Ballast InstallationBallast Installation Best Practices ... COMBO.pdf · Ballast...

2
Ballast Mounting Correct Incorrect Incorrect Incorrect Ballast Installation Ballast Installation Best Practices Guide Best Practices Guide Mount ballast flush against fixture to provide best heat transfer. Also, avoid mounting ballast close to heat source such as fixture cover plate. Lamp Wiring Socket Wiring: Use 18 AWG (1.0 mm 2 ) solid or tinned stranded wire. Refer to ballast label and socket manufacturer for proper strip length. For proper wiring: Follow wiring schematic on ballast. Correct Incorrect Incorrect Wiring schematic Socket Lead Length Requirements: Lamp Type Max. Length of Leads (ballast to socket) T5 Linear T8 Linear T8 U-Bend T4 Compact T5 Twin Tube 7 ft (2.1 m) 3 ft (0.9 m) Yellows in parallel: Make sure yellows are wired in parallel, not in series. Side by side mounting Ballast Wire strip lengths: For power, output and digital terminals (E1, E2) Solid 18 AWG (1.0 mm 2 ) wire 5 /16 in (8 mm) 5 /16 in (8 mm) Sockets Lutron recommends sockets complying with IEC 60400 Use Rapid Start sockets. Do not use Instant Start sockets. See Lutron App Note #122. Lamp Mounting Height Requirements: Lamp Type Hi-lume 3D EcoSystem T8 Linear 1/8 in to 3/4 in 1/8 in to 3/4 in (3.2 mm to 19.1 mm) (3.2 mm to 19.1 mm) T5 Linear 1/16 in to 1/2 in 1/16 in to 1/2 in (1.6 mm to 12.7 mm) (1.6 mm to 12.7 mm) IMPORTANT: Lamps must never touch ground plane and should be placed without obstruction. * NOTE: Class 2 must be separated from Class 1 and line voltage wiring by the following: 0.25 in (6 mm) or physical barrier. Please refer to App Note #142 for further information. Rapid Start (Rotary Locking Variety) Lamp Lamp Socket (side view) Ballast Mounting height Grounded metal Lamp Type Recommended Socket T8 Linear Rapid-start rotary locking or slide-in T5 Linear Rapid-start rotary locking T5 Linear Rapid Start (Slide-In Variety) Correct Incorrect Lamps Temperature: Avoid operating with cold air blowing directly on lamps. Lutron ballasts are designed to strike the lamps when the lamp temperature is at a minimum of 50 ºF (10 ºC). See lamp manufacturer’s specifications for maximum lamp temperature. Lutron Technical Support Hotline 1.800.523.9466 www.lutron.com 041170b 07/2009 For control and sensor terminals Sensor and Power Wiring Class 2 Sensor Wiring EcoSystem Bus Wiring Power Input (Line Voltage): EcoSystem BUS can be Class 1 or Class 2:* Sensor Wiring Class 2:* 22 AWG (1.0 mm 2 ) solid wire. Do not exceed 100 ft (30 m) from sensor to ballast. Connect only one sensor to the IR & Daylight inputs. Wire sensors to one ballast only. 22 AWG (1.0 mm 2 ) solid 16-18 AWG (2.0 to 1.0 mm 2 ) solid 16-18 AWG (2.0 to 1.0 mm 2 ) solid BLU BLU RED RED YEL YEL B/W B/W Blue Yellow Red Striped NEU. DH Optional E1 SH E2 + 20 V COMMON IR OCC DAYLIGHT Wiring to three lamps (EcoSystem and H3D ballasts only) G–can with daylight sensor J–can with occupancy sensor G–can with wallstation White Orange Black +20V +20V +20V Common Common Common IR Occ Daylight E1 E2 Red Black White Red Black Blue Red Black White Yellow White Orange Black +20V +20V +20V Common Common Common IR Occ Daylight E1 E2 +20V Common IR Occ Daylight To the EcoSystem Bus Supply & up to 64 total ballasts Ballast Terminals Ballast Terminals E1 E2 NEU HOT DH 277 V~ Class 2 Bus E1 E2 NEU HOT DH 277 V~ Class 2 Bus Wire Gauge Bus Length (max) 12 AWG (4.0 mm 2 ) 2200 ft (670 m) 14 AWG (2.5 mm 2 ) 1400 ft (427m) 16 AWG (2.0 mm 2 ) 900 ft (274 m) Ballast must be electrically grounded for proper performance and to meet UL® & NEC® requirements. Grounding should be accomplished with paint piercing mounting hardware to ensure electrical connection through ballast enclosure and through fixture. WARNING: To avoid death or serious injury from electric shock, ballast must be properly grounded. Patent Information: These products may be covered under one or more of the following U.S.patents: 5,001,386; 5,041,763; 6,452,344; 6,982,528; 7,208,887; 7,369,060; 7,391,297; 7,432,661; 7,436,131, and corresponding foreign patents. Other U.S. and foreign patents may be pending. Lutron, EcoSystem, Hi-lume, and the Sunburst logo are registered trademarks of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. UL is a registered trademark of Underwriters Laboratories, Inc. Must be > 6 in (150 mm) apart Solid 22 AWG (1.0 mm 2 ) wire Hi-lume R When installing more than one ballast in a fixture, contact Lutron Technical Support at 1.800.523.9466 for specific guidelines to maximize performance. WARNING: To avoid death or serious injury from electric shock or damage to ballast, disconnect power before servicing or installing.

