    Setting Panel Comms Task for Insight 4 Preparing Insight for Panel Connection Enrol a Panel 5 Practical Exercise 1 Programming Introduction 8

    Practical Exercise 2 Zone Programming 9

    Practical Exercise 3 Siren Lists 10 Practical Exercise 4 Area Programming 11 Practical Exercise 5 Systems Area and Area Lists 12 Practical Exercise 6 Area Operation and Alarm Handling 13 Practical Exercise 7 Module Programming, Terminal keypad 14 Practical Exercise 8 Users and User Types 15 Consolidation 1 Security and User control 16 Consolidation 2 Advanced Security 17 Practical Exercise 9 Communications, Alarm Monitoring 18 Practical Exercise 10 Access control Introduction 19

    Practical Exercise 11 Calculated Auxiliaries 20 Consolidation Exercise 3 Everything 21

    Appendices

    Appendix 1 Adding System Inputs to the System Area 24 Appendix 2 Assigning a Prox Card to a User 25 Appendix 3 Access Group ENTRY DOOR 26 Appendix 4 How they all fit together 27

  • 4

    Setting Panel Comms Task for Insight Computer based programming with Insight

    Panel Comms Task Settings

    1. Insight should ALWAYS be programmed in CT001. No other comms task should use CT001.

    Note: changes made to ALL comms tasks should be done in the idle state. Menu 7-3-1

    CT001 Idle -> Insight

    2. Press HELP 9 to enter into the Insight comms task programming.

    PANEL OPTIONS Information details Programmed options

    CT001 Panel ID: 00000000 (00999999)

    Must not be set to all 0s. The first 2 digits MUST be 00. Any Hex values can be used 0,1,2,3,4,5,6,7,8,9, A,B,C,D,E or F

    CT001 Panel ID: 00999999

    CT001 Port to use: 0

    Select the Serial port connected to on the panel UART. Port 0 should only be used for commissioning.

    CT001 Port to use: 1

    CT001 Baud Rate: 9600

    Serial port communication speed. This should be set to default 9600.

    CT001 Baud Rate: 9600

    CT001 . . . . I A C E RS232 n n n n n n n n

    ACE Should be flagged to Y to enable comms via RS232.

    CT001 . . . . I A C E RS232 n n n n n Y Y Y

    The other options in the Insight comms task should be left at default. These options are for other connection methods. 3. Press HELP 0 to go back out. 4. Make the Comms Task Active by Pressing 9

  • 5

    Preparing Insight for Panel Connection Computer based programming with Insight

    Setting up Insight for Panel connection

    1. Once Insight has been installed on the computer, the start menu will have an Inner Range folder. This contains links to the Insight modules. Ensure the Database Tool and Launch Pad are running. This is indicated by two icons in the system tray.

    2. To run Insight, the Database tool must be started. Right Click on the Database Tool and select Start Database. The red slash will disappear from the icon once the database is started.

    3. Start the Launch Pad application by clicking on the little man icon once. This will bring up the Insight Launch Pad screen to let you run the Insight modules. (Insight Pro version shown below)

    4. Click the Enrol Panel icon from the Launch Pad. This will set up panel connection for programming. A login window will be presented for the Username and Password to be entered. The default login credentials are installer/installer or admin/admin. Login as Installer.

  • 6

    5. Fill in the Enrol Panel dialogue box as follows. Note: The fields with the icon must match with what has been programmed in the panel Insight comms task and the panel info screen.

    Identification. Panel Name: Used to identify the enrolled panel in the Insight program. Panel ID: This must be same as the setting in the Insight Comms task. Serial Number: Whilst logged off MENU 2 on the terminal will show the panel serial number. Communication. Protocol: Insight Encryption Key: Should be left blank unless encryption is used (Used to further encrypt panel to Insight communications) Connection: Serial Port > Panel UART since RS232 is used Baud Rate: 9600 same as comms task setting PC Serial Port: PC serial port connected to the panel (Device Manager will provide this info) Panel Server: LOCAL Once everything required has been entered, the Enrol Now button will be enabled. Click it to start the enrolment process.

