Back to basics: AcousticsHVAC installations for vibration reduction

Presented by Clem Sturgess

Causes of vibration

www.vibrationisolation.com.au

Vibration is generally transferred into the structure from out of balance or misaligned rotating equipment

Page 2: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Effect of vibration onequipment

www.vibrationisolation.com.au

Constant vibration forces from misaligned or out of balance forces act on the system like bending a piece of wire backwards and forwards

Vibration noise

www.vibrationisolation.com.au

Vibration can travel easily through structures and is reradiated from walls and ceilings as noise, many floors away from the source of the noise.

Page 3: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Effect of vibration on humans

www.vibrationisolation.com.au

Pipework Support

www.vibrationisolation.com.au

It is important to isolate pipework that is connected to sources of vibration. Generally the pipes should be supported up to 100 pipe diameters from the

source of the vibration.

Page 4: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Pipework Support

www.vibrationisolation.com.au

The spacing of pipework hangers is dependant on the size of the pipework, however, the pipework should be supported at all changes of direction.

Pipework Support

www.vibrationisolation.com.au

Pipework should still be isolated even if a flexible connection is used. Water can take a large distance to settle into even laminar flow in pipework. Also

under high pressures, the flexible connection may be not that flexible

Page 5: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Under normal operation, seismic mounts act like standard open springs

www.vibrationisolation.com.au

Seismic vibration mount•How they work

3mm gaps between central block and rubber provide support in the event of seismic activity

www.vibrationisolation.com.au

Seismic vibration mount•How they work

Page 6: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Force transmitted through to structure

3mm gaps between central block and rubber provide support in the event of seismic activity

www.vibrationisolation.com.au

Seismic loading on equipment

Seismic vibration mount•How they work

Isolation Sleeves

www.vibrationisolation.com.au

Prevents bridging the rubber on the base of the mount

Page 7: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

How Vibration Isolation Works

www.vibrationisolation.com.au

Natural Frequency

www.vibrationisolation.com.au

When an object is struck. It will vibrate at its natural frequency.

Page 8: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Static deflection

www.vibrationisolation.com.au

The more a spring or rubber deflects under load, without compressing to solid, the lower the natural frequency of the mount. This is called the static deflection.

Resonance

www.vibrationisolation.com.au

If an object is given repeated pushes at its natural frequency it will go into resonance. It will move slightly more each time until it gets out of control.

Page 9: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Startup Issues

www.vibrationisolation.com.au

As a motor ramps up from stopped to operating speed, it must pass through the resonant frequency.

The equipment may require some restraint

Effect of height

www.vibrationisolation.com.au

The higher storeys are inherently less stable than lower storeys. So the higher in the building, the more isolation is required.

Page 10: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

Important factors in vibration isolation selection

Isolation Efficiency Chart Static Deflection Guide

www.vibrationisolation.com.au

The 6 most common vibration problems

www.vibrationisolation.com.au

Page 11: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

1: Fixed Pipe Stands

www.vibrationisolation.com.au

Problem:Well isolated pumps or chillers connected to pipes with fixed stands

1: Fixed Pipe Stands

www.vibrationisolation.com.au

Problem:Well isolated pumps or chillers connected to pipes with fixed stands

Isolated EquipmentIsolated Equipment

Fixed pipe mountingFixed pipe mounting

Page 12: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

1: Fixed Pipe Stands

www.vibrationisolation.com.au

Solution:Install spring mounts on the pipe stand base so that they match pump spring deflection

orSupport the top of the pipework using isolation hangers and remove pipe stand

Pipe stand SHS spring hanger

1: Fixed Pipe Stands

www.vibrationisolation.com.au

Pipe stand

spring hanger

Solution:Install spring mounts on the pipe stand base so that they match pump spring deflection

orSupport the top of the pipework using isolation hangers and remove pipe stand

Page 13: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

2: Noise transmitted from isolated pumps

www.vibrationisolation.com.au

Problem:Noise transmitted from isolated pumps

Pumps on isolated inertia bases

Pumps on isolated inertia bases

2: Noise transmitted from isolated pumps

www.vibrationisolation.com.au

Solution:Check under inertia base for nuts, bolts or other debris or adjust springs to raise pumps

Shifter

Nut

Bolt

Page 14: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

3: Pipework hard fixed into wall or ceiling

www.vibrationisolation.com.au

Problem:Noise transmitted from pipework passing through a wall or ceiling

Spring mounted pipework next to a hard grouted wall connection

Spring mounted pipework next to a hard grouted wall connection

3: Pipework hard fixed into wall or ceiling

www.vibrationisolation.com.au

Solution:Seal around openings for pipework with flexible mastic or insulation

10-15mm clear gap around pipe, filled for a depth of 12mm with non-setting flexible mastic similar to Bostik Fireban One.

10-15mm clear gap around pipe, filled for a depth of 12mm with non-setting flexible mastic similar to Bostik Fireban One.

25mm thick Rockwool sectional pipe sleeve insulation around pipe. Rockwool is to be encapsulated to prevent loss of fibres

25mm thick Rockwool sectional pipe sleeve insulation around pipe. Rockwool is to be encapsulated to prevent loss of fibres

1.2mm thick steel or copper sleeve grouted into wall with non-shrinking grout1.2mm thick steel or copper sleeve grouted into wall with non-shrinking grout

75mm

Page 15: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

4: Bridging of spring hangers

www.vibrationisolation.com.au

Problem:Rod is touching the side of the hanger cage, causing bridging of isolation element

BridgingBridging

4: Bridging of spring hangers

www.vibrationisolation.com.au

Solution:Realign pipe clip or hanger cage so rod is central to the hole in the hanger cage

Page 16: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

5: Hard bolted pipework

www.vibrationisolation.com.au

Problem:Condenser pipework hard bolted to floor or walls

5: Hard bolted pipework

www.vibrationisolation.com.au

Solution:Suspend pipework from raised frame

Page 17: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

5: Hard bolted pipework

www.vibrationisolation.com.au

Solution:Install new wall bracket and suspend pipes from the bracket.

6: Generator vibration transmission

www.vibrationisolation.com.au

Problem:Incorrectly adjusted spring mounting

Springs not taking the generator loadSprings not taking the generator load

Page 18: Back to basics: Acoustics - AIRAH...Back to basics: Acoustics HVAC installations for vibration reduction Presented by Clem Sturgess Causes of vibration Vibration is generally transferred

6: Generator vibration transmission

www.vibrationisolation.com.au

Solution:Adjust the height adjustment bolts until the generator is supported by the springs only

Thank you for your timeIf you have any further questions or noise problems then please