ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch...

30
Application of Combustion Blowers ASGE Technical Conference June 7, 2011

Transcript of ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch...

Page 1: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Application of Combustion

Blowers

ASGE Technical Conference

June 7, 2011

Page 2: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Types of Combustion Blowers

• Induced metal

• Induced plastic

• Pressure metal

• Dilution air – water heater

• Non-Dilution air – water heater

• Premix

Page 3: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Induced Draft Metal

CCW rotation with 4” outlet,

C-Frame Motor

Clinch seam construction

CW rotation with 4” outlet,

PSC Motor

Clinch seam construction

Blower taps work well for blocked outlet

Bearing cooling fans

•Aluminized steel housing•Aluminized or galvanized steel impellers•Flue gas temperature throughout housing typically 350˚F - 450˚F•No Condensate

Page 4: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Induced draft Plastic

Internal Fan

Transition Piece with Drain, PVC vent pipeDrain Hole

•Plastic housing•Plastic impellers•Flue gas temperature throughout housing typically 120˚F +/-

Page 5: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Pressure Blowers

Cooling fan

Sleeve Vents

Mounting Flanges

Page 6: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Dilution Air Blowers

Room Air Intake

Room Air Intake

Combustion Exhaust

Page 7: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Dilution Air Blowers

Fresh Air Inlet

Fresh Air Inlet

Exhaust

Water HeaterFlue Gas

Typical 120F

2% CO2 +/-

Outside Airmixing

Exhaust

Typical 400F

8%CO2 +/-

Direct Vent Power Vent

Page 8: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Non-Dilution Air Blowers

•Aluminum or Aluminized steel housing•Aluminized or galvanized steel impellers•Flue gas temperature throughout housing typically 350˚F - 450˚F CAT 1

Page 9: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Premix Blowers

Positive pressure gas valve

Negative pressure gas valve

Page 10: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Typical Combustion Blower Motors• C-Frame – lowest cost and efficiency, up to 2

speeds. Dual and single voltage to 480 VAC.

• Shaded Pole – up to 2 speeds. dual and single

voltage to 480 VAC.

• PSC – (Permanent Split Capacitor Motor) 3

speeds available. Dual & single voltage to 480

VAC.

• 3-Phase - No additional starting devices,

capacitors or switches are required for operation.

Can be controlled with electronics (VFD)

• BLDC/BLAC - Permanent Magnet

Page 11: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

3.3 Motors

Shaded Pole 2-PolePSC2-Pole

Stator

Rotor

Stator

Page 12: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

C-Frame Motor

Stator and BobbinAssembly

Rotor and shaft assembly

Motor

Page 13: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Thermal Protection

Common Protector types include:�Auto reset overloads automatically reconnect

power to the motor after the coils have cooled to a safe level.

�Manual reset protectors include a reset button to close the protector contacts when the motor can be safely re-started.

�One shot protectors will not be reset. The motor winding is permanently opened if the protector operates.

� Impedance protection means the motor is simply to weak to develop dangerously high temperatures. These motors do not include an additional protective device.

.

Page 14: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Types of Bearings

Ball Bearing

Ball Bearing

in a motor

end plate

Sleeve Bearing

in a motor end

plate

Page 15: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Appliance Blower Sizing

• Type of appliance determines the type of combustion blower needed.

• Negative pressure heat exchanger –induced draft blower, Condensing? Flue Temperature?

• Single burner with modulation option –Pre-Mix

Page 16: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Appliance Blower Sizing

•Heat exchanger pressure drop and vent length determine blower pressure requirements•Voltage, number of speeds and speed split. Note: speed tolerance 10% of slip.

Slip = Sync speed – operating speedSynchronous Speed =(120 X Line Freq.)/(#of Poles) or 120 x 60/2 = 3600

•CFM required – Approximately 25 CFM per 100kBtu/hr, if no dilution in the exhaust.

Page 17: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

The 3 Basic Fan Laws:

CFM new / CFM original = RPM new / RPM original

SP new / SP original = (RPM new / RPM original)^2

HP new / HP original = (RPM new / RPM original)^3

Page 18: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Fan Laws

• Flow rate varies directly as the speed ratio

• Flow rate varies directly as the width ratio

• Pressure varies as the square of the speed ratio

• Flow rate varies as the cube of the fan diameter ratio

• Horse Power varies as the cube of the speed ratio.