Transcript of Ballast InstallationBallast Installation Best Practices ... COMBO.pdf · Ballast...

Page 1: Ballast InstallationBallast Installation Best Practices ... COMBO.pdf · Ballast InstallationBallast Installation Best Practices GuideBest Practices Guide Mount ballast flush against

Ballast Mounting

Correct

Incorrect

Incorrect

Incorrect

Ballast InstallationBallast InstallationBest Practices GuideBest Practices Guide

Mount ballast flush against fixture to provide best heat transfer. Also, avoid mounting ballast close to heat source such as fixture cover plate.

Lamp Wiring Socket Wiring: Use 18 AWG (1.0 mm2) solid or tinned stranded wire. Refer to ballast label and socket manufacturer for proper strip length.

For proper wiring:Follow wiring schematic on ballast.

Correct Incorrect

Incorrect

Wiringschematic

Socket Lead Length Requirements:

Lamp Type Max. Length of Leads (ballast to socket)

T5 Linear

T8 Linear

T8 U-Bend

T4 Compact

T5 Twin Tube

7 ft (2.1 m)

3 ft (0.9 m)

Yellows in parallel:Make sure yellows are wired in parallel, not in series.

Side by side mounting

Ballast Wire strip lengths:For power, output and digital terminals

(E1, E2)

Solid 18 AWG (1.0 mm2 )

wire

5/16 in

(8 mm)

5/16 in

(8 mm)

Sockets Lutron recommends sockets complying with IEC 60400 Use Rapid Start sockets. Do not use Instant Start sockets. See Lutron App Note #122.

Lamp Mounting Height Requirements:

Lamp Type Hi-lume 3D EcoSystem

T8 Linear 1/8 in to 3/4 in 1/8 in to 3/4 in (3.2 mm to 19.1 mm) (3.2 mm to 19.1 mm)

T5 Linear 1/16 in to 1/2 in 1/16 in to 1/2 in (1.6 mm to 12.7 mm) (1.6 mm to 12.7 mm)

IMPORTANT:Lamps must never touch ground plane and should be placed without obstruction.

* NOTE: Class 2 must be separated from Class 1 and line voltage wiring by the following: 0.25 in (6 mm) or physical barrier. Please refer to App Note #142 for further information.

Rapid Start(Rotary Locking Variety)

LampLamp Socket(side view)

Ballast

Mounting height

Grounded metal

Lamp Type Recommended Socket

T8 Linear Rapid-start rotary locking or slide-in

T5 Linear Rapid-start rotary locking

T5 LinearRapid Start(Slide-In Variety)

Correct Incorrect

Lamps

Temperature:Avoid operating with cold air blowing directly on lamps. Lutron ballasts are designed to strike the

lamps when the lamp temperature is at a minimum of 50 ºF (10 ºC). See lamp manufacturer’s

specifications for maximum lamp temperature.

Lutron Technical Support Hotline 1.800.523.9466 www.lutron.com

041170b

07/

2009

For control and sensor terminals

Sensor and Power Wiring

Class 2 Sensor Wiring

EcoSystemBus Wiring

Power Input (Line Voltage):

EcoSystem BUS can be Class 1 or Class 2:*

Sensor Wiring Class 2:*

22 AWG (1.0 mm2) solid wire.

Do not exceed 100 ft (30 m)

from sensor to ballast.

Connect only one sensor to the IR & Daylight inputs.

Wire sensors to one ballast only.

