JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 1
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
1. GENERAL DATA & INFORMATION:
2. GENERAL INSPECTION & WIRING CHECK:
SR.NO. ITEM DESCRIPTION REMARKS
1 Inspect for any physical damage or defects.
2 Verify connections as per approved drawings.
3 Check tightness of all the connections.
4 Case Earthing verified
3. ELECTRICAL TEST:
RELAY CHECKS: (WITH RELAY ENERGISED)
Sr. No.
Description
1 Watchdog contacts (M11-M12 opened. M13-M14 Closed)
2Dated & time - Set Clock to local time - Time Maintained when aux. Supply removed
3Alarm (yellow) LED - to check make test Mode Enable under commissioning test meanu.
4Out of service (yellow) LED - to check make test Mode Enable under commissioning test meanu.
5 Trip (red) LED - apply any fault to produce any trip condition
6 All & programmable LEDs - apply test LED under commissioning test menu.
7 Measured Field supply voltage
- Between terminals M7 and M9 =
- Between terminals M8 and M10 =
INPUT OPTO-ISOLATORS CHECKS: (WITH RELAY ENERGISED)
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Make Designation
Model / Type Aux. Voltage
Sr. No. Rated Voltage (Vn)
Rated Current (In)
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign
JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 2
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
Opto Input No.
Test Method(Energize only one at a time with 48V DC Voltage)
Result Display 0 to 1
Opto 1 Energize TB No. E2-E1
Opto 2 Energize TB No. E4-E3
Opto 3 Energize TB No. E6-E5
Opto 4 Energize TB No. E8-E7
Opto 5 Energize TB No. E10-E9
Opto 6 Energize TB No. E12-E11
Opto 7 Energize TB No. E14-E13
Opto 8 Energize TB No. E16-E15
Opto 9 Energize TB No. C2-C1
Opto 10 Energize TB No. C4-C3
Opto 11 Energize TB No. C6-C5
Opto 12 Energize TB No. C8-C7
Opto 13 Energize TB No. C10-C9
Opto 14 Energize TB No. C12-C11
Opto 15 Energize TB No. C14-C13
Opto 16 Energize TB No. C16-C15
Opto 17 Energize TB No. G2-G1
Opto 18 Energize TB No. G4-G3
Opto 19 Energize TB No. G6-G5
Opto 20 Energize TB No. G8-G7
Opto 21 Energize TB No. G10-G9
Opto 22 Energize TB No. G12-G11
Opto 23 Energize TB No. G14-G13
Opto 24 Energize TB No. G16-G15
OUTPUT RELAYS CHECKS: (WITH RELAY ENERGISED)
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign
JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 3
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
Enter Commissioning Test, Test Mode, Contacts Blocked, Test pattern, and select relay no. make 1T1, Go to contact test; apply test, after checking remove
test.
Output Relay No.
Test Method(Energize only one relay at a time in 'Contract test' by' Apply test)
Result Contact Checked
RL1 Contact Operated L1-L2
RL2 Contact Operated L3-L4
RL3 Contact Operated L5-L6
RL4 Contact Operated L7-L8
RL5 Contact Operated L9-L10
RL6 Contact Operated L11-L12
RL7 Contact Operated L13-L14-15
RL8 Contact Operated L16-L17-18
RL9 Contact Operated K1-K2
RL10 Contact Operated K3-K4
RL11 Contact Operated K5-K6
RL12 Contact Operated K7-K8
RL13 Contact Operated K9-K10
RL14 Contact Operated K11-K12
RL15 Contact Operated K13-K14-15
RL16 Contact Operated K16-K17-18
RL17 Contact Operated J1-J2
RL18 Contact Operated J3-J4
RL19 Contact Operated J5-J6
RL20 Contact Operated J7-J8
RL21 Contact Operated J9-J10
RL22 Contact Operated J11-J12
RL23 Contact Operated J13-J14-15
RL24 Contact Operated J16-J17-18
RL25 Contact Operated H1-H2
RL26 Contact Operated H3-H4
RL27 Contact Operated H5-H6
RL28 Contact Operated H7-H8
RL29 Contact Operated H9-H10
RL30 Contact Operated H11-H12
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign
JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 4
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
RL31 Contact Operated H13-H14-15
RL32 Contact Operated H16-H17-18
ZONE REACHES CHEK
ZoneType
of Fault
Reach at 0 Degree
Reach at 90 Degree
Reach at 180Degree
Reach at 270 Degree
Calc Act Calc Act Calc Act Calc Act
Zone1
L1-N
L2-N
L3-N
Zone2
L1-N
L2-N
L3-N
Zone3
L1-N
L2-N
L3-N
6.2 ZONE TIMING TEST
Type of Fault
Zone1 Zone-2 Zone-3
Set Time Act Time Set Time Act Time Set Time Act Time
L1-N
L2-N
L3-N
L1-L2
L2-L3
L3-L1
L1-L2-L3
FAULT LOCATOR
Distance: _______ kilometer, Impedance: ________ Ω
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign
JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 5
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
Type of FaultFault impedance Value setting in test set X ( )
Calculated value of distance in Km.