  • 7

    If the enrolment process is successfully started, the progress indications can be seen. The programming that exists inside the panel will be transferred into Insight during the enrolment process. Once enrolment has completed, return to the Launchpad. 6. Run Insight Edit from the Launchpad. This is the application to program the system. 7. If required, login as the Installer. 8. Down the left hand side of the screen is a list of enrolled panels, connect to the enrolled panel via Serial.

    9. The panels online status bar will now indicate the panel is online and ready to be programmed when the panel is connected to Insight.

    10. The panel is now ready for programming to be done.

  • 8

    Practical Exercise 1

    Programming Introduction.

    1. Power-up a Training Module. 2. Check the Memory version, size and configuration. Menu ________ 3. Default the Memory to Standard configuration. Menu ________ 4. Secure the LAN. Menu ________ 5. Check Review to ensure all expected modules are present and secure. Menu ________ 6. Set General System options. (AC fail Time 30 mins) Menu ________ 7. Set Time and Date. Menu ________

    Question Time

    Q1: What memory configuration would be selected to allow for at least 48 LCD terminals, 8 Mini

    expanders and 65 reader modules? A: ____________________________________________________________________________ Q2: Before powering up the system, the pre-power check indicated a LAN resistance of 100 Ohms

    across A + B. Does this indicate a problem, if so, how would you overcome it? A: ____________________________________________________________________________

    ____________________________________________________________________________ ____________________________________________________________________________

    Q3: If more review information is required to help troubleshoot an issue in the system. Where do you

    find the option to enable this feature? A: ____________________________________________________________________________ Q4: How to filter review information to only show user operations from the keypad? A: ____________________________________________________________________________

    NOTES __________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________

  • 9

    Practical Exercise 2 Zone Programming

    1. Program 4 Zone Inputs: Menu ________

    Name Description SIXSRANT (Options) C01:Z01 Entry Door Reed nnnnnnnn C01:Z02 Entry PIR nnnnnnnn C01:Z03 Office PIR nnnnnnnn C01:Z04 Rear Door Reed nnnnnnnn

    Question Time Q1: How many maximum zone inputs on a system with a Control module, 2 Elite terminals and 1 E

    type expander module? A: ______________________________________________________________________________ Q2: In the zone programming options, what does the N option do to an input? A: ______________________________________________________________________________ ______________________________________________________________________________ Q3: Which menu is used to test the state of an Input? How to view multiple inputs on the screen at

    one time? A: ______________________________________________________________________________ NOTES __________________________________________________________________________________________ ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

    T

  • 10

    Practical Exercise 3

    Siren Lists 1. Program Siren List SL001 to include all Control module Sirens. Menu _________ Question Time Q1: Where are the 8 Ohm sirens connected to on a 2 Door Access Module and what are the terminals

    labelled as? A: ___________________________________________________________________________ Q2: What are the only modules that can directly drive an 8 Ohm horn siren? A: ___________________________________________________________________________ Q3: How many siren lists can you have under a 128k Apartments memory configuration? A: ___________________________________________________________________________ Q4: What would a siren list with a Y under the 0, 3 and 4 on the 1

    st options screen mean?

