Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

20
Auxiliary, signalling and tripping relays RXMA1, RXMA 2, RXMM 1, RXMS 1, RXSF 1, RXME 1, RXME 18, RXMH 2 & RXMT 1 Features Suitable for tripping, blocking, interlocking, signalling etc. in protection, control and industrial systems Various ratings and contact configurations High voltage insulation Screen protected and dust-proof with a transparent plastic cover Low power consumption Heavy-, medium or light duty operation and long mechanical life Indication flags High resistance to shock and vibration Ultra high and high speed operation, down to 1,5 ms Up to 15 contacts in one relay Application The relays are intended for installations where high operating requirements exist, on operating time, contact rating (heavy breaking duty) or else where normal relays of industrial type are not suitable. The relays are especially suitable in protection and control circuits. Models exist that are very suitable for high corrosive atmosphere or seismic areas. Tripping, interblocking and multiplying functions are easily achieved with single relays or combinations of relays. Special requirements can be met by using different contact types, twin contacts, bridge contacts or dry-reed contacts. Types RXMA 1, RXMA 2 and RXMM 1 are used as position repeat relays, as interposing relays in control equipment and as output relay in protection relays. Type RXMM 1 is a space saving relay with two coils, each with 3 contacts for applications where few contacts are needed. Type RXMS 1 is particularly suitable as tripping relay due to its extremely short operate time. A special variant, which is not influenced by capacitive discharges at earth fault and which also has improved insulation across open contact, is available for heavy applications where high disturbance immunity is required. RXMS 1, in combination with heavy-duty relays, is used in high speed tripping assemblies as accessories to protection relays. Type RXSF 1 is a signal flag relay intended for use as operation indicator. A zero voltage type is available and can be used to supervise dc supply voltages. Types RXME 1 and RXME 18 are used where a low number of heavy duty contacts are required e.g. as trip relay. RXME 18 is a RXME 1 with an operating flag indicator. Type RXMH 2 is used when many heavy duty contacts are required. It can be provided with an operating flag indicator, as an option. RXMA 1 RXMS 1 RXSF 1 RXMM 1 RXMH 2 RXME 1 (RXMA_1.eps) (RXMM_1.eps) (RXMS_1.eps) (RXMH_2 .eps) (RXSF.eps) (RXME_1 .eps)

Transcript of Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Page 1: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relaysRXMA1, RXMA 2, RXMM 1, RXMS 1, RXSF 1, RXME 1,RXME 18, RXMH 2 & RXMT 1

Features − Suitable for tripping, blocking, interlocking, signalling etc.

in protection, control and industrial systems − Various ratings and contact configurations − High voltage insulation − Screen protected and dust-proof with a transparent

plastic cover − Low power consumption − Heavy-, medium or light duty operation and long

mechanical life − Indication flags − High resistance to shock and vibration − Ultra high and high speed operation, down to 1,5 ms − Up to 15 contacts in one relay

ApplicationThe relays are intended for installations where high operating requirements exist, on operating time, contact rating (heavy breaking duty) or else where normal relays of industrial type are not suitable.

The relays are especially suitable in protection and control circuits. Models exist that are very suitable for high corrosive atmosphere or seismic areas. Tripping, interblocking and multiplying functions are easily achieved with single relays or combinations of relays.

Special requirements can be met by using different contact types, twin contacts, bridge contacts or dry-reed contacts.

Types RXMA 1, RXMA 2 and RXMM 1 are used as position repeat relays, as interposing relays in control equipment and as output relay in protection relays.

Type RXMM 1 is a space saving relay with two coils, each with 3 contacts for applications where few contacts are needed.

Type RXMS 1 is particularly suitable as tripping relay due to its extremely short operate time. A special variant, which is not influenced by capacitive discharges at earth fault and which also has improved insulation across open contact, is available for heavy applications where high disturbance immunity is required.

RXMS 1, in combination with heavy-duty relays, is used in high speed tripping assemblies as accessories to protection relays.

Type RXSF 1 is a signal flag relay intended for use as operation indicator. A zero voltage type is available and can be used to supervise dc supply voltages.

Types RXME 1 and RXME 18 are used where a low number of heavy duty contacts are required e.g. as trip relay. RXME 18 is a RXME 1 with an operating flag indicator.

Type RXMH 2 is used when many heavy duty contacts are required. It can be provided with an operating flag indicator, as an option.

