August 2007 - Prefco-HVAC Catalog 2-04 v4.pdf · Series 5000 5000 Application Series 5000...
Transcript of August 2007 - Prefco-HVAC Catalog 2-04 v4.pdf · Series 5000 5000 Application Series 5000...
August 2007
Mutliblade Fire DampersSeries 5000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Model 5000Model 5003
Combination Fire + Smoke DampersSeries 5050 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Model 5050-1Model 5050-2Model 5050-3
Series 5000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Model 5053-1Model 5053-2Model 5053-3
Series 5050 TC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6Model 5050 TC-1Model 5050 TC-2
Smoke DampersSeries 5150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Model 5150-1Model 5150-2Model 5150-3
Pressure Drop Information and Actuators . . . . . . . . .8
Curtain DampersSeries 5500 E4 / DE4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5500 E4 A5500 E4 A35500 E4 BC5500 E4 BC35500 E4 C5500 E4 C35500 E4 CR5500 E4 CR35500 E4 CO5500 E4 CO35500 E4 ML5500 E4 ML35500 DE4 A5500 DE4 A35500 DE4 BC5500 DE4 BC35500 DE4 C5500 DE4 C35500 DE4 CR5500 DE4 CR35500 DE4 CO5500 DE4 CO35500 DE4 ML5500 DE4 ML3
Series 5500 E6 / DE6 . . . . . . . . . . . . . . . . . . . . . . . . . . . .105500 E6 LPB5500 E6 BC5500 E6 CR5500 E6 CO5500 E6 LPC5500 E6 M5500 E6 ML5500 DE6 LPB5500 DE6 BC5500 DE6 CR5500 DE6 CO5500 DE6 LPC5500 DE6 M5500 DE6 ML
Series 5500 E8 / DE8 . . . . . . . . . . . . . . . . . . . . . . . . . . . .115500 E8 CR5500 E8 CO5500 E8 LPC5500 E8 M5500 E8 ML5500 DE8 CR5500 DE8 CO5500 DE8 LPC5500 DE8 M5500 DE8 ML
Series 5500 E2 / DE2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .125500 E2 A5500 DE2 A
Series 5500 SF / DSF . . . . . . . . . . . . . . . . . . . . . . . . . . . .135500 SF M5500 DSF LPB5500 DSF 2 1/25500 SF1.5 A5500 DSF1.5 A
Radiation DampersSeries 5600 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
5600 / 5600EF5610 / 5610EF5650 / 5650EF5673 / 5673EF5660 / 5660EF5680 / 5680EF
Butterfly / Single Blade Fire DampersSeries 5600F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5600F5600F35630F5650F5650F35660F5660F3
Table of Contents
About Prefco®
Prefco is a leading brand of Life-Safety Fire, Smoke, and Ceiling Radiation dampers. We are dedicated to providing the best serviceof any manufacturer serving the HVAC market today. Manufactured by Perfect Air Control, Inc., Prefco is an industry leader in the in-novation and development of these important HVAC components.
Our products are designed, manufactured, and tested in compliance with appropriate UL Standards for Safety as well as many stateand international standards.
The Prefco brand is sold throughout the United States as well as Canada, South America, the Far East, and Middle East through abroad network of representatives, distributors, and licensees, knowledgeable in all phases of HVAC design.
In the interest of product development, Prefco reserves the right to make changes without notice.
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
Series 5000 5000
Application
Series 5000 multi-blade fire dampers are UL555 fire dampers that can be eitherstatic or dynamic rated. When applied in a dynamic (fans on) system, thisdamper has been evaluated with bi-directional airflow, and is rated to 3000 FPMand 4" static pressure in compliance with UL555 6th edition.
Series 5000 meets or complies with the following as a fire damper:• CA State Fire Marshall Fire listing #3225-1518:100
• NFPA 90A & B
• All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code
UL Listings – File #R6189
• Model 5000 - UL555 1 1/2 Hour Fire Static or Dynamic
• Model 5003 - UL555 3 Hour Fire Static or Dynamic
Options & Accessories
❑ Dual Blade Position Indicator Switches (Switch#1)
❑ Factory Supplied Sleeves – 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep)
❑ Factory supplied ‘EZ Mount’ mounting angles
❑ Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems
Standard Construction
• Frame4" Wrap around full channel frame – 16 GA Galvanized Steel
• Blades22 GA Galvanized Steel, Modified Triple-V Design
• BearingsIntegral Curl in Frame Design
• Linkage14 GA Galvanized, on Blade Type (in airstream)
• Heat Responsive DeviceFusible Link 165°F standard, 212°, 250° or 350°F optional
Typical Pressure Drop Per Duct Velocity
• Pressure drop information is from a 24" x 24" damper. • Pressure drop through a smaller damper will be higher.
