Automatic Controls for Industrial Refrigeration Systems-DANFOSS

download Automatic Controls for Industrial Refrigeration Systems-DANFOSS

of 102

Transcript of Automatic Controls for Industrial Refrigeration Systems-DANFOSS

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Automatic Controls

    for Industrial Refrigeration Systems

    Application HandbookREFRIGERATION &

    AIR CONDITIONING DIVISION

    MAKING MODERN LIVING POSSIBLE

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    2 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Contents Page

    Foreword. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

    2. Compressor Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

    2.1Compressor Capacity Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    2.2 Discharge TemperatureControl with Liquid Injection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    2.3 Crankcase Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    2.4 Reverse Flow Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.5 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    2.6 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    3. Condenser Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    3.1 Air Cooled Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    3.2 Evaporative Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3.3 Water Cooled Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    3.4 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    3.5 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    4. Liquid Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

    4.1 High Pressure Liquid Level Control System (HP LLRS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 274.2 Low Pressure Liquid Level Control System (LPLLRS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    4.3 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    4.4 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    5. Evaporator Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    5.1 Direct Expansion Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    5.2 Pumped Liquid Circulation Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    5.3 Hot Gas Defrost for DX Air Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    5.4 Hot Gas Defrost for Pumped Liquid Circulation Air Coolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    5.5 Multi Temperature Changeover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    5.6 Media Temperature Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    5.7 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    5.8 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    6. Oil Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    6.1 Oil cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    6.2 Oil Differential Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    6.3 Oil Recovery System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    6.4 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    6.5 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

    7. Safety systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    7.1 Pressure Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    7.2 Pressure and Temperature Limiting Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    7.3 Liquid Level Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    7.4 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    7.5 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    8. Refrigerant Pump Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 698.1 Pump Protection with Differential Pressure Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

    8.2 Pump Bypass Flow Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    8.3 Pump Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    8.4 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

    8.5 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

    9. Others . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

    9.1 Filter Driers in Fluorinated Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

    9.2 Filter Driers in CO2Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

    9.3 Water Removal for Ammonia Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

    9.4 Air purging systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    9.5 Heat Recovery System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

    9.6 Reference Literature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

    10. Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8810.1 Typical Refrigeration Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

    10.2 ON/OFF and modulating controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

    Reference Literature - Alphabetical overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 3

    Foreword This Danfoss application guide is designedto be used as a reference document by allthose involved in the workings of industrialrefrigeration systems.

    This guide aims to provide answers to the variousquestions relating to industrial refrigerationsystem control: - Why a type of control methodis necessary for the refrigeration system? Whyshould it be designed in this way? What type ofcomponents can be used? How to select controlmethods for different refrigeration systems? Inanswering these questions, the principles of thedifferent control methods are introduce followedby same control examples, comprising DanfossIndustrial Refrigeration products.

    The main technical data of the components isalso provided. Finally, comparisons betweendifferent solutions for each control method are

    made, so that the reader should know how toselect a solution.

    In this application guide, the pilot-operated servovalve ICS is recommended as a pressure andtemperature regulator. Please note that the wellestablished PM valve could also be applied whereICS is used.

    For the final design of the installation it isnecessary to use other tools, such as themanufacturers catalogues and calculationsoftware (e.g. Danfoss Industrial Refrigerationcatalogue and DIRcalc software).

    DIRcalc is the software for calculation andselection of Danfoss Industrial Refrigerationvalves. DIRcalc is delivered free of charge.Please contact your local Danfoss sales company.

    Please do not hesitate to contact Danfoss, ifyou have questions about control methods,application and controls described in this

    application guide.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    4 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    1. Introduction Refrigeration System with Pump Circulation

    Oilseparator

    Compressor

    Condenser

    Evaporator

    Expansion valve 1

    Oil cooler

    Refrigerant pump

    Receiver

    Liquid separator

    Oilliquid/vapour mixture of refrigerant

    HP liquid refrigerant

    HP vapour refrigerant LP vapour refrigerant

    LP liquid refrigerant

    1

    2

    3

    5

    4

    6

    Dan

    foss

    Tap

    p_

    0015_

    02

    04-2006

    Compressor Control

    Why?

    Primary: to control the suction pressure;

    Secondary: reliable compressor operation(start/stop, etc.)

    How?

    Control the compressor capacity accordingto the refrigeration load by means ofbypassing hot gas from the HP side back intothe LP side, compressor ON/OFF step control orcontroling the rotating speed of thecompressor;

    Install check valve on the discharge line inorder to prevent reverse flow of the refrigerantto the compressor;

    Keep pressures and temperatures on the inletand outlet of the compressor within theworking range.

    Oil control

    Why?

    Keep optimal oil temperature and pressurein order to guarantee reliable compressoroperation.

    How?

    Pressure: maintain and control the pressuredifferential across the compressor for oilcirculation, maintain the crankcase pressure(only for piston compressors);

    Temperature: bypass some oil around the oilcooler; control the cooling air or water to theoil cooler;

    Level: return the oil in ammonia systems andlow temperature fluorinated systems.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 5

    1. Introduction(continued) Condenser Control

    Why?

    Maintain the condensing pressure above the

    minimum acceptable value in order toguarantee sufficient flow through theexpansion devices;

    Ensure the right distribution of the refrigerantin the system.

    How?

    On/off operation or control the speed of thecondenser fans, control the flow of the coolingwater, flood the condensers with liquidrefrigerant.

    Liquid Level Control

    Why?

    Provide the correct flow of liquid refrigerantfrom the high pressure side to the low pressureside according to the actual demand;

    Ensure safe and reliable operation of the

    expansion devices.

    How?

    Control the opening degree of the expansiondevice according to the change of the liquid

    level.

    Refrigerant Pump Control

    Why? Maintain the pump running in trouble free

    mode by maintaining the flow through thepump within the permissible operating range;

    Maintain a constant differential pressure acrossthe pump in some systems.

    How? Design a bypass loop so that the flow can be

    maintained above the minimum permissibleflow;

    Shut off the pump if it fails to build up enoughdifferential pressure.

    Install a pressure regulating valve.

    Evaporating System Control

    Why? Primary: maintain a constant media

    temperature; Secondary: optimise operation of the

    evaporators; For direct expansion systems: guarantee

    that no liquid refrigerant from the evaporatorsenters the suction line of the compressor.

    How?

    Change the flow rate of the refrigerant intoevaporators according to the demand;

    Defrost evaporators.

    Safety Systems

    Why? Avoid unintended pressure of the vessels; Protect the compressor from being damaged

    by liquid hammering, overloading, oil shortageand high temperature, etc;

    Protect the pump from being damaged by

    cavitation.

    How?

    Install safety relief valve on vessels and othernecessary places; Shut off the compressor and pump if the

    inlet/outlet pressure or differential is out ofpermissible range;

    Shut off the system of part of the system when

    the level in the liquid separator or the receiverexceeds the permissible level.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    6 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    2. Compressor Controls The compressor is the heart of the refrigerationsystem. It has two basic functions:1. Maintain the pressure in the evaporator so

    that the liquid refrigerant can evaporate at therequired temperature;

    2. Compress the refrigerant so that it can becondensed at a normal temperature.

    The basic function of compressor control,therefore, is to adjust the capacity of thecompressor to the actual demand of therefrigeration system so that the requiredevaporating temperature can be maintained.

    If the compressor capacity is bigger thanthe demand, the evaporating pressure andtemperature will be lower than that required, andvice versa.

    Additionally, the compressor should not beallowed to operate outside of the acceptabletemperature and pressure range, in order tooptimise its running conditions.

    2.1Compressor Capacity Control

    The compressor in a refrigeration system isnormally selected to be able to satisfy the highestpossible cooling load. However, the cooling loadduring normal operation is usually lower than thedesign cooling load. This means that it is alwaysnecessary to control the compressor capacity sothat it matches the actual heat load. There areseveral common ways to control the compressorcapacity:

    1. Step control.This means to unload cylinders in a multi-cylindercompressor, to open and close the suction portsof a screw compressor, or to start and stop somecompressors in a multi-compressor system. Thissystem is simple and convenient. Furthermore,efficiency decreases very little during part-load.It is especially applicable to systems with severalmulti-cylinder reciprocating compressors.

    2. Slide valve control.The most common device used to control thecapacity of a screw compressor is the slide valve.

    The action of the oil-driven slide valve allowspart of the suction gas to avoid from beingcompressed. The slide valve permits a smoothand continuous modulation of capacity from100% down to 10%, but the efficiency drops atpart load.

