AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump...

26
© 2014 Pentair Ltd. AURORA ® SELECTION TABLES Horizontal Split Case Fire Pump 60 Hz Electric Motor Driven Section 912 Page 301P Date March 27, 2014 Electric Driven Flow Pressure Speed (rpm) Pump Size and Model (psi) (TDH) 250 GPM 40 92 3560 3-481-10 45 104 3560 3-481-10 50 116 3560 3-481-10 52 120 3560 2.5-481-10B 55 127 3560 2.5-481-10B 3560 3-481-10 60 139 3560 2.5-481-10B 3560 3-481-10 65 150 3560 2.5-481-10B 3560 3-481-10 70 162 3560 2.5-481-10B 3560 3-481-10 75 173 3560 2.5-481-10B 3560 3-481-10 80 185 3560 2.5-481-10B 3560 3-481-10 85 196 3560 2.5-481-10B 3560 3-481-10 90 208 3560 2.5-481-10B 3560 3-481-10 95 219 3560 2.5-481-10B 3560 3-481-10 100 231 3560 2.5-481-10B 3560 3-481-10 105 243 3560 2.5-481-10B 110 254 3560 2.5-481-10B 115 266 3560 2.5-481-10B 120 277 3560 2.5-481-10B 125 289 3560 2.5-481-10B 130 300 3560 2.5-481-10B 135 312 3560 2.5-481-10B 140 323 3560 2.5-481-10B 145 335 3560 2.5-481-10B 150 347 3560 2.5-481-10B 155 358 3560 2.5-481-10B 160 370 3560 2.5-481-10B 165 381 3560 2.5-481-10B 167 386 3560 2.5-481-10B For further details on pump performance, please contact your local Aurora fire pump distributor.

Transcript of AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump...

Page 1: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 301PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

250

GPM

40 92 3560 3-481-1045 104 3560 3-481-1050 116 3560 3-481-1052 120 3560 2.5-481-10B

55 1273560 2.5-481-10B3560 3-481-10

60 1393560 2.5-481-10B3560 3-481-10

65 1503560 2.5-481-10B3560 3-481-10

70 1623560 2.5-481-10B3560 3-481-10

75 1733560 2.5-481-10B3560 3-481-10

80 1853560 2.5-481-10B3560 3-481-10

85 1963560 2.5-481-10B3560 3-481-10

90 2083560 2.5-481-10B3560 3-481-10

95 2193560 2.5-481-10B3560 3-481-10

100 2313560 2.5-481-10B3560 3-481-10

105 243 3560 2.5-481-10B110 254 3560 2.5-481-10B115 266 3560 2.5-481-10B120 277 3560 2.5-481-10B125 289 3560 2.5-481-10B130 300 3560 2.5-481-10B135 312 3560 2.5-481-10B140 323 3560 2.5-481-10B145 335 3560 2.5-481-10B150 347 3560 2.5-481-10B155 358 3560 2.5-481-10B160 370 3560 2.5-481-10B165 381 3560 2.5-481-10B167 386 3560 2.5-481-10B

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 2: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 302PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

500

GPM

40 92 1770 4-481-11A45 104 1770 4-481-11A

50 1161770 4-481-11A3560 3-481-10

55 1271770 4-481-11A3560 3-481-10

60 1391770 4-492-141770 4-481-153560 3-481-10

65 1501770 4-481-153560 3-481-10

70 1621770 4-481-153560 3-481-10

75 1731770 4-481-153560 3-481-10

80 1851770 4-481-153560 3-481-10

85 1961770 4-492-183560 3-481-10

90 2081770 4-492-183560 3-481-10

95 2191770 4-492-183560 3-491-9C3560 3-481-10

100 2311770 4-492-183560 3-481-10

105 2431770 4-492-183560 3-481-10

110 2541770 4-492-183560 3-481-10

115 2661770 4-492-183560 3-481-10

120 2771770 4-492-183560 3-481-10

125 2891770 4-492-183560 3-481-103560 3-492-10A

130 3003560 3-481-103560 3-492-10A

134 310 3560 3-481-10

135 3123560 3-481-103560 3-492-10A

140 3233560 3-481-103560 3-492-10A

145 3353560 3-481-103560 3-492-10A

147 340 3560 3-481-10

Page 3: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 303PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

