ASHIDA Numerical Single Pole EF Protection Relay (Preliminary)
Ashida Relay
Transcript of Ashida Relay
-
8/11/2019 Ashida Relay
1/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
TITLE
ASHIDA Elec tronics Pv t. Ltd.
Page1/1
ADITYA SERIES
Over Current Relay
Version 1.0(For Software V1.xx and V2.xx)
Technical Manual
-
8/11/2019 Ashida Relay
2/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page1/10
CONTENTS
Safe ty Ins t ruc t ion
In t roduc t ion
Hand l i ng & Case D imens ion
User s Gu ide
Menu Content Table
Techn ic a l Spec i f i c a t ion
A pp l i cat i on Gu id e
Commun ica t ion
Ins ta l la t ion , Relay Tes t ing & Commis s ion i ng
Per io d ic Tes t ing
Deta i ls o f In te rnal C i rcu i t D iagram
Prob lems Occurr ed & Hardware Sof tw are Rev is ion
-
8/11/2019 Ashida Relay
3/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page2/10
1.0 SAFETY INSTRUCTION
CONTENTS
1.1 Introduction 3
1.2 Healthy & Safety 3
1.3 Symbol & External Labels 4
1.4 Decommissioning & Disposal 4
1.5 Technical Specifications For Safety 5
1.5.1 Protective Fuse Rating 5
1.5.2 Protective Class 5
1.5.3 Installation Category 5
1.5.4 Environment 5
1.6 CE Marking 5
1.7 Revision Note 6
2.0 INTRODUCTION
CONTENTS
2.1 General 32.2 Features 4
2.3 How to use the Manual 5
2.4 Ordering Information 7
2.5 Revision Note 9
3.0 HANDLING & CASE DIMENSION
CONTENTS
3 Handling 3
3.1 Receipt of Relay 3
3.2 Unpacking 3
3.3 Handling of Electric Components 3
3.4 Storage 4
3.5 Dimensions 4
3.5.1 Connections of Power Terminals and Signal Terminals 4
3.5.2 Earthing 4
3.6 Cabinet drawing 5
3.7 Revision Note 6
-
8/11/2019 Ashida Relay
4/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page3/10
4.0 USERS GUIDE
CONTENTS
4.1 Front Panel and Control 5
4.2 Users Interface 7
4.2.1 LCD Display 7
4.2.2 Touch Keys 7
4.2.3 LEDs 8
4.2.4 RS485 8
4.2.5 RS232 8
4.3 Password 9
4.3.1 Password Entry & Changing the Password 9
4.3.2 Clear Password 10
4.3.3 Default Settings 11
4.3.3.1 General Settings 11
4.3.3.2 Protection Settings 12
4.4 Menus 15
4.4.1 Default Display 15
4.4.2 Main Menu List 16
4.4.2.1 Main Menu List Details 174.4.3 M e a su r e m e n t 23
4.4.3.1 To View - Measurement 23
4.4.4 Ge n e r a l S et t i n g 24
4.4.4.1 To Set General Setting 24
4.4.4.2 To View General Setting 28
4.4.5 Ov e r Cu r r e n t ( OC- G 1 ) S e t t i n g 29
4.4.5.1 To Set OC-G1 Setting 29
4.4.5.2 To View OC-G1 Setting 32
4.4.6 Ea r t h F au l t ( EF- G 1 ) S e t t i n g 33
4.4.6.1 To Set EF-G1 Setting 33
4.4.6.2 To View EF-G1 Setting 36
4.4.7 3 I o - G1 S et t i n g 37
4.4.7.1 To Set 3Io-G1 Setting 37
4.4.7.2 To View 3Io-G1 Setting 40
4.4.8 Ne g a t i v e Ph a s e Se q u e n c e El em e n t ( N PS - G1 ) S e t t i n g 41
4.4.8.1 To Set NPS-G1 Setting 41
4.4.8.2 To View NPS-G1 Setting 43
-
8/11/2019 Ashida Relay
5/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page4/10
4.4.9 Ov e r Cu r r e n t ( OC- G 2 ) S e t t i n g 44
4.4.9.1 To Set OC-G2 Setting 44
4.4.9.2 To View OC-G2 Setting 47
4.4.10 Ea r t h F au l t ( EF- G 2 ) S e t t i n g 48
4.4.10.1 To Set EF-G2 Setting 48
4.4.10.2 To View EF-G2 Setting 51
4.4.11 3 I o - G2 S et t i n g 52
4.4.11.1 To Set 3Io-G2 Setting 52
4.4.11.2 To View 3Io-G2 Setting 55
4.4.12 Ne g a t i v e Ph a s e Se q u e n c e El em e n t ( N PS - G2 ) S e t t i n g 56
4.4.12.1 To Set NPS-G2 Setting 56
4.4.12.2 To View NPS-G2 Setting 58
4.4.13 A u t o R e cl o s e r ( ARR ) S e t t i n g 59
4.4.13.1 To Set ARR Setting 59
4.4.13.2 To View ARR Setting 61
4.4.14 R e la y / L ED Co n f i g u r a t i o n 62
4.4.14.1 Bit Definition for Relay/LED Configuration 62
4.4.14.2 List of Protection Function and Digital Inputs 63
4.4.14.3 To Set Relay/LED Configuration 67
4.4.14.4 To View Relay/LED Configuration 724.4.14.5 Example of Relay / LED Configuration 73
4.4.15 F a u l t 1 88
4.4.15.1 To View Fault 1 Data [Fault 2 to Fault 20] 88
4.4.16 S t a t u s 89
4.4.16.1 To View Status 89
4.4.17 Er r o r L o g 89
4.4.17.1 To View Error Log 89
4.4.18 C l o s e 90
4.4.19 T r i p 90
4.4.20 A c t i v e G r o u p 91
4.4.20 D a t e T im e S et t i n g 92
4.4.20.1 To Set Date Time setting 92
4.4.20.2 To View Date Time Setting 93
4.5 Input Signals 94
4.5.1 Auxiliary Supply Input 94
4.5.2 CT Secondary Input 94
4.5.3 Status Input 94
-
8/11/2019 Ashida Relay
6/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page5/10
4.5.4 Trip Circuit Supervision Input 94
4.6 Output Signals 94
4.6.1 Trip Contact 94
4.6.2 Programmable Contact 94
4.6.3 LBB Protection Contact 94
4.6.4 Relay ( OK ) Healthy Contact 94
4.6.5 Auto Recloser Reclose Contact 94
4.6.6 Auto Recloser Lockout Contact 94
4.6.7 Control Contact selectable 94
4.7 Revision Note 95
5.0 MENU CONTENT TABLE
CONTENTS
5 Menu Content Table 3
5.1 To View Measurement 3
5.2 To Set / View General Setting 4
5.3 To Set / View O/C G1 Setting 5
5.4 To Set / View E/F G1 Setting 6
5.5 To Set / View 3Io G1 Setting 7
5.6 To Set / View NPS G1 Setting 8
5.7 To Set / View O/C G2 Setting 9
5.8 To Set / View E/F G2 Setting 10
5.9 To Set / View 3Io G2 Setting 11
5.10 To Set / View NPS G2 Setting 12
5.11 To Set / View ARR Setting 13
5.12 To Set / View Relay/LED Setting 145.13 To View Fault 1 to Fault 20 Setting 15
5.14 To View Status Setting 19
5.15 To View Error Log Setting 19
5.16 To View Close Setting 19
5.17 To View Trip Setting 20
5.18 To View Active Group 20
5.19 To Set / View Date/Time Setting 21
5.20 Revision Note 22
-
8/11/2019 Ashida Relay
7/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page6/10
6.0 TECHNICAL SPECIFICATION
CONTENTS
6.1 Protection Features 3
6.2 Relay Design Features 3
6.3 Block Diagram 4
6.4 Description 5
6.5 Technical Specification 6
6.6 Revision Note 10
7.0 APPLICATION GUIDECONTENTS
7.1 Main function 3
7.2 Over Current Element 3
7.3 Earth Fault Element 3
7.4 Inverse Time Curve 4
7.4.1 C1 - Normal Inverse 1 (10 Times 3.0 sec) 5
7.4.2 C2 - Normal Inverse 2 (10 Times 1.3 sec) 6
7.4.3 C3 - Very Inverse (10 Times 1.5 sec) 7
7.4.4 C4 - Extremely Inverse (10 Times 0.8 sec) 8
7.4.5 C5 - Long Time Inverse (10 Times 13.3 sec) 9
7.5 Trip Circuit Supervision 10
7.6 Auto Recloser Logic 10
7.7 Breaker Failure Logic 10
7.8 Negative Sequence Over Current 11
7.9 Programmable Di/DO and LED 11
7.10 Monitoring Function (Event, Disturbance Recorder) 11
7.11.1 Wiring Diagram External EF for EF protection 12
7.11.2 Wiring Diagram Internal EF for EF Protection 13
7.12 Trip Diagram 14
7.13 Logic Diagram of RL1 to RL5 and LED 15
7.14 Revision Note 16
-
8/11/2019 Ashida Relay
8/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page7/10
8.0 COMMUNICATION
CONTENTS
8.1 IEC60870-5-103 INTERFACE for ADR241B 3
8.2 Physical connection and link layer 3
8.3 Initialization 4
8.4 Time synchronization 5
8.5 General interrogation 5
8.6 Cyclic measurements 5
8.7 Disturbance records 5
8.8 APPENDIX 5
8.8.1 Frames in Monitor Direction 5
8.8.1.1 System Functions in monitor direction 5
8.8.1.2 Status indications in monitor direction 6
8.8.1.3 Fault indications in monitor direction 6
8.8.1.4 Measurands in monitor direction 7
8.8.1.5 Private frames in monitor direction 7
8.8.1.6 Disturbance data transmission in monitor direction 7
8.8.2 Frames in Control Direction 8
8.8.2.1 Private frames in Control direction 88.8.2.2 System Functions in control direction: 8
8.8.2.3 General commands in control direction 8
8.8.2.4 Disturbance data transmission related messages in control direction 8
8.8.2.5 Actual Channel: Used for DR Transmission: 8
8.9 Revision Note 9
9.0 INSTALLATION, RELAY TESTING & COMMISSIONING
CONTENTS
9.1 Installation 4
9.1.1 Relay Connection & Diagram 4
9.1.2 Before energising following should be checked 4
9.1.3 Relay operating condition 4
9.1.4 CT Circuit 4
