McKee and Associates
Architecture and Interior Design Addendum
No. ONE Date: 4.28.20
631 South Hull Street – Montgomery, Alabama 36104 334-834-9933
Project:
HVAC ImprovementsStevenson Middle School Stevenson, Alabama for theJackson County Board of EducationScottsboro, Alabama
MCKEE PROJECT NO. 2020.110ALABAMA DEPARTMENT OF CONSTRUCTION MANAGEMENT NO. 2020222
The following changes and/or substitutions to the plans and specifications are hereby made a part of same and are incorporated in full force as part of the contract.
Bidders shall acknowledge receipt of this Addendum in writing on his Proposal Form.
A1.1 GENERAL MODIFICATIONS:
A. NONE
A1.2 SPECIFICATION MODIFICATIONS:
A. Refer to the attached letter from Zgouvas, Eiring & Associates Consulting Engineers, Inc., dated April 25, 2020, referencing modifications to Division 15 specifications, herein.
A1.3 DRAWING MODIFICATIONS:
A. See the attached Revised Drawings as follows:Sheet M4 (Revised 4.25.20)Sheet M5 (Revised 4.25.20)Sheet M6 (Revised 4.25.20)Sheet E2.2 (Revised 4.28.20)
A1.4 CLARIFICATIONS & RESPONSES:
A. NONE
END OF ADDENDUM
800 South McDonough Street– Montgomery, AL 36104-5053 (334) 263-4406 FAX (334)263-0349
ZGOUVAS, EIRING & ASSOCIATES CONSULTING ENGINEERS, INC.
April 25, 2020
HVAC ADDENDUM
1. Refer to the specifications Section 15920-1, Part 1, General. Add the following clarification:
H. HVAC controls system equipment and related auxiliaries have been purchased by the Owner under a separate contract. The Mechanical Contractor is responsible for all coordination and installation of this equipment. The equipment proposal includes all low-voltage subcontractor labor, contractor oversight, engineering, equipment, software and tools needed to execute the scope of the work. Motorized dampers, actuators and similar items are to be provided by the BAS Contractor. All requirements shall be coordinated prior to bid with the BAS Contractor. All items not included by the BAS Contractor are the responsibility of the Mechanical Contractor.
2. Refer to the specifications Section 15710-3, Part 2.01. Clarification:
VRF System equipment has been purchased by the Owner under a separate contract. The Mechanical Contractor is responsible for all coordination and installation of this equipment. The Mechanical Contractor is responsible for installation and charging of the system, refrigerant, copper pipe/tubing, couplings, fittings and elbows, tubing insulation, drain lines, & wiring. Commissioning and testing of the installation shall be as required to obtain the Manufacturer’s 10-year warranty. The Installing Contractor shall attend and is responsible for all costs of attending a 3-day Mitsubishi VRF installation and service training session in Suwanee, GA before equipment can be delivered unless a current employee of Mechanical Contractor has completed the training and installation of the system within the last 18 months. All requirements shall be coordinated prior to bid with the VRF system supplier. All items not included by the BAS Contractor are the are responsibility of the Mechanical Contractor.
3. Refer to the specifications Section 15920 add the following requirement: All wiring and cable shall be in EMT conduit except conduit is not required above lift-out (lay-in) ceilings. “Whips” are unacceptable. Minimum conduit size shall be 3/4” and shall be provided above all hard (non-lay in) ceilings. Provide independent, minimum 2” wide, aluminum or rust resistant coated steel J-hook supports for all wiring not in conduit. Wiring supports shall be attached to the building structural system (not other trades’ supports, piping,
800 South McDonough Street– Montgomery, AL 36104-5053 (334) 263-4406 FAX (334)263-0349
duct, ceiling suspension system, etc). Wiring, cabling, etc., shall be neatly bundled together and supported at no more than six (6) feet on center. Control conduit is specified in Electrical Division of the specifications and/or shown on electrical drawings. Minimum control conduit size shall be 3/4”. All control conduit, power wiring, relays, contactors, etc. for controls, which are not shown on the electrical drawings or specified in the Electrical Division of the specifications, shall be provided under this Section. Coordinate all requirements with the appropriate parties prior to bid. All thermostat and humidistat boxes shall be mounted 46” A.F.F. to the center of the box (ADA height). Where wall mounted CO2 Sensors are indicated, they shall be mounted 58” A.F.F to the center of the box. Electrical work performed under this Section shall conform to requirements set forth in the Electrical Division of the specifications.