Duct Velocity (FPM) 500 600 700 800 900 1000 1250 1500 1750 2000 3000 4000
Full Open .010 .013 .015 .021 .030 .035 .040 .067 .080 .100 .250 .480Pressure Drop / Inches of Water
Model 5000 Standard Sizes
Type Fire RatingMin. Vertical or
HorizontalMax.
VerticalMax
Horizontal
Static 1 1/2 HR Fire 6" x 6" 120" x 84" 144" x 90"
Dynamic 1 1/2 HR Fire 6" x 6" 36" x 45" 36" x 45" Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.
Model 5003 Standard Sizes
Type Fire Rating Min. Vertical Max Vertical
Static 3 Hour Fire 6" x 6" 30" x 30"
Dynamic 3 Hour Fire 6" x 6" 30" x 30"Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.
Multiblade Fire DampersFor Use in Static or Dynamic Systems
Available Models
Model Description
5000 1 1/2 HR Fire
5003 3 HR Fire
A dim. is always width of blades
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
Series 5050
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
5050
Application
Series 5050 is a combination fire & smoke damper with a 1 1/2 Hour UL555 firerating available with your choice of Class I, II, or III UL555S Leakage rating. Thisdamper utilizes a thermally responsive electric switch to allow for the return springof the specified actuator to close the damper upon elevated temperature. Thedamper may be installed vertically or horizontally for use in barriers requiring bothfire and leakage protection. This damper has been evaluated with bi-directional air-flow, and is rated to 2000 FPM and 4" static pressure in compliance with UL555 6thedition and UL555S 4th edition.
Series 5050 meets or complies with the following as a smoke, fire or combination fire & smoke damper:• CA State Fire Marshall Fire listing #3225-1518:100
Leakage listing #3230-1518:106
• NFPA 90A & B, 92A & B
• All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code
Models 5050-1 / 5050-2 / 5050-3 UL Listings – File #R6189• UL555 1 1/2 Hour Fire
• UL555S Class I/II/III @ 250°F or 350°F
Series 5050 Standard SizesSee actuator section, pg. 8 for internal mount minimums and pressure drop information
Fire Rating Leakage RatingMin. Verticalor Horizontal
Max. VerticalMax Horizon-
tal
1 1/2 Hour Fire Class I/II/III @ 250°F 6" x 6" 120" x 84" 144" x 90"
1 1/2 Hour Fire Class I/II/III @ 350°F 6" x 6" 120" x 84" 144" x 90"
Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.
Combination Fire & Smoke Dampers1 1/2 Hour Class I/II/III Leakage
For Use in Static or Dynamic Systems
Standard Construction
• Frame4" Wrap around full channel frame – 16 GA Galvanized Steel
• Blades22 GA Galvanized Steel , Modified Triple-V Design
• BearingsIntegral Curl in Frame Design
• Linkage14 GA Galvanized, on Blade Type (in airstream)
• SealsCompression type silicone seals (Class I/II ONLY)
• Heat Responsive DeviceElectric-Thermal Disc, 165°F standard, 212°, 250° or 350°F
optional
• SealantUL Certified silicone caulk (sleeved units only)
Available ModelsModel Description
5050-1 / Class I 1 1/2 HR Fire5050-2 / Class II 1 1/2 HR Fire
5050-3 / Class III 1 1/2 HR Fire
A dim. is always width of blades
Options & Accessories
❑ Dual Blade Position Indicator Switches (Switch#1)
❑ Factory Supplied Sleeves – 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep. Dampers with external mounted actuators are available with a 18 gauge side plate, if no factory sleeve is desired)
❑ Factory supplied ‘EZ Mount’ mounting angles
❑ Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems
Internally mounted actuator
Series 5053
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
5053Application
Series 5053 is a combination fire & smoke damper with a 3 Hour UL555 fire rat-ing available with your choice of Class I, II, or III UL555S Leakage rating. This damper utilizes a thermally responsive electric switch to allow for the returnspring of the specified actuator to close the damper upon elevated temperature.The damper may be installed vertically for use in barriers requiring both fire andleakage protection. This damper has been evaluated with bi-directional airflow, andis rated to 2000 FPM and 4" static pressure in compliance with UL555 6th editionand UL555S 4th edition.
