AS2603109_RevInfo_NewsE

8
B&R Revision Information Version 2.6.0.3109 PVI Runtime 10Okt2008

description

another ............

Transcript of AS2603109_RevInfo_NewsE

  • B&R Revision Information

    Version 2.6.0.3109 PVI Runtime10Okt2008

  • ContentsB&R Revision Information (10.10.2008)Version 2.6.0.3109 PVI Runtime.................................................................................................................................................1

    Contents......................................................................................................................................................................................................................................1Requests and problems by ID number........................................................................................................................................................................................1Requests and problems by version.............................................................................................................................................................................................2Requests and problems by product/component..........................................................................................................................................................................2

    1A4000.02 Automation Runtime........................................................................................................................................................................................2AR AR010.............................................................................................................................................................................................................2AR PP400.............................................................................................................................................................................................................2

    1A4000.02 Automation Net/PVI.........................................................................................................................................................................................3ICOMM.....................................................................................................................................................................................................................3INA2000 Line...........................................................................................................................................................................................................3PocketPC.................................................................................................................................................................................................................3PVI DataLogger.......................................................................................................................................................................................................3PVI Manager............................................................................................................................................................................................................3PVI Setup.................................................................................................................................................................................................................4Tools PVITransfer.................................................................................................................................................................................................4Tools PVITransfer 3.01.00.0002...........................................................................................................................................................................6

    Revision Information Version 2.6.0.3109 PVI Runtime i

  • B&R Revision Information (10.10.2008)Version 2.6.0.3109 PVI RuntimeThe current revision information can be downloaded from the B&R Homepage download area (http://www.brautomation.com/download).

    ContentsRequests and problems by ID number Requests and problems by version Requests and problems by product/component

    Requests and problems by ID number

    ID Valuation known since planned for solved since Description

    74445 New function V2.3.0.0009 V2.6.0.3101 V2.6.0.3101 Windows CE 5.0 support

    147775 Projekt V2.6.0.3108 V2.6.0.3108 New command "Logger": Load and interpret loggermodules

    149175 Problem V2.6.0.3106 V2.6.0.3106 USB / LPT dongle request blocks communication forapprox. 300 ms

    153875 Problem V2.5.3.3105 V2.6.0.3102 V2.6.0.3102 Termination condition no longer works

    159250 New function V2.5.3.3107 V2.6.0.3101 V2.6.0.3102 New command "ARUpdateFileGenerate": Adding thesysconf to the AR update file

    162985 New function V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 I/O monitor support for SGC Targets

    163610 Problem V2.6.0.0003 V2.6.0.3101 V2.6.0.3102 "Create remote install structure" does not workwithout operating system file

    164075 Problem V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 Variable watch: Structure components are onlyshown partially

    164325 Problem V2.5.3.3007 V2.6.0.3101 V2.6.0.3102 "WriteVariableListToPLC" command doesn't workwith TIME variables

    165020 Problem V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 CF creation doesn't work if one has read only accessto the project directory165735 Problem V3.0.70.4 V2.6.0.3101 V2.6.0.3102 CF creation: Problems (CPU never finishes booting)

    with AR 2.92 for large HW configurations

    166440 Problem V2.5.3.3007 V2.6.0.3106 V2.6.0.3106 When the PVI manager is active, a dongle can onlybe read once166575 Problem V2.6.0.3106 V2.6.0.3106 Dongle not recognized 2nd time AR010 is started

    166950 Problem V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 CD creation: The file "bootrom_pp400.sys" ismissing from the output directory

    166965 Problem V2.6.0.3102 V2.6.0.3101 Connection loss when downloading project168200 Problem V2.5.3.0028.SP05 [U2.90] V2.6.0.3102 V2.6.0.3102 Error during MEMCARD UPDATE169020 Problem V2.5.3.3109 V2.6.0.3102 V2.6.0.3102 Error messages when opening the PVI OPCConfigurator169627 Problem V2.5.3.3109 V2.6.0.3102 V2.6.0.3102 Crash when deleting data modules

    170110 New function V2.5.3.0026.SP01 [M2.90] V2.6.0.3103 V2.6.0.3103 X20CS1020 and X20CS1030: Outgoing INAconnections don't work

    170755 Problem V3.0.70.5 V2.6.0.3103 V2.6.0.3103 Variables not shown after repeated download

    171325 Problem V2.6.0.3102 V2.6.0.3103 V2.6.0.3103 In Windows Vista PVI Manager doesn't work asservice.

    173570 Problem V2.5.3.3109 V2.6.0.3104 V2.6.0.3104 "RemoteInstallGenerate" command doesn't copydirectory for USER partition

    173985 Problem V3.0.71.1 V2.6.0.3106 V2.6.0.3106 With a certain registration sequence, RF=0 results ina data event never being triggered.