500

GPM

150 3471770 4-485-153560 3-481-103560 3-492-10A

155 3581770 4-485-153560 3-492-10A

160 3701770 4-485-153560 3-492-10A

164 379 1770 4-485-15

165 3811770 4-485-153560 3-492-10A

170 393 1770 4-485-15175 404 1770 4-485-15180 416 1770 4-485-15185 427 1770 4-485-15190 439 1770 4-485-15

195 4501770 4-485-153565 6-491-12A

200 4621770 4-485-153565 6-491-12A

205 4741770 4-485-153565 6-491-12A

210 4851770 4-485-153565 6-491-12A

215 497 3565 6-491-12A220 508 3565 6-491-12A225 520 3565 6-491-12A228 527 3560 5-485-12230 531 3565 6-491-12A233 538 3565 6-491-12A

235 5433560 5-485-123565 6-491-12A

240 5543560 5-485-123565 6-491-12A

245 5663560 5-485-123565 6-491-12A

250 5783560 5-485-123565 6-491-12A

255 5893560 5-485-123565 6-491-12A

260 6013560 5-485-123565 6-491-12A

265 6123560 5-485-123565 6-491-12A

270 6243560 5-485-123565 6-491-12A

275 6353560 5-485-123565 6-491-12A

277 640 3565 6-491-12A278 642 3565 6-491-12AU*

Page 4: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 304PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

500

GPM

280 647 3560 5-485-12285 658 3560 5-485-12290 670 3560 5-485-12295 681 3560 5-485-12300 693 3560 5-485-12305 705 3560 5-485-12310 716 3560 5-485-12315 728 3560 5-485-12320 739 3560 5-485-12325 751 3560 5-485-12330 762 3560 5-485-12335 774 3560 5-485-12340 785 3560 5-485-12345 797 3560 5-485-12350 809 3560 5-485-12355 820 3560 5-485-12360 832 3560 5-485-12365 843 3560 5-485-12370 855 3560 5-485-12375 866 3560 5-485-12380 878 3560 5-485-12385 889 3560 5-485-12390 901 3560 5-485-12395 912 3560 5-485-12400 924 3560 5-485-12405 936 3560 5-485-12410 947 3560 5-485-12415 959 3560 5-485-12420 970 3560 5-485-12425 982 3560 5-485-12430 993 3560 5-485-12435 1005 3560 5-485-12440 1016 3560 5-485-12445 1028 3560 5-485-12450 1040 3560 5-485-12455 1051 3560 5-485-12460 1063 3560 5-485-12465 1074 3560 5-485-12470 1086 3560 5-485-12476 1100 3560 5-485-12

Page 5: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 305PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

750

GPM

40 92 1770 4-481-11A45 104 1770 4-481-11A

50 1161770 4-481-11A1770 5-481-15

55 127 1770 5-481-1560 139 1770 5-481-15

65 1501770 5-481-153560 4-481-11C

70 1621770 5-481-153560 4-481-11C

75 1731770 4-481-153560 4-481-11C

80 1851770 4-481-153560 4-481-11C

81 187 3560 4-481-11D

85 1961770 4-481-153560 4-481-11D

90 2081770 4-491-14C1770 4-481-153560 4-481-11D

95 2191770 4-481-153560 4-481-11D

100 231

1770 4-492-181770 5-491-18A3550 4-491-11A3560 4-481-11D

105 2431770 4-492-181770 5-491-18A3560 4-481-11D

110 2541770 4-492-181770 5-491-18A3560 4-481-11D

115 2661770 4-492-181770 5-491-18A3560 4-481-11D

120 2771770 4-492-181770 5-491-18A3560 4-481-11D

125 2891770 4-492-181770 5-491-18A3560 4-481-11D

130 3001770 5-491-18A3560 4-481-11D

135 3121770 5-491-18A3560 4-481-11D

140 3231770 5-491-18A3560 4-481-11D

145 3351770 6-485-17A3560 4-481-11D

Page 6: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 306PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

