BC-RFG-IB-04/13-02
Instruction Booklet
BELLCHECK RETRO-FIT
SOUNDER/STROBE
ALARM GONG
![Page 2: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/2.jpg)
![Page 3: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/3.jpg)
Bellcheck® Instruction Booklet
Copyright This instruction booklet is property of Project Fire Products Ltd and must not be used or copied without its written permission.
Information While every effort has been made to ensure that the information contained within this document is correct, Project Fire makes no guarantee for completeness or accuracy. Project Fire Products Ltd reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligation.
Bellcheck is a registered product name of Project Fire Products Ltd.
![Page 4: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/4.jpg)
![Page 5: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/5.jpg)
Contents
01 Operating Principle03 On-site Requirements05 Installation07 Electrical Information08 Wiring Diagram09 Commissioning10 Typical Setup11 Testing12 Troubleshooting13 Technical Support14 Warranty
![Page 6: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/6.jpg)
Operating principle
General operation
Under normal, standby conditions, the pressure above the clack is greater or equal to the pressure below the clack; this holds the alarm valve in the closed valve position. By turning the Bellcheck pump on at the key-switch the pump operates and starts to pump water from above the alarm valve through an orifice plate to the chamber below the alarm valve clack.
As the pressure acting on the under-side of the clack is now greater than the pressure acting above it, the clack inside the alarm valve is pushed open. This allows water to pass through the annular groove to the mechanically driven alarm gong. The flow of water through the gongs chamber causes the gong to emit a continuous ring for as long as the clack is open.
A pressure-switch or flow-switch detects the increase in pressure (or flow) and submits an electronic signal to a remote alarm panel or suitable equivalent. This provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch back to the standby position.
Overview
The Bellcheck® system provides a simple, water saving method for the water motor alarm testing to be carried out as part of the mandatory routine. Rules stipulate that as part of this routine, the gong is exercised on a regular basis. Turning the key-switch and allowing the gong to ring for a predetermined length of time fulfils the testing requirements. In the field, this means that suitable personnel can easily perform a fully code compliant test at the appointed time on each occasion using Bellcheck®.
01
![Page 7: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/7.jpg)
02
WATER SUPPLY
TO DRAIN
SYSTEM
![Page 8: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/8.jpg)
03
On-site Requirements
Space requirements
Before installation it is important to determine that there is enough free space for the Bellcheck line to be installed. Installation requires two mechanical tees & two barrel nipples (not provided) positioned above and below the wet alarm valve arrangement (positioned 880±2 mm apart). In situations where space is restricted, replace the two barrel nipples with two short lengths of 1” BSP threaded galvanised pipework to allow for the Bellcheck to fit around the valve-station. In some scenarios the length of Bellcheck may need to be extended by replacing the 1” vertical pipe with a longer piece of pipe to suit site conditions.
Water-supply non-return valve
Please note that Bellcheck® works by pressurising the chamber beneath the alarm-valve clack. As the pressure increases water should force the ‘water-supply’ non-return valve shut and cause the chamber to increase in pressure until the alarm-valve clack lifts. It is important to establish that this non-return valve on the water supply is functioning correctly prior to the installation.
Alarm-valve
The wet-alarm valve used with Bellcheck® must meet the requirements set out in BS EN12259-2:1999 Part 2: Wet alarm valve assemblies standards.
![Page 9: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/9.jpg)
04
Fig. 1
![Page 10: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/10.jpg)
05
Installation
Bellcheck should be installed by a competent fire sprinkler installer and wired up by a qualified electrician.
Ensure that the system is drained down and isolated prior to any works.
1. Assemble (hand-tight only) the Bellcheck® arrangement, including mechanical tees and marry it up to the valve station.
2. Remove the Bellcheck® line leaving just the mechanical tees and union-halves clamped to the existing pipework in the correct positions (see figure 3).
3. Mark the mechanical tee positions before removing them and drilling the two 1” connections into the pipe wall.
4. Re-connect the two mechanical tees back onto the pipe.
5. Marry up the Bellcheck® line with the union-halves (as per figure 4).
6. Ensure that the Bellcheck® line is aligned correctly and fully tighten the union connections using a spud wrench.
7. Use the temporary commissioning lead to connect the Bellcheck® spur box to a suitable 220v ~ 50Hz mains power supply.
![Page 11: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/11.jpg)
06
Fig. 4
Fig. 3
![Page 12: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/12.jpg)
07
Electrical Information
Bellcheck can be setup and tested by a competent fire sprinkler installer using the temporary commissioning lead. However, all permanent wiring must be carried out by a qualified electrician.
1. Remove the temporary commissioning lead and isolate the unit.
2. Connect a permanent 220 v ~ 50Hz; 2 amp power supply to the Bellcheck® spur box.
3. Wire the pressure-switch (or flow-switch) to the key-switch and fire detection panel.
![Page 13: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/13.jpg)
08
Wiring Diagram
Fig. 5
G
L
N
PUMP N
PUMP L
WF
WF
+
-
E
L
N
COM
B
COMB
COMB
EL N
FIRE DETECTION PANEL STROBE / SOUNDER
PRESSURE-SWITCH
CIRCULATING PUMP
SOLENOID VALVE
KEY-SWITCH
FUSE-SPUR
POWER SUPPLY
![Page 14: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/14.jpg)
09
Commissioning
1. Turn the key to standby at the key-switch (9).
2. Open the Bellcheck® pump inlet valve (6) and the pump outlet valve (7).
3. Check that all valves are now in the correct position according to the valve schedule.
4. Open the alarm manual test valve (3) until the alarm gong (5) sounds.
5. Close the alarm manual test valve (3) on the manual test line. 6. Turn the key-switch to test. Now check that both the pump and water-flow
green lights are on.
