This is a general manual describing a series of racks receiving servo amplifiers having output capability for driving

AC brushless servo motors.

This manual may be used in conjunction with appropriate and referenced drawings pertaining to the various

specific models.

Maintenance procedures should be attempted only by highly skilled technicians (EN 60 204.1 standard)

using proper test equipment.

The conformity with the standards and the "CE" approval are only valid if the items are installed according to the

recommendations of the racks and amplifiers manuals.

Any contact with electrical parts, even after power down, may involve physical damage.

Wait for 30 seconds after power down before handling the rack or the amplifiers (residual voltage).

INFRANOR does not assume any responsibility for any physical or material damage due to improper handling or

wrong descriptions of the ordered items.

INFRANOR reserves the right to change any information contained in this manual without notice.

This manual is a translation of the original document and does not commit INFRANOR's responsibility. The french

manual is the only reference document.

© INFRANOR, September 1999. All rights reserved

Issue: 2.0

Page 4: BF RACK - infranorusa.com

4 BF RACK

BF RACK

Page 5: BF RACK - infranorusa.com

Contents 5

BF RACK

Contents

CONTENTS......................................................................................................................................................................5

CHAPTER 1 – GENERAL DESCRIPTION................................................................................................ .....................7

1 – COMPLIANCE WITH THE EUROPEAN STANDARDS: "CE" CERTIFICATION...............................................7

1.1 – General description.......................................................................................................................................7

1.2 - Reference to the standards ...........................................................................................................................8

1.3 – CE marding ...................................................................................................................................................8

2 – ORDERING CODE OF THE BF-RACK ...............................................................................................................9

3 – ORDERING CODE OF THE MAINS FILTER ......................................................................................................9

CHAPTER 2 – SPECIFICATIONS................................................................................................................................10

1 – MAIN TECHNICAL DATA...................................................................................................................................10

2 – DIMENSIONS OF A 6 AXES BF RACK, 12 TE.................................................................................................11

3 – MAINS FILTER DIMENSIONS...........................................................................................................................12

4 – EXTERNAL BRAKING RESISTOR DIMENSIONS ...........................................................................................12

CHAPTER 3 – CONNECTIONS........................................................................................................ ............................14

1 – RACK BACKPANEL CONNECTION .................................................................................................................14

1.1 – Connection diagramm.................................................................................................................................14

1.2 – Tableau de configuration ............................................................................................................................14

2 – SETTING-UP DIAGRAMS OF THE BACKPANEL (X5 SWITCH, JUMPERS).................................................15

3 – SETTING-UP OF THE CONNECTION CONNECTORS...................................................................................16

4 – XA1 AND XA2 SUPPLY CONNECTORS..........................................................................................................17

5 – XMOT MOTOR CONNECTOR...........................................................................................................................17

6 – THREE-PHASE CONNECTION VIA A 380V/220V (400V/230V) AUTOTRANSFORMER .............................18

7 – MAINS FILTER OPTION ....................................................................................................................................20

8 – SPECIAL CONNECTION REQUIREMENTS ...................................................................................................21

APPENDIX .....................................................................................................................................................................23

Page 6: BF RACK - infranorusa.com

6 BF RACK

BF RACK

Page 7: BF RACK - infranorusa.com

Chapter 1 – General description 7

BF RACK

Chapter 1 – General description

1 – COMPLIANCE WITH THE EUROPEAN STANDARDS: "CE" CERTIFICATION

1.1 – General description

The rack type of the "B" series is "BF". The "F" means "floating" power bus voltage , because it is not

referenced to the chassis.

This range is ALWAYS equipped for rear mounting.

The motor outputs and the supply inputs are ALWAYS on a terminal bar.

The logic inputs - outputs of the X5 connector on the rack backpanel allow the serial connection of the AMP.

READY and POWER READY signals.

All connections are ALWAYS made on the top of the rack (power supply, motors, logics).

The "BF" rack is operating with a 380 V / 220 V (400 V / 230 V) autotransformer . But it can, of course, also work

with an insulation transformer.

The whole "B" range (SMT-BSi and SMT-BD1) is particularly well suited for the "BF" rack.

But the "BF" rack is not compatible with the bipolar amplifiers of the "B" series.

The axis width of the "B" series amplifiers (12 TE, 18 TE or 24 TE) is depending on their current ratings.

The power supply unit ALWAYS includes the auxiliary supply, the power supply and the braking system. It is

mounted on a chassis fixed on the left rack flange. Its width is 12 TE.

The braking system is equipped with a safety function indicating its correct operation. This function is called "D/R

OK" (braking system OK). It controls a relay that can be serially used with the "∑ POWER READY" signal of the

X5 connector (pins 3 and 4) in order to interrupt the power contactor in case of incorrect operation.