750

GPM

148 342 1770 6-485-17A

150 3471770 6-485-17A3560 4-481-11D

155 3581770 6-485-17A3550 4-491-11C3560 4-481-11D

158 365 1770 6-485-16B

160 370

1770 6-485-17A1770 6-485-16B3550 4-491-11C3560 4-481-11D

165 381

1770 6-485-17A1770 6-485-16B3550 4-491-11C3560 4-481-11D

170 390

1770 6-485-17A1770 6-485-16B3550 4-491-11C3560 4-481-11D

175 404

1770 6-485-17A1770 6-485-16B3550 4-491-11C3560 4-481-11D

180 416

1770 6-485-17A1770 6-485-16B3565 6-491-12A3550 4-491-11C3560 4-481-11D

185 427

1770 6-485-17A1770 6-485-16B3565 6-491-12A3550 4-491-11C3560 4-481-11D

190 439

1770 6-485-17A1770 6-485-16B3565 6-491-12A3550 4-491-11C3560 4-481-11D

192 444 3560 4-481-11C

195 450

1770 6-485-17A1770 6-485-16B3565 6-491-12A3550 4-491-11C

200 462

1770 6-485-17A1770 6-485-16B3565 6-491-12A3550 4-491-11C

203 469 1770 6-485-16B

Page 7: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 307PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

750

GPM

205 4741770 6-485-17A3565 6-491-12A3550 4-491-11A

209 4831770 6-485-17A3550 4-491-11A

210 4851770 6-485-17A3565 6-491-12A3550 4-491-11A

215 4971770 6-485-17A3565 6-491-12A3550 4-491-11A

218 504 3550 4-491-11A

220 5081770 6-485-17A3565 6-491-12A3550 4-491-11A

225 5201770 6-485-17A3565 6-491-12A3550 4-491-11A

230 5311770 6-485-17A3565 6-491-12A

235 5431770 6-485-17A3565 6-491-12A

240 5541770 6-485-17A3565 6-491-12A

245 5661770 6-485-17A3565 6-491-12A

250 578 3565 6-491-12A255 589 3565 6-491-12A260 601 3565 6-491-12A265 612 3565 6-491-12A266 614 3565 6-491-12AU*310 716 3560 6-485-12315 728 3560 6-485-12320 739 3560 6-485-12325 751 3560 6-485-12330 762 3560 6-485-12335 774 3560 6-485-12340 785 3560 6-485-12345 797 3560 6-485-12350 809 3560 6-485-12355 820 3560 6-485-12360 832 3560 6-485-12365 843 3560 6-485-12370 855 3560 6-485-12375 866 3560 6-485-12380 878 3560 6-485-12385 889 3560 6-485-12390 901 3560 6-485-12395 912 3560 6-485-12

Page 8: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 308PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

750

GPM

400 924 3560 6-485-12405 936 3560 6-485-12410 947 3560 6-485-12415 959 3560 6-485-12420 970 3560 6-485-12425 982 3560 6-485-12430 993 3560 6-485-12435 1005 3560 6-485-12440 1016 3560 6-485-12445 1028 3560 6-485-12450 1040 3560 6-485-12455 1051 3560 6-485-12460 1063 3560 6-485-12465 1074 3560 6-485-12470 1086 3560 6-485-12475 1097 3560 6-485-12480 1109 3560 6-485-12485 1120 3560 6-485-12490 1132 3560 6-485-12495 1143 3560 6-485-12506 1169 3560 6-485-12

Page 9: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 309PDate March 27, 2014

For further details on pump performance, please contact your local Aurora fire pump distributor.

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1000

GPM

40 92 1770 6-481-1145 104 1770 6-481-11

50 1161770 5-481-151770 6-481-11

55 127 1770 5-481-1560 139 1770 5-481-1565 150 1770 5-481-1570 162 1770 5-481-1575 173 1770 5-481-1580 185 1770 5-481-1585 196 1770 5-481-1588 203 3560 6-481-11HH

90 208

1770 5-481-171770 5-481-153560 5-481-11C3560 6-481-11HH

95 2191770 5-481-173560 5-481-11C3560 6-481-11HH

100 2311770 5-481-173560 5-481-11C3560 6-481-11HH

105 2431770 5-481-173560 5-481-11C3560 6-481-11HH

110 2541770 5-481-173560 5-481-11C3560 6-481-11HH

115 2661770 5-481-173560 5-481-11C3560 6-481-11HH

120 2771770 5-481-173560 5-481-11C3560 6-481-11HH

125 2891770 5-481-173560 5-481-11C3560 6-481-11HH

130 300

1770 5-491-18A1770 6-485-17A3560 5-481-11C3560 6-481-11HH

135 312

1770 5-491-18A1770 6-485-17A3560 5-481-11C3560 6-481-11HH

140 3231770 6-485-17A3560 5-481-11C3560 6-481-11HH

144 333 1770 6-485-16B

Page 10: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 310PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1000

