Air-Side Economizer Cycles Applied to the Rejection of Data Center Heat B. Keith Dunnavant, P.E. Manager, Data Center Cooling Solutions Munters Corporation

Transcript of B. Keith Dunnavant, P.E. Manager, Data Center Cooling ... global leader in energy efficient air...

Air-Side Economizer Cycles

Applied to the Rejection of

Data Center Heat B. Keith Dunnavant, P.E.

Manager, Data Center Cooling Solutions

Munters Corporation

● Founded in 1955

● Manufacturing & Sales Locations in 30 countries

● A Global leader in Air Treatment

• Air-to-Air Energy Recovery Systems

• Indirect & Direct Evaporative Cooling

• Mist Elimination Systems

• Desiccant & Mechanical Dehumidification

• Data Center Heat Rejection Systems

• VOC Abatement

Products

M Fan -

Supply Air

Plenum

(Cold-Aisle)

Server Racks

qITE

Direct Air-side Economizer

MERV 8 Pre-filter MERV 13 filter

O/A

R/A Relief

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.143 Inches HG

PSYCHROMETRIC CHART728 FEET

Weather Data Location:

CHARLOTTE_DOUGLAS_INTL_ARPT, NORTH_CAROLINA, USA

Weather Hours

11 to 1

22 to 12

33 to 23

44 to 34

55 to 45

66 to 56

77 to 67

88 to 78

99 to 89

Recommended

-10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

DRY BULB TEMPERATURE - °F

.001

.002

.003

.004

.005

.006

.007

.008

.009

.010

.011

.012

.013

.014

.015

.016

.017

.018

.019

.020

.021

.022

.023

.024

.025

0

5

10

15

20

25

30

35

40

45

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

15%

25%

2%

4%

6%

8% RELATIVE HUMIDITY

10% RELATIVE HUMIDITY

20%

30%

40%

50%

60%

70%

80%

90%

-50

05

510

1015

1520

20 25

25 30

30 35

3540

40 45

45 50

5055

5560

60

65

65

70

70

75

75

80 WET BU

LB TEMPER

ATURE - °F

80

12.0

12.5

13.0

13.5

14.0

VO

LU

ME

- CU

.FT

. PE

R L

B. D

RY

AIR

14.5

HU

MID

ITY

RA

TIO

- P

OU

ND

S M

OIS

TU

RE

PE

R P

OU

ND

DR

Y A

IR

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.143 Inches HG

PSYCHROMETRIC CHART728 FEET

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Too Humid

Too Dry

Too Hot

Just Right

41.9F dp

59F dp

80.6F db 64.4F db

1 2

1

2

DIRECT EVAPORATIVE

COOLING … A CONSTANT

WET BULB PROCESS

HUMIDIFIES AND COOLS

Use Direct Evaporative Cooling to Expand ASE Envelope

1. Cool Hot, Dry Air

2. Humidify in Winter

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.915 Inches HG

PSYCHROMETRIC CHART6 FEET

Weather Data Location:

VANCOUVER, BRITISH_COLUMBIA, CANADA

Class A1

Recommended

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

DRY BULB TEMPERATURE - °F

.001

.002

.003

.004

.005

.006

.007

.008

.009

.010

.011

.012

.013

.014

.015

.016

.017

.018

.019

.020

.021

.022

.023

.024

.025

.026

.027

.028

.029

.030

5

10

15

20

25

30

35

40

45

50

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

15%

25%

2%

4%

6%

8% RELATIVE HUMIDITY

10% RELATIVE HUMIDITY

20%

30%

40%

50%

60%

70%

80%

90%

05

510

1015

1520

2025

25 30

3035

35 40

40 45

45 50

50 55

5560

60

65

65

70

70

75

75

80

80

85 WET BULB TEM

PERATURE - °F

85

90

12.0

12.5

13.0

13.5

14.0

VO

LU

ME

- CU

.FT

. PE

R L

B. D

RY

AIR

14.5

HU

MID

ITY

RA

TIO

- P

OU

ND

S M

OIS

TU

RE

PE

R P

OU

ND

DR

Y A

IR

85/74.3

Return Air

79.1/68.8

81.3/67.7

25/50%

Mix

S/A

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 1/22/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 1/22/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 1/22/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 1/22/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 1/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 1/25/2012

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.915 Inches HG

PSYCHROMETRIC CHART7 FEET

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Mix Cold Dry Outdoor Air

With Warm Return Air

Humidify with Direct Evaporative Media

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.898 Inches HG

PSYCHROMETRIC CHART23 FEET

Weather Data Location:

