B-11

26
NATIONAL OIL CORPORATION GENERAL ENGINEERING SPECIFICATION GES B.11 LABORATORIES Rev Date Description Checked Approved 0 1999 Issued for Implementation DL Compiled by Teknica (UK) Ltd

Transcript of B-11

Page 1: B-11

NATIONAL OIL CORPORATION

GENERAL ENGINEERING SPECIFICATION

GES B.11

LABORATORIES

Rev Date Description Checked Approved

0 1999 Issued for Implementation DL

Compiled by Teknica (UK) Ltd

Page 2: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 2 of 26 Rev 0 1999

INDEX SECTION TITLE PAGE 1.0 SCOPE OF SPECIFICATION 4 1.1 Introduction 4 1.2 Other NOC Specifications 4 2.0 DEFINITIONS 6 2.1 Technical 6 2.2 Contractual 6 3.0 DESIGN 6 3.1 Codes and Standards 6 3.2 Accommodation 7 3.3 Testing and Analysis Routines 9 4.0 CIVILS 10 4.1 Groundworks 10 4.2 Load Bearing Material 11 4.3 Roofing 11 4.4 Concrete Work 11 4.5 External Walling 11 4.6 Fire Resistance 12 4.7 Thermal Stability 12 4.8 Location and Ground Level 12 4.9 Other Constructional Considerations 12 5.0 COMPONENTS 13 5.1 Doors 13 5.2 Windows 14 5.3 Glazing 14 5.4 Access and Security 14 5.5 Joinery 14 5.6 Ironmongery 14 6.0 INTERNAL FINISHES 15 6.1 Walls 15 6.2 Floors 15 6.3 Ceilings 15

Page 3: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 3 of 26 Rev 0 1999

SECTION TITLE PAGE 7.0 SERVICES 16 7.1 Heating Ventilation and Air-Conditioning 16 7.2 Drainage/Sanitary and Waste Disposal 17 7.3 Water Services 17 7.4 Laboratory Waste 17 7.5 Sample and Solvent Waste 18 7.6 Piped Gas Systems and Wash Solvents 18 7.7 Emergency Services, Fire Alarms, Smoke and Gas Detection 18 7.8 Electrical and Lighting 19 8.0 LABORATORY FITTINGS AND FURNITURE 19 8.1 General 19 8.2 Fume Cupboards 19 9.0 INSPECTION 20 9.1 Inspection Procedure 20 10.0 TESTING 20 10.1 Statutory Testing 20 10.2 Test Procedures 20 10.3 Test Certification 20 10.4 Performance Testing 21 11.0 DOCUMENTATION 21 11.1 Introduction 21 11.2 Design Proposals 21 11.3 Design Programmes 21 11.4 Schedules and Reports 21 11.5 Data and Calculations 22 11.6 Drawings and Specification 22 11.7 Final Records, Documents and Manuals 23 12.0 PRIOR TO SHIPMENT 23 12.1 Spares 23 12.2 Packing and Storage 23 12.3 Shipping 24 12.4 Warranty 24 Figure (1) 25 Figure (2) 26

Page 4: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 4 of 26 Rev 0 1999

1.0 SCOPE OF SPECIFICATION 1.1 Introduction 1.1.1 This specification sets out the minimum requirements and recommended practice for the architectural, civil

and structural design of free standing laboratories located in non-classified areas of oilfields and refineries. It is not a definitive, technical, contract specification, but it is intended to serve as a briefing document for

the Owner and Vendor/Contractor and to set the standards for building function, construction and ease of maintenance. Its scope is limited to functional, planning and construction criteria.

1.1.2 The intent of the document is: - To provide Owners and Vendor/Contractors with clear design guidelines for the building

envelope, components and finishes and to ensure that these are co-ordinated with functional needs of structural/civil engineering, mechanical (air-conditioning, water services and drainage) and electrical services.

- To standardise design, by providing comprehensive recommendations and requirements within a

single document. - To set benchmark standards for both building function and construction and to provide the

framework for cost-control to be implemented. - To give guidance which takes into account the climatic conditions and general methods of

construction prevailing in the region and which allows the use of construction technology requiring the minimum importation of overseas building materials and components.

1.1.3 This document is intended to serve as a design tool for Owners and Vendor/Contractors for the

administration of the building design process during pre-contract stages. It is not a definitive, project specification. Vendor/Contractors are in no way relieved from their responsibilities for the production of completed documentation and safe, functional design.

1.1.4 The Vendor/Contractor shall fully comply with the provisions laid down in the specification. Any

exception shall be authorised in writing by the Owner. 1.1.5 In the event of any conflict between this specification and any applicable codes and standards, the Vendor

shall inform the Owner in writing and receive written clarification before proceeding with the work. 1.1.6 This General Engineering Specification shall form part of the Purchase Order/Contract. 1.2 Other NOC Specifications In designing laboratories, the following additional NOC Specifications shall apply: 1.2.1 General GES A.01 - Plant Layout and Spacing GES A.04 - Noise Level Criteria and Noise Control of Mechanical Equipment GES A.06 - Site Data 1.2.2 Building GES B.12 - Heating, Ventilation and Air-conditioning