Series 5053 meets or complies with the following as a smoke, fire or combina-tion fire & smoke damper:• CA State Fire Marshall Fire listing #3225-1518:100
Leakage listing #3230-1518:106
• NFPA 90A & B, 92A & B
• All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code
UL Listings – File #R6189• UL555 3 Hour Fire
• UL555S Class I/II/III @ 250°F or 350°F
Options & Accessories
❑ Dual Blade Position Indicator Switches (Switch#1)
❑ Factory Supplied Sleeves – 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep. Dampers with external mounted actuators are available with a 18 gauge side plate, if no factory sleeve is desired)
❑ Factory supplied ‘EZ Mount’ mounting angles
❑ Single or Dual Blade stiffeners - for strength & stabilityof wider units in high pressure systems
Standard Construction
• Frame4" Wrap around full channel frame – 16 GA Galvanized Steel
• Blades22 GA Galvanized Steel , Modified Triple-V Design
• BearingsIntegral Curl in Frame Design
• Linkage14 GA Galvanized, on Blade Type (in airstream)
• SealsCompression type silicone seals (Class I/II ONLY)
• Heat Responsive DeviceElectric-Thermal Disc, 165°F standard, 212°, 250° or 350°F optional
• SealantUL Certified silicone caulk (sleeved units only)
Combination Fire & Smoke Dampers3 Hour Class I/II/III LeakageFor Use in Static or Dynamic Systems
Series 5053 Standard SizesSee actuator section, pg. 8 for internal mount minimums and pressure drop information
Fire Rating Leakage Rating Min. Vertical Max. Vertical
3 Hour Fire Class I/II/III @ 250°F 6" x 6" 30" x 30"
3 Hour Fire Class I/II/III @ 350°F 6" x 6" 30" x 30"
Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.
Available ModelsModel Description
5053-1 / Class I 3 HR Fire
5053-2 / Class II 3 HR Fire5053-3 / Class III 3 HR Fire
A dim. is always width of blades
Series 5050 TC 50
50 T
CApplication
Series 5050TC is a combination fire and smoke damper that is UL classified forinterior tunnel corridor ceiling penetrations. When installed in a tunnel-type corri-dor ceiling, the damper assembly carries a 1 hour UL555 fire rating and a ClassI/II UL555S leakage rating.
This damper also can be applied as a standard fire and smoke damper. It may bemounted horizontally or vertically, is approved for bi-directional airflow, and israted to 2000 FPM and 4" static pressure in compliance with UL555 6th editionand UL555S 4th edition.
Series 5050TC meets or complies with the following as a corridor smoke, fire orcombination fire & smoke damper:• CA State Fire Marshall Fire listing #3225-1518:100
Leakage listing #3230-1518:106
• NFPA 90A & B, 92A & B
• All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code
UL Listings – File #R6189• UL555 1 Hour Fire Corridor - 1 1/2 Hour Fire Wall / Floor
• UL555S Class I/II @ 250°F or 350°F
Options & Accessories
❑ Dual Blade Position Indicator Switches (Switch#1)
❑ Factory Supplied Sleeves – 18 or 14 Gauge, 18" or 24"deep
(For other gauges and depths, contact your local rep)
❑ Factory supplied ‘EZ Mount’ mounting angles
❑ Single or Dual Blade stiffeners - for strength & stability ofwider
units in high pressure systems
Standard Construction
• Frame4" Wrap around full channel frame – 16 GA Galvanized Steel
• Blades22 GA Galvanized Steel, Modified Triple-V Design
• BearingsIntegral Curl in Frame Design
• Linkage14 GA Galvanized, on Blade Type (in airstream)
• SealsCompression type silicone seals
• Heat Responsive DeviceElectric-Thermal Disc, 165°F standard, 212°, 250° or 350°F optional
• SealantUL Certified silicone caulk (sleeved units only)
Series 5050 TC Standard SizesSee actuator section, pg. 8 for internal mount minimums and pressure drop information
Application Fire Rating Leakage Rating Min. Vert. or Horiz. Max Vert. Max Horiz.