9.1.5 Insulation 4
9.2. Commissioning 59.2.1 Commissioning Test, Required Equipment 5
-
8/11/2019 Ashida Relay
9/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page8/10
9.2.2 Checking of External Circuitry 5
9.2.2.1 Relay Back Terminal Wiring 5
9.2.2.2 Visual Inspection 5
9.2.2.3 Earthing 6
9.2.2.4 CT Polarity 6
9.2.3 Checking of Relay Setting 6
9.2.4 Final Checking 7
9.2.5 Commissioning Record Sheet 7
9.2.5.1 Relay identification 7
9.2.5.2 Commissioning Test Report 8
9.2.5.3 Commissioning record sheet for ADR241B_V2 Relay. 9
9.3 Post instillation / Commissioning observation 10
9.4 Testing of Relay 10
9.4.1 Relay Calibration 10
9.4.2 Diagram for Pickup and Timing Test 12
9.4.3 Testing of Over Current IP>> Protection 13
9.4.3.1 Pickup Test for Over Current IP>> 13
9.4.3.2 IDMT Time Test for Over Current IP>> 13
9.4.3.3 Pickup Test for Over Current Instantaneous Element IP>> 15
9.4.3.4 Operating Time Test for Over Current Instantaneous Element IP>> 16
9.4.4 Testing of 3Io>> Protection 16
9.4.4.1 Pickup Test for 3Io >> 16
9.4.4.2 IDMT Time Test for 3Io>> 17
9.4.4.3 Operating Time Test for Instantaneous Element 3Io>> 18
9.4.5 Testing of Earth Fault Ie>> Element 19
9.4.5.1 Pickup Test for Earth Fault Ie>> 19
9.4.5.2 IDMT Time Test for Earth Fault Ie>> 19
9.4.5.3 Operating Time Test for Earth Fault Instantaneous Element Ie>> 21
9.4.6 Testing of NPS (Negative Phase Sequence Element) 21
9.4.7 Testing of Annunciation for Both Over Current & Earth Fault 22
9.5 Other Functional Test 23
9.6 Revision Note 24
-
8/11/2019 Ashida Relay
10/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page9/10
10.0 PERIODIC TESTING
CONTENTS
10 Periodic Testing 3
10.1 Trip Test 3
10.2 Functional Test 3
10.3 Testing of Relay 3
10.3.1 Relay Calibration 3
10.3.2 Diagram for Pickup and Timing Test 5
10.3.3 Testing of Over Current Protection 6
10.3.3.1 Pickup Test for Over Current 6
10.3.3.2 IDMT Time Test for Over Current 610.3.3.3 Testing of HF Pickup for Over Current Test 8
10.3.3.4 Operating Time test of HF for Over Current 9
10.3.4 Testing Of Earth Fault Current Protection 9
10.3.4.1 Testing of 3IO element 9
10.3.4.2 IDMT test for 3IO>> 10
10.3.4.3 Operating time test of HF for 3IO 11
10.3.4.4 Testing of EF element 12
10.3.4.5 IDMT time test for Ie >> 12
10.3.4.6 Operating Time test of HF for EF 14
10.3.4.7 Testing of NPS 14
10.3.5 Testing Of Annunciation For Both O/C and EF 14
10.3.6 Other funct ional tests 15
10.4 Revision Note 16
11.0 Details of Internal Circuit Diagram
CONTENTS
11.1 Detail of Internal Circuit diagram 3
11.2 Revision Note 4
12.0 Problems Occurred & Hardware Software Revision
CONTENTS
12.1 Problems Occurred 3
12.2 Hardware / Software Revision 3
12.3 Revision Note 5
-
8/11/2019 Ashida Relay
11/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
CONTENTS
ASHIDA Elec tronics Pv t. Ltd.
Page10/10
Revision Note
Issue Date Descript ion
01 06.05.2008 Original Version02 15.11.2008 Minor Typo Error Corrected
-
8/11/2019 Ashida Relay
12/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
SAFETY INSTRUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Safety
Issue: 02
Date : 15.11.08
Page1/6
SAFETY INSTRUCTION
-
8/11/2019 Ashida Relay
13/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
SAFETY INSTRUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Safety
Issue: 02
Date : 15.11.08
Page2/6
CONTENTS
1.1 Introduction 3
1.2 Healthy & Safety 3
1.3 Symbol & External Labels 4
1.4 Decommissioning & Disposal 4
1.5 Technical Specifications For Safety 5
1.5.1 Protective Fuse Rating 5
1.5.2 Protective Class 5
1.5.3 Installation Category 5
1.5.4 Environment 5
1.6 CE Marking 5
1.7 Revision Note 6
-
8/11/2019 Ashida Relay
14/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
SAFETY INSTRUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Safety
Issue: 02
Date : 15.11.08
Page3/6
1.1 INTRODUCTION
This guide and the relevant operating or service manual documentation for the equipment
provide full information on safe handling, commissioning and testing of this equipment and
also includes description of equipment label markings.
Documentation for equipment ordered from ASHIDA Electronics Pvt. Ltd. is dispatched
separately from manufacture goods and may not be received at the same time. Therefore this
guide is provided to ensure that printed information normally present on equipment is fully
understood by the recipient.
Reference should be made to the external connection diagram before the equipment is
installed, commissioned or serviced.
1.2 HEALTHY AND SAFETY
This information in the Safety Section of the equipment documentation is intended to ensure
that equipment is properly installed and handled in order to maintain it in a safe condition.
It is assumed that everyone who will be associated with the equipment will be familiar with the
contents of that Safety Section, or this Safety Guide.
When electrical equipment is in operated, dangerous voltages will be present in certain parts
of the equipment. Failure to warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning and on careful operation, maintenance and
servicing. For this reason only qualified personal may work on or operate the equipment.
Qualified personnel are individuals who
Are familiar with the installation, commissioning and operation of the equipment andof the system to which it is being connected.
Are able to safely perform switching operation in accordance with accepted safetyand to isolate ground and label it.
Are trained in the care and use of safety apparatus in accordance with safetyengineering practices.
Are trained in emergency procedures (first aid)
-
8/11/2019 Ashida Relay
15/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
SAFETY INSTRUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Safety
Issue: 02
Date : 15.11.08
Page4/6
The operating manual for the equipment gives instruction for its installation, commissioning
and operation. However, the manual cannot cover all conceivable circumstances or include
detailed information on all topics. In the event of questions or specific problems, do not take
any action without proper authorization. Contact the appropriate Ashida technical sales office
and request the necessary information
1.3 SYMBOLS AND EXTERNAL LABELS ON THE EQUIPMENT
For safety reasons the following symbols and external labels, which may be used on the
equipment or referred to in the equipment documentation, should be understood before the
equipment is installed or commissioned
Caution: refer to equipment documentation Caution: risk of electric shock
Protective Conductor (*Earth) terminal.
Functional/Protective Conductor Earth terminal
Note This symbol may also be used for a Protective Conductor (Earth) terminal if that
terminal is part of a terminal block or sub-assembly e.g. power supply.
*NOTE: THE TERM EARTH USED THROUGHOUT THIS GUIDE IS THE 9ij DIRECTEQUIVALENT OF THE NORTH AMERICAN TERM GROUND.
1.4 DECOMMISSIONING AND DISPOSAL
Decommissioning:The supply input (auxiliary) for the equipment may include capacitors across the
supply or to earth. To avoid electric shock or energy hazards, after completely
isolating the supplies to the equipment (both poles of any dc supply), the capacitors
should be safely discharged via the external terminals prior to decommissioning.
Disposal:It is recommended that incineration and disposal to water courses is avoided. The
equipment should be disposed of in a safe manner. Any equipment containing
batteries should have them removed before disposal, taking precautions to avoid
short circuits. Particular regulations within the country of operation, may apply to the
disposal of batteries.
