![Page 1: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/1.jpg)
Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com 21Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com
Air conditioning unit with asymmetrical high-capacity heat exchanger and integrated heat pump for medium-sized and
large public swimming pool halls
The devices of the ThermoCond 37 series are multi-functional systems for air conditioning public swimming pool halls. The design and functionality of all systems are optimally adapted to your requirements. The integrated heat pump increases the total efficiency of the sys-tem and allows the dehumidification of swimming pool hall air in recirc mode. The combination of first-class compo-nents with precise control and regula-
thermoCond 37
at a glance:
AIR VOLUME FLOW: 2,500 – 36,000 m³/h
Dehumidifies, ventilates and heats
Corrosion-free heat exchanger made from polypropylene
Integrated heat pump
energy-saving solVent fan/motor units with active flow rate control and vibration monitoring
Integrated clean water heater
Two-stage supply air filtration
Precise measurement and regulation of the outside air volume
Integrated control and regula-tion system, compatible with all conventional building management systems
Fulfils the requirements of VdI 6022
tion systems guarantees economical operation at all times, while ensuring the highest degree of comfort air con-ditioning. ThermoCond systems dehu-midify, heat and ventilate the swimming pool hall, and simultaneously create good climate and ideal protection for the material of the building. Additional apparatus such as radiators or panel heating systems are generally not re-quired.
- Filtering the air in any operating mode
- Pumped hot water air heater- Individually controllable parameters- Complete unit, ready to connect,
contains all structural elements for air conditioning swimming pool hall air, including all control and regula-tion fittings
- Intensive quality inspection with fac-tory trial run
Options- Pool water condenser- HRC bypass function- Dehumidifying the outside air using
additional outside and exhaust air connection pieces
- Clean water heater in double-walled design
- Sound absorber- Outdoor installation- Thermal bridge factor TB 1- Remote maintenance- And many more
Further performance parameters and options:
Automatically selects the most economical operating mode!
Indoor swimming pool air conditioning | thermoCond 37
Ther
moC
ond
publ
ic
![Page 2: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/2.jpg)
Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com22
Indoor swimming pool air conditioning | thermoCond 37
Functional description
V
V
K
(+)(+)
Return air
Supply air
Outsideair
Exhaust air
V
V
K
(+)(+)
Return air
Supply air
Outsideair
Exhaust air
V(+)
K
(+)
V
Return air
Supply air
Outsideair
Exhaust air
V(+)
K V
(+)
Return air
Supply air
Outsideair
Exhaust air
V(+)
K
(+)
V
Return air
Supply air
Outsideair
Exhaust air
Return air
Supply air
Outsideair
Exhaust air
K(+)
V(+)
K
(+)
V
Standby modeIf no requirements are placed on tem-perature regulation or dehumidifica-tion when the swimming pool hall is in standby mode, the system operates only in recirc mode. The air circula-tion in the swimming pool hall is guar-anteed, but the fans work at a lower capacity.
recirc air Heating operationThe pumped hot water heating coil heats the swimming pool hall as re-quired in recirc mode. In order to reduce the internal pressure losses, the upper
bypass damper is also opened. The out-side air and exhaust air dampers are closed.
Recirc air dehumidificationIn recirc mode, the air is dehumidified in the evaporator of the heat pump – this is reinforced by the fact that the heat exchanger is arranged up-stream. The air that has been cooled and dried in this manner is preheated by the warm swimming pool hall air in the heat exchanger, mixed with a pro-
portion of untreated recirc air, is heated further in the condenser, and is returned to the swimming pool hall as supply air. If the heating ca-pacity of the heat pump is not suf-ficient, the supply air is reheated with the pumped hot water heating coil.
Bathing mode In swimming pool mode the minimum required amount of outside air is added to the recirc air for hygienic reasons (VDI 2089). The proportion of outside air de-pends on the current water evaporation (and therefore the occupancy level of the swimming pool hall), as well as the out-
side air humidity. This is continuously and automatically adjusted. If the waste heat recovery and the heating capacity of the heat pump are not sufficient for achieving the desired supply air temperature, the supply air will be reheated in the pumped hot water heating coil.
outside air exhaust air modeIn the case of rising outside air humid-ity or high outside air temperatures, the recirc air damper is continuously closed as required. If the outside air moisture is high, the damper closes completely, the system works exclu-sively in outside air-exhaust air mode
via the heat exchanger. The heat pump emits heat as required to the supply air, or where there is excess heat, to the clean water heater or the optionally available pool water condenser (PWC).
optionallyIn order to achieve the hall humidity lev-els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper system. A second outside air vent is used to suck in outside air. Some of the outside air is precooled via the recuperator, and then cooled to below the dew point in the evaporator. The air is then rewarmed in the recuperator,
dried and cooled with some of the un-treated outside air, before being intro-duced into the hall as supply air. If no heating of the swimming pool hall is re-quired, the heat of condensation is dis-charged directly into the return air flow.
ThermoCond
public
* PWC: * only unit type 37 xx 11
*
*
*
*
*
*
![Page 3: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/3.jpg)
Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com 23Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com
thermoCond Type 37 System dimensions and weights
Unit Type L W H 1 L1 L2 L3 RA1 RA2 OA1 OA2 EA1 EA2 SA1 SA2 Weight 37 02 01 3,220 570 1,370 1,210 2,010 - 420 580 420 580 420 340 340 580 79037 03 01 3,220 730 1,370 1,210 2,010 - 580 580 580 580 580 340 500 580 87037 04 01 3,220 890 1,370 1,210 2,010 - 740 580 740 580 740 340 660 580 93037 05 01 3,220 1,050 1,370 1,210 2,010 - 900 580 900 580 900 340 820 580 99037 06 01 3,950 730 2,130 1,210 2,010 730 580 900 580 900 580 580 420 900 1,33037 10 01 4,430 1,050 2,130 1,690 2,010 730 900 900 900 900 900 580 740 900 1,82037 13 01 4,430 1,370 2,130 1,690 2,010 730 1,220 900 1,220 900 1,220 580 1,060 900 2,20037 16 01 4,590 1,690 2,220 1,850 2,010 730 1,540 900 1,540 900 1,540 580 1,380 900 2,62037 19 01 4,590 2,010 2,220 1,850 2,010 730 1,860 900 1,860 900 1,860 580 1,700 900 2,80037 25 01 5,550 2,010 2,860 2,010 2,650 890 1,860 1,220 1,860 1,220 1,860 580 1,700 1,220 3,86037 32 01 6,190 2,010 3,500 2,170 3,130 890 1,860 1,540 1,860 1,540 1,860 740 1,700 1,540 5,10037 36 01 6,190 2,330 3,500 2,170 3,130 890 2,180 1,540 2,180 1,540 2,180 740 2,020 1,540 6,000
For service work, a clearance corresponding to dimension W is required on the operating side of the unit. If dimension W is smaller than one metre, please leave a clearance of one metre.
For service work above the unit, please allow 50 mm working height clearance above the cable duct.
Please comply with the dimensions for body size, air duct connections and electrical switch cabinet.
All lengths are given in mm, weights in kg.1 plus cable duct; up to 37 05 01 plus feet, from 37 06 01 incl. 120 mm base frame
Unit Type L W H 1 Weight 37 02 01 2,010 570 1,370 41037 03 01 2,010 730 1,370 45037 04 01 2,010 890 1,370 50037 05 01 2,010 1,050 1,370 55037 06 01 2,010 730 2,130 57037 10 01 2,010 1,050 2,130 74037 13 01 2,010 1,370 2,130 86037 16 01 2,010 1,690 2,220 1,05037 19 01 2,010 2,010 2,220 1,13037 25 01 2,650 2,010 2,860 1,70037 32 01 3,130 2,010 3,500 2,30037 36 01 3,130 2,330 3,500 2,500
Largest transport unit
37 02 01 - 37 05 01 in two-cube design, OA-EA cube and recuperator cube form a single unit.Mirror-image design possible.
Caution!Where a system is being operated in parallel, the supply air and return air ducts must be laid together.
Indoor swimming pool air conditioning | thermoCond 37
Ther
moC
ond
publ
ic
OA
EA
RA
SA
OA
EA
RA
SA
OA1
EA1
RA1
SA1
W
LL1 L2 L3
OA1
EA2
OA2
SA2
RA2
H
Floor drain HTø50 Condensate drainage HTø50
H1
Cable ducts *
PHWFL
PHWRN
* up to unit type 37 25 01 = 40 mm from unit type 37 32 01 = 60 mm
![Page 4: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/4.jpg)
Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com24
Technical specifications and services
Unit Type without pool water condenser 37 02 01 37 03 01 37 04 01 37 05 01 37 06 01 37 10 01 with pool water condenser 37 02 11 37 03 11 37 04 11 37 05 11 37 06 11 37 10 11Nominal flow rate m³/h 2,500 3,500 4,600 5,300 6,300 9,500
Dehumidification capacity according to VDI 2089 kg/h 16.3 22.9 30.1 34.7 41.2 62.1Dehumidification capacity in recirc mode kg/h 6.5 8.4 10.8 12.5 15.5 26.2Heating capacity of heat pump 1 COP 8.7 8.6 9.2 8.9 8.2 8.4Total electrical power rating 2 kW 3.0 3.8 4.8 5.7 7.5 11.4Current consumption2 A 10.8 13.4 16.3 18.1 22.2 33.4Operating voltage 3 / N / PE 400 V 50 HzExt. pressure lossesSupply and fresh air channel Pa 300 300 300 300 300 300Return and exhaust air channel Pa 300 300 300 300 300 300Sound power level 3
Supply air vent dB(A) 65 64 73 74 75 74RA connection dB(A) 63 75 76 78 79 78Outside air vent dB(A) 65 64 73 74 75 74EA connection dB(A) 61 73 74 76 77 76Acoustic pressure at a distance of 1 m from the device3 dB(A) 53 59 62 64 65 64
Fan unitsRated motor input for supply air 4 kW 1.11 1.50 1.98 2.10 2.70 3.93Rated motor input for return air 4 kW 0.89 0.96 1.29 1.84 2.38 3.43Rated motor input for supply air recirc mode 4 kW 0.70 1.24 1.62 1.44 1.80 2.43Rated motor input for return air recirc mode 4 kW 0.71 1.02 1.32 1.51 1.84 2.53SFP category supply air/return air recirc mode 1 | 2 1 | 2 1 | 2 1 | 2 1 | 2 1 | 2
Integrated heat pumpFilling volume of refrigerant type R407C (without PWC | with PWC) kg 3.5 | 5.0 4.5 | 5.0 4.5 | 5.0 4.5 | 5.5 4.0 | 7.0 6.0 | 14.0Rated compressor input for recirc mode 5 kW 1.2 1.5 1.7 2.1 2.7 4.4Heating capacity of heat pump for recirc mode 5 kW 8.1 10.6 13.5 15.6 18.4 30.1Rated compressor input for OA operation kW 1.0 1.3 1.5 1.8 2.4 4.0Heating capacity of heat pump for OA operation kW 8.0 10.3 12.7 14.7 18.0 30.3
Clean water heating 6
Heating capacity for OA operation kW 0.7 0.9 1.09 1.33 1.79 3.2Quantity of flow m³/h 0.08 0.10 0.12 0.14 0.17 0.28
PHWHeating capacity 7 kW 16.8 24.0 31.6 37.1 41.8 62.9
Water flow rate and pressure lossesPHW 7 m³/h|kPa 0.75 | 4.7 1.06 | 5.4 1.47 | 8.6 1.72 | 6.9 1.83 | 8.6 2.76 | 4.1PHW valve 7 m³/h|kPa 0.75 | 9.0 1.06 | 7.0 1.47 | 13.5 1.72 | 7.3 1.83 | 20.9 2.76 | 7.6
Pool water condenser 8
Heating capacity kW 7.5 9.8 12.9 14.6 17.0 28.3Spread of pool water temperature K 8.0 6.0 7.9 9.0 10.4 6.8Pool water volume flow rate m³/h 0.8 1.4 1.4 1.4 1.4 3.6water side pressure loss kPa 6.6 19.0 5.3 5.3 5.3 14.5Rated compressor input for recirc mode 9 kW 1.3 1.7 1.8 2.3 3.0 4.6
ConnectionsPHW connection DN 32 32 32 32 32 32PHW control valve connection DN 15 15 15 20 15 25Clean water heater connection DN 15 15 15 15 15 15Condensate drainage DN 40 40 40 40 40 40Floor drain DN 20 | 40 20 | 40 20 | 40 20 | 40 20 | 40 20 | 40PWC connection 10 DN 25 25 25 25 25 40
Specifications of technical data relate to the nominal flow rate and return air condition 30°C / 53.7% r.h., outside air condi-tion 8°C / 85% r.h., unless otherwise specified
1 incl. heating capacity of clean water heating system in OA operation2 dependent on configuration of measurement and control system/unit
3 at 250 Hz mid-band frequency4 with average filter contamination5 dehumidifying in recirc mode without PWC6 at water inlet temperature 10°C7 in recirc heating; FL = 70°C, SA 50°C8 heat emission full and proportional; when water enters 28°C9 dehumidifying in recirc mode with PWC
10 for units with pool water condensers
Arrange confirmation of technical data and specifications before start of planning.