22 AWG (1.0 mm2) solid16-18 AWG (2.0 to 1.0 mm2) solid

16-18 AWG (2.0 to 1.0 mm2) solid

BLUBLU

REDRED

YELYEL

B/WB/W

Blue

Yellow

Red

Striped

NEU. DH

Optional

E1SH E2 + 20 V COMMON IR OCC DAYLIGHT

Wiring to three lamps (EcoSystem and H3D ballasts only)

G–can with daylight sensor J–can with occupancy sensor G–can with wallstation

White

Orange

Black

+20V+20V+20VCommonCommonCommonIROccDaylight

E1

E2

Red

Black

White

Red

Black

Blue

Red

Black

White

Yellow

White

Orange

Black

+20V+20V+20VCommonCommonCommonIROccDaylight

E1

E2

+20VCommonIROccDaylight

To the EcoSystemBus Supply & up to

64 total ballasts

BallastTerminals

BallastTerminals

E1E2 NEU

HOTDH

277 V~Class 2Bus

E1E2 NEU

HOTDH

277 V~Class 2Bus

Wire Gauge Bus Length (max)

12 AWG (4.0 mm2) 2200 ft (670 m)

14 AWG (2.5 mm2) 1400 ft (427m)

16 AWG (2.0 mm2) 900 ft (274 m)

Ballast must be electrically grounded for proper performance and to meet UL® &

NEC® requirements. Grounding should be accomplished with paint piercing mounting hardware to ensure electrical connection

through ballast enclosure and through fixture.

WARNING: To avoid death or serious injury from electric shock, ballast must be properly grounded.

Patent Information:These products may be covered under one or more of the following U.S.patents: 5,001,386;

5,041,763; 6,452,344; 6,982,528; 7,208,887; 7,369,060; 7,391,297; 7,432,661; 7,436,131,

and corresponding foreign patents. Other U.S. and foreign patents may be pending.

Lutron, EcoSystem, Hi-lume, and the Sunburst logo are registered trademarks of Lutron

Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association,

Quincy, Massachusetts. UL is a registered trademark of Underwriters Laboratories, Inc.

Must be > 6 in (150 mm) apart

Solid 22 AWG (1.0 mm2 )

wire

Hi-lume R

When installing more than one ballast in a fixture, contact Lutron Technical Support at 1.800.523.9466 for specific guidelines to maximize performance.

WARNING: To avoid death or serious injury from electric shock or damage to ballast, disconnect power before servicing or installing.

Page 2: Ballast InstallationBallast Installation Best Practices ... COMBO.pdf · Ballast InstallationBallast Installation Best Practices GuideBest Practices Guide Mount ballast flush against

Montaje de balasto

Cableado de la lámpara

Correcto

Incorrecto

Incorrecto

Incorrecto

R

Monte el balasto al ras de la instalación para proporcionar la mejor transferencia de calor posible. Evite montar el balasto cerca de una fuente de calor tal como la cubierta protectora.

Cableado del enchufe:Use cable estándar 1,0 mm2 (18 AWG) sólido o de estaño. Consulte la etiqueta del balasto y al fabricante del enchufe para las medidas correctas para pelar los cables.

Para cableado correcto:Siga el diagrama de cableado del balasto.

Correcto Incorrecto

Incorrecto

Diagrama de

cableado

Longitud del cable conductor del enchufe:Tipo de lámpara Máxima longitud (del balasto al enchufe)

Linear T5

Linear T8

T8 en U

Compacto T4

Tubo doble T5

2,1 m (7 pies)

0,9 m (3 pies)

Amarillos paralelos:Asegúrese de que los amarillos estén cableados en paralelo, no en serie.

Montajeparalelo

Medidas para pelar el cable del balasto:

Cable sólido1,0 mm2

(18 AWG)

8 mm(5/16 pulg)

8 mm(5/16 pulg)

Enchufes Lutron recomienda enchufes que cumplan con IEC 60400 Use enchufes de arranque rápido: No use enchufes de arranque instantáneo. Consulte Lutron App Nota #122

Requerimientos de altura para montaje de la lámpara:

Tipo de lámpara Hi-lume 3D EcoSystem

Linear T8 3,2 mm a 19,1 mm 3,2 mm a 19,1 mm (1/8 pulg a 3/4 pulg) (1/8 pulg a 3/4 pulg)

Linear T5 1,6 mm a 12,7 mm 1,6 mm a 12,7 mm (1/16 pulg a 1/2 pulg) (1/16 pulg a 1/2 pulg)

IMPORTANTE:Las lámparas nunca deben de tocar el plano de tierra y se deben instalar sin ninguna obstrucción.

*NOTA: El cableado de clase 2 se debe separar del de clase 1 y del voltaje de línea por: 6 mm (0,25 pulg) o por una barrera física. Por favor, consulte App Nota #142 para más información.

