Beam Estimation
Transcript of Beam Estimation
-
8/12/2019 Beam Estimation
1/16
Bar no
span (ft) 5 4 3
steel area (As) in2 0.4 0.4 2 bottom bar area 4
fy (ksi) 60 60 5
fc (Ksi) 3.5 5
Height h (inch) 6 6
Tie #3 0.375 0.375
Main Bar Dia #4 0.625 0.5
Cover 0.5 0.5 assumed
d 4.8 4.9
b 6.0 6.0
a 1.3 0.9
row 0.014 0.014
row balance 0.019 0.024 balance failure
Mu k-ft 7.5 8.8
Point Load p kip 6.0 8.8
Point Load p ton 3.0 4.4
Point Load p KN 29 43.2
Beam Capacity Calculation
-
8/12/2019 Beam Estimation
2/16
SI (mm) area
10 0.11 No of Beam 6
12 0.20 No of Test cylinder 54
16 0.31 Length (ft) 5
Width (In) 6
Depth (In) 6
One beam volume (cft) 1.3
Total volume of beams 7.5
Cylinder volume (dia 4" X heigth 8") 3.1
wastage (%) 80
total volume (cft) 28.7
assumed ration (C:FA:CA) 1
Cement (bag) 4.35
F.A (cft) 8
C.A (cft) 16
Material Estimation
ONLY GIVE INPUT TO GREEN BOXES
this is only for material procurement
purpose
-
8/12/2019 Beam Estimation
3/16
Shrinkage 1.5
1.5 3
500 2176 tk
85 666 tk
150 2350 tk
3016 tk
8209
-
8/12/2019 Beam Estimation
4/16
SI No. Properties Test Methods Value
1 Bulk Specific Gravity (OD Basis) ASTM C127 2.52
2 Apparent Specific gravity (OD Basis) ASTM C 127 2.63
3 Absorption Capacity ASTM C127 1.7
4 Dry Rodded Unit Weight ASTM C29 1581
5 Moisture Content of FA in Laboratory - 5.8
6 Fineness Modulus (FM) ASTM C136 2.43
Remarks
Table 5.3.2.2 Specified Compressive Strength f'c (psi) 3500
Required Strength (psi) 4700
Required Strength (Mpa) 32.6
Table-8 Slump values (mm) 75-100Maximum Size of Aggregate (mm) 12.5
Table-8 Amount of Mixing Water (kg/m3) 216
Table-8 Entrapped Air(%) 2.5By Formula w/c ratio 0.50
Cement Content (kg/m3) 429
Dry Mass of CA (kg/m3) 846.06
SSD Mass of CA (kg/m3) 855
FA OD Basis (kg/m3) 765
FA SSD Basis (kg/m3) 778
Volume
MethodFA Calculation
Assumed BulDry Rodded Bulk Volume of CA (m3 per
m3 of ConcreteTable 6 0.59
CA Calculation
see yellow m
Table-1 : Properties of Fine Aggregate (FA)
Check Yell
-
8/12/2019 Beam Estimation
5/16
Unit SI No. Properties Test Methods
- 1 Bulk Specific Gravity (OD Basis) ASTM C127
- 2 Apparent Specific gravity (OD Basis) ASTM C 127
% 3 Absorption Capacity ASTM C127
Kg/m3 4 Dry Rodded Unit Weight ASTM C29
% 5 Moisture Content of CA in Laboratory -
- 6 Maximum Size ASTM C136
Free Moisture in FA (kg) 31.2
Free Moisture in CA (kg) -6.25
Adjusted Mixing Water 191
Adjusted FA (kg) 809Adjusted CA (kg) 849
Total Adjusted Wet Mass 2278
Total SSD Mass 2278
Final Mix Proportioning0.020734
Water 3.96 k Cement 16.78 kg
FA 17.6 kg
CA 47.2 kg
Adjusted Mass For Lab Aggregate Moisture
Required Volume of Concrete (m3)
GIVE INPUT ONLY TO
GREEN BOXES
Specific Gravity 3.15
ark in book
Table-2 : Properties of Coarse Aggregate (C
w Marks
-
8/12/2019 Beam Estimation
6/16
Value Unit
2.65 -
2.73 - Field Wt 500 gm
1.1 %
1434 Kg/m3 Oven Dry Wt 472.7 gm