Indoor swimming pool air conditioning | thermoCond 37
ThermoCond
public
![Page 5: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/5.jpg)
Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com 25Technical Catalogue 01/2013 | Subject to technical modifications. © Menerga GmbH | www.menerga.com
Unit Type without pool water condenser 37 13 01 37 16 01 37 19 01 37 25 01 37 32 01 37 36 01 with pool water condenser 37 13 11 37 16 11 37 19 11 37 25 11 37 32 11 37 36 11Nominal flow rate m³/h 12,600 15,800 19,000 25,000 32,000 36,000
Dehumidification capacity according to VDI 2089 kg/h 82.4 103.3 124.2 163.4 209.2 235.3Dehumidification capacity in recirc mode kg/h 35.5 41.8 53.5 63.2 82.1 101.9Heating capacity of heat pump 1 COP 8.6 8.7 8.6 8.4 8.9 8.2Total electrical power rating 2 kW 15.8 19.3 23.3 33.0 40.9 47.8Current consumption2 A 41.9 55.6 66.8 83.0 107.5 133.5Operating voltage 3 / N / PE 400 V 50 HzExt. pressure lossesSupply and fresh air channel Pa 400 400 400 500 500 500Return and exhaust air channel Pa 400 400 400 500 500 500Sound power level 3
Supply air vent dB(A) 76 74 72 73 74 75RA connection dB(A) 73 74 75 77 78 78Outside air vent dB(A) 76 74 72 73 74 75EA connection dB(A) 71 72 73 75 76 76Acoustic pressure at a distance of 1 m from the device3 dB(A) 64 62 62 63 64 64
Fan unitsRated motor input for supply air 4 kW 5.57 7.05 8.19 11.99 15.01 16.58Rated motor input for return air 4 kW 4.97 6.11 7.25 10.88 14.17 15.42Rated motor input for supply air recirc mode 4 kW 3.49 4.42 5.38 7.76 10.05 10.79Rated motor input for return air recirc mode 4 kW 3.64 4.48 5.46 8.03 10.40 11.16SFP category supply air/return air recirc mode 1 | 2 1 | 2 1 | 2 1 | 3 3 | 3 2 | 3
Integrated heat pumpFilling volume of refrigerant type R407C (without PWC | with PWC) kg 12.0 | 18.0 12.0 | 27.0 18.0 | 31.0 18.0 | 40.0 28.0 | 50.0 35.0 | 50.0Rated compressor input for recirc mode 5 kW 5.8 6.7 8.7 10.4 13.4 17.2Heating capacity of heat pump for recirc mode 5 kW 40.2 47.9 60.6 72.5 94.6 114.3Rated compressor input for OA operation kW 5.3 6.1 7.9 10.1 11.7 15.8Heating capacity of heat pump for OA operation kW 41.0 48.3 61.6 75.6 94.2 117.1
Clean water heating 6
Heating capacity for OA operation kW 4.4 5.0 6.6 8.8 9.6 12.7Quantity of flow m³/h 0.38 0.41 0.55 0.68 0.82 0.98
PHWHeating capacity 7 kW 78.2 100.1 119.5 160.0 210.1 239.1
Water flow rate and pressure lossesPHW 7 m³/h|kPa 4.38 | 3.8 5.27 | 3.3 6.53 | 3.5 8.53 | 3.2 9.99 | 3.6 11.75 | 3.8PHW valve 7 m³/h|kPa 4.38 | 7.5 5.27 | 4.5 6.53 | 6.8 8.53 | 4.5 9.99 | 6.2 11.75 | 8.6
Pool water condenser 8
Heating capacity kW 37.9 46.5 58.6 70.0 91.1 109.9Spread of pool water temperature K 8.4 6.7 8.4 7.7 6.5 7.9Pool water volume flow rate m³/h 3.9 6.0 6.0 7.8 12.0 12.0water side pressure loss kPa 16.9 12.6 12.6 6.9 15.7 15.6Rated compressor input for recirc mode 9 kW 6.3 6.5 8.6 10.1 12.9 16.9
ConnectionsPHW connection DN 40 40 40 50 50 65PHW control valve connection DN 32 40 40 50 50 50Clean water heater connection DN 15 20 20 20 20 20Condensate drainage DN 40 40 40 40 40 40Floor drain DN 20 | 40 20 | 40 20 | 40 20 | 40 20 | 40 20 | 40PWC connection 10 DN 40 50 50 63 63 63
Specifications of technical data relate to the nominal flow rate and return air condition 30°C / 53.7% r.h., outside air condition 8°C / 85% r.h., unless otherwise specified
1 incl. heating capacity of clean water heating system in OA operation2 dependent on configuration of measurement and control system/unit
3 at 250 Hz mid-band frequency4 with average filter contamination5 dehumidifying in recirc mode without PWC6 at water inlet temperature 10°C7 in recirc heating; FL = 70°C, SA 50°C8 heat emission full and proportional; when water enters 28°C9 dehumidifying in recirc mode with PWC
10 for units with pool water condensers
Arrange confirmation of technical data and specifications before start of planning.
Indoor swimming pool air conditioning | thermoCond 37
Ther
moC
ond
publ
ic
![Page 6: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/6.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 29Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com28
ThermoCond
öffentlichTh
erm
oCon
d öf
fent
lich
Die Geräte der Serie 38 erreichen eine sehr hohe Energieeffizienz, da die integrierte Steuerung und Regelung nur den tatsächlichen Außenluftanteil beimischt, der zur Entfeuchtung der Schwimmhallenluft benötigt wird. ThermoCond 38 entfeuchtet ausschließ-lich mit Außenluft. Der konstruktive Aufbau stellt die Reinigbarkeit und
- Korrosionsfreier Gegenstrom-Platten- wärmeübertrager aus Polypropylen
- Pumpen-Warmwasser-Lufterhitzer- Filterung der Luft in jedem Betriebs-
zustand mit Filter in Ab-, Außen- und Zuluft
- Stetig geregelte Umluft-Heizen-Klappe- Integrierte frei programmierbare
Steuer- und Regeleinheit- Komplettgerät – beinhaltet alle
Bauteile zur Beheizung, Entfeuchtung und Lüftung der Schwimmhalle
- Intensive Qualitätsprüfung mit Werksprobelauf
- Vollständige Reinigung des Wärme-übertragers ohne Ausbau möglich
ThermoCond 38
Auf einen Blick:
LUFTVOLUMENSTROM: 2.600 - 50.000 m3/h
Rückwärmzahl über 95 % bei nur 115 Pa Druckverlust
Ausgelegt auf die Anforderungen der höchsten Energieeffizienz-klassen
WRG-Klasse H1 auch bei hohen Luftgeschwindigkeiten
Energiesparende EC-Ventilatoren / Menerga EcoWall
Optional: Frischwassererwärmer
Integrierte Abtaufunktion
Wärmebrückenfaktor kb = 0,78 - Klasse TB1
Zweistufige Zuluft-Filterung
Frei konfigurierbares RLT-Gerät
Lastabhängige Volumenstrom- anpassung
Erfüllt die Anforderungen der VDI 6022
Desinfektion nach VDI 6022 sicher. Der integrierte Gegenstrom-Plattenwärme-übertrager erreicht mit einem realen Gegenstromanteil von 80 % höchste Wärmerückgewinnungsgrade. Optional können die Geräte zur noch effizienteren Nutzung der in der Abluft enthaltenen Wärmeenergie mit einem Frischwasser-erwärmer ausgestattet werden.
Optionen:- Rekuperator in verkürzter Bauform- Schalldämpfer- Außenaufstellung- Fernwartung- und viele mehr
Klimagerät mit Gegenstrom-Plattenwärmeübertrager für mittlere und große öffentliche Schwimmhallen
Weitere Leistungsparameter und Optionen:
Wählt automatisch die wirtschaftlichste Betriebsweise!
Ther
moC
ond
38 1
3 01
- v
erei
nfac
hte
Dars
tellu
ng
AB
ZU
AU
FO
Badebetrieb Durch Beimischung von Außenluft zum Umluftvolumenstrom wird die Schwimm- halle entfeuchtet. Dazu wird der Umluft die aus hygienischen Gründen minimal notwendige Außenluftmenge (VDI 2089) beigemischt. Der Außenluftanteil ist abhängig von der aktuellen Wasserverdunstung (und somit der
Außenluft-FortluftbetriebMit steigender Außenluftfeuchte wird die Umluftklappe bedarfsgerecht stetig geschlossen. Bei hoher Außenluftfeuchte schließt die Klappe komplett, die Anlage
AbtaubetriebAlle rekuperativen Wärmeübertrager neigen dazu, bei niedrigen Außentem-peraturen im Fortluft-Bereich zu vereisen. Die integrierte Abtauschaltung beseitigt durch das Öffnen des Abluft-Fortluft-Bypasses einen vorhandenen
RuhebetriebIm Ruhebetrieb der Schwimmhalle ist die Wasserverdunstungsmenge geringer, die Anlage wird mit reduzierter Entfeuch-tungsleistung betrieben. Der Umluftanteil in diesem Betrieb wird maximiert. Aus Hygienegründen und zur Sicherstellung der Schadstoffabfuhr empfiehlt es sich einen geringen Außenluftanteil beizumi-schen, somit findet auch im Ruhebetrieb eine kontinuierliche Entfeuchtung der
Belegung der Schwimmhalle) sowie der Außenluftfeuchte. Er wird automatisch kontinuierlich angepasst. Ist die Wärme-rückgewinnung zur Erreichung der gewünschten Zulufttemperatur nicht ausreichend, wird die Zuluft im Pumpen-Warmwasser-Heizregister nacherwärmt.
arbeitet im reinen Außenluft-Fortluft-betrieb über den Gegenstrom-Platten-wärmeübertrager.
Eisansatz, die Abluft wird gezielt in den Bereich möglicher Vereisungen geleitet. Die Frischluftzufuhr wird im Abtaube-trieb nicht unterbrochen.
Richtlinie 1253/2014, zur freien Lüftung regelbar. Auf diese Weise kann durch die kühlere Außenluft eine Überhitzung des Gebäudes verzögert oder gar vermieden werden.
Bypass-BetriebDas Gerät ist mit einer Wärmeübertra-ger-Umgehung ausgestattet. Der Anteil der über den Wärmeübertrager und den Bypass geführten Luft ist bedarfsgerecht bis, konform der Anforderungen der ErP-
Schwimmhallenluft statt. Trotz ver-minderter Ventilatorleistung wird die Luftumwälzung in der Schwimmhalle ge-währleistet. Durch das Pumpen-Warm-wasser-Heizregister wird die Schwimm-halle bedarfsgerecht beheizt.
ThermoCond 38 ThermoCond 38
Ist mit unserem Eurovent-zertifizierten MB 50 Gehäuse
ausgestattet.