-
8/11/2019 Ashida Relay
16/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
SAFETY INSTRUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Safety
Issue: 02
Date : 15.11.08
Page5/6
1.5 TECHNICAL SPECIFICATIONS FOR SAFETY
1.5.1 Protective Fuse Rating
The recommended maximum rating of the external protective fuse for equipments is 8A, high
rupture capacity (HRC) Red Spot type NIT, or TIA, or equivalent, unless otherwise stated in
the technical data section of the equipment documentation. The protective fuse should be
located as close to the unit as possible.
DANGER -CTs must NOT be fused since open circuiting them may produce
lethal hazardous vol tages. 7.2 Protective Class
1.5.2 Protective Class
IEC 61010-1: 2001
EN 61010-1: 2001
Class I (unless otherwise specified in the equipment documentation).
This equipment requires a protective conductor (earth) connection toensure user safety.
1.5.3 Installation Category
IEC 61010-1: 2001
EN 61010-1: 2001
Installation Category III (Over voltage Category III):
Distribution level, fixed installation.
Equipment in this category is qualification tested at 5kV peak,
1.2/50s, 500, 0.5J, between all supply circuits and earth and alsobetween independent circuits
1.5.4 Environment
The equipment is intended for indoor installation and use only. If it is required for use in an
outdoor environment then it must be mounted in a specific cabinet or housing which will
enable it to meet the requirements of IEC 60529 with the classification of degree of protection
IP54 (dust and splashing water protected).
1.6 CE MARKING
Compliance with all relevant European Marking Community directives:Compliance demonstrated by reference to safety standards.
Product safety: Low Voltage Directive - 73/23/EECamended by 93/68/EECEN 61010-1: 2001EN 60950-1: 2001EN 60255-5: 2001IEC 60664-1: 2001
-
8/11/2019 Ashida Relay
17/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
SAFETY INSTRUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Safety
Issue: 02
Date : 15.11.08
Page6/6
1.7 Revis ion Note
Issue Date Descript ion
01 06.05.2008 Original Version
02 15.11.2008 Typo Error Corrected
-
8/11/2019 Ashida Relay
18/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page1/9
INTRODUCTION
-
8/11/2019 Ashida Relay
19/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page2/9
CONTENTS
2.1 General 3
2.2 Features 4
2.3 How to use the Manual 5
2.4 Ordering Information 7
2.5 Revision Note 9
-
8/11/2019 Ashida Relay
20/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page3/9
2.1. General Features of Adit ya-V2 Series : -
ADR241B is a second generation Numerical 3OC + 1EF Over Current Relay. The ADR241B
is part of Ashida Aditya Series ( Aditya-V2 ) of protective relays. General definition and
Aditya series and it model number is give in ordering information.
All the relay are designed using latest numerical technology and having programmable digital
input and outputs to minimized external contact multiplication electromechanical relays. All
relays are tested for EMI / EMC noise as per international IEC specifications. The basic
electronics hardware is common for all relays. The user interface for all relay are similar only
protection logic is different, this make very easy to use. General features of all relays are as
given below
Large 20x4 LCD display
Password Protection for all setting
Disturbance Recorder. Actual waveform of current are captured & saved in the built-in
memory with date time stamping, for analyzing fault condition & fault location.
IEC standard open protocol.
Separate Communication Prot for SCADA (RS485) as well as Local testing (RS232)
Very low burden on CT and PT
Online display current other digital and physical status.
Continuous monitoring of modules internal hardware and alarm generation in case of
failure of any critical components. 10 Digital Output contacts for local alarm Tele-signalling & Control
7 Optically isolated digital status input for monitoring of status and avoid used of external
relay logic
100 nos of event memory, event such CB close, Trip, status change, relay pkp etc. All
events are with date and time stamped up to 1ms
6 Programmable ( 3 Red / 3 Green) LED which can be assigned to any of protection
function
5 Programmable Relay which can be programmed through key board.
5 Optically isolated status input
-
8/11/2019 Ashida Relay
21/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page4/9
The ADR241B is a 3 Over Current and 1 EF relay it consist all the necessary protection and
monitoring functions required for Normal feeder it consist of
1. High Speed Digital DSP Controller
2. Analog Measuring Module
3. Power supply Module
4. Digital Input output module.
The High speed Digital Signal Controller continuously monitors line phase current and E/F
current. Along with different status input, through CTs, and optical isolated status
connections. The high-speed micro-controller samples these current signals through a A/D
converter. The Digital Signal performs powerful Numerical Algorithmsto find out RMS of
fundamental & harmonic contents of the current. All measurement is tuned to fundamental
frequency i.e 50Hz, thus relay remain stable during distorted waveform generated electronics
loco-motive. All these measure values are then used for different protection function such as
IDMT Over current protection, Instantaneous Over current protection, E/F protection etc.
These measured values are also displayed on large 20 x 4 LCD display for metering purpose.
The DSC also monitor different digital input trough optical isolator and perform some
monitoring function such trip circuit supervision, and control potential free contact for control
CB and generate ALARM and Tele-signalling
The power supply module is basically DC DC converted designed using modern PWM
based Switching mode technique to convert 110Vdc station battery supply to the 12V and
24Vdc low voltage supply for relay electronics and control circuit. It also provides necessary
isolation from station battery. There are two type of power supply modules are available 1)
having range of 77Vdc 250Vdc. Covering requirement of 110Vdc and 220Vdc station
battery system 2) having range of 18Vdc to 52Vdc covering 24Vdc, 30Vdc, 48Vdc station
battery requirement.
The relay is having total 8 nos of dual LED of high intensity for easy identification of type of
fault for easy user interface. LEDs L5, L6 and L7 and Relay R1 to R5, digital status input and
controlled output are fully programmable via key pad interface.
2.2. Features : -
Protection Features:
4 Element (3 Phase + EF) Over current IDMT/DMT with instant trip.
Programmable (Non- Volatile) Setting By local keys as well as remote setting by
communication port
-
8/11/2019 Ashida Relay
22/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page5/9
Selection of Curve: Five selectable curve (Normal Inverse 1 (C1), Normal Inverse 2, (C2)
Very inverse (C3), Extremely inverse (C4), Long time inverse (C5)) and Define Time
(C6).
Instantaneous Over-Current Protection with adjustable timer. Breaker Failure detection.
In-built CB Trip Circuit Supervision function during pre closing and post closing of CB.
Negative sequence over current (46).
2.3. HOW TO USE THE MANUAL
This manual contain detail information of ADITYA series over current and earth fault relay
such as ADR241B by using this manual user can be familiar with the application, installation
setting & commissioning of these relays.
The User Interface and Menu will be different for different software version. The user
interface chapter describe latest software version relay. The older relay menus are
shown in menu tables. Before referring manual first identify your relay software
version. The software version can be found by following procedure
After Power ON or when the HW RESET and LED RESET push button is pressedsimultaneously, the relay will display the following message.
1. Safety instruc tion : -
Content of this chapter is regarding safety of human being to operate/handle this relay.
2. Introduction : -
Content of this chapter is about general introduction to the ADITYA series of ADR range
of relays.
3. Handling : -
Content of this chapter is regarding precaution to be taken while handling electronic
equipment.
4. User Guide : -
A detail description of features of ADITYA series relays.
5. Menu content Table : -
This chapter contain detail flash chart of relay as per software history.
6. Technical Specification : -
Comprehensive details on nominal values setting ranges, specification & curve
characteristics.
Ashida Numerical3OC/1EF IDMT RelayADR241B_V2_R2 V02.01
Unit ID = 0001
This window will flash momentarily showing the followingRelay Name : 3OC/1EF IDMT RelayRelay Type : ADR241B_V2_R2 Software Version : V02.01Unit ID = 0001
Then the control will go automatically to default window
-
8/11/2019 Ashida Relay
23/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page6/9
7. Appl ication Guide : -
This chapter contains detail description of each relay setting guidelines.
8. Communication : -
Communication setting & Protocol details.
9. Installation, Relay Testing & Commissioning : -
This chapter contains information regarding installation; complete functional testing of
relay & commissioning data sheet.
10. Periodic Testing : -
This chapter contains periodic relay testing information.
11. Details of Internal Assemblies : -
Information regarding relays internal assemblies.
12. Problem Occurred and Hardware & Software Revision : -
Information regarding Error Codes and Hardware & Software Revisions.
-
8/11/2019 Ashida Relay
24/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page7/9
2.4 ORDERING INFORMATION
Genera l Def in i t i on o f Ad i t ya Ser ies Re lays
Each Relay is ident i f ied by Type No . and Model No .
The Type No. def ines the Funct ion of the Relay as Communicable / Non-Communicable, Number of E lements, Type of Protect ion Funct ion etc.
The Detai l def in i t ion of Type No . is g iven below.
D e f i n i t i o n o f T y p e N o o f A d i t y a S e r i e s o f R e l a y s
ADR 2 4 1 B
Stands
ForAditya
Series
Type of Protection Function
0 = Measurement
1 = Over Current
2 = Over / Under Voltage
3 = Current Differential.
