Argus 7

download Argus 7

of 4

Transcript of Argus 7

  • 7/27/2019 Argus 7

    1/4

    NumericalCheck SynchronisingProtection Relay

    FeaturesArgus 7 is a combined check and system synchronising relay

    which can automatically select check or system synchronise from

    measurements of the relative phase angles between line and

    bus voltages. The relay will prevent closure of the circuit breaker

    if either the phase angle, slip frequency or the voltage magnitude

    of the incoming and running voltages fall outside

    prescribed limits.

    If the parameters are within the limits the relay will issue an

    output which can be used to close the circuit breaker directly or

    in conjunction with an autoreclose scheme. Both the check and

    system synchronise functions have independent settings andblocking features. The relay includes split system detection with

    a variable time delay, which can be used for blocking purposes

    within delayed autoreclose schemes.

    Synchronising bypass logic is provided to connect a dead line

    or bus to a live line or bus. For manual synchronising the relay

    includes a circuit breaker close guard feature which is used to

    prevent the control switch being held closed during a

    synchronising operation. This feature is implemented using

    internal logic and removes the need for an external relay.

    Applications

    Protection

    Check synchronising (25) and system synchronising

    Under voltage blocking (27)

    Differential blocking

    Control

    The basic Argus 7 relay contains 4 programmable digital

    (status) inputs with programmable pick-up and drop-off timers

    The Argus 7 relay contains 7 programmable output

    relays out of which 1 have CO contact 1 have NC contact

    and 5 have NO contacts Configurable dead bus and/or dead line charge

    Adjustable slip frequency, phase angle and time delay

    Integrated manual close guard feature

    Independent Check synchronising and system synchronising

    settings

    Description

    Check synchronising (25) and system

    synchronising

    Numerical Check Synchronising Protection Relay - Argus 7

    ARGUS 7

  • 7/27/2019 Argus 7

    2/4

    Monitoring

    Split system detection Storage of 500 time-tagged event records

    Storage of 5 wave form records

    Metering

    Primary RMS voltage for both line & bus

    Secondary RMS voltage for both line & bus

    Frequency of both line & bus

    Phase difference between line & bus

    Frequency slip between line & bus

    Phase - In/out limits

    Slip - In/out limits

    Line and bus health status (ie live and dead)

    Voltage blocking element status

    User Interface

    Backlit liquid crystal alpha-numeric display with

    16-characters, 2 lines

    LEDs for check/system sync system split and

    protection healthy

    Push buttons for programming and resetting

    Communication

    Fibre optic communication port at rear

    Data communication using IEC 60870-5-103 protocol

    Wiring Diagram

    Notes1. VT Connections are shown for phase-neutral,

    phase-phase is also possible.

    2. VT & Earth connections are typical only.

  • 7/27/2019 Argus 7

    3/4

    VT Input Rating63.5/110V AC, 50/60Hz

    SettingsVT ratio 1:1 to 9999:1

    Check sync AUTO, MANUAL

    Phase angle 5 to 90 1

    Slip timer OFF, 0.1 to 100.0 sec 0.1 sec

    Slip frequency OFF, 0 to 2.000Hz 0.005Hz

    Dead voltage 5 to 127V 0.5V

    Live voltage 10 to 132V 0.5V

    Line undervoltage OFF, 22 to 132V 0.5V

    Bus undervoltage OFF, 22 to 132V

    0.5VDifferential

    Voltage OFF, 0.5 to 44V 0.5V

    Sync bypass OFF, DL&LB, LL&DB, DL&DB,

    DL or DB, DL&/or DB

    System split OFF, 90 to 175 1

    Split timer OFF, 0.1 to 100.0 sec 0.1 sec

    Manual close

    guard function OFF/ON

    System sync LOCKOUT, AUTO, MANUAL

    Phase angle 5 to 90 1

    Slip timer OFF, 0.1 to 100.0 sec 0.1 sec

    Slip frequency OFF, 0 to 2.000Hz 0.005Hz

    Close pulse 0.1 to 2 sec 0.1 sec

    DC Auxiliary supplyNominal Operating range

    24, 30, 48V 18-60V

    110, 220V 88-280V

    Output relays The Argus 7 relay contains 7 programmable output relays out

    of which 1 have CO contact 1 have NC contact and 5 have

    no contacts

    Contact ratings

    Carry continuously 5A AC or DCMake and carry 30A AC or DC for 0.2sec

    Resistive break 75W DC, 1250VA AC

    DC digital(status) inputThe Argus 7 relay contains 4 programmable digital (status) inputs

    which have programmable pick-up and drop-off timers.