Funktions-beschreibung
AU
FO
AB
ZU
AU
FO
AB
ZU
AU
FO
AB
ZU
Ther
moC
ond
öffe
ntlic
h
AU
FO
AB
ZU
![Page 7: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/7.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 31Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com30
ThermoCond
öffentlichTh
erm
oCon
d öf
fent
lich
ThermoCond Typ 38 Gerätemaße und Gewichte
Gerätetyp L1 B2 H3 L11 L21 L31 B1 B2 H1 H2 Gewicht1
38 03 01 4.810 790 1.700 1.240 2.970 600 580 510 1.520 580 1.220 38 05 01 4.970 1.110 1.700 1.400 2.970 600 900 830 1.520 580 1.500 38 06 01 5.610 790 2.340 1.400 3.610 600 580 420 2.160 900 1.650 38 10 01 5.610 1.110 2.340 1.400 3.610 600 900 740 2.160 900 1.900 38 13 01 5.770 1.430 2.340 1.560 3.610 600 1.220 1.060 2.160 900 2.350 38 16 01 5.770 1.750 2.340 1.560 3.610 600 1.540 1.380 2.160 900 2.650 38 19 01 5.770 2.070 2.340 1.560 3.610 600 1.860 1.700 2.160 900 3.000 38 25 01 6.250 2.070 2.980 1.560 4.090 600 1.860 1.700 2.800 1.220 3.900 38 29 01 6.250 2.390 2.980 1.560 4.090 600 2.180 2.020 2.800 1.220 4.300 38 37 01 6.250 3.030 2.980 1.560 4.090 600 2.820 2.660 2.800 1.220 5.700
Gerätetyp L1 B H3 Gewicht1
38 03 01 2.970 790 1.700 660 38 05 01 2.970 1.110 1.700 810 38 06 01 3.610 790 2.340 930 38 10 01 3.610 1.110 2.340 1.110 38 13 01 3.610 1.430 2.340 1.300 38 16 01 3.610 1.750 2.340 1.500 38 19 01 3.610 2.070 2.340 1.720 38 25 01 4.090 2.070 2.980 2.330 38 29 01 4.090 2.390 2.980 2.600 38 37 01 4.090 1.515 2.980 1.750
Größte Transporteinheit
Achtung!Bei einer parallel betriebenen Anla-ge muss der Zuluft- und Abluftka-nal zusammen geführt werden.
Bei parallel betriebenen Geräten je Gerät ein Schaltschrank.
Spiegelbildliche Bauart möglich. * Bodenablauf
** Kondensatablauf
Gerätetyp H x B x T1 Position am Gerät
38 03 01 1.120 x 640 x 210 ZU/AB Seite
38 05 01 1.120 x 640 x 210 ZU/AB Seite
38 06 01 1.120 x 640 x 210 ZU/AB Seite
38 10 01 1.120 x 640 x 210 ZU/AB Seite
38 13 01 1.120 x 640 x 210 ZU/AB Seite
38 16 01 1.120 x 640 x 210 ZU/AB Seite
38 19 01 1.120 x 640 x 210 ZU/AB Seite
38 25 01 1.280 x 640 x 210 ZU/AB Seite
38 29 01 1.280 x 640 x 210 ZU/AB Seite
38 37 01 1.280 x 640 x 210 ZU/AB Seite
Schaltschrank
Für Servicearbeiten wird vor der Bedienungsseite des Gerätes ein Abstand entsprechend Maß B benötigt. Ist das Maß B kleiner als ein Meter, berücksichtigen Sie bitte einen Meter. Für Servicearbeiten oberhalb des Gerätes bitte 50 mm Arbeitshöhe ab Kabelkanal be-rücksichtigen. Für Servicearbeiten wird bei Gerätetyp 38 37 01 rückseitig ein Abstand von mindestens 1.500 mm benötigt.
Bei den Abmessungen bitte Körpermaß, Luftkanalanschlüsse und Elektroschaltschrank beachten.
Alle Längenmaße in mm, Gewicht in kg,Gewicht inkl. Schaltschrank.
1 Verändert sich in Abhängigkeit gewählter Optionen,
z.B. Rekuperator in verkürzter Bauform (- 960 mm) etc.
2 Beschläge erhöhen Gerätebreite pro Bedienseite um 65 mm
3 inkl. 120 mm Sockelrahmen, inkl. 60 mm Kabelkanal
Bis 38 29 01 drei Transporteinhei-ten einschließlich Schaltschrank, 38 37 01 vier Transporteinheiten einschließlich Schaltschrank. Weitere Teilungen für kleinere Montageeinheiten möglich (Zusatzauftrag erforderlich!).
HH1H2
H2
B1
B
B1L1 L2
L
L3
H2H2
10 B2
105
105
105 105105
PWW
-Ans
chlu
ss
** ***
AB
ZU
AU
FO
Gerätetyp 38 03 01 38 05 01 38 06 01 38 10 01 38 13 01 38 16 01 38 19 01 38 25 01 38 29 01 38 37 01Optimaler Volumenstrom m³/h 3.100 4.600 4.600 6.800 9.200 11.200 13.200 17.600 20.500 26.000Max. Volumenstrom 1 m³/h 3.500 5.300 5.600 7.900 10.500 13.000 15.500 21.500 25.000 32.000
Wärmerückgewinnungsgrad 2 % 96,9 96,9 98,0 98,0 98,0 98,0 98,0 98,0 98,0 98,0Wärmerückgewinnungsgrad nach EN 308 % 75,1 75,1 77,3 77,3 77,1 77,4 77,5 79,5 79,5 79,4Entfeuchtungsleistung n. VDI 2089 bei Vopt kg/h 18,9 28,1 28,1 41,5 56,2 68,4 80,6 107,5 197,9 158,8Entfeuchtungsleistung n. VDI 2089 bei Vmax kg/h 21,3 32,4 34,2 48,2 64,1 79,4 94,6 131,3 241,3 195,4Elektr. Gesamtaufnahmeleistung 3 kW 1,98 2,70 2,77 4,04 5,24 6,39 8,60 11,76 15,22 19,44Max. Stromaufnahme 3 A 6,0 7,5 7,5 9,7 12,8 12,8 16,7 26,2 30,8 39,3Betriebsspannung 3 / N / PE 400 V 50 Hz
Ext. Druckverluste Zu- und Außenluftkanal Pa 300 300 300 300 300 300 400 400 500 500Ab- und Fortluftkanal Pa 300 300 300 300 300 300 400 400 500 500
Schallleistungspegel Schallleistung in 1 m Abstand vom Gerät 4 dB(A) 53 52 52 55 55 55 61 62 61 64
VentilatoreinheitenMotor-Aufnahmeleistung Zuluft 100% 5 kW 1,15 1,54 1,58 2,3 2,95 3,6 2x 2,37 2x 3,31 2x 4,16 3x 3,53
Motor-Aufnahmeleistung Zuluft 60% 5 kW 0,48 0,59 0,57 0,85 1,16 1,68 2x 1,35 2x 1,19 2x 1,50 3x 1,23Motor-Aufnahmeleistung Abluft 100% 5 kW 0,83 1,16 1,19 1,74 2,29 2,79 3,86 2x 2,57 2x 3,45 3x 2,95Motor-Aufnahmeleistung Abluft 60% 5 kW 0,32 0,44 0,5 0,58 0,8 1,24 2,02 2x 0,88 2x 1,13 3x 0,94SFP-Kategorie Zuluft | Abluft (60% Vopt) 1 | 1 1 | 1 1 | 1 1 | 1 1 | 1 1 | 1 1 | 2 1 | 1 1 | 1 1 | 1Nennleistung Zuluft | Abluft kW 1,9 | 1,9 1,9 | 2,9 1,9 | 2,9 3,35 | 2,9 5 | 3,3 5 | 3,3 2x 3 | 5 2x 5 | 2x 3 2x 5 | 2x5 3x 5 | 3x 3,3
Effizienzklassen nach EN 13053:2012Wärmerückgewinnungsklasse H1 H1 H1 H1 H1 H1 H1 H1 H1 H1Leistungsaufnahme Ventilatormotoren ZU|AB P1 | P1 P1 | P1 P1 | P1 P1 | P1 P1 | P1 P1 | P1 P1 | P1 P1 | P1 P1 | P1 P1 | P1Luftgeschwindigkeitsklasse V2 V2 V2 V2 V2 V2 V2 V2 V2 V2
Filterung nach ISO 16890Zuluft | Außenluft ISO ePM1 55 % (F7) | ISO ePM10 60 % (M5)Abluft ISO ePM10 60 % (M5)
PWWHeizleistung max. 6 kW 19,9 29,6 29,4 43,5 36,6 71,9 60,5 112,5 130,7 165,5
Wassermengen und DruckverlustePWW m³/h | kPa 1,01 | 3,7 2,12 | 6,6 2,21 | 9,8 2,31 | 4,0 2,13 | 2,9 4,05 | 5,5 2,65 | 5,8 5,86 | 3,5 6,59 | 4,1 7,47 | 6,4PWW-Ventil m³/h | kPa 1,01 | 4,1 2,14 | 7,2 2,22 | 12,4 2,23 | 5,3 1,60 | 4,0 4,08 | 6,5 2,65 | 7,0 5,17 | 3,5 5,71 | 4,4 6,65 | 8,9
Frischwassererwärmer (optional)Leistung 7 kW 1,46 2,52 2,40 3,57 5,03 6,44 7,64 9,87 11,51 14,52Frischwasservolumenstrom m³/h 0,07 0,124 0,122 0,176 0,253 0,328 0,384 0,509 0,584 0,754
AnschlüssePWW-Anschluss DN 32 32 32 32 40 40 40 50 65 65PWW-Regelventil-Anschluss DN 15 20 20 25 25 32 32 40 40 40Kondensatablauf DN 40 40 40 40 40 40 40 40 40 40Bodenablauf DN 20 20 20 20 20 20 20 20 20 20Frischwassererwärmer (optional) DN 15 15 15 15 15 15 15 15 15 15
Angabe der technischen Daten bezieht sich auf optimalen Volumenstrom und Abluftkondition 30° C / 54 % r.F., Au-ßenluftkondition 15° C / 84 % r.F. und Normdichte (1,204 kg/m³), wenn nicht anders angegeben.
1 Bezogen auf Abluftkondition; Erfordert ggf. Änderung der technischen Ausstattung
2 bei AB = 30° C / 54% r.F.; AU = -12° C / 90% r.F.; 1/3 AU Anteil3 abhängig von Konfiguration MSR-Technik/Gerät4 bei 250 Hz Mittenfrequenz5 bei mittlerer Filterverschmutzung6 VL = 70° C; ZU ≈ 50° C7 Wassereintrittstemperatur = 10° C, Wasseraustrittstemperatur ≈ 28° C
Technische Daten und Angaben vor Planungsbeginn bestätigen lassen.
Technische Daten und Leistungen
ThermoCond 38 ThermoCond 38
Ther
moC
ond
öffe
ntlic
h
![Page 8: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/8.jpg)
AquaCond 44Wärmerück ge winnung aus Abwasser
Drysolair 11Energiesparende Lufttrocknung
Frecolair 14Freie Kühlung für thermisch hoch belastete Räume
Adcoolair 75Green IT
Hybritemp 97/98Kompakt-Kaltwasser sätze für Prozess- und Klimakälte
Resolair 62/64/66/68/65Regenerative Wärmerückgewinnung
Adconair 76Wärmerückgewinnung im Gegenstrom
ThermoCond 19/23/29Behaglichkeit durch intelligente Schwimmbadtechnik
Ther
moC
ond
priv
at
ThermoCond 38/39 Gutes Klima für öffentlicheSchwimmhallen
Ther
moC
ond
öffe
ntlic
hDr
ysol
air
Frec
olai
rAd
cool
air
Aqua
Cond
Trisolair 52/59Dreifach rekupe ra tive Wärmerück gewinnung Tr
isol
air
Adsolair 56/58Kühlen ohne Strom
Adso
lair
Reso
lair
Adco
nair
Liebe Kunden und Partner,
wir nicht nur tagtäglich seit 1980, wir definieren durch ständige Weiterent-wicklung auch immer wieder den Stand der Technik neu. Lernen Sie ein beson-deres Unternehmen mit einer besonde-ren Technik kennen, und schaffen Sie mit uns gemeinsam gutes Klima – wir freuen uns darauf!