    174135 New function V2.6.0.3103 V2.6.0.3107 V2.6.0.3107 New command: "CFService": Partitions a CF174307 Problem V2.6.0.3106 V2.6.0.3106 bootrom.sys delays boot by approx. 6 seconds174605 New function V2.6.0.0007 V2.6.0.3108 V2.6.0.3108 Remote install of the CF (user partition)174670 Problem V2.6.0.3002 V2.6.0.3104 V2.6.0.3104 CF images can't be restored on 64 MB SiliconSystems CF cards

    175420 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 "CFGenerate" command: Path for USER partitiondata can not be entered as a relative path

    176650 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 CF creation: Image file can no longer be createdafter process is canceled

    176695 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 Dialog box for selecting the CF appears in thebackground

    177495 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 CD creation: No relative paths are entered for thecommand "CFRestoreFiles"

    178315 Problem V2.6.0.3106 V2.6.0.3108 V2.6.0.3108 CF creation: Operating system error nr. 2 if CF is4GB

    179015 Problem V2.6.0.3106 V2.6.0.3107 V2.6.0.3107 With Windows 2000, CF can only be created oncewithout administrator rights

    179095 Problem V2.6.0.3103 V2.6.0.3107 V2.6.0.3107 Exit code not set when error occurs

    179825 Problem V2.6.0.3104 V2.6.0.3109 V2.6.0.3109 / 3.01.00.0002 User mode: "Initialization..." dialog box stays onscreen

    179835 Problem V2.6.0.3104 V2.6.0.3108 V2.6.0.3108 User mode: File for the command "CFRestore" notfound179840 Problem V2.6.0.3104 V2.6.0.3109 V2.6.0.3109 / 3.01.00.0002 User mode: Progress bar remains in the same place

  • for very long time179845 New function V2.6.0.3109 V2.6.0.3109 / 3.01.00.0002 User mode: Updates to the layout

    181845 New function V2.6.0.3107 V2.6.0.3108 V2.6.0.3108 "CFRestoreFiles" command can also createpartitions on a CF card

    184495 Problem V2.6.0.3108 V2.6.0.3109 V2.6.0.3109 / 3.01.00.0002 "CFRestoreFiles" command with partition datadoesn't create a BootLoader with PP400 CF185265 Problem ARSG4_2.95.2_B02.95 V2.6.0.3109 Checksum errors at download

    Requests and problems by version

    ID valuation known since planned for solved since Description

    185265 Problem ARSG4_2.95.2_B02.95 V2.6.0.3109 Checksum errors at download74445 New function V2.3.0.0009 V2.6.0.3101 V2.6.0.3101 Windows CE 5.0 support166965 Problem V2.6.0.3102 V2.6.0.3101 Connection loss when downloading project164325 Problem V2.5.3.3007 V2.6.0.3101 V2.6.0.3102 "WriteVariableListToPLC" command doesn't work with TIME variables159250 New function V2.5.3.3107 V2.6.0.3101 V2.6.0.3102 New command "ARUpdateFileGenerate": Adding the sysconf to the AR update file162985 New function V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 I/O monitor support for SGC Targets166950 Problem V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 CD creation: The file "bootrom_pp400.sys" is missing from the output directory165020 Problem V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 CF creation doesn't work if one has read only access to the project directory164075 Problem V2.5.3.3109 V2.6.0.3101 V2.6.0.3102 Variable watch: Structure components are only shown partially163610 Problem V2.6.0.0003 V2.6.0.3101 V2.6.0.3102 "Create remote install structure" does not work without operating system file