• Horsepower varies inversely as the square of the density ratio

Pressure varies as the square power of the fan diameterHorsepower varies as the 5th power of the fan diameterHorsepower and pressure vary directly as the air density ratioHorsepower varies directly as the width ratioAir flow varies inversely as the density ratioPressure varies inversely as the density ratioSpeed varies inversely as the density ratio

Page 19: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Motor Testing Torque Curves

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

0 500 1000 1500 2000 2500 3000 3500

To

rqu

e(o

zin

)

Speed(RPM)

Breakdown Point

Start TorqueIdle Speed

Page 20: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Motor Efficiency Curve

0%

5%

10%

15%

20%

25%

30%

35%

40%

0 500 1000 1500 2000 2500 3000 3500

Effic

iency

Speed(RPM)

Operating

range

Page 21: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Blower Wind

Tunnel Curve

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0 20 40 60 80 100

Sta

tic

Pre

ss

ure

In

. W

.C. (@

Std

Air

)

CFM

3280

3300

3320

3340

3360

3380

0 20 40 60 80 100

Sp

ee

d R

PM

Page 22: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Calculate System Curve

• Calculate required combustion air flow required

• Pick that air flow point to get static pressure

• Calculate System Constant (K) = Static Pressure/(air density x CFM^2)

• Generate system curve at various pressure points

Page 23: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Estimate Pressure Drop

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

0 10 20 30 40 50 60 70 80 90

Sta

tic

Pre

ss

ure

In

. W

.C. (@

Std

Air

)

CFM

Dilution air blower

CO2 = 2%

Input = 40,000 But/hr

Heating value = 1020 Btu/ft3

Total Comb Flow = 37.2CFM

System curve

Page 24: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Example - Speed Tolerance

Effects• Appliance 100kBtu/hr, 8.26%CO2, 1.20”

static pressure, 3200RPM, 25CFM.

• Speed tolerance = (3600-3200) x 10% = 40RPM

• At plus tolerance – 3240RPM, 25.3CFM, 8.15% CO2, 1.23” SP.

• At minus tolerance - 3160RPM, 24.7CFM, 8.37% CO2, 1.17” SP.

Page 25: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Example - 60 to 50hz

• Appliance input rate = 400,000Btu/Hr

• Blower – 100CFM 2.7 Static press 3530RPM 60Hz 2.2% slip

• At 50 Hz speed=(120X50/2) X .978 = 2934RPM

• New Flow = 100 X 2940/3530 = 83.3 CFM

• New SP = 2.7 X(2940/3530)^2 = 1.87In.W.C.

Page 26: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

60 to 50hz Effect

• 60hz blower – Gas Input 400,000; 8.3% CO2; 1020HV

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

0 50 100 150 200

Sta

tic

Pre

ss

ure

In

. W

.C (

@ S

td A

ir)

CFM

Blower Performancesystem curve

Page 27: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

60 to 50hz Effect

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

0 20 40 60 80 100 120 140 160 180

Sta

tic

Pre

ss

ure

In

. W

.C (

@ S

td A

ir)

CFM

Blower Performance

system curve

50 hz performance

50Hz Flow pt.

60 Hz flow pt

60 Hz flow

measured

50 Hz flow

fan law

Page 28: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

60 to 50hz Result

• 50hz blower – 83.3CFM

• Gas Input 333,000 with original CO2 = 8.3% & 1020HV

Page 29: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Design to return to 60hz

performance at 50hz• 83.3 to 100 cfm

• 1.87 to 2.7 In. W.C. Static pressure

• Flow rate varies as the cube of the fan diameter ratio

• Pressure varies as the square power of the fan diameter (this example target press)

• Horsepower varies as the 5th power of the fan diameter

Page 30: ASGE Combustion Blowers · Induced Draft Metal CCW rotation with 4” outlet, C-Frame Motor Clinch seam construction CW rotation with 4” outlet, PSC Motor Clinch seam construction

Design to return to 60hz

performance at 50hz

• Current Impeller diameter = 7.0 In.

• Impeller Required = 8.4 in

• New SP = 1.87 X (8.4/7.0)^2 = 2.70

• New Flow = 83.3 X (8.4/7.0)^3 = 144

• HP = .08 X (8.4/7.0)^5 = 0.20