Wir freuen uns, Ihnen mit diesem Katalog ein Beispiel möglicher Anlagen-konfigurationen aus unserem Portfolio zu präsentieren. Lernen Sie die Leis-tungspalette und die Energiephilosophie von Menerga kennen! Unsere Philoso-phie „Wir schaffen gutes Klima – durch Minimale ENERGie Anwendung“ realisieren
Zubehör SchlitzschienenFür private und öffentliche Schwimmhallen
Hybr
item
p
Seite 19
Seite 28
Seite 78
Seite 91
Seite 95
Seite 86
Seite 82
Seite 41
Seite 54
Seite 46
Seite 70
Seite 38
Unsere Philosophie heißt „Minimale ENERGie Anwendung“. Seit 1980.
Jede Innovation beginnt mit einer Vision.
1980Gründung der Menerga Start mit den Serien ThermoCond (intelligente Schwimmbadtechnik) und AquaCond
(Wärmerückgewinnung aus Abwasser)
1983 Automatische Wärmeübertragerreinigung für Serie AquaCond
1985 Start der Serie Resolair, regenerative Wärme- rückgewinnung mit über 90% Wirkungsgrad
1987 Markteinführung Serie Drysolair (energie sparende Lufttrocknung)
1988 Austausch rekuperativer Aluminium- Wärmeübertrager durch eigenentwickelte Polypropylen Wärmeübertrager
1991 Markteinführung der Serien Dosolair (zweifache
rekuperative Energierückgewinnung) und Ad solair (Kühlen ohne Strom durch adiabate
Verdunstungskühlung)
1996 Markteinführung Serie Trisolair (dreifache
rekuperative Energierückgewinnung)
1999 Start des hybriden Kompakt-Kaltwassersatzes
Hybritemp
2000 Menerga Designer: vollständige Aus legung von
Klimasystemen über eigenentwickelte Software als Cloud-Lösung
2003 Solare sorptionsgestützte Klimatisierung, erste Pilotanlagen
2004 Markteinführung energie effizienter Verdichter mit integrierter Leistungsregelung
2007 Neue Generation einer webfähigen Steuerung
und Regelung von Lüftungs- und Klimasystemen
2008 Einführung Fernbedienung für ThermoCond 29
mittels Smartphone
2009 Markteinführung Sorpsolair (sorptionsgestützte
Klimatisierung – mit der Sonne kühlen)
2011 Markteinführung Serie Adcoolair (Green IT) für thermisch hoch belastete Räume
2012 Markteinführung Adconair 76 und ThermoCond
38 mit Gegenstrom-Plattenwärmeübertrager. Markteinführung Polyproylen Regeneratoren für
die Geräteserie Resolair
2013 Menerga wird Teil der Systemair Group. Markteinführung Frischwassererwärmer ohne Energie aus einem Heiz- oder Wärme- pumpenkreislauf für ThermoCond 38
2014 Markteinführung Adiabatik für Adconair 76
2016 Markteinführung von Austauschgeräten für
ThermoCond 22 und ThermoCond 33
2017 Markteinführung der hybriden Verdunstungsküh-
lung AdiabaticzeroGWP (Kombination aus Taupunkt-kühlung und indirekter adiabate Verdunstngsküh-lung) und der thermisch angetriebenen AdiabaticDXcarbonfree (mit integriertem, geschlos-senem Adsorptionskältekreislauf) für Adconair 76
2019 Markteinführung der elektrisch angetriebenen
AdiabaticDXcarbonfree (integrierter Turbokompressor mit R718 als Kältemittel) für Adconair 76
ZUSATZINFORMATIONENInnovationsübersicht 2
Menerga Philosophie 4
Zertifikate 6
Einsatzbereiche 8
Technikdetails 9
Baukastensystem 10
Speziallösungen 11
Gerätegehäuse MB 50 12
Qualitätsversprechen 14
Innen- und Außengeräte 16
Technischer Service 17
Mini-Glossar 100
Anlagenausstattungen 101
Geräteoptionen 102
Referenzen 104
Geräteschlüssel 109
Zube
hör
![Page 9: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/9.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 5Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com4
Wir liefern individuell auf Ihren Bedarf abgestimmte Klimasysteme. Unsere Philosophie „Wir schaffen gutes Klima – durch Minimale ENERGie Anwendung“ realisieren wir tagtäglich, seit der Unternehmensgründung in 1980. Wir sind stolz darauf, seit 2013 Teil der international erfolgreichen Systemair-Gruppe zu sein.
Unsere Anlagen sind Ergebnis hochwertiger, intelligenter Ingenieurs- und Handwerks-arbeit. Sie sind über viele Jahre zuverläs-
sig im Einsatz und minimieren deutlich die Betriebskosten. Warum das? Weil wir schon in der Grundkonzeption alle Komponenten zur Klimatisierung wie Lüftung, Heizung oder Kälteanlage integrieren und alles mit einer intelligen-ten Steuerung und Regelung ausstatten. Jede Anlage wird vor Auslieferung im Werksprobelauf komplett geprüft. Die Lieferung der kompakten Geräte erfolgt anschlussfertig, sie werden bei Ihnen auf der Baustelle mit wenigen Handgriffen angeschlossen und in Betrieb genommen.
Über MenergaMinimale Energie Anwendung
Weise haben wir zusammen mit Partnern unzählige Projekte realisiert, von denen eine Vielzahl Auszeichnungen für ihre Energieeffizienz erhalten haben. Darauf sind wir stolz. Doch was uns wirklich daran gefällt, ist das Wissen um gemeinsam entwickelte Lösungen, mit denen Betreiber und Investoren bares Geld einsparen – Tag für Tag, Monat für Monat und Jahr für Jahr. Die Investitions-kosten amortisieren sich innerhalb kurzer Zeit!
Wir stellen Ihnen gerne Referenzlisten für die Gebäudetypen zusammen, die für Sie von Interesse sind. Und für den Fall, dass Sie uns mit einem vollkommen neuen Projekt überraschen: Wir finden für jede Anforderung die passende Lösung! Mit geschärftem Blick durch unzählige Sonderprojekte – wie zum Beispiel das Teleskopfeld „ALMA“ in der Atacama-Wüste oder die Polarstation „Princess Elisabeth Station“ am Südpol – nehmen wir jede neue Herausforderung gerne an.
Mit über 40.000 weltweit installierten Anlagen decken wir nahezu jeden Einsatzbereich ab. Wir verkaufen nicht nur die Geräte, sondern bieten Ihnen unsere jahrelange Erfahrung an. Bei der Suche nach der besten Lösung analysieren wir gemeinsam mit Ihnen die spezifischen Gegebenheiten vor Ort. Und wir stellen viele Fragen - für die optimale Lösung. Kann vielleicht noch eine alternative Energiequelle genutzt werden, um die Betriebskos-ten weiter zu reduzieren? Auf diese
Überzeugende Argumente für Menerga
Intelligente Technik =
dauerhaft niedrige Betriebskosten
Nutzung regenerativer Energien
Sehr kompakte Bauweise
Integrierte Steuerung und Regelung
Intensive Prüfung vor Auslieferung
Anschlussfertige Lieferung
Hervorragende Wartungskonzepte
![Page 10: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/10.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 7Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com6
Selbstverständlich verfügen wir über alle gängigen weiteren Zertifikate wie TÜV-Baumusterprüfungen, Hygiene-zertifikate, ISO 9001 und mehr.
Bitte sprechen Sie uns an – wir senden Ihnen eine Übersicht oder Kopien der gewünschten Zertifikate gerne zu.
Weitere
Verbände und RichtlinienMenerga ist aktiv und zertifiziert!
Die Mehrheit unserer Lüftungsgeräte ist standardmäßig Eurovent-zertifiziert. Hierzu gehören alle Anlagen, die mit unserem Menerga Air Gehäuse „MB 50“ mit 50 mm Paneelen ausgestattet sind.
Eurovent
IHR VORTEIL!Höhere Effizienz
= geringere Betriebskosten
Die kompletten Resolair 64 und Adconair 76 Serien sind offizielle Passivhaus-zertifizierte Komponenten und somit ideal für den Einsatz in Passivhäusern und allen anderen Niedrigenergiegebäu-den geeignet.
Passivhaus-Instititut
Unser neues Gehäuse für mittlere und große Anlagen glänzt nun mit einer ebenen Innenkonstruktion und verdient das Prädikat „hygienisch top“! Eine Wärmedämmschale aus Spezialkunst-stoff erhöht den Wärmebrückenfaktor des Rahmens auf die beste Klasse TB1. Filtertüren sind mit leicht zu handhaben-den, abschließbaren Griffen ausgestattet.
1/2EUROVENT CERTITA CERTIFICATION SAS au capital de 100 000 € - 48-50 rue de la Victoire 75009 Paris - FRANCE
Tel. : 33 (0)1 75 44 71 71 - 513 133 637 RCS Paris - SIRET 513 133 637 000 35 - TVA FR 59513133637S06 D06 TEMPLATE_ECP_RANGE_REV1.0
CERTIFICATE N° 14.11.003
Air Handling Unit / Centrales de traitement d'air
Range Name / Nom de Gamme :Menerga Air
Granted on November 26, 2014 - Date 1ère admission 26 novembre 2014
This document is valid at the date of issue - Check the current validity on:Document valable à la date d’émission - Vérifier la validité en cours sur :
www.eurovent-cert i f icat ion.com
Participant/Titulaire
MENERGA GmbHAlexanderstrasse 69
45472 Mülheim an der Ruhr, Germany
This certificate is issued by Eurovent Certita Certification according to the certification rules:
ECP AHU - « Air Handling Unit » in force at established date.
Pursuant to the decision notified by Eurovent Certita Certification, the right to use the mark ECP shall be granted to the beneficiary company for the above Range in the conditions defined by the certification program mentioned.
Unless withdrawn or suspended, this certificate remains valid as long as the requirements for the certification program framework are met. The validity of the certificate is to be verified on www.eurovent-certification.com
THIS CERTIFICATE HAS BEEN ISSUED ON 14/06/2019THIS CERTIFICATE IS VALID UNTIL 30/06/2020
Ce certificat est délivré par Eurovent Certita Certification dans les conditions fixées par le référentiel :
ECP AHU – « Centrales de traitement d'air » en vigueur à date d’édition.
En vertu de la décision notifiée par Eurovent Certita Certification, le droit d'usage de la marque ECP, est accordé à la société qui en est bénéficiaire pour la gamme visée ci-dessus, dans les conditions définies par le programme de certification mentionné.
Sauf retrait ou suspension, ce certificat demeure valide tant que les conditions du référentiel du programme de certification sont respectées. La validité du certificat est à vérifier sur le site Internet www.eurovent-certification.com
CE CERTIFICAT A ÉTÉ EMIS LE 14/06/2019CE CERTIFICAT EST VALIDE JUSQU’AU 30/06/2020
Paris, 14 juin 2019
MANAGING BOARD MEMBER / MEMBRE DIRECTOIRE
Organisme accrédité n° 5-0517 Certification Produits et Services selon la norme NF EN ISO/CEI 17065:2012 Portée disponible sur www.cofrac.fr
Accreditation #5-0517 Products and Services Certification according to NF EN ISO/CEI 17065:2012 –Scope available on www.cofrac.fr
COFRAC est signataire des accords MLA d’EA et MLA d’IAF, COFRAC is signatory of EA MLA and IAF MLA, list of EA members is available on www.european-accreditation.org/ea-memberslist of IAF members is available on www.iaf.nu//articles/IAF_MEMBERS_SIGNATORIES/4
Menerga beteiligt sich am Eurovent Certified Performance Programm für die Serie Menerga Air. Prüfen Sie die Gültigkeit des Zertifikates: www.eurovent-certification.com oder www.certiflash.com
Die ATEX-Direktive umfasst aktuell zwei Richtlinien auf dem Gebiet des Explosi-onsschutzes, die ATEX-Produktrichtlinie 2014/34/EU und die ATEX-Betriebsricht-linie 1999/92/EG. Menerga fertigt auf Wunsch Geräte gemäß ATEX für explosi-onsgefährdete Bereiche.