Corridor 1 Hour Class I / II @ 250°F 6" x 6" N/A 24" x 24"
Corridor 1 Hour Class I / II @ 350°F 6" x 6" N/A 24" x 24"
Fire/Smoke 1 1/2 Hour Class I / II @ 250°F 6" x 6" 24" x 24" 24" x 24"
Fire/Smoke 1 1/2 Hour Class I / II @ 350°F 6" x 6" 24" x 24" 24" x 24"
Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.
Combination Fire& Smoke Dampers
For Tunnel Corridor Applications For Use in Static or Dynamic Systems
A dim. is always width of blades
Externally mounted actuator
Internally mounted actuator
Available ModelsModel Description
5050TC-1 / Class I 1 1/2 HR Fire
5050TC-2 / Class II 1 1/2 HR Fire
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
Series 5150
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
5150
Application
Series 5150 is a UL555S approved Smoke damper available for Class I, II, orIII. Series 5150 can utilize a variety of internally or externally mounted actu-ators. The damper may be installed vertically or horizontally in ducts pene-trating barriers requiring leakage protection, within 24" of the barrier beingprotected. This damper has been evaluated with bi-directional airflow, andis rated to 2000 FPM and 4" static pressure in compliance UL555S 4th edi-tion.
Series 5150 meets or complies with the following as a smoke damper:• CA State Fire Marshall Leakage listing #3230-1518:106
• NFPA 90A & B, 92A & B
• All major building codes, including BOCA, ICBO/UBC, SBCCI & the ICC International Code
UL Listings – File #R6189
• UL555S Class I/II/III @ 250°F or 350°F
Options & Accessories
❑ Dual Blade Position Indicator Switches (Switch#1)
❑ Factory Supplied Sleeves – 18 or 14 Gauge, 18" or 24" deep (For other gauges and depths, contact your local rep. Dampers with external mounted actuators are available with a 18 gauge side plate, if no factory sleeve is desired)
❑ Factory supplied ‘EZ Mount’ mounting angles
❑ Single or Dual Blade stiffeners - for strength & stability of wider units in high pressure systems
Standard Construction
• Frame4" Wrap around full channel frame – 16 GA Galvanized Steel
• Blades22 GA Galvanized Steel , Modified Triple-V Design
• BearingsIntegral Curl in Frame Design
• Linkage14 GA Galvanized, on Blade Type (in airstream)
• SealsCompression type silicone seals (Class I/II ONLY)
• SealantUL Certified silicone caulk (sleeved units only)
Smoke DampersClass I/II/III LeakageFor Use in Static or Dynamic Systems
Series 5150 Standard SizesSee actuator section, pg. 8 for internal mount minimums and pressure drop information
Leakage RatingMin. Verticalor Horizontal
Max. Vertical or Horizontal
Class I/II/III @ 250°F 6" x 6" 144" x 96" or 288" x 48"
Class I/II/III @ 350°F 6" x 6" 144" x 96" or 288" x 48"
*Dampers will be fabricated 1/4" under ordered dimensions unless otherwise specified.
Available ModelsModel
5150-1 / Class I5150-2 / Class II5150-3 / Class III
A dim. is always width of blades
Series 5050, 5053, 5050 TC and 5150 Pressure Drop
Series 5050, 5053, 5050 TC and 5150 Actuators
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
Specifications
Actuators will be mounted externally on the right side unless otherwise specified.Actuators available for internal or external mount (all must be factory mounted):
* Damper must be at least 13" in height for actuator to mount internally.* Unit must be 10" or greater in width for any internal actuator mounting orientation.* The factory will mount the actuator parallel to the damper, whenever height allows,
unless otherwise specified.