4. Refer to the specifications Section 15920 add the following requirement:
Typical Split System Heat Pump Sequence of Operation:
UNIT ENABLE: When the network input enable switch is set to occupied, the control sequence shall be enabled. OCCUPIED MODE: The occupancy mode will be controlled via a network input. during occupied mode, the indoor and respective outdoor units will be started. The cooling and heating modes will be indexed to maintain the zone temperature setpoint. When the condensate float switch in the respective condensate drain or aux. drain pan float switch is in "alarm", the cooling control sequence will be disabled. Then the respective unit(s) shall be disabled, and an alarm shall be sent to the BAS operator console. UNOCCUPIED MODE: The unit will cycle on to maintain unoccupied zone setpoints during unoccupied periods. When the condensate float switch is in "alarm", the cooling control sequence will be disabled in the summer mode and an alarm shall be sent to the BAS operator console. Then the unit(s) will be disabled.
SEQUENCE OF OPERATION: Thermostat shall be used to control heating and cooling. Upon a call for the occupied schedule, the outside air damper shall open to its minimum scheduled outside air setpoint and the unit shall start. Upon unit shutdown, the motorized outside air damper shall close. Upon a call for the unoccupied schedule, the outside air damper shall remain closed and the unit shall start. Provide smoke detectors where shown on the plans. Wire the detectors to stop the unit upon smoke detection. Provide required interlocks, wiring, relays, etc., to stop the unit upon detection of smoke by the smoke detectors. AC-39 Additional Requirements: Demand Ventilation: Units shall be provided with factory furnished and installed demand ventilation controls via wall mounted carbon dioxide (CO2) sensor. Factory mounted controls shall modulate the motorized outside air damper to maintain a maximum of 800 PPM (adj.) CO2
concentration in the space as applicable. Upon a rise in CO2 concentration set point, the motorized outside air damper shall modulate open to its scheduled outside air requirement.
800 South McDonough Street– Montgomery, AL 36104-5053 (334) 263-4406 FAX (334)263-0349
Upon satisfaction of the CO2 set point, the motorized damper shall return to the required position to provide a continuous minimum outside air stream as scheduled. Upon unit shutdown or during unoccupied setting, the outside air damper shall close. EDH AC-39 Duct Heater: Provide discharge air temperature sensor in the supply air duct and arrange as required to provide minimum discharge air temperature during winter operation of 95 degrees F.
END OF HVAC ADDENDUM
E24x10
E18x12
E24x10
E12x10 O.A.
E24x18 O.A. LVR.
E24x10
E12x10 O.A.
AC-19
E24x18 O.A. LVR.
E14x14 O.A.
E24x10
E12x10 O.A.
E18x16 O.A. LVR.
E30x24 O.A. LVR.
E15x12 O.A.
E15x12 O.A.
E20x20
E24x14 S.A.
E20x12
E36x24 WALL R.A.
REG. ABOVE BASE
E13x10
E12x12
E60x21 S.A.
E60x24 R.A.
E12x10
E14x12
E12x12
E14x12
E12x12 S.A.
E14x12 R.A.
E12x12
E28x16
E24x10
E12x10 O.A.
E24x18 O.A. LVR.
E14x14 O.A.
E24x10
E15x10 O.A.
E24x16 O.A. LVR.
E14x8
E12x10
E24x10
E12x10 O.A.
E12x10 O.A.
E32x12
E12x10 O.A.
E12x10 O.A.
E24x10
CU-31
CU-29
EXISTING CONDENSING
UNITS TO REMAIN IN
SERVICE
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
AC-20
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN T
AC-21
AC-41
T
AC-21
E8x12
EXISTING R.A.
GRILLES TO
REMAIN
E12x12 DN.
E10x10
E9"Ø
E10x10
E9"Ø
EXISTING EXHAUST FANS
TO REMAIN IN SERVICE
AC-16
T
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXIST
EXHAUST
TO REMAIN
(1,400
CFM)
T
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
AC-35
EXISTING 36x36 R.A.
REG. ABOVE BASE
TO REMAIN
E14x14 O.A. DN.
FROM INTAKE ON
ROOF
EXISTING DIFFUSERS
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
E16x12
AC-3
E24x10
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
AC-37
AC-26
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x14 O.A. DN.