    3. Variable speed control.Variable speed regulation. This solution isapplicable to all kinds of compressors, andis efficient. A two-speed electric motor or afrequency converter can be used to vary thespeed of the compressor. The two-speed electricmotor regulates the compressor capacity byrunning at the high speed when the heat load ishigh (e.g. cooling down period) and at the lowspeed when the heat load is low (e.g. storageperiod). The frequency converter can vary therotation speed continuously to satisfy the actualdemand. The frequency converter observeslimits for min. and max. speed, temperature andpressure control, protection of compressor motoras well as current and torque limits. Frequencyconverters offer a low start up current.

    4. Hot gas bypass.This solution is applicable to compressors withfixed capacities and more typical for commercialrefrigeration. In order to control the refrigerationcapacity, part of the hot gas flow on thedischarge line is bypassed into the low pressurecircuit. This helps to decrease the refrigerationcapacity in two ways: by diminishing the supplyof liquid refrigerant and releasing some heat intothe low pressure circuit.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 7

    Application example 2.1.1:Step control of compressorcapacity

    Step Controller

    Pressure Transmitter

    Oilseperator

    SCA

    EVRAT+FA

    SVA

    FIA

    Piston compressor

    AKS 33

    EKC 331

    Tocondenser

    From liquidseparator/

    evaporator

    SVA

    MDanfoss

    Tapp_0016_02

    04-2006

    HP vapour refrigerantLP vapour refrigerantOil

    Step control solution for compressor capacity canbe achieved by using a step controller EKC 331 .EKC 331 is a four-step controller with up to fourrelay outputs. It controls the loading/unloadingof the compressors/pistons or the electric motorof the compressor according to the suctionpressure signal from the pressure transmitter AKS33or AKS 32R. Based on a neutral zone control,EKC 331 can control a pack system with up to fourequally sized compressor steps or alternatively

    two capacity controlled compressors (eachhaving one unload valve).

    EKC 331T version can accept a signal from aPT 1000 temperature sensor, which may benecessary for secondary systems.

    Neutral Zone ControlA neutral zone is set around the reference value,in which no loading/unloading occurs.Outside the neutral zone (in the hatched areas+zone and - zone) loading/unloading will

    occur as the measure pressure deviates awayfrom the neutral zone settings.

    If control takes place outside the hatched area(named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if itwere in the hatched area.

    For more details, please refer to the manual ofEKC 331(T) from Danfoss.

    Technical data Pressure transmitter-AKS 33 Pressure transmitter-AKS 32R

    Refrigerants All refrigerant including R717

    Operating range [bar] 1 up to 34 1 up to 34

    Max. working pressure PB [bar] Up to 55 >33

    Operating temp. range [C] 40 to 85

    Compensated temp. range [C] LP: 30 to +40 / HP: 0 to +80

    Rated output signal 4 to 20 mA 10 to 90% of V supply

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    8 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 2.1.2:Compressor capacity controlby hot gas bypass

    Stop valveCapacity regulator

    Stop valve

    From receiver

    Tocondenser

    EVRAT+FATEA SVASVA

    EVM

    CVC

    ICS

    SVA

    SVA

    SVA

    EVRAT+FASVA

    ICS

    CVCOilseperator

    Compressor

    SVA

    SCA

    FIA

    Evaporator

    Danfoss

    Tapp_

    0017_

    02

    04-2006

    HP vapour refrigerantHP liquid refrigerantLP vapour refrigerantLP liquid refrigerantOil

    Hot gas bypass can be used to control therefrigeration capacity for compressors with fixedcapacity. The pilot-operated servo valve ICSwith a CVC pilot valve is used to control thehot gas bypass flow according to the pressureon the suction line. The CVC is a back pressure

    controlled pilot valve, which opens the ICS andincreases the flow of hot gas when the suctionpressure is below the set value. In this way, thesuction pressure ahead of the compressor is keptconstant, therefore the refrigeration capacitysatisfies the actual cooling load.

    Technical data Pilot-operated servo valve - ICSMaterial Body: low temp. steel

    Refrigerants All common refrigerants, incl. R717 and R744

    Media temp. range [C] 60 to +120

    Max. working pressure [bar} 52

    DN [mm] 20 to 80

    Pilot valve - CVC

    Material Body: stainless steel

    Refrigerants All common refrigerants

    Media temp. range [C] 50 to 120

    Max. working pressure [bar] High pressure side: 28

    Low pressure side: 17

    Pressure range [bar] 0.45 to 7

    Kvvalue [m3/h] 0.2

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 9

    Application example 2.1.3:Compressor variable speedcapacity control

    FIAFrom liquidseparator/evaporator SVA

    M

    AKD 5000

    SVA

    M

    From liquidseparator/evaporator SVA

    FIA

    PLC/OEM

    controller

    VLT 5000

    To oil separator

    To oil separator

    SVA

    AK2

    AKS 33

    AKS 33

    Danfoss

    Tapp_

    0139_

    02

    08-2006

    Frequency converter

    Controller

    Pressure transducer

    HP vapour refrigerantLP vapour refrigerant

    Frequency converter control offer the following

    advantages:Energy savings

    Improved control and product quality

    Noise reduction

    Longer lifetime

    Simplified installation

    Easy to use complete control of the system

    Technical data Frequenc y conver ter AKD 2800 Frequ ency conver ter AKD500 0

    Enclosure IP 20 IP 20 or IP 54

    Ambient temperature

    KW size 0.37kW to 18.5kW 0.75kW to 55kW

    Voltage 200-240V or 380-480V 200-240V or 380-500V

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    10 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    2.2Discharge TemperatureControl with Liquid Injection

    Compressor manufacturers generallyrecommend limiting the discharge temperaturebelow a certain value to prevent overheating ofvalues, prolonging their life and preventing thebreakdown of oil at high temperatures.

    From the log p-h diagram, it can be seen that thedischarge temperature may be high when:

    the compressor runs with high pressuredifferential.

    the compressor receives highly superheatedsuction vapour.

    the compressor runs with capacity control byhot gas bypass.

    There are several ways to reduce the dischargetemperature. One way is to install water cooledheads in reciprocating compressors, anothermethod is liquid injection, by which liquidrefrigerant from the outlet of the condenser

    or receiver is injected into the suction line, theintermediate cooler, or the side port of the screwcompressor.

    Application example 2.2.1:Liquid injection withthermostatic injection valve

    Stop valve

    Solenoid valve

    Thermostatic injection valve

    Stop valve

    Thermostat

    HP vapour refrigerantHP liquid refrigerantLP vapour refrigerantLP liquid refrigerantOil

    Compressor

    To oilseparator

    RT 107

    EVRA+FA

    TEAT

    SVAFrom receiver

    From liquidseparator/evaporator

    From oilcooler

    SVA

    SVA

    FIA

    RT 1A

    RT 5A

    Danfoss

    Tapp_0018_02

    04-2006

    When the discharge temperature rises abovethe set value of the thermostat RT 107, RT 107will energise the solenoid valve EVRA whichwill start liquid injection into the side port of thescrew compressor.

    The thermostatic injection valve TEATcontrols the injected liquid flow according tothe discharge temperature, which prevents thedischarge temperature from rising further.

    Technical data Thermostat - RT

    Refrigerants R717 and fluorinated refrigerants

    Enclosure IP 66/54

    Max. bulb temp. [C] 65 to 300

    Ambient temp. [C] 50 to 70

    Regulating range [C] 60 to 150

    Differential t [C] 1.0 to 25.0

    Thermostatic injection valve -

    TEAT

    Refrigerants R717 and fluorinated refrigerants

    Regulating range [C] Max. bulb temp. 150P band: 20

    Max. working pressure [bar] 20

    Rated Capacity* [kW] 3.3 to 274

    * Conditions: Te = +5C, p = 8 bar, Tsub = 4C

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 11

    Application example 2.2.2:Liquid injection with motorvalve

    Stop valve

    Solenoid valve

    Motor valve

    Stop valve

    Controller

    Temperature sensor

    HP vapour refrigerantHP liquid refrigerantLP vapour refrigerantLP liquid refrigerantOil

    An electronic solution for liquid injection controlcan be achieved with the motorised valveICM. An AKS 21 PT 1000 temperature sensorwill register the discharge temperature andtransmit the signal to the temperature controller

    EKC 361. If the temperature reaches the setvalue, the EKC 361 sends a control signal to theactuator ICAD which will adjust the openingdegree of the motor valve ICM so that thedischarge temperature is limited.