Actuator Model Voltage (AC)Power Consumption
Running Holding
Belimo FSNF120 120 0.23A, 18W 0.09A, 6W
Belimo FSNF24 24 24VA 24VA
Honeywell ML4115 120 0.18A, 18W 0.11A, 9W
Honeywell ML8115 24 16VA 8VA
Honeywell MS4209F, MS4309F 120 0.25A, 23W 0.13A, 7W
Honeywell MS8209F, MS8309F 24 23VA 7VA
Honeywell MS4120F 120 0.35A, 35W 0.15A, 10W
Honeywell MS8120F 24 45VA 10VA
Mounting Configurations
Actuator Mounted Parallel to the dampe
(140)
(98)
(259)
(110)
(102)
Actuator Mounted perpendicular to the damper
*Available Down ToMin Height
(140)
(270)
(98)
(259)
(102)
Actuator Mounted Parallel to the damp
(140)
(84)
(272)
(111)
(102)
Actuator Mounted
perpendicular to the damper
*Available Down To
Min Height
(140)
(292)
(84)
(272)
(102)
Actuator Mounted Parallel to the damper
(140)
(57)
(191)
(122)
(102)
Actuator Mounted perpendicular to the damper
*Available Down ToMin Height
(140)
(233)
(130)
(191)
(43)
(102)
*Damper height must be at least 18"for actuator to mount internally.
*Damper height must be at least 18"for actuator to mount internally.
*Damper height must be at least 13"for actuator to mount internally.
Typical Pressure Drop Per Duct Velocity
Pressure drop information is from a 24" x 24" damper. Pressure drop through a smaller damper will be higher.
Duct Velocity (FPM) 500 600 700 800 900 1000 1250 1500 1750 2000 3000 4000
Full Open .010 .013 .015 .021 .030 .035 .040 .067 .080 .100 .250 .480
Pressure Drop / Inches of Water
Series 5500 E4/ DE4
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
E4/D
E4
Standard Construction
• FrameWrap-around frame - 21 GA Galvanized Steel
• Blades - Low ProfileRoll Formed - 21 GA Galvanized Steel
• Closure Springs (Horizontal Models)Stainless Steel Constant Force Coil
• Fusible Link - UL-33UL Listed 165 F (standard), 212 F (optional) McCabe Link (optional)
UL555 1 1/2 Hour Fire - Static
5500 E4
A V or H Type A - Frame and blades within airstream
BC V or H Type B - Blades removed from airstream via cap
CR V or H Type C - Frame blades removed from airstream sq. to round
CO V or H Type C - Frame and blades are removed from airstream sq. to oval
C V or H Type C - Frame and blades are removed from airstream
M V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream
UL555 3 Hour Fire - Dynamic
5500DE4
A3 V Type A - Frame and blades within airstream
BC3 V Type B - Blades removed from airstream via cap
CR3 V Type C - Frame blades removed from airstream sq. to round
CO3 V Type C - Frame and blades are removed from airstream sq. to oval
C3 V Type C - Frame and blades are removed from airstream
M3 V Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML3 V Slip connection oversized 2" from duct removes frame and partial blades from airstream
UL555 1 1/2 Hour Fire - Dynamic
5500DE4
A V or H Type A - Frame and blades within airstream
BC V or H Type B - Blades removed from airstream via cap
CR V or H Type C - Frame blades removed from airstream sq. to round
CO V or H Type C - Frame and blades are removed from airstream sq. to oval
C V or H Type C - Frame and blades are removed from airstream
M V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream
UL555 3 Hour Fire - Static
5500 E4
A3 V Type A - Frame and blades within airstream
BC3 V Type B - Blades removed from airstream via cap
CR3 V Type C - Frame blades removed from airstream sq. to round
CO3 V Type C - Frame and blades are removed from airstream sq. to oval
C3 V Type C - Frame and blades are removed from airstream
M3 V Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML3 V Slip connection oversized 2" from duct removes frame and partial blades from airstream
Application
Series 5500 E4 or DE4 curtain fire dampers are UL Classified for installation in walls,floors, and partitions requiring a fire damper. Series 5500 E4 or DE4 is available witha UL555 Listing of either 1 1/2 or 3 hours. These dampers may be installed verticallyor horizontally in static (5500 E4) or dynamic (5500 DE4) systems.