RXMA 1 RXMS 1 RXSF 1

RXMM 1 RXMH 2 RXME 1

(RX

MA

_1.e

ps)

(R

XM

M_1

.ep

s)

(RX

MS

_1.e

ps)

(RX

MH

_2 .

eps)

(RX

SF.

eps)

(RX

ME

_1 .

eps)

Page 2: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

2 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Auxiliary relays can be used in a number of ways with different accessories to obtain a variety of types of operation. A few typical circuits are shown below.

Plug-in units with e.g., diodes, resistors and capacitors are shown in other documents (see References on page 19). Connection blocks type RTXE for attachment to the pocket of the rear side of the terminal bases can be ordered from the same catalogue.

Drop-out time-lag with a diodeTo obtain a dropout delay of a dc relay or to protect an electronic circuit against transients, a diode unit across the relay coil (R) can be used. Diode unit, type RXTDA 1, or terminal base mounted type RTXE can be selected.

If the dropout time (t) in the table is too long it can be reduced with a resistor (r) connected in series with the diode.

Functions which can be obtained with additional components

Type Typical dropout time, t, with diode 2)

RXMA 1 100-125 ms

RXMA 2 20 ms

RXMM 1 40 ms

RXMS 1 1) 10 ms

RXME 1

RXME 18 35 ms

RXMH 2 60 ms

1) The diode is to be connected to terminals 21-28.

2) The deviation in dropout time from the values in the table can be considerable, due to

numbers of contacts, inductance in the coil, depending on operating voltage etc.

rRU

+

S

Drop-out delay can be achieved by connecting a parallel diode across the relay coil as shown. Please observe the polarities of the dc voltage and the diode.

When S makes the relay picks up instantaneously. When S breaks the relay drops out with a time lag caused by the diode.

Inductive transient protectionThe diode also provides transient protection of the relay and also for the parallel connected devices by reducing the induced overvoltages (many kV’s) caused by the inductance of the auxiliary relay upon disconnection from the dc supply when the energizing contact opens.

Transient protection (and shorter drop-out delays) may also be achieved by using a parallel connected resistor, thermistor or varistor across the relay instead of the diode. These components are available for mounting directly in the rear pocket of the terminal base using type RTXE component blocks.

Pick-up time-lag using a thermistor

+ -S

Kt

When S makes, the current heats the thermistor t and its resistance drops as its temperature increases. When the current through K reaches the pick-up value, the relay picks up and the thermistor is short-circuited by a make contact on the relay.

(960

0003

8)(9

7000

109-

1-en

.ep

s)

Page 3: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 3

Pick-up and drop-out time-lag using a capacitor

When S makes, the pick-up time is determinated by the values r, K and C. The relay picks up when C is sufficiently charged and the time lag upon drop-out is caused by C discharging through K after S breaks.

Pick-up time-lag using a capacitor (normal drop-out)

The pick-up time is determined by the values of r1, K and C. When the relay has picked up C is discharged across r2 and normal drop-out is obtained.

Impulse storing circuit (impulse lengthening)

When the impulse contact S momentarily makes, the relay picks up and remains picked up for a period the length of which is determined by r, K and C.

Impulse shortening circuit

-K

r

C+

S

When S makes, the relay K picks up instantaneously and remain a picked up until C is sufficiently charged. The relay then drops out, since the current through r and K falls below the relay drop-out value. (S remains closed all the time).

+ -S

Kr

C

+ -S

Kr1

r2

C

+ -S

K

r C

RTXV Control unitHigh-speed auxiliary relays can at earth-fault in unearthed DC voltage systems give unwanted operation.

To avoid the risk that the voltage caused by the earth-fault causes unwanted operation on auxiliary relays, we have designed a control unit, type designated RTXV, to be connected in series with the terminal of the relay coil.

The control unit connects applied voltage to the relay only if the voltage is larger than 60-80% of the rated voltage of the unit. The voltage drop in the control unit is about 2 V.

The control unit is mounted in a component box, which in its turn can be mounted on the rear of the terminal base of COMBIFLEXrelays.

For more information, see References on page 19.

Shorter pick-up times with separate seriesconnectedresistor

The operating time can be reduced for auxiliary relays by connecting a separate resistor – r in the diagram – in series with the relay coil K.

The connection reduces the L/R ratio, i.e. the time constant for the drawn relay coil operating current.

The pick-up time and characteristics of the series resistor for a number of types of relays are listed in the table 1. The dispersion of the pick-up time is about ±20% at rated voltages and up to ±50% if considering voltage range variations.