GPM

145 335

1770 6-485-17A1770 6-485-16B3560 5-481-11C3560 6-481-11HH

149 344 1780 6-485-16

150 347

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11C3560 6-481-11HH

154 356 3560 6-481-14HH

155 358

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11C3560 6-481-11HH3560 6-481-14HH

160 370

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11B3560 5-481-11C3560 6-481-11HH3560 6-481-14HH

165 381

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

170 393

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

175 404

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

180 416

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 11: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 311PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1000

GPM

185 427

1770 6-485-17A1770 6-485-16B1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

188 434 1770 6-485-16B

190 439

1770 6-485-17A1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

195 450

1770 6-485-17A1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

200 462

1770 6-485-17A1780 6-485-163560 5-481-11B3560 6-481-11HH3560 6-481-14HH

202 467 1780 6-485-16

205 4741770 6-485-17A3560 6-481-11HH3560 6-481-14HH

210 4851770 6-485-17A3560 6-481-11HH3560 6-481-14HH

215 4971770 6-485-17A3560 6-481-11HH3560 6-481-14HH

219 506 3560 6-481-11HH

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 12: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 312PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1000

GPM

220 5081770 6-485-17A3560 6-481-14HH

225 5201770 6-485-17A3560 6-481-14HH

230 5311770 6-485-17A3560 6-481-14HH

235 5431770 6-485-17A3560 6-481-14HH

240 5541770 6-485-17A3560 6-481-14HH

245 566 3560 6-481-14HH250 578 3560 6-481-14HH255 589 3560 6-481-14HH260 601 3560 6-481-14HH265 612 3560 6-481-14HH270 624 3560 6-481-14HH275 635 3560 6-481-14HH280 647 3560 6-481-14HH285 658 3560 6-481-14HH287 663 3560 6-481-14HH

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 13: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 313PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1250

GPM

45 104 1770 8-481-1250 116 1770 8-481-1252 120 1770 8-481-1255 127 1770 6-481-15C60 139 1770 6-481-15C63 146 1770 6-481-15C

65 1501770 6-481-15C1780 5-491-14A

70 1621770 6-481-15C1780 5-491-14A

75 1731770 6-481-15C1780 5-491-14A

80 1851770 6-481-15C1780 5-491-14A

84 1941770 6-481-15C1780 5-491-14A

85 1961770 6-481-15C1770 6-481-20

90 2081770 6-481-15C1770 6-481-20

93 2151770 6-481-15C1770 6-481-20

95 2191770 6-481-15C1770 6-481-20

100 2311770 6-481-18B1770 6-481-20

105 2431770 6-481-18B1770 6-481-20

110 2541770 6-481-18B1770 6-481-20

115 2661770 6-481-18B1770 6-481-20

118 2731770 6-481-18B1770 6-481-20

119 2751780 5-491-18AU*1770 6-481-18B1770 6-481-20

120 2771770 6-481-18B1770 6-481-20

125 2891780 5-491-18AU*1770 6-481-18B1770 6-481-20

130 3001780 5-491-18AU*1770 6-481-18B1770 6-481-20

132 305 3560 6-481-11HH

134 3101780 5-491-18AU*1770 6-481-18B1770 6-481-20

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 14: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 314PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1250

GPM

135 3121770 6-481-18B1770 6-481-203560 6-481-11HH

139 321 1780 6-485-16

140 323

1770 6-481-201770 6-481-18B1775 8-481-211780 6-485-163560 6-481-11HH

145 335

1770 6-481-201775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

147 3401770 6-481-201775 8-481-21

150 347

1770 6-481-201775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

152 3511770 6-481-201775 8-481-21

155 358

1770 6-481-201775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

160 370

1770 6-481-201775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

164 3791770 6-481-201775 8-481-21

165 381

1770 6-481-201775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

168 388 1770 6-481-20

170 393

1775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

175 404

1775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 15: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 315PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1250