4 = Voltage Control Current
5 = Power / Directional
6 = Power / Measurement
7 = Phase Angle/Syncro-Check
8 = Frequency
9 = Distance / Impedance
Nos. of Elements
1 = Single Element
2 = Double Element
3 = Three Element
4 = Four Element
Type of Communication
1 = No Communication
2 = Comm. (ASCADA / IEC Port)
Sub typeA = Simple Economical (Mini Function)
B = Extra Function (Mid Range)
S = Self Power
E = Special EF/ Neutral Function
-
8/11/2019 Ashida Relay
25/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page8/9
O r d er i n g i n f o r m a t i o n :
A D R 2 4 1 B - A M - X X X - X X - X - X - X X - X
Example
A DR241B A M-201-01-3-0-02-0
Type: ADR241B wi th s tandard se t t ing IEC60870-5-103 com
St . Back te rmina l layout
Cab ine t Type: CSE -150 H
Aux i l ia ry Supply: 77-250Vdc
CT sec: 1 Amp. / 5 Amp selectable
D e f i n i t i o n o f M o d e l N o o f A d i t y a S e r i e s o f R e l a y s
A M 2 0 1 X X X X X X X
Auxi liary Supply
01 = 18 52 V dc 06 = 110 V dc
02 = 77 250 V dc 07 = 220 V dc
03 = 24 V dc
04 = 30 V dc
05 = 48 V dc
Reservedfor Future Use
PT Secondary
0 = NA1 = 63.5V ac2 = 110V ac3 = 230V ac
CT Secondary
1 = 1 Amp.
2 = 5 Amp.
3 = 1 Amp. / 5 Amp. Selectable
201 indicatesAditya _V2This Document For Other modelRefer respective document or contactFactory
Back Terminal Lay out
01 = As Per ADV00101 andCabinet as MAC01302
-
8/11/2019 Ashida Relay
26/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
INTRODUCTION
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Introduction
Issue: 02
Date : 15.11.2008
Page9/9
2.5 Revision Note
Issue Date Descript ion
01 06.05.2008 Original Version02 15.11.2008 Typo Error Corrected
-
8/11/2019 Ashida Relay
27/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
HANDLING
ASHIDA Elec tronics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Handling
Issue: 02
Date : 15.11.2008
Page1/6
HANDLING AND CASE
DIMENSION
-
8/11/2019 Ashida Relay
28/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
HANDLING
ASHIDA Elec tronics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Handling
Issue: 02
Date : 15.11.2008
Page2/6
CONTENTS
3 Handling 3
3.1 Receipt of Relay 3
3.2 Unpacking 3
3.3 Handling of Electric Components 3
3.4 Storage 4
3.5 Dimensions 4
3.5.1 Connections of Power Terminals and Signal Terminals 4
3.5.2 Earthing 4
3.6 Cabinet drawing 5
3.7 Revision Note 6
-
8/11/2019 Ashida Relay
29/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
HANDLING
ASHIDA Elec tronics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Handling
Issue: 02
Date : 15.11.2008
Page3/6
3. HANDLING
3.1 RECEIPT OF RELAY
Care must be taken when unpacking & installing the relay so that none of part is damagedinside the box. Operation manual and test report are there store this property for further use.
Relay must be handled by skilled personnel. Relays that have been removed from their boxes
should not be left in situation where they are exposed to dust or damp. This particularity
applies to installation which are carried out at the same time as construction work. Relays that
are not immediately installed should be returned in to there corrugated box.
3.2 UNPACKING
Care must be taken when unpacking and installing the relays so that none of the parts is
damaged or the setting altered. Relays must only be handled by skilled personnel. The
installation should be done by clean, dry and reasonably free from dust and excessive
vibration. The site should be lit to facilitate inspection. Relays that have been removed from
their cases should not be left in situations where they are exposed to dust and damp. This
particularly applies to installation which are being carried out at the same time as construction
work
3.3 HANDLING OF ELECTRIC COMPONENTS
Electrostatic discharge (ESD)
As relay can be tested completely from external connections and relay setting can be done by
push button from front plate, there is no need to open the metal box.
The relay use component that are sensitive to electrostatic discharge. The electronic printed
circuit board (PCB) are well protected by the metal case. So unnecessary do not touch the
PCB tracks, connector, electronic component as they can be damaged by static electricity
discharge form the body as normal movement of a person can easily generate electrostatic
potentials of several thousand volts, discharge these voltage into ESD sensitive component
when handling electronic circuit can cause serious damage which often may not be
immediately apparent but the reliability of the circuit will have been reduced.
The electrostatic discharge when housed in the metal box do not expose them to risk of
damage by electrostatic discharge.
-
8/11/2019 Ashida Relay
30/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
HANDLING
ASHIDA Elec tronics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Handling
Issue: 02
Date : 15.11.2008
Page4/6
3.4 STORAGE
If relays are not to be installed immediately upon receipt they should be stored in a place free
from dust and moisture in their original cartons. Where de-humidifier crystals will be impairedif the bag has been exposed to ambient conditions and may be restored by gently heating the
bag for about an hour, prior to replacing it in the carton
Dust which collect on a carton may, on subsequent unpacking find its way into the relay, in
damp conditions the carton and packing may become Impregnated with moisture and the de-
humidifier will lose its efficiency.Storage temperature: -25C to +70C
3.5 DIMENSIONS
3.5.1 Connection of power terminals , and Signals terminals
The individual equipment are delivered with sufficient M4 screws to connect the relay via
annular terminals, with a maximum recommended of two annular terminals per contact.
To insure the insulation of the terminals and to respect the security and safety instructions,
an isolated sleeve can be used.
We recommend the following cable cross-sections:
Auxiliary sources Vaux : 1.5 mm (some electrical utiliets use 2.5 mm2 )
Communication Port D9 Femel with 0.5 mm2 per core total 4 core screen. The maximum
length of 1000m. Linear capacitance between conductor and earth : 100pF/m
PT Circuit 1.5 mm2
Other circuits 1.0 mm
CT Circuit 4 - 6 mm2
We recommend to protect the auxiliary source connection by using a fuse of type NIT or TIA
with a breaking capacity of 16A. For security reasons, do never install fuses in current
Transformers circuits. The other circuits must be protected by fuses.
3.5.2 Earthing
Each equipment must be connected to a local earth terminal by the intermediary of a M4
earth terminals. We recommend a wire of minimal section of 2,5 mm, connected to cabinet
bolt . Because of the limitations of the annular terminals,
NOTE: To prevent any electrolytic risk between copper conductor or brass conductor and the
back plate of the equipment, it is necessary to take precautions to isolate them one from the
other. This can be done in several ways, for example by inserting between the conductor and
the case a plated nickel or insulated ring washer or by using a tin terminals.
-
8/11/2019 Ashida Relay
31/233
-
8/11/2019 Ashida Relay
32/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
HANDLING
ASHIDA Elec tronics Pv t. Ltd.
