B-6 Testing Numerical Transformer Differential Relays - IEEE

40
IEEE Rural Electric 20 Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., Inc.

description

 

Transcript of B-6 Testing Numerical Transformer Differential Relays - IEEE

Page 1: B-6 Testing Numerical Transformer Differential Relays - IEEE

IEEE Rural Electric 2009

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays

Steve Turner

Beckwith Electric Co., Inc.

Page 2: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Commissioning versus Maintenance Testing

Types of Transformer Differential Protection: Restrained Phase Differential High Set Phase Differential Ground Differential

INTRODUCTION

Page 3: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Topics: Transformer Differential Boundary Test

(Commissioning) Ground Differential Sensitivity Test

(Commissioning/Maintenance) Harmonic Restraint for Transformer Inrush

(Maintenance)

INTRODUCTION

Page 4: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Commissioning

Common Practice: Test all numerical relay settings – verify settings properly entered Easily facilitated using computer – automate test set & store results Hundreds of tests are possible – numerical relays have many settings

Page 5: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Commissioning

Final Goal Ensure the transformer is properly

protected for the particular application

Page 6: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

RG46

Typical Distribution Transformer

46: Negative-Sequence Overcurrent Element (sees ground faults through bank)

RG: Grounding Resistor (Industrial Load)

Page 7: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

RG46

E

+

ZT

ZT

ZT

3RG

46

I2

Sensitive setting for ground fault - overreach for phase-to-phase fault

Page 8: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Transformer Differential Characteristic Boundary Test

I2I1

87

Y Y

YY

I1 = Winding 1 per unit current (A, B or C-phase)

I2 = Winding 2 per unit current (A, B or C-phase)

3 elements per function (A, B & C-phase)

* Simulate Through Current

Page 9: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Differential Characteristic Operating Equations

Id = |I1 – I2|, Differential Current

Ir = |I1| + |I2|, Restraint Current2

Page 10: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Differential Characteristic

Id

Ir

MinimumPickup(per unit)

Percent (%)

Slope

XY

% = Y

X*100%

Page 11: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Differential Characteristic

Id

Ir

MinimumPickup

Percent

Slope

Trip Region

Block Region

Page 12: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Matrix

Id

Ir[ ] =

1 -1½ ½ [ ] * I1

I2[ ]

Page 13: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Inverted Matrix

I1

I2[ ] =

½ 1-½ 1 [ ] * Id

Ir[ ]

Page 14: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Differential Characteristic Test Current Equations

I1 = 0.5*Id + Ir, Winding 1 Test Current (per unit)

I2 = -0.5*Id + Ir, Winding 2 Test Current (per unit)

Page 15: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Differential Characteristic Test Points

Id

Ir

MinimumPickup

Percent

Slope

Minimum Pickup = 0.2 per unit

Slope = 28.6%

1 23

4

Page 16: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Differential Characteristic Test Points (Per Unit)

Id Ir I1 I2

1 0.2 0.3 0.4 0.2

0.2 0.7 0.8 0.6

0.4 1.4 1.6 1.2

0.6 2.0 2.3 1.7

2

3

4

TABLE 1

Page 17: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Delta-Wye Differential Characteristic

I2I1

87

Y

YY

I1 = Winding 1 per unit current (A, B or C-phase)

I2 = Winding 2 per unit current (A, B or C-phase)

3 elements per relay (A, B & C-phase)

* Simulate Through Current

DAB

Page 18: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Delta-Wye Differential Characteristic (Relay Internally Compensates Test Currents)

IA1relay = IA1/TAP1

DAB WINDING

IB1relay = IB1/TAP1

IC1relay = IB1/TAP1

IA2relay = (IA2- IB2)/(TAP2*SQRT(3))

WYE WINDING

IB2relay = (IB2 - IC2)/(TAP2*SQRT(3))

IC2relay = (IC2 - IA2)/(TAP2*SQRT(3))

TAP# = MVA#

kV#LL*CTR#*SQRT(3)

Page 19: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Delta-Wye Differential Characteristic (Single-PhaseSingle-Phase Test for A-Phase Element)

Id Ir I1 I2

0.2 0.7 0.8 0.62

From TABLE 1:

IA1 = I1*TAP1

IA2 = I2*TAP2*SQRT(3)

IA1test = 0.8*TAP1

IA2test = 0.6*TAP2*SQRT(3)

Page 20: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Ground Differential Element Sensitivity Test