    (In Insight, tick boxes S000, S003 and S004) A: ___________________________________________________________________________ Q5: What is important to remember if E and B type expanders are used to drive horn sirens? A: ___________________________________________________________________________

  • 11

    Practical Exercise 4

    Area Programming 1. Check the Memory version, size and configuration. Menu ________ 2. Secure the LAN. Menu ________ 3. Check Review to ensure all expected modules are present and secure. Menu ________ 4. Set General System options. (AC fail Time 30 mins) Menu ________ 5. Set Time and Date. Menu ________ 6. Program 4 Zone Inputs as per Exercise 2. (Refer back to Ex2) 7. Program Siren List 1 to include all Control module sirens. Menu ________ 8. Program Area 001 as follows: Menu ________

    Area to Programme A001 Area Name Office Internal Siren mode Instant External Siren mode Instant Siren List SL001 Siren Time 5 minutes Siren Aux (Piezo) C01:X02 Entry Delay 5 seconds Exit Delay 5 seconds Entry Aux T01:X04 Exit Aux T01:X05 Comms Options: OCAN2S nnnnnn Close Aux T01:X06 Alarm1 Aux (Strobe) C01:X01

    Although, there are more options in Area programming, they will not be used in this course 9. Assign the following Zone Inputs to the Office Area: Menu ________

    Zone Description Process Group C01:Z01 Entry Door Reed Burglary Primary C01:Z02 Entry PIR Burglary Delayed C01:Z03 Office PIR Burglary C01:Z04 Rear Door Reed Burglary

    Question Time Q1: How many Areas can you have under a 32k Special configuration? A: ___________________________________________________________________________ Q2: From the keypad, what is the shortcut to get to the screen to allocate Process Groups to an input

    in an Area? A: ___________________________________________________________________________ NOTES ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

  • 12

    Practical Exercise 5

    System Area and Area Lists 1. Check the Memory version, size and configuration. Menu ________ 2. Secure the LAN. Menu ________ 3. Check Review to ensure all expected modules are present and secure. Menu ________ 4. Set General System options. (AC fail Time 30 mins) Menu ________ 5. Set Time and Date. Menu ________ 6. Program 4 Zone Inputs as per Exercise 2. 7. Program Siren List 1 to include all Control module sirens. Menu ________ 8. Program Area A001 (OFFICE) and Area A009 (SYSTEM). Menu ________

    Area to Programme A001 A009 Area Name Office System Internal Siren mode Instant None External Siren mode Instant None Siren List SL001 None Siren Time 5 minutes 0 Siren Aux C01:X02 None Entry Delay 5 seconds 0 Exit Delay 5 seconds 0 Entry Aux T01:X04 None Exit Aux T01:X05 None Comms Options: OCAN2S nnnnnn nnnnnn Close Aux T01:X06 T01:X02 Alarm1 Aux C01:X01 C01:X01

    9. Assign the following Zone Inputs to the Office Area: Menu ________

    Zone Description Process Group C01:Z01 Entry Door Reed Burglary Primary C01:Z02 Entry PIR Burglary Delayed C01:Z03 Office PIR Burglary C01:Z04 Rear Door Reed Burglary

    10. Assign the default System Inputs to the System Area. Menu ________ See APPENDIX 1 for more information

    11. Program Area List, AL001 called All Areas with Areas 1 and 9 only. Menu ________ Question Time Q1: What is special about AL001? A: ______________________________________________________________________ Q2: What memory configuration will allow 210 Area lists? A: ______________________________________________________________________

  • 13

    Practical Exercise 6

    Area Operation and Alarm Handling 1. Secure Area 1 - "Office". 2. Generate an alarm on one or more Zone Inputs in Area 1. 3. Acknowledge the alarm events. 4. Turn off the "Office" Area. 5. Secure the Area List "All Areas". 6. Generate an alarm on one or more Zone Inputs. 7. Acknowledge the alarm events. 8. Turn off the Area List "All Areas". 9. Repeat the above exercise, paying particular attention to the manner in

    which Entry and Exit delays affect alarm activations. 10. Also generate alarms on System Inputs such as Cabinet Tamper. 11. Turn off 24 hour part of System Area and test cabinet tamper. 12. Turn on 24 hour part of System Area and test cabinet tamper. 13. Turn on System Area then turn System Area off again. Now test cabinet tamper. Note the operation of the alarm system below. NOTES __________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

