Bim log mep (2)

5
S. N Sent by Intec on (DD-MM- YYYY) Drg./Doc. No. LOCATION / GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status 1 01.04.2015 A-TD-201 3rd BASEMENT FLOOR PLAN R6 GRID-B&6A MEP CLASH CABLE TRAY CLASH WITH MECH.EQUIPMENT LAYOUT REVISED Close 2 01.04.2015 A-TD-201 3rd BASEMENT FLOOR PLAN R6 GRID-D1&2 MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT LAYOUT REVISED Close 3 01.04.2015 A-TD-201 3rd BASEMENT FLOOR PLAN R6 GRID-E&6 MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT NO CLASH Close 4 01.04.2015 A-TD-201 3rd BASEMENT FLOOR PLAN R6 GRID-E & 11 MEP CLASH CABLE TRAY CLASH WITH MECH.EQUIPMENT LAYOUT REVISED Close 5 01.04.2015 A-TD-201 3rd BASEMENT FLOOR PLAN R6 GRID-K1&6A MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT DUCT LEVEL REVISED Close TECHNICAL QUERY: 20F6BC70.JPG 2032F3C8.JPG DD183516.JPG C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 1

Transcript of Bim log mep (2)

Page 1: Bim log mep (2)

S.N

Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /

GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status

1

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-B&6A MEP CLASHCABLE TRAY CLASH WITH MECH.EQUIPMENT

LAYOUT REVISED Close

2

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-D1&2 MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT LAYOUT REVISED Close

3

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-E&6 MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT NO CLASH Close

4

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-E & 11 MEP CLASHCABLE TRAY CLASH WITH MECH.EQUIPMENT

LAYOUT REVISED Close

5

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-K1&6A MEP CLASH CABLE TRAY CLASH WITH HVAC DUCT DUCT LEVEL REVISED Close

TECHNICAL QUERY:

20F6BC70.JPG

2032F3C8.JPG

DD183516.JPG

C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 1

Page 2: Bim log mep (2)

S.N

Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /

GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status

6

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-9A&A1 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT

NO CLASH Close

7

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-B&8 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT

NO CLASH Close

8

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-C&4 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT

LAYOUT REVISED Layout not revised Close

9

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-D1&12 MEP CLASHSPRINKLER PIPE CLASH WITH MECH. EQUIPMENT

LAYOUT REVISED Layout not revised Close

10

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-B&6 MEP CLASHRAIN WATER PIPE CLASH WITH HVAC DUCT

LAYOUT REVISED Close

3EF85994.JPG

AD59812E.JPG

FEAC356C.JPG

669B7A5A.JPG

76658378.JPG

C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 2

Page 3: Bim log mep (2)

S.N

Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /

GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status

11

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-M&1A MEP CLASHRAIN WATER PIPE CLASH WITH HVAC DUCT

NO CLASH Close

13

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

CAL MEP CLASHSPRINKLER PIPE CLASH WITH STRUCTURE BEAM

LAYOUT REVISED Close

15

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-B&8 MEPHVAC DUCT CLASH WITH STRUCTURE COLUMN

LAYOUT REVISED Close

16

01.04.2015A-TD-201 3rd BASEMENT FLOOR PLAN R6

GRID-P&1A MEP CLASHHVAC DUCT CLASH WITH STRUCTURE COLUMN

LAYOUT REVISED Close

17

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-E&7 MEP CLASH CABLE TRAY CLASH WITH EACH OTHER LAYOUT REVISED Close

2E9C5046.JPG

F6C29BD0.JPG

9C11025E.JPG

1ABDBE1C.JPG

19B432CC.JPG

2AF03EBA.JPG

5AC871E3.jpg

C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 3

Page 4: Bim log mep (2)

S.N

Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /

GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status

18

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-I&2 MEP CLASH CABLE TRAY CLASH WIH FIRE PIPE LAYOUT REVISED Close

19

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-E&10B MEP CLASHCABLE TRAY CLASH WITH MECH.EQUIPMENT

LAYOUT REVISED Close

20

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-L1&12 MEP CLASHSPRINKLER PIPE CLASH WITH MECH. EQUIPMENT

LAYOUT REVISED Close

21

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-O&4 MEP CLASHSPRINKLER PIPE CLASH WITH HVAC DUCT

NO CLASH Close

22

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-M&1A MEP CLASHRAIN WATER PIPE CLASH WITH HVAC DUCT

NO CLASH Close

460228E9.JPG

E03223DF.JPG

E7DF3845.JPG

8D6CEF61.JPG

4733D2C3.JPG

C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 4

Page 5: Bim log mep (2)

S.N

Sent by Intec on (DD-MM-YYYY) Drg./Doc. No. LOCATION /

GRID Discipline Concerned QUERY Drawing Required / Discrepancy Image Comment Response from Consultant Remarks from Intec Status

23

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-D1&2A MEP CLASHCABLE TRAY CLASH WITH STRUCTURE COLUMN CAP

NO CLASH Close

24

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-K1&10B MEP CLASHCABLE TRAY CLASH WITH STRUCTURE COLUMN CAP

NO CLASH Close

25

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-L&2 MEP CLASHCABLE TRAY CLASH WITH STRUCTURE COLUMN CAP

LAYOUT REVISED Close

26

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-K2&12 MEP CLASHSPRINKLER & PIPE CLASH WITH STRUCTURE BEAM

LAYOUT REVISED Close

27

02.04.2015

A-TD-202 2nd BASEMENT FLOOR PLAN R6 13-3-13

GRID-C1&8 MEP CLASHHVAC DUCT CLASH WITH STRUCTURE BEAM

DUCT LEVEL REVISED Close

97424917.JPG

BB27EA3D.JPG

9DF8F453.jpg

A86884D9.JPG

4B4F154F.JPG

E53EDB35.JPG A3F7280B.JPG87BDFD98.JPG850A9515.JPG 21415CEB.JPG E20C3131.JPGC58B7B67.JPGC90EE10D.JPG79A4A3A3.JPGE94000A9.JPG 4F8E919F.JPGE554AC05.JPGE6E8C15B.JPG A291ABDA.JPG1752E483.JPGF1995489.JPG DBB632A2.JPGD8529B7.JPGE7A7FC6D.jpg 4F8E3603.jpg1E153C1A.jpgF9676B38.jpg183FD8A3.jpg4C04D579.jpg7D79CEEF.jpg5928E5D5.jpgF849ABAB.jpg4CD52DF1.jpgAF321477.jpgD28BAC9D.jpg9ECED1E6.jpgF2068109.jpg25BBD0FF.jpg

C:\Users\HP ELITEBOOK 8760W\Desktop\BIM_LOG_MEP 5