ATEX
Menerga ist Mitglied im Hersteller-verband Raumlufttechnische Geräte e.V. Ziel des Verbandes ist die Entwicklung raumlufttechnischer Geräte auf höchs-tem technischen Niveau sowie aktive Normungsarbeit und die Entwicklung technischer Empfehlungen.
Herstellerverband Raumlufttechnische Geräte e.V.
Mit Inkrafttreten der Verordnung (EU) Nr. 1253/2014 im Dezember 2014 wurden zur Umsetzung der Ökodesign-Richtlinie 2009/125/EG die Anforderun-gen an die umweltgerechte Gestaltung von Lüftungsanlagen festgelegt. Neben grundsätzlichen Anforderungen an den Aufbau der Lüftungsanlagen wurden in zwei Stufen ab 01.01.2016 bzw. 2018 Mindestwerte an die Effizienz des
eingesetzten Wärmerückgewinnungs-systems sowie maximal zulässige Leistungsaufnahmen der Ventilatoren definiert, um den Energieverbrauch der Lüftungsanlagen in der Betriebsphase zu reduzieren. Ziel der Ökodesign-Anfor-derungen an Lüftungsanlagen ist die Erhöhung der Primärenergieeinsparung dieser Produktgruppe im Jahr 2025 um 60 % gegenüber dem Stand von 2010.
Auf die Einführung der Ökodesign-Richtlinie ist Menerga dank der konsequenten Ausrichtung auf Energie-effizienz seit der Firmengründung vorbereitet. Unsere Geräte erfüllen die Anforderungen, die gemäß Ökodesign-Richtlinie zum 1. Januar 2018 in Kraft getreten sind. Mit uns können Sie zukunftssicher planen!
![Page 11: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/11.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 9Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com8
2
1
9
1 Qualität: Menerga Anlagen werden in Deutschland entwickelt und sind auf höchste Qualität ausgelegt.
2 Profile und Rahmen: die Geräte-konstruktion basiert auf einem langlebigen, robusten Aluminium-Stahlrahmengerüst. Gehäusekonstruktionen sind bis zur Wärmebrückenklasse TB1 lieferbar.
3 Steuerung und Regelung: unsere Anlagen werden anschlussfertig geliefert. Die intelligente Steuerung und Regelung garantiert, dass die Anlage jederzeit im Optimum arbeitet.
4 Filter: alle RLT-Anlagen sind zum Schutz von Mensch und Technik mit einer optimalen Filterung ausgestattet.
5 Heiz- oder Kühlregister: zur Deckung des Transmissionswärme- oder -kühlbedarfs.
6 Ventilatoren: energieeffiziente EC-Ventilator-Motor-Einheiten.
7 Indirekte adiabate Verdunstungskühlung: zur Kühlung setzen wir, wenn möglich, naturbasierte Verfahren wie das Kühlen mit Wasser ein.
8 Wärmeübertrager: wir verwenden, ohne Verschlechterung des Wirkungs-grades, Polypropylen statt Aluminium und minimieren so das Anlagengewicht sowie den CO2-Ausstoß bei der Produktion.
9 Tropfenabscheider: leistungsfähige Tropfenabscheider eliminieren zuverlässig Aerosole aus der Luft und verhindern den Eintrag von Feuchtigkeit in Luftkanäle.
10 Luftklappensysteme: zur exakten Verteilung der Luftströme.
11 Luftführung: intelligente Bypass-konzeptionen für ganzjährig effizienten Betrieb.
12 Kompressionskälteanlage/ Wärmepumpe: entspricht den Vorschriften der DIN EN 378 und ist baumusterge-prüft gemäß Druckgeräterichtlinie. Eine Einzelabnahme ist nicht mehr notwendig.
5
8
11
7
10
Einblick:Technik im Detail
6
3
12
4
KernkompetenzenUnsere Einsatzbereiche
SONDERLÖSUNGEN
Privatbäder, öffentliche Schwimmhallen, Erlebnisbäder, Sportbecken, Solebäder, Hotelbäder, Schulschwimmhallen, Therapiebäder und viele mehr. Zusätzlich: Wärmerückgewinnung aus Abwasser.Die Klimatisierung von Schwimmhallen zählt zu den anspruchsvollsten Segmenten der Klimatisierung. Hier sind wir in 1980 gestartet, hier sind wir groß geworden und hier sind wir Markt- und Innovationsführer. Unsere besondere Kompetenz: Höchste Wärmerückgewinnungsgrade senken Betriebskosten, robuste Anlagenkonstruktionen überdauern widrigste Verhältnisse.
KOMFORTKLIMATISIERUNGNiedrigenergiegebäude, Büros, Museen, Sportstätten, Schulen, Kliniken, Hotels, Banken, historische Gebäude und viele mehr.Bei der Komfortklimatisierung steht der Mensch im Mittelpunkt. Unsere Technik basiert auf den jeweiligen Anforderungen eines Projektes, sucht aber gleichzeitig immer den effizientesten Weg mit minimaler Energieanwendung. So kühlen wir beispielsweise mit Wasser, um elektrische Energie zu sparen, oder setzen auf sorptionsgestütze Klimatisie-rung, mit der Sie mit Wärme, z.B. aus Solarthermie oder aus Prozessabwärme, ent-feuchten können. Es ist sogar möglich, überschüssige Solarwärme für Entfeuchtungs-aufgaben zeitlich unbegrenzt verlustlos zu speichern.
PROZESSKLIMATISIERUNG UND KALTWASSERKlimatisierung von Rechenzentren, Industrietrocknung, Prozesskühlung, Lagerkonditionierung, Kaltwassererzeugung und vieles mehr. Zusätzlich: Wärmerückgewinnung aus Abwasser.Die Prozessklimatisierung muss sicherstellen, dass in einer definierten Situation präzise festgelegte Luftkonditionen herrschen. Menerga Anlagen garantieren die zuverlässige Trocknung, Kühlung und Erwärmung. Im Bereich Kaltwasser stellen unsere Anlagen zuverlässig die gewünschten Wasserbedingungen zur Verfügung. Auch in diesem Segment steht das Einsparen von Energie durch Einsatz intelligenter Technik an erster Stelle.
SONDERLÖSUNGENForschungsprojekte, SpezialanwendungenHerausforderungen und ungewöhnliche Projekte sind die Meilensteine der Menerga-Firmenhistorie. Schon seit Firmengründung haben wir Lösungen kundenindividuell konzipiert. Wir wagen uns gerne an herausfordernde Projekte – wir wissen, dass eben diese Projekte wertvolle Erfahrungen bringen und dauerhaft die Qualität unserer „Standard“-Anlagen verbessern.
© S
tadt
Rije
ka©
pol
arfo
unda
tion.
org
SCHWIMMHALLENKLIMATISIERUNG
![Page 12: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/12.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 11Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com10
Immer die richtige LösungBaukastensystem mit Intelligenz
Nach knapp 40 Jahren Erfahrung in der Klimatisierung und mit über 40.000 installierten Anlagen weltweit haben wir viel gelernt. Wir haben unsere Geräte-serien auf die Bedürfnisse der Projekte angepasst. Entstanden ist dabei ein sehr intelligentes Baukastensystem, mit dem Sie ihre Anlage individuell auf Ihr Projekt anpassen lassen können.
Mit der Geräteserie wählen Sie die grundsätzliche Ausrichtung der Klimatisierung. Anlagen der Serien Adconair können beispielsweise mit adiabater Verdunstungskühlung ausge-stattet werden. Wenn Sie Kaltwasser zur Prozesskühlung benötigen, sind Sie bei der Serie Hybritemp richtig. Und im Schwimmbad schaffen ThermoCond Anlagen gutes Klima.
Nach der Grundauswahl der Serie kön-nen Sie jedes Gerät auf Ihre individuellen Anforderungen anpassen. So sind z.B. Luftanschlussstutzenpositionen wählbar, oder die Position des Schaltschrankes.In diesem Schritt wird das Gerät schon speziell auf die Anforderungen des Technikraumes und auf die speziellen Gegebenheiten vor Ort angepasst.
Und es geht natürlich noch mehr. So können bei Anlagen mit Heizregister die Anzahl der Rohrreihen und somit die Heizleistung variiert werden. Oder Sie wählen je nach Einsatzzweck andere Fil-tergüteklassen. Zusätzliche Gerätekom-ponenten können integriert werden und weitere Anpassungen können erfolgen.
Bei Spezialanforderungen sind wir ProfisWenn nötig, bauen wir auch rund Wir finden für jedes Projekt die perfekte Lösung. Und wenn die Anforderungen einmal zu speziell werden, werden eben auch unsere Anlagen spezieller. Wir sind Profis bei hochspezialisierten Anlagen und passen unsere Geräte schneller als jeder andere an Sonderanforderungen an. Ein Beispiel hierfür ist die weltbe-rühmte Anna Amalia Bibliothek in Weimar, ein Weltkulturerbe der UNESCO. Die Klimatisierung des historisch ein-maligen Buchbestandes erfolgt mit Menerga Anlagen. Eines der Resolair-Geräte wurde im Kellergewölbe unter-halb des Bücherturmes installiert. Der rund 15 Meter hohe, runde Turm mit einer hölzernen Wendeltreppe ist eines der architektonischen Highlights im Ensemble der Bibliothek. Das darunter liegende Kellergewölbe ist ebenfalls rund und nur durch einen engen Gang erreichbar. Die besondere Aufgaben-
stellung bestand darin, die Anlage sinnvoll in die Rundung des Kellers einzupassen. In Zusammenarbeit mit dem Installationsbetrieb wurde das in kompakte Transporteinheiten zerlegte Klimagerät durch eine enge Luke an der Rückseite des Turmes eingebracht und montiert. Die Besonderheit ist die halbrunde Anordnung der Anlage, die sicherlich einmalig ist.
Eine schöne Referenz für die Leistungs-fähigkeit von Menerga, aber nur ein Beispiel für die vielen Möglichkeiten. Wir sind in der Lage, schnell und flexibel auf Ihre ganz besonderen Wünsche und Gegebenheiten vor Ort einzugehen. Neben den vielen Wahlmöglichkeiten, die Sie bei unserer Produktpalette haben, entwickeln wir für Ihre speziellen Anforderungen auch vollkommen neue Gerätekonzepte. Wie beim Beispiel des
Freizeitbades Felsland Dahn. Hier sollte die Abwärme eines Blockheizkraftwer-kes sinnvoll genutzt werden – und so entwickelten unsere Ingenieure die erste sorptionsgestützte Schwimmbadent-feuchtung in Deutschland. Das Ergebnis: eine leistungsfähige, zuverlässige Anlage, die die Betriebskosten um ca. 40.000 Euro jährlich reduziert. Von diesen speziellen Systemen gibt es unzählige Beispiele, fragen Sie uns! Für Sie entwickeln und fertigen wir diese Spezialanlagen. Weil wir es können. Seit 1980.
Eine Übersicht der wichtigsten Optionen finden Sie auf den Seiten 102 - 103. Dass wir uns auch bei tiefgreifenden Variati-onen immer noch in unserer regulären
Produktpalette bewegen beweist Ihnen, dass wir von Grund auf die passenden Bausteine intelligent kombiniert haben.
1.
2.
3.
