BD2 System (160 A - 1250 A) - · PDF fileDescription BD2 System (160 A - 1250 A) 5/4 Siemens...
Transcript of BD2 System (160 A - 1250 A) - · PDF fileDescription BD2 System (160 A - 1250 A) 5/4 Siemens...
Siemens LV 70 · 2004
5/2 System overview
5/4 Description
5/12 Engineering
5/23 Fire barriers
Selection and ordering data5/30 Straight trunking units5/46 Feeder units5/50 Junction units5/58 Tap-off units for international use5/67 Tap-off units for Belgium5/68 Tap-off units for Denmark5/69 Tap-off units for Great Britain5/70 Tap-off units for France5/71 Tap-off units for Switzerland5/72 Ancillary equipment units
for international use5/73 Accessories
5/77 Technical data
Dimension drawings5/84 Trunking units, branch units5/84 Junction units5/88 Distribution board feeder units,
feeder units5/89 Feeder units5/90 Cabling boxes, centre feeder units5/91 Centre feeder units5/92 Tap-off units5/96 Ancillary equipment unit,
accessories5/97 Accessories
BD2 System (160 A - 1250 A)
System Overview
Siemens LV 70 · 20045/2
BD2 System (160 A - 1250 A)
5
4
1
4
2
2
5
5
4
5
2
3
3
5
System Overview
Siemens LV 70 · 2004 5/3
BD2 System (160 A - 1250 A)
5
1 Straight trunking unitsWith/without fire barrierDegree of protection IP52, or IP54 withaccessories (IP55 on request)5-conductor systemStandard lengths 3.25 m; 2.25 m; 1.25 mOptional lengths from 0.5 m to 3.24 mTap-off points:NoneOn both sides offset by 0.25/0.5 m to each otherFire barriers: fire resistance ratingS90 and S120 DIN 4102 Sheet 2 – 4
a Page 5/30
2 Feeder unitsEntry/end feeder unitCentre feeder unitDegree of protection IP54 (IP55 on request)Bolt terminalCable entry from 1, 2 or 3 sidesDistribution board feeder unit
a Page 5/46
3 Junction unitsEdgewise/flatWith/without fire barrierDegree of protection IP52, or IP54 with accessories (IP55 on request)L units standard or engineered angleZ unitsT unitsCross unitsFlexible junction units
a Page 5/50
4 Tap-off unitsDegree of protection IP54 (IP55 on request)
Up to 25 AInsulated enclosureDouble anti-rotation feature
Up to 63 ASteel enclosure, hot-galvanized, cover with powder-spray paint finish
Up to 125 ASteel enclosure, hot-galvanized, cover with powder-spray paint finish
Up to 400 ASteel enclosure, hot-galvanized, powder-spray paint finishTap-off unit partitioned according to functionEnclosure for protective devicesEnclosure for power pick-upDouble anti-rotation feature
a Page 5/58
Ancillary equipment unitDegree of protection IP54 (IP55 on request)For 8 space unitsWith or without component mounting unitCover with powder-spray paint finish
a Page 5/72
5 AccessoriesEnd flangeFor degree of protection IP54Flange for edgewise mounting positionFlange for flat mounting positionFlange for vertical mounting positionFor fixingUniversal fixing bracket for edgewise/flat mountingFixing elements for vertical trunking runs, for wall or ceiling mountingClamp terminal
a Page 5/73
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/4
5
• Type-tested low-voltage switchgear and controlgear assembly (TTA) to IEC/EN 60 439-1 and -2
• Quick, straight forward planning• Time-saving, efficient installation• Reliable, safe operation• Flexible modular system with simple solutions for every application• Early planning of power distribution possible without precise knowledge of con-
sumer locations• Fast operational readiness through quick, easy assembly• High degree of protection to IP54 for use in harsh industrial environments• Innovative construction: no compensating units for expansion compensation re-
quired.• Tap-off units and tap-off points can be coded at the factory• Sealable throughout
Power is transferred through tinned and nickel plated aluminium and copper bus-bars.The low inherent impedance and large surface area of the busbars limit the heat build-up.The result is a low transmission loss and a low voltage drop.
The enclosure is made of hot galvanized steel with a paint finish.Colour: light grey RAL 7035.
BD2A-1, BD2C-1 trunking unit
BD2A-2, BD2C-2 trunking unit
BD2A-3, BD2C-3 trunking unit, junction unit, BD2A-..., BD2C-... feeder units
Protected to IP52 degree of protection as standard. Enhancement to IP54 with ad-ditional parts.
The busbar support and tap-off point form a unit.The early-make/late-break PE contact at the tap-off unit provides positive opening or closing of the tap-off point.The tap-off point can be coded at the factory on request, together with the tap-off unit.The tap-off point is sealable.BD2-AK1... and ...4 tap-off units are plug-in types for all systems, BD2-AK5... tap-off units are only for systems from 500 A.
Trunking units are connected quickly and securely via the clamp terminal.
Clamp terminal
Features:• Even holding pressure ensures completely secure connection of all five busbars.
Quick mounting up to 400 A with plug-in terminal, from 500 A to 1250 A with bolt terminal.
• The built-in expansion compensation absorbs the heat expansion of the busbars.• The terminal can be tightened using conventional tools.• Two sizes are available for the whole system.• The clamp terminal is supplied as integral part of the trunking units.
Four screws provide the mechanical connection between housing and terminal as-sembly.
Features
Trunking units
Enclosure
160 to 400 A 500 to 1250 A
mN L1 L2 L3 mPE
167
68
mN L1 L2 L3 mPE
126
167
160 to 400 A 500 to 1250 A
N L1 L2 L3 mPE
167
68
N L1 L2 L3 mPE
126
167
160 to 400 A 500 to 1250 A
N
68
L1
167
L2 L3 PE
N L1
167
L2 L3 PE
126
Tap-off points
Connection
for BD2.-.-160 to BD2.-.-400 for BD2.-.-500 to BD2.-.-1250
Flange cover Clamp terminal
160 to 400 ABD2-400-SK
500 to 1250 ABD2-1250-EK
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/5
5
EquipmentThe trunking units are available in the following versions:• without tap-off points• with tap-off points at both sides at intervals of 0.5 m, offset by 0,25 m
(BD2.-2, BD2.-3) and at intervals of 1m, offset by 0.5 m (BD2.-1).One clamp terminal is included as standard.Fire barriers can be fitted (a Engineering, Fire barrier, page 5/24).The following lengths are available:• 3.25 m• 2.25 m• 1.25 m• Optional lengths
Number of tap-off points
On optional lengths, it may not be possible to fit tap-off units to all tap-off points
EquipmentFlexible copper conductors for the junction units.The L units with configurable angle are available with a fixed angle of 90° or any angle in 5° increments from 85° to 175°.All L and Z units are available with• standard limb lengths of 0.36 m• one or two limb lengths selectable from 0.36 m to 1.25 m.The branch units and junction units are supplied with one clamp terminal.
Straight trunking units
Lengthm
Tap-off points on two sides
1.25 to 2.25 2 to 8
2.26 to 3.25 4 to 12
Branch units and junction units
Flexible junction units
BD2-...-R
L units
Z units
X Y X
Y
X Y YX
Knee, rear
Elbow, right
Knee, front
Elbow, left
BD2.-...-LHBD2.-...-LH-X*BD2.-...-LH-Y*BD2.-...-LH-X*/Y*
BD2.-...-LVBD2.-...-LV-X*BD2.-...-LV-Y*BD2.-...-LV-X*/Y*
BD2.-...-LRBD2.-...-LR-X*BD2.-...-LR-Y*BD2.-...-LR-X*/Y*
BD2.-...-LLBD2.-...-LL-X*BD2.-...-LL-Y*BD2.-...-LL-X*/Y*
X
Z
Y X
Z
Y
X ZY
ZX
Y
FrontRear
Right Left
BD2.-...-ZV-Z*BD2.-...-ZV-X*/Y*/Z*
BD2.-...-ZH-Z*BD2.-...-ZH-X*/Y*/Z*
BD2.-...-ZR-Z*BD2.-...-ZR-X*/Y*/Z*
BD2.-...-ZL-Z*BD2.-...-ZL-X*/Y*/Z*
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/6
5
If the busbar system is routed through a fire wall or ceiling, a fire barrier must be fitted. Depending on the customers requirements, Siemens offers fire barriers with a fire resistance rating of S90 and S120. Standard lengths, optional lengths and branch units are supplied with fire protecti-ve equipment as specified in the ordering data (a Engineering, Fire barrier, Page 5/24).
Factory-fitted equipment:• Internal fire barrier• External fire barrier, if required• Documentation (certificate of approval, wall-mounted signs and declaration of
conformity).Mineral based mortar or “ZZ fire barrier sealant TS90”(engineering “fire barrier” a page 5/29) for sealing joints between the busbar trunking element and fixed structure must be supplied by the customer.
Fire protection for trunking units and branch units
For the incoming supply to BD2 runs, various feeder unit variants are available to meet different requirements.For example: end feeder unit with connected cabling box.
Features:• Cables are introduced from the front face.• Cable entry plate (aluminium) for single-core cable entry available if required.• Cable connection is via bolts. The bolts are included as standard.• The factory-fitted link between PE and N can be removed for connection of
five-core cables.• Feeder units are supplied without clamp terminal.
T units
Cross units
L unit with engineered angle from 85° to 175°
Rear
Right Left
Front
BD2.-...-TH BD2.-...-TV
BD2.-...-TR BD2.-...-TL
Front/rear Right/left
BD2.-...-KVH BD2.-...-KRL
G*= 85°–175°
G*= 85°–175°
G*= 85°–175°G*= 85°–175°
Knee, rear Knee, front
Elbow, right Elbow, left
BD2.-...-LH-G*BD2.-...-LH-X*-G*BD2.-...-LH-Y*-G*BD2.-...-LH-X*/Y*-G*
BD2.-...-LV-G*BD2.-...-LV-X*-G*BD2.-...-LV-Y*-G*BD2.-...-LV-X*/Y*-G*
BD2.-...-LR-G*BD2.-...-LR-X*-G*BD2.-...-LR-Y*-G*BD2.-...-LR-X*/Y*-G*
BD2.-...-LL-G*BD2.-...-LL-X*-G*BD2.-...-LL-Y*-G*BD2.-...-LL-X*/Y*-G*
Fire barriers
For S90 For S120
+BD2-S90-BX*-M*+BD2-S90-BY*-M*+BD2-S90-BZ*-M*
+BD2-S120-BX*-M*+BD2-S120-BY*-M*+BD2-S120-BZ*-M*
Feeder units
M*
BX*
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/7
5
For double-ended feed, an additional clamp terminal is required.
If end feeder units are used in addition to centre feeder units, an additional clamp terminal is required for each end feeder unit.
Cable entry from the front face. For cable entry from the side, the cabling space can be extended using +BD2-...-KR.
The phase sequence can be changed on site by rotating the busbar pack.
For BD2 connection to distribution boards.
Cable entry from three sides. The phase sequence can be changed on site by rota-ting the busbar pack.
End feeder units
BD2.-...-EE BD2.-...-ME
BD2.-...-EE +BD2-...-KR
Distribution feeder unit
Centre feeder unit
N L1 L2 L3 PE
BD2.-...-VE
PE on the left PE on the right
PE at the rear PE at the front
BD2.-...-ME
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/8
5
Tap-off units are available in a number of variants for different applications.
Insulated tap-off units for up to 25 A with fuses, miniature circuit-breakers and sockets
Features:• Insulated enclosure, colour light grey, similar to RAL 7035• Transparent cover for the protective elements• During mounting and removing of the tap-off units, a load switching capacity of
AC-22B up to 400 V is reached.• Anti-rotation feature prevents incorrect mounting• Power pick-up via silver-plated horseshoe contacts• Cables can be introduced from three sides• The tap-off unit must be removed from the trunking before the unit can be ope-
ned and the cables connected.• Built-in strain relief• The connection cable should also be supported separately
Steel enclosed tap-off units BD2-AK02 (AK03) without cover integrated switch-disconnector
Features:• Galvanized steel enclosure and cover with powder-spray finish, colour light grey,
RAL 7035• The tap-off units can be mounted and removed with their cover open and closed.• Anti-rotation feature prevents incorrect mounting• The cable can be introduced from three sides, use plastic cable glands with strain
relief, (not supplied).• Power pick-up via silver-plated horseshoe contacts• If using the PE conductor as a PEN conductor, observe that the PE contacts of the
BD2-AK03 tap-off unit have only half cross-section and can therefore not carry the full rated current.
• The connection cable should also be supported separately
Component mounting unitFor installing devices (such as miniature circuit-breakers) conform to DIN 43 871, with 8 MW. Each MW corresponds with a space requirement of 18 mm. Hinged covers on all tap-off units allow device operation from outside.
Tap-off unit BD2-AK02... up to 63 A with fuses, miniature circuit-breaker
Features:• Miniature circuit-breakers can optionally be operated from the outside
(component mounting unit with 8 MW; 1 MW = 18 mm)
Tap-off unit BD2-AK03... up to 125 A with circuit-breakers, fuse switch-disconnectors, fuse bases, miniature circuit-breakers and fuse-switches
Features:• On versions with fuse switch-disconnectors, fuse switches or circuit-breakers, the
cover is interlocked with these switches and can therefore be opened only when they are switched Off.
• Terminal bolts for cable connection (a page 5/82).• Miniature circuit-breakers can optionally be operated from the outside
(component mounting unit with 8 MW; 1 MW = 18 mm)
63 A and 125 A tap-off units configured to customer specifications
Features:• Device installation to customer specification in compliance with the require-
ments for type-tested low-voltage switchgear and controlgear assemblies (TTA). Engineering, quotations and delivery through the Siemens sales organisations.
• Devices mounted on pre-drilled mounting plates, module mounting rails or top-hat rails to EN 50 022.
Tap-off units
BD2-AK1/CEE165A163
BD2-AK02M2/A323
BD2-AK03X/L...
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/9
5
Steel enclosed tap-off BD2-AK2 (AK3, AK4, AK5) without cover integrated switch-disconnector
Features:• Galvanized steel enclosure and cover with powder-spray finish, colour light grey,
RAL 7035• The tap-off units can be mounted and removed only with their cover open.• Anti-rotation feature prevents incorrect mounting• The cable can be introduced from three sides, use plastic cable glands with strain
relief (not supplied).• Power pick-up via silver-plated horseshoe contacts• If using the PE conductor as a PEN conductor, observe that the PE contacts of the
BD2-AK3..., BD2-AK4... and BD2-AK5... tap-off units have only half cross-section and can therefore not carry the full rated current.
• The connection cable should also be supported separately
Component mounting unitFor installing devices (such as miniature circuit-breakers) conform to DIN 43 871, with 8 MW. Each MW corresponds with a space requirement of 18 mm. Hinged covers on all tap-off units allow device operation from outside.
Tap-off units BD2-AK2... up to 40 A with PKZ2 circuit-breaker
Features:• Built-in PKZ2 circuit-breaker or PKZ2 starter combination with selectable acces-
sories• Equipment fitted as required by the customer (please enquire)• Cover interlock (on version without remote operator)• Switch-disconnector built into the cover, switching capacity AC-22B up to 400 V,
ensures that devices fitted are voltage-free when the cover is open.
Insulated BD2-AK2... tap-off units for up to 63 A with fuses, miniature circuit-breakers and sockets
Features:• Switch-disconnector built into the cover, switching capacity AC-22B up to 400 V,
ensures that devices fitted are voltage-free when the cover is open• Miniature circuit-breakers can optionally be operated from the outside (compo-
nent mounting unit with 8 MW; 1 MW = 18 mm)
Tap-off unit BD2-AK3... up to 125 A with circuit-breakers, fuse switch-disconnectors and fuse bases
Features:• On versions with fuse switch-disconnectors or circuit-breakers, the cover is inter-
locked with these switches and can therefore be opened only when they are swit-ched Off.
• On versions with fuse bases, the isolator built into the cover does not disconnect the load. It only removes the voltage from the installed fuse bases when the co-ver is opened.
• Terminal bolts for cable connection (a page 5/82).
Tap-off unit BD2-AK4... up to 250 A and BD2-AK5... 400 A with fuse switch-disconnectors and fuse bases
Features:• Type BD2-AK5... tap-off units above 250 A can be mounted only on 500 A to
1250 A trunking units.• Tap-off unit partitioned according to function• Enclosure for protective devices• Enclosure for power pick-up• Reliable prevention of incorrect mounting and removal• Power pick-up via silver-plated horseshoe contacts• Zero voltage is ensured by isolating the power pick-up from the tap-off point.
This can be done only with the enclosure cover removed.• On versions with a fuse switch-disconnector, the cover is interlocked with the
switch to ensure zero load and zero voltage at the cable terminals when the tap-off unit is open.
• On versions with fuse bases, the load must be disconnected before the enclosure cover is removed.
• Connections for single-core and multi-core cables (a page 5/82)
63 A and 125 A tap-off units configured to customer specifications
Features:• Switch-disconnector integrated into the cover. Switching capacity with
63 A AC-22B up to 400 V or at 125 A AC-21B, which ensures that the unit is not live when the cover is open.
• Device installation to customer specification in compliance with the require-ments for type-tested low-voltage switchgear and controlgear assemblies (TTA). Engineering, quotations and delivery through the Siemens sales organisations.
• Devices mounted on pre-drilled mounting plates, module mounting rails or top-hat rails to EN 50 022.
BD2-AK2X/CEE325S33
BD2-AK3X/GSTZ00
BD2-AK41/GSTZ1BD2-AK51/GSTZ2
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/10
5
Features:• The enclosure is made from hot-galvanized sheet steel.• The cable can be introduced from three sides, use plastic cable glands with strain
relief (not supplied).• Can be combined with tap-off units (BD2-AK02, AK2, AK03, AK3)• A top-hat rail is built-in for component mounting.• One size with 8 MW (1 MW = 18 mm)• With or without component mounting unit for external operation
(one size with 8 MW)• Installation of devices such as miniature circuit-breakers in accordance with
DIN 43 871 possible up to and including 63 A.
Protective sleeveProvides purely mechanical protection for the busbar system when it is routed through walls and ceilings. The protective sleeve can be retrofitted.
End flangeAn end flange is required for terminating the busbar run. Two sizes are available.
Edgewise mounting positionThe higher degree of protection is achieved by fitting an additional top cover at the connection points.
Flat mounting positionThe higher degree of protection is achieved by fitting an additional top cover at the connection points and the tap-off points.
Vertical mounting positionThe higher degree of protection is achieved by fitting additional covers at all the connection points and at all tap-off points.
Ancillary equipment unit
Accessories
0.185
160 to 400 ABD2-400-D
500 to 1250 ABD2-1250-D
160 A to 400 ABD2-400-FE
500 A to 1250 ABD2-1250-FE
Accessories for IP54
Flange for connection point between straight trunking units
Flange for connection point between trunking unit and end flange
BD2-...-HF BD2-...-HFE
Flange for connection point between straight trunking units
Flange for connection point between trunking unit and end flange
BD2-FF BD2-FFE
Flange for tap-off openings
BD2-FAS
Flange for tap-off openingsFlange for connection point between straight trunking units
BD2-...-VF BD2-FAS
DescriptionBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/11
5
Fixing bracketThe universal fixing bracket can be used for edgewise and flat mounting of all trun-king variants.
Spacer bracketSpacer bracket for compensating building tolerances between trunking unit and wall or ceiling. The spacer bracket slides onto the BD2-...-BB fixing bracket and is secured with screws. For vertically mounted BD2 runs, it can also be used as an in-termediate mounting.
SpacersSpacers for compensating wall and ceiling discrepancies between feeder units and trunking units. The spacers clip onto the fixing bracket.
Retaining element for vertical busbar runsThese consist of a wall mounting element and accessories for fixing to to the ceiling.The retaining elements are adjustable to compensate for uneven walls.Maximum load carrying capacity of retaining element (a page 5/18).