FROM INTAKE ON
ROOF
E24x10
E14x10
EXISTING DIFFUSERS
TO REMAIN
T
T
EXISTING 40x32 R.A.
REG. ABOVE BASE
TO REMAIN
E23x16 E28x16 E20x16 E16x16 E12x10
EXISTING DIFFUSERS
TO REMAIN
T
E8x12
EXISTING R.A.
GRILLE
E12x12 DN.
T
AC-23
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
AC-27
E14x14
EXISTING DIFFUSERS
TO REMAIN
T
E14x12
EXISTING
RELIEF AIR
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN IN SERVICE
EXISTING
RELIEF AIR
TO REMAIN IN SERVICE
AC-22
AC-40
AC-42
AC-43
AC-39
E12x12
E12x12
E8"Ø
E60x21 S.A.
E48x21 S.A.
E34x21 S.A.
E21x21 S.A.
EXISTING DIFFUSERS
TO REMAIN
EXISTING DIFFUSERS
TO REMAIN
EXISTING 60x24
WALL R.A. REG.
ABOVE DOORS
EXISTING 60x24
WALL R.A. REG.
ABOVE DOORS
E12x10
EXISTING EXH.
FAN TO REMAIN IN SERVICE
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
AC-30
EXISTING
RELIEF AIR
T
T
AC-34
EXISTING EXH. FAN
TYPE TO REMAIN IN
SERVICE
E18x18 O.A. LVR.
AC-31
AC-8
E18x12
E12x12
E12x12
EXISTING R.A.
GRILLES
T
AC-8
AC-9
AC-6
E14x10
E14x10
E10"Ø
E10"Ø
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
EXISTING DIFFUSERS
TO REMAIN
T
EXISTING R.A.
GRILLES
EXISTING EXH.
FAN TO REMAIN
IN SERVICE
DN. FROM
ATTIC
VRF-3A
VRF-3B
VRF-4A
VRF-5A
VRF-5B
VRF-2A
BC-1 BC-2
(208V/1PH.)
(208V/1PH)
BC-5
(208V/1PH.)
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4"
1-1/4"
1-1/4"
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4"
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4"
(208V/1PH.) (208V/1PH.)
BC-3
BC-4
(208V/1PH)
BC-6
EXISTING CONC.
PAD TO REMAIN
AC-5
AC-2
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
AC-32
AC-10
CU-38
AC-38
AC-29
CU-36
EXISTING CONDENSING
UNITS TO REMAIN IN
SERVICE
CU-17
VRF-2B
CU-10
EXISTING CONC.
PAD TO REMAIN
CONN. NEW 14x10
TO EXIST. 14x10
CONN. NEW 10"Ø TO
EXISTING 10"Ø
AC-7A
AC-7B
NEW 14x12
NEW 18x10
NEW 8"Ø RUNOUT-
CONN. TO EXISTING
DIFFUSER
NEW 10"Ø RUNOUT-
CONN. TO EXISTING
10"Ø RUNOUT
NEW 16x12
CONN. NEW 14x10
S.A. TO EXISTING
14x10
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
E12x10
E14x14 DN. FROM
INTAKE ON ROOF
E12x10
E14x10
E24x10
E16x14
E24x18 O.A. LVR.
E12x10 O.A.
EXISTING DIFFUSERS
TO REMAIN
T
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
T
EXISTING DIFFUSERS
TO REMAIN
E16x16 DN. FROM
INTAKE ON ROOF
E24x10
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
T
6x6 O.A.
24x24 CLG.
R.A. REG.
24x24 CLG.
R.A. REG.
NEW 18x10
6x6 O.A.
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
AC-17
AC-36
1-1/4" COND. DRAIN LINE
ABOVE CLG. TERMINATE
AT MECH. FL. DRAIN
1-1/4" COND. DRAIN LINE
ABOVE CLG. TERMINATE
AT MECH. FL. DRAIN
CO
CO
1"1"
1-1/4" COND.