Page 5: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 5 of 26 Rev 0 1999

GES B.13 - Plumbing and Sanitary Specifications GES B.17 - Doors and Windows 1.2.3 Fire and Safety GES H.01 - Fire and Gas Alarm Systems GES H.03 - Portable Fire Extinguishers GES H.08 - CO2 and Halon Substitute Systems. GES H.09 - Emergency Shower and Eyewash Facilities 1.2.4 Electrical GES L.19 - Building Electrical Systems GES L.34 - Equipment in Contaminated Environments 1.2.5 Civils and Foundations GES Q.01 - Earthworks (inc. site preparation, pits and trenches) GES Q.03 - Foundations (inc. piling) GES Q.04 - Concrete Structures GES Q.07 - Rainwater, Oily Water and Sanitary Sewer Systems GES Q.14 - Design Loads of Structures 1.2.6 Structural Steelwork GES S.01 - Steelwork Structures 1.2.7 Telecommunications GES T.02 PABX Telephone Systems and Telephone Instruments GES T.10 Local Telephone Cabling Systems 1.2.8 Painting GES X.01 Surface Preparation and Painting Application GES X.02 Colour Coding of Equipment and Piping GES X.03 External Protective Coatings 2.0 DEFINITIONS For the purpose of this specification the following definitions shall apply: 2.1 Technical

Page 6: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 6 of 26 Rev 0 1999

2.1.1 Laboratory The term `laboratory' is a general term defining a building or room(s) within a building, from which

scientific and chemical research and testing is conducted and administered. 2.2 Contractual The commercial terms used in this specification are defined as follows: 2.2.1 Owner The oil or gas company, an associate or subsidiary, who is the end user of the equipment and facilities. 2.2.2 Vendor The company supplying the equipment and material. 2.2.3 Contractor The main contractor for a defined piece of work. 2.2.4 Sub-Contractor A company awarded a contract by a Vendor/Contractor to do part of the work awarded to the

Vendor/Contractor. 2.2.5 Inspection Authority The organisation representing the Owner or Vendor/Contractor that verifies that the equipment and

facilities have been designed, constructed, inspected and tested in accordance with the requirements of this specification and the Purchase Order/Contract.

2.2.6 Inspector A qualified individual representing the Owner, Vendor/Contractor or the assigned Inspection Authority,

who verifies that the equipment and facilities have been designed, constructed, inspected and tested in accordance with the requirements of this specification and the Purchase Order/Contract.

3.0 DESIGN 3.1 Codes and Standards This specification has been based on the requirements of the international standards and codes of practice

set out below. They are to be adhered to in any submitted design for laboratories. In the event of conflict between codes, standards and this specification, the requirements leading to the safer design shall be used as determined and approved by the Owner.

3.1.1 Electrical and Mechanical ASHRAE Guide and Data Book API RP 500A Classification of Areas for Electrical Installations in Petroleum Refineries NFPA 70 National Electrical Code IEE Regulations for Electrical Installations - 16th Edition IEC 79 Electrical Apparatus for Explosive Gas Atmospheres

Page 7: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 7 of 26 Rev 0 1999

3.1.2 Fire and Safety BS 5908 Code of Practice for Fire Precaution in Chemical and Allied Industries. IP Model Code of Practice Part 1 Electrical Safety Code Part 3 Refining Safety Code Part 15 Area Classification Code for Petroleum Installations Part 19 Fire Precautions at Petroleum Refineries and Bulk Storage Installations NFPA 45 Fire Protection for Laboratories Using Chemicals. Oil Association Bulletin No.63 (General Recommendations Spacing). 3.1.3 Building Construction U.B.C Uniform Building Code (USA) The Building Regulations (UK) BS 6375: Performance of Windows, Part 1 Classification of Weather Tightness. BS 5908: Code of Practice for Fire Precautions in Chemical Plant. BS 2750: Part 3: Measurement of Sound Insulation in Buildings and Building Elements. ASTM E 336: Methods of Measurement of Air-Borne Sound Insulation in Buildings. 3.2 Accommodation 3.2.1 Indicative Plans Layouts are contained in Figures 1 and 2 which show indicative arrangements for oilfield, refinery and/or

petrochemical laboratories. Accommodation and fit-out will vary in accordance with the Owner's specific requirements, but will consist of core laboratory working areas and stores, with support accommodation consisting of office space, toilets, cleaner's store and tea-room. Laboratory storage for acids, solvents, reference fuels and samples should be kept to the minimum required for operations. All flammable liquids must be labelled properly and stored in specially designated places.

3.2.2 Schedule of Accommodation The following areas are indicative only and will vary from site to site in accordance with the Owner's

specific requirements: (a) Oilfield Laboratory Laboratory working area - 32sq. metres Offices - 12sq. metres General/Equipment Store - 6sq. metres Tea-room - 6sq. metres Cleaner's Store and Toilet - 8sq. metres Corridor - 11sq. metres Gas Bottle Store - external Hazardous Materials/Waste Store - external

Page 8: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 8 of 26 Rev 0 1999

(b) Refinery Laboratory Laboratory - 84sq. metres Offices - 12sq. metres Laboratory Storage - 9sq. metres Cleaner's/Domestic Store - 8sq. metres Toilets - 12sq. metres Gas Bottle Store - external Waste Store - external HVAC - 60sq. metres Laboratory Workshop - 80sq. metres Maintenance Workshop - 8sq. metre (c) Petrochemical Laboratory Laboratory - 230sq. metres Offices - 50sq. metres Laboratory Storage - 50sq. metres Cleaner's/Domestic Storage - 8sq. metres Toilets - 25sq. metres Gas Bottle Store - external Waste Store - external HVAC - 100sq. metres Laboratory Workshop - 200sq. metres Maintenance Workshop - 30sq. metres 3.2.3 Sound Attenuation It is essential that noise should be kept to a minimum between the rooms of the building and that staff

should be undisturbed by normal external noise. Sound insulation and attenuation performance of external walls and windows therefore shall be no less than 31 Db. In particular, the following standards shall apply:

BS 2750: Part 3: Measurement of the Insulation of Buildings and of Building elements. ASTM E 336: Method of Measurement of Air-borne Sound Insulation in Buildings. 3.2.4 Housekeeping A particularly important aspect of laboratory design concerns the ease with which routine work can be

carried out, while minimising hazards: (a) Provision shall be made for the safe handling and storage of laboratory reagents and solvents

giving due regard to their toxic and reactive natures and quantities involved. These quantities shall be the minimum necessary for operational use and kept in separate, fire-resistant stores within the laboratory working area.