0.4 %
12.5 mm Lab Moisture Content 5.8 %
Dia 4
Hight 8
0.00165
9
Length 5Mix Ratio Width 5
1 Hight 5
1.0
2.8 0.02457
0
0.01481
1.4
0.0207
Lab Moisture Co
Fine Aggregate
Volume of One Cylinder
)
Calculation
OK
Total Volume of Concrete
Volume of Concrete Estimation
Cylinder
Beam
No of Cylinder
Volume of One Beam
No of Beam
Volume of Concrete
Wastage Factor
-
8/12/2019 Beam Estimation
7/16
Field Wt 500 gm
Oven Dry Wt 498.2 gm
Lab Moisture Content 0.4 %
UNIT
inch
inch
m3
ftinchinch
m3
m3
tent Calculation
Coarse aggregate
-
8/12/2019 Beam Estimation
8/16
SIEVE SIZE SIZE
MASS
RETAIN
(gm)
INDIVIDUAL
% RETAIN
CUMULATIVE
% RETAIN
4.75 mm (No. 4 ) 4.75 0 0 0
2.36 mm (No. 8 ) 2.36 11 2 2
1.18 mm (No. 16 ) 1.18 45 9 11
600 m (No. 30 ) 0.6 112 22 34
300 m (No. 50 ) 0.3 190 38 72
150 m (No. 100 ) 0.15 109 22 94
0.075 22 4 98
pan - 11 2 96
TOTAL 500 2.13
A B S
492.6 1321.4 500
2625 gm
7102 gm
2832 cm3
1581 kg/m3
UNIT Wt OF FINE AGGREGATE
SP GRAVITY AND ABSORPTION CAPACITY
Test for Specific Gravity and Absorption Capacity of San
Test Method ASTM C128-88
Oven Dry Sample
(gm)Pyc+Water (gm) pyc+Water +Sample (gm)
C
SSD wt of
Sample(gm)
1629.7
gm/cm3Unit Wt
Weigth of Mold (T)
Weigth of Sand + Mold (G)
Volume of Mold (V)
1.581M=
-
8/12/2019 Beam Estimation
9/16
% PASSING
100
98
89
66
28
6
2
4
Bulk SSD Aparent
1.5 2.57 2.61 2.67
Absorption
Capacity
(nearest 0.1% )
Specific Gravity (nearest 0.01)
0
20
40
60
80
100
0.01 0.1 1
percentfiner(%
)
Particle Size (mm)
+ +
+
100
-
8/12/2019 Beam Estimation
10/16
10
-
8/12/2019 Beam Estimation
11/16
SIEVE SIZE SIZEMASS RETAIN
(gm)
INDIVIDUAL %
RETAIN
CUMULATIVE %
RETAIN
25 mm (1in) 25 0 0 0
19 mm (3/4 in ) 19 0 0 0
12.5 mm (1/2 in) 12.5 33 2 2
9.5 mm (3/8 in) 9.5 303 15 17
4.755 mm (No. 4) 4.75 1477.3 74 91
2.36 mm (No. 8) 2.36 181.3 9 100
Pan - 5.4
TOTAL 2000
Oven Dry Sample (gm) SSD wt in air (gm)SSD wt in water
(gm)
Absorption
Capacity (nearest
0.1% )
Specific Gravity
(nearest 0.01)
Bulk
A B C
1942.6 1982 1796.6 2.03 10.48
2625 gm
6686 gm
2832 cm3
SP GRAVITY AND ABSORPTION CAPACITY
Test for Specific Gravity and Absorption Capacity of Sand
Test Method ASTM C128-88
UNIT Wt OF FINE AGGREGATE
Weigth of Mold (T)
Weigth of Stone + Mold (G)
Volume of Mold (V)
100
-
8/12/2019 Beam Estimation
12/16
1434 kg/m3
Unit Wt.
M=
-
8/12/2019 Beam Estimation
13/16
% PASSING
100
100
98
83
9
0
0
SSD Aparent
10.69 13.31
0
20
40
60
80
100
1 10
PercentFiner(%
)
Particle Size (mm)
-
8/12/2019 Beam Estimation
14/16
-
8/12/2019 Beam Estimation
15/16
100
-
8/12/2019 Beam Estimation
16/16
NAME QUANTITY TK
SAND 11 cft 420
stone 3/4 down 25 cft 3300
stone 1/2 down 5 cft 550
conveyance 1 track 1500
lobour + 42 plastic bag - 500
labour 2 person 1500 5/20/2014
cement 6 bag 2700
cement transport - 300
1 st lab mix + labour 1 person 500 7/15/2014
other cost 230
11500total cost
5/19/2014
10/9/2014