DRAIN LINE
20x20
325
CFM
325
CFM
325
CFM
325
CFM
400
CFM
400
CFM
240
CFM
240
CFM
240
CFM
325
CFM
325
CFM
325
CFM
325
CFM
150
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
325
CFM
325
CFM
325
CFM
325
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
325
CFM
325
CFM
325
CFM
325
CFM
297
CFM
220
CFM
220
CFM
220
CFM
220
CFM
170
CFM
170
CFM
170
CFM
170
CFM
200
CFM
325
CFM
325
CFM
325
CFM
325
CFM
300
CFM
300
CFM
100
CFM
235
CFM
300
CFM
250
CFM
365
CFM
365
CFM
350
CFM
350
CFM
350
CFM
350
CFM
445
CFM
445
CFM
219
CFM
219
CFM
219
CFM
219
CFM
219
CFM
200
CFM
200
CFM
300
CFM
300
CFM
400
CFM
240
CFM
240
CFM
240
CFM
545
CFM
545
CFM
325
CFM
325
CFM
325
CFM
325
CFM
550
CFM
550
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
297
CFM
297
CFM
297
CFM
297
CFM
AC-CC-1
AC-1W-1
T
T
T
VRF-1A
VRF-1B
CO
CO
1-1/4"
1-1/4"
CO
AC-43
VRF-4B
CO
CO
CO
1-1/4" COND.
DRAIN LINE
VRF-6A
VRF-6B
CO
VRF-7A VRF-7B VRF-7C
AC-39
AC-37
AC-26
MITSUBISHI AE-200 CENTRAL CONTROL
PANEL AND RELATED SUB-PANEL-
FINAL LOCATION TO BE COORDINATED
WITH OWNER IN THE FIELD
(120V/1PH EA. PANEL)
T
T
T
T
AC-10
T
T
AC-34
T
T
T
AC-38
AC-29
AC-31
NEW 10x12
NEW 6x12
AC-9
T
T
CH
WHERE EXISTING CONCRETE PAD IS NOT
OF ADEQUATE SIZE FOR NEW EQUIPMENT,
DEMOLISH EXISTING CONC. PAD AND
PROVIDE NEW AS REQUIRED FOR NEW
EQUIPMENT. SEE SPECS FOR CONCRETE
REQUIREMENTS
T
AC-7A
T
AC-7A
REFRIGERANT PIPING - RISE
EXPOSED TO POINT ABOVE
CEILING-EXTEND AND CONN.
TO RESPECTIVE BRANCH
CONTROLLER (BC) - PROVIDE
GALV. SHEETMETAL COVER
OVER EXPOSED PIPING AND
PAINT TO MATCH BUILDING- (TYP)
REFRIGERANT PIPING - RISE
EXPOSED TO POINT ABOVE
CEILING-EXTEND AND CONN.
TO RESPECTIVE BRANCH
CONTROLLER (BC) - PROVIDE
GALV. SHEETMETAL COVER
OVER EXPOSED PIPING AND
PAINT TO MATCH BUILDING- (TYP)
REFRIGERANT PIPING - RISE
EXPOSED TO POINT ABOVE
CEILING-EXTEND AND CONN.
TO RESPECTIVE BRANCH
CONTROLLER (BC) - PROVIDE
GALV. SHEETMETAL COVER
OVER EXPOSED PIPING AND
PAINT TO MATCH BUILDING- (TYP)
AC-CC-2
1156
CFM
1156
CFM
1156
CFM
1156
CFM
1156
CFM
1156
CFM
1156
CFM
1156
CFM
5"Ø
4"Ø
16-1/2" x 7-3/4" BRICK VENT
W/ FULL SIZE PLENUM
INJECTOR FAN WITH FILTER
FRAME AND 1" WASHABLE
FILTER - FANS SHALL BE
SOLERPALAU SERIES
TD-SILENT,125XS, 80 CFM,
.3" EXT. S.P., 50W,
120V/1PH.60HZ, OR
APPROVED EQUIVALENT-
INTERLOCK TO OPERATE
ANYTIME CASSETTE UNIT
OPERATES
5"Ø
4"Ø
INJECTOR FAN WITH FILTER
FRAME AND 1" WASHABLE
FILTER - FANS SHALL BE
SOLERPALAU SERIES
TD-SILENT,125XS, 40 CFM,
.3" EXT. S.P., 50W,
120V/1PH.60HZ, OR
APPROVED EQUIVALENT-
INTERLOCK TO OPERATE
ANYTIME CASSETTE UNIT
OPERATES
SMOKE DETECTOR
MOTORIZED DAMPER (MD)
MANUAL VOLUME DAMPER (MVD)
LEGEND
CEILING DIFFUSER
RETURN AIR GRILLE/REGISTER
EXHAUST AIR GRILLE/REGISTER
CEILING DIFFUSER DESIGNATOR
RETURN AIR GRILLE/REGISTER
EXHAUST AIR GRILLE/REGISTER
4
4
4
DENOTES LOCATION OF VERTICAL
ACTION FIRE DAMPER
DENOTES LOCATION OF HORIZONTAL
ACTION FIRE DAMPER
BAROMETRIC DAMPER
B
DUCT W/ RECTANGULAR SIZE12x12
E12x12
THERMOSTATT
H HUMIDISTAT
CO CLEANOUT
ABOVE FINISH FLOORA.F.F.