    Technical data

    Compressor

    To oilseparator

    SVA

    Fromreceiver

    From oilcooler

    ICAD

    ICMEVRA+FA

    EKC 361

    AKS 21

    SVA

    From liquidseparator/evaporator

    SVA

    FIA

    Danfoss

    Tapp_0019_02

    04-2006

    Motor valve - ICM

    Material Body: Low temperature steel

    Refrigerants All common refrigerants including R717 and R744

    Media temp. range [C] 60 to 120

    Max. working pressure [bar] 52 bar

    DN [mm] 20 to 65

    Nominal Capacity* [kW] 224 to 14000

    * Conditions: Te = 10C, p = 8.0 bar, Tsub = 4K

    Actuator - ICAD

    Material Housing: aluminium

    Media temp. range [C] 30 to 50 (ambient)

    Control input signal 0/4-10mA, or 0/2-10

    Open-close time 3 to 13 seconds depending on valve size

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    12 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 2.2.3:A compact solution for liquidinjection with ICF

    Valve station with:

    Stop valve Filter Solenoid valve Manual opener Motor valve Stop valve

    Controller

    Temperature sensor

    HP vapour refrigerant

    HP liquid refrigerantLP vapour refrigerantLP liquid refrigerantOil

    For liquid injection, Danfoss can supply a verycompact control solution ICF . Up to sixdifferent modules can be assembled into thesame housing. This solution works in the sameway as example 2.2.2, and is very compact andeasy to install.

    Technical data

    SVA

    Compressor

    To oilseparator

    Fromreceiver

    From liquidseparator/evaporator

    From oilcooler

    EKC 361

    AKS 21

    FIA

    ICFS

    ICF

    ICFM

    ICFF

    ICM ICFE ICFS

    DanfossTapp_0020_02

    04-2006

    ICF control solution

    Material Body: Low temperature steel

    Refrigerants All common refrigerants including R717 and R744

    Media temp. range [C] 60 to 120Max. working pressure [bar] 52 bar

    DN [mm] 20 to 40

    M

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 13

    2.3Crankcase Pressure Control

    During start-up or after defrost, the suctionpressure has to be controled, otherwise it canbe too high, and the compressor motor will beoverloaded.

    The electric motor for the compressor may bedamaged by this overloading.

    There are two ways to overcome this problem:1. Start the compressor at part load. The

    capacity control methods can be used tostart compressor at part load, e.g. unload

    part of the pistons for multi-pistonreciprocating compressors, or bypass somesuction gas for screw compressors with slidevalves, etc.

    2. Control the crankcase pressure forreciprocating compressors. By installing aback pressure controlled regulating valve inthe suction line, which will not open untilthe pressure in the suction line drops belowthe set value, suction pressure can be keptunder a certain level.

    Application example 2.3.1:Crankcase pressure control withICS and CVC

    Crankcase pressure regulator

    Stop valve

    HP vapour refrigerantLP vapour refrigerantOil

    In order to control the crankcase pressure duringstart-up, after defrost, or in others cases whenthe suction pressure may run too high, thepilot-operated servo valve ICSwith the backpressure controlled pilot valve CVC is installedin the suction line. The ICS will not open until

    the downstream suction pressure falls belowthe set value of the pilot valve CVC. In this way,the high pressure vapour in the suction linecan be released into the crankcase gradually,which ensures a manageable capacity for thecompressor.

    Technical data

    Tocondenser

    SVA

    EVRAT+FA

    SVA

    ICS

    CVC

    Oilseparator

    CompressorSCA

    Fromevaporator

    Danfoss

    Tapp_0021_02

    04-2006

    Pilot-operated servo valve - ICS

    Material Body: low temp. steel

    Refrigerants All common refrigerants, incl. R717 and R744

    Media temp. range [C] 60 to +120

    Max. working pressure [bar] 52

    DN [mm] 20 to 80

    Capacity* [kW] 11.4 to 470

    * Conditions: Te = 10C, Tl= 30C, p = 0.2 bar, Tsub = 8K

    Pilot valve - CVCMaterial Body: low temperature steel

    Refrigerants All common refrigerants

    Media temp. range [C] 50 to 120

    Max. working pressure [bar] High pressure side: 28

    Low pressure side: 17

    Pressure range [bar] 0.45 to 7

    Kvvalue [m3/h] 0.2

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    14 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 2.3.2:Crankcase pressure control withICS and CVP - (P > 17 bar)

    Pilot-operated servo valve

    Hand regulating valve

    Hand regulating valve

    Constant pressurepilot valve

    Stop valve

    HP vapour refrigerantLP vapour refrigerantOil

    For refrigeration systems with a suction pressure

    above 17 bar (e.g. CO2system), the pilot valveCVC can not be used. Crankcase pressure controlcan be achieved using the constant pressure pilotvalve CVP instead.

    The maximum suction pressure required is set onthe pilot valve CVP. When the suction pressurereaches the set value, CVP opens. Hence thehigh pressure vapour on the servo piston of themain valve ICSis released into the suction line,the pressure over the servo piston drops, andthe valve begins to close. This will prevent thesuction pressure from rising above the set value.

    After operating for some time, the compressor

    will pull so much vapour from the evaporatorthat the evaporating pressure drops below thepressure set on CVP. When this has happened,CVP will close, and the main valve ICS will open.During normal operation the ICS valve will becompletely open. The manual regulating valvesREGandshown are set for an opening whichresults in a suitable opening and closing time onthe main valve.

    Note:The CVH for the pilot CVP should beinstalled against the main flow direction, asshown in the diagram.

    Technical data

    To condenser

    SVA

    EVRAT+FA

    SVA

    CVP(HP)

    Oilseparator

    Compressor

    SCA

    Fromevaporator

    CVH

    REGREG

    ICS

    Danfoss

    Tapp_0022_02

    04-2006

    Constant pressure pilot valve - CVPMaterial CVP (LP) Body: steel

    Base: steel

    CVP (HP) Body: cast iron

    Base: stainless steel

    CVP (XP) Body: steel

    Base: steel

    Refrigerants All common refrigerants

    Media temp. range [C] 50 to 120

    Max. working pressure [bar] CVP (LP): 17

    CVP (HP): 28

    CVP (XP): 52

    Pressure range [bar] CVP (LP): 0.66 to 28

    CVP (HP): 0.66 to 28

    CVP (XP): 25 to 52

    Kvvalue [m3/h] CVP (LP): 0.4

    CVP (HP): 0.4CVP (XP): 0.45

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 15

    2.4Reverse Flow Control

    Reverse flow and condensation of refrigerantfrom the condenser to the oil separator andthe compressor should be avoided at all time.For piston compressors, reverse flow can resultin liquid hammering. For screw compressors,

    reverse flow can cause reversed rotationand damage to the compressor bearings.

    Furthermore, migration of refrigeration into theoil separator and further into the compressor atstandstill should be avoided. To avoid this reverseflow, it is necessary to install a check valve on theoutlet of the oil separator.

    Application example 2.4.1:Reverse flow control

    Stop check valve

    HP vapour refrigerantLP vapour refrigerantOil

    The stop check valve SCAcan function as acheck valve when the system is running, and

    can also shut off the discharge line for serviceas a stop valve. This combined stop/check valvesolution is easier to install and has lower flowresistance compared to a normal stop valve pluscheck valve installation.

    When selecting a stop check valve, it is importantto note:1. Select a valve according to the capacity and

    not the pipe size.

    2. Consider both the nominal and part loadworking conditions. The velocity in the

    nominal condition should be near to therecommended value, at the same timethe velocity in the part load condition shouldbe higher than the minimum recommendedvelocity.

    For details on how to select valves, please refer tothe product catalogue.

    Technical data

    To condenser

    SVA

    EVRAT+FA

    SVA

    Oilseparator

    Compressor

    SCA

    From

    evaporator

    Danfoss

    Tapp_0023_02

    04-2006

    Stop check valve - SCA

    Material Housing: special cold resistant steel approved for low temperature operation.

    Spindle: polished stainless steel

    Refrigerants All common non-flammable refrigerants, incl. R717.

