BIS PL

download BIS PL

of 32

Transcript of BIS PL

  • 8/10/2019 BIS PL

    1/32

    BIS

    Emergency exit and fire

  • 8/10/2019 BIS PL

    2/32

    CODE OF PRACTICE FOR FIRE

    SAFETY OF BUILDINGS (GENERAL):EXIT REQUIREMENTS

  • 8/10/2019 BIS PL

    3/32

    EXIT REQUIREMENTS

    Ample provision for escape of population of abuilding when on fire is vital and all routes shouldbe constructed to ensure that the population

    reaches a place of safety in the shortest period oftime without undue hindrance by smoke, fumes,debris and the like.

    Every building meant for human occupancy

    should be provided with exits sufficient to permitsafe escape of occupants, in case of fire or otheremergency.

  • 8/10/2019 BIS PL

    4/32

    Types of exit

    An exit may be a doorway,

    a corridor or

    passageway(s) to an internal staircase, or

    external staircase, or

    to a verandah or

    terrace(s) which have access to the street, or

    roof of a building, or

    a refuge area.

    An exit may also include a horizontal exit leading to anadjoining building at the same level.

    Lifts and escalators should not be considered as exits.

  • 8/10/2019 BIS PL

    5/32

  • 8/10/2019 BIS PL

    6/32

    General

    Where necessary, adequate and reliable illuminationshould be provided for exits.

    Fire check doors should at appropriate places along theescape routes to prevent spread of fire and smoke and

    particularly at the entrance to lifts and stairs where afunnel or flue effect may be created, including anupward spread of fire.

    All exits should provide continuous means of access tothe exterior of a building or to an exterior open spaceleading to a street.

    Exits should be so arranged that they may be reachedwithout passing through another occupied unit

  • 8/10/2019 BIS PL

    7/32

    Capacity of Exits

    The unit of exit width, used to measure the capacity of anyexit, should be 50 cm. A clear width of 25 cm should becounted as an additional half unit. Clear widths less than 25cm should not be counted for exit width.

    Occupants per unit exit width should be in accordance withTable 2.

    Horizontal Exit AllowanceWhen horizontal exit isprovided in buildings of mercantile, storage, industrial,business and assembly occupancies, the capacity per storey

    per unit width of exit of stairways in Table 2 may beincreased by 50 percent; and in buildings of institutionaloccupancy, it may be increased by 100 percent.

  • 8/10/2019 BIS PL

    8/32

  • 8/10/2019 BIS PL

    9/32

    Arrangement of Exits

    Exits should be so located that the travel distance onfloor should not exceed the distance given in Table 3.

    The travel distance to an exit from the dead end of acorridor should not exceed half the distance specified

    in Table 3, except in educational, Assembly and institutional occupancies in which case it

    should not exceed 6 m.

    Whenever more than one exit is required for any room,

    space or floor of a building, exits should be placed asremote from each other as possible and should bearranged to provide direct access in separate directionsfrom any point in the area served.

  • 8/10/2019 BIS PL

    10/32

  • 8/10/2019 BIS PL

    11/32

    Number of Exists

    General Requirement

    All buildings which are more than 15 m in height and allbuildings used as

    educational (B),

    assembly (D), institutional (F),

    industrial (G),

    Storage (H), and

    hazardous (J) occupancies and mixed occupancies with anyof the aforesaid occupancies, having area more than 500m2on each floor should have a minimum two staircases.

  • 8/10/2019 BIS PL

    12/32

    They should be of enclosed type; at least oneof them should be on external walls ofbuildings and should open directly to the

    exterior, interior open space or to an openplace of safety.

    Further, the provision, or otherwise ofalternative staircase should be subject to therequirements of travel distance beingcomplied with.

  • 8/10/2019 BIS PL

    13/32

    All locking devices which would impede or prohibitexit, such as chain type bolts, limited opening slidingtype locks and burglar locks which are not disengagedeasily by quick-releasing catches, should be prohibited.

    All closet door latches should be such that evenchildren may open the doors from inside.

    All bathroom door locks or fasteners should bedesigned to permit the opening of the locked or closeddoor from the outside in an emergency without the

    use of a special key. Every below-street-level sleeping room should have

    direct access to the outside of the building.

  • 8/10/2019 BIS PL

    14/32

    Industrial(G)

    Not less than two exits should be provided forevery floor or section, including basements usedfor industrial purposes or uses incidental thereto.

    In buildings used for aircraft assembly or otheroccupancy requiring undivided floor areas solarge that the distance from points within thearea to the nearest outside walls where exitdoors could be provided are in excess of 45 m,

    requirements for distance to exits may besatisfied by providing stairs leading to exit tunnelsor to overhead passageways.

  • 8/10/2019 BIS PL

    15/32

    Industrial(G)

    In cases where such arrangements are not

    practicable, permit other exit arrangements for

    one storey buildings with distance in excess of

    the maximum distances specified in 2.6. Basements used only for storage, heating and

    other service equipment, and not subject to

    industrial occupancy should have exits inaccordance with the requirements of Group H

    occupancies.