  • 14

    Practical Exercise 7 Module Programming Terminal keypad

    1. Program a Terminal, options as defined below: Menu ________ LCD Terminal to alter: T01

    T01 SMDLIATO Msgs: nYnYnYnn

    Try different option combinations

    T01 Led Mode None

    Try different options

    T01 Assoc. Area OFFICE

    Select OFFICE

    T01 Door None

    (this option is used for access control)

    T01 Acc IOAQZSPE Opts -> nnnnnnn

    DO NOT SET THE A option. The other options are used for access control

    T01 Extra .LNZ Options nnnn

    Q: What does the N option do? A: _____________________________________

    2. Secure the LAN after any changes are made to terminal Menu ________

    Programming. 3. Check functionality of Terminal and Display by securing and unsecuring an Area and an Area List. 4. Repeat the above exercise with different terminal Message options. (SMDLIATO) Question Time Q1: What happens if you set the A option that you are told not to set? A: ______________________________________________________________________ Q2: What memory configuration will allow 99 Terminals? A: ______________________________________________________________________ Q3: What would the abbreviation T100 mean and how is this module program? A: ______________________________________________________________________ NOTES ____________________________________________________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________ __________________________________________________________________________________________

  • 15

    Practical Exercise 8 Users and User Types

    1. Programming from Exercise 5 should still be in the panel. 2. Program an Area List, AL003 and named it Admin Areas This Area List should have Area 1, OFFICE only. Menu ________ 3. Program an additional User Type, the options as defined below: Menu ________

    User Type to Alter: UT003 U.Type 003 Name: ADMIN STAFF UT003 ON List -> Admin Areas UT003 OFF List -> Admin Areas UT003 Menu Grp -> ALL MENUS

    4. Rename the MASTER User (U00002) to MAXWELL POWERS. Menu ________ 5. Program an additional User, details as follows: Menu ________

    User to Alter: U00003 User 00003 Name PHILIP J FRY U00003 type -> ADMIN STAFF User 00003 PIN No. 03

    6. Log on as PHILIP J FRY and check operation of Areas, etc. Question Time Q1: What are the names and abbreviations of the default Users and User Types in the Concept

    system? A: _________________________________________________________________________________ Q2: What must be done with user programming (but not in the classroom) before you commission a

    system? A: _________________________________________________________________________________ NOTES ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

  • 16

    Consolidation Exercise 1 Combining Security with User Control

    Specifications: 1. All Zone Inputs are to be assigned to one area named OFFICE. 2. The whole system must be audible. 3. System Inputs should be assigned to an area named SYSTEM. 4. A strobe light will be installed on the outside of the building along with a horn siren. 5. Terminal LEDs to indicate the status of the OFFICE and SYSTEM areas. 6. A 12v Piezo screamer will be installed in the store room. 7. The Owner of the building ___________________ must be able to operate ALL areas. 8. One of the Sales Staff ___________________ must be able to operate only the OFFICE area. NOTES ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

    Front Door Reed

    Reception PIR

    Sales Office PIR

    Storeroom PIR

  • 17

    Consolidation Exercise 2 Advanced Security

    May need to document on the floor plan EVERYTHING that is to be installed Assume the 8-way Aux card is installed on C01 (X03 - X10)

    Specifications: 1. All Office Zone Inputs to be assigned to an area named OFFICE. 2. Warehouse Zone Inputs to be assigned to an area named WAREHOUSE. 3. The entrance PIR and REED need to be in an area called ENTRANCE. 4. The entrance reed will be wired back to a zone input on the Terminal. 5. The Terminal is installed on the inside of the entrance of the building. The ENTRANCE area is to be

    operated by ALL staff members. 6. The system must be audible, meaning firing sirens and piezos. 7. A secure location has been chosen to install the control module. There is a designated Comms Room in

    the Warehouse. Two Inputs (Reed and PIR) are protecting this area. These inputs will be in a separate area monitoring the Comms Room.