The power supply can be equipped with a 35 A, 70 A or 90 A rectifier bridge.

The braking system includes all options of the "B" series: D, E, D2 and D1.

Option D Option D2 Option E Option D1

Resistor 15 Ω 10 Ω 2 x 15 Ω parallel mounted 2 x option E

Rated power 140 W 280 W 560 W 1 120 W

Peak power 10 KW 16 KW 21 KW 42 KW

On both options "D" and "D2", the resistor is included in the power supply unit or mounted on the left rack flange,

whereas it is external on options "E" and "D1".

The braking resistor is under high voltage (400 V) and may become very hot. It is recommended to mountit at a correctly cooled place or outside the cabinet. But the "D2" or "E" resistors housing must in anycase be placed at least 30 cm away from any element that may burst into flame because of the brakingresistor heat radiation.

Page 8: BF RACK - infranorusa.com

8 Chapter 1 – General description

BF RACK

The "BF" rack answers the requirements of the EN 55011 standard regarding the electromagneticcompatibility , with optional input filter for the mains rejection.

But the common mode filter of the motor output as well as the mains filter of the auxiliary supply are integrated

in the rack, as standard .

The fan must always be mounted on the top of the rack. The various fan types are depending on the amplifier

continuous current.

1.2 - Reference to the standards

The "B" series amplifiers mounted into the BF rack , which is equipped with the mains filter BF 35/70, have been

approved for their conformity with the Electromagnetic Compatibility standards:

EN 55011, group 1, Class A, regarding conducted and radiated radioelectric disturbances

CEI 801-2-3-4 regarding immunity.

The test results and conditions of the LCIE laboratory (Laboratoire Central des Industries Electriques), which is

approved by the European Community, are referenced under n° 416040 - 416041 - 416042 - 416043.

The results of the tests made according to the Low Voltage directive are referenced in the LCIE report

n° 413777.

Standard for the electrical equipments of industrial machines: EN 60204.1.

1.3 – CE marding

The racks have been CE marked since 1995.

Page 9: BF RACK - infranorusa.com

Chapter 1 – General description 9

BF RACK

2 – ORDERING CODE OF THE BF RACK

BF / - - - V

84 TE 462,80 481,80

A B

6

5

4

3

2

1

72 TE

60 TE

48 TE

36 TE

24 TE

401,84

340,88

279,92

218,96

158,00

420,84

359,88

298,92

237,96

177,00

A

B30

Axis 1

Axis 2

Axis 3

Axis 4

Axis 5

Axis 6

NUMBER OF FANSBig fan 90 l/s - Ex: 1 big fan = V01Small fan 56 l/s - Ex: 1 small fan = V10

BRAKING RESISTORD 15 Ω/140 W internal resistorD2 10 Ω/280 W external resistor mounted

on the rack flangeE 2 x 15 Ω/280 W external resistorD1 2 x option E, external resistor

AXES LOCATIONØ Axis of 1 space (12 TE)1 Axis of 1,5 spaces (18 TE)2 Axis of 2 spaces (24 TE)NOTE Decreasing current rating from

left to right.The power supply requires 1 space (12 TE)

Pow

er s

uppl

y

Axi

s 1

Axi

s 2

Axi

s 3

Axi

s 4

Axi

s 5

Axi

s 6

35 35 ADC on the power bus70 70 ADC on the power bus90 90 ADC on the power bus

3 – ORDERING CODE OF THE MAINS FILTER

F

FILTER SIZING35 according to the70 power supply rating

Page 10: BF RACK - infranorusa.com

10 Chapter 2 - Specifications

BF RACK

Chapter 2 – Specifications

1 – MAIN TECHNICAL DATA

Rated DC bus voltage Three-phase 220 Vac

Maximum AC input power voltage 210 to 240 Vac +/-10 % (including all tolerances)

Minimum AC input power voltage 100 Vac

Rated auxiliary power voltage Single-phase 210 Vac to 240 Vac +/-10 % (including all

tolerances)

Minimum auxiliary supply voltage 100 Vac

Maximum auxiliary supply voltage 240 Vac +10 % (including tolerances)

Maximum section of the supply connector 6 mm2

Maximum section of the motor connector 4 mm2

Rated output current on the DC bus 35 A version 35 A

70 A version 70 A

90 A version 90 A

Output current of the auxiliary supply 1 A

Triggering threshold of the braking system 395 V +/-5 V

Minimum braking resistor (option E) 7,5 Ω

Rated braking power (option D1) 1 100 W

Peak braking power (max 1 s) – option D1 - 42 KW

Maximum section of the braking resistor cables 2,5 mm2

Conformity with the standards – CE approval EMC standards :

- immunity: CEI 801-2-3-4,

- Conducted and radiated disturbances: EN 55011,

group 1, class A

Electrical standards for industrial machines:

- EN 60204-1: insulator 1500 Vac/1min

- Leakage current > 3 mA (EMI filter)

The conformity with the standards and the "CE" approval are only valid if the items are installed according to the

recommendations of the racks and amplifiers manuals.