SACRAMENTO_METROPOLITAN_AP, CALIFORNIA, USA

Weather Hours

27 to 1

54 to 28

81 to 55

108 to 82

135 to 109

162 to 136

189 to 163

216 to 190

243 to 217

Recommended

-10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

DRY BULB TEMPERATURE - °F

.001

.002

.003

.004

.005

.006

.007

.008

.009

.010

.011

.012

.013

.014

.015

.016

.017

.018

.019

.020

.021

.022

.023

.024

.025

0

5

10

15

20

25

30

35

40

45

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

15%

25%

2%

4%

6%

8% RELATIVE HUMIDITY

10% RELATIVE HUMIDITY

20%

30%

40%

50%

60%

70%

80%

90%

-50

05

510

1015

15 20

20 25

25 30

3035

35 40

40 45

45 50

50 55

5560

60

65

65

70

70

75

75

80 WET BU

LB TEMPER

ATURE - °F

80

85

12.0

12.5

13.0

13.5

14.0

VO

LU

ME

- CU

.FT

. PE

R L

B. D

RY

AIR

HU

MID

ITY

RA

TIO

- P

OU

ND

S M

OIS

TU

RE

PE

R P

OU

ND

DR

Y A

IR

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.898 Inches HG

PSYCHROMETRIC CHART23 FEET

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Cool Hot Dry Air

95F cools to 75F

Direct Evaporative Cooling

MERV 8 + MERV 13 Filters

Wet Bulb Economizer Requires:

• Modulating O/A

Dampers

• Pressure Controls

• Humidity Controls

• MERV 8 +13 Filters

Does Not:

• Reduce Cooling Load

At WB Design

Modulating Face & Bypass

Dampers

VFD Controlled

Relief Fans

(Pressure Control)

Cooling Coil

Direct Evaporative Cooling

Mixing

Box

Return Damper

O/A

R/A S/A

Supply

Fans

Direct Air-Side Economizer

• Takes advantage of cooler ambient conditions

• Outdoor air is delivered DIRECTLY into the data hall

• Requires Good Air Filtration

• Requires Relief fans or barometric relief

• Requires a good means of mixing O/A with R/A

• Requires a means of humidification for winter use

• Requires a means of accurately regulating the humidification

• Cannot be used during high ambient dew point conditions

95F

75F

Indirect Air Side Economizer Polymer Tube Heat Exchanger

Indirect Air-Side Economizer with

Polymer Tube Heat Exchanger

95F 75F

96.5F

3 Operating Modes 1) Winter – Dry HX

2) Summer – Wet HX (IEC)

3) Summer Extreme – IEC + DX

100F db / 70F wb

76.6F

Condenser Coil

Indirect Air-Side Economizer

• Uses an air-to-air heat exchanger to reject heat from the data

hall to a scavenger outdoor airstream

• Outdoor air IS NOT delivered DIRECTLY into the data hall

• Filtration may be eliminated from some units

• Room pressure is not impacted

• Room absolute humidity levels are not impacted

• CAN be used with great benefit during high ambient dew point

And wet bulb conditions

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.143 Inches HG

PSYCHROMETRIC CHART728 FEET

Weather Data Location:

CHARLOTTE_DOUGLAS_INTL_ARPT, NORTH_CAROLINA, USA

Weather Hours

11 to 1

22 to 12

33 to 23

44 to 34

55 to 45

66 to 56

77 to 67

88 to 78

99 to 89

Recommended

-10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

DRY BULB TEMPERATURE - °F

.001

.002

.003

.004

.005

.006

.007

.008

.009

.010

.011

.012

.013

.014

.015

.016

.017

.018

.019

.020

.021

.022

.023

.024

.025

0

5

10

15

20

25

30

35

40

45

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

15%

25%

2%

4%

6%

8% RELATIVE HUMIDITY

10% RELATIVE HUMIDITY

20%

30%

40%

50%

60%

70%

80%

90%

-50

05

510

1015

1520

20 25

25 30

30 35

3540

40 45

45 50

5055

5560

60

65

65

70

70

75

75

80 WET BU

LB TEMPER

ATURE - °F

80

12.0

12.5

13.0

13.5

14.0

VO

LU

ME

- CU

.FT

. PE

R L

B. D

RY

AIR

14.5

HU

MID

ITY

RA

TIO

- P

OU

ND

S M

OIS

TU

RE

PE

R P

OU

ND

DR

Y A

IR

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 4/25/2012

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 29.143 Inches HG

PSYCHROMETRIC CHART728 FEET

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Too Humid

Too Dry

Too Hot

Just Right

41.9F dp

59F dp

80.6F db 64.4F db

Indirect Evaporative

Heat Exchanger Provides

80% of Total Cooling

Indirect Evaporative

Heat Exchanger Provides

100% of Total Cooling

Indirect Air-Side vs. Direct Air-Side Economizer

3 Primary Functions Required by the

Data-Center Air Management System

• Heat Rejection

• Particulate Removal (Filtration)

• Ventilate & Control Pressure & Humidity

Data Center Heat Rejection Total Air Management Design Schematic integrating IASE

Make-up Air & Humidity Control Module

Integrated with a Heat Rejection Unit

Polymer Tube HX module

Flexible Polymer Tubes

●8 feet length

●75-80% approach to outdoor

scavenger air wb

●50-55% dry heat recovery

Close-up of tube face and water-tight seal

Water distribution nozzle

Bottom of Heat Exchanger

Water Sprays on

Control/Electrical panels

Compressor vestibule

Aluminum mesh

Scavenger air filter

Supply air isolation damper

with walk on grating installed above

Benefits of IASE Cooling Systems

● Lowest life-cycle cost option for cooling data-centers in most climates

● Filters may be eliminated from 75% of the Cooling Units – resulting in reduced

maintenance and fan power

● Reduced risk from Outdoor Air Pollutants entering the data-center

● Dry heat exchange during cooler ambient conditions eliminates freeze concerns

● Recirculation air cooling does not impact space humidity.