    165735 Problem V3.0.70.4 V2.6.0.3101 V2.6.0.3102 CF creation: Problems (CPU never finishes booting) with AR 2.92 for large HWconfigurations

    168200 Problem V2.5.3.0028.SP05 [U2.90] V2.6.0.3102 V2.6.0.3102 Error during MEMCARD UPDATE153875 Problem V2.5.3.3105 V2.6.0.3102 V2.6.0.3102 Termination condition no longer works169627 Problem V2.5.3.3109 V2.6.0.3102 V2.6.0.3102 Crash when deleting data modules169020 Problem V2.5.3.3109 V2.6.0.3102 V2.6.0.3102 Error messages when opening the PVI OPC Configurator170110 New function V2.5.3.0026.SP01 [M2.90] V2.6.0.3103 V2.6.0.3103 X20CS1020 and X20CS1030: Outgoing INA connections don't work171325 Problem V2.6.0.3102 V2.6.0.3103 V2.6.0.3103 In Windows Vista PVI Manager doesn't work as service.170755 Problem V3.0.70.5 V2.6.0.3103 V2.6.0.3103 Variables not shown after repeated download173570 Problem V2.5.3.3109 V2.6.0.3104 V2.6.0.3104 "RemoteInstallGenerate" command doesn't copy directory for USER partition174670 Problem V2.6.0.3002 V2.6.0.3104 V2.6.0.3104 CF images can't be restored on 64 MB Silicon Systems CF cards166575 Problem V2.6.0.3106 V2.6.0.3106 Dongle not recognized 2nd time AR010 is started174307 Problem V2.6.0.3106 V2.6.0.3106 bootrom.sys delays boot by approx. 6 seconds149175 Problem V2.6.0.3106 V2.6.0.3106 USB / LPT dongle request blocks communication for approx. 300 ms166440 Problem V2.5.3.3007 V2.6.0.3106 V2.6.0.3106 When the PVI manager is active, a dongle can only be read once

    173985 Problem V3.0.71.1 V2.6.0.3106 V2.6.0.3106 With a certain registration sequence, RF=0 results in a data event never beingtriggered.179095 Problem V2.6.0.3103 V2.6.0.3107 V2.6.0.3107 Exit code not set when error occurs174135 New function V2.6.0.3103 V2.6.0.3107 V2.6.0.3107 New command: "CFService": Partitions a CF177495 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 CD creation: No relative paths are entered for the command "CFRestoreFiles"176695 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 Dialog box for selecting the CF appears in the background176650 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 CF creation: Image file can no longer be created after process is canceled

    175420 Problem V2.6.0.3104 V2.6.0.3107 V2.6.0.3107 "CFGenerate" command: Path for USER partition data can not be entered as a relativepath179015 Problem V2.6.0.3106 V2.6.0.3107 V2.6.0.3107 With Windows 2000, CF can only be created once without administrator rights147775 Projekt V2.6.0.3108 V2.6.0.3108 New command "Logger": Load and interpret logger modules174605 New function V2.6.0.0007 V2.6.0.3108 V2.6.0.3108 Remote install of the CF (user partition)179835 Problem V2.6.0.3104 V2.6.0.3108 V2.6.0.3108 User mode: File for the command "CFRestore" not found178315 Problem V2.6.0.3106 V2.6.0.3108 V2.6.0.3108 CF creation: Operating system error nr. 2 if CF is 4GB181845 New function V2.6.0.3107 V2.6.0.3108 V2.6.0.3108 "CFRestoreFiles" command can also create partitions on a CF card

    Requests and problems by product/component1A4000.02 Automation Runtime

    AR AR010

    ID#166575 : solved problem, known since unbekannt, solved since V2.6.0.3106

    Dongle not recognized 2nd time AR010 is started

    If the PVI manager and AR010 are running on a PC at the same time, AR010 no longer recognizes the dongle. If the PVI manager is closed,the problem goes away.

    AR PP400

    ID#174307 : solved problem, known since unbekannt, solved since V2.6.0.3106

    bootrom.sys delays boot by approx. 6 seconds

    If a PLC (AR10x, PP300, PP400) is booted when the network cable is unplugged, the boot process is delayed by 5 seconds.

