Back-up Transformer Protection Relays
-
Upload
eagle-technology -
Category
Documents
-
view
163 -
download
20
description
Transcript of Back-up Transformer Protection Relays
EAGLE TECHNOLOGY http://www.eaglewanlida.com
Supplier of Magnetic Controlled Rectifier Type Static Var Compensator (MCR Type SVC), 48 Pulse MV Drives, Active Power Filter, Protection Relays and Intelligent Switchgear at reasonable price in India.
Contact us Mr. Sunil Jha
Mobile: +91-9590273474 E-mail: [email protected], [email protected]
SKYPE: jhasunil100 Google Talk: [email protected]
To Read and Download all our Products catalogs: http://www.scribd.com/sunil_jha To Read and Download Online our MV-VFD Catalogs http://www.scribd.com/doc/63980384/MV-Drives
To Watch Online Video Presentation on YouTube:
http://www.youtube.com/watch?v=W2AVlS4-0SM
To Read MV-VFD Presentation Online on our website:
http://eaglewanlida.com/vfdpresentation.aspx
To Read and Download online our relays catalog:
http://www.scribd.com/doc/73143176/MMPR-620-HB-Micro-Computer-M
otor-Protection-and-Monitoring-Device
User’s manual for MTPR-650Hb main
transformer backup protection device
Manufactured by ZuHai Wanlida Electric co Ltd, China.
Sole Distributor in India: EAGLE TECHNOLOGY
Prepared by:
Proofed by:
Approved by:
Document No.:WLD[K]-JY-228-2010 Version No.: V2.00.01
Date of publication:July, 2010
Copyright: Zhuhai Wanlida Electric Co., Ltd.
Note: Our company reserves the right to modify this manual. For any inconsistency
between the product and this manual, please contact us for relevant services.
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 1
F o r e w o r d
1. Model description
MTPR-650Hb device: microcomputer transformer low voltage side backup
protection measuring and control, the structural type is Hb.
2. References
General specification for static protection, security and automatic
equipment, DL 478-2001
Technical code for relaying protection and security automatic
equipment, GB/T 14285-2006
Design code for relaying protection and automatic device of electric
power installation, GB50062-92
3. Caution
Negative sequence voltage involved in this series of protection is combined with
phase voltage,all of low voltage component depend on line voltage in compound
voltage block,if one of the three line voltages is lower than low voltage setting, low
voltage component will operate and unblock over current protection. Three-section
over-current respectively has composite voltage block on/off words controlling on/off
of each composite voltage block function.
The appearance should be inspected before power is applied, to ensure that the
panel is OK without scratch, the screws are tightened, the device is grounded firmly,
all screws of plug-ins are tightened and in good contact.
When power is applied, the “Run” indicator on the panel should flash, nixie tube
displays primary measuring value in cycle and LCD displays protective, measuring
value etc. in cycle.
Terminals D25~D28 are DC 4~20mA measuring circuit, the signal must be provided
by specific equipment when testing, it is prohibited to apply the signal by relay testing
device.
The operation circuit in the device fits DC power only, if it is to connect with AC power,
the power should be rectified and filtered.
It is prohibited to plug or unplug the plug-ins when power is present, in order to avoid
damage to the device.
It is prohibited to do binary output test when the device is running with primary
equipments.
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 2
1. Product description..................
1.1 Scope of application
MTPR-650Hb microcomputer transformer low voltage side backup protection device
applies to 110KV power system. MTPR-650Hb, MTPR-630Hb differential protection
device and MTPR-640Hb microcomputer transformer high voltage side backup protection
device together constitute a complete protection for a large transformer.
1.2 Function and specification
1.2.1 Protective function
Three-section(three time limit for each section)composite voltage block direction
over-current protection
Zero sequence voltage alarm function
Bus charging protection
Zero sequence current protection
Overload
Starting fan
Block voltage regulation
composite voltage block output
PT failure alarm/block
CT failure alarm
1.2.2 Auxiliary Function
Harmonic spectrum analysis
Phase display
Integral energy
Alarm on device self-test fault
Protective settings read and modified by remote
Fault recorder
2-way programmable 4~20mA output
Provide ethernet print function(manual print setting value, manual/auto print reports).
1.2.3 Measuring and controlling function
Power measurement(remote measurement): Voltage, current, active power,
reactive power, active energy, reactive energy, power factor, power grid frequency,
non-electric quantity measurement and so on
Remote signal: 19 binary inputs, including: 16 for outside collection, 3-way for the
internal collection
1.2.4 Communication capability
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 3
2 standard RS485 multipoint communication ports
2 industrial ethernet ports
Supports single, dual network communication, it is fully qualified for network
redundancy and backup
IEC-60870-5-103 (RS485 communication mode), IEC-60870-5-104 (industrial
ethernet communication mode) standard communication protocol
1.2.5 GPS clock synchronization function
The device is able to receive GPS clock minute synchronization (or second
synchronization) through RS485 differentiate voltage, and it can be done with
monitoring system to accomplish GPS precise clock synchronization.
1.2.6 Device specifications
32-bit DSP microprocessor
Real-time multi-task operating system and C++ program techniques, realizing online
programming
Double-screen display (LCD display and nixie tube display), easy for inspection
2-way 4~20mA DC quantity output, which can be set flexibly as any corresponding
electric quantity (such as current, voltage, power, frequency, etc.)
Collecting 2 ways of 4~20mA DC quantities for measurement of non-electric
quantities, such as temperature, pressure, and realizing online monitoring
Power quality analysis capabilities, complete harmonic analysis function
Integration of perfect meter function, measuring function
Excellent hardware interchangeability, easy user maintenance and reduced quantity
of spare parts
Protection output relays can be configured flexibly for user convenience
Using a 6U, 19/3” standard enclosure in a rear plug-in structure; the device can be
installed in site on a switchboard or combined in a centralized manner
1.2.7 Main technical specifications
Rated data
Power supply:DC/AC 86~265V
Operating voltage:DC 220V or DC 110V
AC voltage:100/ 3 V or 100V
AC current:5A or 1A
Frequency: 50Hz
Power consumption
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 4
DC circuit: <10W(normal operation);<15W(protection operation).
AC voltage circuit:<0.5VA/phase
AC current circuit:<1VA/phase(In=5A);<0.5VA/phase(In=1A).