GPM

180 416

1775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

185 427

1775 8-481-211780 6-485-163560 6-481-11HH3560 6-481-14HH

189 437 1780 6-485-16

190 4391775 8-481-213560 6-481-11HH3560 6-481-14HH

193 446 1775 8-481-21

195 4501775 8-481-213560 6-481-11HH3560 6-481-14HH

200 4623560 6-481-11HH3560 6-481-14HH

205 4743560 6-481-11HH3560 6-481-14HH

210 4853560 6-481-11HH3560 6-481-14HH

215 4973560 6-481-11HH3560 6-481-14HH

216 499 3560 6-481-11HH220 508 3560 6-481-14HH225 520 3560 6-481-14HH230 531 3560 6-481-14HH235 543 3560 6-481-14HH240 554 3560 6-481-14HH245 566 3560 6-481-14HH250 578 3560 6-481-14HH255 589 3560 6-481-14HH260 601 3560 6-481-14HH265 612 3560 6-481-14HH270 624 3560 6-481-14HH275 635 3560 6-481-14HH280 647 3560 6-481-14HH285 658 3560 6-481-14HH287 663 3560 6-481-14HH

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 16: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 316PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1500

GPM

40 92 1770 8-481-1245 104 1770 8-481-12

50 1161770 6-481-151770 8-481-12

55 127 1770 6-481-1560 139 1770 6-481-1565 150 1770 6-481-1570 162 1770 6-481-1571 164 1770 6-481-15C

75 1731770 6-481-151770 6-481-15C

80 1851770 6-481-151770 6-481-15C1770 6-481-20

81 1871770 6-481-15C1770 6-481-20

85 1961770 6-481-151770 6-481-15C1770 6-481-20

90 2081770 6-481-151770 6-481-15C1770 6-481-20

95 2191770 6-481-18B1770 6-481-20

100 2311770 6-481-18B1770 6-481-203550 6-492-10

105 2431770 6-481-18B1770 6-481-203550 6-492-10

110 2541770 6-481-18B1770 6-481-203550 6-492-10

115 2661770 6-481-18B1770 6-481-203550 6-492-10

120 2771770 6-481-18B1770 6-481-203550 6-492-10

125 2891770 6-481-18B1770 6-481-203550 6-492-10

130 3001770 6-481-18B1770 6-481-203550 6-492-10

135 3121770 6-481-201770 8-481-213550 6-492-10

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 17: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 317PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1500

GPM

140 3231770 6-481-201770 8-481-213550 6-492-10

142 328 3560 6-481-11HH

145 335

1770 6-481-201770 8-481-213550 6-492-103560 6-481-11HH

150 347

1770 6-481-201770 8-481-213550 6-492-103560 6-481-11HH

155 358

1770 6-481-201770 8-481-213550 6-492-103560 6-481-11HH

158 365 3560 6-481-14HH

160 370

1770 6-481-201770 8-481-213550 6-492-103560 6-481-11HH3560 6-481-14HH

165 381

1770 6-481-203550 6-492-103560 6-481-11HH3560 6-481-14HH

170 393

1770 8-481-213550 6-492-103560 6-481-11HH3560 6-481-14HH

175 404

1770 8-481-213550 6-492-103560 6-481-11HH3560 6-481-14HH

180 4161770 8-481-213560 6-481-11HH3560 6-481-14HH

185 4271770 8-481-213560 6-481-11HH3560 6-481-14HH

190 4391770 8-481-213560 6-481-11HH3560 6-481-14HH

195 4501770 8-481-213560 6-481-11HH3560 6-481-14HH

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 18: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 318PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

1500

GPM

200 4621770 8-481-213560 6-481-11HH3560 6-481-14HH

205 4743560 6-481-11HH3560 6-481-14HH

209 483 3560 6-481-11HH210 485 3560 6-481-14HH215 497 3560 6-481-14HH220 508 3560 6-481-14HH225 520 3560 6-481-14HH230 531 3560 6-481-14HH235 543 3560 6-481-14HH240 554 3560 6-481-14HH245 566 3560 6-481-14HH250 578 3560 6-481-14HH255 589 3560 6-481-14HH260 601 3560 6-481-14HH265 612 3560 6-481-14HH270 624 3560 6-481-14HH275 635 3560 6-481-14HH280 647 3560 6-481-14HH283 654 3560 6-481-14HH

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 19: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 319PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

2000

GPM

53 122 1770 8-481-17B55 127 1770 8-481-17B60 139 1770 8-481-17B62 143 1770 8-481-17B65 150 1770 8-481-17B70 162 1770 8-481-17B75 173 1770 8-481-17B