Ref: Manual/ADR241B_V2/Handling
Issue: 02
Date : 15.11.2008
Page6/6
3.7 Revision Note
Issue Date Descript ion
01 06.05.2008 Original Version02 15.11.2008 Typo Error Corrected
-
8/11/2019 Ashida Relay
33/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page1/95
USERS GUIDE(For Software V2.xx)
-
8/11/2019 Ashida Relay
34/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page2/95
CONTENTS
4.1 Front Panel and Control 5
4.2 Users Interface 7
4.2.1 LCD Display 7
4.2.2 Touch Keys 7
4.2.3 LEDs 8
4.2.4 RS485 8
4.2.5 RS232 8
4.3 Password 9
4.3.1 Password Entry & Changing the Password 9
4.3.2 Clear Password 10
4.3.3 Default Settings 114.3.3.1 General Settings 11
4.3.3.2 Protection Settings 12
4.4 Menus 15
4.4.1 Default Display 15
4.4.2 Main Menu List 16
4.4.2.1 Main Menu List Details 17
4.4.3 M e a su r e m e n t 23
4.4.3.1 To View - Measurement 23
4.4.4 Ge n e r a l S et t i n g 24
4.4.4.1 To Set General Setting 24
4.4.4.2 To View General Setting 28
4.4.5 Ov e r Cu r r e n t ( OC- G 1 ) S e t t i n g 29
4.4.5.1 To Set OC-G1 Setting 29
4.4.5.2 To View OC-G1 Setting 32
4.4.6 Ea r t h F au l t ( EF- G 1 ) S e t t i n g 33
4.4.6.1 To Set EF-G1 Setting 33
4.4.6.2 To View EF-G1 Setting 36
4.4.7 3 I o - G1 S et t i n g 37
4.4.7.1 To Set 3Io-G1 Setting 37
4.4.7.2 To View 3Io-G1 Setting 40
4.4.8 Ne g a t i v e Ph a s e Se q u e n c e El em e n t ( N PS - G1 ) S e t t i n g 41
4.4.8.1 To Set NPS-G1 Setting 41
4.4.8.2 To View NPS-G1 Setting 43
-
8/11/2019 Ashida Relay
35/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page3/95
4.4.9 Ov e r Cu r r e n t ( OC- G 2 ) S e t t i n g 44
4.4.9.1 To Set OC-G2 Setting 44
4.4.9.2 To View OC-G2 Setting 47
4.4.10 Ea r t h F au l t ( EF- G 2 ) S e t t i n g 48
4.4.10.1 To Set EF-G2 Setting 48
4.4.10.2 To View EF-G2 Setting 51
4.4.11 3 I o - G2 S et t i n g 52
4.4.11.1 To Set 3Io-G2 Setting 52
4.4.11.2 To View 3Io-G2 Setting 55
4.4.12 Ne g a t i v e Ph a s e Se q u e n c e El em e n t ( N PS - G2 ) S e t t i n g 56
4.4.12.1 To Set NPS-G2 Setting 564.4.12.2 To View NPS-G2 Setting 58
4.4.13 A u t o R e cl o s e r ( ARR ) S e t t i n g 59
4.4.13.1 To Set ARR Setting 59
4.4.13.2 To View ARR Setting 61
4.4.14 R e la y / L ED Co n f i g u r a t i o n 62
4.4.14.1 Bit Definition for Relay/LED Configuration 62
4.4.14.2 List of Protection Function and Digital Inputs 63
4.4.14.3 To Set Relay/LED Configuration 67
4.4.14.4 To View Relay/LED Configuration 72
4.4.14.5 Example of Relay / LED Configuration 73
4.4.15 F a u l t 1 88
4.4.15.1 To View Fault 1 Data [Fault 2 to Fault 20] 88
4.4.16 S t a t u s 89
4.4.16.1 To View Status 89
4.4.17 Er r o r L o g 89
4.4.17.1 To View Error Log 89
4.4.18 C l o s e 90
4.4.19 T r i p 90
4.4.20 A c t i v e G r o u p 91
4.4.20 D a t e T im e S et t i n g 92
4.4.20.1 To Set Date Time setting 92
4.4.20.2 To View Date Time Setting 93
-
8/11/2019 Ashida Relay
36/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page4/95
4.5 Input Signals 94
4.5.1 Auxiliary Supply Input 94
4.5.2 CT Secondary Input 94
4.5.3 Status Input 94
4.5.4 Trip Circuit Supervision Input 94
4.6 Output Signals 94
4.6.1 Trip Contact 94
4.6.2 Programmable Contact 94
4.6.3 LBB Protection Contact 94
4.6.4 Relay ( OK ) Healthy Contact 94
4.6.5 Auto Recloser Reclose Contact 94
4.6.6 Auto Recloser Lockout Contact 94
4.6.7 Control Contact selectable 94
4.7 Revision Note 95
-
8/11/2019 Ashida Relay
37/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page5/95
4.1. Front Panel and Contro l
1
2
3
4
6
5
7 9 10 11 12 13
8 14
11
22
33
44
66
555
777 999 10 1111 1212 1313
88 1414
Sr. No. Legend Descript ion
LEDs Total 8 dual colours LED (Red and Green) are provided foruser interface. The some of LEDs are pre defined. While
some are spare and can be programmed as per therequirement. Following are fix LED
1 PROTH / ERR Protection Healthy This is a green LED and become off inflowing condition. During Error It become Red
a When Auxiliary supply is not sufficient to operaterelay.
b Relay detect some internal hardware error (LED willbecome RED)
c When there Trip circuit is faulty
(LED will become RED)
2 FAULT / PKP Green LED indicates FAULT condition. This is Hand Reset(HR) indication and remains on till Reset either by localswitch or through communication
Red LED indicates Relay PICKUP condition This is SelfReset (SR) type. Indicates at least one of the current inputsis above set threshold.
-
8/11/2019 Ashida Relay
38/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page6/95
3 DT / REC Green LED indicates Dead Time
Red LED indicate Reclaim time
4 LOCK / BF Green LED indicates ARR lock-out Hand Reset (HR) Type.
Red LED indicates Breaker Fail Hand Reset (HR) Type.
5 ARR. E / ARR.D Green LED indicates ARR Enable
Red LED indicates ARR Disable
(Note : The above function can be assigned to this LEDafter loading default Setting)
6 L6 / L7 Spare LED Programmable
7 TRIP / CLOSE Green LED indicates Output TRIP Relay contact closer(Self Reset SR) Type
Red LED indicate Output CLOSE Relay contact closer
Self Reset (SR) Type8 LCD display A 20 character by 4 line back-lit large LCD display will be
provided for display of setting / status and measured valuesuch as line current etc.
9 LED Reset 1 Key will be provided for LED reset
10 TEST 1 key will be provided for Trip test. This key could beblocked through general setting, if required.
11 ARR 1 Key will be provided to Enable/Disable ARR (AutoRecloser Relay) function.
12 HW Reset 1 key will be provided for Hardware reset. This key will beinterlocked with LED reset.
13 Navigation Key 4 keys will be provided for navigation through differentdisplay menu and to do setting
14 Cover This is a removable cover. After removing this cover, localcommunication port (RS232) will be accessible.
-
8/11/2019 Ashida Relay
39/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page7/95
4.2. USER INTERFACE
4.2.1. LCD Disp lay
Back-lit LCD display 20 x 4 is provided for parameter and setting display and for easy viewing
of measurement, setting, fault records, date & time, error message. Back-lit will automatically
switch off if any push button key will not be pressed for more than 100sec. The display back-
lit can be made on by pressing any push button key. Back-lit is also automatically turned on
when any tripping occurs on particular equipment.
4.2.2. Touch Keys
The function of relay is controlled by the following keys, Left Arrow key (), Right Arrow key
(), Up Arrow key () Down Arrow key () and LED Reset Key, Test Key, Bypass Key and
HW Reset Key which are provided on the front Plate.
When the Right Arrow key () is pressed the operator is able to view the setting of the
relay. When the Right Arrow key () is pressed again it will go to the next setting page,
but in case there are no more setting to be displayed it returns to the main menu.
When the Left Arrow key () is pressed than you can return to previous display page, it
relay is already on main menu then, you are able to enter the setting which can be now
modified using Up Arrow key () Down Arrow key (). When the Left Arrow key ()
pressed again it will go to the next setting.
The Up Arrow key () is used to increment the value, the Down Arrow key () is used to
decrement the value in the display.
The Left Arrow key () Right Arrow key () can be used to go forward or backward,
both when doing the settings and while viewing the settings
At the time of sett ing i f changes are not carr ied wi thin 100s then the display wil l reset it
self and return to the main menu. Or you can discard setting and abort to main menu
by pressing LED RESET key
HW RESET key is never require in normal operation, It is series with LED RESET
key, When both keys are pressed simultaneously it reset total hardware of relay. This
normally required during firmware update of relay.
-
8/11/2019 Ashida Relay
40/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page8/95
4.2.3. LEDs
The relay is having total 8 nos of dual LED of high intensity for easy identification of type of
fault for easy user interface. LEDs L6 and L7 are fully programmable via key pad interface as
these are bi-color LED effectively 6 LEDs are full programmable.
Sr. No. Legend Description
1 PROT.H /ERR
: Green LED indicates Relay OK (Protection Healthy)
: In case of following condition led become Red
1. Problem in relay Hardware.
2. Trip Circuit Fault
2 FAULT /PICK-UP
: Green LED indicates FAULT Hand Reset (HR) Type.
: Red LED indicate Start of timer Self Reset (SR) Type
3 DT / REC : Green LED indicate Dead Time
: Red LED indicate Reclaim time
4 LOCK /BF
: Green LED indicate ARR lock-out (HR) Type
: Red LED indicate Breaker Fail (HR) Type
5 ARR. E /ARR. D
Green LED indicates ARR Enable
Red LED indicates ARR Disable
(Note : The above function can be assigned to this LED afterloading default Setting)
6 L6 : Spare LED Programmable
7 L7 : Spare LED Programmable
8 TRIP /
CLOSE
: Green LED indicates Output Trip relay contact closer (SR) Type
: Red LED indicate output Close relay contact closer (SR) Type
4.2.4. RS485 Port
RS485 port is provided at the back side of relay (near to terminal block) for permanent
SCADA connectivity. The physical connection is through D9 type male connector, to avoid
accentual connection power warring to communication input. There are 4 wire are used 2 for
transmission and 2 for receiving. The actual connection diagram is given in communication
section. Using RS485 port Fault data live event, disturbance record, etc can be downloaded
port.
4.2.5. RS232 Port
RS232 Communication port D9 type male is provided on front panel of relay, after opening of
front cover this port is available. This is very useful for down loading relay data and analysis it.
For proper operation user must select communication port from keyboard (general setting)
detail description is given in communication chapter.
-
8/11/2019 Ashida Relay
41/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page9/95
4.3. Password
4.3.1. Password Entry and changing the password
To enter passwordin allADR241B_V2 refer following steps ( User can go to this screen bypressing HW RESET + LED RESET Simultaneously)
In ADR241B the password protected windows are 1. General Setting 2. OC G1 Setting
3. EF G1 Setting 4. 3Io G1 Setting 5. NPS G1 Setting6. OC G2 Setting 7. EF
G2 Setting 8. 3Io G22 Setting 9. NPS G2 Setting 10. ARR Sett ing 11. Relay LED
Config and 12.Date Time Setting
Procedure to enter the password is same for all windows to enter the password follow these
steps.
General Settings
New Password = 000
Range 000-099
Use Inr/Dec
By using the up arrow key ()
or the down arrow key ()New Passwordcan be set. The range is from 000-099 insteps of 001.