![Page 13: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/13.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 13Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com12
Messergebnisse nach DIN EN 1886
Gehäusefestigkeit D1 (M)
Luftdichtheit -400 Pa L1 (M)
Luftdichtheit +700 Pa L1 (M)
Filterbypassleckage F7 (M), optional F9 (M)
Wärmedurchgang T2
Wärmebrückenfaktor TB1
Eurovent 2014
WärmedämmschaleDie PUR-Wärmedämmschale reduziert Wärmeverluste und somit den Energie-aufwand. Das bedeutet: Bestmögliche Wärmebrückenfreiheit, nahezu keine Kondensation an der Außenseite des Gerätes.
Wärmebrückenfaktor TB1
GerätedeckelGerätedeckel als doppelschaliges Sandwichelement mit umlaufendem Rahmenprofil. Paneelstärke 50 mm. Innen- und Außenbleche verzinkt mit Polyesterbeschichtung. Korrosions-klasse III. Farbe RAL 2004 oder RAL 7035. Blechstärke 0,75 mm, wahlweise 1,5 mm. Schaugläser nach Erfordernis. Alle öffenbaren Gerätedeckel mit integrierter, austauschbarer Dichtung. Ab 1,3 m lichter Gerätehöhe Ausführung als Tür.
Höchste Dichtigkeit, Wärmedurchgang T2
Scharniere/VerschlüsseIn wartungrelevanten Bereichen auf der Bedienseite Einsatz von 180° 2D-Scharnieren mit Türverschluss. Türverschlüsse mit Klinkengriff, im Überdruckbereich zusätzlich mit Druck-entlastung bzw. Rückhaltesicherung gegen Aufschlagen. Die Türverschlüsse an Türen vor gefährlichen Komponenten sind abschließbar (Steckschlüssel).
Einfache Handhabung, höchste Sicherheit
DeckelverschlüsseAn den nicht wartungsrelevanten Bereichen auf der Bedienseite Sicherung der Deckel mit Kunststoff-Klemmver-schlüssen, die auf der Geräteaußenseite angebracht sind und die Gerätehülle nicht durchdringen. Zusätzliche Hand-griffe erleichtern das Handling.
Geringere Leckagen, einfache Handhabung
ProfilkonstruktionGehäuseprofilkonstruktion aus verzinktem Stahl garantiert höchste Stabilität.
Robuste, langlebige Konstruktion
Sockel Umlaufender Sockelrahmen aus verzinktem Stahl, Standardhöhe 120 mm. Andere Höhen ebenfalls lieferbar. Bei wetterfester Ausführung geschweißter Sockel in einem Stück oder wenigen Teilungen.
Extrem hohe Belastbarkeit
M-Profil mit Dämmschale
Om
ega-
Profi
l m
it Dä
mm
scha
le
Deckel
Deck
el
Deckel
50 mmAufbau des Gehäuses, Blick von oben:
Bezieht sich auf Ausführung Menerga Air. Prüfen Sie die Gültigkeit des Zertifikates: www.eurovent-certification.com oder www.certiflash.com
Einsatz des Gehäuses MB 50
Geräte-standard
Menerga Air
ThermoCond 19 -
ThermoCond 23 -
ThermoCond 29 -
ThermoCond 38
ThermoCond 39
Drysolair 11 -
Adcoolair 75 -
Trisolair 52/59 -
Adsolair 56/58
Resolair 62/66 -
Resolair 64/68
Adconair 76
Verwendet für alle Geräte der Menerga Air RangeGerätegehäuse MB 50
![Page 14: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/14.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 15Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com14
Busverbindung der Sensoren und Aktoren schaffen störungsfreie Verbindungen, sichere Messwerte und dank integrierter LEDs Licht in der Anlage.
Solides, wärmebrückenfreiesGehäuse mit Stahlrahmen, Wärme-dämmschale und bei Außenaufstel-lung mit wetterfestem Blechdach.
Indirekte adiabate Verdunstungskühlung im Wärme-übertrager. Hohlkegeldüsen gewährleisten eine hauchfeine, homogene Verteilung des Wassers in der Abluft.
Microchannel-Kondensatoren reduzieren die CO2-Emissionen durch um ⅔ reduziertes Kälte-mittelvolumen und um die Hälfte niedrigeren luftseitigen Druck-verlust.
Steuerung und Regelung sind seit jeher fester Bestandteil unserer Geräte und sichern einen optimalen Betrieb ausgelegt auf höchste Energieeffizienz.
Niveausonde mit integriertem Gyrosensor im Wasservorratstank der adiabaten Verdunstungskühlung, misst jederzeit präzise den Wasser-stand. Extrem wartungsarm.
CNC-gebogene Verrohrung im Bereich der Kompressionskälte-anlage. Das bedeutet deutlich weniger Lötstellen und somit weniger Schwachstellen.
Außenluftfühler mit integriertem GSM-Router überträgt Anlagenwerte per Funk und sichert die Verbindung in Echtzeit.
Extrem langlebige Wärmeübertrager, die in allen Bereichen luft- und wasserdicht sind. Wir verwenden korrosions-freies Polypropylen in erstklassiger Verarbeitung.
Ventilatorenverbünde mit Antriebsmotoren der Effizienz-klasse IE 4 für mehr Leistung und mehr Sicherheit, bei gleichzeitig sehr kompakten Anlagen.
Rekuperatorwannen, leicht zugängliche Wannen des adiabaten Kühlsystems erleichtern die Inspektion und gewährleisten eine restlose Entleerung zum Betriebsende.
Smartphone-Lösungen für Fernbedienung, Energie-monitoring oder weltweiteStörungsüberwachung.
Gerategehäuse MB 50 nach DIN 1886:Wärmedurchgang: T2Wärmebrückenfaktor: TB1 Mechanische Festigkeit: D1Dichtheitsklasse: L1Filterbypassklasse: bis F9
Ausgestrichener Boden in allen wasser-führenden Bereichen.
Seit 1980 „on the top“!Das Menerga Qualitätsversprechen
![Page 15: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/15.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 17Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com16
Experten zu Ihren DienstenTechnischer Service von MenergaExperten zu Ihren Diensten, zu jeder Zeit und an jedem Ort. Mit einem umfassen-den Serviceangebot und einem flächen-deckenden Servicenetz europaweit garantiert der Technische Service von Menerga vom Tag der Inbetriebnahme über den gesamten Lebenszyklus Ihrer Anlage die wirtschaftlichsten und vorteilhaftesten Serviceleistungen.
Mehr als 140 Service-Techniker an verschiedenen Servicestützpunkten und 60 Service-Mitarbeiter an den Menerga Standorten bieten einen professionellen Rund-Um-Service, mit dem Ziel einer hohen Verfügbarkeit der Anlagen und
einem Maximum an Effizienz. Das Leistungsspektrum des Technischen Service erstreckt sich vom Werksprobe-lauf und der Inbetriebnahme vor Ort über periodische Wartungen, Instandsetzun-gen, Fernwartungen und Ferndiagnose über direkte Einwahlmöglichkeiten bis hin zur Sanierung und Optimierung der Anlagen. Und das übrigens auch für Anlagen anderer Hersteller. Wir bieten Ihnen maßgeschneidert kunden- und anwendungsspezifisch das passende Servicekonzept. Im Falle eines Falles erreichen Sie uns rund um die Uhr unter folgender Telefonnummer: +49 208 9981-199
Innen- und AußengeräteImmer passend gerüstet
Außen- und Innengeräte sind ideal für den jeweiligen Einsatzzweck gerüstet. So wird z.B. bei Außengeräten gesichert, dass wasserführende Leitungen im Winter nicht einfrieren können. Ein geschweißter Sockel erhöht die Stabilität. Der direkt im Gerät angebrachte Reparaturschalter vereinfacht die Wartung, da direkt vor Ort Ventilatormotoren ausgeschaltet werden
können. Bei integrierter Steuerung und Regelung ist diese Funktion, die sonst der Installeteur vor Ort sicherstellen muss, bereits ab Werk im Gerät installiert.
Bei Innengeräten liegt der Fokus auf einer möglichst einfachen Einbringung der Anlage in den Technikraum. Je nach Platz-angebot und Größe des Gerätes wird der
Schaltschrank direkt am Gerät montiert oder kann zur Wandmontage vorgesehen werden.
Die finale Ausstattung Ihres Innen- oder Außengerätes bestimmen Sie. Wir beraten Sie dabei gerne.
Außenaufstellung Deckelfarbe entsprechend RAL 7035 lichtgrau
Stahlsockel verzinkt, geschweißt
Wetterfestes Gerätedach mit Abtropfkante
Anlieferung in kleinstmöglicher Anzahl
Transporteinheiten zur einfachen Aufstellung
Schaltschrank im Gebäude,
Klemmenkasten im Gerät
Kondensatablauf mit Begleitheizung
Lieferung komplett mit Reparaturschalter
im Gerät
Innenaufstellung Deckelfarbe entsprechend RAL 2004 Reinorange
Stahlsockel verzinkt, geschraubt, 120 mm
oder Gerätefüße
Anlieferung in kompakten
Transporteinheiten zur einfachen
Einbringung ins Gebäude
Schaltschrank am Gerät oder für
Wandmontage
Lieferung mit Haupt-/Reparaturschalter
am Schaltschrank
![Page 16: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/16.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 101Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com100
Mini-GlossarWärmerückgewinnungsgradNach VDI 2071 definiert als das Verhält-nis der Temperaturdifferenz zwischen Zuluft und Außenluft zur Temperaturdif-ferenz zwischen Abluft und Außenluft in einer Lüftungsanlage mit Wärmerück-gewinnung. Die Kennzahl beschreibt, welcher Anteil der theoretisch nutzbaren Energie aus der Abluft auf die Zuluft übertragen wird. Sensible und latente Wärme werden berücksichtigt. Angabe in %. Theoretisch sind Wärmerückgewin-nungsgrade über 100 % möglich.
………………………Temperaturwirkungsgrad = Rückwärmzahl = WärmebereitstellungsgradVerhältnis der übertragenen Temperatur im WRG-System zum Temperaturunter-schied der Eintrittsmedien. Die Kennzahl beschreibt wieviel Energie aus der Abluft zurückgewonnen und auf die Außenluft zur Erwärmung der Zuluft übertragen werden kann. Achtung: Abwärme der Ventilatoren wird berücksichtigt! Keine Beachtung des Energiegehalts der feuch-ten Luft (latente Wärme). Auf Basis der EN 308 müssen die Werte unter trocke-nen Bedingungen angegeben werden. Die Rückwärmzahl wird mit Ф angege-ben und liegt zwischen 0 und 1. Setzt man ausgeglichene Volumenströme und geringe interne Leckagen voraus, entspricht der Temperaturwirkungsgrad im Wesentlichen dem Wärmebereitstel-lungsgrad.
………………………WirkungsgradProzentuale Angabe der Rückwärmzahl. Bei einem Gegenstrom-Plattenwär-meübertrager liegt beispielsweise die Rückwärmzahl bezogen auf die Außen-luft bei Ф = 0,8. Der Wirkungsgrad liegt damit bei 80 %.
………………………RückfeuchtezahlWird analog zur Rückwärmzahl bei der Rückgewinnung von Luftfeuchtigkeit berechnet. Die Rückfeuchtezahl wird mit Ψ angegeben, die absolute Feuchtigkeit in g/kg mit X.
Energieeffizienz nach DIN EN 13053 Berücksichtigung des trockenen Tem-peraturwirkungsgrades nach EN 308 sowie des elektrischen Energiebedarfs für die Überwindung der Druckverluste des Wärmerückgewinnungssystems auf beiden Wegen.
………………………SFP-KlassenDie spezifische Ventilatorleistung defi-niert das Verhältnis von aufgenomme-ner elektrischer Ventilatorleistung zum geförderten Luftvolumenstrom. Je kleiner der SFP-Wert, desto weniger elektrische Energie wird für die Förderung eines Kubikmeters Luft benötigt.