Wall mounting element for busbar run and end feeder unit
At the transition from the horizontal to the vertical busbar run, the ceiling mounting must be used as a support element.
Ceiling mounting element for busbar run
Wall mounting element for busbar run at each clamp terminal
Mounting accessories
160 A to 400 ABD2-400-BB
500 A to 1250 ABD2-1250-BB
BD2-BD
BD2-DSB
BD2-BWV
BD2-BDV
BD2-BVF
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/12
5
Specimen text for tenders and quotations
Item Quantity Description Unit price Amount
... m Busbar trunking system (see Appendix for diagram)
• As “type-tested low-voltage switchgear and controlgear assembly” (TTA) to IEC/EN 60 439-1 and -2
• Rated current, corresponds with therm. rated current at max. +40 °C and +35 °C average over 24 hours for indoor installation
• Rated insulation voltage Ui 690 V AC, 800 V DC; overvoltage category/pollution degree III/3
• Operational voltage ...V, ...Hz
• Rated peak withstand current of busbar trunking system,... kA tested to IEC/EN 60 439-1
• Degree of protection IP52, IP54 (with accessories)
• Tested for sprinkler systems (with additional parts)
• Halogen free system
• Functional endurance E30, E90 (with additional parts)
• 5-conductor system: L1, L2, L3, N, PE
• Busbar: aluminium or copper, nickel-plated and tinned; supported by insula-ted busbar supports
• Trunking units steel-enclosed, galvanized and with paint finish; Colour light-grey RAL 7035
• Busbar connection via clamp terminal with built-in expansion compensation
• Tap-off points: on both sides at 0.5 m intervals; offset by 0.25 m to one another and every 1 m; offset by 0.5 m
• Supplied ready for connection, with all assembly parts
• Made by Siemens
• Type BD2.-...
• Consisting of:
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/13
5
Key to type references for BD2 for various conductor versions
BD2 . - . - ... - ... - ...
(details of length)
(Type length)
Current Aluminium Copper1602503154005006308001000
16025031540050063080010001250
1: L1, L2, L3, 1/2 N, 1/2 PE; 6 tap-off points2: L1, L2, L3, 1/1 N, 1/2 PE; 12 tap-off points3: L1, L2, L3, 1/1 N, 1/1 PE; 12 tap-off points(N-conductor with 150 or 200 percent cross-section on request)
A: AluminiumC: Copper
BD2 . - ... - ... - ...
(Length details with junction unit)
(Type junction unit, feeder unit)
Current Aluminium Copper250 (only feed-in)4001000
250 (only feed-in)4001000 (feeder only)1250
A: AluminiumC: Copper
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/14
5
Structures made from standard materials.Manufacturer: Rieth & Co, Kirchheim-Teck, Tel. +49 (0) 7021 977-0.BD2-...-BB bracket not included with struts and beams.
Examples for mounting edgewise runs
• Length L of strut in 100 mm increments
• Length L of strut in 100 mm increments• Trunking units can be secured at the side and at the centre of the strut
Wall beam100 mmF BF 600 mm• Width in 50 mm increments
Examples for mounting flat runs
• Length L of strut in 100 mm increments
H strutLF 2500 mm100 mmF BF 600 mm• Length in 100 mm increments• H strut with beam• Width B in 50 mm increments• For securing runs without BD2-...-BB bracket
Wall beam100 mmF BF 600 mm• Width B in 50 mm increments• For securing runs without BD2-...-BB bracket
Example for securing busbar runs between floors
Tubular strut with beam200 mmF BF 600 mm• Width B in 50 mm increments• For securing runs without BD2-...-BB bracket
Notes on supporting structures
C strut with accessoriesLF 500 mm
Double C strutLF 500 mm
Z strut500 mmF LF 2000 mm
H strutLF 2500 mm
L L
L
L
B
C strut with accessoriesLF 500 mm
Double C strut500 mmF LF 2000 mm
L
L
LB
B
B
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/15
5
Suspension support on flange mounts using clamp brackets
90 mmF bF 150 mm• For Z and H struts only
Securing trunk units on the cable trays
• Can be fitted to standard cable trays using BD2-...-BB fixingbrackets or angle clamp
• Sundries required
Clamp brackets
For securing trunking units to the illustrated supporting structures.
To simplify engineering of BD2 systems, engineering symbols have been introduced. On the engineering drawings, these symbols clearly indicate the component moun-ting position, the phase sequence, the open busbar end, the end with the terminal, the position of the flange cover and the side from which the terminal can be acces-sed.The following conventions apply to all components of the busbar run (feeder units, straight trunking units, branch units and junction units):
Open busbar end
Phase sequence, PE on the right
The PE side is marked with a bold black line.
Terminal end of the trunking unit
Terminal access side Top flange cover
Example: Straight trunking unit with tap-off points on both sides,Type: BD2.-...-SB-.
The engineering symbols are used on the selection data pages.
Determining the orientation of L units
= L = Left = V= Front = R= Right = H= Back
Example: Elbow, right, Type: BD2.-...-LR
= R = Right
Determining the orientation of feeder unitsOn feeder units, the position of the cabling box relative to the trunking box is not critical for type selection, since the busbar connection flange can be turned on site to provide the required phase sequence.
Basic engineering information
b
N L1 L2 L3 PE
SB
End feeder unit
Centre feeder unit
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/16
5
Horizontal installationWith the BD2 system, the mounting position can be chosen as required, allowing a horizontal busbar run to be laid out in two ways:
Horizontal, edgewise
Horizontal, flat
As can be seen from the illustration, any phase sequence is possible. A reduction factor in horizontal edgewise mounting position (x 0.9) is necessary with power transmission.This applies for straight trunking units and branch/junction units. The engineering symbol identifying the type shown on the selection page only needs to be turned to the desired mounting position in the engineering drawing.
Example: Elbow, right, Type: BD2.-...-LR
Horizontal edgewise mounting has the advantage of a larger suspension span and the need for fewer accessories (flanges) to achieve IP54 degree of protection (a page 5/10).
Vertical installationWhen engineering vertical busbar runs (a page 5/22) the height of the storey measured from the centre of one ceiling to the centre of the next determines the choice of busbar trunking lengths. If no fire barriers are required, standard lengths with protective sleeves can be used. In this case a distance of at least 0.185 m must be maintained between the end of the trunking unit and the upper edge of the pro-tective sleeve.For vertically mounted systems, only one mounting position is possible.The PE bar must always be on the right-hand side, and the trunking unit end with the clamp terminal must point towards the top. This ensures that• the flange cover can be push-fitted to the terminal from the front and the screws
can be tightened,• the tap-off units are not mounted upside-down, i.e. they can only be fitted in the
correct position.
No derating is required for vertical busbar runs. Further information about vertical installation h page 5/22.
Mounting positions
NL1L2L3PE
PEL3L2L1N
N L1 L2 L3 PE PE L3 L2 L1 N
Mounting:Flat Edgewise
N L1 L2 L3 PE
PE
Clamp terminal Tap-off point Cable gland BD2.-...-EE feeder unit Cover Clamp terminal (of the last trunking unit in the vertical busbar run) Tap-off unit
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/17
5
Dimensions in the engineering drawings BD2.-2, BD2.-3 tap-off point clearance = 0.5 m, (BD2.-1 tap-off point clearance = 1 m)
Dimension
Straight trunking unit, optional lengths BD2.-2, BD2.-3 tap-off point clearance = 0.5 m, (BD2.-1 tap-off point clearance = 1 m)The open busbar end is used as the reference edge. The grid spacing between the tap-off points is shown in the diagram.
Distance x is the distance between the centre of the terminal at the open end and the next tap-off point on the trunking unit. For the standard length x = 250 mm. For optional length, 260 mmFxF 490 mm (depending on the optional length w).
Measuring and determining the optional lengths on site
On site, the dimension a between the housing edges of the two trunking units to be connected is measured. The optional length is then determined as follows:
Branch junction unitsX dimension (side with open busbar end): from centre of terminal to outside edge of housingY dimension (side with clamp terminal): from centre of terminal to outside edge of housingZ dimension: from one outside edge of the housing to the next Dimensioning data a page 5/84.
Defining the engineering reference dimensions
Straight trunking unit, standard lengthsStandard lengths from centre of terminal to centre of terminal
Example: Standard length with tap-off points on both sides, Type: BD2.-...-SB-3
SB
3.25 m
220307 (557)
167
163
n × 500 (1000)
167
w
nX 250 (500) 250
PE
PEL3
L2L1
N
On optional lengths, it may not be possible to fit tap-off units to all tap-off points
Length m
Tap-off points on two sides
0.5 to 1.24 –
1.25 to 2.25 2 to 8
2.26 to 3.25 4 to 12
a
w
w[m] = a[m] – 0.14 m
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/18
5
Max. length/height of vertical BD2 busbar runs,supported by one BD2-BWV or BD2-BDV retaining element
BD2A-.-...Rated current A 160 250 315 400 500 630 800 1000 1250
Max. supported length or heightat max. weight (see below)
m 11,3 10,9 8,2 7,9 5,8 5,8 5,8 5,3 –
Max. weight per 3.25 m trunking unitfitted with tap-off units
kg 50 53 71 74 106 106 108 108 –
BD2C-.-...Rated current A 160 250 315 400 500 630 800 1000 1250
Max. supported length or heightat max. weight (see below)
m 10,0 9,9 7,7 7,2 5,2 5,2 4,8 4,1 3,25
Max. weight per 3.25 m trunking unitfitted with tap-off units
kg 50 53 71 74 106 106 108 108 108
NotesFor taller BD2 trunking runs, additional mountings must be used.The maximum load applied to the BD2-BWV and BD2-BDV verticalmountings must not exceed 175 kg.The vertical mountings must be fitted at the terminal.
Overload and short-circuit protection
Busbar trunking systems must be protected against overload and short-circuits. Fu-ses and circuit-breakers are used for this purpose. The highest prospective short-cir-cuit currents, selectivity requirements or operator control and signalling functions may be deciding factors in selecting protective devices.Due to their high response threshold (1.3 to 1.6 times rated current) and their long rupturing times at small overcurrents, fuses are generally less suitable for overload protection.To ensure that fuses provide sufficient protection against busbar trunking system overload, the rated current of the fuse must be one level lower than the rated cur-rent of the busbar trunking system to be protected. This prevents optimum utiliza-tion of the busbar trunking system.
If circuit-breakers are used, the thermally delayed overload release is set to the ra-ted current value for the busbar trunking system. This allows 100 % utilization of the system. Where fuses and circuit-breakers are used for short-circuit protection, the specified short-circuit rating of the busbar trunking system must not be exceeded.The need for a current limiting protective device and the required short-circuit bre-aking capacity of the protective device depend on the magnitude of the prospective short-circuit current.The table below provides an overview of the circuit-breakers suitable for short-cir-cuit and overload protection (400 V and 50 Hz) of the respective busbar trunking sy-stem.
The following applies:
I ″k = prospective short-circuit current at the installation locationIcc = rated conditional short-circuit current of the busbar trunking systemIcu = rated short-circuit breaking capacity of the circuit-breaker
I ″k Icc Icu
The conditional rated fused short-circuit current Icc values below apply to the busbar trunking systems without consideration of any tap-off units.
Rated current Circuit-breaker with normal switching capacity
Circuit-breaker with medium switching capacity
Circuit-breaker with high switching capacity
IeA
IcukA
IcckA
IcukA
IcckA
IcukA
IcckA
BD2.-160 160 NZM7-160N 25 25 NZM7-160S 1) 65 65 NZM7-160H 1) 100 100BD2.-250 250 NZM7-250N 35 35 NZM7-250S 1) 65 65 NZM7-250H 1) 100 100BD2.-315 315 NZM10-400N 45 45 NZM10-400S 1) 65 65 NZM10-400H 1) 100 65BD2.-400 400 NZM10-400N 45 45 NZM10-400S 1) 65 65 NZM10-400H 1) 100 65BD2.-500 500 NZM10-630N 45 45 NZM10-630S 1) 65 65 NZM10-630H 1) 100 65BD2.-630 630 NZM10-630N 45 45 NZM10-630S 1) 65 65 NZM10-630H 1) 100 65BD2.-800 800 – – – NZM14-800S 85 50 – – –BD2.-1000 1000 – – – NZM14-1000S 85 50 – – –BD2.-1250 1250 – – – NZM14-1250S 85 50 – – –
Notes 1) current limiting circuit-breaker
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/19
5
For long busbar runs, it may be necessary to calculate the voltage drop.
Factor “a” used in the equation for calculating the voltage drop is dependent on the load distribution.
Temperature characteristic of BD2 systems
115
120
110
105
100
95
90
85
80
75
70
65
Rated current (%)
–5 5 15 25 35 45 55 65
Ambient temperature ˚C(average over 24 hours)
Voltage drop
∆U = Voltage drop (V)I = Load current (A)l = Length (m)a = Load distribution factorR = Ohmic resistance R1 (mΩ/m)X = Inductive reactance X1 (mΩ/m)cos ϕ = Power factor
Load distribution Factor a
Supply at AOne tap-off at B 1
Supply at ATap-off at B, C, D, E 0,5
Supply at ATap-off at B, C 0,25
Supply at ATap-off at B, C, D, E 0,125
Supply at ATap-off at C, D, E, F 0,25
DU = ax 3x Ix lx (Rx cos v + Xx sin v)x 10–3 (V)
AB
AEDCB
CAB
CEADB
A BFEDC
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/20
5
Required detailsThe following details are required for configuring BD2 busbar trunking systems (ho-rizontal installation):• Installation orientation, direction, quantity, type and approximate ratings of pro-
spective loads, cos ϕ• Utilization and rated diversity factor = reduction factor a• Feeding transformers (short-circuit current)• Nature of the installation site (dimensions, construction of the building, trans-
port paths, cellar, etc.)• Routing of supply lines from other power sources• Co-ordination of lighting system with the BD busbar run• Crane operation in installation area
Given are 1. Σ the load 600 kW, cos ϕ = 0.8; Ue = 400 V2. Floor plan and machine layout3. Reduction factor α = 0.64. Incomer cables 2 185 mm2 from distribution board5. Transformer: 1 500 kVA6. Steel frame shed construction7. Suspension height: 3 m8. Installed power on machine lines:
200, 182, 118, 100 kW9. No crane operation10. Edgewise mounting
Operational currentThe operational current is calculated using the following formula:
1) If no data is available about the actual currents (reduction factors) occurringsimultaneously, the following table to IEC/EN 60 439-1 applies:
Determining the operational current
Main busbar run
Machine line200 kW
Machine line182 kW
Machine line118 kW
Machine line100 kW
Installation planIt contains: the position of the busbar trunking system in the building, the position of the PE and the tap-off openings and consequently the installation direction of the tap-off units,the number of components with item numbers and the method and height of sus-pension. The information assists the installer later. If the system is correctly assembled, the entire system will have the same sense of rotation as the three phase motors throughout the entire system. As a result, it will not be necessary to check the direction of rotation of the motors when relocating a machine.
Example: horizontal engineering example
IB = Operational current (A)Ue = Rated operational voltage (V)cos ϕ = Power factorPinst = Installed power (kW)
α = Reduction factor 1)
b = Supply factorb = 1 = Single end feedb = ½ = Double end feed
Centre feeder unit
Number of main circuits Rated diversity factor α
2 and 3 0.9
4 and 5 0.8
6 to 9 inclusive 0.7
10 or more 0.6
IB = Pinstx a x b x 103 (A)3x Uex cos v
IB = 600x 0.6 x 1 x 103 = 650 A3x 400x 0.8
IB = 200x 0.6 x 1 x 103 = 217 A3x 400x 0.8
IB = 182x 0.6 x 1 x 103 = 197 A3x 400x 0.8
IB = 118x 0.6 x 1 x 103 = 128 A3x 400x 0.8
IB = 100x 0.6 x 1 x 103 = 108 A3x 400x 0.8
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/21
5
Installation plan
Parts list
The parts list should contain all the items shown on the installation plan, with type reference, description and quantity.
15 m118 kW
200 kW
182 kW
100 kW
ID 2000
Machine Line IVMachine Line II
Machine Line III
Access Path
36 m
N, L
1, L
2, L
3, P
ETa
p-of
f uni
ts
Machine Line V
6 m
22 m
PE, L3, L2, L1, N, Tap-off units
Feeder unit Trunking units End flange Tap-off units Tap-off units Feeder units Trunking units Trunking units Trunking units Trunking units End flanges
Suspension: at a height of 3 m with ceiling mounted supporting structures. BD2 busbar run I, 800 A, supplies BD2 runs II, III, IV and V via tap-off units and end feeder units, connected by short cable lengths.
ItemNo.(Installation site)
FWLK
Type Description, assignmentDescriptionDénomination
NumberQuant.
Listenpreis List price Prix brut
einzelneach unitaire
zusammentotal
1 BD2A-1000-EE Feeder unit 1
2 BD2A-1-800-SB-3 Trunking units 6
3 BD2-1250-FE End flange 1
4 BD2-AK41/GS1 Tap-off units 3
5 BD2-AK3X/GS00 Tap-off units 1
6 BD2A-400-EE Feeder unit 4
7 BD2A-1-160-SB-3 Trunking units 8
8 BD2A-1-160-SB-1 Trunking units 2
9 BD2A-1-250-SB-3 Trunking units 8
10 BD2A-1-250-SB-1 Trunking units 2
11 BD2-400-FE End flange 4
12 BD2-1250-BB Fixing bracket 5
13 BD2-400-BB Fixing bracket 14
EngineeringBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/22
5
Required details• Number and height of storeys• Ratings and types of load per storey• Utilization and diversity factor = reduction factor α• Feeding transformers (characteristics, position)• Special requirements (degree of protection, fire barriers, etc.)
Given are 1. Six storeys with five apartments each2. 38 kW connected load per apartment3. Ue = 400 V, cos ϕ = 0.84. Reduction factor α = 0.85. Reduction factor β = 0.456. Incoming supply cables 2 240 mm2
7. Protected by NZM14-800S8. Details and site plans required for routing the trunking
Operational currentThe operational current per floor, which also determines the required rated current of the tap-off units, is calculated using the following formula
The operational current per busbar run is:
Table 1 (IEC/EN 60 439-1)
Table 2
Once the system has been selected, in this case BD2A-1-800, the following docu-ments must be completed to place an order:• Installation plan• Parts list• Order from
Parts list
Example: engineering a vertical busbar trunking system
INops = Operational current per storey (A)Ue = Rated operational voltage (V)cos ϕ = Power factorPinst = Sum of inst. power per storey (kW)
α = Reduction factor If α is not specified, the values from table 1 cannot be used. If cos ϕ is not known, this can be set for a block of apartments = 1
β = Utilization and diversity factor for the total number of loads. They vary from region to region. Average values are indicated in table 2.
Number of main circuits Rated diversity factor α
2 and 3 0,9
4 and 5 0,8
6 to 9 inclusive 0,7
10 or more 0,6
INops = Pinstx a x 103 (A)3x Uex cos v
INops = 5x 38x 0.8 x 103 = 274 A3x 400x 0.8
IB = (INopsx b)
IB = 6x 274 Ax 0.45 = 740 A
Item ß
Schools, nursery schools 0.6 to 0.9
Carpenters' and joiners' workshops 0.2 to 0.7
Restaurants, hotels 0.4 to 0.7
Butchers 0.5 to 0.8
Bakeries 0.4 to 0.8
Laundries 0.5 to 0.9
Conference halls 0.6 to 0.8
Small offices 0.5 to 0.7
Large offices 0.4 to 0.8
Department stores, supermarkets 0.7 to 0.9
Metal processing works 0.2 to 0.3
Car factories 0.2 to 0.3
Lighting systems for road tunnels 1,0
Building sites 0.2 to 0.4
ItemNo.
FWLK
Type Description, assignmentDescriptionDénomination
NumberQuant.