The drop-out time of the relay will be approximately the same as for a relay without the series resistor.

K

r

U

(970

0011

0-1-

en.e

ps)

(970

0011

1-1-

en.e

ps)

(970

0011

3-1-

en.e

ps)

(970

0011

4-1-

en.e

ps

(970

0011

5-1-

en.e

ps)

Page 4: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

4 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Table 1: Dimensioning the series resistor for obtaining shorter pick-up times

D.c. supplied auxiliary relays with supply voltage U = 110, 125. 220 and 250 V.

(The table contains information also for some non-standard voltages for relays available on request.)

Relay Pick-up time 1) U = 110 V U = 125 V Max. permitted

connection timetype operating

value

group

Break

contact

ms

Make

contact

ms

Relay

with

rated

voltage V

Series

resistance,

r Ω

Wattage

of r W

Wattage

of r + R

W

Relay

with

rated

voltage V

Series

resistance,

r Ω

Wattage

of r W

Wattage

of r + R

W

RXME 1 10

7

20

15

24

12

630

400

9

21

13

25

24

12

750

450

11

25

15

30

5 min.

5 min.

RXMH 2 10

6

25

15

24

12

500

160

14

48

19

60

24

12

600

200

17

54

21

65

Cont.

5 min.

RXMA 1 1-3 5 10 12 2000 5 6 12 2250 6 7 Cont.

RXMA 2 6 8 13 12 330 25 30 12 400 28 33 Cont.

Relay Pick-up time 1) U = 220 V U = 250 V Max. permitted

connection timetype operating

value

group

Break

contact

ms

Make

contact

ms

Relay

with

rated

voltage V

Series

resistance,

r Ω

Wattage

of r W

Wattage

of r + R

W

Relay

with

rated

voltage V

Series

resistance,

r Ω

Wattage

of r W

Wattage

of r + R

W

RXME 1 10

7

20

15

48-55

24

2500

1600

9

21

13

25

48-55

24

3000

1800

11

26

15

30

5 min.

5 min.

RXMH 2 10

6

25

15

48

24

2000

630

15

50

19

62

48

24

2300

750

18

57

22

69

Cont.

5 min.

RXMA 1 1-3 5 10 24 8000 5 6 24 9000 6 7 Cont.

RXMA 2 6 8 13 24 1600 22 26 24 1800 26 30 Cont.

1) The dispersion of the pick-up time is about ±20%, ±50% if considering voltage range variations

Table 2: Coil resistance, relays with twin contacts

(The table contains information also for some non-standard voltages for relays available on request.)

Rated

voltage

V

Relays with twin contacts

RXMA 1 RXMA 2, dc RXMM 1 RXMS 1, dc RXMS 1, dc

dc

op. v. gr.1)

1–3

op. v. gr.1) 6 dc Variant A, E Variant B

Coil resistance Ω Coil

resistance Ω

Series

resistance Ω

Total

resistance Ω

Coil

resistance Ω

Series

resistance Ω

Total

esistance Ω

12

24

30-36

36

110

460

625

-

70

270

375

-

140

460

735

-

6,3

21

-

40

18

72

-

156

23,3

93

-

196

21

82

-

210

27

110

-

240

48

192

-

450

48

48-55

55

110

-

2020

-

-

-

1070

-

-

-

2050

-

-

108

-

108

380

320

-

360

1430

428

-

468

1810

360

-

465

1920

410

-

570

2070

770

-

1035

3990

110-125

125

9680

-

6120

-

10800

-

-

610

-

2000

-

2610

-

2450

-

2900

-

5370

220

220-250

250

-

39200

-

-

19300

-

-

40000

-

1520

-

1920

5700

-

8000

7220

-

9920

6090

-

8670

8420

-

10700

14510

-

19370

1) op. v. gr. = Operating value group

Page 5: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 5

Rated voltage Relays with bridge contacts

RXME 1

RXME 18

RXMH 2

dc dc ac

50 and 60 Hz

Coil resistance Ω

12

24

48

48-55

78

301

-

1130

39

155

564

-

-

39

-

-

55

110

110-125

-

-

5780

700

2930

-

194

700

-

125

127

220

-

-

-

3610

-

10600

-

890

2930

220-250

250

380

23300

-

-

-

13500

-

-

-

8520

Table 3: Coil resistance, relays with bridge contacts

Rated voltage V Relays with single contacts, RXMT 1

Symbol No.110 Symbol No. 111 Symbol No. 112

Terminal marks of coils

11-12 21-22 11-12 21-22 11-12 21-22

Coil resistance Ω

12-15

24

48-60

110-125

670

2600

6800

16800

670

2600

6800

16800

670

2600

6800

16800

670

2600

6800

16800

670

2600

6800

16800

670

2600

6800

16800

Table 4: Coil resistance, relays with single contacts

Page 6: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

6 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Design

The auxiliary relays in the COMBIFLEX system permit interchanging between various types of relays chiefly because the coil terminals are always connected to the same terminal on the plug-in base of the relay. Relays having the same contact symbol can be interchanged without alteration of the connection.