(b) Where refrigerants such as dry ice or liquid nitrogen are used in the laboratory, care is needed to

avoid cold burns, asphyxiation and related hazards. (c) Prompt and correct disposal of waste materials helps to reduce fire and environmental hazards and

the necessary exposure of personnel to disagreeable odours and toxic vapours. (d) Care shall be taken in the location and use of electrical apparatus not designed for hazardous

atmospheres. In particular, domestic refrigerators shall not be used for the storage of solvents and flammable liquids.

Page 9: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 9 of 26 Rev 0 1999

3.3 Testing and Analysis Routines The design of laboratories shall be based on well defined test requirements for the routine standard tests

carried out in oil fields, refineries and petrochemical plants. The exact lab space requirements shall be developed only after all the required instruments to carry out

these tests have been specified. The eventual need for additional space for any future requirements shall be examined at the preliminary

stage. While laboratory activities for oil fields require simple tests using conventional benching, storage cupboards and sinks, the test requirements for Refinery and Petrochemical labs are very complex requiring a wide range of analytical and physical testing processes and procedures, thus the lab space is bigger especially for the Petrochemical Labs where the need also for a plastics workshop for extrusion and other machines requires a lot of space. Laboratory designers, should take into consideration the fact that the performed tests involve the use of volatile, corrosive, toxic and flammable substances, thus provisions shall be made in the design to minimise any potential hazard to personnel and the environment.

Whenever possible very hazardous tests shall be performed in segregated areas from the remaining

Laboratory space. The required tests for the following types of laboratories may include, but not be confined to the following as listed:-

3.3.1 Oilfields . Basic, Sediment and Water (BS&W) (Bottom Sediment and Water) . Specific Gravity . Viscosity . Water Analysis for Mg, Na, Cl, S04, S02 . Mass Chromatography . Flashpoint . RVP . Pour Point 3.3.2 Refineries . Tetraethyl Lead Test (TEL) . Basic, Sediment and Water . Sulphur . Hydrogen Sulphide . Copper Strip . pH . Viscosity . RVP (vapour pressure) . Density . Distillation . Water Content . Pour Point . Cloud Point . Wax Point . Mass Chromatography . Titration . Acidity . Water Treatment Tests 3.3.3 Petrochemicals . Composition Analysis by Gas Chromatography . Composition Analysis by Mass Spectography

Page 10: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 10 of 26 Rev 0 1999

. Distillation . Density . Extrusion . Film Forming Tests will vary from site to site in accordance with the Owner's specific requirements. 4.0 CIVILS 4.1 Groundworks Refer to GES A.06 for requirements regarding basic background information on site conditions. 4.1.1 Site Investigation Reports The extent and type of groundworks and foundation design will vary from site to site and will be dependent

amongst other factors, on the overall structural design of the building. In all cases, a site investigation report shall be prepared for the Owner's approval before detailed design development is embarked upon. A site investigation should demonstrate the suitability of the proposed site for the construction of civil engineering and building works. It shall examine all parameters which may influence the design of the building and the security of neighbouring land and property. All site investigation reports shall include an appraisal of the following:

(a) Site access (b) Levels (c) Drainage and Sewage (d) Ground bearing capacity (e) The presence of buried services (f) Adjacent buildings (g) Overhead power lines and other features Foundation design shall conform to the guidelines set out in GES Q.03. Particular care shall be taken to

ascertain the degree of sulphates and other aggressive salts in the ground. As a general rule, allowance shall be made for sulphate resisting cement to be used in all below ground construction.

4.1.2 General Ground floor levels shall be raised to minimum 450mm above the general external ground to reduce the

entry into the building of wind-borne sand and dust and to protect the building during heavy storms which are liable to cause local or flash flooding. Local surface conditions shall be investigated to ensure an adequate run-off of water during the brief but intense periods of rainfall.

4.2 Load Bearing Material Structural load bearing materials shall be of reinforced concrete, load bearing concrete block (where

available) or steel, fully protected from fire. No material shall be accepted, which supports combustion. 4.3 Roofing The majority of laboratory roofs will be flat construction. Water proofing shall consist of bitumen-based

felts, asphalt or similar material. Proposals for flat roof specifications shall demonstrate that requirements are clearly set out regarding watertightness, drainage, thermal and sound installation, fire precautions, maintenance and repair. In all cases, proposals for flat roof waterproofing shall also include the following:

Page 11: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 11 of 26 Rev 0 1999

- Due to the prevailing intense solar radiation in the region, flat roofs shall be of the `inverted' type whereby loose-laid rigid insulation boards are placed over the waterproof membrane. Boards shall be ballasted with gravel and or paving flags. This will ensure that membranes are protected from deterioration arising from exposure to ultraviolet light and from roof traffic.

- All roofs shall be insulated with 50mm thickness of extruded, expanded polystyrene boards or

similar Owner approved material, polystyrene bead board shall not be acceptable. - Waterproofing shall be fully protected, at upstands, from sunlight by means of reflection gravel

and flashings. - Rainfall in the region is infrequent but often violent and designs shall allow for 3" (75mm) per

hour precipitation. Parapet walls shall have sufficient openings to ensure that roofs do not flood as a result of blockage to piped outlets. A slope of 1:80 towards the rainwater outlets shall be provided.

