Clean Environment Commission – Fall 2012 – SP Bipole III Transmission Project Clean Environment Commission Public Hearings Fall 2012 System Planning Ronald Mazur

Transcript of Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost -...

Page 1: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Bipole III Transmission Project

Clean Environment Commission Public Hearings

Fall 2012 System Planning

Ronald Mazur

Page 2: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

OVERVIEW • Transmission Options

• 500 kV HVDC ~ 1384 km transmission line

• Keewatinoow converter station Rated 2000 MW Northern Collector System transmission

• Riel 2000 MW converter station

Rated 2000 MW Riel 230 kV AC transmission

• Converter Technology Options LCC vs. VSC

• Conclusion

Limestone

Kettle

Jenpeg

Selkirk

Brandon

Grand Rapids

Kelsey

Dorsey

Riel

Keewantinoow

BP III

Page 3: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Transmission Options

• High Voltage DC

• High Voltage AC

Page 4: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Why HVdc ?

• Technical Merits

Facilitates

Connection to

isolated Northern

Collector System

Lower Losses

RIEL

DORSEY

Manitoba AC system

KEEWATINOOW

Bipole III Line

Page 5: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Why HVdc ?

• Economic considerations HVdc converters are

costly HVdc line is less

costly AC stations are less

costly AC line is more

expensive

HVdc more economical than AC for long distance

0

500

1000

1500

2000

2500

3000

3500

4000

4500

0 500 1000 1500

Cap

ital c

ost (

$ M

illon

)

tx distance (km)

Comparison of capital cost (in-service $) of AC and HVdc Transmission based on Current Estimates Available to

MH (Losses not considered)

MH - HVdc cost estimates

AC Cost Estimates - Based on MH line&station costs

Cost of Bipole III converters +

NClines

3.28 $Billion Estimated cost of Bipole III 2000MW

500kV station + NClines

Break even distance approx. < 800km 4.18

$Billion

Page 6: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Why HVdc ?

• Environmental advantages compared to AC Smaller transmission

tower

Narrower right-of-

way

Source : HVdc – Proven Technology for Power Exchange by Siemens

AC Double Circuit tower

Page 7: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Bipole III Transmission – Sending End

• Northern Converter - Keewatinoow CS

• Northern Collector System Lines Long Spruce –

Keewatinoow 1 x 230 kV line - 52 km Henday – Keewatinoow 4 x 230 kV lines – 27 km each

7

Keewatinoow 1350MW

Page 8: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Bipole III Transmission – Receiving End

• Southern Converter - Riel CS Sectionalize Richer

230 kV lines R49R

DORSEY

Richer

D602F To Forbes

230kV lines

4

RIEL

Ridgeway

Page 9: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

What is HVdc ?

Y∆

YY

Y∆

YY

Y∆

YY

Y∆

YY

AC filters

Y∆

YY

Y∆

YY

Y∆

YY

Y∆

YY

DC filters

DC filters

AC filters

Lower half bridge

Upper half bridge

+500kV

-500kV

Irated = 2000A

Irated = 2000A

Receiving End Converters

HVdc line

Generators

Load

DC filters

DC filters Sending End AC BUS

Smoothing Reactor

Receiving End AC BUS

Sending End converters

Electrode line & Electrode

Page 10: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Converter Station

Y∆

YY

Y∆

YY

Y∆

YY

Y∆

YY

AC filters

Lower half bridge

Upper half bridge

+500kV

-500kV

DC filters

DC filters Sending End AC BUS

Smoothing Reactor

Converter Station (Henday)

Page 11: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

HVdc Line – Two Conductors

Y∆

YY

Y∆

YY

Y∆

YY

Y∆

YY

AC filters

Lower half bridge

Upper half bridge

+500kV

-500kV

DC filters

DC filters Sending End AC BUS

Smoothing Reactor

HVdc line

Triple Bundle

Pole 1 Pole 2

Insulator String

Page 12: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Shield Wire & Communication