    Revision Information Version 2.6.0.3109 PVI Runtime 2

  • 1A4000.02 Automation Net/PVI

    ICOMM

    ID#168200 : solved problem, known since V2.5.3.0028.SP05 [U2.90], solved since V2.6.0.3102

    Error during MEMCARD UPDATE

    In rare cases, deleting the Memcard before creating the Memcard update causes an error.

    ID#166965 : solved problem, known since unbekannt, solved since V2.6.0.3101

    Connection loss when downloading project

    If many PVs are registered with an open watch window at the time of the download, connection losses can occur.

    ID#170110 : new function since V2.6.0.3103

    X20CS1020 and X20CS1030: Outgoing INA connections don't work

    You can't establish a connection to another device from an interface an an X20CS1020 or X20CS1030 module, because of limitations in theINA addressing string.

    ID#162985 : new function since V2.6.0.3102

    I/O monitor support for SGC Targets

    INA2000 Line

    ID#170755 : solved problem, known since V3.0.70.5, solved since V2.6.0.3103

    Variables not shown after repeated download

    ID#169627 : solved problem, known since V2.5.3.3109, solved since V2.6.0.3102

    Crash when deleting data modules

    ID#185265 : known problem since ARSG4_2.95.2_B02.95, correction planned for V2.6.0.3109

    Checksum errors at download

    PocketPC

    ID#74445 : new function since V2.6.0.3101

    Windows CE 5.0 support

    PVI support for Windows CE 5.0 platforms (PP100, PP40/50, Windows Pocket PC)

    PVI DataLogger

    ID#153875 : solved problem, known since V2.5.3.3105, solved since V2.6.0.3102

    Termination condition no longer works

    PVI Manager

    ID#173985 : solved problem, known since V3.0.71.1, solved since V2.6.0.3106

    With a certain registration sequence, RF=0 results in a data event never being triggered.

    If a process object is only setup with EV=e and then EV=d or EV=ed is set, the data event is not triggered until the next cyclic read. WhenRF=0, no cyclic read is triggered. Now a read is always started after a change to the "ed" events.

    ID#171325 : solved problem, known since V2.6.0.3102, solved since V2.6.0.3103

    In Windows Vista PVI Manager doesn't work as service.

    In Windows Vista the PVI Manager can not be operated as a service.

    ID#166440 : solved problem, known since V2.5.3.3007, solved since V2.6.0.3106

    When the PVI manager is active, a dongle can only be read once

    Once the PVI manager is started, the dongle can only be read one more time. If you call BrSecChk.exe again, the dongle can no longer befound. The problem only occurs with the LPT1 dongle holder on the APC.A USB dongle can be read multiple times even when the PVI manager is running.

    ID#149175 : solved problem, known since unbekannt, solved since V2.6.0.3106

    USB / LPT dongle request blocks communication for approx. 300 ms

    When using a USB or LPT dongle, communication with the PLC is blocked for approximately 300 ms each minute.

    Revision Information Version 2.6.0.3109 PVI Runtime 3

  • PVI Setup

    ID#179095 : solved problem, known since V2.6.0.3103, solved since V2.6.0.3107

    Exit code not set when error occurs

    When the PVI setup is opened from the command line (in autoinstall mode), the exit code is not set when the following errors occur: The PVI setup is installed in a writeprotected directory The PVI manager is running

    ID#169020 : solved problem, known since V2.5.3.3109, solved since V2.6.0.3102

    Error messages when opening the PVI OPC Configurator

    When starting the PVI OPC Configurator, error messages appeared stating that the OS9 Arcnet and MTC lines could not be loaded.

    Tools PVITransfer

    ID#179835 : solved problem, known since V2.6.0.3104, solved since V2.6.0.3108

    User mode: File for the command "CFRestore" not found

    If the command "CFRestore" is used in an include statement in user mode, the corresponding mapping file can sometimes not be found. Theproblem only occurs when the path for the mapping file is entered as a relative path, and the mapping file is in a subdirectory.

    ID#179015 : solved problem, known since V2.6.0.3106, solved since V2.6.0.3107

    With Windows 2000, CF can only be created once without administrator rights

    If a CF is created in Windows 2000 without administrator rights, on some PCs this process can't be repeated. During the second attempt no CFis displayed, so the process no longer works.The PC must be restarted in order for a second CF to be generated. This problem does not occur when the user has administrator rights.