Listenpreis List price Prix brut
einzelneach unitaire
zusammentotal
1 BD2A-1000-EE End feeder unit 1
2 BD2A-1-800-WB-2W1,50+BD2-S120-BX1.00-M0.25
Trunking unit,optional length 1.5 m andfire barrier a = 1.0 mCeiling thickness M = 0.25 m
1
3 BD2A-1-800-SB-2 Trunking units, 2.25 m 5
4 BD2A-1-800-WO-1W1,00+BD2-S120-BX0.50-M0.25
Trunking unit,optional length 1.0 m andfire barrier a = 0.5 mCeiling thickness M = 0.25 m
4
5 BD2-1250-FE End flange 1
6 BD2-BWV Vertical retaining elements 4
7 BD2-1250-BB Fixing bracket 5
8 BD2-BD Spacer bracket 5
9 BD2-AK51/GSTZ2 Tap-off units withLow-voltage h.b.c. fuse switch-disconnector
6
Alternatively:
2 – 4 BD2A-1-800-SB-3+BD2-S120-BX1.00-M0.25
Trunking units, 3.25 mwith fire barrier a = 1.0 mCeiling thickness M = 0.25 m
5
Fire barriersBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/23
5
a Position of fire barrier in mCentre of fire barrier is always at centre of fire ceiling
b Dimension for spacer bracket in mc Dimension for retaining element in m
• Second retaining element at approx. 5 m height (always near the terminal)• Third retaining element at approx. 10 m height• Fourth retaining element at approx. 15 m height
M Ceiling thickness in m
NotesThe fixing points for all fixing brackets, retaining elements and spacer brackets must be specified in the installation plan.Item number, a parts list page 5/22.
Installation plan
MM
a
c
a
b
3.25
m
3.10
m
Fire barriersBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/24
5
Fire barriers
To ensure fire protection to S90 or S120, the following points must be observed when engineering and installing trunking and junction units with fire barriers:• The centre of the fire barrier in the trunking unit must be positioned in the centre
of the fire wall or ceiling.Exception: With branch/junction units, this may not be possible due to insuf-ficient clearance from the wall or ceiling, i.e. the centre of the fire barrier may not coincide with the centre of the fire wall or ceiling. In such cases, PROMA-TECT-H(L) panels are added to achieve the actually required wall or ceiling thick-ness.
• The following information must be provided: For BX*, BY* and BZ* trunking units, position of the centre of the fire barrier in the trunking unit (or the centre of the fire wall or ceiling for branch/junction units with insufficient clearance from the wall or ceiling); the desired fire resistance rating S90 or S120; and the thickness M* of the wall or ceiling.
• There are no tap-off points in the area covered by the fire barrier.• The trunking units must be installed by an approved fire protection installation
specialist.
NotesFor BX* and BY*, replace the asterisk in the type reference by the required dimen-sion in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.For BZ*, replace the asterisk in the type reference by the required dimension in metres from the outside edge of limb X to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
BX*, BY*, BZ*
M*
BX*, BY*, BZ*
M*
Centre line of fire barrier
Positioning in fire wall Positioning in fire ceiling
Fire barriersBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/25
5
Type: BD2.-...-S(W).-. +BD2-S90(S120)-BX*-M*
Position of fire barrier on a straight trunking unit
Fire resistance rating S90+BD2-S90-BX*-M*
Wall thickness M f 150 mm
L (L min. = 370+M) BX* min. = 185+M/2 BX*max. = L-BX* min.
620 (min.) 310 310
– – –
– – –
3250 (max.) 310 2940
Fire resistance rating S120+BD2-S120-BX*-M*
Wall thickness 150 mm F M < 250 mm
L (L min. = 570+M) BX* min. = 285+M/2 BX*max. = L-BX* min.
720 (min.) 360 360
– – –
– – –
3250 (max.) 360 2890
Wall thickness M f 250 mm
L (L min. = 370+M) BX* min. = 185+M/2 BX*max. = L-BX* min.
620 (min.) 310 310
– – –
– – –
3250 (max.) 310 2940
L
BX*
250
Mf
150
M =
150
– 2
50
100
100
Mf
250
Fire barriersBD2 System (160 A - 1250 A)
Siemens LV 70 · 20045/26
5
Position of fire barrier on branch/junction units
The minimum dimensions applicable for positioning fire barriers on the limbs of branch/junction units
Elbow, Type: BD2.-...-LR(L)-X* (Y*), +BD2-S90(S120)-BX*(BY*)-M*
differ, depending on the routing of the trunking and the distance from the fire wall to the inside edge of the trunking unit.
Knee, Type: BD2.-...-LV(H)-X* (Y*), +BD2-S90(S120)-BX*(BY*)-M*
Fire resistance rating S90+BD2-S90-BX*(BY*)-M*
Wall thickness 150 mm F M < 150 mm (clearance from wall/inside corner A f 200 mm)
Branch/junction units LL, LR
X*(Y*)(X*(Y*) min. = 185+M+A+170)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-170-A-M/2
760 (min.) 310 310
– – –
1250 (max.) 310 800
Branch/junction units LV, LH 400 A
X*(Y*)(X*(Y*) min. = 185+M+A+70)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-70-A-M/2
660 (min.) 310 310
– – –
1250 (max.) 310 900
Branch/junction units LV, LH 1000, 1250 A
X*(Y*)(X*(Y*) min. = 185+M+A+130)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-130-A-M/2
720 (min.) 310 310
– – –
1250 (max.) 310 840
X* (Y*)
170
Y* (X*)BY* (BX*)
BY*
(BX*
)
Y* (X
*)
X* (Y*)
c 160 A – 400 A 500 A – 1250 A
C 70 130
150F
M <
250
Af
200
Fire barriersBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/27
5
Fire resistance rating S90+BD2-S90-BX*(BY*)-M*
Wall thickness 150 mm M < 250 mm(clearance from wall to inside corner 30 mm A < 200 mm)
Branch/junction units LL, LR
X*(Y*)(X*(Y*) min. = 285+M+A+170)
BX*(BY*) min. = 285+M/2
BX*(BY*) max. = X*(Y*)-170-A-M/2
640 (min.) 360 360
– – –
1250 (max.) 360 970
Branch/junction units LV, LH 400 A
X*(Y*)(X*(Y*) min. = 285+M+A+70)
BX*(BY*) min. = 285+M/2
BX*(BY*) max. = X*(Y*)-70-A-M/2
540 (min.) 360 360
– – –
1250 (max.) 360 1070
Branch/junction units LV, LH 1000, 1250 A
X*(Y*)(X*(Y*) min. = 285+M+A+130)
BX*(BY*) min. = 285+M/2
BX*(BY*) max. = X*(Y*)-130-A-M/2
600 (min.) 360 360
– – –
1250 (max.) 360 1010
Fire resistance rating S90+BD2-S90-BX*(BY*)-M*
Wall thickness M f 250 mm (clearance from wall/inside corner A f 30 mm)
Branch/junction units LL, LR
X*(Y*)(X*(Y*) min. = 185+M+A+170)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-170-A-M/2
640 (min.) 310 310
– – –
1250 (max.) 310 920
Branch/junction units LV, LH 400 A
X*(Y*)(X*(Y*) min. = 185+M+A+70)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-70-A-M/2
540 (min.) 310 310
– – –
1250 (max.) 310 1020
Branch/junction units LV, LH 1000, 1250 A
X*(Y*)(X*(Y*) min. = 185+M+A+130)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-130-A-M/2
600 (min.) 310 310
– – –
1250 (max.) 310 960
Notes: with other fire barrier configurations, please contact your local Siemens sales office or select using the Busbar Select design software.
100
M =
150
– 2
50
A =
30
– 19
0Af
30
Mf
250
Fire barriers
Siemens LV 70 · 20045/28
BD2 System (160 A - 1250 A)
5
Fire resistance rating S120+BD2-S120-BX*(BY*)-M*
Wall thickness 150 mm M < 250 mm (clearance from wall/inside corner A 200 mm)
Branch/junction units LL, LR
X*(Y*)(X*(Y*) min. = 285+M+A+170)
BX*(BY*) min. = 285+M/2
BX*(BY*) max. = X*(Y*)-170-A-M/2
810 (min.) 360 360
– – –
1250 (max.) 360 800
Branch/junction units LV, LH 400 A
X*(Y*)(X*(Y*) min. = 285+M+A+70)
BX*(BY*) min. = 285+M/2
BX*(BY*) max. = X*(Y*)-70-A-M/2
710 (min.) 360 360
– – –
1250 (max.) 360 900
Branch/junction units LV, LH 1000, 1250 A
X*(Y*)(X*(Y*) min. = 285+M+A+130)
BX*(BY*) min. = 285+M/2
BX*(BY*) max. = X*(Y*)-130-A-M/2
770 (min.) 360 360
– – –
1250 (max.) 360 840
Fire resistance rating S120+BD2-S120-BX*(BY*)-M*
Wall thickness M f 250 mm (clearance from wall/inside corner A f 200 mm)
Branch/junction units LL, LR
X*(Y*)(X*(Y*) min. = 185+M+A+170)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-170-A-M/2
810 (min.) 310 310
– – –
1250 (max.) 310 750
Branch/junction units LV, LH 400 A
X*(Y*)(X*(Y*) min. = 185+M+A+70)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-70-A-M/2
710 (min.) 310 310
– – –
1250 (max.) 310 850
Branch/junction units LV, LH 1000, 1250 A
X*(Y*)(X*(Y*) min. = 185+M+A+130)
BX*(BY*) min. = 185+M/2
BX*(BY*) max. = X*(Y*)-130-A-M/2
770 (min.) 310 310
– – –
1250 (max.) 310 790
Notes: with other fire barrier configurations, please contact your local Siemens sales office or select using the Busbar Select design software.
100
100
M =
150
–250
Af
200
Mf
250
Af
200
Fire barriersBD2 System (160 A - 1250 A)
Siemens LV 70 · 2004 5/29
5
Installing trunking units with fire barriers
Positioning in fire ceiling
Positioning in fire wall
Recommended minimum dimensions of ceiling or wall cut-out
Systemcurrent up to
a2)
mmbmm
400 A 90 200
1250 A 150 200
Trunking units with cmm
Tap-off unitBD2-AK1...BD2-AK02..., BD2-AK2...BD2-AK03..., BD2-AK3...
125
Tap-off unitBD2-AK4...BD2-AK5...
200
BD2-BWV or BD2-BDV(with or without tap-off unit)
200
BD2.-...-EE(with or without tap-off unit)
200
2) For Z units depending on the lengths X*, Y*.
For installing trunking units with fire barriers, the following points must be observed in addition to correct positioning:• Horizontally mounted busbar runs must be supported by a fixing bracket fitted ap-
prox. 500 mm before and after the structural element they pass through.• The space surrounding the busbar trunking unit within the structural element it
passes through must be packed with mineral-based mortar or ZZ fire barrier sealant TS90.
• The gaps between PROMATECT-H(L) panels, the busbar trunking unit and the structural element must be sealed with ZZ fire barrier sealant TS90 (included as standard if panels are specified).
• The installation must be carried out to pertinent building regulations.• ZZ fire barrier sealant TS90 is available from:
Diederich Industrievertretung (Brandschutztechnik), Cologne(Tel.: +49 221 966520; Fax: +49 221 966522).
Notes The mortar or ZZ fire barrier sealant TS90 must conform to the applicable regulations for establishing fire resistance rating or the construction of the wallor ceiling (e.g. DIN 1045 and DIN 1053 Part 1)
28–82
mm
c
b
a
a
b
250 mm
100
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 20045/30
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 1 mL1, L2, L3, M N, M PE
Rated current Length Tap-off points Type PriceSeePrice List
Number Clearance Article no.IeA m m
Standard lengthsTap-off points on both sidesWith clamp terminal
160 3.25 6 1 BD2A-1-160-SB-3255987
2.25 4 1 BD2A-1-160-SB-2255986
1.25 2 1 BD2A-1-160-SB-1255985
250 3.25 6 1 BD2A-1-250-SB-3255990
2.25 4 1 BD2A-1-250-SB-2255989
1.25 2 1 BD2A-1-250-SB-1255988
315 3.25 6 1 BD2A-1-315-SB-3255993
2.25 4 1 BD2A-1-315-SB-2255992
1.25 2 1 BD2A-1-315-SB-1255991
400 3.25 6 1 BD2A-1-400-SB-3255996
2.25 4 1 BD2A-1-400-SB-2255995
1.25 2 1 BD2A-1-400-SB-1255994
500 3.25 6 1 BD2A-1-500-SB-3256002
2.25 4 1 BD2A-1-500-SB-2256001
1.25 2 1 BD2A-1-500-SB-1256000
630 3.25 6 1 BD2A-1-630-SB-3256008
2.25 4 1 BD2A-1-630-SB-2256007
1.25 2 1 BD2A-1-630-SB-1256006
800 3.25 6 1 BD2A-1-800-SB-3256014
2.25 4 1 BD2A-1-800-SB-2256013
1.25 2 1 BD2A-1-800-SB-1256012
1000 3.25 6 1 BD2A-1-1000-SB-3256020
2.25 4 1 BD2A-1-1000-SB-2256019
1.25 2 1 BD2A-1-1000-SB-1256018
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 2004 5/31
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 0.5 mL1, L2, L3, N, M PE
Tap-off point clearance 0.5 mL1, L2, L3, N, PE
Tap-off points Type PriceSeePrice List
Type PriceSeePrice List
NotesNumber Clearance Article no. Article no. PS*
m
12 0.5 BD2A-2-160-SB-3261410
BD2A-3-160-SB-3261480
1 unit Special colours available on request
8 0.5 BD2A-2-160-SB-2260958
BD2A-3-160-SB-2261479
4 0.5 BD2A-2-160-SB-1260957
BD2A-3-160-SB-1261478
12 0.5 BD2A-2-250-SB-3261413
BD2A-3-250-SB-3261483
8 0.5 BD2A-2-250-SB-2261412
BD2A-3-250-SB-2261482
4 0.5 BD2A-2-250-SB-1261411
BD2A-3-250-SB-1261481
12 0.5 BD2A-2-315-SB-3261416
BD2A-3-315-SB-3261486
8 0.5 BD2A-2-315-SB-2261415
BD2A-3-315-SB-2261485
4 0.5 BD2A-2-315-SB-1261414
BD2A-3-315-SB-1261484
12 0.5 BD2A-2-400-SB-3261419
BD2A-3-400-SB-3261489
8 0.5 BD2A-2-400-SB-2261418
BD2A-3-400-SB-2261488
4 0.5 BD2A-2-400-SB-1261417
BD2A-3-400-SB-1261487
12 0.5 BD2A-2-500-SB-3261425
BD2A-3-500-SB-3261495
8 0.5 BD2A-2-500-SB-2261424
BD2A-3-500-SB-2261494
4 0.5 BD2A-2-500-SB-1261423
BD2A-3-500-SB-1261493
12 0.5 BD2A-2-630-SB-3261431
BD2A-3-630-SB-3261501
8 0.5 BD2A-2-630-SB-2261430
BD2A-3-630-SB-2261500
4 0.5 BD2A-2-630-SB-1261429
BD2A-3-630-SB-1261499
12 0.5 BD2A-2-800-SB-3261437
BD2A-3-800-SB-3261507
8 0.5 BD2A-2-800-SB-2261436
BD2A-3-800-SB-2261506
4 0.5 BD2A-2-800-SB-1261435
BD2A-3-800-SB-1261505
12 0.5 BD2A-2-1000-SB-3261443
BD2A-3-1000-SB-3261513
8 0.5 BD2A-2-1000-SB-2261442
BD2A-3-1000-SB-2261512
4 0.5 BD2A-2-1000-SB-1261441
BD2A-3-1000-SB-1261511
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 20045/32
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 1 mL1, L2, L3, M N, M PE
Rated current Length Tap-off points Type PriceSeePrice List
Number Clearance Article no.IeA m m
Standard lengthsTap-off points on both sidesWith clamp terminal
160 3.25 6 1 BD2C-1-160-SB-3261550
2.25 4 1 BD2C-1-160-SB-2261549
1.25 2 1 BD2C-1-160-SB-1261548
250 3.25 6 1 BD2C-1-250-SB-3261553
2.25 4 1 BD2C-1-250-SB-2261552
1.25 2 1 BD2C-1-250-SB-1261551
315 3.25 6 1 BD2C-1-315-SB-3261556
2.25 4 1 BD2C-1-315-SB-2261555
1.25 2 1 BD2C-1-315-SB-1261554
400 3.25 6 1 BD2C-1-400-SB-3261559
2.25 4 1 BD2C-1-400-SB-2261558
1.25 2 1 BD2C-1-400-SB-1261557
500 3.25 6 1 BD2C-1-500-SB-3261565
2.25 4 1 BD2C-1-500-SB-2261564
1.25 2 1 BD2C-1-500-SB-1261563
630 3.25 6 1 BD2C-1-630-SB-3261571
2.25 4 1 BD2C-1-630-SB-2261570
1.25 2 1 BD2C-1-630-SB-1261569
800 3.25 6 1 BD2C-1-800-SB-3261577
2.25 4 1 BD2C-1-800-SB-2261576
1.25 2 1 BD2C-1-800-SB-1261575
1000 3.25 6 1 BD2C-1-1000-SB-3261583
2.25 4 1 BD2C-1-1000-SB-2261582
1.25 2 1 BD2C-1-1000-SB-1261581
1250 3.25 6 1 BD2C-1-1250-SB-3261589
2.25 4 1 BD2C-1-1250-SB-2261588
1.25 2 1 BD2C-1-1250-SB-1261587
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX* , replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 2004 5/33
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 0.5 mL1, L2, L3, N, M PE
Tap-off point clearance 0.5 mL1, L2, L3, N, PE
Tap-off points Type PriceSeePrice List
Type PriceSeePrice List
NotesNumber Clearance Article no. Article no. PS*
m
12 0.5 BD2C-2-160-SB-3261631
BD2C-3-160-SB-3261712
1 unit Special colours available on request
8 0.5 BD2C-2-160-SB-2261630
BD2C-3-160-SB-2261711
4 0.5 BD2C-2-160-SB-1261629
BD2C-3-160-SB-1261710
12 0.5 BD2C-2-250-SB-3261634
BD2C-3-250-SB-3261715
8 0.5 BD2C-2-250-SB-2261633
BD2C-3-250-SB-2261714
4 0.5 BD2C-2-250-SB-1261632
BD2C-3-250-SB-1261713
12 0.5 BD2C-2-315-SB-3261637
BD2C-3-315-SB-3261718
8 0.5 BD2C-2-315-SB-2261636
BD2C-3-315-SB-2261717
4 0.5 BD2C-2-315-SB-1261635
BD2C-3-315-SB-1261716
12 0.5 BD2C-2-400-SB-3261640
BD2C-3-400-SB-3261721
8 0.5 BD2C-2-400-SB-2261639
BD2C-3-400-SB-2261720
4 0.5 BD2C-2-400-SB-1261638
BD2C-3-400-SB-1261719
12 0.5 BD2C-2-500-SB-3261646
BD2C-3-500-SB-3261727
8 0.5 BD2C-2-500-SB-2261645
BD2C-3-500-SB-2261726
4 0.5 BD2C-2-500-SB-1261644
BD2C-3-500-SB-1261725
12 0.5 BD2C-2-630-SB-3261652
BD2C-3-630-SB-3261733
8 0.5 BD2C-2-630-SB-2261651
BD2C-3-630-SB-2261732
4 0.5 BD2C-2-630-SB-1261650
BD2C-3-630-SB-1261731
12 0.5 BD2C-2-800-SB-3261658
BD2C-3-800-SB-3261739
8 0.5 BD2C-2-800-SB-2261657
BD2C-3-800-SB-2261738
4 0.5 BD2C-2-800-SB-1261656
BD2C-3-800-SB-1261737
12 0.5 BD2C-2-1000-SB-3261664
BD2C-3-1000-SB-3261745
8 0.5 BD2C-2-1000-SB-2261663
BD2C-3-1000-SB-2261744
4 0.5 BD2C-2-1000-SB-1261662
BD2C-3-1000-SB-1261743
12 0.5 BD2C-2-1250-SB-3261670
BD2C-3-1250-SB-3261751
8 0.5 BD2C-2-1250-SB-2261669
BD2C-3-1250-SB-2261750
4 0.5 BD2C-2-1250-SB-1261668
BD2C-3-1250-SB-1261749
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 20045/34
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 1 mL1, L2, L3, M N, M PE
Rated current Length Tap-off points Type PriceSeePrice List
Number Clearance Article no.IeA m m
Optional lengthsTap-off points on both sidesWith clamp terminal
160 2.26 – 3.24 4 – 6 1 BD2A-1-160-WB-3W*256024
1.26 – 2.24 2 – 4 1 BD2A-1-160-WB-2W*256025
250 2.26 – 3.24 4 – 6 1 BD2A-1-250-WB-3W*256026
1.26 – 2.24 2 – 4 1 BD2A-1-250-WB-2W*256027
315 2.26 – 3.24 4 – 6 1 BD2A-1-315-WB-3W*256028
1.26 – 2.24 2 – 4 1 BD2A-1-315-WB-2W*256029
400 2.26 – 3.24 4 – 6 1 BD2A-1-400-WB-3W*256030
1.26 – 2.24 2 – 4 1 BD2A-1-400-WB-2W*256031
500 2.26 – 3.24 4 – 6 1 BD2A-1-500-WB-3W*256032
1.26 – 2.24 2 – 4 1 BD2A-1-500-WB-2W*256033
630 2.26 – 3.24 4 – 6 1 BD2A-1-630-WB-3W*256034
1.26 – 2.24 2 – 4 1 BD2A-1-630-WB-2W*256035
800 2.26 – 3.24 4 – 6 1 BD2A-1-800-WB-3W*256036
1.26 – 2.24 2 – 4 1 BD2A-1-800-WB-2W*256037
1000 2.26 – 3.24 4 – 6 1 BD2A-1-1000-WB-3W*256038
1.26 – 2.24 2 – 4 1 BD2A-1-1000-WB-2W*256039
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 2004 5/35
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 0.5 mL1, L2, L3, N, M PE
Tap-off point clearance 0.5 mL1, L2, L3, N, PE
Tap-off points Type PriceSeePrice List
Type PriceSeePrice List
NotesNumber Clearance Article no. Article no. PS1)
m
8 – 12 0.5 BD2A-2-160-WB-3W*261447
BD2A-3-160-WB-3W*261517
1 unit Special colours available on requestOptional length(a page 5/17)For W*, replace the asterisk in the type reference by the required dimension in metres between the centre of one clamp terminal to the centre of the next.