Series 5500 E4 or DE4 meets or complies with the following as a fire damper:• NFPA Standards
• All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code
• BS 476:Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1 PREN 1366-2 Internationally Tested 4 hour
• CA State Fire Marshall - #3225-1518-101
UL Listing – File #R6189• UL555 Listing 1 1/2 or 3 Hour Static (5500 E4)
• UL555 Listing 1 1/2 or 3 Hour Dynamic (5500 DE4)
Curtain Fire Dampers (4” Frame)For Use in Static or Dynamic Systems
Series 5500 E6/DE6
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
E6/
DE
6
Standard Construction
• Blades - Low ProfileRoll Formed - 21 GA Galvanized Steel
• Closure Springs (Horizontal Models)Stainless Steel Constant Force Coil
• Fusible Link - UL-33UL Listed 165 F (standard), 212 F (optional)McCabe Link (optional).
Curtain Fire Dampers (6” Frame)
For Use in Static or Dynamic Systems
UL555 1 1/2 Hour Fire - Static
5500 E6
LPB V or H Type A - Frame and blades within airstream
BC V or H Type B - Blades removed from airstream via cap
CR V or H Type C - Frame blades removed from airstream sq. to round
CO V or H Type C - Frame and blades are removed from airstream sq. to oval
LPC V or H Oversized 2" from duct removes frame and partial blades from airstream
M V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream
UL555 1 1/2 Hour Fire - Dynamic
5500 DE6
LPB V or H Type A - Frame and blades within airstream
BC V or H Type B - Blades removed from airstream via cap
CR V or H Type C - Frame blades removed from airstream sq. to round
CO V or H Type C - Frame and blades are removed from airstream sq. to oval
LPC V or H Oversized 2" from duct removes frame and partial blades from airstream
M V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream
Application
Series 5500 E6 or DE6 curtain fire dampers are UL Classified for installation inwalls, floors, and partitions with a fire rating of less than 3 hours. These dampersmay be installed vertically or horizontally in static (5500 E6) or dynamic (5500DE6) systems.
Series 5500 E6 or DE6 meets or complies with the following as a fire damper• NFPA Standards
• All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code
• BS 476: Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1PREN 1366-2 Internationally Tested 4 hour
• CA State Fire Marshall - #3225-1518-101
UL Listing – File #R6189• UL555 Listing 1 1/2 Hour Static (5500 E6)
• UL555 Listing 1 1/2 Hour Dynamic (5500 DE6)
Series 5500 E8/DE8
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
E8/D
E8
Application
Series 5500 E8 or DE8 curtain fire dampers are UL Classified for installation inwalls, floors, and partitions with a fire rating of less than 3 hours. These dampersmay be installed vertically or horizontally in static (5500 E8) or dynamic (5500DE8) systems. The 8” frame allows for installation without the use of an additionsleeve.
Series 5500 E8 or DE8 meets or complies with the following as a fire damper:• NFPA Standards
• All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code
• BS 476:Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1PREN 1366-2 Internationally Tested 4 hour
• CA State Fire Marshall - #3225-1518-101
UL Listing – File #R6189• UL555 Listing 1 1/2 Hour Static (5500 E8)
• UL555 Listing 1 1/2 Hour Dynamic (5500 DE8)
Standard Construction
• Blades - Low ProfileRoll Formed - 21 GA Galvanized Steel
• Closure Springs (Horizontal Models)Stainless Steel Constant Force Coil
• Fusible Link - UL-33UL Listed 165 F (standard), 212 F (optional)McCabe Link (optional)
Curtain Fire Dampers (8” Frame)For Use in Static or Dynamic Systems
UL555 1 1/2 Hour Fire - Static
5500 E8
CR V or H Type C - Frame blades removed from airstream sq. to round
CO V or H Type C - Frame and blades are removed from airstream sq. to oval
LPC V or H Oversized 2" from duct removes frame and partial blades from airstream
M V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream
UL555 1 1/2 Hour Fire - Dynamic
5500 DE8
CR V or H Type C - Frame blades removed from airstream sq. to round
CO V or H Type C - Frame and blades are removed from airstream sq. to oval
LPC V or H Oversized 2" from duct removes frame and partial blades from airstream
M V or H Flanged frame, oversized 2" from duct removes frame and partial blades from airstream
ML V or H Slip connection oversized 2" from duct removes frame and partial blades from airstream
Series 5500 E2/DE2
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
E2/
DE
2Application
Series 5500 E2 or DE2 curtain fire dampers are UL Classified for installation inwalls, floors, and partitions with a fire rating of less than 3 hours. These dampersmay be installed vertically or horizontally in static (5500 E2) or dynamic (5500DE2) systems.