    Nominal Operating Range

    30 V DC 18 - 37.5V DC

    48 V DC 37.5 - 60V DC

    110/125 V DC 87.5 - 137.5 V DC

    220/250 V DC 175 - 280 V DC

    For relays to ESI48-4 standard and 110/125 or 220/250

    Technical Information volt DC working a 48 volt digital (status) input is supplied for

    use with external dropper resistors:110/125V Resistor 2K7 5% 2.5W

    270/250V Resistor 8K2 5% 6.0W

    BurdensAC < 0.2VA

    DC 3W Quiescent (Typical)

    10W maximum

    Indications LEDs for check/system sync, system split and protection healthy

    indications

    LCD - alphanumeric display for settings, instruments and fault

    data

    EnvironmentalTemperature IEC 68-2-1/2

    Operating range -10C to +55C

    Storage range -25C to +70C

    Humidity IEC 68-2-3

    Vibration IEC 255-21-1 class I

    Shock and bump IEC 255-21-2 class I

    Seismic IEC 255-21-3 class I

    Insulation IEC 255-5

    2 KVrms for 1 min all terminals to earth.

    2 KVrms for 1 min between independent circuits.

    1 KVrms for 1 minute across NO contacts.

    Transient overvoltage IEC 255-4 class III

    5KV 1.2/50s between all terminals and earth without

    damage or flashover.

    High frequency disturbance IEC 255-22-1 class III

    2.5KV common mode < 3% deviation

    1.0KV series mode < 3% deviation

    Electrostatic discharge IEC 255-22-2 class III

    8KV direct without maloperation or damage

    Radio frequency disturbance IEC 255-22-3

    20MHz to 1GHz at 10V/m < 5% deviation

    Fast transient IEC 255-22-4 class IV

    4KV 5/50ns < 3% deviation

    Mechanical ClassificationDurability 106 operations

  • 7/27/2019 Argus 7

    4/4

    Auxiliary and digital (status) input voltage

    Qualification

    ISO 9001 - 2000

    Cutout Details

    Ordering Information

    F A C T / A R G U S

    7 / 1 2 -

    0 5 / R E V

    0

    Case WeightArgus 7 - E4 3.15 kg

    The policy of Easun Reyrolle is one of continuous improvement and development. The company therefore reserves the right to supply equipment, which may

    differ slightly from that described and illustrated in this publication.

    AUTOMATION DIVISION

    Ashirwad, #25, 29th Main,4th B Cross, BTM Layout 2nd Stage,Bangalore-560 076, India.Tel: +91 80 26685496/51311405Fax: +91 80 26685446Email: [email protected]

    HOSUR WORKS#98, Sipcot Industrial Complex,Hosur 635 126, India.Tel: +91 4344 401600/01/02Fax: +91 4344 276397

    SWITCHGEAR WORKS

    Ernavur,Chennai-600 057, India.Tel: +91 44 25733715/358Fax: +91 44 25733468Email: [email protected]

    BANGALORE WORKS#17/3 Arakere,Bannerghatta Road,Bangalore-560 076, India.Tel: +91 80 26581023 / 3268Fax: +91 80 26580642Email: [email protected]

    EXPORTS DIVISION

    #17/3 Arakere,Bannerghatta Road,Bangalore-560 076, India.Tel: +91 80 26581023 / 3268Fax: +91 80 26580642Email: [email protected]

    Sales Offices

    MumbaiTel: +91 22 22022270/22855415Fax: +91 22 22825703Email: [email protected]

    BangaloreTel: +91 80 26685496/51311405Fax: +91 22 26685446Email: [email protected]

    BhopalTelefax: +91 755 2684221Email: [email protected]

    DelhiTel: +91 11 25747321/25747322Fax: +91 11 25747320Email: [email protected]

    ChennaiTel: +91 44 24346425/24347608Fax: +91 44 24346435Email: [email protected]

    SecunderabadTelefax: +91 40 27817847Email: [email protected]

    KolkataTel: +91 33 22848320Fax: +91 33 22848326Email: [email protected]

    Corporate Office

    Easun Reyrolle Limited. 98 Sipcot Industrial ComplexHosur 635 126 India. Tel: +91 4344 401600/01/02Fax: +91 4344 276397

    www.easunreyrolle.com