4 – 8 0.5 BD2A-2-160-WB-2W*261448
BD2A-3-160-WB-2W*261518
8 – 12 0.5 BD2A-2-250-WB-3W*261449
BD2A-3-250-WB-3W*261519
4 – 8 0.5 BD2A-2-250-WB-2W*261450
BD2A-3-250-WB-2W*261520
8 – 12 0.5 BD2A-2-315-WB-3W*261451
BD2A-3-315-WB-3W*261521
4 – 8 0.5 BD2A-2-315-WB-2W*261452
BD2A-3-315-WB-2W*261522
8 – 12 0.5 BD2A-2-400-WB-3W*261453
BD2A-3-400-WB-3W*261523
4 – 8 0.5 BD2A-2-400-WB-2W*261454
BD2A-3-400-WB-2W*261524
8 – 12 0.5 BD2A-2-500-WB-3W*261455
BD2A-3-500-WB-3W*261525
4 – 8 0.5 BD2A-2-500-WB-2W*261456
BD2A-3-500-WB-2W*261526
8 – 12 0.5 BD2A-2-630-WB-3W*261457
BD2A-3-630-WB-3W*261527
4 – 8 0.5 BD2A-2-630-WB-2W*261458
BD2A-3-630-WB-2W*261528
8 – 12 0.5 BD2A-2-800-WB-3W*261459
BD2A-3-800-WB-3W*261529
4 – 8 0.5 BD2A-2-800-WB-2W*261460
BD2A-3-800-WB-2W*261530
8 – 12 0.5 BD2A-2-1000-WB-3W*261461
BD2A-3-1000-WB-3W*261531
4 – 8 0.5 BD2A-2-1000-WB-2W*261462
BD2A-3-1000-WB-2W*261532
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 20045/36
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 1 mL1, L2, L3, M N, M PE
Rated current Length Tap-off points Type PriceSeePrice List
Number Clearance Article no.IeA m m
Optional lengthsTap-off points on both sidesWith clamp terminal
160 2.26 – 3.24 4 – 6 1 BD2C-1-160-WB-3W*261593
1.26 – 2.24 2 – 4 1 BD2C-1-160-WB-2W*261594
250 2.26 – 3.24 4 – 6 1 BD2C-1-250-WB-3W*261595
1.26 – 2.24 2 – 4 1 BD2C-1-250-WB-2W*261596
315 2.26 – 3.24 4 – 6 1 BD2C-1-315-WB-3W*261597
1.26 – 2.24 2 – 4 1 BD2C-1-315-WB-2W*261598
400 2.26 – 3.24 4 – 6 1 BD2C-1-400-WB-3W*261599
1.26 – 2.24 2 – 4 1 BD2C-1-400-WB-2W*261600
500 2.26 – 3.24 4 – 6 1 BD2C-1-500-WB-3W*261601
1.26 – 2.24 2 – 4 1 BD2C-1-500-WB-2W*261602
630 2.26 – 3.24 4 – 6 1 BD2C-1-630-WB-3W*261603
1.26 – 2.24 2 – 4 1 BD2C-1-630-WB-2W*261604
800 2.26 – 3.24 4 – 6 1 BD2C-1-800-WB-3W*261605
1.26 – 2.24 2 – 4 1 BD2C-1-800-WB-2W*261606
1000 2.26 – 3.24 4 – 6 1 BD2C-1-1000-WB-3W*261607
1.26 – 2.24 2 – 4 1 BD2C-1-1000-WB-2W*261608
1250 2.26 – 3.24 4 – 6 1 BD2C-1-1250-WB-3W*261609
1.26 – 2.24 2 – 4 1 BD2C-1-1250-WB-2W*261610
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 2004 5/37
BD2 System (160 A - 1250 A)
5
Tap-off point clearance 0.5 mL1, L2, L3, N, M PE
Tap-off point clearance 0.5 mL1, L2, L3, N, PE
Tap-off points Type PriceSeePrice List
Type PriceSeePrice List
NotesNumber Clearance Article no. Article no. PS1)
m
8 – 12 0.5 BD2C-2-160-WB-3W*261674
BD2C-3-160-WB-3W*261755
1 unit Special colours available on requestOptional length(a page 5/17)For W*, replace the asterisk in the type reference by the required dimension in metres between the centre of one clamp terminal to the centre of the next.
4 – 8 0.5 BD2C-2-160-WB-2W*261675
BD2C-3-160-WB-2W*261756
8 – 12 0.5 BD2C-2-250-WB-3W*261676
BD2C-3-250-WB-3W*261757
4 – 8 0.5 BD2C-2-250-WB-2W*261677
BD2C-3-250-WB-2W*261758
8 – 12 0.5 BD2C-2-315-WB-3W*261678
BD2C-3-315-WB-3W*261759
4 – 8 0.5 BD2C-2-315-WB-2W*261679
BD2C-3-315-WB-2W*261760
8 – 12 0.5 BD2C-2-400-WB-3W*261680
BD2C-3-400-WB-3W*261761
4 – 8 0.5 BD2C-2-400-WB-2W*261681
BD2C-3-400-WB-2W*261762
8 – 12 0.5 BD2C-2-500-WB-3W*261682
BD2C-3-500-WB-3W*261763
4 – 8 0.5 BD2C-2-500-WB-2W*261683
BD2C-3-500-WB-2W*261764
8 – 12 0.5 BD2C-2-630-WB-3W*261684
BD2C-3-630-WB-3W*261765
4 – 8 0.5 BD2C-2-630-WB-2W*261685
BD2C-3-630-WB-2W*261766
8 – 12 0.5 BD2C-2-800-WB-3W*261686
BD2C-3-800-WB-3W*261767
4 – 8 0.5 BD2C-2-800-WB-2W*261687
BD2C-3-800-WB-2W*261768
8 – 12 0.5 BD2C-2-1000-WB-3W*261688
BD2C-3-1000-WB-3W*261769
4 – 8 0.5 BD2C-2-1000-WB-2W*261689
BD2C-3-1000-WB-2W*261770
8 – 12 0.5 BD2C-2-1250-WB-3W*261690
BD2C-3-1250-WB-3W*261771
4 – 8 0.5 BD2C-2-1250-WB-2W*261691
BD2C-3-1250-WB-2W*261772
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 20045/38
BD2 System (160 A - 1250 A)
5
L1, L2, L3, M N, M PERated current Length Type Price
SeePrice List
Article no.IeA m
Standard lengthsWithout tap-off pointsWith clamp terminal
400 3.25 BD2A-1-400-SO-3255999
2.25 BD2A-1-400-SO-2255998
1.25 BD2A-1-400-SO-1255997
500 3.25 BD2A-1-500-SO-3256005
2.25 BD2A-1-500-SO-2256004
1.25 BD2A-1-500-SO-1256003
630 3.25 BD2A-1-630-SO-3256011
2.25 BD2A-1-630-SO-2256010
1.25 BD2A-1-630-SO-1256009
800 3.25 BD2A-1-800-SO-3256017
2.25 BD2A-1-800-SO-2256016
1.25 BD2A-1-800-SO-1256015
1000 3.25 BD2A-1-1000-SO-3256023
2.25 BD2A-1-1000-SO-2256022
1.25 BD2A-1-1000-SO-1256021
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 2004 5/39
BD2 System (160 A - 1250 A)
5
L1, L2, L3, N, M PE L1, L2, L3, N, PEType Price
SeePrice List
Type PriceSeePrice List
NotesArticle no. Article no. PS*
BD2A-2-400-SO-3261422
BD2A-3-400-SO-3261492
1 unit Special colours available on request
BD2A-2-400-SO-2261421
BD2A-3-400-SO-2261491
BD2A-2-400-SO-1261420
BD2A-3-400-SO-1261490
BD2A-2-500-SO-3261428
BD2A-3-500-SO-3261498
BD2A-2-500-SO-2261427
BD2A-3-500-SO-2261497
BD2A-2-500-SO-1261426
BD2A-3-500-SO-1261496
BD2A-2-630-SO-3261434
BD2A-3-630-SO-3261504
BD2A-2-630-SO-2261433
BD2A-3-630-SO-2261503
BD2A-2-630-SO-1261432
BD2A-3-630-SO-1261502
BD2A-2-800-SO-3261440
BD2A-3-800-SO-3261510
BD2A-2-800-SO-2261439
BD2A-3-800-SO-2261509
BD2A-2-800-SO-1261438
BD2A-3-800-SO-1261508
BD2A-2-1000-SO-3261446
BD2A-3-1000-SO-3261516
BD2A-2-1000-SO-2261445
BD2A-3-1000-SO-2261515
BD2A-2-1000-SO-1261444
BD2A-3-1000-SO-1261514
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 20045/40
BD2 System (160 A - 1250 A)
5
L1, L2, L3, M N, M PERated current Length Type Price
SeePrice List
Article no.IeA m
Standard lengthsWithout tap-off pointsWith clamp terminal
400 3.25 BD2C-1-400-SO-3261562
2.25 BD2C-1-400-SO-2261561
1.25 BD2C-1-400-SO-1261560
500 3.25 BD2C-1-500-SO-3261568
2.25 BD2C-1-500-SO-2261567
1.25 BD2C-1-500-SO-1261566
630 3.25 BD2C-1-630-SO-3261574
2.25 BD2C-1-630-SO-2261573
1.25 BD2C-1-630-SO-1261572
800 3.25 BD2C-1-800-SO-3261580
2.25 BD2C-1-800-SO-2261579
1.25 BD2C-1-800-SO-1261578
1000 3.25 BD2C-1-1000-SO-3261586
2.25 BD2C-1-1000-SO-2261585
1.25 BD2C-1-1000-SO-1261584
1250 3.25 BD2C-1-1250-SO-3261592
2.25 BD2C-1-1250-SO-2261591
1.25 BD2C-1-1250-SO-1261590
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 2004 5/41
BD2 System (160 A - 1250 A)
5
L1, L2, L3, N, M PE L1, L2, L3, N, PEType Price
SeePrice List
Type PriceSeePrice List
NotesArticle no. Article no. PS*
BD2C-2-400-SO-3261643
BD2C-3-400-SO-3261724
1 unit Special colours available on request
BD2C-2-400-SO-2261642
BD2C-3-400-SO-2261723
BD2C-2-400-SO-1261641
BD2C-3-400-SO-1261722
BD2C-2-500-SO-3261649
BD2C-3-500-SO-3261730
BD2C-2-500-SO-2261648
BD2C-3-500-SO-2261729
BD2C-2-500-SO-1261647
BD2C-3-500-SO-1261728
BD2C-2-630-SO-3261655
BD2C-3-630-SO-3261736
BD2C-2-630-SO-2261654
BD2C-3-630-SO-2261735
BD2C-2-630-SO-1261653
BD2C-3-630-SO-1261734
BD2C-2-800-SO-3261661
BD2C-3-800-SO-3261742
BD2C-2-800-SO-2261660
BD2C-3-800-SO-2261741
BD2C-2-800-SO-1261659
BD2C-3-800-SO-1261740
BD2C-2-1000-SO-3261667
BD2C-3-1000-SO-3261748
BD2C-2-1000-SO-2261666
BD2C-3-1000-SO-2261747
BD2C-2-1000-SO-1261665
BD2C-3-1000-SO-1261746
BD2C-2-1250-SO-3261673
BD2C-3-1250-SO-3261754
BD2C-2-1250-SO-2261672
BD2C-3-1250-SO-2261753
BD2C-2-1250-SO-1261671
BD2C-3-1250-SO-1261752
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 20045/42
BD2 System (160 A - 1250 A)
5
L1, L2, L3, M N, M PERated current Length Type Price
SeePrice List
Article no.IeA m
Optional lengthsWithout tap-off pointsWith clamp terminal
400 2.26 – 3.24 BD2A-1-400-WO-3W*256040
1.26 – 2.24 BD2A-1-400-WO-2W*256041
0.50 – 1.24 BD2A-1-400-WO-1W*256042
500 2.26 – 3.24 BD2A-1-500-WO-3W*256043
1.26 – 2.24 BD2A-1-500-WO-2W*256044
0.50 – 1.24 BD2A-1-500-WO-1W*256045
630 2.26 – 3.24 BD2A-1-630-WO-3W*256046
1.26 – 2.24 BD2A-1-630-WO-2W*256047
0.50 – 1.24 BD2A-1-630-WO-1W*256048
800 2.26 – 3.24 BD2A-1-800-WO-3W*256049
1.26 – 2.24 BD2A-1-800-WO-2W*256050
0.50 – 1.24 BD2A-1-800-WO-1W*256051
1000 2.26 – 3.24 BD2A-1-1000-WO-3W*256052
1.26 – 2.24 BD2A-1-1000-WO-2W*256053
0.50 – 1.24 BD2A-1-1000-WO-1W*256054
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Unit, Aluminium
Siemens LV 70 · 2004 5/43
BD2 System (160 A - 1250 A)
5
L1, L2, L3, N, M PE L1, L2, L3, N, PEType Price
SeePrice List
Type PriceSeePrice List
NotesArticle no. Article no. PS1)
BD2A-2-400-WO-3W*261463
BD2A-3-400-WO-3W*261533
1 unit Special colours available on requestOptional length(a page 5/17)For W*, replace the asterisk in the type reference by the equired dimension in metres between the centre of one clamp terminal to the centre of the next.
BD2A-2-400-WO-2W*261464
BD2A-3-400-WO-2W*261534
BD2A-2-400-WO-1W*261465
BD2A-3-400-WO-1W*261535
BD2A-2-500-WO-3W*261466
BD2A-3-500-WO-3W*261536
BD2A-2-500-WO-2W*261467
BD2A-3-500-WO-2W*261537
BD2A-2-500-WO-1W*261468
BD2A-3-500-WO-1W*261538
BD2A-2-630-WO-3W*261469
BD2A-3-630-WO-3W*261539
BD2A-2-630-WO-2W*261470
BD2A-3-630-WO-2W*261540
BD2A-2-630-WO-1W*261471
BD2A-3-630-WO-1W*261541
BD2A-2-800-WO-3W*261472
BD2A-3-800-WO-3W*261542
BD2A-2-800-WO-2W*261473
BD2A-3-800-WO-2W*261543
BD2A-2-800-WO-1W*261474
BD2A-3-800-WO-1W*261544
BD2A-2-1000-WO-3W*261475
BD2A-3-1000-WO-3W*261545
BD2A-2-1000-WO-2W*261476
BD2A-3-1000-WO-2W*261546
BD2A-2-1000-WO-1W*261477
BD2A-3-1000-WO-1W*261547
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 20045/44
BD2 System (160 A - 1250 A)
5
L1, L2, L3, M N, M PERated current Length Type Price
SeePrice List
Article no.IeA m
Optional lengthsWithout tap-off pointsWith clamp terminal
400 2.26 – 3.24 BD2C-1-400-WO-3W*261611
1.26 – 2.24 BD2C-1-400-WO-2W*261612
0.50 – 1.24 BD2C-1-400-WO-1W*261613
500 2.26 – 3.24 BD2C-1-500-WO-3W*261614
1.26 – 2.24 BD2C-1-500-WO-2W*261615
0.50 – 1.24 BD2C-1-500-WO-1W*261616
630 2.26 – 3.24 BD2C-1-630-WO-3W*261617
1.26 – 2.24 BD2C-1-630-WO-2W*261618
0.50 – 1.24 BD2C-1-630-WO-1W*261619
800 2.26 – 3.24 BD2C-1-800-WO-3W*261620
1.26 – 2.24 BD2C-1-800-WO-2W*261621
0.50 – 1.24 BD2C-1-800-WO-1W*261622
1000 2.26 – 3.24 BD2C-1-1000-WO-3W*261623
1.26 – 2.24 BD2C-1-1000-WO-2W*261624
0.50 – 1.24 BD2C-1-1000-WO-1W*261625
1250 2.26 – 3.24 BD2C-1-1250-WO-3W*261626
1.26 – 2.24 BD2C-1-1250-WO-2W*261627
0.50 – 1.24 BD2C-1-1250-WO-1W*261628
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataStraight Trunking Units, Copper
Siemens LV 70 · 2004 5/45
BD2 System (160 A - 1250 A)
5
L1, L2, L3, N, M PE L1, L2, L3, N, PEType Price
SeePrice List
Type PriceSeePrice List
NotesArticle no. Article no. PS1)
BD2C-2-400-WO-3W*261692
BD2C-3-400-WO-3W*261773
1 unit Special colours available on requestOptional length(a page 5/17)For W*, replace the asterisk in the type reference by the required dimension in metres between the centre of one clamp terminal to the centre of the next.