    8. A 5 second entry/exit timer will suffice for the commissioning of the system. 9. System Inputs are to be assigned to an area named SYSTEM. And Only the INSTALLER will have

    access to this area. 10. Terminal LEDs are to indicate the status of all programmed areas individually. 11. The Manager Sally Smith must be able to operate ALL BUILDING Areas. 12. The Receptionist Anna Bolic must be able to operate the OFFICE Area. 13. The Storeman Geoff Jones must be able to operate the WAREHOUSE Area. 14. An IT Technician will need access to ALL BUILDING Areas. 15. A Piezo screamer will be installed in each of the building areas. The screamer will activate when the area

    it is installed in goes into alarm. 16. A Strobe/Horn unit need to be installed in a location that is visible from the road. Additional Programming Practice Instructor will demonstrate Sub Area Processing/Time Zone Processing if time allows. 17. The ENTRANCE area will automatically arm/disarm with the OFFICE and WAREHOUSE areas. 18. The IT Technician will only have access to the system over the weekends.

    Warehouse PIR

    Office Reed

    Office PIR

    Entrance PIR

    Warehouse REED

    OFFICE

    WAREHOUSE

    Entrance Reed

  • 18

    Practical Exercise 9 Communications and monitoring

    Programming from Consolidation Exercise 1 or 2 could still be in the panel for this exercise. 1. Program a Telephone Number for a monitoring station as follows:

    Menu ________

    Phone # to program: TN001 Phone #001 Name: XL SECURITY Phone #001 is: 9753 3488

    2. Program a Contact ID Comms Task, as follows:

    Menu ________ Comm task to program: CT002 CT002 Idle -> Contact ID or IR fast

    Press HELP 9 to go to nested table.

    CT002 Client Code: 3333 CT002 1st No. > XL SECURITY CT002 2nd No. -> XL SECURITY

    Press HELP 0 to go back out. 3. Make the Comms Task Active. 4. Setup the OFFICE area from the Consolidation Exercise to report Open & Close activities to the

    monitoring station. Menu ________

    Question Time Q1: What do the abbreviations S and 2 mean in the options screen of Area programming? A: _____________________________________________________________________________ Q2: Which key is used to toggle between the Active and Idle states of a comms task? A: _____________________________________________________________________________ Q3: What must CT001 ALWAYS be set to? A: _____________________________________________________________________________

  • 19

    Practical Exercise 10

    Access Control Introduction

    Specifications: 1. All the building Zones to be assigned to one Area named OFFICE. 2. All alarms occurring in the OFFICE Area must be audible. 3. System Inputs to be assigned to an Area named SYSTEM. 4. Terminal LEDs to indicate the status of the OFFICE and SYSTEM Areas. 5. The General Manager of the business, John Smith must be able to operate ALL BUILDING Areas. 6. John Smith is to be issued a 26bit Wiegand card which will allow him to access the FRONT DOOR. 7. When John presents his card at the reader, the system must turn off the OFFICE Area automatically

    before releasing the door. 8. When John presents his card three times at the reader, the system should automatically arm the

    OFFICE Area. 9. The OK button on the Terminal inside the building should act as a REX button whilst the terminal is

    logged off. 10. One of the Sales Staff, Peter Jones is to be issued a 26 bit Wiegand card. 11. Peter is to be allowed access through the FRONT DOOR but only if the OFFICE Area has already

    been turned off. Peter should not be able to turn the OFFICE Area on or off. 12. All areas are to report open and close activities via client code 3333 to the ABC Security company,

    Phone number 9753 3488. 13. Horn sirens, strobe lights and a Piezo screamer are also to be installed and programmed. See APPENDIX 2 for information regarding assigning a card to a user.