Overload capability
AC voltage circuit:1.2 times rated voltage continuous operation
Measuring current:1.2 times rated current continuous operation
Protection current:2 times rated current continuous operation
10 times rated current,allowed for 10 s
40 times rated current,allowed for 1 s
Range and error of setting value
Maximum range of setting value:
Voltage component:1V~120V
Current component:0.1In~20In
Frequency:45.00Hz~55.00Hz
Delay component:0.00s~100.00s
Error of setting value:
Current and voltage setting value:≤±3% of setting value
Frequency setting value:≤±0.02Hz
Angle setting value:≤±2°
Whole-group operation time (including relay’s intrinsic time):
Intrinsic operation time of percentage differential protection: 1.5 times the
setting value not greater than 40ms.
Measuring accuracy
AC current: Class 0.2
AC voltage: Class 0.2
4~20mA DC quantity input:≤± 1%
Power: Class 0.5
Integral energy: Class 1 (active), Class 2 (reactive)
Frequency: ≤±0.02Hz
SOE resolution: ≤2ms
Pulse width of pulse quantity: ≥10ms
4~20mA DC quantity output: ≤±1%
Capacity of trip/closing output contact
Can be connected to DC 250V,8A for prolonged periods
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 5
GPS time synchronization error
Synchronization error≤2ms
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃.
Storage:-25℃~+70℃,rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas;
no excitation quality is applied at the limits, the device shall not have any irreversible
change; after temperature restoration, the device shall operate properly.
Relative humidity: The average relative humidity of the most humid month shall not
be greater than 90%, the average minimum temperature of this month not lower than 25℃
and there shall be no surface condensation; at the highest temperature of +40℃, the
average maximum humidity shall not exceed 50%.
Atmospheric pressure:80kPa~110kPa(below relative altitude of 2km).
1.2.8 Hardware structure
The device uses a 6U, 19/3” standard enclosure, with aluminum alloy casing and
installed by overall embedding. The display panel is mounted in the front, and the other
plug-in modules are rear mounted. From the rear view, the power, I/O, CPU and AC
plug-in modules are from the left to the right.
External dimensions and boring diagram
Structural and dimensional diagram Boring diagram for installation
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 6
Devices fabricated on-screen steps: first release on-screen stents unfastening
screws, remove the stents; installed the device on the screen from the front and push until
close to the fixed plate; install the stent 2, and then stent 1, and then use fastening screw
to insertion hole from rear of stent1, and then screwed into stent 2 and tighten screw; the
stents from up and down are installed in the same way; use grounding screws to connect
grounding line.
2. Functional description
2.1 Three-section composite voltage block direction over-current protection
This device sets up three-section over-current protection. Each has three time delays.
By setting the control word soft strap, it can be set that whether each of the protection is
on or off and whether it is equipped with direction judgment( it can be set as positive or
reverse), and whether it is blocked by composite voltage. Direction operating zone is
-60°~120°(when it is in positive direction,suppose U is 0°,the phase of I is changeable,
when in the opposite direction, the operating zone is the remaining 180°;in which,Ia
corresponds to Ubc,Ib corresponds to Uca,Ic corresponds to Uab).
Composite voltage component consists of negative sequence voltage
U2(over-vlotage) and phase-to-phase low-voltage U(the minimum line voltage).It is used
for block over-current protection when any fault occurs. When either negative sequence
voltage U2 or low-voltage U is satisfied, over-current protection can be on, otherwise,
over-current protection is blocked.
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 7
When composite voltage operates, the device will output the signal to other side
backup protection through output terminal, in order to control the over-current protection
output. That is to say, besides accepting its side composite voltage block, the over-current
protection can also accept other sides’ composite voltage block. The protection logic is
shown in Fig.2-1
Fig 2-1 Operation logic of composite voltage block direction over-current protection
2.2 Zero sequence voltage alarm function
When zero sequence voltage is more than zero sequence voltage setting, the
protection will operate after delay. The protection logic is shown in Fig2-2.
Fig 2-2 Operation logic of Zero sequence voltage alarm function
2.3 Bus charging protection
Bus charging protection is the time limit instantaneous over-current protection. The
protection is only on for bus charging for a short time. When the device detects its side
breaker changing from trip to close, bus charging protection will be on for a short time.
When the operating condition is met, the protection will trip its side breaker after set delay.
The on time can be set. When the on time is over, the bus charging protection will be off.
The protection logic is shown in Fig 2-3.
≥
U2>
≥
&
I>
Over-current protection control
word ON
Over-current protection plate
closing
Directional component operating
Other side compound voltage
Low voltage component operating
Other side compound voltage block
Hard plate function ON/OFF
Directional block ON/OFF
Compound voltage block ON/OFF
Compound voltage output ON/OFF
Compound voltage
output
T1 delay
T2 delay
T3 delay
Protection output
Protection output
Protection output
U0>zero sequence
voltage setting value
TZero sequence voltage
alarm ON/OFFProtection output
sequence
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 8
Fig 2-3 Operation logic of bus charging protection
2.4 Zero sequence current protection
When zero sequence current is more than zero sequence over-current setting, the
protection will operate after delay. The protection logic is shown in Fig 2-4.
Fig 2-4 Operation logic of Zero sequence current protection
2.5 Over-load protection
Three phase A, B, C ,when maximum phase current is more than over-load setting,
the protection will operate after delay. Protection operating logic is as Fig 2-5.
Fig.2-5 Operation logic of Over-load protection
2.6 Starting fan
When a certain phase current is more than starting fan setting, the output relay will
block. The protection logic is shown in Fig 2-6.
Fig.2-6 Operation logic of Starting fan
Imax>over load
setting valueTOver load ON/OFF Protection
output sequence
I > t/0
ON/OFF
Protection output sequence
I0>zero sequence over-current setting value
TZero sequence over-
current protection ON/OFF Protection output sequence
&
&
Breaker position from tripping to
closing
T<opening time
Charged protection plate closing
Imax>current setting value of bus charging protection
Hard plate function ON/OFF
Bus charging protection ON/OFF
Delay Protection output
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 9
2.7 Block voltage regulation
When a certain phase current is more than block voltage when a certain phase
current is more than block voltage regulation setting, the output relay will block after
delay. The protection logic is shown in Fig2-7.
Fig 2-7 Operation logic of Block voltage regulation
2.8 PT failure alarm
The criteria of PT failure differ depending on different wiring mode. When PT failure
block function is on, if PT failure occurs, the device will block the complex voltage
components and current direction components. The criteria of PT failure are as follows:
V-V wiring mode
The current of the phase with the maximum current is less than the maximum
load-current(use the load-current setting).
① The maximum phase-to-phase voltage is less than 30V and the maximum
phase current is more than 0.1In;
② Negative sequence voltage is more than 8V,
When any of the above condition is met, the device will report PT failure after delay
(settable). When the failure disappears, the alarm will return.