Page 11: BF RACK - infranorusa.com

Chapter 2 - Specifications 11

BF RACK

2 – DIMENSIONS OF A 6 AXES BF RACK, 12 TE

266m

m

286mm

36,7mm

Ø 7 x 12

190,

5mm

D2

462,8mm

483mm

513mm (option D2)

355m

m

80m

m90

mm

NOTE: The heatsink does not modify the dimensions.

Example: 6 axes rack: Axes 1 to 6 = 12 TE each.

NOTE

For other rack dimensions than 6 axes, see chapter 1, part 2: "Ordering code of the BF rack".

Page 12: BF RACK - infranorusa.com

12 Chapter 2 - Specifications

BF RACK

3 – MAINS FILTER DIMENSIONS

7384

9536

229

1,5

yyyyyyyyyyy

yy

yyy

60

88

5

740

218

L1 L2 L3

LOAD

L1 L2 L3LINE

4 – EXTERNAL BRAKING RESISTOR DIMENSIONS

A

B

7

740

52

C

BRAKING RESISTOR POWER A B C

D2 280 W 290 278 83

E 560 W 290 278 145

Page 13: BF RACK - infranorusa.com

Chapter 2 - Specifications 13

BF RACK

EXTERNAL BRAKING RESISTOR D1 (1100 W)

234

250

108

23445

0

102

Page 14: BF RACK - infranorusa.com

14 Chapter 3 - Connections

BF RACK

Chapter 3 – Connections

1 – RACK BACKPANEL CONNECTION

1.1 – Connection diagramm

The AMP. READY, POWER READY and Idyn signals can be serially or individually wired for all axes according

to the configuration below. The ENABLE signal can also be wired individually or as a common signal to all axes

on the front panel connector X4.

+24V

+24V

+24V

+24V

R1

R2

R3

0V 21

7

8

4

3

6

5

29

30

31

32

B

A

N N

D

O

P

E

F

G

H

B

A

GNDX5

1

2

3

4

5

6

7

8

Log > 0 Log < 0ENABLE

∑ ENABLE

∑ Idyn

∑ POWER READY

∑ AMP. READYGND

GND

GND

Axi

s 1

Idyn

POWER READY

AMP. READY

Bridge

Switch onbackpanel

Last wired axis

Idyn

POWER READY

AMP. READY

The jumpers A, B, N are located on the backpanel - see section 2 -.

symbolizes the closed contact of the BD1 amplifier relays.

The POWER READY signal is only available on the rack backpanel connector X5. If the POWER READY signal

is not used, make jumper JK on the amplifier in order to get the AMP. READY signal taking into account the

power status. The POWER READY signal includes both power supply status and braking system operation (DR

OK).

1.2 – Tableau de configuration

JUMPER/SWITCH ENABLE AMP.READY Idyn Power Ready and DROK

A closed on last wired axis

Switchs G and H « ON »

Serial

A closed on each axis

Switchs G and H « OFF »

Independent

B closed on last wired axis

Switchs E and F « ON »

Serial

B closed on each axis

Switchs E and F « OFF »

Independent

N closed on last wired axis

Switchs O and P « ON »

Serial

N closed on each axis

Switchs O and P « OFF »

Independent

Switch D « ON » Common to all axes

Switch D « OFF » Independent with X4

on each axis

Page 15: BF RACK - infranorusa.com

Chapter 3 – Connections 15

BF RACK

As standard, all these signals are serially wired: jumpers A, N and B are closed on the last wired axis and

switches D, E, F, G, H, O and P are all ON.

DEFINITION OF THE X5 CONNECTOR

PIN FUNCTION REMARK

1 ENABLE signal of all axes Common ENABLE signal to all axes

2 0 Volt

3 and 4 POWER READY signal of all axes POWER READY relay of all serially connected axes

5 and 6 AMP. READY signal of all axes AMP. READY relay of all serially connected axes

7 and 8 Idyn signal of all axes OPTION (Idyn of all serially connected axes)

The X5 connector allows to have:

- the logic ENABLE signal common to all axes,

- the POWER READY relay serially wired on all axes ,

- the AMP. READY relay serially wired on all axes ,

- the Idyn relay serially wired on all axes .