BD2C-2-400-WO-2W*261693
BD2C-3-400-WO-2W*261774
BD2C-2-400-WO-1W*261694
BD2C-3-400-WO-1W*261775
BD2C-2-500-WO-3W*261695
BD2C-3-500-WO-3W*261776
BD2C-2-500-WO-2W*261696
BD2C-3-500-WO-2W*261777
BD2C-2-500-WO-1W*261697
BD2C-3-500-WO-1W*261778
BD2C-2-630-WO-3W*261698
BD2C-3-630-WO-3W*261779
BD2C-2-630-WO-2W*261699
BD2C-3-630-WO-2W*261780
BD2C-2-630-WO-1W*261700
BD2C-3-630-WO-1W*261781
BD2C-2-800-WO-3W*261701
BD2C-3-800-WO-3W*261782
BD2C-2-800-WO-2W*261702
BD2C-3-800-WO-2W*261783
BD2C-2-800-WO-1W*261703
BD2C-3-800-WO-1W*261784
BD2C-2-1000-WO-3W*261704
BD2C-3-1000-WO-3W*261785
BD2C-2-1000-WO-2W*261705
BD2C-3-1000-WO-2W*261786
BD2C-2-1000-WO-1W*261706
BD2C-3-1000-WO-1W*261787
BD2C-2-1250-WO-3W*261707
BD2C-3-1250-WO-3W*261788
BD2C-2-1250-WO-2W*261708
BD2C-3-1250-WO-2W*261789
BD2C-2-1250-WO-1W*261709
BD2C-3-1250-WO-1W*261790
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataFeeder Units
Siemens LV 70 · 20045/46
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A
Type/Type suffix PriceSeePrice ListVersion Article no.
End feeder unit without clamp terminalFor introducing multi-core cables from the front • Bolt terminal (bolt included as standard) • PE position can be changed
Aluminium BD2A-250-EE261993
Copper BD2C-250-EE262001
Cabling boxFor introducing multi-core cables from 2 sides • Suitable for use with end feeder unit
–
Cabling entry plateFor introducing single-core cable. Undrilled, drilling template included • Suitable for use with end feeder unit or cabling boxes
+BD2-250-EBAL203526
Distribution feeder unit without clamp terminalBolt terminal (bolt included as standard)• PE position can be changed
Aluminium BD2A-250-VE261994
Copper BD2C-250-VE262002
Selection and ordering dataFeeder Units
Siemens LV 70 · 2004 5/47
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A800 A, 1000 A
Rated current Ie1250 A
Type/Type suffix PriceSeePrice List
Type/Type suffix PriceSeePrice List
Type/Type suffix PriceSeePrice List
Notes
Article no. Article no. Article no. PS*
BD2A-400-EE261995
BD2A-1000-EE261998
– 1 unit Special colours available on request
BD2C-400-EE262003
BD2C-1000-EE262006
BD2C-1250-EE262009
1 unit
+BD2-400-KR045526
+BD2-1000-KR261977
+BD2-1250-KR261983
1 unit
+BD2-400-EBAL045522
+BD2-1000-EBAL261975
+BD2-1250-EBAL261981
1 unit
BD2A-400-VE261996
BD2A-1000-VE261999
– 1 unit
BD2C-400-VE262004
BD2C-1000-VE262007
BD2C-1250-VE262010
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataFeeder Units
Siemens LV 70 · 20045/48
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 AType/Type suffix Price
SeePrice List
Version Article no.
Centre feeder unit without clamp terminalFor introducing multi-core cables from 3 sides• Bolt terminal (bolt included as standard)• Edgewise, flat and PE positions can be changed
(by rotating the whole busbar section)
Aluminium BD2A-400-ME261997
Copper BD2C-400-ME262005
Cabling entry plateFor introducing single-core cable. Undrilled, drilling template included• Suitable for use with centre feeder units
+BD2-400-MBAL045524
Selection and ordering dataFeeder Units
Siemens LV 70 · 2004 5/49
BD2 System (160 A - 1250 A)
5
Rated current Ie500 A, 630 A800 A, 1000 A
Rated current Ie1250 A
Type/Type suffix PriceSeePrice List
Type/Type suffix PriceSeePrice List
Notes
Article no. Article no. PS*
BD2A-1000-ME262000
– 1 unit Special colours available on request
BD2C-1000-ME262008
BD2C-1250-ME262011
1 unit
+BD2-1000-MBAL261979
+BD2-1250-MBAL261985
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Aluminium
Siemens LV 70 · 20045/50
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A800 A, 1000 A
Length/Optional length
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS1)
mL unit with clamp terminal
(fitted to Y as standard)Knee, rear X 0.36/Y 0.36 BD2A-400-LH
261793 BD2A-1000-LH
261803 1 unit
X 0.36 – 1.25/Y 0.36 BD2A-400-LH-X*261846
BD2A-1000-LH-X*261874
X 0.36/Y 0.36 – 1.25 BD2A-400-LH-Y*261847
BD2A-1000-LH-Y*261875
X/Y 0.36 – 1.25 BD2A-400-LH-X*/Y*261848
BD2A-1000-LH-X*/Y*261876
Knee, front X 0.36/Y 0.36 BD2A-400-LV261796
BD2A-1000-LV261806
X 0.36 – 1.25/Y 0.36 BD2A-400-LV-X*261849
BD2A-1000-LV-X*261877
X 0.36/Y 0.36 – 1.25 BD2A-400-LV-Y*261850
BD2A-1000-LV-Y*261878
X/Y 0.36 – 1.25 BD2A-400-LV-X*/Y*261851
BD2A-1000-LV-X*/Y*261879
Elbow, right X 0.36/Y 0.36 BD2A-400-LR261795
BD2A-1000-LR261805
X 0.36 – 1.25/Y 0.36 BD2A-400-LR-X*261852
BD2A-1000-LR-X*261880
X 0.36/Y 0.36 – 1.25 BD2A-400-LR-Y*261853
BD2A-1000-LR-Y*261881
X/Y 0.36 – 1.25 BD2A-400-LR-X*/Y*261854
BD2A-1000-LR-X*/Y*261882
Elbow, left X 0.36/Y 0.36 BD2A-400-LL261794
BD2A-1000-LL261804
X 0.36 – 1.25/Y 0.36 BD2A-400-LL-X*261855
BD2A-1000-LL-X*261827
X 0.36/Y 0.36 – 1.25 BD2A-400-LL-Y*261856
BD2A-1000-LL-Y*261828
X/Y 0.36 – 1.25 BD2A-400-LL-X*/Y*261857
BD2A-1000-LL-X*/Y*261829
Notes Special colours available on requestOptional length (A page 5/17)For X* and Y* replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal to the outside edge of the trunking unit.
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX* and BY*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (BX* end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
+BD2-S90-BY*-M*931957
+BD2-S120-BY*-M*931960
1 unit
XY
Y
X
XY
XY
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Copper
Siemens LV 70 · 2004 5/51
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A 800 A, 1000 A, 1250 A
Length/Optional length
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS1)
mL unit with clamp terminal
(fitted to Y as standard)Knee, rear X 0.36/Y 0.36 BD2C-400-LH
261885 BD2C-1250-LH
261895 1 unit
X 0.36 – 1.25/Y 0.36 BD2C-400-LH-X*261938
BD2C-1250-LH-X*261966
X 0.36/Y 0.36 – 1.25 BD2C-400-LH-Y*261939
BD2C-1250-LH-Y*261967
X/Y 0.36 – 1.25 BD2C-400-LH-X*/Y*261940
BD2C-1250-LH-X*/Y*261968
Knee, front X 0.36/Y 0.36 BD2C-400-LV261888
BD2C-1250-LV261898
X 0.36 – 1.25/Y 0.36 BD2C-400-LV-X*261941
BD2C-1250-LV-X*261969
X 0.36/Y 0.36 – 1.25 BD2C-400-LV-Y*261942
BD2C-1250-LV-Y*261970
X/Y 0.36 – 1.25 BD2C-400-LV-X*/Y*261943
BD2C-1250-LV-X*/Y*261971
Elbow, right X 0.36/Y 0.36 BD2C-400-LR261887
BD2C-1250-LR261897
X 0.36 – 1.25/Y 0.36 BD2C-400-LR-X*261944
BD2C-1250-LR-X*261972
X 0.36/Y 0.36 – 1.25 BD2C-400-LR-Y*261945
BD2C-1250-LR-Y*261973
X/Y 0.36 – 1.25 BD2C-400-LR-X*/Y*261946
BD2C-1250-LR-X*/Y*261974
Elbow, left X 0.36/Y 0.36 BD2C-400-LL261886
BD2C-1250-LL261896
X 0.36 – 1.25/Y 0.36 BD2C-400-LL-X*261947
BD2C-1250-LL-X*261919
X 0.36/Y 0.36 – 1.25 BD2C-400-LL-Y*261948
BD2C-1250-LL-Y*261920
X/Y 0.36 – 1.25 BD2C-400-LL-X*/Y*261949
BD2C-1250-LL-X*/Y*261921
Notes Special colours available on requestOptional length (a page 5/17)For X* and Y* replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal to the outside edge of the trunking unit.
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX* and BY*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (BX* end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
+BD2-S90-BY*-M*931957
+BD2-S120-BY*-M*931960
1 unit
XY
Y
X
XY
XY
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Aluminium
Siemens LV 70 · 20045/52
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A800 A, 1000 A
Version Length/Optional length
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS1)
mZ units with clamp terminal
(fitted to Y as standard)Rear X 0.36/Y 0.36 BD2A-400-ZH-Z*
261814 BD2A-1000-ZH-Z*
261818 1 unit
400 A1250 A
/Z 0.14 – 1.25/Z 0.26 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2A-400-ZH-X*/Y*/Z*261822
BD2A-1000-ZH-X*/Y*/Z*261826
400 A1250 A
/Z 0.14 – 1.25/Z 0.26 – 1.25
Front X 0.36/Y 0.36 BD2A-400-ZV-Z*261813
BD2A-1000-ZV-Z*261817
400 A
1250 A/Z 0.14 – 1.25/Z 0.26 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2A-400-ZV-X*/Y*/Z*261821
BD2A-1000-ZV-X*/Y*/Z*261825
400 A1250 A
/Z 0.14 – 1.25/Z 0.26 – 1.25
Right X 0.36/Y 0.36 BD2A-400-ZR-Z*261811
BD2A-1000-ZR-Z*261815
400 A
1250 A/Z 0.34 – 1.25/Z 0.34 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2A-400-ZR-X*/Y*/Z*261819
BD2A-1000-ZR-X*/Y*/Z*261823
400 A1250 A
/Z 0.34 – 1.25/Z 0.34 – 1.25
Left X 0.36/Y 0.36 BD2A-400-ZL-Z*261812
BD2A-1000-ZL-Z*261816
400 A
1250 A/Z 0.34 – 1.25/Z 0.34 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2A-400-ZL-X*/Y*/Z*261820
BD2A-1000-ZL-X*/Y*/Z*261824
400 A1250 A
/Z 0.34 – 1.25/Z 0.34 – 1.25
Notes Special colours available on requestOptional length (a page 5/17)For X* and Y* replace the asterix in the type reference by the required dimension in metres from the centre of the clamp terminal to the outside edge of the trunking unit, and for Z* from one outside edge to the other.
XZ
Y
X
ZY
Z
X
Y
Z XY
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Copper
Siemens LV 70 · 2004 5/53
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A 800 A, 1000 A, 1250 A
Version Length/Optional length
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS1)
mZ units with clamp terminal
(fitted to Y as standard)Rear X 0.36/Y 0.36 BD2C-400-ZH-Z*
261906 BD2C-1250-ZH-Z*
261910 1 unit
400 A1250 A
/Z 0.14 – 1.25/Z 0.26 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2C-400-ZH-X*/Y*/Z*261914
BD2C-1250-ZH-X*/Y*/Z*261918
400 A1250 A
/Z 0.14 – 1.25/Z 0.26 – 1.25
Front X 0.36/Y 0.36 BD2C-400-ZV-Z*261905
BD2C-1250-ZV-Z*261909
400 A
1250 A/Z 0.14 – 1.25/Z 0.26 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2C-400-ZV-X*/Y*/Z*261913
BD2C-1250-ZV-X*/Y*/Z*261917
400 A1250 A
/Z 0.14 – 1.25/Z 0.26 – 1.25
Right X 0.36/Y 0.36 BD2C-400-ZR-Z*261903
BD2C-1250-ZR-Z*261907
400 A
1250 A/Z 0.34 – 1.25/Z 0.34 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2C-400-ZR-X*/Y*/Z*261911
BD2C-1250-ZR-X*/Y*/Z*261915
400 A1250 A
/Z 0.34 – 1.25/Z 0.34 – 1.25
Left X 0.36/Y 0.36 BD2C-400-ZL-Z*261904
BD2C-1250-ZL-Z*261908
400 A
1250 A/Z 0.34 – 1.25/Z 0.34 – 1.25X 0.36 – 0.60/Y 0.36 – 0.60
BD2C-400-ZL-X*/Y*/Z*261912
BD2C-1250-ZL-X*/Y*/Z*261916
400 A1250 A
/Z 0.34 – 1.25/Z 0.34 – 1.25
Notes Special colours available on requestOptional length (a page 5/17)For X* and Y* replace the asterix in the type reference by the required dimension in metres from the centre of the clamp terminal to the outside edge of the trunking unit, and for Z* from one outside edge to the other.
XZ
Y
X
ZY
Z
X
Y
Z XY
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Aluminium
Siemens LV 70 · 20045/54
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A800 A, 1000 A
Length/Optional length
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS1)
mL unit with clamp terminal
(fitted to Y as standard)With engineered angleKnee, rearFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2A-400-LH-G*261858
BD2A-1000-LH-G*261830
1 unit
X 0.36 – 1.25/Y 0.36 BD2A-400-LH-X*-G*261859
BD2A-1000-LH-X*-G*261831
X 0.36/Y 0.36 – 1.25 BD2A-400-LH-Y*-G*261860
BD2A-1000-LH-Y*-G*261832
X/Y 0.36 – 1.25 BD2A-400-LH-X*/Y*-G*261861
BD2A-1000-LH-X*/Y*-G*261833
Knee, frontFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2A-400-LV-G*261862
BD2A-1000-LV-G*261834
X 0.36 – 1.25/Y 0.36 BD2A-400-LV-X*-G*261863
BD2A-1000-LV-X*-G*261835
X 0.36/Y 0.36 – 1.25 BD2A-400-LV-Y*-G*261864
BD2A-1000-LV-Y*-G*261836
X/Y 0.36 – 1.25 BD2A-400-LV-X*/Y*-G*261865
BD2A-1000-LV-X*/Y*-G*261837
Elbow, rightFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2A-400-LR-G*261866
BD2A-1000-LR-G*261838
X 0.36 – 1.25/Y 0.36 BD2A-400-LR-X*-G*261867
BD2A-1000-LR-X*-G*261839
X 0.36/Y 0.36 – 1.25 BD2A-400-LR-Y*-G*261868
BD2A-1000-LR-Y*-G*261840
X/Y 0.36 – 1.25 BD2A-400-LR-X*/Y*-G*261869
BD2A-1000-LR-X*/Y*-G*261841
Elbow, leftFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2A-400-LL-G*261870
BD2A-1000-LL-G*261842
X 0.36 – 1.25/Y 0.36 BD2A-400-LL-X*-G*261871
BD2A-1000-LL-X*-G*261843
X 0.36/Y 0.36 – 1.25 BD2A-400-LL-Y*-G*261872
BD2A-1000-LL-Y*-G*261844
X/Y 0.36 – 1.25 BD2A-400-LL-X*/Y*-G*261873
BD2A-1000-LL-X*/Y*-G*261845
Notes Special colours available on requestElbow sectionsThe required angle in ° should be entered for G*.Optional length (a page 5/17)For X* and Y* replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal to the outside edge of the trunking unit.
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX* and BY*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (BX* end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
+BD2-S90-BY*-M*931957
+BD2-S120-BY*-M*931960
1 unit
85° – 175°Y
X
X
Y 85° – 175°
85°– 175°Y
X
85°– 175°
XY
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Copper
Siemens LV 70 · 2004 5/55
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A 800 A, 1000 A, 1250 A
Length/Optional length
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS1)
mL unit with clamp terminal
(fitted to Y as standard)With engineered angleKnee, rearFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2C-400-LH-G*261950
BD2C-1250-LH-G*261922
1 unit
X 0.36 – 1.25/Y 0.36 BD2C-400-LH-X*-G*261951
BD2C-1250-LH-X*-G*261923
X 0.36/Y 0.36 – 1.25 BD2C-400-LH-Y*-G*261952
BD2C-1250-LH-Y*-G*261924
X/Y 0.36 – 1.25 BD2C-400-LH-X*/Y*-G*261953
BD2C-1250-LH-X*/Y*-G*261925
Knee, frontFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2C-400-LV-G*261954
BD2C-1250-LV-G*261926
X 0.36 – 1.25/Y 0.36 BD2C-400-LV-X*-G*261955
BD2C-1250-LV-X*-G*261927
X 0.36/Y 0.36 – 1.25 BD2C-400-LV-Y*-G*261956
BD2C-1250-LV-Y*-G*261928
X/Y 0.36 – 1.25 BD2C-400-LV-X*/Y*-G*261957
BD2C-1250-LV-X*/Y*-G*261929
Elbow, rightFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2C-400-LR-G*261958
BD2C-1250-LR-G*261930
X 0.36 – 1.25/Y 0.36 BD2C-400-LR-X*-G*261959
BD2C-1250-LR-X*-G*261931
X 0.36/Y 0.36 – 1.25 BD2C-400-LR-Y*-G*261960
BD2C-1250-LR-Y*-G*261932
X/Y 0.36 – 1.25 BD2C-400-LR-X*/Y*-G*261961
BD2C-1250-LR-X*/Y*-G*261933
Elbow, leftFrom 85° to 175° in 5° increments
X 0.36/Y 0.36 BD2C-400-LL-G*261962
BD2C-1250-LL-G*261934
X 0.36 – 1.25/Y 0.36 BD2C-400-LL-X*-G*261963
BD2C-1250-LL-X*-G*261935
X 0.36/Y 0.36 – 1.25 BD2C-400-LL-Y*-G*261964
BD2C-1250-LL-Y*-G*261936
X/Y 0.36 – 1.25 BD2C-400-LL-X*/Y*-G*261965
BD2C-1250-LL-X*/Y*-G*261937
Notes Special colours available on requestElbow sectionsThe required angle in ° should be entered for G*.Optional length (a page 5/17)For X* and Y* replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal to the outside edge of the trunking unit.
Type suffix for fire barrier S90
PriceSeePrice List
Type suffix for fire barrier S120
PriceSeePrice List
Notes
Article no. Article no. PS1)
+BD2-S90-BX*-M*931956
+BD2-S120-BX*-M*931959
1 unit Fire barrier (a page 5/24) For BX* and BY*, replace the asterisk in the type reference by the required dimension in metres from the centre of the clamp terminal (BX* end without clamp terminal) to the centre of the fire wall or ceiling; for -M* specify the wall or ceiling thickness.
+BD2-S90-BY*-M*931957
+BD2-S120-BY*-M*931960
1 unit
85° – 175°Y
X
X
Y 85° – 175°
85°– 175°Y
X
85°– 175°
XY
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Aluminium
Siemens LV 70 · 20045/56
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A800 A, 1000 A*
Type PriceSeePrice List
Type PriceSeePrice List
NotesLength/Optional
Article no. Article no. PS1)
m
Flexible junction unit with clamp terminal
(fitted to Y as standard) 1.25 BD2-400-R045889
– 1 unit Special colours available on request* not with BD2-800-R1.75 – BD2-800-R
0458901 unit
T units with clamp terminalRear 0.36 BD2A-400-TH
261797BD2A-1000-TH261807
1 unit
Front 0.36 BD2A-400-TV261800
BD2A-1000-TV261810
Right 0.36 BD2A-400-TR261799
BD2A-1000-TR261809
Left 0.36 BD2A-400-TL261798
BD2A-1000-TL261808
K units with clamp terminalFront/rear 0.36 BD2A-400-KVH
261792BD2A-1000-KVH261802
1 unit
Right/left 0.36 BD2A-400-KRL261791
BD2A-1000-KRL261801
1 unit
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataJunction Unit, Copper
Siemens LV 70 · 2004 5/57
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500 A, 630 A, 800 A,1000 A*, 1250 A*
Type PriceSeePrice List
Type PriceSeePrice List
NotesLength/Optional
Article no. Article no. PS1)
m
Flexible junction unit with clamp ter-minal(fitted to Y as standard) 1.25 BD2-400-R
045889– 1 unit Special colours available
on request* not with BD2-800-R1.75 – BD2-800-R
0458901 unit
T units with clamp terminalRear 0.36 BD2C-400-TH
261889BD2C-1250-TH261899
1 unit
Front 0.36 BD2C-400-TV261892
BD2C-1250-TV261902
Right 0.36 BD2C-400-TR261891
BD2C-1250-TR261901
Left 0.36 BD2C-400-TL261890
BD2C-1250-TL261900
K units with clamp terminalFront/rear 0.36 BD2C-400-KVH
261884BD2C-1250-KVH261894
1 unit
Right/left 0.36 BD2C-400-KRL261883
BD2C-1250-KRL261893
1 unit
1) This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20045/58
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesVersion Rated
currentRatedoperationalvoltage
Article no. PS*
IeA
UeV
Tap-off unit (size 1)
Insulated enclosure, up to 25 AWith fuse base 3 x D02 25 400 BD2-AK1/S18
047112 1 unit M25 cable grommet included as
standard.Gauge screw, fuse cartridges, fuse caps and plastic cable glands with strain relief to be used (not included as standard).