    Media temp. range [C] 60 to 150

    Opening differential pressure [bar] 0.04

    Max. working pressure [bar] 40

    DN [mm] 15 to 125

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    16 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Solution Application Benefits Limitations

    Compressor Capacity ControlStep control of compressor

    capacity with EKC 331 and

    AKS 32/33

    Applicable to multi-

    cylinder compressor, screw

    compressor with multiplesuction ports, and systems

    with several compressors

    running in parallel.

    Simple.

    Almost as efficient at part

    load as at full load.

    The control is not

    continuous, especially when

    there are only few steps.Fluctuations in the suction

    pressure.

    Compressor capacity controlwith hot gas bypass using

    ICS and CVC PC

    Applicable to compressorswith fixed capacities.

    Effective to control thecapacity continuously

    according to the actual

    heat load.The hot gas canhelp the oil return from the

    evaporator.

    Not efficient at part load.Energy consuming.

    Compressor variable speed

    capacity control MApplicable to all

    compressors with the ability

    to run at reduced speed.

    Low start up current

    Energy savings

    Lower noise

    Longer lifetimeSimplified installation

    AKD2800 cannot be used

    for piston compressor

    applications.

    Compressor must be suitedfor reduced speed operation.

    Discharge Temperature Control with Liquid Injection

    Mechanical solution for

    liquid injection with TEAT,

    EVRA(T) and RT

    TC

    TSHL

    Applicable to systems where

    the discharge temperatures

    may run too high.

    Simple and effective. Injection of liquid refrigerant

    may be dangerous to the

    compressor. Not as efficientas intermediate cooler.

    Electronic solution for liquidinjection control with EKC

    361 and ICM

    M

    TC

    Applicable to systems wherethe discharge temperatures

    may run too high.

    Flexible and compact.Possible to monitor and

    control remotely.

    Not applicable to flammablerefrigerants. Injection of

    liquid refrigerant may

    be dangerous to thecompressor. Not as efficient

    as intermediate cooler.

    Electronic solution for liquid

    injection control with EKC

    361 and ICF

    Crankcase Pressure Control

    Crankcase pressure control

    with ICS and CVC

    PC Applicable to reciprocating

    compressors, normally

    used for small and mediumsystems.

    Simple and reliable. Effective

    in protecting reciprocating

    compressors at start-up orafter hot gas defrost.

    Gives constant pressure

    drop in the suction line.

    Crankcase pressure control

    with ICS and CVP

    PC

    Reverse Flow Control

    Reverse flow control with

    SCA

    Applicable to all

    refrigeration plants.

    Simple.

    Easy to install.

    Low flow resistance.

    Gives constant pressure

    drop in the discharge line.

    2.5Summary

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 17

    2.6Reference Literature

    For an alphabetical overview ofall reference literature please go

    topage 101

    To download the latest version of the literature please visit the Danfoss internet sitehttp://www.danfoss.com/BusinessAreas/RefrigerationAndAirConditioning/Products/Documentation.htm

    Type Literature no.

    AKD RB.8D.B

    AKS 21 ED.SA0.A

    AKS 32R RD.5G.J

    AKS 33 RD.5G.H

    CVC PD.HN0.A

    CVP PD.HN0.A

    EKC 331 RS.8A.G

    EKC 361 RS.8A.E

    EVRA(T) RD.3C.B

    Type Literature no.

    ICF PD.FT0.A

    ICM PD.HT0.A

    ICS PD.HS0.A

    REG PD.KM0.A

    SCA RD.7E.C

    SVA PD.KD0.A

    TEAT RD.1F.A

    Technical Leaflet / Manual

    Type Literature no.

    AKD 2800 EI.R1.H

    AKD 5000 EI.R1.R

    AKS 21 RI.14.D

    AKS 32R PI.SB0.A

    AKS 33 PI.SB0.A

    CVC RI.4X.L

    CVP RI.4X.D

    EKC 331 RI.8B.E

    EKC 361 RI.8B.F

    EVRA(T) RI.3D.A

    Type Literature no.

    ICF PI.FT0.A

    ICM PI.HT0.A

    ICS PI.HS0.A

    REG PI.KM0.A

    SCA PI.FL0.A

    SVA PI.KD0.B

    TEAT PI.AU0.A

    Product instruction

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    18 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    3. Condenser Controls In areas where there are large variations inambient air temperatures and/or load conditions,it is necessary to control the condensingpressure to avoid it from falling too low. Toolow condensing pressures results in there being

    insufficient pressure differential across theexpansion device and the evaporator is suppliedwith insufficient refrigerant. It means thatcondenser capacity control is mainly used in thetemperate climate zones and to a lesser degree insubtropical and tropical zones.

    The basic idea of control is to control thecondenser capacity when the ambienttemperature is low, so that the condensingpressure is maintained above the minimumacceptable level.

    This condensing capacity control is achievedeither by regulating the flow of circulating air orwater through the condenser, or by reducing theeffective heat exchange surface area.

    Different solutions can be designed for different

    types of condensers:3.1 Air cooled condensers3.2 Evaporative condensers3.3 Water cooled condensers

    3.1Air Cooled Condensers

    An air cooled condenser is a condenser cooled byambient air drawn from bottom to the top acrossthe heat exchange surface (tubes with fins) byaxial or centrifugal fans.

    Condensing pressure control for air cooledcondensers can be achieved in the followingways:

    3.1.1 - Step Control of Air Cooled Condensers

    The first method was using the required numberof pressure controls in the form the Danfoss RT-5and adjusting them to different set cut-in andcut-out pressures.

    The second method of controlling the fans wasby using a neutral zone pressure controller in theform of the Danfoss type RT-L. Initially it was usedtogether with a step controller with the requirednumber of contacts for the number of fans.

    3.1.2 - Fan speed control of air cooled condensersThis method of condenser fan control is mainlyused whenever a reduction in noise level isdesired due to environmental concerns.

    For this type of installation Danfoss frequencyconverter AKD can be used.

    3.1.3 - Area control of air cooled condensers

    For area or capacity control of air cooledcondensers a receiver is required. This receiver

    must have sufficient volume to be able toaccommodate the variations in the amount ofrefrigerant in the condenser.

    Two ways this condenser area control can bedone:1. Main valve ICS or PM combined with the

    constant pressure pilot CVP(HP) mounted inthe hot gas line on the inlet side to thecondenser and ICV combined with adifferential pressure pilot CVPP(HP) mountedin the pipe between the hot gas line and thereceiver. In the pipe between the condenserand the receiver a check valve NRVA ismounted to prevent liquid migration from the

    receiver to the condenser.

    However this system reacted too fast and timerswere used for delaying the cut-in and cut-out ofthe fans.

    The Third method is todays step controller theDanfoss EKC-331.

    2. Main valve ICS combined with the constantpressure pilot CVP(HP) mounted in the pipebetween the condenser and the receiver anda ICS combined with a differential pressurepilot CVPP(HP) mounted in the pipe betweenthe hot gas line and the receiver. This methodis mainly used in commercial refrigeration.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 19

    Application example 3.1.1:Step control of fans with stepcontroller EKC 331

    Step controller

    Pressure transmitter

    Stop valve

    Stop valve

    Stop valve

    HP vapour refrigerantHP liquid refrigerant

    EKC 331is a four-step controller with up tofour relay outputs. It controls the switching of thefans according to the condensing pressure signal

    from a pressure transmitter AKS 33or AKS 32R.Based on neutral zone control, EKC 331 can control the condensing capacity so that thecondensing pressure is maintained above therequired minimum level.

    For more information on neutral zone control,please refer to section 2.1.

    The bypass pipe where SVAis installed isan equalizing pipe, which helps balance thepressure in the receiver with the inlet pressure ofthe condenser so that the liquid refrigerant in thecondenser can be drained into the receiver.

    In some installations, EKC 331T is used. In thiscase the input signal could be from a PT 1000temperature sensor, e.g. AKS 21. The temperature

    sensor is usually installed in the outlet of thecondenser.

    Please note:This solution is not as accurate asthe solution with pressure transmitter, becausethe outlet temperature may not correctly reflectthe condensing pressure because of subcooling.If the subcooling is too small flash gas may occurwhen fans are starting up.