Series 5500 E2 or DE2 meets or complies with the following as a fire damper:• NFPA Standards
• All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code
• BS 476:Part 8; 20 & 22; ISO/DIS 834-1 & 10294-1 PREN 1366-2 Internationally Tested 4 hour
• CA State Fire Marshall - #3225-1518-101
UL Listing – File #R6189• UL555 Listing 1 1/2 Hour Static (5500 E2)
UL555 Listing 1 1/2 Hour Dynamic (5500 DE2)
Standard Construction
• Blades - Low ProfileRoll Formed - 21 GA Galvanized Steel
• Closure Springs (Horizontal Models)Stainless Steel Constant Force Coil
• Fusible Link - UL-33UL Listed 165 F (standard), 212 F (optional)McCabe Link (optional)
Curtain Fire Dampers(2” Frame - “Thin-Line”)
For Use in Static Systems or Dynamic Systems
UL555 1 1/2 Hour Fire - Static
5500 E2 A V or H Type A - Frame and blades within airstream
UL555 1 1/2 Hour Fire - Dynamic
5500 DE2 A V or H Type A - Frame and blades within airstream
Series 5500 SF/DSF
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
SF
/DS
F
For more product information visit us at www.prefco-hvac.com
13
Application
Series 5500 SF or DSF curtain fire dampers are UL Classified for installation inwalls, floors, and partitions with a fire rating of less than 3 hours. These dampersmay be installed vertically or horizontally in static (5500 SF) or dynamic (5500DSF) systems.
Series 5500 SF or DSF meets or complies with the following as a fire damper:• NFPA Standards
• All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code
• CA State Fire Marshall - #3225-1518-101
UL Listing – File #R6189• UL555 Listing 1 1/2 Hour Static (5500 SF)
• UL555 Listing 1 1/2 Hour Dynamic (5500 DSF)
Standard Construction
• Blades - Full Length Hinge 21 GA Galvanized Steel
• Closure Springs Stainless Steel
• Fusible Link - UL-33UL Listed 212F (standard) 165 F (optional)McCabe Link (optional)
Curtain Fire Dampers (“Sub Frame”)For Use in Static Systems or Dynamic Systems
4 1/2” Wide Blade - “Sub” Frame
UL555 1 1/2 Hour Fire - Static
5500 SF LPB V or H Type A - Frame and blades within airstream
UL555 1 1/2 Hour Fire - Dynamic
5500 DSF LPB V or H Type A - Frame and blades within airstream
2 1/2” Wide Blade - “Sub” Frame
UL555 1 1/2 Hour Fire - Static
5500 SF 2 1/2 V or H Type A - Frame and blades within airstream
UL555 1 1/2 Hour Fire - Dynamic
5500 DSF 2 1/2 V or H Type A - Frame and blades within airstream
1 1/2” Wide Blade - “Sub” Frame
UL555 1 1/2 Hour Fire - Static
5500 SF 1 1/2 V or H Type A - Frame and blades within airstream
UL555 1 1/2 Hour Fire - Dynamic
5500 DSF 1 1/2 V or H Type A - Frame and blades within airstream
Series 5600
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
5600
Application
Series 5600 provide fire and heat radiation protection of HVAC penetrations infloor/ceiling and roof/ceiling assemblies with restrained or unrestrained ratings of ei-ther 2 or 3 hours. Standard fire dampers (1 1/2 or 3 hr) do not provide the requiredheat protection for ceiling penetrations.