Y-Y wiring mode
The current of the phase with the maximum current is less than the maximum
load-current(use the load-current setting).
① When |Ua+Ub+Uc|>7V and the difference between the maximum line voltage
and the minimum line voltage is more than, it is considered as one-phase or
two-phase PT failure;
② When |Ua+Ub+Uc∣ > 7V and the minimum line voltage is less than 18V;it is
used for checking two-phase failure.
③ When MAX{Uab,Ubc,Uca}<7V and the maximum phase current is more than
0.1In, it’s considered as PT three-phase failure.
When any of the above condition is met, the device will report PT failure after delay
(settable). When the failure disappears, the alarm will return.
I > t/0
ON/OFF
Protection output sequence
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 10
Fig 2-8 Operation logic of PT failure alarm protection PT failure alarm
2.9 CT failure alarm
When CT failure function is on, if CT failure occurs, the device will send alarm
signal.
When in normal operation,the sum of the three phase current of each side is zero.
(less than 0.1 times rated current).When one phase CT failure occurs,the sum of three
phase current is not zero (more than 0.1 times rated current). In order to distinguish with
ground fault,the following judgment should be conducted:
①Among the three phases,the current of the one with the minimum current is zero.
(less than 0.1 times rated current).
②The current of the one with the maximum current is not zero. (more than 0.1 times
rated current), but less than CT failure block current.
2.10 Integral Energy
Active power and reactive power are accumulated into active energy and reactive
energy in real-time by software.
2.11 Fault record
See the communication coding table for the protection voltage and current waveform
data collected by the recording unit.
PT failure operation
information
&
TPT
PT failure ON/OFF
|MaxU-MinU|>18V
&MinU<18V
&
MaxU<7V MaxU=Max(Uab,Ubc,Uca)
MinU=Min(Uab,Ubc,Uca)
&
MaxU<30V
U2>8V
≥
&
V-V wiring
Max{Ia,Ib,Ic}>0.1*In
≥
Max{Ia,Ib,Ib}<Igfh
&
≥
&
Max{Ia,Ib,Ic}>0.1*In
7V|cUbUaU|
7V|cUbUaU|
PT
failu
re c
om
po
ne
nt
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 11
3. List of parameters and setting values
3.1 System parameters
Parameters Range Description
Basic parameters setting
Secondary rated
current(In) 0-1 Set step:1(factory default 0)00:5A;01:1A
PT ratio 1-1500 Set step:1(factory default 100)
CT ratio 1-5000 Set step:1(factory default 100)
PT wiring mode 0-1 Set step:1(factory default 0)00:Y-Y;01:V-V
Harmonic calculation
channel choice 0-11
Harmonic calculation choice corresponding reference
(when it is YY wring mode):
00:Off
1:Ia,2:Ib,3:Ic,4:I0,5:IA,6:IB,7:IC,
8:Ua,9:Ub,10:Uc,11:U0
Wave Recrod 1/0 1/0:On/Off (factory default Off)
Hardword on/off 1/0 1/0:On/Off (factory default Off)
Earth Mode 0-2 00:No Earth,01:Earth,02:Res. Earth
(factory default 0)
D/A Channel setting
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 12
Parameters Range Description
DA1~2 Channel
choice 0-11
Select DA1~2 output corresponding reference:00:No
1:IA,2:IB,3:IC,4:Ua,5:Ub,6:Uc,7:Uab,8:Ubc,
9:Uca,10:P,11:Q
Voltage reference : 0—120V corresponding to
4mA—20mA,
Rated 5A:
Current reference : 0—6A corresponding to
4mA—20mA,
Power reference : 0—1000W corresponding to
4mA—20mA.
Rated 1A:
Current reference : 0—1.2A corresponding to
4mA—20mA,
Power reference:0—200W corresponding to
4mA—20mA.
DA1~2 Adjusting
Factor 0.5-1.5 Adjust parameter of channel D/A 1~2(4-20mA)
3.2 List of setting value
Setting name Range Description
Protection On/Off
Over-current 1 section protection
(Overcurrent 1) 1/0 1/0:On/Off (factory default Off)
Over-current 2 section protection
(Overcurrent 2) 1/0 1/0:On/Off (factory default Off)
Over-current 3 section protection
(Overcurrent 3) 1/0 1/0:On/Off (factory default Off)
Over-current 1 section direction
(OC 1 Direction) 1/0 1/0:On/Off (factory default Off)
Over-current 2 section direction
(OC 2 Direction) 1/0 1/0:On/Off (factory default Off)
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 13
Over-current 3 section direction
(OC 3 Direction) 1/0 1/0:On/Off (factory default Off)
Over-current 1 section
compounded voltage latching
(OC 1 CV Lock)
1/0 1/0:On/Off (factory default Off)
Over-current 2 section
compounded voltage latching
(OC 2 CV Lock)
1/0 1/0:On/Off (factory default Off)
Over-current 3 section
compounded voltage latching
(OC 3 CV Lock)
1/0 1/0:On/Off (factory default Off)
Zero sequence alarm
(ZS Voltage Alarm) 1/0 1/0:On/Off (factory default Off)
Bus charging protection
(Bus Charge PROT) 1/0 1/0:On/Off (factory default Off)
Zero sequence over-current
protection (ZS OC Protect) 1/0 1/0:On/Off (factory default Off)
Overload 1/0 1/0:On/Off (factory default Off)
Startup cooling 1/0 1/0:On/Off (factory default Off)
Block voltage regulation
(V Adjust Lock) 1/0 1/0:On/Off (factory default Off)
External side composite voltage
block
(Other CV Lock)
1/0 1/0:On/Off (factory default Off)
Composite voltage block output
(CV Out Lock) 1/0 1/0:On/Off (factory default Off)
PT failure alarm 1/0 1/0:On/Off (factory default Off)
PT failure block 1/0 1/0:On/Off (factory default Off)
CT failure alarm 1/0 1/0:On/Off (factory default Off)
Three-section composite voltage block direction over-current protection
(Overcurrent)
Low voltage 10.00-90.00V Set step:0.01V(factory default 90V)
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 14
Negative sequence voltage
(NS Voltage) 5.00-30.00V Set step:0.01V(factory default 10V)
Over-current 1 section current
(Overcurrent 1) (0.1-20)In Set step:0.01A(factory default 20In)
Over-current 2 section current
(Overcurrent 2) (0.1-20)In Set step:0.01A(factory default 20In)
Over-current 3 section current
(Overcurrent 3) (0.1-20)In Set step:0.01A(factory default 20In)
Over-current 1 section direction
(OC 1 Direction) 0-1
Set step:1(factory default 0)
00:Positive;01:Reverse
Over-current 2 section direction
(OC 2 Direction) 0-1
Set step:1(factory default 0)
00:Positive;01:Reverse
Over-current 3 section direction
(OC 3 Direction) 0-1
Set step:1(factory default 0)
00:Positive;01:Reverse
Over-current 1 section delay1
(T1 Overcurrent 1) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 1 section delay 2