- Design proposals shall always include details of roof entries of piped services, demonstrating that

adequate waterproofing is allowed for. - Roof access doors shall always have thresholds a minimum of 150mm above the finished level,

i.e. with allowance for thickness of screeds, insulation and ballast. 4.4 Concrete Work Attention is drawn to the importance of adhering to good concrete practice in the prevailing climatic

conditions in the region. Vendor/Contractors shall conform to the recommendations and standards set out in GES Q.03 and GES Q.04, particularly with reference to hot weather conditions.

4.5 External Walling The most readily available and economic material for external walling will be rendered concrete

blockwork, although other materials may be acceptable, subject to Owner approval. Designs incorporating blockwork shall conform to the recommendations set out in GES Q.05. Laboratories designed with un-insulated single-skin blockwork walls will not be accepted. Where budgets allow, external block walling shall be insulated, or if cavity construction, incorporating insulation. Whatever the construction of external walling, designs shall incorporate external shading such as roof overhangs or other features to reduce the degree of direct exposure to sunlight.

4.6 Fire Resistance The design, materials and methods of construction of laboratories shall conform to accepted good practice.

The primary special characteristic required is for construction materials, components and finishes to be non-combustible throughout which shall produce little or no toxic fumes or heat when exposed to heat.

4.7 Thermal Stability Oil field laboratories require stable conditions for general testing. In addition, Refinery and Petrochemical

laboratories contain sensitive, expensive and sophisticated diagnostic equipment such as chromatographs and spectrograms, the accuracy of which require constant and precise conditions. These can only be achieved within building envelopes that are both thermally efficient and stable and free from vibrations. Generally, this may be achieved if permanent laboratories are housed in buildings of high thermal capacity. Construction of insulated load-bearing masonry or reinforced concrete frames, floors and roofs with concrete masonry walls, will satisfy both this criterion and the need for fire resistance. External walls shall be of insulated construction. Un-insulated external walls shall be avoided and designs should incorporate features which reduce the degree of exposure of external walls to direct sunlight, such as roof overhangs or shaded verandas.

Page 12: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 12 of 26 Rev 0 1999

4.8 Location and Ground Level Laboratories shall, wherever possible, be located in non-hazardous areas, it is impracticable to ensure the

elimination of sources of ignition. They shall also preferably be free-standing buildings and shall not be contained within control buildings. For any laboratory building adjacent to hazardous areas, consideration shall be given to the requirement for blast resistance or protection. Generally the building shall be located far enough away from processing operations to allow for adequate dispersal of potentially hazardous vapour. Siting criteria should be based on the recommendations set out in IP Model Code of Practice: Part 15, or the Oil Insurance Association Bulletin No 631 (General Recommendations Spacing). Vendor/Contractors shall conform to the recommendations and standards set out in GES A.01.

4.9 Other Constructional Considerations The design of laboratories shall incorporate features which shall minimise the entry of Cockroaches, Flies

and Rodents in to the Lab spaces. The following precautions when taken during construction shall alleviate the pest problem. 4.9.1 Cockroaches, Black Beetles and Crickets Passage from room to room or floor to floor along pipe-runs, ducts and chases shall be prevented by

suitable sealing, intermediate lengths of ducts and chases shall be easily accessible. 4.9.2 Flies Well-fitted screens shall be provided for windows and ventilators. 4.9.3 Rodents (a) Service pipes and installation pipes - Wherever pipes and cables pass through a wall, they shall be

carried in sleeves and the space between the pipe and sleeve shall be effectively sealed. (b) Ducts and Chases - Ducts, chases and ventilating shafts shall be effectively sealed against the

entry of rats or mice. Where pipes are in ducts or chases passing through a wall or floor, they shall be embedded in rodent-proof material. Metal turnings and broken glass are useful for this purpose.

(c) Waste receivers - Waste receivers shall be of back-inlet type, any open channel shall be protected

by a grid to prevent the entry of rodents into the channel waste pipe. (d) Rain water down pipes - Down-pipes shall be protected against the entry of rodents and where

possible shall be connected to a back-inlet or similar gullies. The use of wire netting, or other obstruction to the outlets is not recommended.

(e) Hollow Walls - Hollow walls shall be sealed at the roof-plate level. There should be no access to

the cavity where service pipes, ducts, cables pass through or into the walls. (f) Footings - The base of all footings of outside walls and party walls shall be not less than 60cm

below the finished ground level to prevent access by burrowing, except where site concrete affords sufficient protection.

(g) Partitions, etc. - Joints between partitions and the main structure shall be effectively sealed. In the

construction within a building of a permanent structure or semi-permanent structure, precautions shall be taken to avoid harbourage in hollow partitions, or between the floor of the main building and the floor of the subsidiary structure or between their ceilings.

(h) Ventilating grids, screens, baffles and balloon pipe guards - Grids and other barriers shall restrict

Page 13: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 13 of 26 Rev 0 1999

passage to a width of _" (10mm). Soil pipes and ventilating pipes shall always be provided with guard cages. Balloon pipe guards

should be resistant to corrosion. 5.0 COMPONENTS 5.1 Doors Vendor/Contractors shall conform to the recommendations and standards set out in GES B.17. 5.1.1 External Doors - External doors may be of timber, with glazed viewing panels, or alternative glazed anodised

aluminium frame. Doors shall be set into steel frames anchored into the structure. - External doors shall open outwards to counteract the effect of seasonal high wind. - External doors shall be fitted with effective, draught-excluding brushes and seals to ensure

weather-tightness and exclude wind borne sand, dust and the ingress of toxic gases. - Doors shall be heavy duty construction and shall be fitted with kicking plates to reduce damage

from trolleys etc.