The contact elements are made of silver, however, gold elements on the contacts can sometimes be necessary, for example in sulfuric atmospheres or when the voltage in the contact circuit is lower than 10 V and the current lower than 10 mA.

Each relay has a dust-tight cover, except the RXMS variants A and E, and is intended to be mounted on a terminal base. Terminal bases are available in four sizes. The relays are fixed to the terminal bases with two or four Phillips No. 2 cross-head screws. Each relay cover has a hole covered by a removable plastic plug with the exception of RXME 18, RXSF 1 and RXMT 1. Through the hole the armature of the relay can be activated. Relays with indicating flags have a resetting knob accessed from the outside of the cover.

The relays are marked with the type designation, Ordering No., rated voltage, and where applicable, the symbol of the relay is also shown.

All dc supplied relays, with the exception of RXMS 1 and RXMT 1, can be supplied with full-wave or half-wave rectified ac.

For supply with full-wave rectified ac, select relays with a rated voltage equivalent to the supply voltage.

For supply with half-wave rectified ac, a diode in addition to the series diode is to be connected in parallel across the coil and the rated voltage of the relay is to be equivalent to half the supply voltage. If transients are expected in the supply voltage, these determine the choice of matching diodes.

Smoothing capacitors are unnecessary in both cases.

The auxiliary relays will operate within a range of 80-110% of the rated voltage. If the rated voltage is given as a voltage range, e.g. 110-125 V, the relays will operate within a range of 80-110 % of each rated voltage between 110 and 125 V. Permissible temperature range is given in the data table.

Relays with twin contactsAuxiliary relays used in automatic equipment for control and regulation must have a very high degree of contact reliability even at lower voltages. Auxiliary relays with twin contacts fulfil this requirement. A twin contact has two contact elements on each contact member and each of these makes independent and simultaneous contact with the corresponding element on the other contact member. This gives two parallel current paths and greatly reduces the risk of contact failures. The contact sets have contact levellers of wear-resistant material with a low coefficient of expansion. This means that the correct contact force is always obtained even in contact units containing numerous contact springs. Type RXMA, RXMM, RXMS and RXSF contain twin contacts.

Figure 1: Twin contact

RXMA 1This relay is designed for dc supply. The outstanding features of this relay are its low power consumption and long mechanical life.

A few variants of RXMA 1 is ac operated with a valid frequency between 50-60 Hz and rated voltage of 115 or 230 V. A half-wave rectifier is built in, connected in parallel across the coil.

RXMA 2This relay is a variant of RXMA 1, with a larger terminal plug-in plate, and a greater number of contacts.

The relay occupies two seats.

(960

0003

9)

Page 7: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 7

RXMA 1 and RXMA 2 have one, two or three sets of contact stacks. The system voltage across one stack of contacts must not exceed 300 V dc or 250 V ac. The corresponding voltage between contact stacks must not exceed 600 V dc or 500 V ac.

RXMM 1The relay is designed for dc supply. Two smaller type relays are included in RXMM 1. These relays can each have up to 3 contacts (6 contact springs). Relay RXMM 1 with different rated voltages for the two relays is also available as an option.

RXSF 1The unit contains one or two smaller relays with three contacts and red indicating flags. The flags are reset manually with an external knob or automatically when the dc is switched off.

The RXSF 1 is also available as loss-of-voltage relay. The indicating flag is always automatically reset in this variant.

There are DC voltage and DC current operated versions of the RXSF 1 relay. See the selection tables on p. 16. The current operated relay may e.g. be used to indicate that breaker trip coil current has flown, i.e. as a series trip current flag (target).

SCADA Interposing Relay type RXSF 1Interposing relays for SCADA equipment must not misoperate due to induced AC overvoltages that may occur as a result of a relatively long distance between the RTU and the remote control panel. Such a misoperation may lead to maloperation of breaker or isolator open / close commands.