FIRE DAMPERF.D.
GENERAL CONTRACTORG.C.
OUTSIDE AIRO.A.
S.A. SUPPLY AIR
R.A.R. RETURN AIR REGISTER
R.A.G. RETURN AIR GRILLE
R.A. RETURN AIR
CONNECT OR CONNECTIONCONN.
CONNECT TO EXISTING
C CO2 SENSOR
RECTANGULAR SUPPLY AIR DUCT TURNING DOWN
RECTANGULAR RETURN AIR OR EXHAUST
RECTANGULAR SUPPLY DUCT TURNING UP
RECTANGULAR RETURN AIR OR EXHAUST
DUCT TURNING UP
DUCT TURNING DOWN
EXISTING DUCT W/ RECTANGULAR SIZE
EDH ELECTRIC DUCT HEATER
18x10
18x10
18x10
16x16 CLG.
R.A. GRILLE
SET MVD TO
650 CFM
2020-110
03.31.2020
SHEET TITLE :
MCKEE JOB # :
CHECKED BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a n
d
I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
3
61
04
(3
34
) 8
34
-9
93
3
- M
onday, A
pril 27, 2020 7:32:35 A
M
- Z
:\M
ckee\20-37 S
tevenson M
iddle S
chool H
VA
C\20-37 M
ech P
lans B
.dw
g
T. ZGOUVAS
REVISED DATE:
REVISED DATE:
REVISED DATE:
HV
AC
IM
PR
OV
EM
EN
TS
TO
ST
EV
EN
SO
N M
ID
DLE
S
CH
OO
L
FO
R T
HE
JA
CK
SO
N C
OU
NT
Y B
OE
ST
EV
EN
SO
N, A
LA
BA
MA
DRAWN BY :C. WARD
MONTGOMERY, AL. 36104800 S McDONOUGH STREET
334.263.4406
ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS
THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 20-37
4-25-2020
4-25-2020
M4
OVERALL HVAC PLAN
SCALE: 3/32" = 1'-0"
N
E
S
W
KEY PLAN
NOT TO SCALE
N
E
S
W
"A"
OVERALL HVAC
PLAN
"B"
E24x10
E12x10 O.A.
E24x18 O.A. LVR.
E24x10
E12x10 O.A.
AC-19
E24x18 O.A. LVR.
E14x14 O.A.
E24x10
E12x10 O.A.
E18x16 O.A. LVR.
E30x24 O.A. LVR.
E15x12 O.A.
E15x12 O.A.
E20x12
E36x24 WALL R.A.
REG. ABOVE BASE
E13x10
E12x12
E60x21 S.A.
E60x24 R.A.
E12x10
E14x12
E12x12
E14x12
E12x12 S.A.
E14x12 R.A.
E12x12
E28x16
E24x10
E12x10 O.A.
E24x18 O.A. LVR.
E14x14 O.A.
E24x10
E12x10 O.A.
E12x10 O.A.
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
AC-20
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
T
AC-21
AC-41
T
AC-21
E8x12
EXISTING R.A.
GRILLES TO
REMAIN
E12x12 DN.
E10x10
E9"Ø
E10x10
E9"Ø
EXISTING EXHAUST FANS
TO REMAIN IN SERVICE
AC-16
T
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXIST
EXHAUST
TO REMAIN
(1,400
CFM)
T
E14x10
E24x10
E14x10
EXISTING DIFFUSERS
TO REMAIN
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
AC-37
AC-26
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x14 O.A. DN.
FROM INTAKE ON
ROOF
E24x10
E14x10
EXISTING DIFFUSERS
TO REMAIN
T
T
EXISTING 40x32 R.A.