    ID#178315 : solved problem, known since V2.6.0.3106, solved since V2.6.0.3108

    CF creation: Operating system error nr. 2 if CF is 4GB

    If a 4GB CF is created with relatively small partitions (e.g. 5MB), the following error message appears: "Operating system error nr. 2 occurred.Details: The system cannot find the specified file".If the size of the partitions is increased (e.g. 15MB), the problem no longer occurs.

    ID#177495 : solved problem, known since V2.6.0.3104, solved since V2.6.0.3107

    CD creation: No relative paths are entered for the command "CFRestoreFiles"

    If a CD is created from a .pil file that contains the "CFRestoreFiles" command, it will not work. The problem is that the paths are not entered asrelative paths for the "CFRestoreFiles" command.

    ID#176695 : solved problem, known since V2.6.0.3104, solved since V2.6.0.3107

    Dialog box for selecting the CF appears in the background

    If a CF is created automatically using the .pil file, under certain circumstances the dialog for selecting the CF appears in the background.

    ID#176650 : solved problem, known since V2.6.0.3104, solved since V2.6.0.3107

    CF creation: Image file can no longer be created after process is canceled

    If the process is cancelled while creating an image file, an image file can then no longer be created. The dialog window must be closed andreopened before an image can be created again.

    ID#175420 : solved problem, known since V2.6.0.3104, solved since V2.6.0.3107

    "CFGenerate" command: Path for USER partition data can not be entered as a relative path

    For the CFGenerate command, if the path for the USER partition data is entered as a relative path, even though it is correct it will result in anerror message stating that the directory does not exist.

    ID#174670 : solved problem, known since V2.6.0.3002, solved since V2.6.0.3104

    CF images can't be restored on 64 MB Silicon Systems CF cards

    If an image is created from a 64 MB SanDisk or Silicon Systems CF card, the image file can be restored, but the resulting CF card doesn'twork. The respective target system (e.g. PP400) can't be started with this CF card.This problem only occurs when the image is restored on a 64 MB card from Silicon Systems. If the image is restored on a 64 MB card fromSanDisk, the error doesn't occur.

    ID#173570 : solved problem, known since V2.5.3.3109, solved since V2.6.0.3104

    "RemoteInstallGenerate" command doesn't copy directory for USER partition

    If a directory is specified for the USER partition, it is not copied when generating the remote install structure.

    Revision Information Version 2.6.0.3109 PVI Runtime 4

  • ID#166950 : solved problem, known since V2.5.3.3109, solved since V2.6.0.3102

    CD creation: The file "bootrom_pp400.sys" is missing from the output directory

    When a CD is created from a PP300/PP400 project, the file "bootrom_pp400.sys" is missing from the created directory. As a result, the CDthat is created cannot be used to setup a CompactFlash card for a PP300/PP400 device.

    Workaround:The file "bootrom_pp400.sys" must be manually copied from the PVI Transfer installation folder to the output directory.

    ID#165735 : solved problem, known since V3.0.70.4, solved since V2.6.0.3102

    CF creation: Problems (CPU never finishes booting) with AR 2.92 for large HW configurations

    When the PVI Transfer Tool is used to create a CF for AR 2.92 (or higher), and the HW configuration is large, the CPU gets stuck in the bootprocedure and never finishes. The reason for this is that the default setting for the SYSTEM partition of the PVI Transfer Tool is too small.

    Workaround:The size of the SYSTEM partition must be increased manually before creating the CF.

    ID#165020 : solved problem, known since V2.5.3.3109, solved since V2.6.0.3102

    CF creation doesn't work if one has read only access to the project directory

    When the user only has read only access to the project from which a CF should be created, the CF creation is completed without errors, butthe resulting CF is empty.The problem occurs, for example, when a user tries to create a CF from a project that is stored on a network (where he or she has read onlyrights). The CF is created without errors, but is empty.

    ID#164325 : solved problem, known since V2.5.3.3007, solved since V2.6.0.3102

    "WriteVariableListToPLC" command doesn't work with TIME variables

    If the command "WriteVariableListToPLC" is used to write a TIME variable to the PLC, the TIME value does not reach the PLC correctly. If,however, the function "WriteVariable" is used, everything works fine.