7. Allow the alarm gong (5) to ring for 30 seconds. Now turn the key-switch to standby and remove the key.
8. Check that all valves are left in the correct position corresponding to the valve schedule.
Valve Schedule
1
2
3
4
5
6
7
8
9
12
13
14
15
Main inlet valve
Main drain valve
Alarm manual-test valve
Alarm isolating valve
Water-motor alarm gong
Pump inlet valve
Pump outlet valve
n/o
n/c
n/c
n/o
n/o
n/on/o Normally Openn/c Normally Closed
Bellcheck Pump
Key-switch
Strobe/sounder
Strainer
Maintenance isolation valve
Flow-switch
n/o
![Page 15: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/15.jpg)
10
Fig. 6 Typical layout only
Typical setup
1
23
4
5
6
7
8
9
12
13
14
15
WATER SUPPLY
SYSTEM
TO DRAIN
![Page 16: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/16.jpg)
Weekly Test
Weekly Test (Bellcheck®)REF Fig. 6
1. Advise all applicable parties and alarm receiving stations of the planned routine test.
2. Visually check that the main inlet valve (1) is secured open.3. Check and record the pressures at the ‘B’ and ‘C’ pressure gauges.4. Insert the key into the key-switch (9); turn the key to the test position.5. When the water motor alarm gong (5) has sounded for 30 seconds, turn the key
to the standby position (9). (Note: this will cause the clack to re-seat, the gong to stop ringing and the water in the gong line to stop flowing to drain).
6. Remove the key.7. Record the pressures at the ‘B’ and ‘C’ pressure gauges.8. Contact any alarm stations to check that the system operated signal has operated
and reset. Or reset any locally connected alarm panel.9. Record the test results.
Weekly Test (traditional)REF Fig. 6
1. Advise all applicable parties and alarm receiving stations of the planned routine test.
2. Visually check that the main inlet valve (1) is secured open.3. Check and record the pressures at the ‘B’ and ‘C’ pressure gauges.4. Fully open the test valve (3) and record the time taken for the mechanical alarm
gong to ring.5. Allow the gong to ring for 30 seconds continuously , now close the test valve (3).6. Record the pressures at the ‘B’ and ‘C’ pressure gauges.7. Contact any alarm stations to check that the system operated signal has operated
& reset and/or reset any locally connected alarm panel.8. Record the test results.
11
![Page 17: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/17.jpg)
12
1. Open main drain valve (2) to flush any possible obstructions, after 30 seconds close the valve.
2. Open the alarm isolating valve (4) to flush out any possible obstructions in the gong line, after 30 seconds close the valve.
3. Retry Bellcheck® weekly test.
No Water-motor alarm
Water-motor alarm-gong will not stop ringing after a weekly test has been completed:
No fire alarm 1. Check there is power to the key-switch.2. Check the control module on the pump for any error
messages, follow the on screen instructions for pump maintenance.
3. Check the correct valves have been opened/closed using valve schedule in this booklet.
4. Check the signal wiring using the wiring diagram in this booklet.
5. Retry Bellcheck® weekly test.
1. Turn the Bellcheck® key-switch to standby. Close alarm isolating valve (4).
2. Remove & clean the filter in the strainer (13). Replace the filter.
3. Remove the alarm gong cover. Check the clapper is still in place and clean the ø3 mm orifice hole.
4. Retry Bellcheck® weekly test.
Troubleshooting
Bellcheck should be troubleshooted by a competent fire sprinkler installer and wiring checked by a qualified electrician.
If Bellcheck is still not operating correctly contact your service and maintenance company.
![Page 18: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/18.jpg)
13
Project Fire Products Ltd
Pasturefields Industrial EstatePasturefields LaneHixonStaffordshireST18 0PHUK
tel +44 (0)1889 270999fax +44 (0)1889 272735email [email protected] www.projectfireglobal.com
Manufacturer:
Technical Support
For technical support contact the manufacturer.
Technical information and product support is also available for download from our website (www.projectfire.co.uk).
![Page 19: BC-RFG-IB-04/13-02 - Project Fire Products€¦ · provides an alarm signal to indicate that the sprinkler system is in operation. The test is completed by turning the key-switch](https://reader034.fdocuments.in/reader034/viewer/2022042204/5ea648e68e27bf7414386b19/html5/thumbnails/19.jpg)
14
Warranty
Project Fire Products warrants its enclosed Bellcheck® alarm gong tester to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. Project Fire Products makes no other express warranty for this alarm gong tester. No agent, representative, dealer or employee of the company has the authority to increase or alter the obligations or limitations of this warranty. The companies obligation of this warranty shall be limited to the repair or replacement of any part of the alarm gong tester, which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning Project Fire’s number +44(0)1889 271271 for a return authorization number, send defective units postage prepaid to Project Fire, Pasturefields Industrial Estate, Pasturefields Lane, Hixon, ST18 0PH, UK. Please include a note describing the malfunction and suspected cause of failure. The company shall not be obligated to repair or replace the units which are found to be defective because of damage, unreasonable use, modification or alterations occurring after the date of manufacture. In no case shall the company be liable for any consequential or incidental damages for breach of this or any other warrant, expressed or implied whatsoever, even if the loss or damage is caused by the companies negligence or fault.