood
![Page 8: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/8.jpg)
The New Code …The New Code …
• The importance of bonding is best described in the following graphics which review how bonding performs in a typical circuit
![Page 9: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/9.jpg)
L O A D
A Typical Circuit …A Typical Circuit …
•100’ of Overhead Distribution Line
•25’ of Service Drop
•25’ of Service Entrance Conductor
•100’ of Branch Circuit Conductors
![Page 10: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/10.jpg)
L O A D
Current flows…...
A Typical Circuit …A Typical Circuit …
![Page 11: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/11.jpg)
L O A D
From the transformer to our service …
Path of Current Flow - Path of Current Flow - Normal OperationNormal Operation
![Page 12: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/12.jpg)
L O A D
Through the overcurrent device to our load …
Path of Current Flow - Path of Current Flow - Normal OperationNormal Operation
![Page 13: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/13.jpg)
L O A D
Through the load returning to the service …
Path of Current Flow - Path of Current Flow - Normal OperationNormal Operation
![Page 14: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/14.jpg)
And back to the transformer.
L O A D
Path of Current Flow - Path of Current Flow - Normal OperationNormal Operation
![Page 15: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/15.jpg)
What determines the amount of current that will flow in this circuit?
L O A D
Path of Current Flow - Path of Current Flow - Normal OperationNormal Operation
![Page 16: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/16.jpg)
The total resistanceresistance or impedanceimpedance in the circuit will determine the amount of current that will flow in the circuit.
L O A D
Path of Current Flow - Path of Current Flow - Normal OperationNormal Operation
![Page 17: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/17.jpg)
Things You Can Count Things You Can Count On …On …
• Ohm’s Law Works– We can change the code, or
– Hire a different contractor, or
– Use romex instead of EMT, but
• E = I x R still works!
![Page 18: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/18.jpg)
How is our circuit protected against overload and short circuit?
L O A D
Overload and Short Overload and Short Circuit ConditionsCircuit Conditions
![Page 19: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/19.jpg)
The overcurrent device protects this circuit from both overload and short circuit.
15A Circuit Breaker
L O A D
Overload and Short Overload and Short Circuit ConditionsCircuit Conditions
![Page 20: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/20.jpg)
Ground Fault ConditionGround Fault Condition
• So let’s talk about a ground fault condition …
• Which certainly sounds like the one condition where grounding would be important and decide for ourselves whether …
• Grounding provides protection for equipment or personnel under a ground fault condition
![Page 21: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/21.jpg)
What happens if the hot conductor comes into contact with our metal box?
L O A D
Ground Fault ConditionGround Fault Condition
![Page 22: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/22.jpg)
L O A D
And our friend comes along and touches it? Is he in jeopardyjeopardy?
Ground Fault ConditionGround Fault Condition
![Page 23: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/23.jpg)
No … not at all … and why not?
L O A D
Ground Fault ConditionGround Fault Condition
![Page 24: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/24.jpg)
Because the transformer we’re looking at is not groundedgrounded so there is no no path through the earthpath through the earth for current to return to the transformer.
L O A D
Ground Fault ConditionGround Fault Condition
![Page 25: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/25.jpg)
Yes, that was a “trick” question … sorry about that … but the intent was to make a point.
L O A D
Ground Fault ConditionGround Fault Condition
![Page 26: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/26.jpg)
Things You Can Count Things You Can Count On …On …
• No circuit – no current No circuit – no current
• Current does not flow unless there is a continuous path from one side of the source of supply to the other
• Current cannot travel through the earth to return to a transformer unless the transformer is grounded
![Page 27: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/27.jpg)
So our friend in this situation is perfectly safe … however …
L O A D
Ground Fault ConditionGround Fault Condition
![Page 28: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/28.jpg)
What do we know about utility company transformers?
L O A D
Ground Fault ConditionGround Fault Condition
![Page 29: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/29.jpg)
They’re grounded … and, with this transformer grounded, our friend is in serious jeopardy.
L O A D
Ground Fault ConditionGround Fault Condition
![Page 30: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/30.jpg)
Because utility transformers are grounded, we need to do something to our equipment to keep our friend from being electrocuted.
L O A D
Ground Fault ConditionGround Fault Condition
![Page 31: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/31.jpg)
Can we protect our friend by grounding our metal equipment? Let’s take a look.
L O A D
Ground Fault ConditionGround Fault Condition
![Page 32: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/32.jpg)
Grounding our equipment provides a second path for fault current.
L O A D
Ground Fault ConditionGround Fault Condition
![Page 33: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/33.jpg)
L O A D
The first path is through our friend to earth and back to the transformer.
Ground Fault ConditionGround Fault Condition
![Page 34: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/34.jpg)
L O A D
The new second path is through our metal equipment to earth and back to the transformer.
Ground Fault ConditionGround Fault Condition
![Page 35: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/35.jpg)
Fault Current PathFault Current Path
• We need to open a 15A Circuit Breaker as quickly as possible. This will require a fault current of 60A to 75A (four to five times the rating of the breaker)
• We can use Ohm’s Law to find out how much current will flow on our new path
![Page 36: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/36.jpg)
The voltage is 120V. We need to know the resistance in this circuit to calculate current.