REG. ABOVE BASE
TO REMAIN
E23x16 E28x16 E20x16 E16x16 E12x10
EXISTING DIFFUSERS
TO REMAIN
T
E8x12
EXISTING R.A.
GRILLE
E12x12 DN.
T
AC-23
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
AC-27
E14x14
EXISTING DIFFUSERS
TO REMAIN
T
E14x12
EXISTING
RELIEF AIR
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN IN SERVICE
EXISTING
RELIEF AIR
TO REMAIN IN SERVICE
AC-22
AC-40
AC-42
AC-43
AC-39
E12x12
E12x12
E8"Ø
E60x21 S.A.
E48x21 S.A.
E34x21 S.A.
EXISTING DIFFUSERS
TO REMAIN
EXISTING 60x24
WALL R.A. REG.
ABOVE DOORS
EXISTING 60x24
WALL R.A. REG.
ABOVE DOORS
E12x10
EXISTING EXH.
FAN TO REMAIN IN SERVICE
T
DN. FROM
ATTIC
VRF-3A
VRF-3B
VRF-2A
BC-1 BC-2
(208V/1PH.)
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4"
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4"
(208V/1PH.) (208V/1PH.)
BC-3
CU-36
EXISTING CONDENSING
UNITS TO REMAIN IN
SERVICE
CU-17
VRF-2B
EXISTING CONC.
PAD TO REMAIN
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
EXISTING
RELIEF AIR
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
AC-17
AC-36
325
CFM
325
CFM
325
CFM
325
CFM
400
CFM
400
CFM
240
CFM
240
CFM
240
CFM
325
CFM
325
CFM
325
CFM
325
CFM
150
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
220
CFM
325
CFM
325
CFM
325
CFM
325
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
350
CFM
325
CFM
325
CFM
325
325
219
CFM
219
CFM
219
CFM
219
CFM
219
CFM
200
CFM
200
CFM
300
CFM
300
CFM
400
CFM
240
CFM
240
CFM
240
CFM
545
CFM
545
CFM
325
CFM
325
CFM
325
CFM
325
CFM
T
T
T
VRF-1A
VRF-1B
CO
CO
1-1/4"
1-1/4"
CO
AC-43
VRF-7A VRF-7B VRF-7C
AC-39
AC-37
AC-26
CH
WHERE EXISTING CONCRETE PAD IS NOT
OF ADEQUATE SIZE FOR NEW EQUIPMENT,
DEMOLISH EXISTING CONC. PAD AND
PROVIDE NEW AS REQUIRED FOR NEW
EQUIPMENT. SEE SPECS FOR CONCRETE
REQUIREMENTS
REFRIGERANT PIPING - RISE
EXPOSED TO POINT ABOVE
CEILING-EXTEND AND CONN.
TO RESPECTIVE BRANCH
CONTROLLER (BC) - PROVIDE
GALV. SHEETMETAL COVER
OVER EXPOSED PIPING AND
PAINT TO MATCH BUILDING- (TYP)
REFRIGERANT PIPING - RISE
EXPOSED TO POINT ABOVE
CEILING-EXTEND AND CONN.
TO RESPECTIVE BRANCH
CONTROLLER (BC) - PROVIDE
GALV. SHEETMETAL COVER
OVER EXPOSED PIPING AND
PAINT TO MATCH BUILDING- (TYP)
1156
CFM
1156
CFM
1156
CFM
1156
CFM
LEGEND
12x12
E12x12
18x10
18x10
18x10
16x16 CLG.
R.A. GRILLE
SET MVD TO
650 CFM
2020-110
03.31.2020
SHEET TITLE :
MCKEE JOB # :
CHECKED BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a
n
d
I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
3
61
04
(3
34
) 8
34
-9
93
3
- M
onday, A
pril 27, 2020 7:33:07 A
M
- Z
:\M
ckee\20-37 S
tevenson M
iddle S
chool H
VA
C\20-37 M
ech P
lans B
.dw
g
T. ZGOUVAS
REVISED DATE:
REVISED DATE:
REVISED DATE:
HV
AC
IM
PR
OV
EM
EN
TS
TO
ST
EV
EN
SO
N M
ID
DLE
S
CH
OO
L
FO
R T
HE
JA
CK
SO
N C
OU
NT
Y B
OE
ST
EV
EN
SO
N, A
LA
BA
MA
DRAWN BY :C. WARD
MONTGOMERY, AL. 36104800 S McDONOUGH STREET
334.263.4406
ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS
THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 20-37
4-25-2020
4-25-2020
M5
HVAC PLAN - PART "A"
SCALE: 1/8" = 1'-0"
N
E
S
W
KEY PLAN
NOT TO SCALE
N
E
S
W
"A"
"B"
HVAC PLAN
PART "A"
E24x10
E18x12
E20x20
E24x14 S.A.