SPECIFICATIONS: Umax : 50 V, Imax = 100 mA, Prated = 5 W.

On some INFRANOR amplifier types, the Idyn relay may have another function, particularly the control of the

motor brake relay on the ranges BD1/m, BD1/h, BD1/p and BD1/s. In this case, the Idyn relay must be

independent on the rack backpanel (switches O and P = OFF).

2 – SETTING-UP DIAGRAMS OF THE BACKPANEL (X5 SWITCH, JUMPERS)Front view of the rack

12 TE BACKPANEL

B B B

A A A

N N N

a ab b a b

X5

01624 01624 01624

8 1DOPEFGH

12345678

DOPEFGH

12345678

View fromcomponents side

IMPORTANT

Page 16: BF RACK - infranorusa.com

16 Chapter 3 - Connections

BF RACK

18 TE BACKPANEL 24 TE BACKPANEL

B

A

N

a b

DOPEFGH

X5

01625

View fromcomponents side

B

A

N

a b

DOPEFGH

X5

01626

View fromcomponents side

3 – SETTING-UP OF THE CONNECTION CONNECTORS

XA1XA2 X MOT X MOT

X5

1

Power supply Axis 1 Axis 2

Switch

FRONT VIEW

Page 17: BF RACK - infranorusa.com

Chapter 3 – Connections 17

BF RACK

4 – XA1 AND XA2 SUPPLY CONNECTORS

The power supply connector includes the power supply inputs (XA1), the auxiliary supply and the connections

for the braking resistor(s), according to the selected option (XA2).

Braking resistor option D1

Braking resistor options E and D1230 VACauxiliary supply

1 2 3

L1 L2 L3

XA1

1 2 3 4 5

XA2

220 VAC three-phase3x220 VAC three-phase supplymax. section: 6 mm2

max. continuous current: 82 A

Earth: Ø 5 screw

NOTES

Power cables must not run in the proximity of low potential cables.

Option D: the braking resistor is wired inside the rack.

Option D2: the braking resistor is mounted and wired on the left rack flange.

5 – XMOT MOTOR CONNECTOR

The motor connection connector is particularly well suited for the electromagnetic compatibility and the motor

cables shield connection over 360° to the chassis is easy to make by means of a clamping collar.

The ground connection is made by a fastening lug according to the safety standards regarding the grounding.

U V W

Motor cable

Motor cable shield

360° shield connection collar

Motor screw connector

Support module having the chassisas mechanical reference potential

EarthØ 5 screw

Maximum section: 4 mm2.

Maximum continuous current: 44 Arms.

Page 18: BF RACK - infranorusa.com

18 Chapter 3 - Connections

BF RACK

NOTEThe conformity with the EMC standards requires the mandatory shielding of the motor cables, with a 360°

connection at both ends.

The motor cables must not run in the proximity of input command and resolver cables.

6 – THREE-PHASE CONNECTION VIA A 380V/220V (400V/230V) AUTOTRANSFORMER

The 380 V / 400 V three-phase power supply requires the use of a 380 V / 220 V autotransformer.

The 230 Vac phase/neutral connection is possible for the auxiliary supply.

The auxiliary supply can be connected between two 220 V phases to the autotransformer OUTPUT

The auxiliary supply is connected to the autotransformer output and the power contactor is put after the auxiliary

supply connection (see connection diagram).

K

K.1L1L2L3

N

UV

W

GND

X1

!

380(400)

220(230)

L1 L2 L3

!

24 VK1

+24V

(**)

0V

Autotransformer

Powerrelay Aux.relay

BF 35/70 FILTER

GND

6 pair shielded cables (+thermal probe)

RES

MOTOR

4 cables + shield

Rack chassis grounding

(*) POWER READY only available on X5 of the rack backpanel.If the POWER READY signal is unused, make jumper JK on theamplifier in order to have the AMP. READY signal taking intoaccount the power status.

Aux.relay

Aux. OFF

Aux.ON

Aux. relayPowerrelay

PowerON

Amp.ready

PowerOFF

Aux. relay

Powerrelay

Enable

Disable

Powerrelay

Enablerelay

(**) Magnetothermal circuit-breaker sized at 20/40/60 A for BF 35/70/90

3Acurve C

Log > 0 Log < 0

ENABLE

AMP. READY

POWERREADY

AMPLIFIER

(*)POWER READY

GND

Aux.relay

Page 19: BF RACK - infranorusa.com

Chapter 3 – Connections 19

BF RACK

NOTES

With a three-phase connection, all supply lines must ABSOLUTELY be cut off to ALL POLES.