80 1851770 6-481-15B1770 8-481-17B

85 1961770 6-481-15B1770 8-481-17B

90 2081770 6-481-15B1770 8-481-17B

95 2191770 6-481-15B1770 8-481-17B

100 2311770 6-481-15B1770 6-481-18C1770 8-481-17B

105 2431770 6-481-18C1770 8-481-17B

110 2541770 6-481-18C1770 8-481-17B

115 2661770 6-481-18C1770 8-481-17B

120 2771770 6-481-18C1770 8-481-17B

125 2891770 6-481-18C1770 6-481-201770 8-481-17B

130 300

1770 6-481-18C1770 6-481-201770 8-481-17B1770 8-481-21

135 3121770 6-481-18C1770 6-481-201770 8-481-21

140 3231770 6-481-18C1770 6-481-201770 8-481-21

145 3351770 6-481-201770 8-481-21

150 3471770 6-481-201770 8-481-21

155 3581770 6-491-19A1770 8-481-21

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 20: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 320PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

2000

GPM

160 370 1770 8-481-21165 381 1770 8-481-21167 386 1770 8-481-24

170 393

1770 8-481-211770 8-481-24

175 4041770 8-481-211770 8-481-24

180 4161770 8-481-211770 8-481-24

185 4271770 8-481-211770 8-481-24

190 4391770 8-481-211770 8-481-24

195 4501770 8-481-211770 8-481-24

200 462 1770 8-481-24205 474 1770 8-481-24210 485 1770 8-481-24214 494 1770 8-481-24

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 21: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 321PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

2500

GPM

50 116 1770 8-491-14A55 127 1770 8-491-14A60 139 1770 8-491-14A65 150 1770 8-491-14A70 162 1770 8-491-14A74 171 1770 8-491-14A75 173 1770 8-481-17B80 185 1770 8-481-17B85 196 1770 8-481-17B90 208 1770 8-481-17B95 219 1770 8-481-17B100 231 1770 8-481-17B105 243 1770 8-481-17B110 254 1770 8-481-17B115 266 1770 8-481-17B120 277 1770 8-481-17B

125 2891770 8-481-17B1770 8-481-21A

130 3001770 8-481-21A1770 8-481-17B

135 3121770 8-491-18A1770 8-481-21A

140 323 1770 8-481-21A145 335 1770 8-481-21A150 347 1770 8-481-21A155 358 1770 8-481-21A

160 3701770 8-481-21A1770 8-481-24

165 3811770 8-481-21A1770 8-481-24

170 3931770 8-481-21A1770 8-481-24

175 4041770 8-481-21A1770 8-481-24

180 4161770 8-481-21A1770 8-481-24

185 4271770 8-481-21A1770 8-481-24

190 4391770 8-481-21A1770 8-481-24

193 446 1770 8-481-21A195 450 1770 8-481-24200 462 1770 8-481-24205 474 1770 8-481-24210 485 1770 8-481-24215 497 1770 8-481-24

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 22: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 322PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

3000

GPM

60 139 1770 8-491-14AU*65 150 1770 8-491-14AU*70 162 1770 8-491-14AU*75 173 1770 8-491-14AU*79 182 1770 8-491-14AU*80 185 1770 8-491-14A90 208 1770 10-481-18D95 219 1770 10-481-18D

100 2311775 10-481-181770 10-481-18D

102 236 1775 10-481-18

104 2401770 8-491-18A1775 10-481-18

105 2431770 8-491-18A1775 10-481-181770 10-481-18D

110 2541770 8-491-18A1775 10-481-181770 10-481-18D

115 2661770 8-491-18A1775 10-481-181770 10-481-18D

120 2771770 8-491-18A1775 10-481-181770 10-481-18D

125 2891770 8-491-18A1775 10-481-181770 10-481-18D

130 3001770 8-491-18A1775 10-481-181770 10-481-18D

135 3121770 10-492-181775 10-481-181770 10-481-18D

138 319 1770 10-481-18D

140 3231770 10-492-181775 10-481-18

145 3351770 10-492-181775 10-481-18

150 347 1770 10-492-18153 353 1770 10-492-18

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 23: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 323PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