………………………Luftgeschwindigkeitsklassen Vgemäß DIN EN 13053:2012Gemessene Durchtrittsgeschwindigkei-ten (m/s) im lichten Gehäusequerschnitt bezogen auf Filtereinheit oder Ventilator-einheit, wenn kein Filter vorhanden ist. Je größer der Wert (und entsprechend die V-Klasse in der Klassifizierung, V1 - V9), desto größer die Geschwindigkeit. Klassifizierung siehe unten. ………………………Leistungsaufnahme Ventilator-Motor-Einheit Pgemäß DIN EN 13053:2012Referenzwert in Klassen P1 - P7, gebil-det aus dem Luftvolumenstrom und der statischen Druckerhöhung eines freilau-fenden Ventilators. Die Liestungsmes-sung beeinhaltet auch Verluste durch Frequenzumrichter und den Antrieb. Je geringer die Klasse, desto höher die Effi-zienz der Ventilator-Motor-Einheit. Klassifizierung siehe unten.
Energieeffizienz H1gemäß DIN EN 13053:2012Die Energieeffizienz errechnet sich aus dem Temperaturübertragungsgrad und dem elektrischen Aufwand, hervorgeru-fen durch den Druckverlust der Luftvo-lumenströme und der Antriebsleistung für Rotor und Pumpe. Klassifizierung der Werte in Klassen H1 - H6, je geringer die Klasse desto höher ist die Effizienz. Klassifizierung siehe unten. ………………………VDI 2089Planerische Richtlinie für Entfeuch-tungs-, Wärme-, Raumluft-, Sanitär-, und elektrotechnische Anlagen in öffentlich genutzten Hallenbädern. Gilt sowohl für Neubauten als auch für die Modernisie-rung bestehender Anlagen.
………………………VDI 6022Planerische Richtlinie für Hygiene in raumlufttechnischen Anlagen und Geräten, mit dem Ziel, die Raumluft mindestens nicht negativ zu beeinflus-sen. Definition von Anforderungen an die Planung, Errichtung und den Betrieb von RLT-Anlagen, RLT-Geräten sowie deren Komponenten.
………………………VDI 3803 Blatt 3Richtlinie für die Luftbefeuchtung im Zu-, Ab- und Fortluftbereich von zentralen RLT-Anlagen. Sie gibt eine Übersicht über verschiedene Befeuchtersysteme sowie über die bei der Auswahl zu beachten-den Kriterien. Definition von Anforde-rungen an Planung, Errichtung, Betrieb und Instandhaltung von Luftbefeuchter-systemen.
Luftgeschwindigkeitsklasse V
Klasse Geschwindigkeit [m/s]
V1 ≤ 1,6
V2 > 1,6 - 1,8
V3 > 1,8 - 2,0
V4 > 2,0 - 2,2
V5 > 2,2 - 2,5
V6 > 2,5 - 2,8
V7 > 2,8 - 3,2
V8 > 3,2 - 3,6
V9 > 3,6
Effizienz Parameter P
Klasse Energieeffizienz ηe 1-1 [%]
P1 ≤ Pm ref * 0,85
P2 ≤ Pm ref * 0,90
P3 ≤ Pm ref * 0,95
P4 ≤ Pm ref * 1,00
P5 ≤ Pm ref * 1,06
P6 ≤ Pm ref * 1,12
P7 > Pm ref * 1,12
Effizienz Parameter H
Klasse Energieeffizienz ηe 1-1 [%]
H1 ≥ 71
H2 ≥ 64
H3 ≥ 55
H4 ≥ 45
H5 ≥ 36
H6 keine Anforderung
Pm ref = (DPstat/450)0,925 * (qv + 0,08)0,95
Pm ref [kw] elektrische Leistungsaufnahme∆Pstat [Pa] statische Druckerhöhung Ventilatorqv |m3/s] Luftvolumenstrom
ηe = ηt *(1-1 / ε)ηe [%] Energieeffizienzηt [%] Temperaturübertragungsgrad (trocken) ε [-] Leistungsziffer
Die Werte gelten für ausgeglichene Massenströme.
Wärmeübertrager Ausstattung und Funktionen
Rege
nera
tiv
Reku
pera
tiv
Adia
batik
Adso
rptio
nspr
ozes
s
Turb
okom
pres
sor
Kom
pres
sion
s-kä
ltean
lage
Entf
euch
ten
Wär
mep
umpe
Heiz
en
Kühl
en
Frei
e Kü
hlun
g
Steu
erun
g +
Rege
lung
ThermoCond 19
ThermoCond 23
ThermoCond 29
ThermoCond 38
ThermoCond 39
Trisolair 52
Trisolair 59
Adsolair 56
Adsolair 58
Resolair 62
Resolair 64
Resolair 66
Resolair 68
Resolair 65
Adconair 76
Drysolair 11
Frecolair 14
Adcoolair 75
Hybritemp 97/98
Die hier dargestellten Funtkionen und Gerätetypen sind nur Beispiele von möglichen Ausprägungen. Im Rahmen der
Menerga Air Gruppe stellen wir Ihnen jede gewünschte Kombination nach Wunsch zusammen.
Ausstattung und Funktionen
Glossar Ausstattung und Funktionen
![Page 17: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/17.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 103Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com102
Optionen
Schwimmhallen-klimatisierung
Komfort-klimatisierung
Geräteserie 19 23 29 38 39 52 56 58 59 62 64 66 68 76
Gerätegehäuse
Gerätedeckel 50 mm / MB 50
Bedienseite Zuluft links oder rechts
Deckelfarbe in RAL 7035 (lichtgrau)
Dämm-Material PUR-Schaum für Gehäusedeckel
Gehäusedeckel mit verstärktem Innenblech
Eckfuß mit Höhenverstellung
Gerätesockel
Gerätelieferung in zusätzlichen Teileinheiten 1
Lieferung des WRG-Systems separat auf Palette zur bauseitigen Montage vor Ort
Rekuperatorteil horizontal teilbar
Senkrechte Teilung
Zusätzliche Sichtfenster
Schaltschrank
Schaltschrank am Gerät
Schaltschrank zur Wandmontage
Anschlussstutzen
Flexible Anschlussstutzen
Luftfilter
Filterklassen und -größen wählbar
Ventilatorsystem
Anpassung der externen Pressung
Griffschutz vor Laufrad und Einströmdüse der Ventilatoren
Luftklappensystem
Umluftklappe
Außenluft-Bypassklappe im Gerät
Fortluft-Bypassklappe im Gerät
Umluft-Entfeuchtensektor
Stellmotor mit Notrücklauf und Stellungsrückmeldung
Motorbetätigte Außenluft/Fortluft Klappen anstatt dynamischer Klappen
Zuluft/Abluft Luftweg getauscht und motorbetätigte Außenluft/Fortluft Klappen
Heizsektor
PWW
Anpassung der PWW-Leistung
PWW Pumpensteuerung für elektronische Pumpe
PWW-Pumpensteuerung mit Schütz und Bi-Relais
PWW-Ventil zur bauseitigen Montage lose mitgeliefert
Im Standard enthalten
Wählbar
Gegen Mehrpreis wählbar
Abwählbär
1 alle Module können in separate Transporteinheiten verpackt werden
Die nachfolgende Übersicht zeigt eine Auswahl wählbarer Geräteoptionen der Anlagentypen im Bereich Schwimmhallen- und Komfortklimatisierung. Weitere Optionen bei anderen Anlagentypen sowie
Spezialanfragen sind jederzeit möglich. Bitte kontaktieren Sie hierzu Ihr Vertriebs-büro.
Geräteoptionen Schwimmhallen-klimatisierung
Komfort-klimatisierung
Geräteserie 19 23 29 38 39 52 56 58 59 62 64 66 68 76
Kühlsektor
PKW
Anpassung der PKW-Leistung
PKW-Pumpensteuerung für elektronische Pumpe
PKW-Pumpensteuerung mit Schütz und Bi-Relais
PKW-Ventil zur bauseitigen Montage lose mitgeliefert
Kälteanlage
Kälteanlage wählbar/abwählbar
Kälteleistungsregelung
Anpassung der Kälteleistung
Kältemittelunterkühler/Frischwassererwärmung
Wärmeauskopplung auf PWW mit separatem WWK-Umschaltventil
Reversierbare Kompressionskälteanlage
Hauswärmepumpenschaltung für PWW 2
Adiabate Verdunstungskühlung
AdiabaticzeroGWP, AdiabaticDXcarbonfree (elektrisch oder thermisch)
Ausrüstung mit Zinkopferanode
Spüleinrichtung für Plattenwärmeübertrager
Regelung
vicomo
Analoges Modem für DDC
Fernbedientableau
Zuluft-Temperatur Konstantregelung programmtechnisch vorhanden
Zuluftkanal Temperaturfühler separat mitgeliefert
PWW-Rücklauftemperatur Begrenzung programmtechnisch vorhanden
Anlegefühler separat mitgeliefert
Zuluft-Druckregelung programmtechnisch vorhanden
Zuluft Differenzdruckdose (C-Bus) separat mitgeliefert
Abluft-Druckregelung programmtechnisch vorhanden
Abluft Differenzdruckdose (C-Bus) separat mitgeliefert
Wassergeführte Temperaturregelung programmtechnisch vorhanden
Tauchfühler L = 55 o. L = 100 (C-Bus) lose mitgeliefert
Feuchteschiebung im Ruhebetrieb
Badepausenschaltung mit separatem Abluft-Kombifühler IP54, separat mitgeliefert
ModBus RTU Interface für Datenübergabe an die GLT
BACnet Interface für Datenübergabe an die GLT
Interface für Ospa Blue Control
Freischaltung WEB Server über Ethernet in DDC
Umluftsteuerungen
CO2-abhängige Umluft-/Außenluftsteuerung und/oder Volumenstromregelung
Wärmeauskopplung an Beckenwasser
Beckenwasserkondensator
Beckenwasserkondensator Pumpensteuerung
Beckenwasserpumpe
Beckenwasser-Temperaturregelung programmtechnisch vorhanden
Tauchfühler L = 55 o. L = 100 (C-Bus) lose mitgeliefert
Kunststoff-Kegeldurchflussmesser zur bauseitigen Montage lose mitgeliefert
Geräteoptionen
Optionen
2 nicht in Kombination mit Beckenwasserkondensator
![Page 18: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/18.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 105Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com104
FORSCHUNG // SPECIALS
Gerätetyp: Kundenspezifisch
FORSCHUNGSPROJEKT ALMA, CHILE 60 Teleskope in der Atacama-Wüste sammeln Daten zur Entstehung des Universums.
Gerätetyp: Resolair
PRINCESS ELISABETH STATION, ANTARKTIS Belgische Zero-Emission-Forschungsstation in Passivbauweise.
Gerätetyp: Adsolair
ZERO ENERGY HOUSE, SEOULLeuchtturmprojekt zum Thema Energieeffizienz, regenerative Energieträger und Nachhaltigkeit.
Gerätetyp: Resolair
DEUTSCHES MUSEUM SCHLEISSHEIMDer Flugplatz zeigt auf historischem Gelände eine bedeutende Luftfahrtsammlung.
Gerätetyp: Adsolair
URBIS, MANCHESTERDas Glasgebäude zeigt eine Erkundungsreise durch verschiedene Metropolen der Welt.
Gerätetyp: Adsolair
SCHLOSS TRAUTMANNSDORF, MERANEhemals das Feriendomizil von „Sissi“, beherbergt das Schloss heute das Südtiroler Landesmuseum für Tourismus.
MUSEEN // GALERIEN
Gerätetyp: Resolair
ETRIUM, KÖLNPassivbürohaus mit DGNB Gütesiegel in Gold.
Gerätetyp: Resolair
MENERGA SLOWENIEN Bürogebäude Menerga Slowenien, ausgezeichnet mit dem Green-Building-Award 2008.
Gerätetyp: Adsolair
IBEROSTAR, PALMA DE MALLORCA Moderne Zentrale mit A-Energiezertifizierung.
NIEDRIGENERGIE- GEBÄUDE
REFERENZPROJEKTE
Wir schaffen gutes Klima.©
pol
arfo
unda
tion.
org
© E
SO/J
osé
Fran
cisc
o Sa
lgad
o (j
osef
ranc
isco
.org
)©
ZEH
THEATER //KULTURSTÄTTEN
HISTORISCHE GEBÄUDE
SPORTSTÄTTEN //MULTIFUNKTIONSHALLEN
Gerätetyp: Adsolair
DEUTSCHE OPER, DÜSSELDORF Ein charmantes Juwel der 50er Jahre am Rande der Altstadt.