    Technical data

    AKS 33

    EKC 331

    Fromdischarge line Condenser

    To expansiondevice

    SFA SFA

    LLG

    SVA

    SNV

    Receiver

    SNVDSV

    SVASVA

    SVA

    Danfoss

    Tapp_0031_02

    04-2006

    Pressure transmitter - AKS 33 Pressure transmitter - AKS 32R

    Refrigerants All refrigerant including R717

    Operating range [bar] 1 up to 34 1 up to 34

    Max. working pressure [bar] Up to 55 >33

    Operating temp. range [C] 40 to 85

    Compensated temp. range [C] LP: 30 to +40 / HP: 0 to +80

    Rated output signal 4 to 20 mA 10 to 90% of V supply

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    20 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 3.1.2:Fan speed control of air cooledcondensers

    SVA

    SVA

    AKS 33

    SVA

    AKD

    Fromdischargeline

    Condenser

    SFV SFV

    To expansiondevice

    Receiver

    DSV

    SNV

    LLG

    SVADanfoss

    Tapp_0141_02

    08-2006

    Frequency converter

    Pressure transducer

    HP vapour refrigerantHP liquid refrigerant

    Frequency converter control offer the followingadvantages:

    Energy savings

    Improved control and product quality

    Noise reduction

    Longer lifetime

    Simplified installation

    Easy to use complete control of the system

    Technical data

    * Larger kW sizes on request

    Frequenc y conver ter AKD 2800 Frequency conver ter AKD50 00

    Enclosure IP 20 IP 20 or IP 54

    KW size* 0.37kW to 18.5kW 0.75kW to 55kW

    Voltage 200-240V or 380-480V 200-240V or 380-500V

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 21

    Technical data(continued)

    Constant pressure pilot valve - CVP (HP/XP)

    Material CVP (HP) Body: cast iron

    Base: stainless steel

    CVP (XP) Body: steel

    Base: steel

    Refrigerants All common refrigerants

    Media temp. range [C] 50 to 120

    Max. working pressure [bar] CVP (HP): 28

    CVP (XP): 52

    Pressure range [bar] CVP (HP): 0.66 to 28CVP (XP): 25 to 52

    Kvvalue [m3/h] CVP (HP): 0.4

    CVP (XP): 0.45

    Overflow valve - OFV

    Material Body: steel

    Refrigerants All common refrigerants, incl. R717

    Media temp. range [C] 50 to 150

    Max. working pressure [bar] 40

    DN [mm] 20/25Opening differential pressure range [bar] 2 to 8

    3.2Evaporative Condensers

    An evaporative condenser is a condenser cooledby ambient air combined with water sprayedthrough orifices and air baffles in counter flowwith the air. The water evaporates and theevaporation effect of the water drops adds muchto the condenser capacity

    Todays evaporative condensers are enclosed in asteel or plastic enclosure with axial or centrifugalfans at the bottom or at the top of the condenser.

    The heat exchanger surface in the wet air streamconsists of steel pipes.Above the water spray orifices (in the dry air) it iscommon to have a de-super heater made of steelpipes with fins to reduce the hot gas temperaturebefore it reaches the heat exchanger in the wet

    air stream. In this way the building up of calciumscales on the surface of the main heat exchangerpipes is greatly reduced.

    This type reduces the water consumptionconsiderably compared to a normal water cooledcondenser. Capacity control of an evaporativecondenser can be achieved by either two speedfan or variable speed control of the fan andat very low ambient temperature conditions

    switching off the water circulation pump.

    3.2.1 - Control of Evaporative Condensers

    Controlling the evaporative condenserscondensing pressure or the condenser capacitycan be achieved in different ways:

    1. RT or KP pressure controls for fan and water

    pump control (as it was earlier).2. RT-L neutral zone pressure control for fan and

    water pump control.

    3. Step controller for controlling two speed fansand the water pump.

    4. Frequency converters for fan speed controland water pump control.

    5. Saginomiya flow-switch for alarm if watercirculation fails.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    22 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 3.2.1:Step control of evaporativecondenser with pressurecontroller RT

    Suctionline

    Compressor

    SCA

    SNVDSV

    Receiver

    To oilcooler

    LLG

    SVA SNV

    To expansiondevice

    SFA

    SVA

    SFA

    SVA

    RT 5A

    Condenser

    RT 5A

    SVAWaterpump

    Danfoss

    Tapp_0033_02

    04-2006

    Pressure controller

    Pressure controller

    Stop valve

    Stop valve

    Stop valve

    This solution maintains the condensingpressure, as well as the pressure in the receiverat a sufficiently high level in low ambient

    temperature.

    When the inlet pressure of the condenser dropsbelow the setting of the pressure controller RT5A, the controller will switch off the fan, todecrease the condensing capacity.

    In extremely low ambient temperature, when thecondensing pressure drops below the setting ofRT 5Aafter all the fans have been switched off,

    RT 5A

    will stop the water pump.

    When the pump is stopped, the condenser andthe water pipes should be drained to avoidscaling and freezing.

    Technical data

    HP vapour refrigerant

    HP liquid refrigerantOil

    HP pressure control - RT 5A

    Refrigerants R717 and fluorinated refrigerants

    Enclosure IP 66/54

    Ambient temp. [C] 50 to 70

    Regulating range [bar] RT 5A: 4 to 17

    Max. working pressure [bar] 22

    Max. test pressure [bar] 25

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 23

    Application example 3.2.2:step control of evaporativecondenser with step controllerEKC331 EKC 331

    AKS 33

    To expansiondevice

    Suctionline

    LLG

    To oilcooler

    SVA

    Receiver

    SNV

    SNVDSV

    Compressor

    SCA

    SVASVA

    SFA SFA

    Condenser

    SVAWaterpump

    Danfoss

    Tapp_0034_02

    04-2006

    Step controller

    Pressure transmitter

    Stop valve

    Stop valve

    Stop valve

    This solution works in the same way as example3.2.1, but operated via step controller EKC 331.For more information on EKC 331, please refer to

    page 7.Step control solution for compressor capacity canbe achieved by using a step controller EKC 331 .EKC 331 is a four-step controller with up to fourrelay outputs. It controls the loading/unloadingof the compressors/pistons or the electric motorof the compressor according to the suctionpressure signal from the pressure transmitter AKS33or AKS 32R. Based on a neutral zone control,EKC 331 can control a pack system with up to fourequally sized compressor steps or alternativelytwo capacity controlled compressors (eachhaving one unload valve).

    EKC 331T version can accept a signal from a

    PT 1000 temperature sensor, which may benecessary for secondary systems.

    Neutral Zone ControlA neutral zone is set around the reference value,in which no loading/unloading occurs.Outside the neutral zone (in the hatched areas+zone and - zone) loading/unloading willoccur as the measure pressure deviates awayfrom the neutral zone settings.

    HP vapour refrigerant

    HP liquid refrigerantOil

    If control takes place outside the hatched area(named ++zone and --zone), changes of the cut-in capacity will occur somewhat faster than if it

    were in the hatched area.For more details, please refer to the manual ofEKC 331(T) from Danfoss.

    Technical data Pressure transmitter-AKS 33 Pressure transmitter-AKS 32R

    Refrigerants All refrigerant including R717

    Operating range [bar] 1 up to 34 1 up to 34

    Max. working pressure PB [bar] Up to 55 >33

    Operating temp. range [C] 40 to 85

    Compensated temp. range [C] LP: 30 to +40 / HP: 0 to +80

    Rated output signal 4 to 20 mA 10 to 90% of V supply

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    24 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    3.3Water Cooled Condensers

    The water cooled condenser was originally a shelland tube heat exchanger, but today it is veryoften a plate heat exchanger of modern design(for ammonia made of stainless steel).

    Water cooled condensers are not commonlyused, because in many places it is not allowedto use the large amount of water these typesconsume (water shortage and/or high prices forwater).

    Today water cooled condensers are popularin chillers, with the cooling water cooled by acooling tower and re-circulated. It can also beused as a heat recovery condenser to supply hotwater.

    The control of the condensing pressure can beachieved by a pressure controlled water valve,or a motorised water valve controlled by anelectronic controller to control the flow of thecooling water according to the condensingpressure.