    Front Door Reed

    Entry PIR

    Sales Office PIR

    Storeroom PIR

    FRONT DOOR

  • 20

    Practical Exercise 11 Calculated Auxiliaries

    1. Program CA001 as below.

    CA001 Action -> OPPOSITE to 1st CA001 Result Aux: T01:X02 CA001 1st Aux: T01:X06

    The other screens for Calculated Auxiliaries programming can be explored in your own time. 2. From the testing menu, turn the 1st Aux on and off in the Calculated Auxiliary, and observe the operation

    of the Result Auxiliary. ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ 3. Program different Calculated Auxiliary actions and take note of their operations.

    Equal to 1st

    ON if 1

    st ON

    OFF if 1st

    ON NOTES: ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________ ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

  • 21

    Consolidation Exercise 3 Security, Access Control and Building Automation Integration

    Document on the floor plan EVERYTHING thats going to be installed. You have been commissioned to install a system for Moran Enterprises. The Manager, Carl has given you the following description of how he wishes the system to operate as well as users, PINs and access permissions. The hardware chosen for the job is outlined below.

    1. One Concept 4000 controller, 128k RAM (An 8-way Aux expander is assumed to be fitted) 2. One Universal Elite Terminal 3. One 2 Door Access Module

    The control module and reader module will be installed in a designated communications room. The keypad will be installed on the wall in the foyer to allow users to arm/disarm their allowed areas. The floor plan indicates the location of the detection devices and other hardware. The consultant that did the plans left out some key elements of the system. These will have to be added to the floor plan accordingly.

    OFFICE

    FRONT DOOR

    VAULT DOOR LIGHT VAULT

    FOYER

    WAREHOUSE

  • 22

    User Names and Permissions: 1. All users are to have access to the Foyer to arm/disarm their allowed areas. 2. Carl is to have access to all Areas in the building. He likes the word "stash" so his PIN should spell the

    word "stash" on the keypad. (77173) 3. Mick is to have access to all Areas except the Vault. His PIN spells "cash" (1173). 4. Roberta is only to have access to the Office Area. Her PIN spells "pills" (63447). 5. The Maintenance guy Frank needs access to all the building areas. His PIN is (16958). 6. Vince the storeman needs access to the Warehouse. He wants his PIN to be bling (14353) Other Specifications: 1. A Reader module (R01) has been installed so a card can be used to access the VAULT.

    2. FOYER

    T01:Z01 Foyer REED T01:Z02 Foyer PIR C01:X03 Foyer Piezo Screamer OFFICE C01:Z01 Office PIR C01:Z02 Storeroom PIR C01:X04 Office Piezo Screamer WAREHOUSE C01:Z03 Warehouse REED C01:Z04 Warehouse PIR C01:X05 Warehouse Piezo Screamer VAULT C01:Z05 Vault PIR R01:Z01 Vault REED C01:X06 Vault Piezo Screamer SYSTEM

    Add system inputs in this area

    3. The SYSTEM Area is only to be available to the INSTALLER. 4. There will be a Siren fitted to the main building and should be triggered by all Areas when they go into

    alarm. It should sound for no more than 5 minutes at a time. 5. The Strobe light will be connected to C01:X01. 6. Carl wants the Reader module installed for the Vault Door. The Vault Door lock will be attached to

    R01:X01. The Vault Door is only to be opened by Carl when he uses the Proximity Key Fob that is to be issued to him.

    7. When Carl uses his Key Fob to access the Vault, the security within the Vault is to automatically turn off

    and the light is to automatically turn on. When the Vault Area is turned on, the light inside the Vault is to turn off automatically.

    8. Carl also wants to be able to secure the Vault by presenting his Key Fob at the card reader three times.

    (He knows this feature is available) 9. The light inside the Vault will be controlled by a relay connected to C01:X02.

    10. Future expansion requires a memory configuration to be chosen to allow 32 reader modules and 2

    Wireless RF expanders. Carl wants to expand his enterprise in the near future. 11. The LEDs on the Terminal are to indicate the status of the OFFICE, VAULT, FOYER and WAREHOUSE

    Areas.