Directionality

(I0 vs. IG)

Ground Fault Location along Windings

Page 21: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Ground Differential Element Directional ElementDirectional Element

+90o

-90o

IGI0

Disabled if |3I0| less than 140 mA(Improves Security for CT saturation during external faults)

Internal External

Page 22: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Ground Differential Element PickupPickup

Operate When:

|3I0 – IG| > Pickup

Page 23: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Ground Differential Element Sensitivity Test

Power System Parameters:•Source Impedance (Varies)•XT = 10%•RF (Varies)•Ground Fault Location (5% from Transformer Neutral)

Page 24: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

87GD Sensitivity

0

20

40

60

80

100

120

140

160

180

0 20 40 60 80 100 120

Source Impedance

Fau

lt R

esis

tan

ce

IG = 200 mA IG = 500 mA IG = 1 Amp

Ground Differential Element RRFF Coverage vs. Source Strength Coverage vs. Source Strength

Page 25: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Ground Differential Element Pickup Setting

Cold Load Pickup

Reclosing into Single-Phase Load

Pickup > UnbalanceDirectional Element Disabled if 3I0 Low

IG

R

Page 26: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

IG2 = 0.3 Amps @ 177o

3I0(2) = 0.136 Amps @ 58o (Threshold = 0.14 AmpsThreshold = 0.14 Amps)

|CTCF*3I0(2) – IG2| = 0.75 Amps

Original Pickup = 0.3 Amps

Page 27: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

IG2

CTCF*3I0(2)

INTERNAL EXTERNAL

IOP

New Pickup = 1.0 AmpsNew Pickup = 1.0 Amps

Directional ElementDirectional Element

Page 28: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush COMTRADE PLAYBACKCOMTRADE PLAYBACK

Waveform Sources:•Events from Numerical Relays•Events from Digital Fault Recorders•Simulate using Transient Software

Page 29: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush Traditional ApproachTraditional Approach

•2nd Harmonic Restraint•Cross Phase Blocking

Page 30: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush Auto-Transformer ModelAuto-Transformer Model

wye wye

delta

13.2 kV

345 kV 230 kV

W1 W2

W3

600 MVA Auto-Transformer (Tertiary Winding DAC)

Page 31: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Auto-transformer Characteristics ZHM = 0.01073 per unit ZHL = 0.04777 per unit ZML = 0.03123 per unit

2MLHLHM ZZZ

= 0.0140 per unit

2HLMLHM ZZZ

= -0.0029 per unit

2HMMLHL ZZZ

CTRW1 = 1200:5 (wye connected)

CTRW2 = 2000:5 (wye connected)

Even Harmonic Restraint during Inrush

Auto-Transformer ModelAuto-Transformer Model

ZH =

ZM =

ZL = = 0.0340 per unit

Page 32: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush Auto-Transformer ModelAuto-Transformer Model

TAP1 =600 MVA

345 kV * 240 * SQRT(3)

TAP2 =600 MVA

230 kV * 400 * SQRT(3)

= 4.18

= 3.77

Minimum Pickup* = 0.5 per unit

Slope = 25%

*Original Pickup = 0.45 per unitOriginal Pickup = 0.45 per unit

Page 33: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush Energize Bank with Heavy A-Phase Residual FluxEnergize Bank with Heavy A-Phase Residual Flux

Total Phase Current

Page 34: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush Energize Bank with Heavy A-Phase Residual FluxEnergize Bank with Heavy A-Phase Residual Flux

2nd Harmonic Phase Current

Page 35: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic RestraintEven Harmonic Restraint

Ieven = (I22 + I4

2)1/2

Page 36: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush Energize Bank with Heavy A-Phase Residual FluxEnergize Bank with Heavy A-Phase Residual Flux

4th Harmonic Phase Current

Page 37: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Even Harmonic Restraint during Inrush A-Phase Current (Winding 2)A-Phase Current (Winding 2)

Page 38: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

CONCLUSIONSCONCLUSIONS

Page 39: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

Transformer Differential Boundary Test(Commissioning)

Ground Differential Sensitivity Test(Commissioning/Maintenance)

Harmonic Restraint for Transformer Inrush(Maintenance)

CONCLUSIONSCONCLUSIONS

Page 40: B-6 Testing Numerical Transformer Differential Relays - IEEE

Testing Numerical Transformer Differential Relays

QUESTIONSQUESTIONS