    Application example 3.3.1:Water flow control of watercooled condensers with a watervalve

    Condenser

    Compressor

    Coolingwater out

    Coolingwater in

    SCA SVA

    To expansiondevice

    Suctionline

    SVA

    SNV

    SFA

    DSV

    SFA

    SNV

    WVS

    Danfoss

    Tapp_0035_02

    04-2006

    Stop valve

    Stop valve

    Water valve

    This solution maintains the condensing pressureat a constant level. The refrigerant condensingpressure is directed through a capillary tube tothe top of the water valve WVS, and adjusts theopening of WVSaccordingly. The water valveWVS is a P-regulator.

    Technical data

    HP vapour refrigerantHP liquid refrigerantOil

    Water valve - WVS

    Materials Valve body: cast ironBellows: aluminium and corrosion-proofed steel

    Refrigerants R717, CFC, HCFC, HFC

    Media Fresh water, neutral brine

    Media temp. range [C] 25 to 90

    Adjustable closing pressure [bar] 2.2 to 19

    Max. working pressure on refrigerant side [bar] 26.4Max. working pressure on liquid side [bar] 10

    DN [mm] 32 to 100

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 25

    Application example 3.3.2:Water flow control of watercooled condensers with amotor-valve

    Coolingwater in

    Coolingwater out

    Suctionline

    Compressor

    SNV

    VM2

    Condenser

    To expansiondevice

    SVA

    SFA

    SNV

    SCA

    SVA

    SFA

    DSV

    AMV 20

    AKS 33

    Controller

    DanfossTapp_0036_02

    04-2006

    Pressure transmitter

    Controller

    Motor-valve

    Stop valve

    Stop valve

    The controllerreceives the condensingpressure signal from the pressure transmitter AKS33, and sends out a corresponding modulatingsignal to actuator AMV 20 of the motor valveVM 2. In this way, the flow of cooling water isadjusted and the condensing pressure is keptconstant.

    Technical data

    HP vapour refrigerantHP liquid refrigerantOil

    In this solution, PI or PID control can beconfigured in the controller.

    VM 2 and VFG 2 are motor-valves designed fordistrict heating, and can also be used for waterflow control in refrigeration plants.

    Motor valve - VM 2

    Material Body: red bronze

    Media Circulation water/ glycolic water up to 30%

    Media temp. range [C] 2 to 150

    Max. working pressure [bar] 25

    DN [mm] 15 to 50

    Motor valve - VFG 2

    Material Body: cast iron/ductile iron/cast steel

    Media Circulation water/ glycolic water up to 30%

    Media temp. range [C] 2 to 200

    Max. working pressure [bar] 16/25/40

    DN [mm] 15 to 250

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    26 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Solution Application Benefits Limitations

    Air Cooled Condenser ControlStep control of fans with

    step controller EKC331

    Condenser

    Receiver

    PT

    Used mainly in industrial

    refrigeration in hot climatesand to a much lesser degree

    in colder climates

    Control of air volume in

    steps or with variable fanspeed control; Energy

    saving;

    No use of water.

    Very low ambient

    temperatures; Fan stepcontrol can be noisy.

    Fan speed control of air

    cooled condensers

    Condenser

    PT

    Receiver

    Applicable to all condensers

    with the ability to run at

    reduced speed.

    Low start up current

    Energy savings

    Lower noiseLonger lifetime

    Simplified installation

    Very low ambient

    temperatures;

    Evaporative Condenser Control

    Step control of evaporative

    condenser with pressurecontroller RT

    Fromdischarge line

    Condenser

    Receiver

    PS PS

    Industrial refrigeration

    with very large capacityrequirement

    Large reduction in water

    consumption compared towater cooled condensers

    and relatively easy to

    capacity control; Energysaving.

    Not applicable in countries

    with high relative humidity;In cold climates special

    precaution has to be taken

    so the water pipe is drainedfor water during water pump

    off periods.

    Step control of evaporative

    condenser with step

    controller EKC331

    Fromdischargeline

    Receiver

    Condenser

    Waterpump

    PT

    Industrial refrigeration

    with very large capacity

    requirement

    Large reduction in water

    consumption compared to

    water cooled condensersand relatively easy to

    capacity control; Possible

    to control remotely. Energy

    saving.

    Not applicable in countries

    with high relative humidity;

    In cold climates specialprecaution has to be taken

    so the water pipe is drained

    for water during water pump

    off periods.

    Water Cooled Condenser Control

    Liquid flow control with awater valve

    Condenser

    Compressor

    Coolingwater in

    Coolingwater out

    PCChillers, heat recoverycondensers

    It is easy to capacity control Not applicable when wateravailability is a problem.

    Liquid flow control with a

    motor valveCoolingwater in

    Coolingwater out

    Compressor

    Condenser

    M

    PT

    PC Chillers, heat recovery

    condensers

    It is easy to capacity control

    the condenser and the heat

    recovery; Possible to controlremotely.

    This type of installation

    is more expensive than

    a normal set up; Notapplicable when water

    availability is a problem.

    3.4Summary

    3.5Reference Literature

    For an alphabetical overview ofall reference literature please gotopage 101

    Type Literature no.

    AKD RB.8D.B

    AKS 21 ED.SA0.A

    AKS 32R RD.5G.J

    AKS 33 RD.5G.H

    AMV 20 ED.95.N

    CVPP PD.HN0.A

    CVP PD.HN0.A

    Type Literature no.

    ICS PD.HS0.A

    NRVA RD.6H.A

    RT 5A RD.5B.A

    SVA PD.KD0.A

    VM 2 ED.97.K

    WVS RD.4C.A

    Technical Leaflet / Manual

    Type Literature no.

    AKD 2800 EI.R1.H

    AKD 5000 EI.R1.R

    AKS 21 RI.14.D

    AKS 32R PI.SB0.A

    AKS 33 PI.SB0.A

    AMV 20 EI.96.A

    CVPP RI.4X.D

    CVP RI.4X.D

    Type Literature no.

    ICS PI.HS0.A

    NRVA RI.6H.B

    RT 5A RI.5B.C

    SVA PI.KD0.B

    VM 2 VI.HB.C

    WVS RI.4C.B

    Product instruction

    To download the latest version of the literature please visit the Danfoss internet sitehttp://www.danfoss.com/BusinessAreas/RefrigerationAndAirConditioning/Products/Documentation.htm

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 27

    4. Liquid Level Control Liquid level control is an important element inthe designing of industrial refrigeration systems.It controls the liquid injection to maintain aconstant liquid level.

    Two main different principles may be used whendesigning a liquid level control system:

    High pressure liquid level control system (HPLLRS)

    Low pressure liquid level control system (LPLLRS)

    High pressure liquid level control systems aretypically characterised by:1. Focus on the liquid level on the condensing

    side of the system2. Critical refrigerant charge3. Small receiver or even no receiver4. Applies mainly to chiller units and other

    systems with small refrigerant charge (forexample, small freezers)

    Low pressure systems are typicallycharacterized by:1. Focus on the liquid level on the evaporating

    side of the system2. Receiver is usually big

    3. Large (enough) charge of refrigerant4. Mainly applied to de-centralized systems

    Both principles can be achieved, usingmechanical and electronic components

    4.1High Pressure Liquid LevelControl System (HP LLRS)

    When designing a HP LLRS, the following pointshave to be taken into consideration:

    As soon as liquid is formed in the condenser theliquid is fed to the evaporator (low pressure side).

    The liquid leaving the condenser will have littleor no sub-cooling. This is important to considerwhen the liquid flows to the low pressure side.If there is pressure loss in the piping or thecomponents, flash-gas may occur and cause the

    flow capacity to be reduced.

    The refrigerant charge must be preciselycalculated in order to ensure that thereis adequate refrigerant in the system. Anovercharge increases the risk of flooding theevaporator or the liquid separator causingliquid carry over into the compressor (liquid

    hammering). If the system is undercharged theevaporator will be starved. The size of the lowpressure vessel (liquid separator/ shell-tubeevaporator) must be carefully designed sothat it can accommodate the refrigerant in allconditions without causing liquid hammering.

    Because of the above reasons, HP LLRS areespecially suitable for systems requiring smallrefrigerant charge, like chiller units, or smallfreezers. Chiller units usually do not need

    receivers. Even if a receiver is necessary in orderto install pilots and provide feed refrigerant to anoil cooler, the receiver could be small.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    28 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 4.1.1:Mechanical solution for HPliquid level control

    Stop valve

    Filter

    Servo-operated main valve

    Stop valve

    Float valve

    Stop valve

    Stop valve

    On large HP LLRS the SV1or SV3 float valve isused as a pilot valve for a PMFHmain valve.As illustrated above, when the liquid level in thereceiver rises above the set level, the SV1 floatvalve provides a signal to the PMFH main valveto open.