  • 23

    12. All areas are to report open and close activities via client code 1121 to Dodgy Bros. Monitoring Station, Phone number 97533488.

    * OPTIONAL PROGRAMMING (To be done upon completion of the previous specifications) 13. Carl wishes to have a reader on the front door, he knows he has a 2 Door Reader module so he wants to

    make the most of it. Set up a second door to allow this to happen. All users should have access through this second door.

    14. The Foyer area will automatically disarm when a valid card is presented at the reader head and unlock

    the front door for 10 seconds. 15. A light in the Foyer should turn on when the Foyer disarms. T01:X01 has a relay connected to switch

    power for this light. The light will turn off when the area rearms. 16. Users will still have to disarm/arm the Office or Warehouse Areas from the keypad. Program 3-badge

    arming to be used to arm the Foyer once they have left for the day. 17. The OK key on the keypad will act as a REX button to unlock the front door to allow egress of the

    building. FEELING REALLY GAME? 17. Use the WORKING HOURS Time Zone to automatically stop everyone other than Carl access to the

    building on the weekends and after hours. NOTES __________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

  • 24

    Appendix 1 Adding System Inputs to the System Area 01 OK (LOGIN as Installer) MENU 7-1 (Area Programming Options) Area to program: A009 (Use Area 9 as the System Area) HELP 9 (Hyperlink to Area Options) Press RIGHT ARROW until you see Area Default -> Add Sys. Inputs OK Select T S L I i a s Inputs-> Y YYY n n n NOTE: *** The T S L I i a s options are the default system inputs process groups 9 to 15 (refer to Menu 2-4-3). What process groups should be given to the system inputs can be found in the Tables Tab at the back of the programming manual (Tables T01). OK Push 9 key to Confirm Default Default Done will show on the screen. NOTE: *** Insight program will not know about these changes until a full panel upload is done.

  • 25

    Appendix 2 Assigning a Prox Card to a User (Using the Direct Entry Mode) 01 OK (LOGIN as Installer) MENU 2-1 (User Programming) User to (First Screen) alter: U00001 OK (Skip past three screens) OK OK U00001 Crd Typ-> (Right Arrow to select Direct Entry) Direct Entry OK U00001 Raw Card Data: 0000000000 PRESS the ON KEY U00001 Waiting for card PRESENT THE CARD AT THE READER HEAD (Screen Will Change Back To) U00001 Crd Typ-> Direct Entry PRESS OK Key to view the raw card data. There should be card data displayed for this User. * Note: Insight will not know about these changes until a full panel upload is done.

  • 26

    Appendix 3

    Inside Area or Entry Area (Office)

    Reader Head or Terminal to ENTER

    Access Group - ENTRY DOOR Inside & Outside

    Exit options Out this way

    Entry options In this way

    REX to Exit

    D001 - Front Door

    Outside Area or Exit Area (None)

  • 27

    Appendix 4

    How they all fit together

    USER (U) MENU 2,1

    USER TYPE (UT) MENU 2,2

    AREA LIST (AL) MENU 2,3,1

    AREAs (A) MENU 7,1

    PROCESS GROUP (PG) MENU 2,4,3

    INPUT (Z) 7,0

    COMMS TASK (CT)

    MENU 7,3,1

    PHONE # (TN) MENU 7,3,2

    SIREN LIST (SL) MENU 2,3,3

    AREA AUX (X)

    MENU GROUP (MG) MENU 2,4,1

    DOOR LIST (DL) MENU 2,3,2

    DOORs (D) MENU 7,6

    ACCESS GROUP (AG)

    MENU 2,4,2

    READER MOD. (R) MENU 7,2,4

    ENTRY/ EXIT

    BEEPS OPEN/CLOSE

    AUX

    SIREN/STROBE AUX

    CARD ENROLLED (DIRECT ENTRY)

    TERMINAL MENU 7,2,1