3 x D01 16 400 BD2-AK1/S14047113
With 3-pole 16 A miniature circuit-breaker, C characteristic
– 16 400 BD2-AK1/A163047146
With 2 x D01 fuse basesand two 3-pole 16 A CEE socket
– 16 230 BD2-AK1/2CEE163S14047167
With 3 x D01 fuse basesand 5-pole 16 A CEE socket
– 16 400 BD2-AK1/CEE165S14047230
With two 1-pole 16 A miniature circuit-breakers, B characteristic and two 3-pole 16 A CEE sockets
– 16 230 BD2-AK1/2CEE163A161047231
With one 3-pole 16 A miniature circuit-breaker, C characteristic, and one 1-pole 16 A CEE socket
– 16 400 BD2-AK1/CEE165A163047283
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 2004 5/59
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Ratedoperationalvoltage
Article no. PS*
IeA
UeV
Tap-off units (Size 1)
Insulated enclosure, up to 25 AWith 3 x D01 fuse base • Three 16 A Schuko sockets
16 230 BD2-AK1/3SD163S14047284
1 unit For BD2-AK1/..., the M25 cable grommet is included as standard.Fuse cartridge, fuse cap and plastic cable glands with strain relief to be used (not included as standard).
With three 1-pole 16 A miniature circuit-breakers, B characteristic • Three 16 A Schuko sockets
16 230 BD2-AK1/3SD163A161047335
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20045/60
BD2 System (160 A - 1250 A)
5
Tap-off unit (size 02)
Steel enclosure up to 63 A
With 3-pole D02 fuse base 63 400 BD2-AK02X/S18262438
1 unit For BD2-AK02X/... andBD2-AK02M2/... special colours available on request.Fuse cartridge, fuse cap and plastic cable glands with strain relief to be used (not included as standard).
With 3-pole S27 fuse basewith gauge screw system
25 500 BD2-AK02X/S27262439
With 3-pole S33 fuse basewith gauge screw system
63 500 BD2-AK02X/S33262450
With 3-pole SP38 fuse base for 10 x 38 mm cylinder fuses
25 400 BD2-AK02X/F1038-3262469
With 4-pole SP38 fuse base for 10 x 38 mm cylinder fuses
25 400 BD2-AK02X/F1038-3N262470
With 3-pole SP51 fuse base for 14 x 51 mm cylinder fuses
32 400 BD2-AK02X/F1451-3262471
With 4-pole SP51 fuse base for 14 x 51 mm cylinder fuses
32 400 BD2-AK02X/F1451-3N262472
With 3-pole SP58 fuse base for 22 x 58 mm cylinder fuses
63 400 BD2-AK02X/F2258-3262473
With 4-pole SP58 fuse base for 22 x 58 mm cylinder fuses
63 400 BD2-AK02X/F2258-3N262474
With 3-pole 3 x CM32F fuse base 32 400 BD2-AK02X/GB323262435
With 3-pole 3 x CM63F fuse base 55 400 BD2-AK02X/GB633262436
Tap-off units (size 02)
With 3-pole 32 A miniature circuit-breaker, C characteristic
32 400 BD2-AK02M2/A323262451
1 unit
With 3-pole and N pole miniature circuit-breaker32 A, C characteristic
32 400 BD2-AK02M2/A323N262452
With 3-pole 63 A miniature circuit-breaker, C characteristic
63 400 BD2-AK02M2/A633262453
With 3-pole and N pole 63 A miniature circuit-breaker, C characteristic
63 400 BD2-AK02M2/A633N262454
Type PriceSeePrice List
NotesRated current
Ratedoperationalvoltage
Article no. PS*
IeA
UeV
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 2004 5/61
BD2 System (160 A - 1250 A)
5
Tap-off unit (size 2)
Steel-enclosure up 63 A
With 3-pole D02 fuse base 63 400 BD2-AK2X/S18203135
1 unit With BD2-AK2X/... special colours on request.Gauge screw, fuse cartridges, fuse caps and plastic cable glands with strain relief to be used (not included as standard).
With 3-pole S27 fuse base 25 500 BD2-AK2X/S27203136
With gauge screw system 25 500 BD2-AK2X/S27/FORMP203137
With 3-pole S33 fuse base 63 690 BD2-AK2X/S33203138
With gauge screw system 63 690 BD2-AK2X/S33/FORMP203140
With 3-pole S33 fuse base • One 5-pole 32 A CEE socket
32 400 BD2-AK2X/CEE325S33203142
With gauge screw system 32 400 BD2-AK2X/CEE325S33/FORMP203143
With 3-pole S33 fuse base • One 5-pole 63 A CEE socket
63 400 BD2-AK2X/CEE635S33203146
With gauge screw system 63 400 BD2-AK2X/CEE635S33/FORMP203147
With 2 x 3-pole D01 fuse bases• Two 5-pole 16 A CEE sockets
16 400 BD2-AK2X/2CEE165S14203148
2 x 3-pole S27 fuse basewith gauge screw system• Two 5-pole 16 A CEE sockets
32 400 BD2-AK2X/2CEE165S27/FORMP203149
Type PriceSeePrice List
NotesRated current
Ratedoperationalvoltage
Article no. PS*
IeA
UeV
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20045/62
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 2)With 3-pole 32 A miniature circuit-breaker, C characteristic
32 400 BD2-AK2M2/A323203144
1 unit For BD2-AK2M2/..., special colours available on request.Gauge screw, fuse cartridges, fuse caps and plastic cable glands with strain relief to be used (not included as standard).
With 3-pole 32 A miniature circuit-breaker, C characteristic• One 5-pole 32 A CEE socket
32 400 BD2-AK2M2/CEE325A323207986
With 3-pole and 2 x 1-pole 16 A miniature circuit-breakers, B characteristic • One 5-pole 16 A CEE socket• Two 16 A Schuko sockets
16 230 BD2-AK2M2/2SD163CEE165A163203150
With two 3-pole 16 A miniature circuit-breakers, C characteristic • Two 5-pole 16 A CEE sockets
16 400 BD2-AK2M2/2CEE165A163203151
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 2004 5/63
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 03) with miniature circuit-breaker
With 3-pole 125 A miniature circuit-breaker, characteristic
125 400 BD2-AK03M2/A1253262485
1 unit For BD2-AK03M2/... and BD2-AK03X/... special colours on request.Plastic cable glands with strain relief to be used (not included as standard)
With 3-pole and N pole 125 Aminiature circuit-breaker, C characteristic
125 400 BD2-AK03M2/A1253N262486
1 unit
Tap-off unit (size 03) with circuit-breakerWith normal switching capacity and box terminals3-pole
Circuit-breakers NZMN1-A40 40 400 BD2-AK03X/L40-3262489
1 unit
NZMN1-A63 63 400 BD2-AK03X/L63-3262490
NZMN1-A80 80 400 BD2-AK03X/L80-3262491
NZMN1-A100 100 400 BD2-AK03X/L100-3262492
NZMN1-A125 125 400 BD2-AK03X/L125-3262493
4-poleCircuit-breakers NZMN1-4-A40 40 400 BD2-AK03X/L40-4
283391 1 unit
NZMN1-4-A63 63 400 BD2-AK03X/L63-4283392
NZMN1-4-A80 80 400 BD2-AK03X/L80-4283393
NZMN1-4-A100 100 400 BD2-AK03X/L100-4283394
NZMN1-4-A125 125 400 BD2-AK03X/L125-4283395
Type suffix Rotary drive for BD2-AK03X/L... – – – +BD2-LD0G
262494 1 unit
Tap-off unit (size 03) with fuse switch-disconnectorwith terminal bolt3-pole
Fuse-switch IEC 125 400 BD2-AK03X/FS125IEC-3262499
1 unit
BS 125 400 BD2-AK03X/FS125BS-3262500
1 unit
4-poleFuse-switch IEC 125 400 BD2-AK03X/FS125IEC-4
262501 1 unit
BS 125 400 BD2-AK03X/FS125BS-4262502
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20045/64
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 03)
With fuse bases, fuse switch-disconnectors and bolt terminalsLow-voltage h.b.c. fuse switch-disconnector, size 00
125 690 BD2-AK03X/GSTA00262496
1 unit Fuse cartridge and cable glands with strain relief to be used (not included as standard)
Tap-off unit (size 03)With three pole SP58 fuse base 125 690 BD2-AK03X/F2258-3
262497 1 unit
With four pole SP58 fuse base 125 690 BD2-AK03X/F2258-3N262498
1 unit
With 3-pole 3 x CM100F fuse base 80 400 BD2-AK03X/GB1003262484
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 2004 5/65
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 3) with circuit-breaker
With medium switching capacity and box terminals3-pole For BD2-AK3X/..., special
colours available on request.Plastic cable glands with strain relief to be used (not included as standard)
Circuit-breakers
NZM 7-40S 40 400 BD2-AK3X/L40-3203152
1 unit
NZM 7-63S 63 400 BD2-AK3X/L63-3203153
NZM 7-80S 80 400 BD2-AK3X/L80-3203154
NZM 7-100S 100 400 BD2-AK3X/L100-3203155
NZM 7-125S 125 400 BD2-AK3X/L125-3203156
4-poleCircuit-breakers
NZM 74-40S 40 400 BD2-AK3X/L40-4203157
1 unit
NZM 74-63S 63 400 BD2-AK3X/L63-4203158
NZM 74-80S 80 400 BD2-AK3X/L80-4203159
NZM 74-100S 100 400 BD2-AK3X/L100-4203160
NZM 74-125S 125 400 BD2-AK3X/L125-4203161
Type suffix Rotary drive for BD2-AK3X/L... – – – +BD2-LDG
203164 1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for International Use
Siemens LV 70 · 20045/66
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 3)
With fuse bases, fuse switch-disconnectors and bolt terminalsLow-voltage h.b.c. fuse base, size 00 125 690 BD2-AK3X/GS00
203162 1 unit For BD2-AK41/... and
BD2-AK51/..., KT3 cable grommet included as standard.For BD2-AK3X/..., BD2-AK41/... and BD2-AK51/... special colours on request.Fuse cartridge and cable glands with strain relief to be used (not included as standard).
Low-voltage h.b.c. fuse switch-disconnector, size 00
125 690 BD2-AK3X/GSTZ00203163
1 unit
Tap-off unit (size 4)
With fuse bases, fuse switch-disconnectors and bolt terminalsLow-voltage h.b.c. fuse base, size 1 250 690 BD2-AK41/GS1
021481 1 unit
Low-voltage h.b.c. fuse switch-disconnector, size 1
250 690 BD2-AK41/GSTZ1023854
1 unit
Tap-off unit (size 5)(only for 500 A to 1250 A systems)
With fuse bases, fuse switch-disconnectors and bolt terminalsLow-voltage h.b.c. fuse base, size 2 400 690 BD2-AK51/GS2
028600 1 unit
Low-voltage h.b.c. fuse switch-disconnector, size 2
400 690 BD2-AK51/GSTZ2026227
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Belgium
Siemens LV 70 · 2004 5/67
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off units (size 1)
With 1-pole 16 A miniature circuit-breaker, C characteristic
16 230 BD2-AK1/A161/1203195
1 unit For BD2-AK1/..., the M25 cable grommet is included as standard.For BD2-AK2M2/... special colours available on request.Plastic cable glands with strain relief to be used (not included as standard)
With 2-pole 16 A miniature circuit-breaker, C characteristic
16 230 BD2-AK1/A162203170
With 3-pole and N pole 16 A miniature circuit-breaker, C characteristic
16 400 BD2-AK1/A163N203171
With 1-pole 20 A miniature circuit-breaker, C characteristic
20 230 BD2-AK1/A201203173
With 2-pole 20 A miniature circuit-breaker, C characteristic
20 230 BD2-AK1/A202203174
With 3-pole 20 A miniature circuit-breaker, C characteristic
20 400 BD2-AK1/A203203175
With 3-pole and N pole 20 A miniature circuit-breaker, C characteristic
20 400 BD2-AK1/A203N203176
With two 2-pole 16 A miniature circuit-breakers, C characteristic• Two 3-pole 16 A CEE sockets
16 230 BD2-AK1/2CEE163A162203172
With two 2-pole 16 A miniature circuit-breakers, C characteristic • Two 3-pole 16 A CEE sockets
16 230 BD2-AK1/2PC163A162203177
Tap-off unit (size 2)
With 3-pole and N pole 32 A miniature circuit-breaker, C characteristic
32 400 BD2-AK2M2/A323N203178
1 unit
With 3-pole 63 A miniature circuit-breaker, C characteristic
63 400 BD2-AK2M2/A633203179
With 3-pole and N pole 63 A miniature circuit-breaker, C characteristic
63 400 BD2-AK2M2/A633N203180
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Denmark
Siemens LV 70 · 20045/68
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 1)With 3 x D01 fuse base• Three 10 A sockets
13 230 BD2-AK1/3DKS103S14203167
1 unit Fuse cartridge and screw cap are not included as standard.
With two 1-pole 13 A miniature circuit-breakers, C characteristic• Three 10 A sockets
13 230 BD2-AK1/3DKS103A131203168
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Great Britain
Siemens LV 70 · 2004 5/69
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 2)With 3 x CM32F fuse base• Three 13 A BS1363 sockets
13 230 BD2-AK2X/3BS133GB131203181
1 unit Special colours available on requestFuse cartridge and cable glands with strain relief to be used not included as standard).
With two 1-pole 13 A miniature circuit-breakers, B characteristic• Three 13 A Schuko sockets
13 230 BD2-AK2M2/3BS133A131203182
With 3-pole 3 x CM32F fuse base 32 400 BD2-AK2X/GB323203236
With 3-pole 3 x CM63F fuse base 55 400 BD2-AK2X/GB633203237
Tap-off unit (size 3)With 3-pole 3 x CM100F fuse base 80 400 BD2-AK3X/GB1003
203238 1 unit
Tap-off unit (size 4)With 3-pole 3 x RS200H fuse base 170 690 BD2-AK41/GB200
012523 1 unit
Tap-off unit (size 5)(only for 500 A to 1250 A systems)With 3-pole 3 x RS400H fuse base 340 690 BD2-AK52/GB400
012547 1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for France
Siemens LV 70 · 20045/70
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 1)For BD2-AK1/..., the M25 cable grommet is included as standard.For BD2-AK2X/..., special colours available on request.Fuse cartridges and cable glands with strain relief to be used (not included as standard).
With 3-pole SP38 fuse base for 10 x38 mm cylinder fuses
25 400 BD2-AK1/F1038-3203189
1 unit
With 4-pole SP38 fuse base for 10 x38 mm cylinder fuses
25 400 BD2-AK1/F1038-3-N203190
With 2-pole 16 A miniaturecircuit-breaker, B characteristic, and 2-pole 40 A/30 mA residual-current protective module
16 230 BD2-AK1/FI40-162214822
Tap-off unit (size 2)
With 3-pole SP51 fuse base for 14 x51 mm cylinder fuses
32 400 BD2-AK2X/F1451-3203192
1 unit
With 3-pole SP58 fuse base for 22 x58 mm cylinder fuses
63 400 BD2-AK2X/F2258-3203193
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataTap-Off Units for Switzerland
Siemens LV 70 · 2004 5/71
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesRated current
Rated operational voltage
Article no. PS*
IeA
UeV
Tap-off unit (size 1)With 3 x 1-pole 10 A miniature, circuit-breakers, B characteristic
10 400 BD2-AK1/A101203194
1 unit M25 cable grommet included as standard.Plastic cable glands with strain relief to be used (not included as standard)
With three 1-pole 16 A miniature circuit-breakers, B characteristic
16 400 BD2-AK1/A161203169
With three 1-pole 10 A miniature circuit-breakers, B characteristic• Three 3-pole 10 A sockets, type 13
10 230 BD2-AK1/3X13A101203199
With 3-pole 10 A miniature circuit-breaker,B characteristic• One 5-pole 10 A socket, type 15
10 400 BD2-AK1/15A103203196
With 3-pole 16 A miniature circuit-breaker,B characteristic• Two 5-pole 10 A sockets, type 15
16 400 BD2-AK1/2X15A163203198
With 3-pole 16 A miniature circuit-breaker,B characteristic• One 5-pole 15 A socket, type 34
16 400 BD2-AK1/34A163203197
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAncillary Equipment Units for International Use
Siemens LV 70 · 20045/72
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
NotesArticle no. PS*
Ancillary equipment unit
Pv max. 30 W; Ue max. 400 VFreely assignable• 8 MW• Built-in top-hat rail• For overvoltage protection• For remote control/remote switching• For intelligent equipment• For electronic control equipment• For PKZ0 etc.
BD2-GKX/F203165
1 unit Special colours available on request.Including sundries for connecting the enclosures.Plastic cable glands with strain relief to be used (not included as standard).
With component mounting unitFreely assignable• 8 MW• Built-in top-hat rail
– For remote control/remote switching– For intelligent equipment– For electronic control equipment– For PKZ0 etc.
(With hinged flags to allow operator access to fitted com-ponents,e.g. miniature circuit-breakers)
BD2-GKM2/F203166
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAccessories
Siemens LV 70 · 2004 5/73
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500A, 630 A, 800 A 1000 A, 1250 A,
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS*
Clamp terminalBD2-400-SK203516
BD2-1250-EK261989
1 unit
End flangeBD2-400-FE043977
BD2-1250-FE261990
1 unit
Fixing bracketfor flat and edgewise installation BD2-400-BB
045154 BD2-1250-BB
261987 1 unit
Spacerfor 40 mm intervals• For use with fixing bracket
BD2-DSB203532
BD2-DSB203532
1 unit
Spacer bracketfor wall and ceiling mounting• For use with fixing bracket
BD2-BD034228
BD2-BD034228
1 unit
Retaining element
For vertical busbar runsWall mounting• Distance from wall adjustable
BD2-BWV045503
BD2-BWV045503
1 unit
Ceiling mounting BD2-BDV045504
BD2-BDV045504
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAccessories
Siemens LV 70 · 20045/74
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500A, 630 A, 800 A 1000 A, 1250 A,
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS*
Fixing bracket
For securing vertical systems to the wall at the connecting flange
BD2-BVF203531
BD2-BVF203531
1 unit
Protective sleeveBD2-400-D045505
BD2-1250-D261988
1 unit
Cabling entry plate
For introducing single-core cables, undrilled,drilling template included
For use with 250 A feeder units BD2-250-EBAL203530
– 1 unit
For use with feeder units or cabling box BD2-400-EBAL045507
BD2-1000-EBAL261976
– BD2-1250-EBAL261982
For use with centre feeder units BD2-400-MBAL045509
BD2-1000-MBAL261980
– BD2-1250-MBAL261986
Cabling box
For introducing multi-core cables from 2 sidesFor use with feeder units
BD2-400-KR045511
BD2-1000-KR261978
1 unit
– BD2-1250-KR261984
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAccessories
Siemens LV 70 · 2004 5/75
BD2 System (160 A - 1250 A)
5
Rated current Ie160 A, 250 A315 A, 400 A
Rated current Ie500A, 630 A, 800 A 1000 A, 1250 A,
Type PriceSeePrice List
Type PriceSeePrice List
Article no. Article no. PS*
Flange for IP54 degree of protectionEdgewise mounting position
At all junction points BD2-400-HF045513
BD2-1250-HF261991
1 unit
At end flanges BD2-400-HFE045515
BD2-1250-HFE261992
1 unit
Flat mounting positionAt all junction points BD2-FF
045517 BD2-FF
045517 1 unit
At end flanges BD2-FFE045518
BD2-FFE045518
At top tap-off points BD2-FAS045519
BD2-FAS045519
Vertical mounting positionAt all junction points BD2-400-VF
045520 BD2-1250-VF
262125 1 unit
At all tap-off points BD2-FAS045519
BD2-FAS045519
1 unit
* This quantity or a multiple thereof can be ordered.