(T2 Overcurrent ) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 1 section delay 3
(T3 Overcurrent 1) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 2 section delay 1
(T1 Overcurrent 2) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 2 section delay 2
(T2 Overcurrent 2) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 2 section delay 3
(T3 Overcurrent 2) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 3 section delay 1
(T1 Overcurrent 3) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 3 section delay 2
(T2 Overcurrent 3) 0.00-100.00s Set step:0.01s(factory default 5s)
Over-current 3 section delay 3
(T3 Overcurrent 3) 0.00-100.00s Set step:0.01s(factory default 5s)
Zero sequence voltage alarm(ZS Voltage Alarm)
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 15
Zero sequence voltage setting
(ZS Voltage Vaule) 0-200V Set step:0.01V(factory default 120V)
Zero sequence voltage delay
(ZS Voltage Time) 0.00-100.00s Set step:0.01A(factory default 100s)
Bus charging protection(Bus Charge PROT)
Bus charging protection current
setting (Bus Char.Current) (0.1-20)In Set step:0.01A(factory default 20In)
Bus charging protection delay
setting (Bus Char.Time) 0.00-15.00s Set step:0.01s(factory default 1s)
Bus charging protection on time
(Bus Char. Open T) 0.00-15.00s Set step:0.01s(factory default 3s)
Zero-sequence over-current protection(ZS OC Protect)
Zero-sequence over-current
setting (ZS OC Vaule) 0-100A Set step:0.01A(factory default 2A)
Zero-sequence over-current delay
(ZS OC Time) 0.00-100.00s Set step:0.01s(factory default 100s)
Overload
Overload current (0.1-20)In Set step:0.01A(factory default 20In)
Overload time 0.00-100.00s Set step:0.01s(factory default 100s)
Starting fun (Startup Cooling)
Starting fan current
(Cooling Current) 0.00-50.00A Set step:0.01A(factory default 50A)
Starting fan delay
(Cooling Time) 0.00-100s Set step:0.01s(factory default 5s)
Block voltage regulation(V Adjust Lock)
Block voltage regulation setting
(V Adjust Value) 0.00-50.00A Set step:0.01A(factory default 50A)
Block voltage regulation delay
(V Adjust Time) 0.00-100s Set step:0.01s(factory default 5s)
PT/CT Failure
CT failure block current
(CT Failure Lock) 1-10.00A Set step:0.01A(factory default 10A)
CT failure delay
(CT Failure Time) 5.00-100s Set step:0.01s(factory default 15s)
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 16
PT failure delay
(PT Failure Time) 5.00-100s Set step:0.01s(factory default 15s)
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 17
4.Description of binary input/output and analog quantities
4.1 Monitoring analog quantities
Under【Protection Data 】, 【Measuring Data】,【Integral Energy】 menu in【State
Display】, monitor analog quantity. Press the “”, “” keys to flip over. The precision of
the device has been calibrated. The protection current is calibrated at double the rated
current, and the measuring current is calibrated at a time the rated current. The list and
description are as follows:
Analog quantity
terminal
Analog quantity
name Testing method
Terminals D01, D02 Protecting Phase A
current(Ia)
Add double the rating, displayed
deviation not exceed 1%
Terminals D03, D04 Protecting Phase B
current (Ib)
Add double the rating, displayed
deviation not exceed 1%
Terminals D05, D06 Protecting Phase C
current (Ic)
Add double the rating, displayed
deviation not exceed 1%
Terminals D07, D08 Zero sequence
current(I0)
Add double the rating, displayed
deviation not exceed 1%
Terminals D11, D12 Testing phase A
current(IA)
Add one times the rating, displayed
deviation not exceed 0.2%
Terminals D13, D14 Testing phase B
current (IB)
Add one times the rating, displayed
deviation not exceed 0.2%
Terminals D15, D16 Testing phase C
current (IC)
Add one times the rating, displayed
deviation not exceed 0.2%
Terminals D17, D18 Phase A Voltage(Ua) Add 50V, displayed deviation not
exceed 0.5%
Terminals D19, D20 Phase B Voltage (Ub) Add 50V, displayed deviation not
exceed 0.5%
Terminals D21, D22 Phase C Voltage (Uc) Add 50V, displayed deviation not
exceed 0.5%
Terminals D23, D24 Zero voltage(U0) Add 50V, displayed deviation not
exceed 0.5%
Terminals D25, D26 4~20mA DC input1 Add 10mA, displayed deviation not
exceed 3%
Terminals D27, D28 4~20mA DC input2 Add 10mA, displayed deviation not
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 18
Analog quantity
terminal
Analog quantity
name Testing method
exceed 3%
Add current to
terminals D11, D12;
D15, D16 according to
polarity; add voltage
to D17, D18;D19, D20;
D21, D22 according to
polarity
Three-phase active
power
Add one times rated current,add100V
line voltage
Change phase angle,displayed power
deviation not exceed 0.5%
Add current to
terminals D11, D12;
D15, D16 according to
polarity;add voltage to
D17, D18;D19, D20;
D21, D22 according to
polarity
Three-phase reactive
power
Add one times rated current,add100V
line voltage
Change phase angle,displayed power
deviation not exceed 0.5%
4.2 Check of binary input quantity
Under 【Binary input】menu in【State Display】menu,check binary input, press the
“”, “”keys to flip over.
Binary input
terminal
Binary input name Check method
B01 Binary input common terminal
(used to be connected with
the negative pole of DC220
and DC110V external power)
Binary input can be connected to external
220V or110V DC power. Connect negative
pole to terminal B01,connect positive pole
to terminals B02~B13,under【Binary
input】 menu in【State Display】, the input
state can be seen. This device also
provides 24V DC power. If a
self-generated power is used, terminal
B14 can be connected to terminals B02~
B13,under【Binary input】 menu in【State
Display】,the input state can be seen. For
the choice of input power, please specify
B02 Breaker position
B03 Trolley operation position
B04 Trolley test position
B05 Grounded knife position
B06 Spring non-storage
B07 Other side composite voltage
operation
B08 Binary input 7
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 19
B09 Binary input 8 in the order. Factory default is external
DC220V B10 Binary input 9
B11 Binary input 10
B12 Binary input 11
B13 Binary input 12
B14 Positive pole of
self-generated DC 24V
C12 Binary input 13
Connect C16 to C12, C13, C14, C15,
under 【 Binary input 】 menu in 【 State
Display】, the input state can be seen.
