REL316*4 Auto- Reclosure; Synchro- Check & Voltage Check
BASICSBASICS
ABB© A
BB S
witz
erla
ndLt
d.-2
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 Auto Reclosure; Synchro- & Voltage Check
Objectives
Auto Reclosure (79)Rules / FactsImportant SettingsSupervision of the breaker (CB memory)the four AR cyclesFunction of the operating timeExamplesSubstations with single busbar or multiple busbar1 1/2 breaker schemeMaser / Follower schemeLine Protection Interfaces
ABB© A
BB S
witz
erla
ndLt
d.-3
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 Auto Reclosure; Synchro- & Voltage Check
Objectives
Synchro Check (25) & Voltage Check (27/59)Auto Reclosure interfaces3-pole tripping with 3-pole AR1-pole tripping with 1-pole AROperating ModesSynchronism MonitoringApplication ExampleVoltage Selection
ABB© A
BB S
witz
erla
ndLt
d.-4
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 Auto Reclosure (79)
Application
SYSTEM
SYSTEM
SYSTEM
TRIP LP TRIP LP
AR Close CB AR Close CB
Load
SYSTEM
Load
ABB© A
BB S
witz
erla
ndLt
d.-5
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 79 - Rules / Facts
On several auto-reclosing cycle, only the first cycle can be single pole tripping with fast auto-reclosing Following auto-reclosing cycles must be three phase tripping and reclosing
The line protection must provide single phase trip for the first fault, following faults must be tripped three phase
The closing command always goes to all three phases
ABB© A
BB S
witz
erla
ndLt
d.-6
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 79 - Rules / Facts
No synchro check is needed for fast single phasereclosing (Sychro-check by-pass)The system will not loose synchronity: 3 of 4 conductors (2 phases and ground) are still in serviceDuring the pause time the line still transmits more than 50% of the maximum power
If AR is not ready for a single cycle, the tripping circuit must be prepared or switched to 3-phase trippingReasons for AR not ready:
- AR blocked or switched off- AR blocked with t inhibit after reclosing (CB recovery time)- Fast AR dead time expired- No 1- pole AR permitted
ABB© A
BB S
witz
erla
ndLt
d.-7
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 79 - Rules / Facts
During the 1-pole dead time (one pole from the breaker is open) all other functions who react on unsymmetry and have a shorter tripping time then t-dead-1P-setting must be blockedExample:
- Directional earth fault with tripping scheme POTT- Pole discrepancy protection
ABB© A
BB S
witz
erla
ndLt
d.-8
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 79 - Important Settings
1-pole dead time One pole opens and closes after t-dead -1P (t dead 1P) Typical dead time: 0.3 – 0.5 s in high voltage
systems3-pole dead time All 3 pole open and close after t-dead-3P (t dead 3P) Typical dead time: 0.5 s – sev. minutesOperating time Prevents an AR for a long during fault (t oper) (eg. in the 2nd zone) Discrimination time Decision about 1-pole AR, 3 pole AR or (t discrim.1P, definitive trip after evolving fault t discrim.3P)Blocking time Prolongation of the AR blocking after a manual(t AR Block) close command or after close command from
the control system
ABB© A
BB S
witz
erla
ndLt
d.-9
RE
.316
_AR
_Syn
/ 20
03-1
0-01
/ R
W
REL316*4 79 - Important Settings
Inhibit time Blocking of the AR for 5 ….. 180 s after an(t inhibit) unsuccessful AR attempt.t inhibit is also called
recovery time. The breaker needs time to be ready for a new AR cycle
Close pulse duration Must be long enough to make sure the breaker(t close) closes properly. The close pulse is reset direct
after an unsuccessful AR attempt.
ABB© A
BB S
witz
erla
ndLt
d.-1
0R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - Supervision of the breaker (CB memory)
Breaker position: Open circuit breaker blocks the AR device. (CB open) During a running AR cycle the position of the
breaker is not interrogated. This prevents underall circumstances an AR for a switched off CB
Close open The breaker is able to switch on to a fault and to(CO ready) open again. This information is interrogated
direct before re-closing Open-Close-Open The breaker is able to do a complete AR cycle(CB ready) This input is not interrogated during a running
AR cycle.
If the AR function operates two breakers the supervision signals are needed from both breakers.