Selection and ordering dataAccessories
Siemens LV 70 · 20045/76
BD2 System (160 A - 1250 A)
5
Type PriceSeePrice List
Article no. PS*
Accessories for tap-off units and ancillary equipment units16 A Schuko socket• With adapter enclosure • With wiring • With fixing kit
BD2-SD163203253
1 unit
CEE socket• With adapter enclosure • With wiring • With fixing kit
3-pole 16 A BD2-CEE163203254
1 unit
3-pole 16 A BD2-CEE165203255
5-pole 32 A BD2-CEE325203256
Adapter enclosureFor sockets with fixing kit
BD2-AG203257
1 unit
Adapter plateFor use with adapter enclosure
For customized socket cut-outs BD2-APO203258
1 unit
With 44 mm socket cut-out BD2-APM203259
1 unit
* This quantity or a multiple thereof can be ordered.
Technical Data
Siemens LV 70 · 2004 5/77
BD2 System (160 A - 1250 A)
5
Combustive energy
Type Combustive energy
Without single-bolt clamp terminal kWh/mTrunking unitsBD2.-.-160-SB-. 1.32BD2.-.-160-WB-. 1.32BD2.-.-250-SB-. 1.32BD2.-.-250-WB-. 1.32BD2.-.-315-SB-. 1.32BD2.-.-315-WB-. 1.32BD2.-.-400-SB-. 1.32BD2.-.-400-WB-. 1.32BD2.-.-400-SO-. 0.60BD2.-.-400-WO-. 0.60BD2.-.-500-SB-. 2.00BD2.-.-500-WB-. 2.00BD2.-.-500-SO-. 0.67BD2.-.-500-WO-. 0.67BD2.-.-630-SB-. 2.00BD2.-.-630-WB-. 2.00BD2.-.-630-SO-. 0.67BD2.-.-630-WO-. 0.67BD2.-.-800-SB-. 2.00BD2.-.-800-WB-. 2.00BD2.-.-800-SO-. 0.67BD2.-.-800-WO-. 0.67BD2.-.-1000-SB-. 2.00BD2.-.-1000-WB-. 2.00BD2.-.-1000-SO-. 0.67BD2.-.-1000-WO-. 0.67BD2.-.-1250-SB-. 2.00BD2.-.-1250-WB-. 2.00BD2.-.-1250-SO-. 0.67BD2.-.-1250-WO-. 0.67Branch/junction unitsBD2.-400-L.. 1.27BD2.-400-Z.. 1.88BD2.-1000-L.. 1.27BD2.-1000-Z.. 1.88BD2.-1250-L.. 1.27BD2.-1250-Z.. 1.88BD2.-400-T.. 2.00BD2.-400-K.. 2.67BD2.-1000-T.. 2.00BD2.-1000-K.. 2.67BD2.-1250-T.. 2.00BD2.-1250-K.. 2.67Feeder units kWhBD2.-250-EE 3.20BD2.-250-VE 3.00BD2.-400-EE 3.50BD2.-400-ME 3.90BD2.-400-VE 3.20BD2.-1000-EE 3.80BD2.-1250-EE 4.10BD2.-1000-VE 3.60BD2.-1250-VE 4.00BD2-1000-ME 8.10BD2-1250-ME 12.30
Type Combustive energykWh
Tap-off unitsBD2-AK1/S14 6.9BD2-AK1/S18 6.9BD2-AK1/A163 5.83BD2-AK1/CEE165S14 8.5BD2-AK1/CEE165A163 8.7BD2-AK1/2CEE163S14 9.5BD2-AK1/2CEE163A161 7.5BD2-AK1/3SD163S14 8BD2-AK1/3SD163A161 4.3BD2-AK1/A161/1 5.5BD2-AK1/A162 5.5BD2-AK1/A163N 6.1BD2-AK1/2CEE163A162 7.5BD2-AK1/A201 5.2BD2-AK1/A202 5.5BD2-AK1/A203 5.8BD2-AK1/A203N 6.1BD2-AK1/2PC163A162 5.8BD2-AK1/3DKS103S14 7.2BD2-AK1/3DKS103A131 5.9BD2-AK1/F1038-3 5.9BD2-AK1/F1038-3-N 6.1BD2-AK1/FI30-162 5.5BD2-AK1/A101 5.2BD2-AK1/A161 5.2BD2-AK1/15A103 4.5BD2-AK1/34A163 4.5BD2-AK1/2X15A163 5.5BD2-AK1/3X13A101 5.7BD2-AK.2X/S18 4.8BD2-AK.2X/S27(/FORMP) 2.94BD2-AK.2X/S33(/FORMP) 2.94BD2-AK2X/CEE325S33(/FORMP) 4.57BD2-AK.2M2/A323 5.1BD2-AK2M2/CEE325A323 6.7BD2-AK2X/CEE635S33(/FORMP) 5.8BD2-AK2X/2CEE165S14 7.9BD2-AK2X/2CEE165S27(/FORMP) 6.1BD2-AK2M2/2SD163CEE165A163 6.9BD2-AK2M2/2CEE165A163 9.4BD2-AK.2M2/A323N 5.1BD2-AK.2M2/A633 5BD2-AK.2M2/A633N 5.3BD2-AK2X/3BS133GB131 7.9BD2-AK2X/3BS133A131 5.9BD2-AK.2X/GB323 7.6BD2-AK.2X/GB633 7.9
Type Combustive energykWh
BD2-AK.2X/F1451-3(N) 5.9BD2-AK.2X/F2258-3(N) 6.1BD2-AK.3X/L40-3 9.79BD2-AK.3X/L63-3 9.79BD2-AK.3X/L80-3 9.79BD2-AK.3X/L100-3 9.79BD2-AK.3X/L125-3 9.79BD2-AK3X/L40-4 12.8BD2-AK3X/L63-4 12.8BD2-AK3X/L80-4 12.8BD2-AK3X/L100-4 12.8BD2-AK3X/L125-4 12.8+BD2-LD.G 1.7BD2-AK3X/GS00 8.07BD2-AK.3X/GST.00 9.07BD2-AK.3X/GB1003 14BD2-AK03X/FS125...-3 10.0BD2-AK03X/FS125...-4 13.0BD2-AK03X/F2258...-3(N) 6.1BD2-AK03M2/A1253(N) 5.7BD2-AK41/GS1 10.12BD2-AK41/GSTZ1 16.65BD2-AK41/GB200 23BD2-AK51/GS2 12.16BD2-AK51/GSTZ2 18.6BD2-AK52/GB400 26Ancillary equipment unitsBD2-GKX/F 0.4BD2-GKM2/F 1.5AccessoriesBD2-400-SK 1.64BD2-400-FE –BD2-400-BB –BD2-400-HF –BD2-400-HFE –BD2-400-VF –BD2-1250-EK 2.46BD2-1250-FE –BD2-1250-BB –BD2-1250-HF –BD2-1250-HFE –BD2-1250-VF –BD2-FFE –BD2-FF –BD2-FAS –BD2-SD163 0.1BD2-CEE163 0.2BD2-CEE165 0.2BD2-CEE325 0.3BD2-AG –BD2-APO –BD2-APM –
Technical DataAluminium
Siemens LV 70 · 20045/78
BD2 System (160 A - 1250 A)
5
BD2A-.-160 BD2A-.-250 BD2A-.-315 BD2A-.-400
Conducting pathsRated insulation voltage Ui V AC/DC 690/800 690/800 690/800 690/800Overvoltage category/pollution degree III/3 III/3 III/3 III/3Rated operational voltage Ue V AC 690 690 690 690Frequency Hz 50 – 60 50 – 60 50 – 60 50 – 60Rated current Ie = thermal nominal current atmax. 40 °C and 35 °C on a 24 h average
A 160 250 315 400
Impedance per unit length of current paths with 50 Hz and 20 °C ambient temperature (cold rails)– Equivalent resistance R20 mOhm/m 0.467 0.351 0.285 0.167– Positive reactance X20 mOhm/m 0.162 0.113 0.113 0.123– Impedance Z20 mOhm/m 0.495 0.369 0.306 0.207Impedance per unit length of current paths with 50 Hz and 20 °C ambient temperature (rail under operating conditions warm)– Equivalent resistance R1 mOhm/m 0.564 0.438 0.383 0.215– Positive reactance X1 mOhm/m 0.158 0.111 0.112 0.122– Impedance Z1 mOhm/m 0.586 0.452 0.399 0.247Impedance per unit length of current paths in case of failure– AC resistance per unit length RF mOhm/m 0.865 0.909 0.722 0.548– Positive reactance per unit length XF mOhm/m 0.365 0.487 0.438 0.456– Impedance per unit length ZF mOhm/m 0.939 1.031 0.844 0.713Zero phase-sequence impedance acc. to VDE 0102
Phases R0 mOhm/m 1.893 1.963 1.494 1.217-N X0 mOhm/m 0.759 0.824 0.658 0.640
Z0 mOhm/m 2.040 2.128 1.633 1.375Phases R0 mOhm/m 1.638 1.279 1.225 1.059-PE X0 mOhm/m 0.606 0.516 0.524 0.518
Z0 mOhm/m 1.746 1.379 1.332 1.179Short-circuit resistanceRated peak withstand current Ipk kA 17 32 36 40Rated short-time withstand current Icw kA 5.5 10 14 16Rated operating voltage Icw kA 10 16 18 20Number of conductors 5 5 5 5Conductor cross-section L1, L2, L3 mm2 63 90 113 205
N mm2 63 90 113 2051/2 N mm2 63 90 90 113PE mm2 63 90 113 2051/2 PE mm2 63 90 113 205
Conductor material AI AI AI AIMax. interval between trunking unit supports atnormal mechanical loadingEdgewise m 4 4 4 4Edgewise with BD2-BD1) m 4 4 4 4Flat m 3.5 3.5 3.5 3.5Combustive energy kWh/m 1.32 1.32 1.32 1.32
Notes 1) when using distance bracket BD2-BD.
Tap-off units Rated current Ie25 A 63 A 125 A 250 A 400 A
Switching capacity of contact system AC-22B – – – –Switching capacity of the built in switch-disconnector toIEC/EN 60 947-3 at 400 V
– AC-22B AC-21B – –
Max. admissible rated prospective short-circuitwithstand current when tap-off units with miniaturecircuit-breakers are used:
10 kAeff: for higher rated prospective short-circuit currents, refer to ”Back-up protection“ for miniature circuit-breakers.25 kAeff: for higher rated prospective short-circuit currents the upstream protective device must limit to: Max. let-through energy I2t = 12 x 104 A2s; Max. let-through energy ID = 9.5 kA
Technical DataAluminium
Siemens LV 70 · 2004 5/79
BD2 System (160 A - 1250 A)
5
BD2A-.-500 BD2A-.-630 BD2A-.-800 BD2A-.-1000 General Technical Data
690/800 690/800 690/800 690/800III/3 III/3 III/3 III/3690 690 690 69050 – 60 50 – 60 50 – 60 50 – 60500 630 800 1000
0.111 0.113 0.073 0.0510.057 0.057 0.058 0.0580.125 0.127 0.094 0.077
0.135 0.149 0.098 0.0660.056 0.057 0.057 0.0570.146 0.159 0.114 0.088
0.264 0264 0.225 0.1570.232 0.238 0.239 0.2400.352 0.355 0.328 0.287
0.537 0.538 0.494 0.3400.329 0.331 0.312 0.3010.630 0.632 0.584 0.4540.492 0.492 0.438 0.4080.299 0.303 0.280 0.2730.576 0.578 0.520 0.491
59 64 84 9021 26 32 3428 32 40 435 5 5 5276 276 446 699276 276 446 699276 276 446 699276 276 446 699276 276 276 350AI AI AI AI
4 4 3.5 32 2 1.75 1.53.5 3.5 3 2.52 2 2 2
Standards and specifications IEC/EN 60 439-1 and -2Climatic proofing Damp heat, constant, to IEC 60 068-2-78
Dampf heat, cyclic, to IEC 60 068-2-30Ambient temperaturemin./max. °C
–5/+40
Degree of protectionTrunking units IP52, IP54 with accessories on the busbar run,
construction type 2 IEC/EN 60 529Feeder units, tap-off units
IP54, construction type 2 IEC/EN 60 529
Mounting position Edgewise, flat, tap-off points on sideWeigth AnnexDimensions a page 5/84MaterialTrunking units, feeder units, tap-off units
Hot galvanized sheet steel with paint finish (RAL 7035), light grey insulated enclosure with BD2-AK1/...
Busbars Nickel-plated and tinned aluminium busbarsImportant engineering notesNot all tap-off units have a rated voltage of 690 V and a short-circuit rating that corresponds to the system as a whole.The short-circuit rating and rated voltage of the tap-off units used in a system must be appropriate for it.If the rated voltage of a tap-off unit does not match, choose one equipped with the appropriate components. Larger prospective short-circuit currents must be limited by fitting protective devices (such as circuit-breakers) upstream.
Technical DataCopper
Siemens LV 70 · 20045/80
BD2 System (160 A - 1250 A)
5
s+
BD2C-.-160 BD2C-.-250 BD2C-.-315 BD2C-.-400
Conducting pathsRated insulation voltage Ui V AC/DC 690/800 690/800 690/800 690/800Overvoltage category/pollution degree III/3 III/3 III/3 III/3Rated operational voltage Ue V AC 690 690 690 690Frequency Hz 50 – 60 50 – 60 50 – 60 50 – 60Rated current Ie = thermal nominal current atmax. 40 °C and 35 °C on a 24 h average
A 160 250 315 400
Impedance per unit length of current paths with 50 Hz and 20 °C ambient temperature (cold rails)– Equivalent resistance R20 mOhm/m 0.303 0.295 0.295 0.180– Positive reactance X20 mOhm/m 0.157 0.158 0.123 0.114– Impedance Z20 mOhm/m 0.341 0.334 0.316 0.213Impedance per unit length of current paths with 50 Hz and 20 °C ambient temperature (rail under operating conditions warm)– Equivalent resistance R1 mOhm/m 0.333 0.383 0.383 0.239– Positive reactance X1 mOhm/m 0.157 0.158 0.112 0.115– Impedance Z1 mOhm/m 0.368 0.414 0.399 0.266Impedance per unit length of current paths in case of failure– AC resistance per unit length RF mOhm/m 0.666 0.674 0.664 0.548– Positive reactance per unit length XF mOhm/m 0.511 0.530 0.436 0.446– Impedance per unit length ZF mOhm/m 0.839 0.857 0.795 0.706Zero phase-sequence impedance acc. to VDE 0102
Phases R0 mOhm/m 1.419 1.429 1.301 1.191-N X0 mOhm/m 0.691 0.702 0.590 0.632
Z0 mOhm/m 1.579 1.592 1.458 1.349Phases R0 mOhm/m 1.027 1.139 1.065 1.956-PE X0 mOhm/m 0.641 0.529 0.507 0.507
Z0 mOhm/m 1.211 1.256 1.179 1.082Short-circuit resistanceRated peak withstand current Ipk kA 17 32 36 40Rated short-time withstand current Icw kA 5.5 10 14 16Rated operating voltage Icw kA 10 16 18 20Number of conductors 5 5 5 5Conductor cross-section L1, L2, L3 mm2 63 63 66 108
N mm2 63 63 66 1081/2N mm2 63 63 66 66PE mm2 63 63 66 1081/2 PE mm2 63 63 66 66
Conductor material Cu Cu Cu CuMax. interval between trunking unit supports atnormal mechanical loadingEdgewise m 4 4 4 4Edgewise with BD2-BD1) m 4 4 4 4Flat m 3.5 3.5 3.5 3.5Combustive energy kWh/m 1.32 1.32 1.32 1.32
Notes 1) when using distance bracket BD2-BD.
Tap-off units Rated current Ie25 A 63 A 125 A 250 A 400 A
Switching capacity of contact system AC-22B – – – –Switching capacity of the built in switch-disconnector toIEC/EN 60 947-3 at 400 V
– AC-22B AC-21B – –
Max. admissible rated prospective short-circuitwithstand current when tap-off units with miniaturecircuit-breakers are used:
10 kAeff: for higher rated prospective short-circuit currents, refer to ”Back-up protection“ for miniature circuit-breakers.25 kAeff: for higher rated prospective short-circuit currents the upstream protective device must limit to: Max. let-through energy I2t = 12 x 104 A2s; Max. let-through energy ID = 9.5 kA
Technical DataCopper
Siemens LV 70 · 2004 5/81
BD2 System (160 A - 1250 A)
5
BD2C-.-500 BD2C-.-630 BD2C-.-800 BD2C-.-1000 BD2C-.-1250 General Technical Data
690/800 690/800 690/800 690/800 690/800III/3 III/3 III/3 III/3 III/3690 690 690 690 69050 – 60 50 – 60 50 – 60 50 – 60 50 – 60500 630 800 1000 1000
0.113 0.113 0.050 0.050 0.0320.053 0.054 0.053 0.053 0.0540.125 0.125 0.073 0.073 0.063
0.136 0.151 0.065 0.068 0.0410.053 0.053 0.053 0.053 0.0540.146 0.160 0.084 0.086 0.068
0.259 0.261 0.136 0.134 0.0940.218 0.222 0.226 0.227 0.2290.338 0.343 0.264 0.264 0.248
0.532 0.529 0.284 0.284 0.1860.313 0.314 0.261 0.264 0.2750.617 0.615 0.386 0.388 0.3320.473 0.470 0.258 0.270 0.1740.274 0.277 0.265 0.249 0.2650.547 0.545 0.370 0.367 0.317
59 64 84 90 9021 26 32 34 3428 32 40 43 435 5 5 5 5158 158 280 418 699158 158 280 418 699158 158 158 280 418158 158 280 418 699158 158 158 280 418Cu Cu Cu Cu Cu
4 4 3.5 3 22 2 1.75 1.5 13.5 3.5 3 2.5 1.52 2 2 2 2
Standards and specifications IEC/EN 60 439-1 and -2Climatic proofing Damp heat, constant, to IEC 60 068-2-78
Dampf heat, cyclic, to IEC 60 068-2-30Ambient temperaturemin./max. °C
–5/+40
Degree of protectionTrunking units IP52, IP54 with accessories on the busbar run,
construction type 2 IEC/EN 60 529Feeder units,tap-off units
IP54, construction type 2 IEC/EN 60 529
Mounting position Edgewise, flat, tap-off points on sideWeigth AnnexDimensions a page 5/84MaterialTrunking units,feeder units,tap-off units
Hot galvanized sheet steel with paint finish (RAL 7035), light grey insulated enclosure with BD2-AK1/...
Busbars Nickel-plated and tinned copper busbarsImportant engineering notesNot all tap-off units have a rated voltage of 690 V and a short-circuit rating that corresponds to the system as a whole.The short-circuit rating and rated voltage of the tap-off units used in a system must be appropriate for it.If the rated voltage of a tap-off unit does not match, choose one equipped with the appropriate components. Larger prospective short-circuit currents must be limited by fitting protective devices (such as circuit-breakers) upstream.