Display at relaydistance in km
AN 25%
BN 50%
CN 75%
AB 100%
BC 25%
CA 50%
ABC 100%
MEASUREMENT ACCURACY CHECK
Current Inputs Check:
CT InputApplied Value
Displayed Secondary Value
% ErrorCT Ratio Applied
Displayed Primary Value
% Error
IA
IB
IC
IN
IM
Voltage Inputs Check:
VT InputApplied Value
Displayed Secondary Value
% ErrorVT Ratio Applied
Displayed Primary
% Error
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign
JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 6
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
Value
VA
VB
VC
V C/S
SETTING CHECK (DIFFERENTIAL & BIAS FEATURE CHECK):Ensure all the settings are applied.
BIAS CHARACTERISTIC TEST:
Lower Slope Check - Set the relay in Test Loop back mode
- Set relay as 1st = 0.2A, k1=30% 1s2 = 2A- Set phase & E/F CT correction Factor = 1.00
Bias Current Differential Current
Phase Magnitude Phase Expected MagnitudeActual Magnitude
Pick-up Drop-Off
A 1pu=1A B 0.25A +/-10%
B 1pu=1A C 0.25A +/-10%
C 1pu=1A A 0.25A +/-10%
Upper Slope Check :
- Set the relay in loop back mode- Set relay as 1s1 = 0.2A, k1=30%, 1s2 = 2A, k2=as in table below
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign
JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 7
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
Bias Current Differential Current
Phase Magnitude Phase Expected MagnitudeActual Magnitude
Pick-up Drop-Off
A 3pu=3A B
K2
150% 1.15A +/-20%
100% 0.9A +/-20%
B 3pu=3A C
K2
150% 1.15A +/-20%
100% 0.9A +/-20%
C 3pu=3A A
K2
150% 1.15A +/-20%
100% 0.9A +/-20%
DIFFERENTIAL PICK-UP CHECK:
Setting = 200mA
Phase
2 - TERMINAL
Pick-up (mA) Drop-Out (mA)
Injected I diff I bias Injected I diff I bias
A
B
C
Note: Idiff = k1 (1 bias) + 1s1,I bias = 1/2 (Ia + Ib) for 2-TerminalI diff & I bias are display values on the relay.
DIFFERENTIAL OPERATION & CONTACTS CHECK :
Note: Inject only one current for this test to the phase under test.
Phase Injected Current Expected Trip Time Measured Trip Time Contacts Operated
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign
JAL InternationalJAL International INSPECTION AND TEST RECORDDescription : MICOM P546 LINE MICOM P546 LINE
DIFFERENTIAL & DISTNACEDIFFERENTIAL & DISTNACEContract No. 30433118/00 Sheet no. 8
Customer SEC-ERB Customer Ref:
Site 230kV POWER SUPPLY TO HADEED -2 Panel/Feeder Ref.
A 3A < 35ms
B 3A < 35ms
C 3A < 35ms
4. TEST EQUIPMENTS:
Sverker 760 Freja 300 Fluke 187 / 189
JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.JAL International, P. O. Box 2989, Al-Khobar 31952, K.S.A.
Tested By JAL INT’L Test Witnessed & Accepted By SEC-ERB Date
Name USMAN Name
Sign Sign