Page 14: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 14 of 26 Rev 0 1999

5.1.2 Internal Doors Internal doors generally shall be solid, 44mm thick, incorporating plaster board and providing at least 1

hour fire-resistance classification. Door leaves shall contain vision panels of wired or safety glass and be fitted at all edges with intumescent seals to resist the passage of smoke. They shall be equipped with kicking plates and overhead or similar closers. Storage rooms containing flammable materials shall be equipped with steel-faced doors or doors classified as giving 2 hours fire resistance.

5.2 Windows - Windows may be timber or anodised aluminium framed. - Windows shall be fitted with effective draught-excluding brushes and seals to ensure weather-

tightness and to exclude wind borne sand and dust. - Windows shall conform to the requirements of BS 6375. Vendor/Contractors shall conform with

the recommendations and standards set out in GES B.17. - Windows shall be kept to a functional minimum in non-hazardous areas. Where openable,

windows shall preferable be of sliding sashes and shall be fitted with integral fly screens. - For laboratories close to hazardous areas, windows shall be avoided on walls facing processing

plant. 5.3 Glazing Glazing shall generally be kept to a minimum to reduce solar heat gain, confined to those walls facing away

from direct sunlight or protected by shading. Windows are to have venetian blinds and curtains. Openable windows shall have insect screens.

5.4 Access and Security Various levels of security and selective access to laboratories may be required. Owner requirements shall

be confirmed at the initial design stages. 5.5 Joinery All timber, whether used as a finishing material or for general construction, shall be properly treated

against insect and fungal attack. 5.6 Ironmongery Requirements for ironmongery will vary, but Vendor/Contractors and Designers should seek Client

guidance for master key and suiting, together with security and restricted or selective access requirements. Any design submission should include schedules which clearly set out proposed standards of ironmongery in terms of:

- Quality - Finish - Means of Escape - Safety including fire resistance - Security 6.0 INTERNAL FINISHES

Page 15: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 15 of 26 Rev 0 1999

6.1 Walls All walls shall be washable. For most applications, a washable acrylic polymer emulsion will be

acceptable. All toilet areas shall be tiled to door height with ceramic tiles. All washbasins and sinks shall be provided with tiled splashbacks. Generally, external walls of masonry construction should receive a reflective masonry paint finish or sand/cement rendering.

6.2 Floors The primary factors affecting the choice of floor finish in the working laboratory areas are durability, fire

behaviour, slip resistance and resistance to oils, solvents and acids. In addition, floor finishes shall be resistant to the creation of static electricity. Floor finishes shall therefore be restricted to the following:

6.2.1 Laboratories - Non-slip sheet PVC with welded joints, resilient backing and continuous skirtings. - Non-slip ceramic quarry tiles with covered skirtings. - Non-slip epoxy resin finishes. 6.2.2 Storage Areas for Solvents, Acids, Reference Fuels and Samples - Non-slip ceramic quarry tiles with covered skirtings. - Non-slip epoxy resins, especially selected for resistance to the above compounds. Specific mandatory safety details regarding floors in these areas include: - where laboratories are equipped with acid and electric battery stores, these shall be provided with

a vented and trapped floor drain to serve eyewash facilities and the washdown of electrolyte spills. - The spreading of electrolyte spills to other areas must be prevented by the use of bunded upstands

and changes of levels. 6.2.3 Offices and Corridors - Sheet PVC with resilient backing and skirting. 6.2.4 Tearooms, Toilets and Storage Areas - Quarry tiles. 6.3 Ceilings Proprietary suspended ceiling systems may be used in corridors, laboratory and office areas, provided that

dividing walls are taken to the structural slab level and fully sealed and that the compartmentalisation of the building is not compromised regarding fire resistance and the spread of smoke and flame. In general, textured paint finishes applied directly to the soffits of ceiling slabs will be acceptable where there is no central, ducted air-conditioning system. Storage areas may be left as fair-faced concrete.

7.0 SERVICES 7.1 Heating, Ventilation and Air-conditioning

Page 16: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 16 of 26 Rev 0 1999

Proposals shall be based on the sometimes extreme climatic conditions prevailing in the region, with seasonal high winds and high temperatures.

Maximum ambient temperature 50°C Minimum ambient temperature 0°C Maximum relative humidity generally less than 30%, could reach 95% in coastal regions Maximum wind speed 145Kph 7.1.1 General Vendor/Contractors shall conform with the recommendations and standards set out in GES B.12. Laboratory working areas shall be separately air-conditioned or ventilated from associated office and

support accommodation. Solvent, retention sample and reference fuel storage shall be kept in separate, permanently ventilated areas. Particular attention shall be paid to fume cupboards to prevent backflow. All exhaust fans must be of appropriate non-sparking materials with motors outside the airstream and should discharge vertically upwards at high velocity. If they cannot be avoided, underfloor ducts shall be mechanically ventilated. Where a bottle-washing area is provided, an extract system shall be installed to prevent the accumulation of vapours.

Lead alkyl blending cabinets shall be vented direct to the atmosphere and well away from fresh air intakes.

Separate vents for depressurising gas and LPG sample containers shall be taken to a high point outside the building.

7.1.2 Air-conditioning Air-conditioning will be necessary in all working areas for the comfort of occupants and protection of

sensitive electronic equipment, e.g. chromatographs. Allowance shall also be made for heating during winter months. In addition, some laboratories will also require positive air pressure systems to prevent the entry of wind borne sand and dust and to achieve a non-hazardous classification. In all instances, electrical equipment associated with the air-conditioning systems serving working laboratory areas, shall be intrinsically safe.