ABB© A
BB S
witz
erla
ndLt
d.-1
1R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 – four AR cycles
Why several AR cycles?
First AR: With the opening of the breaker the voltage whichsupplies the arc is switched off ⇒ the arc will extinguishThe dead time is set as short as possible. So the line canbe back in normal service as fast as possible.
Second AR: If the arc is not extinguished with the first AR attempt (tree, bamboo) a second attempt with a longer dead timewill be started (2nd and 3rd attempt are 3-phase cycles)
Third AR: This attempt is just an automatic voltage checkOne side will be switched on. An immediate trip occurs if the fault is still present. The opposite station will onlyreclose if the line was successful energized from the ownstation (Synchro- & V - Check)
Fourth AR: normally not applied in high voltage systems
ABB© A
BB S
witz
erla
ndLt
d.-1
2R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - Function of the operating time t-oper
Supervision of the fault duration is important in distance protection
Fault duration < operating timeExample: Trip in zone 1 initates an
AR cycle
Fault duration > operating timeExample: Trip in a higher zone stops the a
fast AR cycle
Tripping
Discrimination time
StartingStartingTripping
Operating timeDiscrimination time
Dead timeOn pulse
Definitive tript dead 1PQ0 Ph R
Q0 Ph SQ0 Ph T
t dead 3P Normal setting: t-oper < t2 of distance protectionThe operating time prevents AR for faults in higherzones ⇒ faults outside of the own line.Q0 Ph R
Q0 Ph SQ0 Ph T
ABB© A
BB S
witz
erla
ndLt
d.-1
3R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - Examples
AR Mode: fast AR 1 / 3 - pole Fault:: 1- phase FaultExample: - fast AR successful
Starting 1-phaseTripping 1-pole
Discrimination time
Dead time fast AR 1-pole, On - pulse
Q0 Phase R
Q0 Phase SQ0 Phase T
fast AR 1-pole
ABB© A
BB S
witz
erla
ndLt
d.-1
4R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - ExamplesAR Mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase faultExample: - fast AR not successful, - slow AR successful
Starting 1-phaseTripping 1-pole
Discrimination time 1-pole
Dead time fast AR 1-pole,
Starting 1-phaseTripping 3-pole
On-pulse, interrupted with second tripping
Discrimination time 3-pole
Dead time slow AR
Q0 Phase R
Q0 Phase SQ0 Phase T
LAR
fast AR 1-pole
ABB© A
BB S
witz
erla
ndLt
d.-1
5R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - ExamplesAR Mode:fast AR 1 / 3 - pole, followed by a long dead time Fault: 1- phase faultExample: - fast AR not successful; - slow AR not successful
Discrimination time 3-pole
Definitive tripping
StartingTripping 3-pole
Starting 1-phaseTripping 1-pole
Discrimination time 1-pole On-pulse, interrupted with second tripping
Dead time 1-pole,
Starting 1-phaseTripping 3-pole
Dead time 3-pole
Q0 Phase RQ0 Phase SQ0 Phase T
fast AR 1-pole slow AR
ABB© A
BB S
witz
erla
ndLt
d.-1
6R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - ExamplesMode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase faultExample: - Evolving fault before expiring of discrimination time
- fast AR not successful, slow AR successful
Starting 1-phaseTripping 1-pole
Discrimination time 1-pole
On-pulse, interrupted with tripping
Dead time 1-pole, interrupted with 2nd fault before expiring of 3-pole discrimination time
Q0 Phase R
Q0 Phase SQ0 Phase T
Starting 1-phase(other phase)Tripping 3-pole
Discrimination time 3-pole
Dead time fast AR 3-pole
Starting 1-phaseTripping 3-pole
Discrimination time 3-pole
fast AR 1-poleinterrupted
fast AR 3-pole Slow AR
Dead time slow AR
ABB© A
BB S
witz
erla
ndLt
d.-1
7R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - ExamplesAR mode: fast AR 1 / 3 - pole and slow AR Fault: 1- phase faultExample: - Evolving fault after expiring of discrimination time of fast AR
- Definitive tripping
Starting 1-phaseTripping 1-pole
Discrimination time 1-pole
Dead time 1-pole, interrupted with 2ten fault after expiring of 3-pole discrimination time
Q0 Phase R
Q0 Phase SQ0 Phase T
fast AR 1-poleinterrupted
ABB© A
BB S
witz
erla
ndLt
d.-1
8R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - Substations with single busbar or multiple busbar
Trip 2
Main 1
Main 2
AR
Trip 1 Close
3 3
Main 1
Main 2AR
Trip 1 Close
3 3
Trip 2
Standard - solution
“Cheap” - solution
Bus I
Bus II
Main 1 Main 2
AR
Main 1 Main 2
ABB© A
BB S
witz
erla
ndLt
d.-1
9R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - 1 1/2 breaker scheme
AR AR
AR
Main 1 Main 2 Main 1 Main 2
AR
Bus A
AR ARQ0 ABus A - CB
ARQ0 CCenter - CB
“Diameter”
All breakers are closedduring normal service
AR ARQ0 BBus B - CB
Bus B
Each CB next to a lineneeds an AR function.