• Optical Ground Wire Lightning

protection Communication

Shield Wire

Page 13: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Electrode Line & Electrode

Y∆

YY

Y∆

YY

Y∆

YY

Y∆

YY

AC filters

Lower half bridge

Upper half bridge

+500kV

-500kV

DC filters

DC filters Sending End AC BUS

Smoothing Reactor

Electrode line connecting station neutral to ground electrode site

Electrode site

Page 14: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Converter - Converts ac dc

-1.5

-1

-0.5

0

0.5

1

1.5

0 45 90 135 180 225 270 315 360

• Filters clean up the ripple further

Source : HVdc – Proven Technology for Power Exchange by Siemens

-1.5

-1

-0.5

0

0.5

1

1.5

0 90 180 270 360

Alternating Current (AC)

Direct Current (DC)

Page 15: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Converter Components

AC Switchyard Station bus and circuit breakers that are used to terminate transmission lines from the ac transmission system/generating stations, the ac harmonic and high frequency filters, converter transformers etc. Dorsey Converter Station

Page 16: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Converter Components AC Harmonic and

High Frequency Filters

• Removes the

harmonic (multiples of 60 hertz) currents created by converter operation

• Supplies the reactor power consumed by the converter.

Radisson AC Filters

Page 17: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Converter Components

Converter Transformer • Interface between the

ac system and the thyristor valves.

• Specialized transformer that must be designed to withstand dc voltage stresses & ac harmonics

• Contains Oil for insulating and cooling

BPII Converter Transformers

Page 18: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

HVdc Converter Components

• Provides transformation from ac to dc (or dc to ac)

• Most LCC converters are 12 pulse bridges – 12 valves each containing many series connected thyristors to achieve the dc rating of the scheme.

• Designed for each project

• Valves are normally contained in a special purpose building called a valve hall.

Converter Valves

BP I Valves

BP II Valves

Page 19: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Converter Technology Converters LCC or VSC

• Line Commutated Converter (LCC) – like BPI & II known technology - lot of experience

• Voltage Source Converter (VSC) New technology with many appealing benefits Suitable for weak AC systems like MH’s Control of active and reactive power Black-Start Capability Synchronous Condensers not Required at Riel However new technology – new challenges

• eg. DC line fault clearing

• Decision after tenders received

Page 20: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Converter Components cont ..

• Reduces the dc current ripple caused by the conversion process on the dc line.

• Limits the line fault currents

• Protects the thyristor valve from lightning hits on the dc line.

DC Smoothing Reactor

BPII Smoothing Reactors

Page 21: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Converter Components cont ..

• Eliminates ac harmonic currents on the dc line, which can cause interference with adjacent telecommunication systems

DC filters

Dorsey DC Filters

Page 22: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Converter Components cont ..

• Provides reactive power to the HVdc converters

• Provides inertia (flywheel) to maintain acceptable system frequency

• Provides voltage control at the ac/dc interface.

Synchronous Condensers

Machine Transformer

Dorsey Synchronous Condensers

Page 23: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Line Design

• Three types of loads considered: - Reliability loads based

on weather data - Security loads – Anti

cascading towers at about 5km intervals

- Safety loads – for construction and maintenance work

• Reliability level of 150 yr Return Period for weather loads selected

Design Loads • Two main weather load zones established based on analysis of the weather data:

• Different combinations of wind and ice loads considered

Loading Southern

Zone Northern

Zone

Design Wind Speed

107 km/h 93 km/h

Design Ice Thickness

33 mm 25 mm

Page 24: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Line Design

• To carry the required current (2000A), minimize losses minimize flashovers and minimize EMF effects Minimum conductor

diameter: 37 mm

3-Bundle Configuration

Thermal ampacity of 4500A

Conductor

• Optimization based on - sag and clearance - conductor cost - tower cost - tower design