Air-conditioning shall be provided in all areas except toilets and cleaner's store, which must be provided

with mechanical air extract fans. Allowance shall be made for winter months. For general, functional purposes, split units will be appropriate and are preferred to through the wall package units. Fan-coil units shall be wall-mounted to leave floor areas clear. Compressors shall be roof-mounted to reduce damage from wind borne sand and dust.

The following details shall be presented at design-development stage: (a) Roof entry arrangements for power conduit and refrigerant, indicating weather-tight details. (b) Condensate drainage details. (c) Refrigerant line, condensate and power conduit route details, indicating ducting arrangements and

tidy installation. (d) Indication of access arrangements for maintenance, filter changes etc. 7.2 Drainage/Sanitary and Waste Disposal 7.2.1 General Suitable drains shall be provided where required in accordance with GES B.13 and GES Q.07. Normal foul waste from WCs, toilet washbasins, tea-rooms and drinking water fountains shall be collected

Page 17: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 17 of 26 Rev 0 1999

separately from any laboratory waste and directed to a sewage system or septic tank. 7.2.2 Sanitary Installation In designing sanitary installations, the following shall be noted: (a) Plumbing pipework shall wherever possible, be concealed and contained within an accessible,

purpose-built service duct. (b) WC cubicles shall be equipped with hygiene sprays. WC pans shall preferably be wall mounted to

allow for all round cleaning. Cisterns shall preferably be contained within an accessible service duct. Overflow pipes shall discharge to a position where such drainage is visible.

(c) Washbasins shall be firmly fixed on brackets or legs and shall not be fixed to hollow clay block walls.

(d) Sanitary sewers shall form a drainage system separated from those into which oil and other waste shall be discharged.

(e) A floor drain shall be provided in each toilet/washroom and shall discharge into the sanitary sewer systems.

7.3 Water Services (a) Water services shall be designed to allow for ease of maintenance and wherever practicable, water

pipework shall be surface-mounted preferably within accessible service ducts. (b) For remote sites, allowance shall be made for storage of three days water supply. (c) For drinking water, a chilled drinking water fountain shall be provided. (d) Potable and drinkable water lines shall be sterilised before being placed in service. 7.4 Laboratory Waste Chemical laboratories and analyser rooms must be provided with trapped and vented, acid-resistant sinks

and funnels for collection of acid waste. In addition, acid-resistant floor gullies are required. All acid and chemical wastes shall be piped into a neutralisation tank. The tank shall be made of, or coated

with, acid resistant material. The tank shall be buried preferably outside the lab and shall have a sealed inspection cover at ground level.

The tank shall be sized for the expected acid flow and chemical waste for one week normal laboratory

operation. The tank shall have the following accessories: - Vent Pipe - Overflow (into the waste water system) - Inspection Cover at Ground Level - Injection Port (for neutralising solution) - pH Meter (Auto) - Depth Gauge (Auto) - Low Water Indicator Light - High Water Indicator Light - High Water Alarm - Permanent Chart with the required amounts of the neutralisation solution for different pH and

different water levels - Discharging Valve (normally closed) piped into the waste water system All neutralisation tank instrumentation including the injection port shall be sited within the Laboratory and

shall be free from obstruction for ease of use.

Page 18: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 18 of 26 Rev 0 1999

Neutralisation chemicals for neutralisation of acid and/or alkaline water are to be stored in a cabinet conveniently located to the neutralisation tank.

Following chemical treatment, the contents of the neutralisation tank will be discharged into the waste

water system. 7.5 Sample and Solvent Waste Waste samples and water from bottle-washing areas will normally be disposed of via a standard, three-

chambered, vented, petrol interceptor, to the main oily water drain for recirculation through the processing system.

Any other hazardous waste shall be safely disposed of to eliminate the risk of pollution and fire hazard.

This may be arranged by safe temporary storage from where it may be collected for disposal elsewhere. Such stores shall be vented and bunded.

7.6 Piped Gas Systems and Wash Solvents Laboratories will usually require a supply of LPG gas distributed to the workstations by fixed piping

systems. Where bottled gas is used, cylinders shall be located externally in a permanently ventilated store. Piping must be earthed and installed to material and construction specifications that ensure a high standard of integrity and freedom from leakage.

Where other piped laboratory gases may be required, e.g. CO2, Helium, Oxygen, Nitrogen, compressed air,

etc., pipework and taps must be clearly colour coded. Fittings and couplings for each individual gas must be incompatible in order to avoid accidental connection.

Solvents used for cleaning bottles and apparatus should be stored outside the laboratory in a ventilated

store. 7.7 Emergency Services, Fire Alarms, Smoke and Gas Detection All laboratory buildings shall be equipped with fire alarm, smoke and gas detection systems as set out in

GES H.01. These shall include: - manual break-glass alarm points positioned along escape routes; - alarm signal activation relayed to a central alarm point, where fire-fighting services can be alerted; - alarm systems to be fully addressable, i.e. indicate the alarm source on a panel in the central

alarm/control point; - all rooms, including storage areas and ceiling voids to be fitted with a combination of ionisation

and optical-type smoke detectors; - consideration to be given to the need for toxic gas detectors; - fixed, inert gas extinguishing systems to be considered for unmanned storage areas; - gas detection systems to be installed at points such as fresh air intakes to detect the presence of

toxic, explosive or flammable gases; - alarm and detection systems to activate the automatic cut-out of air-conditioning system. 7.8 Electrical and Lighting Vendor/Contractors shall conform to the recommendations and standards set out in GES L.19. The following notes shall apply: (a) Apparatus and cabling associated with the generation, distribution and use of electricity shall be

designed, constructed, installed, operated and maintained in accordance with the recommendations of the IP Electrical Safety Code and the sixteenth edition of the IEE Regulations.