3500

GPM

88 203 1770 10-481-18D90 208 1770 10-481-18D95 219 1770 10-481-18D99 229 1770 10-492-18

100 2311775 10-481-181770 10-481-18D

105 2431775 10-481-181770 10-481-18D

110 2541775 10-481-181770 10-481-18D

115 2661775 10-481-181770 10-481-18D

120 2771770 10-492-181775 10-481-181770 10-481-18D

125 2891770 10-492-181775 10-481-181770 10-481-18D

130 3001770 10-492-181775 10-481-181770 10-481-18D

135 3121770 10-492-181775 10-481-181770 10-481-18D

140 3231770 10-492-181775 10-481-18

145 335 1770 10-492-18151 349 1770 10-492-18

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 24: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 324PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

4000

GPM

85 196 1770 10-481-18D90 208 1770 10-481-18D94 217 1785 10-491-20

95 2191775 10-481-181785 10-491-201770 10-481-18D

100 2311775 10-481-181785 10-491-201770 10-481-18D

105 2431775 10-481-181785 10-491-201770 10-481-18D

109 2521775 10-481-181785 10-491-20

110 2541775 10-481-181785 10-491-201770 10-481-18D

115 2661785 10-491-201770 10-481-18D

120 2771785 10-491-201770 10-481-18D

125 2891785 10-491-201770 10-481-18D

130 3001785 10-491-201770 10-481-18D

134 310 1770 10-481-18D135 312 1785 10-491-20140 323 1785 10-491-20145 335 1785 10-491-20150 347 1785 10-491-20155 358 1785 10-491-20160 370 1785 10-491-20165 381 1785 10-491-20170 393 1785 10-491-20175 404 1785 10-491-20180 416 1785 10-491-20185 427 1785 10-491-20190 439 1785 10-491-20195 450 1785 10-491-20198 457 1785 10-491-20

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 25: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 325PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

4500

GPM

81 187 1770 10-481-18D85 196 1770 10-481-18D

90 2081785 10-491-201770 10-481-18D

95 2191785 10-491-201770 10-481-18D

100 2311785 10-491-201770 10-481-18D

105 2431785 10-491-201770 10-481-18D

110 2541785 10-491-201770 10-481-18D

115 2661785 10-491-201770 10-481-18D

119 275 1785 10-491-20

120 2771785 10-491-201770 10-481-18D

125 2891785 10-491-201770 10-481-18D

130 3001785 10-491-201770 10-481-18D

132 305 1770 10-481-18D135 312 1785 10-491-20140 323 1785 10-491-20145 335 1785 10-491-20150 347 1785 10-491-20155 358 1785 10-491-20160 370 1785 10-491-20165 381 1785 10-491-20170 393 1785 10-491-20175 404 1785 10-491-20180 416 1785 10-491-20185 427 1785 10-491-20188 434 1785 10-491-20190 439 1785 10-491-20195 450 1785 10-491-20

For further details on pump performance, please contact your local Aurora fire pump distributor.

Page 26: AURORA 912 Page 301P Horizontal Split ase Fire Pump Date...AURORA ® Horizontal Split ase Fire Pump 0 Hz Electric Motor Driven Section . 912. Page . 301P. Date . March 27, 2014. Electric

© 2014 Pentair Ltd.

AURORA® SELECTION TABLESHorizontal Split Case Fire Pump

60 Hz Electric Motor Driven

Section 912 Page 326PDate March 27, 2014

Electric Driven

Flow

PressureSpeed (rpm)

Pump Size and

Model(psi) (TDH)

5000

GPM

88 203 1785 10-491-2090 208 1785 10-491-2091 210 1770 10-481-18D

95 2191785 10-491-201770 10-481-18D

100 2311785 10-491-201770 10-481-18D

101 233 1785 10-491-20102 236 1785 10-491-20

105 2431785 10-491-201770 10-481-18D

110 2541785 10-491-201770 10-481-18D

114 263 1785 10-491-20

115 2661785 10-491-201770 10-481-18D

120 2771785 10-491-201770 10-481-18D

125 2891785 10-491-201770 10-481-18D

130 3001785 10-491-201770 10-481-18D

135 312 1785 10-491-20140 323 1785 10-491-20145 335 1785 10-491-20150 347 1785 10-491-20155 358 1785 10-491-20160 370 1785 10-491-20165 381 1785 10-491-20170 393 1785 10-491-20175 404 1785 10-491-20180 416 1785 10-491-20185 427 1785 10-491-20190 439 1785 10-491-20

For further details on pump performance, please contact your local Aurora fire pump distributor.