C13 Binary input 14
C14 Charging protection strap
C15 Over-current protection strap
C16 Binary input common terminal
(+24V)
A17 Manual trip binary input Connect 220V to A17,A19 grounding
A15 Manual close binary input Connect 220V to A15,A19 grounding
A07 Operation circuit failure Connect 220V to A20,A13or A14
grounding A08
4.3 Check of binary output quantity
Under 【Output Test】menu,monitor binary output. Press the “”, “”keys to flip over.
Binary output terminal Binary output name Check method
B15-B16 Device fault signal
Enter On/Off menu, use “+”,
“-”keys to operate. The
corresponding terminals
should be connected.
B31-B32 and B34-B35 are
normal open terminals that
should be closed.
B17-B18 Block this side backup power
B19-B20 Starting fan
B21-B22 Trip this side section breaker
B23-B24 Trip this side breaker
B25-B26 Trip other side breaker 1
B27-B28 Trip other side breaker 1
B29-B30 Composite voltage output1
B31-B32(normal open) Composite voltage output 2
B32-B33
B34-B35(normal open) Block voltage regulation
B35-B36
A22-A23 Remote close output
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 20
A22-A24 Remote open output
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 21
4. Operation instructions
5.1 Control panel of device
128*64 matrix LCD (The LCD will go off after a period of absence of keyboard operation;
the LCD will be illuminated automatically when any key is pressed or in case of
protection trip or alarm.)
Signal indicator: run, communication, operation, alarm, body, fault (device fault).
Circuit breaker state indication: indicating the current state of the circuit breaker (“Open”,
“Close” position indication)
Key pad: ,,,, Cancel, -, +, Enter, Revert
The 6-bit nixie tube displays the primary measuring value in real time: Ia, Ib, Ic, Uab, Ubc,
Uca, P, Q, Cosφ(Please set the PT, CT transformation ratios properly in the System
Parameters menu). The maximum display range is 99999.
Note:Measuring Ia:AA,Measuring Ib:bA, Measuring Ic:CA
Voltage Uab:AbkV,Voltage Ubc:bCkV,Voltage Uca:CAkV
Active power:PkW,Reactive power:qkvar,Power factor: H
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the measuring current, power,
time in cycle. Press the “Enter” key to enter the main menu, which is a multi-level tree
menu. Press the ““, ““ keys to move the cursor to the desired entry, press the “Enter”
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 22
key to enter this entry, and press the “Cancel” key to return to the next higher level of
screen. If this screen is still a menu, continue to press the ““, ““ key to select the
desired entry, press the “Enter” key to enter the next level of screen, and press the
“Cancel” key to return to the next higher level of menu. If there is no menu screen, be sure
to press the “Cancel” key to return to the next higher level of menu. The main menu is
shown at the center of the following figure, with the corresponding submenus on both
sides..
The main interface displays the primary operating parameters in turn. The maximum
displayed current is 6000.0A. For systems with a rated current of 5A, the set CT
transformation ratio shall not exceed 2000.Primary display power unit will be MW, when
the power is higher than 1000kW, otherwise it is kW
5. System Parameters
(Note 1)
Setting Zone No.
Comm. Setting
B. Parameters
D/A Setting
Integral Energy
Trip Times Clear
Output matrix
Type:MTPR-650Hb(Note 3)
Ver : V□.□□.□□ Date: 20□□-□□-□□
□□□CRC :□□□□□□□□H
Main menu
1. State Display
2. Signal Revert
3. Report Display
4. Output Test
5. SYS Parameter
6. Setting Value
7. Clock Setting
8. Password
9. Version Info
1. State display
Protection Data
Measuring Data
Binary Input
Integral Energy
Phase Angle
Harmonic Data
DC Input Date
Trip Times
3. Report Display
Trip Report
Binary Report
Event Report
Report Clear
6.Settings(note 2)
Protecion on/off
......
Note: See protection
setting table for….
4.Output Test
Device Failure
Local Lock
Startup Cooling
Trip Native
Trip Native SW
Trip Other SW 1
Trip Other SW 2
Comp. V Out 1
Comp. V Out 2
V Adjudt Lock
Remote Close
Remote Trip
Operate All
7.Clock Setting
Date:□□-□□-□□
Time:□□:□□:□□
8.Input Password
□□□□
2. Signal Revert
Enter
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 23
Note 1:Basic parameters in system parameters and D/A setting are different according
to devices, see device description for details.
Note 2:See protection setting table for detailed setting menus.
Note 3:Corresponding to 103, 104version, program shows 103CRC, 104CRC
respectively.
State Display
【State Display】menu contains 8 submenus, protection data, measuring data, binary
input, pulse energy, phase angle display, harmonic data, DC display, switch open
counting . It is described as follows:
Protection Data ↑↓
Ia = □□□·□□ A
Ib = □□□·□□ A
Ic = □□□·□□ A
Uab = □□□·□□ V
Ubc = □□□·□□ V
Uca = □□□·□□ V
I0 = □□□·□□ A
F = □□□·□□ Hz
......
PT secondary line voltage value
Frequency
Protection CT secondary current value
Zero sequence voltage
Meas. Data ↑↓
IA = □□·□□□ A
IB = □□·□□□ A
IC = □□·□□□ A
Ua = □□□·□□ V
Ub = □□□·□□ V
Uc = □□□·□□ V
P = □□□□·□ W
Q = □□□□·□ var
Cosφ = □·□□□
......
Measuring CT secondary current value
PT secondary phase voltage value, when VV wring mode, not display
Cosine value of the angle between voltage and
current, when -90°<φ<90° COSφ will be positive;
when 90°<φ<270° COSφ will be negative.
Convert to PT, CT secondary active power
Convert to PT, CT secondary reactive power
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 24
Note:In the standard configurations, the input circuit of binary input has the connection
to an external 220VDC control power supply. When no DC control power supply or control
system is available on site, but a 110VDC control power supply is available, a 110VDC
control power supply may be used for direct connection through local hardware
adjustment, or the 24V power supply of the device may be used as the input power supply
(when the input common terminal is +24V, terminal number: B14, Terminal B01 is kept
float). However, this must be specified upon ordering
Integral Energy
+□□□□□□□·□□□kWh
+□□□□□□□·□□□kvh
-□□□□□□□·□□□kWh
-□□□□□□□·□□□kvh
The device real-time computes time
accumulation of active and reactive power,+ is
positive,- is negative.