Page 19: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 19 of 26 Rev 0 1999

(b) The area classification and electrical components will determine the minimum enclosure, conduit and sealing requirements.

(c) Ducts, conduits or entry plates shall be sealed in accordance with applicable electrical codes to

prevent the entry of hazardous vapours. (d) AC power supply to panel is usually 120 Volt, 50/60 Hertz, earthed, 3-wire, single-phased or as

detailed by the Owner. (e) Emergency lighting shall be installed along all escape routes and at emergency exits. (f) Light fittings in laboratory working areas, storerooms and gas stores shall be of suitable design for

the hazardous conditions anticipated. 8.0 LABORATORY FITTINGS AND FURNITURE 8.1 General Fittings and furniture should be selected to provide a safe and practical environment in which to work.

Account shall be taken of ergonomics, working practice, chemical resistance and cleanliness. Most laboratory work for oilfields and refineries consists of standardised tests, which can be served by pedestal units with integral storage drawers, cupboards and sinks. Allowance should be made for the limited inclusion of fire-resistant storage units for solvent and acids. Sink units and work tops must be resistant to acids, solvents and oil products. All plumbing and other services should be fully accessible for maintenance purpose.

8.2 Fume Cupboards Design and installation of fume cupboards shall be in accordance with the recommendations and

requirements of NFPA 45. The primary requirements are: - air exhausted from fume cupboards shall be discharged above the roof at a location, height and

velocity sufficient to prevent re-entry of hazardous chemicals; - ducts serving fume cupboards shall be constructed from non-combustible materials; - when flammable vapours or gases or combustible dusts are passed through the fans, the rotating

element shall be non-ferrous or of spark-resistant construction; - motors and their controls shall be located outside the location where flammable or combustible

vapours or combustible dusts are generated or conveyed; - fans shall be labelled with an arrow or other means to indicate proper direction of rotation and

with the location of the fume cupboard and exhaust system served; - fume cupboards shall be provided with a means of containing minor spills; - electrical services and their controls shall be provided external to the fume cupboard and be

backed up by an emergency disconnect system. 9.0 INSPECTION 9.1 Inspection Procedure The inspection requirements are covered by the Purchase Order/Contract. Additional requirements are

listed below: - The Vendor/Contractor shall allow the Inspector free access to all areas of manufacture,

fabrication, assembly and testing. - The Vendor/Contractor has the responsibility to provide adequate control and inspection of

Page 20: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 20 of 26 Rev 0 1999

equipment and materials. Any inspection by the Owner or his Inspector shall not relieve the Vendor/Contractor of these responsibilities or those under the Purchase Order/Contract.

During construction and installation, inspection and tests will be required for all aspects of laboratories and

their structures together with all the building services. Vendor/Contractors shall set out detailed schedules for this in design proposals and include adequate time for testing and inspection within their contract programmes and documentation.

10.0 TESTING 10.1 Statutory Testing Specification and related documentation shall state the type of tests to be performed, acceptance criteria, the

sources and types of testing equipment, the requirements for test reports and the qualified personnel to perform the tests.

Comprehensive and exhaustive testing shall be carried out of all components, systems and sub-systems

within the building, in the presence of the Owner's Inspector. Vendor/Contractors shall make allowance for this in their construction programmes.

10.2 Test Procedures The Vendor/Contractor shall submit all the necessary test procedures in writing to the Owner for approval

prior to the start of the testing programme. 10.3 Test Certification Test certificates shall be issued by the specialised Inspection Authorities when all test procedures are

successfully complied with. Test Certificates shall be issued for the following: - Fire Regulation - Alarms and Sound Systems - Air-Conditioning and Ventilation Systems - Electrical Distribution - Water and Drainage Services - Health and Safety certificates for the working environment. 10.4 Performance Testing As required by the Purchase Order/Contract the Vendor/Contractor shall carry out a performance test on the

plant and equipment associated with the Laboratory. 11.0 DOCUMENTATION 11.1 Introduction 11.1.1 This section covers the documentation required for the design, material selection, construction, inspection

and testing for the Laboratories provided against this specification. 11.1.2 The detailed list of documents that are required shall be included with the Purchase Order/Contract. 11.1.3 The documents as listed may be considered as a minimum, all details to confirm compliance with the

relevant specifications and to allow a full and detailed appraisal to be made of the Vendor/Contractor's

Page 21: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 21 of 26 Rev 0 1999

proposals and interpretations of the ordered equipment shall be submitted in good time. 11.1.4 Any production or procurement undertaken prior to the relevant documentation being submitted and

reviewed is at the Vendor/Contractor's risk. 11.1.5 The Purchase Order/Contract number and project name shall be quoted on all documents. 11.2 Design Proposals Proposals shall be submitted for Owner approval at each design stage and shall contain the following: (a) Site criteria as set out in section 4.0 above. (b) A clear indication of all proposed building components, services and finishes. (c) Design Programme (d) Estimated Construction Programme (e) Budget outline (f) Cashflow forecast 11.3 Design Programmes Design programmes shall give a clear indication of deadlines for all criteria decision requirements and

Owner approvals. Design submittals shall be staged to allow for progressive design development from outline proposals through to comprehensive contract documentation. Progress from each stage will be subject to Owner approval.

11.4 Schedules and Reports 11.4.1 The Vendor/Contractor shall submit with his tender a Quality Control Plan for the entire Purchase

Order/Contract when received. 11.4.2 The Vendor/Contractor shall include with his tender documentation proposed sub-vendors, programmed

schedule for all documents based on a review cycle of two (2) weeks and outline programme for procurement and production activities.