  • 8/10/2019 BIS PL

    16/32

    Industrial(G)

    If completely automatic sprinkler protection isprovided and if the heights of ceiling curtain boardsand roof ventilation are such as to minimize thepossibility that employees will be overtaken by the

    spread of fire or smoke within 180 cm of the floor levelbefore they have time to reach exits,

    Provided, however, that in no case may the distance oftravel to reach the nearest exit exceed 120 m where

    smoke venting is required as a condition for permittingdistances of travel to exits in excess of the maximumotherwise allowed.

  • 8/10/2019 BIS PL

    17/32

    The following exceptions should apply to special purpose

    industrial occupancies:

    Exits need be provided only for the persons actuallyemployed; spaces not subject to human occupancybecause of the presence of machinery or equipment

    may be excluded from consideration. Where unprotected vertical openings are necessary to

    manufacturing operations, these may be permittedbeyond the limits specified for industrial occupancy

    provided every floor level has direct access to one ormore enclosed stairways or other exits protectedagainst obstruction by any fire in the open areasconnected by the unprotected vertical openings orsmoke therefrom.

  • 8/10/2019 BIS PL

    18/32

    The following exceptions should apply to high hazardindustrial occupancies:

    Exits should be so located that it will not be necessary totravel more than 22 5 m from any point to reach thenearest exit.

    From every point in every floor area, there should at leastbe two exits accessible in different directions; where floorareas are divided into rooms, there should be at least twoways of escape from every room, however small, excepttoilet rooms, so located that the points of access theretoare out of or suitably shielded from areas of high hazard.

    In addition to types of exits for upper floors specified forGroup G occupancies, slide escapes may be used asrequired exits for both new and existing buildings.

  • 8/10/2019 BIS PL

    19/32

    FIRE

    It covers the requirement for fire prevention,

    life safety in relation to fire, and fire

    prevention of buildings. The code specifies

    planning and construction features and fireprotection features for all occupancies that

    are necessary to minimize danger to life and

    property

  • 8/10/2019 BIS PL

    20/32

    Fire

    Fire escapes should not be taken into account in calculatingthe evacuation time of a building.

    All fire escapes should be directly connected to the ground.

    Entrance to the fire escape should be separate and remote

    from the internal staircase. Care should be taken to ensure that the wall opening or

    window opens on to or close to a fire escape.

    The route to the fire escape should be free of obstructionsat all times.

    The fire escape should be constructed of non-combustiblematerials, and any doorway leading to the fire escapeshould have the required fire resistance.

  • 8/10/2019 BIS PL

    21/32

    Fire

    No staircase, used as a fire escape, should be inclined at an anglegreater than 45 to the horizontal.

    Fire escape stairs should have straight flight not less than 75 cmwide with 20 cm treads and risers not more than 19 cm. Thenumber of risers should be limited to 15 per flight.

    Hand rails should be of a height not less than 100 cm and notexceeding 120 cm.

    Spiral Fire EscapeThe use of spiral staircase should be limited tooccupant load and to a building not exceeding 9 m in height unlessthey are connected to platforms, such as balconies and terraces toallow escapees to pause.

    Spiral fire escape should be not less than 150 cm in diameter andshould be designed to give adequate headroom.

  • 8/10/2019 BIS PL

    22/32

    Fire Tower

    Fire towers are the preferred type of escape route forstoreyed buildings and their application should beconsidered as the safest route for escape.

    Their number, location and size should depend on thebuilding concerned, and its associated escape routes.

    In every mercantile, industrial, business, assembly buildingsother than theatres, institutional and residential buildings,over 6 storeys or 25 m in height, at least one requiredmeans of egress should be a fire tower.

    The enclosure of fire towers should be constructed of wallswith a 4 h fire-resistance rating without openings otherthan the exit doorways with platform, landings andbalconies of not less than 3 h fire-resistance rating.

  • 8/10/2019 BIS PL

    23/32

    FIRE PROTECTION SAFETY SIGNS

  • 8/10/2019 BIS PL

    24/32

  • 8/10/2019 BIS PL

    25/32

  • 8/10/2019 BIS PL

    26/32

  • 8/10/2019 BIS PL

    27/32

  • 8/10/2019 BIS PL

    28/32

  • 8/10/2019 BIS PL

    29/32

  • 8/10/2019 BIS PL

    30/32

  • 8/10/2019 BIS PL

    31/32

    BIS reference

    https://law.resource.org/pub/in/bis/S03/is.12

    349.1988.pdf

    https://law.resource.org/pub/in/bis/S03/is.16

    44.1988.html

    https://law.resource.org/pub/in/bis/S03/is.16

    44.1988.html

    https://law.resource.org/pub/in/bis/S03/is.12349.1988.pdfhttps://law.resource.org/pub/in/bis/S03/is.12349.1988.pdfhttps://law.resource.org/pub/in/bis/S03/is.1644.1988.htmlhttps://law.resource.org/pub/in/bis/S03/is.1644.1988.htmlhttps://law.resource.org/pub/in/bis/S03/is.1644.1988.htmlhttps://law.resource.org/pub/in/bis/S03/is.1644.1988.htmlhttps://law.resource.org/pub/in/bis/S03/is.12349.1988.pdfhttps://law.resource.org/pub/in/bis/S03/is.12349.1988.pdf
  • 8/10/2019 BIS PL

    32/32

    Thank You