Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia •...

24
End User End User Experience Experience with with Ammonia Ammonia and and CO CO 2 2 Paul Homsy

Transcript of Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia •...

Page 1: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

End UserEnd UserExperience Experience

withwithAmmonia Ammonia

and and COCO22

Paul Homsy

Page 2: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

2International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Presentation Steps

Priority to Natural Refrigerants

Beyond codes

20’

Page 3: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

3International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Industrial Refrigeration Industrial Refrigeration

• CO2 / NH3 cascade• CO2 as brine•• COCO22 / NH/ NH3 3 cascadecascade•• COCO22 as brineas brine

Negative TemperaturesNegative Temperatures

• NH3 Chillers• HC’s , CO2 ?•• NHNH33 ChillersChillers•• HCHC’’s , s , COCO22 ??

Positive TemperaturesPositive Temperatures

Priority to natural refrigerants

Deployment on going, cost and availability issue for small size units

Page 4: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

4International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

COCO22NH3

CO2 / NH3 cascade (Japan - Coffee Freeze Drying)

Page 5: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

5International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

No.1No.1 UNIT UNIT

NH3NH3EVAPORATIVEEVAPORATIVECONDENSERCONDENSER

NH3NH3

CASCADECASCADECONDENSERCONDENSER

No.2No.2 UNITUNIT

NH3NH3

No.3No.3 UNITUNIT

NH3NH3

No.4No.4 UNITUNITSTANDBYSTANDBY

NH3NH3NH3NH3RECEIVERRECEIVER

CO2CO2CO2CO2 CO2CO2 CO2CO2

CO2 HPCO2 HP--RECEIVERRECEIVER

CO2 LPCO2 LP--RECEIVERRECEIVER CO2 LPCO2 LP--

RECEIVERRECEIVER

CO2 LIQUIDCO2 LIQUID

TO ICE CONDENSERTO ICE CONDENSERCO2 LIQUID CO2 LIQUID PUMPPUMP

CO2 LIQUID CO2 LIQUID PUMPPUMP

CO2 Gas CO2 Gas

CO2 LIQUID CO2 LIQUID

TO AIR TO AIR COOLERCOOLER

CO2 Gas CO2 Gas

HighHigh side (NHside (NH33))is is separated in 4separated in 4

Low side (COLow side (CO22) ) is is commoncommon

CO2 / NH3 cascade (Japan - Coffee Freeze Drying)

Page 6: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

6International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

World first CO2 ice cream freezer

• First skid mounted unit Thailand IC Factory • Refrigeration capacity: @ -45°C/-7°C/+38°C: 380 kW

High stageNH3

Low stageCOCO22

Page 7: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

7International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

CO2 / NH3 cold store (Moscow)

Page 8: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

8International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

CO2 / NH3 cascade (Czech Republic)

COCO22 piston piston compressorscompressors

Page 9: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

9International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Ammonia Chiller - Nigeria

Page 10: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

10International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Ammonia chilled water plant Indonesia

• Cooling capacity 3’000 kW • Water supply temperature +3°C• 2 screw compressor package• 2 Falling film evaporator

Page 11: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

11International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Ammonia Water Chiller Shanghai

• 2 screw compressors (duo) • Cooling Capacity: 1’000 kW• Ammonia charge: 110 kg• Water temperature +12°C/+7°C• Evaporator/Condenser: Plate Heat Exchangers

Page 12: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

12International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Ammonia Water Chiller Vietnam

• 1 piston compressor • Cooling Capacity: 700 kW• Ammonia charge: 30 kg• Water temperature: +13°C/+7°C• Evaporator/Condenser: Plate Heat Exchangers

Page 13: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

13International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Low charge Ammonia water chillers for buildings

Computers Servers centre

NH3 absorber

R&D Centre~100 kW, 5 kg NH3

installed above the walk-on ceiling

Page 14: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

14International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

WellNes centre - Vevey HO - Switzerland

NHNH33 glycol Chillerglycol Chiller

COCO22 DX DX unitunit

Page 15: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

15International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Flammable HC water chillers

Page 16: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

16International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Public information portal www.nestle.com

Page 17: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

17International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Presentation Steps

Priority to Natural Refrigerants

Beyond Codes

Page 18: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

18International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Beyond codes

• Compliance to codes is not enough. Not all aspects are covered: The way the equipment is arranged, installed, operated and maintained. A safe component that is not properly installed or maintained can lead to unsafe situations.• With the number of ammonia systems increasing, new safeguards are needed to avoid incidents that will be detrimental to ammonia and that can often be avoided.• Safety of refrigeration plants is impacted by all 4 major activities:

1. Design and Manufacturing Manufacturer/Contractor2. Installation Contractor3. Operation End user / Contractor4. Maintenance End user / Contractor

Page 19: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

19International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Safe Accesses

Good access is essential to allow to maintenance personnel to work in safe conditions and to easily access all parts of the ammonia circuits, while carrying a tool box.

Page 20: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

20International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Condensations

Frost

Defective insulation

Page 21: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

21International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Good, long lasting protection against corrosion: Grease tape

Heavy corrosion under insulation

One of the most common diseases of refrigeration plants

Page 22: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

22International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Defrosting with a screw driver and a hammer…

Punctured aluminium coilPunctured aluminium coil

Punctured steel coilPunctured steel coil

Page 23: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

23International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

A code of good practice and know how development are needed.

Conclusion

Ammonia is an excellent refrigerant, much safer when used in combination with CO2Ammonia is an excellent refrigerant, much safer when used in combination with CO2

Poor example of outsourcing: Any live opened pipe must be blinded with plain counter flanges, not relying on shut off valves alone.

Example of a suction valve flange just blanked with a piece of tape.

Page 24: Atmosphere 2009 Paul Homsy Brussels October 2009 · Ammonia chilled water plant Indonesia • Cooling capacity 3’000 kW • Water supply temperature +3°C • 2 screw compressor

25International Conference on Natural Refrigerants International Conference on Natural Refrigerants -- October 19October 19--20, 2009, Brussels 20, 2009, Brussels

Thank you for the opportunityThank you for the opportunity