11.4.3 The Vendor/Contractor shall incorporate any revisions agreed with the Owner during the Purchasing Cycle

and submit revised Vendor/Contractor documentation for approval with their acknowledgement of Purchase Order/Contract.

11.4.4 Monthly reports shall be submitted by the Vendor/Contractor regarding design, procurement, construction,

installation and documentation activities the format of which shall be agreed with the Owner. 11.5 Data and Calculations 11.5.1 The Vendor/Contractor shall supply with his tender completed Data Sheets containing all the relevant

information necessary for appraisal of the design by the Owner. Also included shall be any additional drawings, specifications, etc and a list of any proposed sub-contractors.

11.5.2 The documents shall be submitted for approval/review to the Owner and to the Inspection Authority within

periods agreed between the Owner and Vendor/Contractor. It shall be the responsibility of the Vendor/Contractor to ensure that the production schedule includes documentation submission periods, plus

Page 22: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 22 of 26 Rev 0 1999

a two (2) week approval review period by the Owner and/or the Inspection Authority. 11.5.3 The Vendor/Contractor shall be responsible for obtaining approvals from the Inspection Authority. 11.5.4 All calculations shall be carried out in clear and logical manner. where conditions involve the use of

formulae or methods not mentioned in the Design Codes, the source of these formulae or methods shall be clearly referenced.

11.5.5 Computer calculations will only be acceptable if all input is shown, together with calculated values of

intermediate terms, factors and options chosen as well as final calculated dimensions, stresses or other values. The computer programme shall be validated to the satisfaction of the Owner.

11.5.6 Calculations and drawings that are interdependent, i.e. foundation loading and equipment foot print, shall

be presented for appraisal together. 11.6 Drawings and Specification 11.6.1 The number, type or title of drawings and specifications will vary for each project. Drawings will consist

of construction plans, sections, elevations and details supplemented by structural, mechanical and electrical services drawings. Plot plans shall show access to and clearance around the building, including access for emergency vehicles. Essential minimum information on drawings shall include:

- Overhead and/or underfloor routings of signal, power and communications cables - Layouts of heating, ventilating and air-conditioning requirements - Lighting layouts - Fire protection systems and equipment - Door opening dimensions to ensure that they are sufficiently sized to allow access for installation

or removal of equipment - Trunking and cable terminations, layouts and positioning - Drainage and sewerage layouts - Hazardous area plans 11.6.2 The drawings listed with the Purchase Order/Contract shall be sent by the Vendor/Contractor to the Owner

and/or the Inspection Authority for review and approval. 11.6.3 Detail drawings which may be included on the general arrangement shall include thickness and dimensions

of all components, weld details, machining and surface finish requirements, gasket and nameplate details. 11.6.4 As-built drawings shall be listed in the index and copies of the drawings shall be included in the operating

and maintenance manual. In additional, reproducible prints shall be provided. Where drawings are CAD generated, 2 sets of copy disks shall be supplied.

11.7 Final Records, Documents and Manuals 11.7.1 The handover of O&M (Operating and Maintenance Manuals), as-built drawings, spare parts lists, etc., for

all aspects of the building, its components, services and finishes is a prerequisite of contract completion. 11.7.2 On completion all documents shall be "as-built", i.e. all drawings and documents shall be marked up to

show field changes by installers/modifiers and presented in Data Dossier and Operating and Maintenance Manuals.

11.7.3 The Data Dossier shall comprise mechanical catalogue which shall include full operating data at all the

envisaged operating loads. The mechanical catalogues shall include full data concerning specification, installation, commissioning, maintenance, operation and spare or service replaceable parts of all proprietary items of the building. Two sets of data books shall be supplied.

11.7.4 The operation philosophy shall have been developed jointly by the Vendor/Contractor and the Owner's

Page 23: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 23 of 26 Rev 0 1999

operating personnel and incorporated into the installation, maintenance and operating manuals so that there is continuity from project conception to the final building and its operation. Six sets of operating manuals shall be supplied.

12.0 PRIOR TO SHIPMENT 12.1 Spares The Vendor/Contractor shall submit with his proposal a priced list of recommended spares for start-up and

two years operation for review by the Owner. The Vendor/Contractor shall quote the price of each item in the spare parts list and shall undertake not to increase the price for a period of two years.

12.2 Packing and Storage This section describes the minimum requirement for the preservation and protection of materials and

equipment during sea and land transportation and storage prior to installation. 12.2.1 The probable storage period shall be specified in the order enquiry and shall extend from the time of

despatch to the time of unpacking at site. If the storage period is not stated, a minimum of 24 months shall be assumed. All packing to be suitable for sea freight.

12.2.2 The following preparations for shipment shall be a minimum requirement. - After the mechanical completion at the works, the materials and equipment shall be left in a clean

dry condition. - The Vendor/Contractor shall be responsible for loading and anchoring the items to prevent

damage during shipment. 12.3 Shipping All detailed shipping arrangements are to be covered by the Purchase Order/Contract. Equipment and material shall not leave the Vendor/Contractor's works for shipment until the release has

been approved by the Owner's Inspector. 12.4 Warranty The Vendor/Contractor shall warrant all materials and services supplied against any defect for a minimum

of 12 months after commissioning or 24 months from the date of delivering to site, whichever is the shorter period, or for the period stipulated in the Purchase Order/Contract.

Should any item be found defective, the Vendor/Contractor shall be responsible for all costs associated

with restoring the equipment to the standard specified by the Purchase Order/Contract.

Page 24: B-11

GENERAL ENGINEERING SPECIFICATION LABORATORIES

GES B.11 Page 24 of 26 Rev 0 1999

S:\NOC9077\ADMIN\SPECIFICATIONS\B-SERIES\B-11\GESB11RF

Page 25: B-11
Page 26: B-11