There is a variant of the well proven relay RXSF 1 that may be used to reduce the risk of such a misoperation. The RXSF 1 is designed

to reject induced AC voltages. The SCADA interposing version of RXSF 1 is in addition designed to provide a higher operating current in order to even further increase security against maloperation due to induced AC voltage interference.

RXMS 1This relay is designed for dc supply. It has a very short pick-up time, down to 4 ms for a make contact (variant A, 7 W). Variant B is a low power variant (3 W) with 1,5 ms longer pick-up time.

Variant E (7 W) is safe for capacitive discharge through the coil at dc earth faults. It has also a larger contact gap, which can withstand 2 kV test voltage.

Because of the high power consumption in variants A and E these variants should not be continuously energized.

The relay has an additional terminal (28) brought out between the coil and the series resistor. This terminal is intended for dropout delay by connecting a diode across the coil.

Figure 2: RXMS 1

Relays with bridge contactsAuxiliary relays which are to be used as tripping relays or as operating relays should have a high breaking capacity, good contact reliability and be free from risk of contact welding. These qualities are possessed by relays with bridge contacts.

The contacts have two fixed contact members and a moving bridge-shaped member. This design with two breaking points in series gives high breaking capacity.

The moving contact member is designed so that a considerable sliding motion is obtained between the contact elements during closing; this increases contact reliability and reduces the risk of welding.

(RX

MA

_2.e

ps)

(960

0004

0)

Page 8: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

8 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Design

Types RXME 1, RXME 18 and RXMH 2 contain bridge contacts.

Figure 3: Bridge contact

RXME 1This relay is designed for dc supply. It has two or four contacts.

RXME 18The relay consists of an RXME 1 relay fitted with a red indicating flag. The flag becomes visible when the armature picks-up and remains visible after drop-out. The flag is manually reset by means of a resetting knob in the cover. The relay has two contacts.

RXMH 2This relay has eight heavy duty contacts and can be fitted with an indicating flag which becomes visible when the armature picks-up and remains visible after drop-out. The flag is manually reset by means of a resetting knob in the cover. For checking the operation the relay has a push-button which is accessible through a hole in the cover. The relay occupies two seats.

Relays with single contacts (dry-reed relays)In certain cases auxiliary relays are used in a highly corrosive atmosphere or under other conditions where special contacts are required, e.g. for low voltages and currents such as in automatic control circuits with static components. For such applications, auxiliary relays with built-in special contacts, e.g. dry-reed elements should be used. A dry-reed element has one fixed and one moving contact of magnetic material. If the coil, which encircles a dry-reed element with a make contact, is energized, magnetic flux flows through the contact which then closes. When the coil is de-energized the contact opens.

In dry-reed relays with break contacts the coil also encircles a permanent magnet of which the flux holds the contact closed. When the coil is energized the flux of the permanent magnet is counter-balanced and the contact opens. When the coil is de-energized the contact is reclosed by the permanent magnet. This implies that dry-reed relays with break contacts are dependent on polarity, and the coil must be connected in accordance with the symbols in the ordering table.

Figure 4: Single contact

(RX

ME

_1.e

ps)

(960

0004

1)

(960

0004

2)

(RX

ME

_18.

eps)

Page 9: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 9

RXMT 1RXMT 1 has 2 dc-supplied dry-reed relays, each with one make or break contact (dryreed element). The relay is very fast and has a pick-up time of < 1,5 ms.

RXMT 1 should not be positioned alongside relays which have powerful magnets as they may cause RXMT 1 to remain in the pickedup position.

Tripping assembliesSingle auxiliary or flag relays of any model may be used in tripping circuits, depending on requirements. Specially designed combinations of relays mounted on terminal bases and apparatus bars are available. These tripping units combine an ultra-high speed relay, type RXMS1 and a heavy duty relay for carrying and breaking high currents. Combinations with latching relays or time relays for prolonged trip pulse and delayed resetting are available.

Trip and indication moduleAn auxiliary trip module for tripping from transformer protection device, e.g. Buchholz, temperature, etc., is available. It contains up to 10 inputs and the inputs are safe for capacitive discharge. A timer provides the required pulse length.