Arranque rápido(de rosca)

LámparaEnchufe de la lámpara(vista lateral)

Balasto

Altura de montaje

Metal conectado a tierra

Tipo de lámpara Enchufe recomendado

Linear T8 Arranque rápido de rosca o deslizador

Linear T5 Arranque rápido de rosca

Linear T5 Arranque rápido(deslizador)

Correcto Incorrecto

LámparasTemperatura:

Evite operar donde le dé aire frío directamente a las lámparas. Los balastos de Lutron están

diseñados para detener las lámparas cuando la temperatura de éstas está a un mínimo de

10 °C (50 °F). Consulte las especificaciones del fabricante de la lámpara para saber la

temperatura máxima de la lámpara.

Línea de soporte técnico de Lutron +1.888.235.2910 www.lutron.com

Para terminales de control y de sensor

Para alimentación, terminales de

salida y digitales (E1, E2)

Cable sólido1,0 mm2 (18 AWG)

Cableado del sensor y de alimentación

Cableado de clase 2 para el sensor

Cableado del bus EcoSystem

Entrada de alimentación(Voltaje de línea):

El bus EcoSystem puede ser clase 1 o clase 2:*

Cableado del sensor clase 2:*

• Cable sólido 1,0 mm2 (22 AWG). No excede 30 m (100 pies) del sensor al balasto.• Conecte solamente un sensor a las entradas de IR y de luz natural.• Cablee los sensores a un balasto solamente.

Sólido 1,0 mm2 (22 AWG)

Sólido 2,0 a 1,0 mm2

(16 a 18 AWG)Sólido 2,0 a 1,0 mm2

(16 a 18 AWG)

BLUBLU

REDRED

YELYEL

B/WB/W

Azul

Amarillo

Rojo

Cable Pelado

Neu V. Aten

Opcional

E1Vivo E2 +20 Común IR Ocup. Luz Nat

Cableado a tres lámparas (Balastos EcoSystem y H3D solamente)

G-can con sensor de luz natural J-can con sensor de ocupación G-can con teclado

Blanco

Naranja

Negro

+20 V+20 V+20 VComúnComúnComúnIROcuLuz natural

E1

E2

BlancoAzul

Rojo

Negro

Blanco

Amarillo

Blanco

Naranja

Negro

+20 V+20 V+20 VComúnComúnComúnIROcuLuz natural

E1

E2

+20 VComúnIROcuLuz natural

Desde la fuente bus

EcoSystem y hasta un

total de 64 balastos

Terminalesde balasto

Terminalesde balasto

E1E2 NEU

HOTDH

277 V~Class 2Bus

E1E2 NEU

HOTDH

277 V~Class 2Bus

Calibre del cable Medida del bus (máx)

4,0 mm2 (12 AWG) 670 m (2 200 pies)

2,5 mm2 (14 AWG) 427 m (1 400 pies)

2,0 mm2 (16 AWG) 274 m (900 pies)

ADVERTENCIA: Para evitar la muerte o heridas graves por choque eléctrico, el balasto debe estar conectado a tierra apropiadamente. ADVERTENCIA: Para evitar la muerte o heridas graves por

choque eléctrico o daños al balasto, apague la alimentación al balasto antes de servicio o de instalación.

Información de Patente:Estos productos pueden estar bajo una o más de las siguientes patentes en EUA: 5,001,386;

5,041,763; 6,452,344; 6,982,528; 7,208,887; 7,369,060; 7,391,297; 7,432,661; 7,436,131, y patentes

extranjeras correspondientes. Pueden estar pendientes otras patentes en EUA y en el extranjero. Lutron, EcoSystem, Hi-Lume y el logo Sunburst son marcas registradas de Lutron Electronics Co., Inc. NEC es una marca registrada de National Fire Protection Association, Quincy Massachusetts. UL es

una marca registrada de Underwriters Laboratories, Inc.

Guía de prácticas adecuadaspara la instalación de balastos

Rojo Rojo

Negro Negro

Colocar a > 150 mm (6 pulg)

Hi-lume

El balasto debe estar conectado a tierra para óptimo rendimiento y para cumplir con los requerimientos UL® & NEC®. La conex-ión a tierra debe lograrse con herrería de

montaje que atraviese la pintura para asegurar la conexión eléctrica a través de la caja del balasto y a través de la luminaria.

Cuando instale más de un balasto en una luminaria, contacte al Centro de Soporte Técnico de Lutron al 1.800.523.9466 para más información acerca de las pautas específicas para maximizar el rendimiento.