Page 25: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Line Design

• South zone - Self supporting 4-legged towers Reduce impact on

farming practices More expensive

• Northern zone Guyed towers Better suited for

difficult soil conditions

Less Expensive

Towers – Two Types

• Tangent tower for straight line sections

• Angle towers for where the route takes turns based on analysis of

the preferred route

Family of Towers

Page 26: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

HVdc Line Design

• Reliability level of 150-yr Return Period for climatic weather

• This reliability level is recommended for all overhead lines above 230 kV voltage level

• Reliability level of 500-yr return period: Sections of the Bipole III within 50 km from the

Bipole I & II Amounts to a total of approx. 340 km.

Reliability Level

Page 27: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

54.2m

42m

54.2m

Sag 20m

Typical HVdc Tower 13.41m

13.6m

5.5m

Typical Self Supporting

Tower Footing 7.85m x 7.85m approx 64m2

Page 28: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Towers: • Family of Self Supporting Towers

0°-2° TANGENT SUSPENSION TOWER

A-540 Height: 41 – 56 m

2°-7° LIGHT ANGLE SUSPENSION TOWER

B-540 Height: 43 – 55 m

7°-25° MEDIUM ANGLE DEAD-END TOWER

C-540 Height: 40 – 49 m

25°-92° HEAVY ANGLE DEAD-END TOWER

D-540 Height: 44 – 53 m

Page 29: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Towers: • Family of Guyed Towers

0°-2° TANGENT SUSPENSION TOWER

A-530 Height: 41 – 56 m

2°-7° LIGHT ANGLE SUSPENSION TOWER

B-530 Height: 45 – 54 m

7°-60° HEAVY ANGLE DEAD-END TOWER

C-530 Height: 40 – 49 m

Page 30: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Ground Electrode • Under normal

operation For defining the

system voltage by providing a reference to earth

Insulation coordination

Over voltage protection

Carries very small unbalance current

2000MW of power transfer

+500kV

Keewatinoow Riel

-500kV

~0kV

HVdc Line

2000A

2000A

Page 31: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Ground Electrode

• During loss of a Pole Conductor provides a

temporary current return path for through the earth

monopolar operation

1000MW of power transfer

+500kV

Keewatinoow Riel

-500kV

~0kV

HVdc Line

2000A

2000A

Page 32: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Ground Electrode

• During loss of a Converter Pole provides a

temporary current return path till metallic return is established.

1000MW of power transfer

+500kV

Keewatinoow Riel

-500kV

~0kV

HVdc Line

2000A

2000A

2000A

Page 33: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Riel Reliability Improvement Project

• A separate project • Enhances reliability

by securing the import capability

• Sectionalized 500kV – D602F

• Sectionalized 230kV – R32V, R33V

RIEL Sectionalization

DORSEY

To Forbes

D602F

230kV lines

4

Page 34: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Before

After

Existing Dorsey 500 kV Station

Existing 230 kVConnections

Existing 230 kVConnections

Additional & New 230 kVConnections

Existing Dorsey 500 kV Station

Existing Forbes, MN Station

Existing Forbes, MN Station

Transmission Line A

Transmission Line B

Transmission Line C

New RielStation

One line (Transmission Line A) before the new station is constructed becomes two lines (Transmission Lines B & C)

after the station is constructed.

What is “Sectionalization”?

Page 35: Bipole III Transmission Project -043Mazur... · Bipole III Transmission Project ... - tower cost - tower design . ... Typical Self Supporting Tower Footing 7.85m x 7.85m

Clean Environment Commission – Fall 2012 – SP

Conclusion • Provided an overview of the Bipole III Project • Defined the details of the HVdc transmission

system • Demonstrated the complexity of the HVdc

converter stations • Provided insight into why we need long lead

times to restore the HVdc Bipoles I and II in the event of a catastrophic outage!!!!

• Highlights the need for Bipole III