    ID#164075 : solved problem, known since V2.5.3.3109, solved since V2.6.0.3102

    Variable watch: Structure components are only shown partially

    If the command "VariableWatch" is used to monitor multiple structure components from the same structure, only the first structure componentis ever shown, all others are not.

    ID#163610 : solved problem, known since V2.6.0.0003, solved since V2.6.0.3102

    "Create remote install structure" does not work without operating system file

    If you select the option "Installation/Update of Automation Runtime" and begin the process of creating a remote install structure without havinga valid .pil file, the PVI Transfer Tool will crash.

    ID#181845 : new function since V2.6.0.3108

    "CFRestoreFiles" command can also create partitions on a CF card

    A new parameter has been added to the command "CFRestoreFiles". This parameter can also be used to partition the CF card before copying.The same functions are now available as for the "CFService" command. This makes it possible to completely install a CF card in one step (withone command).

    ID#174605 : new function since V2.6.0.3108

    Remote install of the CF (user partition)

    Option for generating a remote install structure for a CF card added for the function "Generate remote install structure" and the command"RemoteInstallGenerate". The created directory structure can then be copied directly to the USER partition of the CF card.

    ID#174135 : new function since V2.6.0.3107

    New command: "CFService": Partitions a CF

    The new "CFService" command can be used to partition a CF card without copying data to it.

    ID#159250 : new function since V2.6.0.3102

    New command "ARUpdateFileGenerate": Adding the sysconf to the AR update file

    The "ARUpdateFileGenerate" command is used to generate an AR update file (.br) from an AR base file (.s*). The AR update file can then betransferred directly to the PLC, where it updates Automation Runtime. You can also add .br modules such as sysconf.br to the AR update file.

    ID#147775 : new function since V2.6.0.3108

    New command "Logger": Load and interpret logger modules

    The new "logger" command can be used to load and interpret logger modules. The following functions are available: Load the system logger module

    Revision Information Version 2.6.0.3109 PVI Runtime 5

  • Load the user logger module Load a usercreated logger module Interpret an existing .br file that contains logger data

    The logger data can be saved in the following output formats: .arl .csv .html

    Tools PVITransfer 3.01.00.0002

    ID#184495 : solved problem, known since V2.6.0.3108, solved since V2.6.0.3109

    "CFRestoreFiles" command with partition data doesn't create a BootLoader with PP400 CF

    If the command "CFRestoreFiles" is used to generate a CF with partition data for a PP400, the PP400 doesn't boot. On the PP400 you get themessage "No boot device present. Halting".

    ID#179840 : solved problem, known since V2.6.0.3104, solved since V2.6.0.3109

    User mode: Progress bar remains in the same place for very long time

    If multiple commands are called in sequence in user mode (using "include" command), the progress bar stops moving for a long time. Thisproblem occurs when a command is used that takes a long time (e.g. CFRestore). For the user, it appears that the process has frozen.

    ID#179825 : solved problem, known since V2.6.0.3104, solved since V2.6.0.3109

    User mode: "Initialization..." dialog box stays on screen

    In user mode, the "Initialization" output stays in the middle of the screen throughout the initialization phase. During long initialization phasesthis dialog box is usually in the way, and the process cannot be stopped during this time.

    ID#179845 : new function since V2.6.0.3109

    User mode: Updates to the layout

    The following changes were made to user mode: In order to display the progress better, there are now 2 progress bars (current command and total progress) New command "CustomModeSettings": This command makes it possible to turn the online status on/off (connection status and PLCinformation) during runtime.

    Revision Information Version 2.6.0.3109 PVI Runtime 6

    ContentsB&R Revision Information (10.10.2008)Version 2.6.0.3109 PVI RuntimeContentsRequests and problems by ID numberRequests and problems by versionRequests and problems by product/component1A4000.02 Automation RuntimeAR - AR010AR - PP400

    1A4000.02 Automation Net/PVIICOMMINA2000 LinePocketPCPVI DataLoggerPVI ManagerPVI SetupTools - PVITransferTools - PVITransfer 3.01.00.0002