Phase Angle ↑↓
Ua=□□□.□□°
Ub=□□□.□□°
Uc=□□□.□□°
Ia=□□□.□□°
Ib=□□□.□□°
Ic=□□□.□□°
IA=□□□.□□°
IB=□□□.□□°
IC=□□□.□□°
......
The angles are with respect to Ua, which default
value is 0°. When it’s V V connection,Ua, Ub, Uc
are changed into Uab, Ubc and Uca).
Protection current with respect to Ua
Measuring current with respect to Ua
When closed, means energy not storaged
Binary Input ↑↓
Breaker □
Trolley Run □
Trolley Test □
Earth Switch □
Spring □
Other CV □
Input 7 □
Input 8 □
Input 9 □
Input 10 □
......
Description depends on protection device, see
corresponding terminal diagram for details.
When closed, means breaker is closed; when opened,
means breaker is opened. Note: Position of breaker is
relative to protective.
When closed, means trolley is at operating position
When closed, means it is closed
When closed, means trolley is at testing position
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 25
Trip Times
Total:□□□□Times
Signal Revert
In the [Signal Revert] menu, press the “Enter” key, the signal relay and the “Operation”
indicator on the panel will be reset.
Report Display
The [Report Display] menu includes 4 submenus, including trip report, remote signal
report, event report and clear report. Event recording includes: device self-check fault,
device setting value modification, system parameter modification and setting zone
number modification, etc. The maximum events can be stored are: 50, 100, and 30.
Beyond this, the latest report will overwrite the earliest one. Press the “Enter” key to enter
the corresponding [To view xx report, please enter report number: 00] menu, and enter
0~99, press the “Enter” key to display the contents of that report. The screen is as follows.
Press key to see the specific operation value. Press the keys and to flip over.
Harmonic ↑↓
2nd :□□□·□□%
3rd :□□□·□□%
4th :□□□·□□%
5th :□□□·□□%
......
11th r:□□□·□□%
The order of harmonic from 2~11 is selected in
system
DC Input
DC1:□□□·□□mA
DC2:□□□·□□mA External DC input 4~20mA (2-way)
Report No.:□□ ↓
□□□□-□□-□□
□□:□□:□□:□□□
□□□□□□
Year, month, day
Hour, minute, second and millisecond
when it took place
Report content description
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 26
Operation values
Output Test
After entering the [Output Test] menu, the correct password is required to enter the
[Output Test] menu. It displays the following:
Press “Enter” key
——————>
<——————
Press “Cancel” key
(Note:After the signal relay closes, make sure to press “Revert” key or select “Signal
revert” menu and press “Enter” key to revert the signal relay.When doing output test to the
6 protection outputs, the startup relay will be closed automatically. The “+”, “-” keys are
used for switching between the “On/Off” control).
System Parameters
After entering the [SYS Parameters] menu, the correct password is required to enter
the [SYS Parameters] menu. It displays the following:
4. Output test ↑↓
Device Failure
Local Lock
Startup Cooling
Trip Native
Trip Native SW
Trip Other SW 1
Trip Other SW 2
Comp. V Out 1
. . . . . .
Operate All
Device fault signal
On Off
Ia = □□□·□□ A
Ib = □□□·□□ A
Ic = □□□·□□ A
I0 = □□□·□□ A
U2 = □□□·□□ V
U0 = □□□·□□ V
Ua = □□□·□□ V
Ub = □□□·□□ V
Uc = □□□·□□ V
......
5.Parameters ↑↓
Setting Zone No.
Comm. Setting
B.Parameters
D/A setting
Integral Energy
Trip Times Clear
Output Matrix
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 27
Com. Setting ↑↓
RS485 device address
□□
RS485 baud rate
□□
IP address
Subnet mask
K W default value
Setting zone number setting: range 00~07.
Communication settin
Setting of basic parameters
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to
adjust the accuracy of the channel output. The DA1~DA2 channel selection is used to
select the corresponding analog quantity channel (see the description of the protection
device for specific reference quantities). In the accuracy test, make sure the field ground
is in good contact; otherwise the accuracy might be affected.
Integral energy setting
The initial value of energy can be set including: positive active energy, positive
reactive energy, negative active energy and negative reactive energy.
Clear trip count
Communication address of device 01~99
00:2.4KB;01:4.8KB;02:9.6KB;03:19.2KB;
04:38.4KB;05:115.2KB;
Setting CT rated secondary current 00:5A;01:1A
Setting PT ratio:1~1500
Setting CT ratio:1~5000
B. parameters ↑↓
Rating Current
□□
PT ratio
□□□□
CT ratio
□□□□
PT wring mode
□□
Harmonic Channel
□□
Wave Record
□□
......
Setting PT secondary wring mode 00:Y-Y;01:
V-V
Setting the harmonic analog channel to be monitored
0~7,select 0 to quit harmonic calculation function
Setting fault recorder on/off 0~1,select 0 to quit fault
recorder function
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 28
Clearing statistical count of trip.
Settings
After entering the password, you can enter the [Setting Value] menu. See the
setting description of the protection device for the detailed description.
Clock Setting
A battery-back real-time clock is provided in the device, which can perform time
adjust remotely via the communication network or in-site time adjust in the [Clock Setting]
menu.
Enter this menu and press the “Enter” key, the clock will stop
refreshing and a cursor will appear. Move the cursor to the
desired position for modification by pressing the ““,
““ keys, modify to the desired value with the “+”, “-” keys.
Press the “Enter” key to complete setting. If the “Cancel”
key is pressed, the setting will be cancelled and the screen
continues to refresh the clock.
Password
The [Password] menu is used to modify the password for entry into the Settings,
System parameters and Output Test submenus. The initial password is provided by the
factory. The universal password is “1000”.
Move the cursor to the desired position for modification by
pressing the ““, ““ keys, modify to the desired password
with the “+”, “-” keys. Press the “Enter” key to enter the new
password setting menu as above; press the “Cancel” key to
cancel the setting.
GPS clock synchronization
The GPS clock synchronization signal is input as rs485 differential voltage, the
device is able to receive GPS clock minute synchronization (or second synchronization). If
there is GPS signal, there will be and flashing on the bottom of cycle menu;
otherwise won’t.
The principle of GPS clock synchronization: The second pulse or minute pulse act
with the monitoring system, the time base with second precision is sent by monitoring
system, when the GPS second differential signal arrives, the time base is unified and the
milliseconds are cleared..
