BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

22
TRANSSOLAR KLIMAENGINEERING BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

description

BCIT NE01 Energy Upgrade and Retrofit Study Result Summary. Introduction. Transsolar Goals for Study: Understand the NE01 building and assess its current state Analyze the climate situation to drive passive design strategies - PowerPoint PPT Presentation

Transcript of BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

Page 1: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

BCIT NE01 Energy Upgrade and Retrofit StudyResult Summary

Page 2: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Transsolar Goals for Study:

• Understand the NE01 building and assess its current state

• Analyze the climate situation to drive passive design strategies

• Engage students and faculty for feedback and idea generation through a workshop

• Investigate potential for comfort improvements in the space and energy reduction

• Develop an energy strategy to meet the ambitious Factor Four goals

Introduction

Page 3: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Building Understanding

3

HVAC System

• All-air Conditioning System

• Centralized Air Handling Units

• Air Recirculation

• Centralized reheat coils

• BCIT district heating supply with back-up local gas boilers

Page 4: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Building Understanding

4

Lighting

Page 5: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Creating a Base Case

5

Calculated values

Adjusted Energy Consumption for Comparison

Page 6: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Creating a Base Case

6

Load Type Description Current Case Base CaseVentilation Air Supply Flow Rate 1266 m3/hour 1266 m3/hour

Ventilation Control 8:30 am – 9:30 pm 8:00 am – 10:30 pm

Economizer Mix Set Temperature 13°C N/A

Minimum Outdoor Air Supply 2 ACH 100% Outdoor Air

Heating Daytime Set Point

Temperature

21°C Air Temp. 21°C Operative Temp.

Nighttime Set Point

Temperature

15°C Air Temp. 15°C Operative Temp.

Simulated values

*without lighting or plug-loads

*

Page 7: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Building Understanding

7

Current Thermal Comfort Level

Page 8: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING 8

Base Case Thermal Comfort Level

Page 9: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Interventions

9

Intervention Affected Area

1 Operable Windows on Façade Façade

2 Improve Window Quality Façade

3 Exhaust Heat Recovery Whole Building

4 Light Redirection Façade

5 Lighting Controls Whole Building

6 Light bulb Retrofit Whole Building

7 Separate Conditioning from Ventilation

System

Whole Building

8 Insulation Enhancement Façade

9 Increase Window Area Façade

10 Internal Skylight Shading Cafeteria Atrium

11 Instant Hot Water Heaters Core

Page 10: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Intervention Evaluation

10

Intervention Energy Savings Cost Comfort Complexity/Effort Recommended

Operable Windows on

Façade

Small Reduction Medium + Low 1

Improve Window Quality Small Reduction Medium + Low 2

Exhaust Heat Recovery Significant Savings Medium 0 High 3

Light Redirection No Savings Low 0/+ Low 5

Lighting Controls Savings Low 0 Low 4

Light bulb Retrofit Savings Low 0/+ Low 4

Separate Conditioning from

Ventilation System

Significant High + Medium 1

Insulation Enhancement   Medium + Medium 2

Increase Window Area on

North Façade

+ High + High 5

Evaluation Matrix – Façade Affected Interventions

Page 11: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

11

NE01 Building Upgrade Strategy:

1. Building-Wide Ventilation: Split HVAC with Natural Ventilation

2. Façade Improvements

3. Integration of Heat Recovery in Ventilation System

4. Lighting Upgrades

5. Additional Interventions

Page 12: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

12

1. Building-Wide Ventilation: Separation and Natural Ventilation

• Radiative conditioning system

• Dedicated outdoor air ventilation system (driven by air quality not heating)

• Natural Ventilation through installation of operable windows along facade

Page 13: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING 13

Night Flushing Effect – Transsolar Office

Effect of opening windows

Page 14: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

14

Thermal Comfort Level With Split HVAC and Natural Ventilation (incl. nighttime flushing)

Page 15: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

15

2. Façade Improvements

• Double Glazed Windows with High Quality Frame

• Internal Insulation Addition

Page 16: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

16

3. Integration of Heat Recovery in Ventilation System

• Heat Recovery Installation in Central Air Handling Units

• Unit-by-Unit Investigation to determine best heat recovery solution

Page 17: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

17

Final Thermal Comfort Level

Page 18: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

18

4. Lighting Improvements

• LED Lighting in common spaces (bathrooms, corridors, etc.)

• Occupation and Daylight controls in common spaces

• Vacancy controls in offices and classrooms

Page 19: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING 19

5. Additional Interventions

• Natural ventilation and shading in cafeteria atrium space

• Replacement of hot water systems for bathrooms with electrical instantaneous hot water heaters

Page 20: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

20

Page 21: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Recommendations

21

Energy Reduction Potential

Page 22: BCIT NE01 Energy Upgrade and Retrofit Study Result Summary

TRANSSOLAR KLIMAENGINEERING

Thermal Simulation Weather Data Validation

22