Technical Data
Siemens LV 70 · 20045/82
BD2 System (160 A - 1250 A)
5
Terminal capacities tap-off units
Cable and wiring entry for tap-off units
Designation Type L1, L2, L3 N PE Size of terminalscrews orboltsL1, L2, L3
Tap-off unitsmin.mm2
max. mm2
min.mm2
max. mm2
min.mm2
max. mm2
Up to 25 A BD2-AK1/S14 0.5 (f, st) 4 (so) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) –BD2-AK1/S18 0.5 (f, st) 16 (so, f, st) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) –BD2-AK1/A... 0.75 (so, st) 16 (so) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) –BD2-AK1/A...N 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so) 1 (so, f, st) 6 (so, st) –BD2-AK1/F... 0.75 (so, st) 16 (so) 1 (so, st) 6 (so) 1 (so, f, st) 6 (so, st) –BD2-AK1/F...N 0.75 (so, st) 16 (so) 0.75 (so, st) 16 (so) 1 (so, f, st) 6 (so, st) –
Up to 63 A BD2-AK.2X/S18 0.5 (f, st) 25 (f, st) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) –BD2-AK.2X/S27 0.75 (f, st) 10 (so, f, st) 1 (so, f, st) 6 (so, st) 1 (so, f, st) 6 (so, st) –BD2-AK.2X/S33 1.5 (f, st) 25 (f, st) 2.5 (so, f, st) 16 (so, st) 2.5 (so, f, st) 16 (so, st) –BD2-AK.2M2/A... 0.75 (so, st) 25 (st) 2.5 (so, f, st) 25 (st) 2.5 (so, f, st) 25 (st) –BD2-AK.2M2/A...N 0.75 (so, st) 25 (st) 0.75 (so, f, st) 25 (st) 2.5 (so, f, st) 25 (st) –BD2-AK.2X/F... 0.75 (so, st) 25 (st) 2.5 (so, f, st) 25 (st) 2.5 (so, f, st) 25 (st) –BD2-AK.2X/GB323 0.75 (so, st) 16 (so, st) 0.75 (so, st) 16 (so, st) Cable –BD2-AK.2X/GB633 0.75 (so, st) 50 (st) 0.75 (so, st) 50 (st) Cable –
Up to 125 A BD2-AK.3X/L40-L125 2.5 (so, st) 70 (st) 2.5 (so, st) 70 (st) 2.5 (so, st) 70 (st) –BD2-AK3X/GS00 16 70 16 70 10 70 M8BD2-AK.3X/GSTZ(A)00 16 70 16 70 10 70 M8BD2-AK.3X/GB1003 6 (so, st) 70 (st) 6 (so, st) 70 (st) Cable
armouring–
Up to 250 A BD2-AK41/GS1 6 150 6 150 6 150 M10BD2-AK41/GSTZ1 6 150 6 150 6 150 M10BD2-AK41/GB200 6 (so, st) 120 (st) 6 (so, st) 120 (st) Cable
armouring–
Up to 400 A BD2-AK51/GS2 10 2 120 10 2 120 10 2 120 M10BD2-AK51/GSTZ2 10 2 120 10 2 120 10 2 120 M12BD2-AK52/GB400 10 (so, st) 2120 (st) 10 (so, st) 2 120 (st) Cable
armouring–
Notes so = solid, st = stranded, f = flexible with ferrule
Tap-off unitsBD2-AK1/... BD2-AK.2... BD2-AK.3... BD2-AK41/GS... BD2-AK51/GS...
Cable grommets M25 2) – – KT 3 3) 2 x KT 3 3)
Cable gland 1) – M25, 32, 40 M25, 40, 63 – –For cable mm 11 – 16 11 – 27 11 – 42 14 – 54 14 – 54
Min./max. cable entry capacity for multi-core cablesNYY... mm2 5 1.5 to 5 4 5 1.5 to 5 16 5 1.5 to 5 25 – –NYCWY... mm2 4) 4 1.5 to 4 2.5 4 1.5 to 4 16 4 1.5 to 4 70 5 1.5 to
4 1502 5 1.5 to 2 4 150
Cable entry plate for singe-core cable(plates fitted, undrilled)
Max. number of cable entries – – – 10 M40 10 M40
Notes 1) For cable glands: use plastic cable glands with strain relief(not included as standard).
2) Strain relief in BD2-AK1/...3) With strain relief4) Fifth conductor: concentric conductor
Technical Data
Siemens LV 70 · 2004 5/83
BD2 System (160 A - 1250 A)
5
Terminal capacity of feeder units
Cable and wiring entry for feeder units
Cable entry plate for single core cable feeder systems(undrilled cable entry plate)
Cable entry plate for single core cable with centre feeder systems(undrilled cable entry plate)
Designation Type L1, L2, L3 N PE Size of terminalscrews or bolts L1, L2, L3, N, PE
min.mm2
max. mm2
min.mm2
max. mm2
min.mm2
max. mm2
Feeder unitswith terminal bolts
BD2.-250-EE (1–3) x 6 1 x 150 2x 70
(1–3) x 6 1 x 150 2x 70
(1–3) x 6 1 x 150 2x 70
M10
BD2.-400-EE (1–3) x 10 1) 1 x 240 2x 120
(1–3) x 10 1) 1 x 240 2x 120
(1–3) x 10 1) 1 x 240 2x 120
M12
BD2.-1000-EE (1–3) x 10 1) 2 x 240 3x 185
(1–3) x 10 1) 2 x 240 3x 185
(1–3) x 10 1) 2 x 240 3x 185
M12
BD2.-1250-EE (1–4) x 10 1) 3 x 300 4x 240
(1–4) x 10 1) 3 x 300 4x 240
(1–4) x 10 1) 3 x 300 4x 240
M12
Centre feeder unitswith terminal bolts
BD2.-400-ME (1–3) x 10 1) 2 x 240 3x 185
(1–3) x 10 1) 2 x 240 3x 185
(1–3) x 10 1) 2 x 240 3x 185
M12
BD2.-1000-ME (1–5) x 10 1) (1–5) x 300 (1–5) x 10 1) (1–5) x 300 (1–5) x 10 1) (1–5) x 300 M12BD2.-1250-ME (1–7) x 10 1) 6 x 300
7x 240(1–7) x 10 1) 6 x 300
7x 240(1–7) x 10 1) 6 x 300
7x 240M12
1) minimum possible cross-section for cable lugs
Feeder units BD2.-250-EE BD2.-400-EE BD2.-1000-EEBD2.-400-ME
BD2.-1000-ME BD2.-1250-EE BD2.-1250-ME
Cable grommets 1 x KT3 2) 2 x KT4 2) 3 x KT4 2) 6 x KT4 2) 4 x KT4 2) 8 x KT4 2)
For cable o mm 14 – 54 14 – 68 14 – 68 14 – 68 14 – 68 14 – 68
2) with strain relief
Feeder units BD2.-250-EE BD2.-400-EE BD2.-1000-EE BD2.-1250-EE
Cable entry plate BD2-250-EBAL BD2-400-EBAL BD2-1000-EBAL BD2-1250-EBALNumber of cable entries(max.)
10 x M32 10 x M40 15 x M40 36 x M50
Number of cable entries(max.)
5 x M40 – 6 x M50 and 4 x M40
–
Notes Use plastic cable glands with strain relief (not included as standard).
Feeder units BD2.-400-ME... BD2.-1000-ME BD2.-1250-ME
Cable entry plate BD2-400-MBAL BD2-1000-MBAL BD2-1250-MBALNumber of cable entries(max.)
12 x M40 and 3 x M32
31 x M40 36 x M50
Number of cable entries(max.)
6 x M50 and 4 x M40
16 x M50 and 4 x M40
–
Notes Use plastic cable glands with strain relief (not included as standard)
Dimension drawingsTrunking Units, Branch Units
Siemens LV 70 · 20045/84
BD2 System (160 A - 1250 A)
5
Straight trunking units
BD2.-...-...
Centre of clamp terminal
Junction unitsL units
BD2.-...-LR-...(-G*)BD2.-...-LL-...(-G*)
BD2.-...-LV-...(-G*)BD2.-...-LH-...(-G*)
Z units
BD2.-...-ZR-...BD2.-...-ZL-...
BD2.-...-ZV-...BD2.-...-ZH-...
330
c
Length (m) Number of double conductor run tap-off pointsn x 500 n x 1000
0.5 to 1.251.26 to 2.252.26 to 3.25
–4 to 88 to 12
–2 to 44 to 6
On optional lengths, it may not be possible to fit tap-off units to all tap-off points
220307 (557)
16716
3
n × 500 (1000)
c
Rated current (A) c mm160 to 400 68500 to 1250 126
x =
360–
1250
G* = 85 –175
70
y = 360–1250
70
c
x =
360–
1250
y = 360–1250
G* = 85 –175
c
70x = 360–600
z = 3
40–1
250
y = 360–600
Rated current (A) z mm160 to 400 140 to 1250500 to 1250 260 to 1250
y = 360 – 600
c
x = 360 – 600
z
Dimension drawingsJunction Units
Siemens LV 70 · 2004 5/85
BD2 System (160 A - 1250 A)
5
T units
BD2.-...-TRBD2.-...-TL
BD2.-...-TVBD2.-...-TH
cc1184
184 70
167
275 275
163
275
Rated current (A) c mm c1 mm160 to 400 68 64500 to 1250 126 122
16716
3
70
184
275 275
275
184
c1 c
Dimension drawingsJunction Units
Siemens LV 70 · 20045/86
BD2 System (160 A - 1250 A)
5
Cross units
BD2.-...-KRL
BD2.-...-KVH
cc1184
184
70
167
275 275
275
275
184
163
Rated current (A) c mm c1 mm160 to 400 68 64500 to 1250 126 122
167
163
70184
184
c1 c
275 275
275
275
184
Dimension drawingsJunction Units
Siemens LV 70 · 2004 5/87
BD2 System (160 A - 1250 A)
5
Flexible junction units
U shape
Z shape
BD2-...-R
182
a1
c
bc2
c1
156.6
c3
a3 a2 a4
167
163
205
Type a1 a2 a3 a4 b C c1 c2 c3BD2-400-R 1250 424 187 187 79 68 64 101 50BD2-800-R 1750 786 350 250 146.5 126 122 195 145
c6 R
Type Shape a5 a6 c6 RBD2-400-R U – – 220 min.
110BD2-400-R Z 175 1000 355BD2-800-R U – – 340 min.
170BD2-800-R Z 530 1590 400
c6
a5
a6
Dimension drawingsDistribution Board Feeder Units, Feeder Units
Siemens LV 70 · 20045/88
BD2 System (160 A - 1250 A)
5
Distribution feeder unit
BD2.-400(1000)-VE BD2.-250-VE
Enclosure cut-out BD2.-1250-VE
End feeder units
BD2.-250-EE
c
c1
c2
163
200
307
295
4 × 6512.5
108.
518
3.5
123
11
90 102
285.
5
8
58
158
c
185
167
a b
6.6
Type a b C c1 c2BD2.-250-VE 34 68 121 64 84BD2.-400-VEBD2.-1000-VE 92 126 155,5 122 142BD2.-1250-VE
129 146
154
338
163
200
84
242
88
452
124
31.544
o 12.5
64.5
77
88
112
122
9
40
64
74
143.
5
100
20
270
3
14 × 9
163
245
270
290
300
250
478
563
200
75
Dimension drawingsFeeder Units
Siemens LV 70 · 2004 5/89
BD2 System (160 A - 1250 A)
5
End feeder units
BD2.-400-EE BD2.-1000-EE
BD2.-1250-EE
4064
105
200
4012
2
9
100
50
125
219
395
420
440
85163
423
100
387.5
605
687
200
9 14 × 9
304
170
15
200
186
4012
216
3
258
386.5
606
688
200
366
587
611
631
86
Dimension drawingsCabling Boxes, Centre Feeder Units
Siemens LV 70 · 20045/90
BD2 System (160 A - 1250 A)
5
Cabling boxes
BD2-400-KR (BD2.-400-EE)
BD2-1000-KR (BD2.-1000-EE)
BD2-1250-KR (BD2.-1250-EE)
Centre feeder unit
BD2.-400-ME
223
247.5
191
924
0
100
285
223
253
14 × 9
308
332.5
191
308
325
338
100
370
190.
5
9.5
325
481
100
473
488.5
26.5
950
1000
650
250
686
9
12
27
624
753
224
2716
5
40
40 64
163 24
0
100
285
223
253
14 × 9
Dimension drawingsCentre Feeder Unit
Siemens LV 70 · 2004 5/91
BD2 System (160 A - 1250 A)
5
Centre feeder unit
BD2.-1000-ME
BD2.-1250-ME
1200
1250
680
190
916
936
9
12
27
654
783
327
374
2718
9
40
40 122
163
40
40 163
122
Dimension drawingsTap-Off Units
Siemens LV 70 · 20045/92
BD2 System (160 A - 1250 A)
5
Tap-off units up to 25 A
BD2-AK1/... BD2-AK1/3SD163...BD2-AK1/3DKS...BD2-AK1/3X13...
BD2-AK1/2CEE163... BD2-AK1/CEE165...
Tap-off units up to 63 A
20.5
144190
93
199.
712
6.2
75
C2
C1 C2
C1
C2
C1
170
170
170
170
Type c1 c2BD2-AK1/3SD163... 71 13BD2-AK1/2CEE163... 88 44BD2-AK1/CEE165... 106 52
101
2050
For M25, 32, 40, 63
BD2-AK02X/F...BD2-AK02X/GB...BD2-AK02X/S...
331
214
BD2-AK02M2/A...
331
214
Dimension drawingsTap-Off Units
Siemens LV 70 · 2004 5/93
BD2 System (160 A - 1250 A)
5
Tap-off units up to 63 A
Tap-off units up to 63 A
BD2-AK2X/CEE635S33 (/FORM P)
BD2-AK2X/3BS133...
BD2-AK2X/CEE325S33 (/FORMP)BD2-AK2M2/CEE325A323BD2-AK2X/2CEE165S14BD2-AK2M2/2CEE165A163BD2-AK2X/2CEE165S27 (/FORMP)
BD2-AK2M2/2SD163CEE165A163
For M32
20
101
50
9
For M25, 32, 40
5035
4
77
314 7
BD2-AK2X/F...BD2-AK2X/GB...BD2-AK2X/S...
205
320
BD2-AK2M2/A...
160
320
for M20
77
Type b1 b2BD2-AK2X/CEE325S33 (/FORMP) 98 –BD2-AK2M2/CEE325A323 98 –BD2-AK2X/2CEE165S14 86 –BD2-AK2X/2CEE165S27 (/FORMP) 86 –BD2-AK2M2/2SD163CEE165A163 86 54BD2-AK2M2/2CEE165A163 86 –BD2-AK2X/3BS133... – 54
b2 b2
b1
b2 b1
Dimension drawingsTap-Off Units
Siemens LV 70 · 20045/94
BD2 System (160 A - 1250 A)
5
Tap-off units up to 125 A
BD2-AK03X/GSTA00 BD2-AK03X/GB1003BD2-AK03X/F...
BD2-AK03M2/A...
BD2-AK03X/L... BD2-AK03X/L...+BD2-LD0G BD2-AK03X/FS...
Type HBD2-AK03X/G... 101BD2-AK03X/F...BD2-AK03X/FS...BD2-AK03M2/A...BD2-AK03X/L...BD2-AK03X/L...+BD2-LD0G
141
BD2-AK03X/FS...
101
2050
For M25, 32, 40, 63
101
431
214
431
214
160
101
26
141
69
141
69
Dimension drawingsTap-Off Units
Siemens LV 70 · 2004 5/95
BD2 System (160 A - 1250 A)
5
Tap-off units up to 125 A
BD2-AK3X/GS00BD2-AK3X/GB1003
BD2-AK3X/GSTZ00
BD2-AK3X/L...-3 BD2-AK3X/L...-4 BD2-AK3X/L...+BD2-LDG
Tap-off units up to 400 A
Low-voltage h.b.c. fuse bases Low-voltage h.b.c. fuse switch-disconnector
20
101
50
9
For M32For M25, 40, 63
5047
4
434 7 for M20
60
R 175
205
440
55R 114R 114
18
73
67
129
191
l
h5.
557
156.5206
170
54.5
42
291
Type l HBD2-AK41/GS1 490 193BD2-AK41/GB200BD2-AK51/GS2 640 193BD2-AK52/GB400 258
209
400
250
l
h5.
557
156.5206
170
54.5
42
291
Type l HBD2-AK41/GSTZ1 490 193BD2-AK51/GSTZ2 640 193
209
400
Dimension drawingsAncillary Equipment Unit, Accessories
Siemens LV 70 · 20045/96
BD2 System (160 A - 1250 A)
5
Ancillary equipment unit
Protective sleeve Fire barriers
BD2-400-D BD2-1250-D +BD2-S90 (S120)-...
BD2.-(160, 250, 315, 400)-...
BD2-...-D
BD2.-500 (630, 800, 1000, 1250)-...
Spacer bracketBD2-BD
54h
10 15
77
for M20 For M25, 32, 40
Type hBD2-GKM2/F 101BD2-GKX/F 151
BD2-GKM2/F
160
205
320
BD2-GKX/F20
5
320
208
110
208
168
64
163
64
163
208
500
122
163
165
205
C
110
28
14
100
208
250
288
9
To secure systems directly to concrete walls, always use steel expansion bolts approved by the local building inspectorate.
For example: RICO, order ref. 15J1-A08/40Fischerwerke, type SLM8N, article no. 50521
Rated current (A) C160 to 1250 30 to 82
Dimension drawingsAccessories
Siemens LV 70 · 2004 5/97
BD2 System (160 A - 1250 A)
5
Vertical retaining elements
BD2-BWV BD2-BDV
End flangeBD2...-FE
Length of trunking unit
End of end flange = centre of clamp terminal
Fixing bracketBD2-...-BB
SpacersBD2-DSB
Vertical fixing bracket
BD2-BVFFlange fixing bracket
246
200
9
25
1615 135
48+
10-5
91
28–8
2
400+1
0-5
11
4327
600
640
15
Rated current (A) c mm160 to 400 68500 to 1250 126
c
167
Rated current (A) Dimensions C c1
160 to 400 86.5 48500 to 1250 144.5 77
169
199
33 c1
34
15
100
7.2
7.2
11
c
25
26
33
11
40
165
140
230
200
40
55
11514
0
16
9
Dimension drawingsAccessories
Siemens LV 70 · 20045/98
BD2 System (160 A - 1250 A)
5
Clamp terminal
BD2-...-.K
Flanges for protection to IP54Flat mounting position
BD2-FF BD2-FAS
Vertical mounting position
Edgewise mounting position
BD2-FFE
Rated current (A) a mm160 to 400 68500 to 1250 126
330
a
167
6
.6
80
140
a b c364 170 17.5
a
b
c
a b c122 166 19
a
b
c
Type a b cBD2-400-VF 212 72 16BD2-1250- 212 130 16
a
b
c
Type a b cBD2-400-HF 362 72 16BD2-1250-HF 362 130 16
a
b
ca b c183 170 17.5
ab
c
Type a b cBD2-400-HFE 182 72 16BD2-1250- 182 130 16
a
b
c
Dimension drawingsAccessories
Siemens LV 70 · 2004 5/99
BD2 System (160 A - 1250 A)
5
Sockets with adapter enclosure
BD2-CEE...
BD2-SD163
Adapter enclosure
BD2-AG
Adapter plate
BD2-APM BD2-APO
Type I1 I2BD2-CEE163 50 89BD2-CEE165 50 110BD2-CEE325 61 123
75
75
75
75
40
l2
l1
15
69
75
75
M25
26
403
10
60
75
R 6
38
60 7538
5.3
3.5
44 75
75
Notes
Siemens LV 70 · 20045/100
BD2 System (160 A - 1250 A)
5