CellTech Energy Systems AB • Äggelundavägen 2 • S-175 62 Järfälla TEL + 46 8 445 78 70 FAX + 46 8 445 78 78 E-MAIL [email protected] INTERNET www.celltech.se Model CT200-12 Nominal voltage 12 V Number of cells 6 Nominal capacity +25˚C 20 hour rate (10 A - 10,5V) 200 Ah 10 hour rate (19,6 A - 10,5V) 196 Ah 5 hour rate (36,7 A - 10,5 V) 183,5 Ah 1 hour rate (138 A - 9,60V) 138 Ah Internal resistance 3 mOhm Self discharge 3% of capacity decline per month at +20° C Operating temperature range Discharge -20 to +60° C Charge -10 to +60° C Storage -20 to +60° C Max discharge current (5 sec) 1000 A Short circuit current 3500 A Max. charge current 60 A Charging methods at +20°C Cycle use Constant voltage charge 14,4 - 14,7 V Temperature compensation -30 mV/° C Stand-by use Constant voltage charge 13,6 - 13,8 V Temperature compensation -20 mV/° C SPECIFICATIONS FEATURES Valve Regulated Lead Acid Batteries, [AGM]. Positive and negative plates in lead-calcium alloy. • Sealed construction • Maintenance free operation 10 years design life according to Eurobat Guide - High Performance. • Low pressure venting system • Low selfdischarge • U.L. component recognition Six month shelf life at +20° C DESCRIPTION The CT Leader range is designed for general purpose applications, such as UPS, alarm systems, telecom and technical utilities. With 10 years design life, the batteries comply to the international standards IEC896-2 and BS6290-4 Eurobat guide. Lenght 522 mm Width 238 mm Height 218 mm Total height 240 mm Weight 65 kg DIMENSIONS AND WEIGHT CT200-12 [12V-200Ah] LEADER VALVE REGULATED LEAD ACID BATTERIES - [AGM]

Transcript of Blybatterier - Leader - Leader LX - Vision - REPS · The CT Leader range is designed for general...

Page 1: Blybatterier - Leader - Leader LX - Vision - REPS · The CT Leader range is designed for general purpose ... the batteries comply to the international standards IEC896-2 and BS6290-4

CellTech Energy Systems AB • Äggelundavägen 2 • S-175 62 Järfälla • TEL + 46 8 445 78 70 • FAX + 46 8 445 78 78 • E-MAIL [email protected] • INTERNET www.celltech.se

Model CT200-12Nominal voltage 12 VNumber of cells 6Nominal capacity +25˚C

20 hour rate (10 A - 10,5V) 200 Ah10 hour rate (19,6 A - 10,5V) 196 Ah5 hour rate (36,7 A - 10,5 V) 183,5 Ah

1 hour rate (138 A - 9,60V) 138 AhInternal resistance 3 mOhmSelf discharge 3% of capacity decline per month at +20° COperating temperature range

Discharge -20 to +60° CCharge -10 to +60° C

Storage -20 to +60° CMax discharge current (5 sec) 1000 AShort circuit current 3500 AMax. charge current 60 ACharging methods at +20°CCycle use

Constant voltage charge 14,4 - 14,7 V Temperature compensation -30 mV/° C

Stand-by use Constant voltage charge 13,6 - 13,8 V

Temperature compensation -20 mV/° C

SPECIFIC ATIONS

F E AT U R E S

• Valve Regulated Lead Acid Batteries, [AGM].

• Positive and negative plates in lead-calcium alloy.

• Sealed construction

• Maintenance free operation

• 10 years design life according to Eurobat Guide - High Performance.

• Low pressure venting system

• Low selfdischarge

• U.L. component recognition

• Six month shelf life at +20° C

D E S C R I P T I O N

The CT Leader range is designed for general purpose applications, such as UPS, alarm systems, telecom and technical utilities. With 10 years design life, the batteries comply to the international standards IEC896-2 and BS6290-4 Eurobat guide.

Lenght 522 mmWidth 238 mmHeight 218 mmTotal height 240 mmWeight 65 kg

D I M E N S I O N S A N D W E I G H T

CT200-12 [12V-200Ah]

LEADERV A LV E R E G U L AT E D L E A D A C I D B AT T E R I E S - [ A G M ]

Page 2: Blybatterier - Leader - Leader LX - Vision - REPS · The CT Leader range is designed for general purpose ... the batteries comply to the international standards IEC896-2 and BS6290-4

CellTech Energy Systems AB • Äggelundavägen 2 • S-175 62 Järfälla • TEL + 46 8 445 78 70 • FAX + 46 8 445 78 78 • E-MAIL [email protected] • INTERNET www.celltech.se

End voltage (V/cell)

5 min 10 min 15 min 30 min 1 h 3 h 5 h 10 h 24 h

1,60 550 440 358 210 138 53,1 39,0 20,2 10,401,65 508 414 337 203 135 52,0 38,2 20,0 10,301,70 470 390 316 195 132 51,0 37,5 19,8 10,101,75 440 364 295 188 129 49,8 36,7 19,6 10,001,80 380 334 274 180 126 48,4 35,9 19,5 9,95

D I S C H A R G E D ATA ( A M P E R E S AT +25˚ C )

End voltage (V/cell)

5 min 10 min 15 min 30 min 45 min 1 h 2 h 3 h 5 h

1,60 915 756 611 402 287 266 145 103 74,31,65 866 719 591 387 282 261 142 102 73,71,70 817 681 572 372 276 256 139 100 73,11,75 768 641 553 357 270 250 136 98,8 72,61,80 718 609 520 342 265 245 132 97,7 72,0

D I S C H A R G E D ATA ( WAT T S P E R C E L L AT +25˚ C )

C H A R G E C H A R AC T E R I S T I C

D I S C H A R G E C H A R AC T E R I S T I C ( +25˚ C )

S E L F D I S C H A R G E S TAT E O F C H A R G E I N R E L AT I O N TO V O LTAG E

CT200-12 [12V-200Ah]

LEADERV A LV E R E G U L AT E D L E A D A C I D B AT T E R I E S - [ A G M ]