Gerätetyp: Resolair
TUSCHINSKI THEATER, AMSTERDAMSeit 1921 locken die hochflorigen Teppiche des luxuriösen Filmtheaters in eine bunte, märchen-hafte Welt.
Gerätetyp: Kundenspezifisch
STAATSTHEATER STUTTGART Die Klimatisierung des Chorprobensaales erfor-derte eine absolute „Silent“-Variante.
Gerätetyp: ThermoCond
HILTON SA TORRE, MALLORCA 5 Sterne-Luxushotel aus dem 14. Jahrhundert.
Gerätetyp: Adsolair
SCHLOSS BAD BERLEBURG Sitz der Fürsten-Familie Sayn-Wittgenstein-Berleburg.
Gerätetyp: Resolair, Hybritemp
BIBLIOTHEK HERZOGIN ANNA AMALIA,
WEIMAR Weltberühmtes Gebäude mit einem Bestand von mehr als 110.000 Büchern.
Gerätetyp: Resolair
SPORTHALLE GROSS-OSTHEIM Gewinner des IOC/IAKS AWARD 2003 in Silber.
Gerätetyp: Adsolair, Hybritemp
MULTIFUNKTIONSHALLE OSIJEK, KROATIENEiner der Austragungsorte der Handballwelt-meisterschaft 2009, größte Leichtathletikhalle Kroatiens.
Gerätetyp: ThermoCond, AquaCond
KANTRIDA RIJEKA, KROATIENOlympisches Schwimmstadion mit komplett zu öffnender Dachkonstruktion.
REFERENZPROJEKTE
Wir schaffen gutes Klima.
© S
tadt
Rije
ka
![Page 19: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/19.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 107Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com106
ÖFFENTLICHE SCHWIMMHALLEN
PRIVAT- // HOTELBÄDER
HOTELS //GASTRONOMIE
Gerätetyp: ThermoCond, Resolair
NATIONAL ZWEMCENTRUM DE
TONGELREEP, NIEDERLANDE Im größten Schwimmzentrum Europas werden u.a. nationale Wettkämpfe ausgetragen.
Gerätetyp: ThermoCond
LIPPE BAD, LÜNENErstes öffentliches Passivhaus-Hallenbad in Europa.
Gerätetyp: Kundenspezifisch, ThermoCond, AquaCond, Adsolair, Resolair
THERME LASKO, SLOWENIEN Wellness-Park mit 2.200 m2 Wasserfläche.
Gerätetyp: ThermoCond
PRIVATBAD Ein prachtvolles Wellnessdomizil in luxuriösem Ambiente.
Gerätetyp: ThermoCond
PRIVATBADDas private Schwimmbad scheint über den Dächern der Stadt zu schweben.
Gerätetyp: ThermoCond
5*-HOTEL VILLA AM RUHRUFER, MÜLHEIM
AN DER RUHR Spa-Bereich eines der kleinsten und exklusivsten 5*-Hotels in NRW.
Gerätetyp: Trisolair, ThermoCond
HOTEL DOLLENBERG5-Sterne Superior Hotel auf 650 Meter Höhe am Dollenberg im Schwarzwald.
Gerätetyp: Adsolair
PIZ SETEUR, SELVA DI VAL GARDENA, IT Im Herzen der Dolomiten lädt das Restaurant auf 2.064 Meter Höhe zum Verweilen ein.
Wir schaffen gutes Klima.
© T
. Phi
lippi
© T
. Phi
lippi
© B
äder
gese
llsch
aft L
ünen
mbH
REFERENZPROJEKTE
Gerätetyp: Kundenspezifisch, Trisolair, ThermoCond
WEISSENHÄUSER STRAND Ferien- und Freizeitpark mit Abenteuerland an der Ostsee.
Gerätetyp: Resolair
ANGELASCHULE, OSNABRÜCK Historischer Schulkomplex mit denkmal-geschützter Fassade.
Gerätetyp: Resolair
SCHULZENTRUM NECKARGMÜNDDie größte deutsche Passivhausschule bietet in 206 Räumen Platz für 1.250 Realschüler und Gymnasiasten.
Gerätetyp: Adsolair, Resolair, Trisolair, Hybritemp
UNIVERSITÄT, PASSAUÜber 100 Menerga-Anlagen schaffen gutes Klima an Bayerns jüngster Universität.
Gerätetyp: Kundenspezifisch, Adsolair
TLLV, BAD LANGENSALZA Thüringer Landesamt für Lebensmittel-sicherheit und Verbraucherschutz.
Gerätetyp: Kundenspezifisch
UNIKLINIKUM, FREIBURG Sorptionsgestützte Klimatisierung des Ambulanz- und Notfallbereiches.
Gerätetyp: Adsolair
UNIKLINIKUM, HAMBURG-EPPENDORF Gutes Klima in Hörsaal, Seminar- und Arbeits-räumen.
Gerätetyp: Adsolair, Resolair
MERCATOR PESNICA, SLOWENIEN5.000 m2 großes Einkaufszentrum, ausgezeichnet
mit mit Green Bulding Award 2011.
Gerätetyp: Resolair
AUDI TERMINAL, LUDWIGSBURGGroßzügiges Fahrzeugzentrum von Hahn Automobile.
Gerätetyp: Kundenspezifisch
TOYOTA FREY, SALZBURGDas „grünste“ Autohaus der Welt wurde kürzlich nach BREEAM mit „excellent“ ausgezeichnet.
SCHULEN //UNIVERSITÄTEN
KLINIKEN // LABORE
EINKAUFSTÄTTEN //SHOPPING CENTER
Wir schaffen gutes Klima.
© S
chin
delb
eck
© U
nive
rsitä
tskl
inik
um F
reib
urg
© U
nger
-Ste
el-G
roup
© U
nive
rsitä
tskl
inik
um H
ambu
rg-E
ppen
dorf
REFERENZPROJEKTE
![Page 20: Automatically selects the most economical operating mode ... · els required by VDI 2089 in summertime conditions, it may be necessary and more economical to use an additional damper](https://reader035.fdocuments.in/reader035/viewer/2022081622/613436b4dfd10f4dd73b9659/html5/thumbnails/20.jpg)
Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com 109Technischer Katalog v3.00/2019 | Technische Änderungen vorbehalten. © Menerga GmbH | www.menerga.com108
Gerätetyp: Adsolair
USM, MÜNSINGEN Am Firmensitz des Schweizer Möbel-herstellers werden seit vielen Jahren Trends gesetzt.
Gerätetyp: Adsolair
KÄRCHER CENTER, WINNENDENVerkaufscenter und Bürogebäude eines der größten Reinigungsgeräteherstellers weltweit.
Gerätetyp: Adsolair, Resolair
OTTO GROUP, HAMBURG Der Handels- und Dienstleistungskonzern einer der größten Online-Händler der Welt.
Gerätetyp: Resolair
TECHNO, BUBSHEIM Spezialist für den Drehteilevertrieb mit Sitz inBubsheim bei Stuttgart.
Gerätetyp: Adsolair
STIHL, WAIBLINGEN Das in über 160 Ländern tätige Familienunterneh-men ist u.a. bekannt für Motorsägen.
Gerätetyp: Adsolair
MAPAL, AALEN Standort des Herstellers für Präzisionswerkzeuge.
Gerätetyp: Adcoolair
BANCO SANTANDER, SPANIENRechenzentrum mit 16 MW Gesamtkühlleistung.
Gerätetyp: Hybritemp
LANDRATSAMT, FREIBURGKlimatisierung des Rechenzentrums, Kälteleistung 59,1 kW.
Gerätetyp: Adcoolair
COMMUNICODE, ESSENCommunicode ist spezialisiert auf das Hosting von Webshops, wie z.B. von Deichmann.
BÜROGEBÄUDE //VERWALTUNG
INDUSTRIE //PRODUKTIONSSTÄTTEN
RECHENZENTREN //SERVERRÄUME
Wir schaffen gutes Klima.©
Ott
o Gr
oup
© U
SM
REFERENZPROJEKTE DER MENERGA-GERÄTESCHLÜSSEL
z.B. Resolair 64 12 01 Resolair 64 12 01
Nam
e
Serie
Baug
röße
Ausf
ühun
g
Serie Name Funktion Ausstattung Ausführung
11 Drysolair Lufttrocknung Wärmepumpe, Rekuperator
14 Frecolair Lüftung/Kühlung freie Kühlung, Kompressionskälteanlage
19 ThermoCond
Schwimmhallen-klimatisierung
Kreuz-Gegenstrom-Wärmeübertrager
23 ThermoCond Kreuz-Gegen-Kreuzstrom-Wärmeübertrager
01 Innenaufstellung91 Außenaufstellung
29 ThermoCond Kreuz-Gegenstrom-Wärmeübertrager, Wärmepumpe
38 ThermoCond Gegenstrom-Plattenwärmeübertrager, bedarfsgerechte Volumenstromabsenkung
39 ThermoCond asymmetrischer Hochleistungswärmeübertrager, leistungsregelbare Wärme-pumpe, Frischwassererwärmer, bedarfsgerechte Volumenstromabsenkung
44 AquaCond Wärmerückgewinnung aus Abwasser
Wärmepumpe, Gegenstrom-Koaxial-Rekuperator, Wärmepumpe, automatische Wärmeübertragerreinigung
0 AWÜ: Cu FWÜ: Cu1 AWÜ: Cu FWÜ: Cu-verzinnt2 AWÜ: Cu-Ni FWÜ: Cu3 AWÜ: Cu-Ni FWÜ: Cu-verzinnt
* AWÜ=Abwasserwärmeübertrager* FWÜ=Frischwasserwärmeübertrager
52 Trisolair
Komfortklimatisierung, rekuperative Wärmerück-gewinnung
Kreuz-Gegen-Kreuzstrom-Wärmeübertrager, Luftvolumenstrom bis 5.000 m3/h
01 Innenaufstellung91 Außenaufstellung
56 Adsolair Doppelplatten-Wärmeübertrager, adiabate Verdunstungskühlung, max. Volumenstrom bis 40.800 m3/h
58 Adsolair Doppelplatten-Wärmeübertrager, adiabate Verdunstungskühlung, Kompressionskälteanlage, max. Volumenstrom bis 40.800 m3/h
59 Trisolair Kreuz-Gegen-Kreuzstrom-Wärmeübertrager, Kompressionskälteanlage,Luftvolumenstrom bis 5.000 m3/h
62 Resolair
Komfort- und Prozessklimatisierung, regenerative Wärmerück-gewinnung
Wärmespeichermodule, max. Volumenstrom bis 4.320 m3/h
64 Resolair Wärmespeichermodule, max. Volumenstrom bis 51.000m3/h
65 Resolair Wärmespeichermodule, Luftvolumenstrom bis 40.000 m3/h
66 Resolair Wärmespeichermodule, Kompressionskälteanlage, max. Volumenstrom bis 4.320 m3/h
68 Resolair Wärmespeichermodule, Kompressionskälteanlage, max. Volumenstrom bis 51.000 m3/h
75 Adcoolair Umluftkühlung freie Kühlung, adiabate Verdunstungskühlung, Kompressionskälteanlage
76 AdconairKomfortklimatisierung, rekuperative Wärmerück-gewinnung
Gegenstrom-Plattenwärmeübertrager, max. Luftvolumenstrom bis 45.200 m3/h, mit adiabater Verdunstungskühlung, Kompressionskälte-anlage, integriertem Adsorptionsprozess oder Turboverdichter
97 HybritempKompakt-Kaltwassersatz
indirekte freie Kühlung, adiabate Verdunstungskühlung, wirkungsgradoptimierte Kompressionskälteanlage
98 Hybritemp freie Kühlung, adiabate Verdunstungskühlung, leistungsoptimierte Kompressionskälteanlage