Press the arrow key () the relay will display otherwindows on by one till the following window.
Measurement Using + / (INR) or- / (DEC)key scroll the main menu togo to General Setting
Secondary Current
R = 000.00 Y = 000.00
B = 000.00 3Io=000.00
CT Sec. Selected = 1A
This is default window showing the actual Secondary LoadCurrent as per CT Sec selection
Press the arrow key () the relay will display Main menudirectly as follows.
Password = 001
Use Inr/Dec
Enter the previously set password, by using the up arrowkey or the down arrow key ().
Note : Default password setting is 000
Press the arrow key () the relay will display as follow.
General Settings
Password protected window for General Setting forsetting New Password, language Selection, Unit ID, BaudRate, Com Port, Set Parity, BF Enable, BF Delay, BFCont,. CT Sec., CT EF, CT Primary, Local Control, TripCkt. Trip Cont., Active Group, Cold Load Pick_up. and EFCurrent
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
42/233
-
8/11/2019 Ashida Relay
43/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page11/95
4.3.3. Default Settings
4.3.3.1. General Settings
Index Settings Value Range
1 BF Enable 1 YES/NO
2 BF Delay 200mSec Range 200-1000ms
3 BF Cont 1 SR/HR
4 CT Sec. 2Amp 1Amp/5Amp
5 CT EF 2Amp 1Amp/5Amp
6 CT Primary 300 Range 10-2000
7 Local Control 2 YES/NO
8 Trip Ckt 2 YES/NO
9 Trip Cont 1 SR/HR
10 Active Group 1 G1/G2
11 Cold Ld PKP 2 Enable/Disable
12 RL1 H 14560
13 RL1 L 32768
14 RL2 H 50944
15 RL2 L 32769
16 RL3 H 0
17 RL3 L 0
18 RL4 H 0
19 RL4 L 020 RL5 H 0
21 RL5 L 0
22 L5 Green H 0 Special LED
23 L5 Green L 0 Special LED
24 L5 Red H 0 Special LED
25 L5 Red L 2 Special LED
26 L6 Green H 0
27 L6 Green L 32772
28 L6 Red H 0
29 L6 Red L 3277030 L7 Green H 0
31 L7 Green L 0
32 L7 Red H 0
33 L7 Red L 0
34 S1 0
35 S2 0
36 S3 1
37 S4 2
38 S5 0
-
8/11/2019 Ashida Relay
44/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page12/95
4.3.3.2. Protection Settings
Index Settings Value Range
1 IP> Enable - G1 2 YES/NO
2 IP> 90% Range 10%-200%
3 IP> TMS 0.15 Range x0.02-x1.00
4 IP> Curve 6 C1-C6
5 IP> C6 Delay 0.01S 0-99.90S
6 IP>> Enable 1 YES/NO
7 IP>> 100% Range 10%-200%
8 IP>> TMS 0.15 Range x0.02-x1.00
9 IP>> Curve 1 C1-C6
10 IP>> C6 Delay 0.1S 0-99.90S
11 P>>> Enable 1 YES/NO12 IP>>> 400% Range 50%-2000%
13 IP>>> Delay 0.1S 0-2.00S
14 EF > Enable - G1 2 YES/NO
15 EF > 20% Range 10%-200%
16 EF > TMS 0.02 Range x0.02-x1.00
17 EF > Curve 1 C1-C6
18 EF > C6 Delay 0.01S 0-99.90S
19 EF >> Enable 1 YES/NO
20 EF >> 80% Range 10%-200%
21 EF >> TMS 0.15 Range x0.02-x1.00
22 EF >> Curve 1 C1-C6
23 EF >> C6 Delay 0.1S 0-99.90S
24 EF >>> Enable 1 YES/NO
25 EF >>> 100% Range 50%-2000%
26 EF >>> Delay 0.1S 0-2.00S
27 3Io > Enable - G1 2 YES/NO
28 3Io > 20% Range 10%-200%
29 3Io > TMS 0.02 Range x0.02-x1.00
30 3Io > Curve 1 C1-C6
31 3Io > C6 Delay 0.01S 0-99.90S
32 3Io >> Enable 1 YES/NO
33 3Io >> 20% Range 10%-200%
34 3Io >> TMS 0.02 Range x0.02-x1.00
35 3Io >> Curve 1 C1-C6
36 3Io >> C6 Delay 0.01S 0-99.90S
37 3Io >>> Enable 2 YES/NO
38 3Io >>> 100% Range 50%-2000%
39 3Io >>> Delay 0.1S 0-2.00S
-
8/11/2019 Ashida Relay
45/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page13/95
Index Settings Value Range
40 I2 >> Enable 2 YES/NO
41 I2 >> 20% Range 10%-200%42 I2 >> TMS 0.02 Range x0.02-x1.00
43 I2 >> Curve 1 C1-C6
44 I2 >> C6 Delay 0.01S 0-99.90S
45 I2 >>> Enable 2 YES/NO
46 I2 >>> 100% Range 50%-2000%
47 I2 >>> Delay 0.05S 0-2.00S
48 IP> Enable - G2 2 YES/NO
49 IP> 20% Range 10%-200%
50 IP> TMS 0.02 Range x0.02-x1.00
51 IP> Curve 1 C1-C6
52 IP> C6 Delay 0.01S 0-99.90S
53 IP>> Enable 1 YES/NO
54 IP>> 100% Range 10%-200%
55 IP>> TMS 0.2 Range x0.02-x1.00
56 IP>> Curve 1 C1-C6
57 IP>> C6 Delay 0.1S 0-99.90S
58 P>>> Enable 1 YES/NO
59 IP>>> 600% Range 50%-2000%
60 IP>>> Delay 0.2S 0-2.00S
61 EF > Enable - G2 2 YES/NO
62 EF > 20% Range 10%-200%
63 EF > TMS 0.02 Range x0.02-x1.00
64 EF > Curve 1 C1-C6
65 EF > C6 Delay 0.01S 0-99.90S
66 EF >> Enable 1 YES/NO
67 EF >> 90% Range 10%-200%
68 EF >> TMS 0.2 Range x0.02-x1.00
69 EF >> Curve 1 C1-C6
70 EF >> C6 Delay 0.1S 0-99.90S71 EF >>> Enable 1 YES/NO
72 EF >>> 200% Range 50%-2000%
73 EF >>> Delay 0.15S 0-2.00S
74 3Io > Enable - G2 2 YES/NO
75 3Io > 20% Range 10%-200%
76 3Io > TMS 0.02 Range x0.02-x1.00
77 3Io > Curve 1 C1-C6
78 3Io > C6 Delay 0.01S 0-99.90S
-
8/11/2019 Ashida Relay
46/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page14/95
79 3Io >> Enable 2 YES/NO
80 3Io >> 20% Range 10%-200%
81 3Io >> TMS 0.02 Range x0.02-x1.00
82 3Io >> Curve 1 C1-C6
83 3Io >> C6 Delay 0.01S 0-99.90S
84 3Io >>> Enable 2 YES/NO
85 3Io >>> 100% Range 50%-2000%
86 3Io >>> Delay 0.05S 0-2.00S
87 I2 >> Enable - G2 2 YES/NO
88 I2 >> 20% Range 10%-200%
89 I2 >> TMS 0.02 Range x0.02-x1.00
90 I2 >> Curve 1 C1-C6
91 I2 >> C6 Delay 0.01S 0-99.90S
92 I2 >>> Enable 2 YES/NO
93 I2 >>> 100% Range 50%-2000%
94 I2 >>> Delay 0.05S 0-2.00S
95 ARR Enable 1 YES/NO
99 N SHOT 2 Range 00-04
97 DT1 40S Range 0.10-180.00S
98 DT2 60S Range 0.10-180.00S
99 DT3 1S Range 0.10-180.00S
100 DT4 1S Range 0.10-180.00S
101 Reclaim Time 30S Range 1.0-200.0S
-
8/11/2019 Ashida Relay
47/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page15/95
4.4. MENUS
4.4.1. Default Display :
After Power ON or when the HW RESET + LED RESET push button is pressedsimultaneously, the relay will display the following message.
Ashida Numerical3OC/1EF IDMT Relay
ADR241B_V2_R2 V02.08Unit ID = 0001
This window will flash momentarily showing the followingRelay Name : 3OC/1EF IDMT RelayRelay Type : ADR241B_V2_R2 Software Version : V02.01Unit ID = 0001Then the control will go automatically to default window
Secondary Current
R = 000.01 Y = 000.01
B = 000.02 3Io = 000.02
CT Sec. Selected = 1A
This is default window showing the actual Secondary LoadCurrent as per CT Sec selection
Press the arrow key () the relay will display Main menudirectly as follows.