L O A D
Ground Fault ConditionGround Fault Condition
![Page 37: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/37.jpg)
Fault Current PathFault Current Path
• Assuming a minimum of 5 ohms resistance through each grounding electrode, we know there is at least 10 ohms resistance in the fault path that we created by grounding our equipment
![Page 38: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/38.jpg)
Fault Current PathFault Current Path
• Therefore, using Ohm’s Law:– E = I x R
– Transposed to: I = E / R
– Where: I (current) = E (voltage) / R (resistance)
– And so, I = 120 / 10 = 12A
![Page 39: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/39.jpg)
Fault Current PathFault Current Path
Only 12 Amps …Only 12 Amps …• Will 12 Amps trip our 15A circuit
breaker?
Absolutely not!
![Page 40: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/40.jpg)
L O A D
So the overcurrent device does not open and we have fried our friend!
With Equipment With Equipment GroundedGrounded
![Page 41: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/41.jpg)
Conclusion …Conclusion …
•Grounding does not protect equipment or personnel from a ground fault!
![Page 42: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/42.jpg)
The vital connection left out of our discussion until now is the bonding of metal equipment to the service neutral.
L O A D
The Bonding The Bonding ConnectionConnection
![Page 43: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/43.jpg)
The Bonding The Bonding ConnectionConnection
• Every piece of conductive metal which is a part of our system or likely to become energized …
• Must be connected together by an electrically continuous metal-to-metal contact or by an equipment grounding conductor
![Page 44: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/44.jpg)
The Bonding The Bonding ConnectionConnection
• These connections create an electrically continuous, low resistance path from every part of our system back to the service equipment
• At the service, these connections terminate on the neutral bus creating an:
• “Effective Ground Fault Current Path”
![Page 45: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/45.jpg)
These bonding connections let us use the neutral as a return path for fault current.
L O A D
The Bonding The Bonding ConnectionConnection
![Page 46: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/46.jpg)
Bonding provides a third path for fault current to return to the source of supply.
L O A D
The Bonding The Bonding ConnectionConnection
![Page 47: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/47.jpg)
Fault Current PathFault Current Path
• We need to open a 15A circuit breaker as quickly as possible. This will require a fault current of 60A to 75A (four to five times the rating of the breaker)
• We can use Ohm’s Law to find out how much current will flow on our new path
![Page 48: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/48.jpg)
Fault Current PathFault Current Path
The resistance in this path includes
• 100’ - #2 AL OH Distribution .032
• 25’ - #4 AL Service Drop .013
• 25’ - #2 CU Service Entrance .005
• 100’ - #14 CU Branch Circuit .307
Resistance to the point of fault .357 ohms
![Page 49: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/49.jpg)
L O A D
.357 ohms
The resistance from the point of fault through our metal equipment back to the neutral is assumed to be the same as the branch circuit wiring and 100’ of #14 cu has a resistance of .3 ohms.
.3 ohms
The Bonding The Bonding ConnectionConnection
![Page 50: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/50.jpg)
L O A D
.357 ohms
.3 ohms
.57 ohms
The total resistance in this path created by bonding is .714 ohms.
The Bonding The Bonding ConnectionConnection
![Page 51: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/51.jpg)
Fault Current PathFault Current Path
• Therefore, using Ohm’s Law:– E = I x R
– Transposed to: I = E / R
– Where: I (current) = E (voltage) / R (resistance)
– And so, I = 120 / .714 = 168A
![Page 52: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/52.jpg)
The effective ground fault current path allows 168A of fault current to flow and forces the overcurrent device to open.
L O A D
The Bonding The Bonding ConnectionConnection
![Page 53: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/53.jpg)
This path does not rely on grounding and works even if our system is not grounded.
L O A D
The Bonding The Bonding ConnectionConnection
![Page 54: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/54.jpg)
Conclusion …Conclusion …
• The overcurrent device protects against ground fault conditions provided that …
• Our circuits have been installed so that all conductive metals are bonded together and to the service neutral
![Page 55: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/55.jpg)
In Review …In Review …
• GroundingGrounding is a connection to earth intended to protect our electrical system from lightning and high voltage
![Page 56: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/56.jpg)
In Review …In Review …
• The overcurrent deviceovercurrent device protects our electrical system from overload and short circuit
![Page 57: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/57.jpg)
In Review …In Review …
• The overcurrent deviceovercurrent device protects our electrical system from a ground fault condition if …..
![Page 58: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/58.jpg)
In Review …In Review …
• Proper bonding …Proper bonding …
• Has created a permanent, electrically continuous and low impedance path
• Which allows fault current to return to the neutral at the service
![Page 59: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/59.jpg)
Wiring Methods Are Wiring Methods Are CriticalCritical
• Clearly, an effective ground-fault current path must be created throughout our wiring system
• This is accomplished through the proper installation of a listed wiring method
![Page 60: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/60.jpg)
Wiring Methods Are Wiring Methods Are CriticalCritical
• The safety of our electrical system relies on– The wiring method selected, and
– Its proper installation
![Page 61: Bonding, Grounding and the NEC Presented by The National Association of Certified Home Inspectors .](https://reader035.fdocuments.in/reader035/viewer/2022062407/56649da65503460f94a914eb/html5/thumbnails/61.jpg)
Wiring Methods Are Wiring Methods Are CriticalCritical
• A wiring method that has been specifically designed as an equipment grounding conductor, and
• Engineered to assure a low impedance fault current path, is
• Clearly the best choice for a safe electrical installation