AVR.xls

download AVR.xls

of 2

Transcript of AVR.xls

  • 8/11/2019 AVR.xls

    1/2

    23.26 %

    40 MVA+12 % to -16 %

    110 kV

    123.20 kV

    92.40 kV

    12.5 kV

    1847.52 A

    22 TAPS

    10 TAP

    1.27 %

    2 STEPS

    2.55 %

    500 A

    12500V / 100V = 125

    300A / 1A = 300

    IC = V |Z|

    112.20 kV

    CORRESPONDING SECONDARY VOLTAGE: 12.75 kV

    250 V

    11.72

    2.73

    IC = 91.72 A

    = 90 A

    Current carrying capacity of OLTC as per manufacturer = 500 A

    Corresponding current on Secondary side = 4400 A

    Set over current Blocking at = 80% OF 4400A

    = 3520.00 A

    Relay current = 11.7333 A

    PRIMARY VOLTAGE ON LOWER TAP:

    RESULTANT VOLTAGE:

    BASE IMPEDANCE (IN OHMS):

    TRAFO IMPEDNACE (IN OHMS):

    RECOMMENDED SETTING

    NUMBER OF TAPS:

    NOMINAL TAP IS NO.:

    LOWER THAN OTHER PARALLELED TRANSFORMER(S).

    STEP VOLTAGE:

    VOLTAGE REGULATION AFTER:

    REGULATION SETTING:

    TRANSFORMER REGULATION:

    PRIMARY SIDE RATED VOLTAGE (NOMINAL TAP):

    PRIMARY SIDE RATED VOLTAGE (MAXIMUM TAP):

    OVERCURRENT BLOCKING

    RATED SECONDARY SIDE CURRENT:

    CALCULATION OF CIRCULATING CURRENT

    FOR CALCULATION PURPOSES, ASSUME TRANSFORMER IS TWO TAPS

    PRIMARY SIDE RATED VOLTAGE (MINIMUM TAP):

    SECONDARY SIDE RATED VOLTAGE (AT NOMINAL PRIMARY TAP):

    OLTC RATED CURRENT:

    CT & VT DATA

    VT RATIO FACTOR:

    CT RATIO FACTOR:

    AVR SETTING CALCULATION

    BASIC TRANSFORMER DATA

    VECTOR GROUP: YNyn0(d5)

    TRANSFORMER RATED POWER IN MVA:

    PERCENTAGE IMPEDANCE:

  • 8/11/2019 AVR.xls

    2/2

    Recommended O/C blocking I> = 11.7333 A

    Recommended Band width Us = 2.55%

    corresponding to two tap to avoid the hunting of the OLTC.

    BANDWIDTH SELECTION

    It is necessary to keep the band width approximately