(RX

MT_

1.ep

s)

(SE

9708

73)

Page 10: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

10 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Technical data

Rated voltage Ur see ordering table

Duty range in % of Ur

RXMA 1

other types

80-125%

80-110% 1)

Relay type Pick-up value Drop-out value Pick-up time, typical

values, make/break contact

Drop-out time, typical

values, make/break contact

% of Ur % of Ur ms ms

RXMA 1 < 50 > 12 40/30 15/20

RXMA 1, variant 37 and 52 dc < 40 > 10 25/15 15/20

RXMA 1, variant 37 and 52 ac < 70 > 30 50/35 80/80

RXMA 2 < 80 > 25 30/20 5/10

RXME 1 < 80 > 10 35/25 5/15

RXMH 2 dc < 80 > 20 60/35 25/35

RXMH 2 ac < 80 > 20 60/35 60/60

RXMM 1 < 80 > 5 30/20 5/10

RXMS 1 var. A < 80 > 5 4/3,5 2,5/5

RXMS 1 var. B < 80 > 5 5,5/5 2,5/5

RXMS 1 var. E 55-80 > 10 8/6 3/5

RXMT 1 < 80 > 10 1,5/1,5 1,5/1,5

RXSF 1 < 80 > 5 30/20 5/10

Operate values and times

Salient features of SCADA interposing relay type RXSF 1 − Immune to AC induced voltages across coil up to 150 V

AC − Higher burden than its counterparts

− Minimum pickup current >25mA − Drop-off current >15mA

− Pickup voltage is 30% - 50% of Un − Maximum permitted energizing time is 10 seconds every

2 minutes − Drop-out voltage is more than 60% of Pickup voltage − Self reset flag indicator − 2 NO + 1 NC contacts

Technical data for current relay RXSF 1 is identical as for voltage

relay except for following:

Operating time (closing contact)

2 x Ir4 x Ir

< 14 ms

< 10 ms

Minimum pulse time for the flag 50 ms

Operate value, % of IrThermal capacity, % of IrContinuous with both relays energized

80-100

250

250%

Power consumption at I = Ir 0,1 W

Page 11: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 11

Power consumption at U = Ur

RXMA 1 dc 1,1-1,3 W

RXMA 1 ac appr 2 VA

RXMA 2 2,0-2,5 W

RXMM 1,1-1,3 W

RXSF 1,1-1,3 W

RXMS var. A 1) 6-7 W

RXMS var. B 2,9-3,3 W

RXMS var. E 1) 6-7 W

RXME 1,9-2,1 W

RXMH dc 3,7-4,6 W

RXMH ac appr. 8 VA

RXMT 0,2-0,7 W1) The RXMS variants A and E can be energized for max five minutes per interval of ten minutes

Contact data

Relay type Max. system

voltage dc/ac

within a contact set

Current-carrying

capacity (for already closed

contact) 200 ms/1 s/cont.

Making and conducting

capacity L/R > 10 ms 200 ms/1 s/

two contacts in parallell1 s

Breaking capacity

ac cos j > 0,1

max. 250 V

Breaking capacity

dc L/R < 40 ms

24/48/110/220 V

V A A A A

RXMA 1 300/250 (600/5003)) 90/50/5 30/10/15 10 4/1,5/0,4/0,2

RXMA 2 300/250 (600/5003)) 90/50/5 30/10/15 10 4/1,5/0,4/0,2

RXME 1 450/400 55/30/6 30/20/30 201) 20/18/3/1 2)

RXMH 2 600/500 135/75/10 30/20/30 20 20/20/6/1,2

RXMM 1 300/250 90/50/5 30/10/15 10 4/1,5/0,4/0,2

RXMS 1

var. A, B

var. E

300/250

300/250

35/20/4

35/20/4

30/10/15

30/10/15

10

10

2,3/1,2/0,3/0,15

2,7/1,4/0,35/0,17

RXMT 1 250/250 3/2,5/2 2/2/- 0,6 1/0,5/0,2/0,1

RXSF 1 300/250 90/50/5 30/10/15 10 4/1,5/0,4/0,2

1) 10 A for RXME 1 with four contacts

2) 15/6/0,9/0,3 A for RXME 1 with four contacts

3) between sets of contacts

Permitted ambient temperature -25°C – +55°C

Dimensions RXMA 1, RXME 1, RXMM 1, RXMS 1, RXMT 1, RXSF 1 2U 6C

RXMA 2, RXMH 2 2U 12C

Weight RXMA 2 0,5 kg

RXMH 2 0,7 kg

Other types 0,4 kg

Insulation tests: Dielectric test, 50 Hz, 1 min

RXME, RXMH 2,5 kV

Other types 2,0 kV

Impulse voltage test

1,2/50 µs, 0,5 J 5,0 kV

Page 12: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

12 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Diagrams and ordering

Specify: − Type − Quantity − Ordering No.