-
8/11/2019 Ashida Relay
48/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page16/95
4.4.2. Main Menu Lis t
Measurement
General Settings
OC G1 Settings
EF G1 Settings
3Io G1 Settings
NPS G1 Settings
OC G2 SettingsEF G2 Settings
3Io G2 Settings
NPSG2 Settings
ARR Sett ings
Relay/LED Config
Fault 1
Fault 2
Fault 3
Fault 4
Fault 5
Fault 6
Fault 7
Fault 8
Fault 9
Fault 10
Fault 11
Fault 12
Fault 13
Fault 14
Fault 15
Fault 16
Fault 17
Fault 18
Fault 19
Fault 20
Status
Error Log
Close
Trip
Act ive Group G2
Date/Time
Measurement, General Settings, OCG1 Settings, EFG1
Settings, 3IoG1 Settings, NPSG1 Settings, OCG2
Settings, EFG2 Settings, 3IoG2 Settings, NPSG2
Settings ARR Settings, Relay/LED Config, Fault 1, Fault 2,
Fault 3, Fault 4, Fault 5, Fault 6, Fault 7, Fault 8, Fault 9,
Fault 10, Status, , Fault 11, Fault 12, Fault 13, Fault 14, Fault
15, Fault 16, Fault 17, Fault 18, Fault 19, Fault 20, Status,
Error Log, Close, Trip, Active Group G1 and Date/Time,
these are the Main Menusavailable in this relay.
Since the LCD Display consist only of 4 Lines, the main
menu list can be scrolled up or down by using the Up
Arrow key () or the Down Arrow key (). The arrow
pointers suggest that particular main menu is selected.
Secondary Current
R = 000.00 Y = 000.00B = 000.00 3Io = 000.02
CT Sec. Selected = 1A
This is default window showing the actual Secondary Load
Current as per CT Sec selectionPress the arrow key () the relay will display Main menu
directly as follows.
-
8/11/2019 Ashida Relay
49/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page17/95
4.4.2.1. Main Menu Lis t Details
Measurement
This menu is to view the actual load current in primary as
well as secondary as per the CT Secondary and CT Primary
selection for all protection function.
Press the arrow key () the relay will display as follow.
General Settings
Password protected window for General Setting for
setting New Password, Language Selection , Unit ID, Baud
Rate, Com Port, Set Parity, BF Enable, BF Delay, BF Cont,.
CT Sec., C.T. EF, CT Primary, Local Control, Trip Circuit,
Trip Cont., Active Group, Cold Load Pick-up and EF Current
Press the arrow key () the relay will display as follow.
OC- G1 Settings
Password protected window for OC Settings for setting
IP> Enable, Ip>% Range, IP>TMS, IP> Curve, IP>C6 Delay,
IP>> Enable, Ip>> % Range, IP>>TMS, IP>> Curve, IP>>C6
Delay, IP>>> Enable, Ip>>>% Range, IP>>> C6 Delay.
Press the arrow key () the relay will display as follow.
NPS G1 Settings
Password protected window for NPS Setting for setting
I2>> Enable, I2>>% Range, I2>>TMS, I2>>Curve, I2>>C6
Delay, I2>>> Enable, I2>>>% Range, I2>>>Delay
Press the arrow key () the relay will display as follow.
EF G1 Settings
Password protected window for EF Settings for setting
IE> Enable, IE>% Range, IE>TMS, IE> Curve, IE>C6 Delay,
IE>> Enable, IE>>% Range, IE>>TMS, IE>> Curve, IE>>C6
Delay, IE>>> Enable, IE>>> % Range and IE>>> C6 Delay
Press the arrow key (
) the relay will display as follow.
3Io G1 Settings
Password protected window for 3Io Settings for setting
3Io> Enable, 3Io>% Range, 3Io>TMS, 3Io> Curve, 3Io>C6
Delay, 3Io>> Enable, 3Io>>% Range, 3Io>>TMS, 3Io>>
Curve, 3Io>>C6 Delay, 3Io>>> Enable, 3Io>>> Range,
3Io>>> C6 Delay
Press the arrow key () the relay will display as follow.
OC- G2 Settings
Password protected window for OC Settings for setting
IP> Enable, Ip>% Range, IP>TMS, IP> Curve, IP>C6 Delay,
IP>> Enable, Ip>> %Range, IP>>TMS, IP>> Curve, IP>>C6
Delay, IP>>> Enable, Ip>>>% Range, IP>>> C6 Delay.
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
50/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page18/95
Relay/LED Config
Password protected window for Relay LED Config for
setting RL1, RL1 Cont, RL2, RL2 Cont, RL3, RL3 Cont,
RL4, RL4 Cont, RL5, RL5 Cont, L5 Green, L5 Green, L5
Red, L5 Red, L6 Green, L6 Green, L6 Red, L6 Red, L7
Green, L7 Green, L7 Red , L7 Red, S1, S2, S3, S4 & S5
Press the arrow key () the relay will display as follow.
Fault 1
This menu is to view the latest fault data stored by the relay.
That is Trip Flag, Trip Counter (TC), Secondary current, Date
Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 2
This menu is to view the first latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
ARR Settings
Password protected window for ARR Setting for setting
N SHOT, DT1, DT2, DT3, DT4 and Reclaim Time selection.
Press the arrow key () the relay will display as follow.
EF G2 Settings
Password protected window for EF Settings for setting
IE> Enable, IE>% Range, IE>TMS, IE> Curve, IE>C6 Delay,
IE>> Enable, IE>>% Range, IE>>TMS, IE>> Curve, IE>>C6
Delay, IE>>> Enable, IE>>> % Range and IE>>> C6 Delay
Press the arrow key () the relay will display as follow.
NPS G2 Settings
Password protected window for NPS Setting for setting
I2>> Enable, I2>>% Range, I2>>TMS, I2>>Curve, I2>>C6Delay, I2>>> Enable, I2>>>% Range, I2>>>Delay
Press the arrow key () the relay will display as follow.
3Io G2 Settings
Password protected window for 3Io Settings for setting
3Io> Enable, 3Io>% Range, 3Io>TMS, 3Io> Curve, 3Io>C6
Delay, 3Io>> Enable, 3Io>>% Range, 3Io>>TMS, 3Io>>
Curve, 3Io>>C6 Delay, 3Io>>> Enable, 3Io>>> Range,
3Io>>> C6 Delay
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
51/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page19/95
Fault 3
This menu is to view the second latest fault data stored by
the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key (
) the relay will display as follow.
Fault 4
This menu is to view the third latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 5This menu is to view the fourth latest fault data stored by therelay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 6
This menu is to view the fifth latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 7
This menu is to view the sixth latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 8
This menu is to view the seventh latest fault data stored by
the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 9
This menu is to view the eight latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
52/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page20/95
Fault 10
This menu is to view the ninth latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 11
This menu is to view the tenth latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 12
This menu is to view the eleventh latest fault data stored by
the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 13
This menu is to view the twelfth latest fault data stored by the
relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 14
This menu is to view the thirteenth latest fault data stored by
the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 15
This menu is to view the fourteenth latest fault data stored by
the relay. That is Trip Flag, Trip Counter (TC), Secondarycurrent, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 16
This menu is to view the fifthteenth latest fault data stored by
the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
53/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page21/95
Status
This menu is to view the Statusof the digital input S1, S2,
S3, S4 and S5 also Trip circuit Supervision digital input T1
and T2
Press the arrow key () the relay will display as follow.
Error Log
This menu is to view the Error Code detected by the self
supervision function of the relay and showing detail
information of trip circuit supervision.
Press the arrow key () the relay will display as follow.
Fault 17
This menu is to view the sixteenth latest fault data stored by
the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 18
This menu is to view the seventeenth latest fault data stored
by the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 19This menu is to view the eighteenth latest fault data storedby the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Fault 20
This menu is to view the nineteenth latest fault data stored
by the relay. That is Trip Flag, Trip Counter (TC), Secondary
current, Date Time and Primary current.
Press the arrow key () the relay will display as follow.
Close
This menu is to perform Closeoperation for Circuit Breaker
by pressing () arrow key this menu will be function only
when Local Control = ON from password protected General
Setting menu.
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
54/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page22/95
Date Time
Password protected window for setting Date Time
Press the arrow key () the relay will display as follow.
Measurement
Trip
This menu is to perform Tripoperation for Circuit Breaker by
pressing () arrow key this menu will be function only when
Local Control = ON from password protected General
Setting menu.
Press the arrow key () the relay will display as follow
Active Group G1
This menu will show selected Active Group from password
protected menu General Setting.
Press the arrow key () the relay will display as follow
-
8/11/2019 Ashida Relay
55/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page23/95
4.4.3. MEASUREMENT
4.4.3.1. To View Measurement
Measurement
This menu is to view the actual load current in primary as
well as secondary as per the CT Secondary and CT Primary
selection.
Press the arrow key () the relay will display as follow.
Secondary Current
R = 000.00 Y = 000.00
B = 000.00 3Io =000.03
CT Sec. Selected = 1A
This window will show actual Secondary Current as per CT
Sec. selection
Press the arrow key () the relay will display as follows.
Primary Current
R = 00000A Y = 00000A
B = 00000A 3Io = 00000A
This window will show actual Primary Current as per
CT Primary. selection, it will display current in K (KAmp) .
When CT Primary 500?
Press the arrow key () the relay will display as follows.
Measurement
I1=000.01
I2=000.01
EF=000.01
This window will show actual Secondary Current as per
respective C.T. Secondary setting.
Positive phase sequence Current I1
Negative phase Sequence Current I2
Exta EF current (from external CBCT) - Ie
Press the arrow key () to display the main menu.