Version Information
In the main menu, after entering the [9. Version Info.] menu, the model, software
7. Clock Setting
Date:20□□-□□-□□
Time:□□:□□:□□
Input Password
0 0 0 0
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 29
Fig 6-1
MTPR-650Hb
D1(3,5)
D2(4,6) A01
D17
D19
D21 A02
D18(20,22)
14(16,18)
Ia’(Ib’, Ic’)
Ia(Ib, Ic)
Ua
Ub Power supply
Uc
Ua’(Ub’, Uc’)
version and date of the device will be displayed.
Note: For a corresponding nonstandard model, the device’s displayed model does not
have to be changed.
5. Check of protection function
6.1 Check of over-current protection
Over-current protection can be divided into three sections and each section can
be set as On/Off. All are based on the same principle. Take the example of
over-current section I, wire as Fig 6-1,set over-current section I protection to on, set
over-current section I direction to on and set over-current sectionI composite voltage
block to on, set hard strap protection to off(when in on, over-current protection strap
C15 should be connected).
Set according to the following table. Measure the operating current and take down in
the following table. When over-current section I operates(delay has T1, T2, T3), the
corresponding terminals should be connected according to output matrix.
Add phase
A current Ubc,
add voltage
30V, voltage
phase as
reference,
check the
operating zone.
Over-current
section I setting(A) 1ln 2ln 5ln 10ln
Operating value
Operating zone
Add phase
B current Uca,
Over-current
section I setting (A) 1 ln 2 ln 5 ln 10 ln
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 30
add voltage
30V, voltage
phase as
reference,
check the
operating zone
Operating value
Operating zone
Add phase
C current Uab,
add voltage
30V, voltage
phase as
reference,
check the
operating zone
Over-current
section I setting (A) 1 ln 2 ln 5 ln 10 ln
Operating value
Operating zone
Instantaneous
over-current
protection
setting is 5A,
Add current
6A
Low voltage
setting(V) 20 40 60 80
Low voltage
block value
Negative sequence
voltage setting( V) 5 10 15 20
Negative voltage
block setting
6.2 Check of Zero sequence voltage alarm
Zero sequence voltage alarm is judged by Zero sequence voltage. Wire as Fig 6-2,
set Zero sequence voltage alarm to on.
U0
U0’
Power supply
MTPR-650Hb
D23 A01
D24
A02
Fig 6-2
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 31
Set according to the following table. Measure the operating current and take down in
the following table. When zero sequence voltage alarm operates, the corresponding
terminals should be connected according to output matrix(factory fault of output matrix is
0).
Zero sequence voltage
setting(V) 60 100 120 180
Zero sequence voltage
delay(s) 5 4 2 1
Zero sequence voltage
operating value(V)
Zero sequence voltage
operating time(s)
6.3 Check of Bus charging protection
Bus charging protection is judged by the maximum phase current. Wire as Fig
6-3,set Bus charging protection to on, set hard strap function to off(when in on,
charging protection strap C14 should be connected).
According to binary input checking method, let the breaker position B02 change
from open to close. The bus charging protection is effective during on time. When
exceeding on time, the bus charging protection is automatically off.
Set according to the following table. Measure the operating current and take down
in the following table. When over-load alarm operates, the corresponding terminals
should be connected according to output matrix.
Bus charging protection
current setting (A) 1ln 2 ln 5 ln 10 ln
Bus charging protection 6 5 3 1
Ia(Ib, Ic)
Ia’(Ib’, Ic’)
Power supply
MTPR-650Hb
D1(3,5) A01
D2(4,6)
A02
Fig 6-3
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 32
delay setting(s)
Bus charging protection on
time (s) 3 3 3 3
Bus charging protection
operating value (A)
Bus charging protection
operating time(s)
6.4 Check of zero sequence over-current protection
Zero sequence over-current protection is judged by zero sequence current. Wire as
Fig 6-4,set zero sequence over-current protection to on.
Set according to the following table. Measure the operating current and take down in
the following table. When zero sequence over-current protection operates, the
corresponding terminals should be connected according to output matrix.
Zero sequence
over-current setting (A) 1 2 5 10
Zero sequence
over-current delay(s) 5 4 2 1
Zero sequence
over-current operating
value(A)
Zero sequence
over-current operating
time(s)
I0
I0’
Power supply
MTPR-650Hb
D07 A01
D08
A02
Fig 6-4
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 33
6.5 Check of over-load protection
Over-load protection is judged by the maximum phase current. Wire as Fig 6-5,set
over-load to on.
Set according to the following table. Measure the operating current and take down
in the following table. When over-load alarm operates, the corresponding terminals
should be connected according to output matrix.
Over-load setting(A) 5 10 15 20
Over-load delay(s) 10 5 2 1
Over-load operating value(A)
Over-load operating time(s)
6.6 Check of PT, CT Failure
Wire as Fig 6-1,simulate PT failure or CT failure,the device will send alarm signal
and the alarm light will lit.
The checking method of other protection functions such as starting fan, block voltage
regulation, composite voltage block output is easy. We are not going to elaborate it here;
users may refer to "device function" section of this manual.
Ia(Ib, Ic)
Ia’(Ib’, Ic’)
Power supply
MTPR-650Hb
D1(3,5) A01
D2(4,6)
A02
Fig 6-5
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 34
Appendix 1:Device terminal diagram
(+24V)
Input 7
D26
D28D27
D25 DCSIn1+
DCSIn1-
DCSIn2-
DCSIn2+
Note:
1.Ia1,Ib1,Ic1 are protection
currents.
2.IA,IB,IC are measure
currents.
3.I0 is zero sequence current.
4.Ua,Ub,Uc,U0 are voltages.
5.DCSIn1~2 are 2-way 4~20mA inputs.
6.DCS1~2 are 2-way 4~20mA outputs.
7.COM1 and COM2 are 485 interfaces, Net1 and Net2 are
ethernet ports.