− consists of a number and letters for the rated voltage, example RK 211 052-AN, see tables below.

− Ordering No. for flag and reset knob when applicable

RK 211 025-.. RK 211 037-.. RK 211 052-.. RK 211 063-.. RK 211 064-..

Ordering number selection table RXMA 1

16 17

11 21

26 2715 16

11 21

17X

25 2627

Z

14 15

11 21

16 17

24 2526 27

X

Z

12 13

11 21

14 1516 17

X

22 2324 2526 27

Z

12 13

11 21

14 15

22 2324 25

X

Z

16 17

26 27RK 211 066-.. RK 211 072-.. RK 211 073-.. RK 211 074-..

12 13

11 21

14 15

22 2324 25

X

Z

16 17

26 27

13 14

11 21

15 X16 1718

12 22

23 242526 2728

Z

Y

13 14

11 21

15 X16 1718

12 22

23 242526 2728

Z

Y

12 13

11 21

16 17

X14 15

18 28

26 27

22 2324 25

Y

Z

Letter selection table, DC rated voltage V

24 48-55 110-125 220-250

AD AH AN AS

Letter selection table, AC rated voltage V, 50-60 Hz

115 230

BN BS

RK 211 037-.. RK 211 052-..

15 16

11 21

17X

25 2627

Z

14 15

11 21

16 17

24 2526 27

X

Z

Page 13: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 13

RK 211 185-.. RK 211 186-.. RK 211 188-.. RK 211 189-..

Ordering number selection table RXMA 2

116 117

121 211

118X127 128

218217 228227

114 115124

Y125 126214215 216226

111 112113

Z122 123212213 222221

223 224225

116 117

121 211

118X127 128

218217 228227

114 115126

Y125 216215226 225224

Z

111 112122 123124 113212 213214 223221 222

116 117

121 211

127 118217 128 X218 228224 225226 227

Y114 115125 126215 216

111 112122 123124 113 Z212 213214 223221 222

116 117

121 211

127 118217 128 X218 228224 225226 227

Y114 115125 126215 216

111 112122 123124 113 Z212 213214 223221 222

Letter selection table, DC rated voltage V

24 48-55 110-125 220-250

AD AH AN AS

RK 221 025-.. RK 221 026-..

Ordering number selection table RXME 1

RK 221 027-.. RK 221 052-..

RK 221 825-.. RK 221 826-..

16 17

11 21

26 2716 17

11 21

26 27

Ordering number selection table RXME 18

RK 221 827-..

16 17

11 21

26 27

Letter selection table, DC rated voltage V

24 48-55 110 220-250

AD AH AN AS

Page 14: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

14 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Diagrams and ordering

RK 223 067-.. RK 223 068-.. RK 223 069-..

Ordering number selection table RXMH 2

111 112

121 211

113 114115 116117 118221 222223 224225 226227 228

111 112

121 211

113 114115 116221 222223 224225 226117 118227 228

111 112

121 211

113 114221 222223 224115 116117 118225 226227 228

Letter selection table, rated voltage V

24 48 110 120 125 127 220 250

DC AD AH AN - AP - AS AT

AC - - EN EC - EP ES -

15-60 Hz

RK 214 002-.. RK 214 003-..

13 14

16 1715

18

11 12

A

23 24

26 2725

28

21 22

B

Letter selection table, DC rated voltage V

24 48-55 110-125 220-250

AD AH AN AS

RXMH 2 with red flag and resetting knob Ordering No. for desired relay according to the table above + RK 223 900-XA

No. selection table RXMM 1

RK 214 004-.. RK 214 005-.. RK 214 006-..

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

Page 15: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 15

Ordering number selection table RXMS 1Variant A: RK 216 237-.. RK 216 263-.. RK 216 265-.. RK 216 266-..Variant B: RK 216 037-.. RK 216 063-.. RK 216 065-.. RK 216 066-..Variant E: RK 216 463-.. RK 216 465-.. RK 216 466-..

15 16

11 21

17X

25 2627

Y

12 13

11 21

14 1516 17

X

22 2324 2526 27

Y

12 13

11 21

14 15

22 2324 25

X

Y

16 17

26 27

12 13

11 21

14 15

22 2324 25

X

Y

16 17

26 27

Letter selection table, DC rated voltage V

24 48 110 125 220 250

AD AH AN AP AS AT

Ordering number selection table RXMT 1RK 241 110-.. RK 241 111-.. RK 241 112-..