    Technical data

    FIASVASVA

    To seperatorTo oilcooler

    From condenser

    EVM

    PMFH

    SNV

    SV1

    SVA

    SNV

    DSV

    LLGReceiver

    SVASVA

    SFASFA

    SVA

    SVA

    Fromdischargeline

    Danfoss

    Tapp_

    0044_

    02

    04-2006

    HP vapour refrigerantHP liquid refrigerantLP liquid refrigerant

    PMFH 80 - 1 to 500

    Material Low temp. spherical cast iron

    Refrigerants R717, HFC, HCFC and CFC

    Media temp. range [C] 60 to + 120

    Max. working pressure [bar] 28

    Max test pressure [bar] 42

    Rated capacity* [kW] 139-13900

    * Conditions: R717, +5/32C, T l = 28C

    * Conditions: R717, +5/32C, T l = 28C

    Float valve - SV 1 and SV3

    Material Housing: steelCover: low temperature cast iron

    Float: stainless steel

    Refrigerants R717, HFC, HCFC and CFC

    Media temp. range [C] 50 to + 65

    P-band [mm] 35

    Max. working pressure [bar] 28

    Max test pressure [bar] 36

    Kvvalue [m3

    /h] 0.06 for SV 10.14 for SV 3

    Rated capacity* [kW] SV1: 25SV3: 64

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 29

    Application example 4.1.2:Mechanical solution for HPliquid level control with HFI

    HFI

    To liquidseperator

    Fromcompressor

    Cooling water out

    Cooling water in

    Plate type condenser

    Purge pipe (option 1)

    Purge pipe(option 2)

    Danfoss

    Tapp_0045_02

    08-2006

    HP float valve

    If the condenser is a plate heat exchanger, themechanical float valve HFIcan be used tocontrol the liquid level.

    The HFI is a direct acting high pressure floatvalve; therefore no differential pressure isrequired to activate the valve

    Technical data

    * Conditions: R717, 10/35C

    HP vapour refrigerantHP liquid refrigerant

    LP liquid refrigerantOil

    In certain cases it may be necessary to connectthe purge pipe to the HP/LP (option 1/option 2)side, as indicated on the drawing. This solutionenables reaching the required capacity when HFIis placed remotely from the condenser.

    HFI

    Material Special steel approved for low temperature application

    Refrigerants R717 and other non- flammable refrigerant. For the refrigerants with density greater than 700kg/m 3,please consult Danfoss.

    Media temp. range [C] 50 to 80

    Max. working pressure [bar] 25 bar

    Max test pressure [bar] 50 bar (without float)

    Rated capacity* [kW] 400 to 2400

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    30 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 4.1.3:Electronic solution for HP liquidlevel control

    FIA SVASVA

    To seperator

    To oil

    cooler

    SNV

    SVA

    SNV

    SFA

    DSV

    SFA

    LLGReceiver

    SVASVA

    EKC 347

    ICAD

    ICM

    SVA

    SVA

    AKS 41

    From condenser

    Fromdischargeline

    Danfoss

    Tapp_

    0046_

    02

    04-2006

    Stop valve

    Filter

    Motor valve

    Stop valve

    Controller

    Level transmitter

    Stop valve

    Stop valve

    When designing an electronic LLRS solution theliquid level signal can be given either by an AKS38 which is a level switch (ON/OFF) or an AKS 41which is a level transmitter (4-20 mA).

    The electronic signal is sent to an EKC 347electronic controller which controls the injectionvalve.

    The liquid injection can be controled in severaldifferent ways:

    With a modulating motor valve type ICM with

    an ICAD actuator.

    With a pulse-width-modulating expansionvalve type AKVA. The AKVA valve should beused only where the pulsation from the valveis acceptable.

    Technical data

    HP vapour refrigerantHP liquid refrigerantLP liquid refrigerant

    * Conditions: R717, Te= 10C, p = 8.0 bar, Tsub= 4K;

    With a regulating valve REG acting as anexpansion valve and an EVRA solenoid valveto implement ON/OFF control.

    The system illustrated is an AKS 41leveltransmitter which sends a level signal to anEKC 347liquid level controller. The ICMmotor valve acts as an expansion valve.

    Motor valve - ICM

    Material Body: Low temperature steel

    Refrigerants All common refrigerants including R717 and R744

    Media temp. range [C] 60 to 120

    Max. working pressure [bar] 52

    DN [mm] 20 to 80

    Nominal capacity* [kW] 224 to 14000

    Level transmitter - AKS 41

    Material Thread and pipe: stainless steel

    Top part: cast aluminium

    Refrigerants R717, R22, R404a, R134a, R718, R744

    Media temp. range [C] 60 to 100

    Max. working pressure [bar] 60

    Measuring range [mm] 207 to 2927

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 31

    4.2Low Pressure LiquidLevel Control System (LPLLRS)

    When designing a LP LLRS, the following pointshave to be taken into consideration:

    The liquid level in the low pressure vessel (liquidseparator/ shell-tube evaporator) is maintained at

    a constant level. This is safe to the system, sincea too high liquid level in the liquid separatormay cause liquid hammering to the compressor,and a too low level may lead to cavitation of therefrigerant pumps in a pump circulation system.

    The receiver must be big enough to accumulatethe liquid refrigerant coming from theevaporators when the content of refrigerant insome evaporators vary with the cooling load,some evaporators are shut off for service, or partof the evaporators are drained for defrosting.

    As a result of the above, LP LLRS are especiallysuitable for de-centralised systems in whichthere are many evaporators, and the refrigerantcharge is large, like cold stores. With LP LLRS,these systems could run safely even though the

    refrigerant charge is impossible to be preciselycalculated.

    In conclusion, HP LLRS are suitable for compactsystems like chillers; the advantage is the reducedcost (small receiver or no receiver). While LP LLRSare very suitable for de-centralised systems withmany evaporators and long piping, like a largecold storage; the advantage being the highersafety and reliability.

    Application example 4.2.1:Mechanical solution for LP

    liquid level control

    FIASVA

    Fromreceiver

    AKS 38

    AKS 38

    SNV

    SVASNV

    DSV

    LiquidSeparator

    Tocompressorsuction line

    From evaporator

    To evaporator

    LLG

    SVA

    SVA

    SVA

    EVM

    ICS1

    SVA

    SFASFASVA

    SVA

    SVA

    SV4

    QDVDanfoss

    Tapp_0047_02

    04-2006

    Stop valve

    Filter

    Solenoid valve

    LP float valve

    Stop valve

    Stop valve

    SV float valves monitor the liquid level in lowpressure vessels. If the capacity is small the SV valves can directly act as an expansion valve inthe low pressure vessel as shown.

    Technical data

    HP liquid refrigerantLiquid/vapour mixtureof refrigerantLP vapour refrigerantLP liquid refrigerant

    SV 4-6

    Material Housing: steelCover: low temperature cast iron(spherical)

    Float: stainless steel

    Refrigerants R717, HFC, HCFC and CFC

    Media temp. range [C] 50 to +120

    P-band [mm] 35

    Max. working pressure [bar] 28

    Max test pressure [bar] 42

    Kvvalue [m3/h] 0.23 for SV 4

    0.31 for SV 5

    0.43 for SV 6

    Rated capacity* [kW] SV4: 102

    SV5: 138

    SV6: 186

    * Conditions: R717, +5/32C, Tsub= 4K.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    32 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 4.2.2:Mechanical solution for LPliquid level control

    AKS 38

    AKS 38

    SNV

    SV4

    SVASNV

    DSV

    LiquidSeparatorLLG

    SVA

    SVA

    SVA

    SVA

    SFASFA

    SVA

    SVA

    FIAPMFL

    EVM

    SVA

    SVA

    Tocompressorsuction line

    SVA

    Fromreceiver

    Fromevaporator

    To evaporatorQDV

    Danfoss

    Tapp_0048_02

    04-2006

    Stop valve

    Filter

    Servo-operated main valve

    Stop valve

    LP float valve

    Stop valve

    Stop valve

    If the capacity is large, the float valve SVisused as a pilot valve for the PMFL main valve.As illustrated above, when the liquid level in thereceiver falls below the set level, the float valveSVprovides a signal to the PMFL value to open.