ABB© A
BB S
witz
erla
ndLt
d.-2
0R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 - Master / Follower scheme
1 1/2 breaker scheme
The Master re-closes after the set dead timeAR AQ0 A CB image
LineM
Q0 C The Follower re-closes only after successful re-closing of the Master.
In case the master is not ready for an AR-cycle a signal will be send to the follower.The follower will now re-close in the set dead time.
AR CCB image
ABB© A
BB S
witz
erla
ndLt
d.-2
1R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 79 – Line Protection Interfaces
RE.316*4
HEST 965 010 C
Start
Trip CBTrip CB 3P
Trip 3-Pol
ZExtension
CondBlkAR
Start RST
Trip CBTrip CB 3P
1PolAR
ZExtensionAR
Start SOTF
< Z Auto-reclosurefunction
CB
open
CB
read
y
CO
read
y
Clo
s eC
B
ABB© A
BB S
witz
erla
ndLt
d.-2
2R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 25; 27/59 – Auto Reclosure Interfaces
2527/59
the Auto Reclosure is able to send a closing command if the Permit to close Signal is active
ABB© A
BB S
witz
erla
ndLt
d.-2
3R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 27/59 – Voltage Check
The Voltage Check is required to detect if
the Bus / Line is
Live or Dead
!!!
ABB© A
BB S
witz
erla
ndLt
d.-2
4R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 27/59 - 3-pole tripping with 3-pole AR
Check of only one phase to phase voltage for the busbar and the line is enough
Q0
Synchro- & voltage-check
V Bus bar VLine
ABB© A
BB S
witz
erla
ndLt
d.-2
5R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 27/59 - 1-pole tripping with 1-pole AR
On the busbar the check of one phase to phase voltage is enoughOn the line the check of all three phase to ground voltage is recommended
Q0
Synchro- & Voltage-check
Vbus bar vLine
ABB© A
BB S
witz
erla
ndLt
d.-2
6R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 25; 27/59 – Operating Modes
Selectable Operating Modes
(bus dead AND line dead)
the Permit to close Signal is active, if the Conditions are fulfiled
ABB© A
BB S
witz
erla
ndLt
d.-2
7R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 25 – Synchro Check
The Synchro Check is required to detect if in case of a
Live Bus & Live Line
the grid is synchronized or not
!!!
ABB© A
BB S
witz
erla
ndLt
d.-2
8R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 25 – Synchronism Monitoring
∆V
∆ϕ
VLine
ωBusbar ωLine
fBusbar = ωBusbar /2 πfLine = ωLine /2 π
∆f = fBusbar - fLine = fSchlupf < 0.10 Hz
VLine > 80% Un
VBusbar > 80% Un
SETTINGS
VBusbar
∆V < 20% Un
∆ϕ < 15°
ABB© A
BB S
witz
erla
ndLt
d.-2
9R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 25 – Application Example
Feeder Connected to a double busbar
ABB© A
BB S
witz
erla
ndLt
d.-3
0R
E.3
16_A
R_S
yn /
2003
-10-
01 /
RW
REL316*4 25 – Voltage Selection
• Only one phase to phase voltage is used for the synchro-check
Reasons:
• A three phase measuring is not needed because the synchro-check is only needed for 3-phase faults
• For 1-phase AR the synchro-check is bypassed
• Phase to ground voltage should not be used. The natural zero sequence voltage disturbs in the medium voltage system the sychro-check measuring