13 14

11 12

A

23 24

21 22

B

14 15

11 12

A

24 25

21 22

B

+

+

14 15

11 12

A

23 24

21 22

B

+

Letter selection table, DC rated voltage V

24 48-60 110-125

AD AH AN 1)

1) This relay for 110-125 V can also be used at 220-250 V when it is connected via a

resistor block type RTXE, RK 741 225-EF 18 kohm, 2W

Page 16: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

16 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Diagrams and ordering

RK 271 006-.. RK 271 007-.. RK 271 016-..

Ordering number selection table RXSF 1

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

13 14

11 12

A

15 1617 18

RK 271 017-..

13 14

11 12

A

15 1617 18

RK 271 018-..

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

RK 271 019-..

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

Flag is automatically reset when deenergizing the coil

Flag is to be reset

Loss of voltage relay

Voltage operated relay

Letter selection table, DC rated voltage V

24 48-55 110-125 220-250

AD AH AN AS

Current operated relay

Letter selection table, DC rated Current A

0,2 1,0 2,0

HB HF HG

Other current operated variants on request

Scada interposing relay RXSF 1Ordering Number: 1MRK 001 799-AP

13 14

11 12

A

21 22

B

15 1617 18

23 2425 2627 28

Rated voltage 125 V DC.

(960

0039

2)

Page 17: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 17

Figure 5: High-speed tripping assembly, RK 651 231-AB, Diagram No. 5651 109-AB

High-speed trip units

Specify: − Ordering No. − Auxiliary DC voltage

211 121

111112

113114

115116

117118

221222

223224

225226

227228

101

21 11

1312

1415

1617

2223

2425

2627

301

21 11

1615

17

2625

27

307

+

+

+

+

+

+

+

RL+

RL-

1)

2)

101

301 307

12C

4U

101 RXMH 2

301 RXMS 1

307 RXKL 1

TRIPPING, ETC.

ALARM, ETC.

1)

2)

RXMS 1 RXME 1 RXMH 2 RXMVB 2 RXKL 1 Ordering No. Diagram No.

1 1 5651 273-C 5651 273-CA

1 1 5651 260-F 5651 260-AA

1 1 5651 261-D 5651 261-AA

1 1 1 RK 651 231-AB 5651 109-AB

2 2 5651 260-G 5651 260-AA

2 2 5651 261-E 5651 261-AA

Page 18: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

18 | Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D

Diagrams and ordering

Auxiliary trip unit for transformer protection device

Specify: − Ordering No. − No. of inputs − Auxiliary DC voltage

Function Ordering No. Diagrams

6 inputs (+ 4 alarm inputs) RK 891 031-AA 5651 284-AA/ -AAA

4 inputs RK 891 031-BA 5651 284-BA/ -BAA

Figure 6: Auxiliary trip unit, RK 891 031-AA, Diagram No. 5651 284-AAA

Page 19: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

Auxiliary, signalling and tripping relays - 1MRK 508 015-BEN Revision: D | 19

References

COMBIFLEX

Connection and installation components 1MRK 513 003-BEN

Relay mounting systems 1MRK 514 001-BEN

RTXE Component blocks 1MRK 513 019-BEN

RXT Plug-in component unit 1MRK 513 017-BEN

Time relay RXKL 1 1MRK 508 002-BEN

Voltage control unit RTXV 1MRK 513 007-BEN

Auxiliary relays, Self-reset and bistable 1MRK 508 015-UEN

Auxiliary relays RXMB 1 and RXMB 2 1MRK 508 006-BEN

Bistable relay RXMD 1 and RXMD 2 1MRK 508 017-BEN

Page 20: Auxiliary, signalling and trippning relays RXMA 1 RXMA 2 RXMS 1 ...

1MR

K 5

08 0

15-B

EN

Rev

isio

n: D

Contact us

ABB AB Substation Automation Products721 59 Västerås, Sweden Phone: +46 (0) 21 32 50 00

www.abb.com/substationautomation

ABB Limited Plot no. 4A, 5 & 6, II PhasePeenya Industrial AreaBangalore - 560 058. India Phone: +91 80 2294 9632Facsimile: + 91 80 2294 9188

Note:We reserve the right to make technical changes or modify the contents of this document without prior notice. ABB AB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.We reserve all rights in this document and in the subject matter and illustrations contained herein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in part – is forbidden without prior written consent of ABB AB.