8. Whether +24V on IO board is the standard configuration or not can be fixed when using internal +24V as feeder.
Uc Uc'
U0 U0'
Input 10
Input 9
Input 8
Ub'Ub
Ua'Ua
IC'IC
D02
D04
D06
D08
D10
D12
D14
D16
D18
D20
D22
D24
I/OPOWER
B01B02
ON B06B05B04B03
IaD01
IbD03
IcD05
IB
D07
OFFB10
B08B09
B12
B14
B13
B11
B07
A02
A01
I0
D09
D11 IA
D13
D15
Power off
Power off
B17B18
B16
B19
B21B20
D17
D19
D21
D23
B23B24B25B26B27B28B29
B22
A04
A06A05
B15A03
B30B31
B32
B34B35B36
B33
CPU
Ia'
Ib'
Ic'
IA'
AC
I0'
IB'
COM2A
COM2A
COM2B
COM2B
Deb
ug
COM2
COM1
Net2
Net1
Run
C13
C17
DCS2+C19C20 DCS2-
C18 DCS1-
C16DCS1+
C14C15
C12
C10C11
COM1B
C08
C09
COM1B
COM1A
C06
C07
COM1A
C02
C04C05
C03
GPSB
GPSAC01
A21
A23A24
A22
A19
A20
A18
+WC
-WC
Trip coil
A10
A17A16A15A14A13A12A11
A08A09
A07
Closure coil Input 13
Input 14
Input 11
Input 12
Terminals diagram of MTPR-650Hb microcomputer transformer backup protection
measuring and control device
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 35
Appendix 2:Device typical wiring diagram
(+24
V)
Blo
ck
back
up p
ow
er
auto
-sw
itchin
g o
f th
is s
ide
WC
WC
CP
U plug-ins
Po
wer
AC plug-ins
plug-ins
WC
WC
MTPR-650Hb transformer backup protection device
Debugging port
Ethernet port
AC plug-ins
I/O plug-ins
I0'I0Ic'IcIb'IbIa'Ia
Operation circuit
disconnected
Power supply+
Power off
Shielded ground
Power supply-
Trip position
Closure
position
Closure position
monitor
Trip coil
Trip position
monitor
Closure coil
-WC
Remote control
common portRemote control
closureManual closure
input
Remote control trip
Manual trip input
+WC
Input 12
Input 11
Input 10
Input 8
Input 9
Input 7
Sp
rin
g e
nerg
y
no
n-s
tora
ged
Gro
un
de
d c
utter
positio
n
Trolley
test
position
Tro
lley w
ork
ing
po
sitio
n
Bre
aker
positio
n
Input
co
mm
on
port-
GPSA
GPSB
Input 13
Input 14
Input common(+24V)
COM A
COM A
COM B
COM B
COM A
COM A
COM B
COM B
DCSOut1+
IA IA' IB IB'Ua Ua' Ub Ub' Uc Uc' U0'U0
Bre
ake
r
Charged protection
plate
Over-current protection plate
DCSIn1+
DCSOut1-
DCSOut2+
DCSOut2-
DCSIn2+
IC'IC
Co
mp
ou
nd
vo
lta
ge
of
the
oth
er
sid
e
Note:
1.ZK(remote/local switchover switch) and KK(manual operation switch) in the diagram are installed on the plate of panel, and
when using remote/local switchover switch and manual operation button of device panel, terminal A21 would be put in +KM. 2.PT secondary in the diagram is wye-connection, and when it is V-V connection on site, terminals D15,D20 would be connected
with phase A of PT secondary, terminals D16,D17 with phase B of PT secondary, terminals D18,D19 with phase C of PT secondary.
Bus voltage Measuring current
DCSIn2-
DCSIn1-
Block backup power
auto-switching of
this side
Ethernet port
Net 1
Net 2
Shielded ground
Zero sequence
voltage Protection currentZero sequence current
Standby
Device fault signal
De
vic
e f
au
lt sig
na
l
Trip
se
ctio
n o
f
this
sid
e
Start wind
cooling
Start wind
cooling
Trip section
of t
his side
Trip section
of t
his side
Trip section
of t
his side
Trip
sw
itch
1 of
the
oth
er side
Trip
swit
ch 1 of
the
other side
Trip
switch 2 o
f th
e ot
her side
Trip
switch 2
of
the
other side
Co
mp
ou
nd
vo
lta
ge
ou
tpu
t 1
Compound voltage
output 2
Compound voltage
outp
ut 1
Compound voltage
output 2
Block voltage regulator
norm
ally
open
Block voltage
regulator
com
mon
Block voltage regulator
norm
ally
clo
sed
MTPR-650Hb transformer backup protection device typical wiring diagram
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 36
Appendix 3: Operation circuit of MXPR-600Hb series device
Traditional operating circuits are started by current, while a voltage maintaining circuit
realizes electric trip prevention. An anti-trip relay will be selected depending on the current
of the trip/closing circuit of the circuit breaker. However, this has poor generality and can
hardly be realized for circuit breakers with low trip and closing currents (such as 10KV
circuit breakers from AEG Company in Germany, whose trip and closing currents are not
greater than 0.2A). To simplify wiring and design finalization, and to improve the generality
of the product, we offer a new operating circuit shown below..
TBJ2
TBJTCJ1
SHJ
YTJ
HBJA20
HBJ
Trip output
TCJ2
STJ
STJ
1LP
JnTn3
Tn4
HWJ
A10TWJ
A09
Manual trip
DL
A13HWJ
TWJ
A08TWJ
A12HWJ
A14
A20
A07
A11
TCJ
SHJ
TBJ1
Tn2
A24
Tn1
Jn
A22
YHJ
A18
A19
A17
A23
A15
Clo
su
re c
ircu
itT
rip
circu
it
Fuse
Small bus
TQDL
HQDL
KK84 5
ZK2
2LP
7KK
686ZK
3ZK
1
A16
closureProtection
Schematic diagram of operating circuit
Manual for MTPR-650Hb main transformer backup protection device ETWLD[K]-JY-228-2010
EAGLE TECHNOLOGY Address: No. 201, L-2, B-11, Surya City, Bangalore-560081
E-mail: [email protected], Phone No: +91-9535-122013 , Web: http://eaglewanlida.com Page 37
In the diagram, KK is the traditional operation switch used for manual trip/closing
operation. ZK is the shift switch used for shift between local and remote control. When ZK
is in the “Remote” position, the remote control circuit power will be connected, i.e.,
Terminal A22 of the device is connected to +KM, while the manual operation circuit power
will be cut off and manual closing and manual trip won’t work. On the contrary, when ZK is
in the “Local” position, the manual operation circuit power will be connected, while the
remote control circuit power will be cut off.
Note: In the dotted frame, there is the internal circuit of the protection device. All of our
devices marked with “anti-trip circuit” are designed according to this operation circuit.
Terminals Tn1, Tn2 corresponding to protection relay Jn are determined by the
corresponding protection output control word. Jn can be any one or more of Protection
outputs 1-8.
Whether in local control or in remote control, jump phenomenon occurs on the
premise that terminal A15 of the device is always connected with +WC. After manual or
remote closing, if a short-circuit fault occurs, the protection will operate to trip the circuit
breaker. Though Terminal A15 of the device is connected with +WC. The closing circuit is
disconnected by TBJ1. Therefore, the circuit will not be closed again. The circuit breaker
jump phenomenon can be effectively avoided in this way.