    Technical data

    HP liquid refrigerantLiquid/vapour mixtureof refrigerantLP vapour refrigerantLP liquid refrigerant

    * Conditions: R717, +5/32C, Tsub= 4K.

    PMFL 80 - 1 to 500

    Material Low temp. spherical cast iron

    Refrigerants R717, HFC, HCFC and CFC

    Media temp. range [C] 60 to +120

    Max. working pressure [bar] 28

    Max test pressure [bar] 42Rated capacity* [kW] 139-13,900

    Application example 4.2.3:Electronic solution for LP liquidlevel control

    AKS 38

    SNV

    SVA

    DSV

    LiquidSeparator

    From evaporator

    LLG

    SFASFA

    ICSFIA

    EVM

    EKC 347AKS 41

    SVA

    SVA

    SVA SVA

    SVA

    SVA

    SVA

    SNV

    ICAD

    ICM

    Fromreceiver

    Tocompressorsuction line

    To evaporator QDVDanfoss

    Tapp_0049_02

    04-2006

    Stop valve

    Filter

    Solenoid valve

    Motor valve

    Stop valve

    Controller

    Level transmitter

    Level switch

    The level transmitter AKS 41, monitors the

    liquid level in the separator and sends a levelsignal to the liquid level controller EKC 347,which sends a modulating signal to the actuatorof the motor valve ICM. The ICM motor valveacts as an expansion valve.

    HP liquid refrigerantLiquid/vapour mixtureof refrigerantLP vapour refrigerant

    LP liquid refrigerant

    The liquid level controller EKC 347also

    provides relay outputs for upper and lower limitsand for alarm level. However, it is recommendedthat a level switch AKS 38is fitted as a highlevel cut out.

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 33

    Application example 4.2.4:Electronic solution for LP liquidlevel control

    AKS 38

    SNV

    SVA

    DSV

    LiquidSeparatorLLG

    SFASFA

    AKVAICS1

    FIA

    EVM

    EKC 347

    AKS 41

    SVA

    SVA

    SVA

    SVA

    SVA

    SVA

    SVA

    SNV

    Tocompressorsuction line

    Fromreceiver

    To evaporator

    From evaporator

    QDVDanfoss

    Tapp_0050_02

    04-2006

    Stop valve

    Filter

    Solenoid valve

    Electronically operatedexpansion valve

    Stop valve

    Controller

    Level transmitter

    This solution is similar to solution 4.2.3. However,with this example the motor valve ICM isreplaced by a pulse width electronically operatedexpansion valve AKVA. The servo valve ICS isbeing used as an additional solenoid valve toensure 100% closure during off cycles.

    Technical data

    HP liquid refrigerant

    Liquid/vapour mixtureof refrigerantLP vapour refrigerantLP liquid refrigerant

    * Conditions: R717, +5/32C, Tsub= 4K.

    Application example 4.2.5:Electronic solution for LP liquidlevel control

    AKS 38

    SNV

    SVA

    DSV

    LiquidSeparatorLLG

    SFASFA

    AKS 41

    SVA

    SVA

    SVA

    SVA

    SVA

    SNV

    Tocompressorsuction line

    To evaporator

    From evaporator

    EKC 347

    ICFS

    ICM

    ICF

    ICFM

    ICFE

    ICFF

    ICFS

    From receiver

    QDVDanfoss

    Tapp_0051_02

    04-2006

    ICF valve station including:

    Stop valve

    Filter Solenoid valve Manual opener Motor valve Stop valve

    Controller

    Level transmitterDanfoss can supply a very compact valve

    solution ICF. Up to six different modules can beassembled into the same housing, which is easyto install.

    HP liquid refrigerantLiquid/vapour mixtureof refrigerantLP vapour refrigerantLP liquid refrigerant

    The module ICM acts as an expansion valve and

    the module ICFE is a solenoid valve.This solution works in an identical manner toexample 4.2.3. ICF solution similar to example4.2.4 is also available. Please refer to ICF literaturefor further information.

    The liquid level controller EKC 347alsoprovides relay outputs for upper and lower limitsand for alarm level. However, it is recommendedthat a level switch AKS 38 is fitted as a high levelcut out.

    AKVA

    Material AKVA 10: stainless steelAKVA 15: cast iron

    AKVA 20: cast iron

    Refrigerants R717

    Media temp. range [C] AKVA 10: 50 to +60

    AKVA 15/20: 40 to +60

    Max. working pressure [bar] 42DN [mm] 10 to 50

    Nominal capacity* [kW] 4 to 3150

    M

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    34 DKRCI.PA.000.C1.02 / 520H1623 Danfoss A/S (RA Marketing/MWA), 12 - 200 6

    Application example 4.2.6:Electronic solution for LP liquidlevel control

    AKS 38

    SNV

    SVA

    DSV

    LiquidSeparator

    LLG

    SFASFA

    SVA

    SVA

    SVA

    SVA

    SVA

    SNV

    Tocompressorsuction line

    To evaporator

    From evaporator

    Fromreceiver

    REG

    SVA SVA

    EVRA+FA

    AKS 38

    QDVDanfoss

    Tapp_0052_0204-2006

    AKS 38

    Stop valve

    Solenoid valve

    Hand regulating valve

    Stop valve

    Level switch

    This solution controls the liquid injection usingon/off control. The level switch AKS 38 , controlsthe switching of the solenoid valve EVRA , inaccordance with liquid level in the separator.

    The hand regulating valve REGacts as theexpansion valve.

    Technical data

    HP liquid refrigerantLiquid/vapour mixtureof refrigerantLP vapour refrigerantLP liquid refrigerant

    AKS 38

    Material Housing: zinc chromate cast iron

    Refrigerants All common non-flammable refrigerants, including R717.

    Media temp. range [C] 50 to +65

    Max. working pressure [bar] 28Measuring range [mm] 12.5 to 50

    REG

    Material Special cold resistant steel approved for low temperature operation

    Refrigerants All common non-flammable refrigerants, including R717.

    Media temp. range [C] 50 to +150

    Max. working pressure [bar] 40

    Test pressure [bar] Strength test: 80Leakage test: 40

    Kvvalue [m3/h] 0.17 to 81.4 for fully open valves

    EVRA

    Refrigerants R717, R22, R134a, R404a, R410a, R744, R502

    Media temp. range [C] 40 to +105

    Max. working pressure [bar] 42

    Rated capacity* [kW] 21.8 to 2368

    Kvvalue [m3/h] 0.23 to 25.0

    * Conditions: R717, 10/+25C, p = 0.15 bar

  • 5/21/2018 Automatic Controls for Industrial Refrigeration Systems-DANFOSS - slidepdf...

    http:///reader/full/automatic-controls-for-industrial-refrigeration-systems-

    Application Handbook Automatic Controls for Industrial Refrigeration Systems

    Danfoss A/S (RA Marketing/MWA), 12 - 200 6 DKRCI.PA.000.C1.02 / 520H1623 35

    Solution Application Benefits LimitationsHigh pressure mechanical

    solution:SV1/3 + PMFH

    Receiver

    Applicable to systems with

    small refrigerant charges,like chillers.

    Pure mechanical.

    Wide capacity range.

    Unable to control remotely,

    the distance between SVand PMFH is limited to

    several meters.

    A little bit slow in response.

    High pressure mechanical

    solution:

    HFI Plate typecondenser

    Applicable to systems

    with small refrigerant

    charges and with plate type

    condensers only.

    Pure mechanical.

    Simple solution.

    Especially suitable for plate

    heat exchanger

    Unable to provide

    thermosyphon oil cooling.

    High pressure electronic

    solution:

    AKS 41+EKC 347 + ICM Receiver

    M

    LC

    LT Applicable to systems with

    small refrigerant charges,

    like chillers.

    Flexible and compact.

    Possible to monitor and

    control remotely.

    Covers a wide range of

    capacity.

    Not allowed for flammable

    refrigerant.

    Low pressure mechanical

    solution:

    SV4-6Liquid separator

    Applicable to small systems. Pure mechanical.

    Simple, low cost solution.

    Limited capacity.

    Low pressure mechanical

    solution:

    SV 4-6 + PMFLLiquid separator

    Particularly applicable to

    de-central systems, like cold

    stores.

    Pure mechanical.

    Wide c