Series 5600 meets or complies with the following as a ceiling radiation damper:• NFPA Standards
• All major building codes including BOCA, ICBO/UBC, SBCCI, and ICC International Code
• CA State Fire Marshall - #3225-1518-103
UL Listing – File #R7365• UL555C Listing 2 or 3 Hour
Standard Construction
• Frame21 GA Galvanized Steel
• Blades - Full Length Hinge 21 GA Galvanized Steel
• Closure Springs Stainless Steel
• Fusible Link - UL-33UL Listed 212F (standard) 165 F (optional)McCabe Link (optional)
• Blade InsulationCeramic fiber
Ceiling Radiation Dampers
Series 5600
Round Butterfly
5600 H Un-insulated - 2 Hours
5600EF H Un-insulated - 2 Hours, w/extended flange
5610 H Insulated - 3 Hours
5610EF H Insulated - 3 Hours, w/extended flange
Square/Rectangular Butterfly
5660 H Un-insulated - 2 Hours
5660EF H Un-insulated - 2 Hours, w/extended flange
5680 H Insulated - 3 Hours
5680EF H Insulated - 3 Hours, w/extended flange
Square/Rectangular Single Blade
5650 H Un-insulated - 2 Hours
5650EF H Un-insulated - 2 Hours, w/extended flange
5673 H Insulated - 3 Hours
5673EF H Insulated - 3 Hours, w/extended flange
Series 5600F
©2004 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
5600F
For more product information visit us at www.prefco-hvac.com
15
Application
Series 5600F fire damper is UL Classified for installation inwalls, floors, and partitions available with a UL555 Listing ofeither 1 1/2 or 3 hours. This damper may be installed verti-cally or horizontally in static HVAC systems that automaticallyshut down in the event of fire
Series 5600F meets or complies with the following as a firedamper:• NFPA Standards
• All major building codes including BOCA,ICBO/UBC, SBCCI, and ICC International Code
• CA State Fire Marshall - #3225-1518-101
UL Listing – File #R6189• UL555 Listing 1 1/2 or 3 Hour
Standard Construction
• Frame21 GA Galvanized Steel
• Blades - Full Length Hinge 21 GA Galvanized Steel
• Closure Springs Stainless Steel
• Fusible Link - UL-33UL Listed 212F (standard) 165 F (optional)McCabe Link (optional)
Butterfly/Single Blade Fire Dampers
Series 5600 F
Round Butterfly
5600F V or H 1 1/2 hours
5600F3 V 3 hours
Round Single Blade
5630F V 1 1/2 hours
Square/Rectangular Butterfly
5660F V or H 1 1/2 hours
5660F3 V 3 hours
Square/Rectangular Single Blade
5650F V or H 1 1/2 hours
5650F3 V 3 hours
©2007 Perfect Air Control, Inc. • All Rights Reserved • 1310 N. Hercules Ave. • Clearwater, FL 33765 • (800) 437-6653 • (727) 443-7167 Fax • www.prefco-hvac.com
Perfect Air Control, Inc. manufactures Prefco products under one or more of the following patents.3,648,328/3,725,972/3,727,663/3,796,248/3,796,249/3,814,165/3,833,989/3,866,656/3,866,657/3,889,3143,899,156/3,960,065/3,977,456/4,040,304/4,041,570/4,074,388/4,080,978/4,081,173/4,099,292/4,113,2304,133,232/4,114,656/4,146,048/4,241,748/4,263,930/4,295,486/4,185,658/4,472,999/4,442,862/4,372,3424,338,967/4,301,569/4,219,185/4,474,167/4,372,485/4,195,384/4,200,954/4,213,227/4,287,638/3,273,6823,327,764/4,219,041/4,183,129/4,185,657/4,277,870/4,304,427/4,404,990/4,390,123/4,494,449/RE 323623,401,734/3,580,160/3,605,603 Other Patents Pending. Also Patented in other countries.
Prefco-Johnson Tech Air Control Inc. manufactures Prefco products under one or more of the following patents.3,648,328/3,725,972/3,727,663/3,796,248/3,796,249/3,814,165/3,833,989/3,866,656/3,866,657/3,889,3143,899,156/3,960,065/3,977,456/4,040,304/4,041,570/4,074,388/4,080,978/4,081,173/4,099,292/4,113,2304,133,232/4,114,656/4,146,048/4,241,748/4,263,930/4,295,486/4,185,658/4,472,999/4,442,862/4,372,3424,338,967/4,301,569/4,219,185/4,474,167/4,372,485/4,195,384/4,200,954/4,213,227/4,287,638/3,273,6823,327,764/4,219,041/4,183,129/4,185,657/4,277,870/4,304,427/4,404,990/4,390,123/4,494,449/RE 323623,401,734/3,580,160/3,605,603 Other Patents Pending. Also Patented in other countries.