Article 352. PVC Conduit Part I. General 352.2 Definition Part II. Installation 352.10 Uses Permitted FPN: In extreme cold, PVC conduit can become brittle and is more susceptible to physical damage. 352.10 Uses Permitted (F) Exposed. Schedule 40 PVC conduit is permitted where not subject to physical damage.

Transcript of Article 352. PVC Conduit 352.10 Uses Permitted Part I ... 3… · PVC conduit is prohibited as a...

Article 352. PVC Conduit

Part I. General

352.2 Definition

Part II. Installation

352.10 Uses Permitted

FPN: In extreme cold, PVC conduit can become brittle and is more susceptible to physical damage.

352.10 Uses Permitted

(F) Exposed. Schedule 40 PVC conduit is permitted where not subject to physical damage.

352.12 Uses Not Permitted

(B) Support of Luminaires. PVC conduit cannot be used for the support of luminaires or other equipment.

352.12 Uses Not Permitted

(C) Physical Damage. Where subject to physical damage, unless identified for such use.

352.12 Uses Not Permitted

(D) Ambient Temperature. PVC conduit cannot be installed where the ambient temperature exceeds 122°F.

352.12 Uses Not Permitted

(E) Operating Temperature.

352.12 Uses Not Permitted

(E) Operating Temperature. Exception: Conductors rated above the PVC

conduit temperature rating can be installed if the conductors do not operate at a temperature above the raceway temperature rating.

Author’s Comment

PVC conduit is prohibited as a wiring method for patient care areas in health care facilities [517.13(A)] or in ducts, plenums, and other environmental air spaces [300.22].

352.20 Trade Size

(A) Minimum. Trade size ½.(B) Maximum. Trade size 6.

352.26 Number of Bends

352.28 Trimming

The cut ends of PVC conduit must be trimmed (inside and out) to remove the burrs and rough edges.

352.30 Secured and Supported

(A) Secured. PVC conduit must be secured within 3 ft of every box, cabinet, or termination fitting, such as a conduit body.

352.30 Secured and Supported

(B) Supports. PVC conduit must be supported at intervals not exceeding the values in Table 352.30.

352.30 Securing and Supporting

(C) Unsupported Raceways.

352.44 Expansion Fittings 352.46 Bushings

352.60 Equipment Grounding Conductor