The connection via an autotransformer is the most cost effective one but it is always possible to use a 380 V /

220V (400V / 230V) insulation transformer instead of an autotransformer (same connection as shown above, with

a grounded screened transformer).

The use of the auto-transformer does not allow the insulation between mains and power stage (and consequently

the motor) anymore. It is then mandatory to mount a correctly sized circuit-breaker inside the rack in the event of

a short-circuit (rectifier bridge, power bridge, motor). Further, the AMP. READY information (pins 18-19 of X4)

must be used for opening the power relay if a failure occurs.

ELECTROMAGNETIC COMPATIBILITY

A common mode inductance is mounted on the motor output and the auxiliary supply is also equipped with a

mains filter . In order to keep the conformity with the EN 55011 standard, group 1, class A, the mains filter on the

power is optional and must be mounted before the 220 VAC three-phase input.

The GROUNDING of the "BF" rack chassis is MANDATORY in order to avoid any physical damage in case of

defective mains insulation.

INFRANOR will withdraw any warranty on items that do not meet these requirements .

IMPORTANT

Page 20: BF RACK - infranorusa.com

20 Chapter 3 - Connections

BF RACK

7 – MAINS FILTER OPTION

The mains filter is MANDATORY for the conformity with the CE certification.

Curve n° 11 shows the conduction level for an average detection, according to the EN 55011 standard, group 1,

class A, with a rack connection via an autotransformer (5 dB overshoot at 250 kHz).

Curve n° 26 shows the improvement obtained with the mains filter. It allows a 10 dB margin with regard to the

maximum level authorized by the standard.

CURVE N° 11

Page 21: BF RACK - infranorusa.com

Chapter 3 – Connections 21

BF RACK

CURVE N° 26

MAINS FILTER CONNECTION

The mains filter must be connected as near the BF rack as possible (max. 30 cm). A metallic braiding must

connect the filter ground terminal to a fastening screw of the BF rack in order to get the equipotentiality. It is

recommended to use the cabinet housing for ensuring the equipotentiality.

The current rating must correspond to the rack current rating, that is:

- FT 35 --à 35 A,

- FT 70 --à 70 A.

8 – SPECIAL CONNECTION REQUIREMENTS

Wiring and ground connections must be very carefully made.

CAUTIONLow potential cables MUST NEVER run in the proximity of high potential cables.

NC, amplifier, motor and machine housing must be grounded via connections as short as possible. Use the

cabinet housing for the equipotential. Use rather braidings than wires, even thick ones.

Keep the equipotential between NC/amplifier, machine housing and motor.

The connectors must be metallic or metal plated (according to the CEI 801 standard ) and must allow "360°"

shield connections.

Page 22: BF RACK - infranorusa.com

22 Chapter 3 - Connections

BF RACK

The reference potential is the earth (ground).

The input command and the logic cables MUST be shielded.

The motor cable MUST be shielded and connected over 360° at both ends. Connect the shield on the motour or

machine housing by means of a metallic collar, as close to the motor as possible, after having removed the paint

if the connector is not metallic.

The sensor cable must be shielded. The correct sensor wiring is an absolutely necessary condition for the

correct operation of the amplifier. If these requirements are not answered, the described specifications will not be

obtained. Further, the wiring will not comply with the EMC requirements and will commit the user's own

responsibility.

The shield connections must be made as follows:

The connector housing is metallic or plated and allows an "360" shield connection, according to the CEM- CEI 801 - 2 - 3 - 4 - 5 recommendations.

Page 23: BF RACK - infranorusa.com

Appendix 23

BF RACK

Appendix

SHIELDING RECOMMENDATIONS

RULE

The shield must never be interrupted or corrupted over the whole cable length.

X

X

W

VU

L1L2

UW

NV

U V W

Self-sticking copper ribbon if necessary,for increasing the shield diameter in order

to get it correctly tightenedunder the clamp

Motor connector forresolver and motor

BF RACK

Ground

The cable can be soldered on the shieldbecause the connector box is metallic.

This solution does not exactly meet the EMC requirements but

it is acceptable.

Motor connector box

Metallic or metal plated plasticSUB-D pin package

360° shield ensured by the tightening clamp

The fastening screws mustbe tightened in order to ensure

the shield continuity on theamplifier housingINFRANOR

amplifier

SUB-D connectors

GroundUVW

As short as possible

SMT.AS / M.AS

BM 20 A

NOTE

When the 360° shield is made by means of a clamp, it is not necessary to additionally connect a cable on the

appropriate connection pin of the SUB-D connector.