-
8/11/2019 Ashida Relay
56/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page24/95
4.4.4. GENERAL SETTINGS
4.4.4.1. To Set General Setting
General Setting
Password protected window for General Setting for
setting New Password, Language Selection , Unit ID, Baud
Rate, Com Port, Set Parity, BF Enable, BF Delay, BF Cont,.
CT Sec., C.T. EF, CT Primary, Local Control, Trip Circuit,
Trip Cont., Active Group, Cold Load Pick-up and EF Current
Press the arrow key () the relay will display as follow.
Password = 001
Use Inr/Dec
Enter the previously set password, By using the up arrow
keyor the down arrow key ().
Note : Default password setting is 000
Press the arrow key () the relay will display as follow.
General Settings
Unit ID = 001
Range 001-250
Use Inr/Dec
By using the up arrow key ()
or the down arrow key ()
the desired Unit ID address can be selected. The unit
address can be set from 001 to 250 in steps of 001, which
means total 250 devises can be connected to single
computer. The 250th
address is reserved for special
command. These settings are required to communicate with
the SCADA computer.
Press the arrow key () the relay will display as follow.
General Settings
Baud Rate = 09600
Range 1200-57600
Use Inr/Dec
By using the up arrow key ()
or the down arrow key ()
the desired Baud Rate can be set. The range is from 1200-
57600. (i.e. 1200, 2400, 9600, 19200, 38400 and 57600)
Press the arrow key () the relay will display as follow.
General Settings
New Password = 000
Range 000-099
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
New Password can be set. The range is from 000-099 in
steps of 001.
Press the arrow key () the relay will display as follow.
General SettingsLanguage Sel. = ENG
Range ENG / TUR
Use Inr/Dec
By using the up arrow key (
)
or the down arrow key (
)Language English / Turkey can be selected.
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
57/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page25/95
General Settings
BF Delay = 0200
Range 200-1000ms
Use Inr/Dec
By using the up arrow key ()or the down arrow key ()
the desired BF Delay Setting (Breaker Fail delay for back-
up protection) can be set. The range of setting is from 200-
1000ms in steps of 100ms. The BF fail function is used for
back-up protection, when CB fails to trip even after relay
gives the trip command, the BF Delay is set to operate
backup protection.
Press the arrow key () the relay will display as follow.
General SettingsBF Enable = YES
YES/NO
Use Inr/Dec
By using the up arrow key ()or the down arrow key ()
the desired BF Enable(Breaker Fail) can be set, that is YES
or NO. If set YES then BF relay is enable and if set NO then
it will be disable.
Press the arrow key () the relay will display as follow.
General Settings
CT Sec. = 1Amp
1Amp/5Amp
Use Inr/Dec
By using the up arrow key ()or the down arrow key ()
the CT Sec. Setting of protection function such as Ip> , Ip>>
, Ip>>> , 3Io >, 3Io>>, 3Io>>>, NPS>>,NPS>>>
can be selected 1 Amp. or 5 Amp.
Note : Care should be taken to see proper connection
are established at the back terminal, i.e. between Com.
and 1 while selecting 1 Amp and between Com. and 5
while selecting 5Amp.
Press the arrow key () the relay will display as follow.
General Settings
Com Port = RS232
RS232/RS485Use Inr/Dec
By using the up arrow key ()
or the down arrow key ()
the Com Port can be set. It can be set either RS232 Serial
Port or RS485 Port.Press the arrow key () the relay will display as follow.
General Settings
Set Parity = Even
None/Even/Odd
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
the desired Set Parity can be set, that is None/Even/Odd.
Press the arrow key () the relay will display as follow.
General Settings
BF Cont = SR
SR/HR
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
the BF Contact can be set, that is SR (Self Reset) or HR
(Hand Reset).
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
58/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page26/95
General Settings
CT Primary = 0100
Range 10-2000
Use Inr/Dec
By using the up arrow key ()
or the down arrow key ()
the CT Primary setting can be applicable for protection
function such as Ip> , Ip>> , Ip>>> , 3Io >, 3Io>>, 3Io>>>,
NPS>>,NPS>>>.
The range for CT Primary setting is form 10 to 2000 insteps of 1.
Press the arrow key () the relay will display as follow.
General Settings
Local Control = YES
YES / NO
Use Inr/Dec
By using the up arrow key ()
or the down arrow key ()
Local Control selection can be enable TRIP push button
function from relays front plate.
Press the arrow key () the relay will display as follow.
General Settings
Trip Ckt = NO
YES/NO
Use Inr/Dec
By using the up arrow key ()
or the down arrow key ()
Trip Circuit Supervision function can be Enable / Disable that
is YES or NO. If set YES then the Trip Circuit Supervision
function will be Enable, if it is set as NO then Trip Circuit
Supervision function will be Disable
Press the arrow key () the relay will display as follow.
General Settings
Trip Cont = SR
SR/HR
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
the Trip Contact can be set, that is SR (Self Reset) or HR
(Hand Reset).
Press the arrow key () the relay will display as follow.
General Settings
CT Sec. EF = 1 Amp
1Amp/5Amp
Use Inr/Dec
By using the up arrow key ()or the down arrow key ()
the CT Sec. Setting of protection function such as IE>,
IE>>, IE>>> can be selected 1 Amp. or 5 Amp.
Note : Care should be taken to see proper connection
are established at the back terminal, i.e. between Com.
and 1 while selecting 1 Amp and between Com. and 5
while selecting 5Amp.
Press the arrow key () the relay will display as follow.
General Settings
Active Group = G1
G1 / G2
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
Active Group can be selected.
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
59/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page27/95
Save Settings
Mode for Save
To Saveany changes.
Press the arrow key () the relay will save the change and
the following message is display.
Note : If changes made are not to be saved press LED
Reset or leave key pad untouched for 100 sec.
OK
This window will flash for moment
The control will return to the main menu
General Setting
General Settings
Cold Ld. PKP = NO
YES / NO
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
the Cold Load Pick-up function can be Enable / Disable,
That is YES for Enable and NO for Disable.
Press the arrow key () the relay will display as follow.
-
8/11/2019 Ashida Relay
60/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page28/95
4.4.4.2. To View General Setting
General Setting
Press the arrow key () the relay will display as follow.
General Setting
Language Sel. = ENG
Unit ID = 0001
Baud Rate = 09600
Com Port = RS232
This window will show General Setting done previously.
Press the arrow key () the relay will display as follow.
This is Page 1
Set Parity = Even
BF Enable = YES
BF Delay = 0200
BF Cont = SR
This window will show General Setting done previously.
Press the arrow key () the relay will display as follow.
This is Page 2
CT Sec. = 1Amp
CT Sec. EF = 1Amp
CT Primary = 0100Local Control = YES
This window will show General Setting done previously.
Press the arrow key () the relay will display the mainmenu.
This is Page 3
Trip Ckt = NO
Trip Cont. = SR
Active Group = G1
Cold Ld PKP = NO
This window will show General Setting done previously.
Press the arrow key () the relay will display the mainmenu.
This is Page 3
-
8/11/2019 Ashida Relay
61/233
NUMERICAL OVER CURRENT PROTECTION RELAY ADR241B_V2
USERS GUIDE
ASHIDA Elec tron ics Pv t. Ltd.
Ref: Manual/ADR241B_V2/User_Guide
Issue: 02
Date : 15.11..2008
Page29/95
4.4.5. OVER CURRENT (OC- G1) SETTINGS
4.4.5.1. To Set :- OC G1 Setting
OC- G1 SettingPassword protected window for OC-G1 Setting for settingPassword, IP> Stage1 Enable, IP> %Trip Setting, IP> TMS,
IP> Curve selection, IP>C6 Delay, IP>> Stage 2 Enable,
IP>> Trip Setting Stage 2, IP>> TMS, IP>> Curve selection,
IP>>C6 Delay, IP>>> Stage 3 Enable, IP>>>
Instantaneous Element Trip Setting, IP>>> Delay,
Press the arrow key () the relay will display as follow.
Password = 001
Use Inr/Dec
Enter the previously set password, By using the up arrow
key or the down arrow key ().
Note : Default password setting is 000
Press the arrow key () the relay will display as follow.
OC- G1 Settings
IP> Enable = YES
YES/NO
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
the desired IP> Enable(IDMT/DMT Trip setting stage 1) can
be Enable / Disable that is YES / NO respectively.
If set YES then IP> is enabled and if set NO then it will be
disabled.
Press the arrow key () the relay will display as follow.
OC- G1 Settings
IP> = 0020
Range 10%-200%
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
the desired IP> (IDMT/DMT Trip setting stage 1) can be set.
The range is 10% to 200% in steps of 1%.
Press the arrow key () the relay will display as follow.
OC- G1 Settings
IP> TMS = 01.00
Range x0.02-x1.00
Use Inr/Dec
By using the up arrow key () or the down arrow key ()
the desired IP> TMS(IDMT Time Multiplier Setting
stage1 can be set. The range is from x0.02 to x1.00 in steps
of 0.01
Note: If C6 DMT Curve is selected then ignore this setting
Press the arrow key () the relay will display as follow.
OC- G1 Settings
IP> Curve = 0001