● Reduced water consumption compared to data-centers cooled with conventional

water-side economizer systems

●Rapid Restart following Power Loss

●No relief fans or space pressure controls required

Predicted Annual Hrs Mech. Cooling Active 1437

% Annual Hrs IEC Rejects 100% of load 83.6%

Estimated system SEER 41.4

Percentage of cooling provided by Mechanical vs IEC

0%

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

79.0

73.0

67.0

61.0

55.0

49.0

43.0

37.0

31.0

25.0

19.0

13.0 7.

01.

0

Ambient WB

Pe

rce

nta

ge

0

100

200

300

400

500

600

Bin

Ho

urs

Mech. Cooling

IEC Cooling

Bin Hours

Performance of IASE operating in Newark, NJ

95F hot-aisle cooling to 75F Cold-aisle

Annual COP = 12.1 / PUEc = 1.08

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 28.701 Inches HG

PSYCHROMETRIC CHART1148 FEET

Weather Data Location:

ROANOKE_REGIONAL_AP, VIRGINIA, USA

Weather Hours

12 to 1

24 to 13

36 to 25

48 to 37

60 to 49

72 to 61

84 to 73

96 to 85

108 to 97

Class A1

Recommended

-10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110

DRY BULB TEMPERATURE - °F

.001

.002

.003

.004

.005

.006

.007

.008

.009

.010

.011

.012

.013

.014

.015

.016

.017

.018

.019

.020

.021

.022

.023

.024

.025

0

5

10

15

20

25

30

35

40

45

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

15%

25%

2%

4%

6%

8% RELATIVE HUMIDITY

10% RELATIVE HUMIDITY

20%

30%

40%

50%

60%

70%

80%

90%

-50

05

510

1015

1520

20 25

25 30

30 35

35 40

40 45

45 50

50 55

5560

60

65

65

70

70

75

75

80 WET BU

LB TEMPER

ATURE - °F

80

12.5

13.0

13.5

14.0

14.5

VO

LU

ME

- CU

.FT

. PE

R L

B. D

RY

AIR

HU

MID

ITY

RA

TIO

- P

OU

ND

S M

OIS

TU

RE

PE

R P

OU

ND

DR

Y A

IR

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Prepared By: Name: Keith Dunnavant Company: Munters Tel: 540-264-1022 email: [email protected] Date: 2/20/2012

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

A global leader in energy efficient air treatment solutionswww.munters.us 800-843-5360 [email protected]

Barometric Pressure - 28.701 Inches HG

PSYCHROMETRIC CHART1148 FEET

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

IEC

DX

IEC Provides 80%

Of total cooling

When Ambient WB

Is < 75F

95F

75F

Rooftop View of Polymer Tube IASE Units

on Australian Data Center

Polymer Tube IASE Units

Operating in Wenatchee, WA

Units Seismic Certified to Ip=1.5

42,000 CFM

Operating in Alhambra, CA

IASE Designs using

Indirect Evaporative Cooling

Meet Current and Future Load Requirements

Now – 150kW with 20F dt

95F db / 80F wb

Outdoor air

DB (°F) WB (°F) ACFM

1 (R/A) 95.0 68.6 25,874

2 97.2 69.3 25,975

3 84.0 65.3 25,362

4 (S/A) 75.0 62.3 24,941

5 (O/A) 95.0 80.0 28,916

6 85.0 82.4 28,610

7 (E/A) 94.9 84.6 29,135

*Includes estimated supply fan heat

Elevation = 1,175 ft (Roanoke, VA

19.25 tons DX

COP = 4.7

DB (°F) WB (°F) ACFM

1 (R/A) 115.0 74.2 25,874

2 117.2 74.8 25,975

3 88.7 66.8 24,692

4 (S/A) 80.0 64.0 24,298

5 (O/A) 95.0 80.0 27,910

6 87.8 85.2 27,865

7 (E/A) 97.5 87.1 28,355

Future – 253kW with 35F dt

18 tons DX

COP = 7.9

25,000 CFM

Standard Rooftop Unit

(DX sized for extreme WB)

25,000 CFM

Standard Rooftop Unit

With MUA Humidity Control

25,000 CFM

Standard Rooftop Unit

with 100% DX

25,000 CFM

Standard Perimeter Mount Unit