E24x10
E15x10 O.A.
E24x16 O.A. LVR.
E14x8
E12x10
E32x12
E12x10 O.A.
E12x10 O.A.
E24x10
CU-31
CU-29
EXISTING CONDENSING
UNITS TO REMAIN IN
SERVICE
E9"Ø
E9"Ø
T
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
AC-35
EXISTING 36x36 R.A.
REG. ABOVE BASE
TO REMAIN
E14x14 O.A. DN.
FROM INTAKE ON
ROOF
EXISTING DIFFUSERS
TO REMAIN
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
E16x12
AC-3
EXISTING DIFFUSERS
TO REMAIN
RELIEF AIR
TO REMAIN IN SERVICE
EXISTING
RELIEF AIR
TO REMAIN IN SERVICE
E48x21 S.A.
E34x21 S.A.
E21x21 S.A.
EXISTING DIFFUSERS
TO REMAIN
EXISTING DIFFUSERS
TO REMAIN
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
AC-30
EXISTING
RELIEF AIR
T
AC-34
EXISTING EXH. FAN
TYPE TO REMAIN IN
SERVICE
E18x18 O.A. LVR.
AC-31
AC-8
E18x12
E12x12
E12x12
EXISTING R.A.
GRILLES
T
AC-8
AC-9
AC-6
E14x10
E14x10
E10"Ø
E10"Ø
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
EXISTING DIFFUSERS
TO REMAIN
T
EXISTING R.A.
GRILLES
EXISTING EXH.
FAN TO REMAIN
IN SERVICE
VRF-4A
VRF-5A
VRF-5B
(208V/1PH)
BC-5
(208V/1PH.)
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
1-1/4"
1-1/4"
1-1/4"
1-1/4" COND. DRAIN LINE
DN. IN MECH. ROOM
AND TERMINATE AT
FL. DRAIN
BC-4
(208V/1PH)
BC-6
EXISTING CONC.
PAD TO REMAIN
AC-5
AC-2
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
AC-32
AC-10
CU-38
AC-38
AC-29
CU-10
CONN. NEW 14x10
TO EXIST. 14x10
CONN. NEW 10"Ø TO
EXISTING 10"Ø
AC-7A
AC-7B
NEW 14x12
NEW 18x10
NEW 8"Ø RUNOUT-
CONN. TO EXISTING
DIFFUSER
NEW 10"Ø RUNOUT-
CONN. TO EXISTING
10"Ø RUNOUT
NEW 16x12
CONN. NEW 14x10
S.A. TO EXISTING
14x10
EXISTING HEATING
AND A/C SYSTEMS TO
REMAIN IN SERVICE -
PROVIDE NEW
CONTROLLER & TSTAT
FOR EXISTING UNITS
E12x10
E14x14 DN. FROM
INTAKE ON ROOF
E12x10
E14x10
E24x10
E16x14
E24x18 O.A. LVR.
E12x10 O.A.
EXISTING DIFFUSERS
TO REMAIN
T
EXISTING
RELIEF AIR
TO REMAIN
IN SERVICE
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
T
EXISTING DIFFUSERS
TO REMAIN
E16x16 DN. FROM
INTAKE ON ROOF
E24x10
EXISTING 24x24 R.A.
REG. ABOVE BASE
TO REMAIN
E14x10
T
6x6 O.A.
24x24 CLG.
R.A. REG.
24x24 CLG.
R.A. REG.
NEW 18x10
6x6 O.A.
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-7
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
FOR WORK IN THIS AREA
SEE LARGE SCALE MECH.
ROOM ON SHEET M-8
1-1/4" COND. DRAIN LINE
ABOVE CLG. TERMINATE
AT MECH. FL. DRAIN
1-1/4" COND. DRAIN LINE
ABOVE CLG. TERMINATE
AT MECH. FL. DRAIN
CO
CO
1"1"
1-1/4" COND.
DRAIN LINE
20x20
240
CFM
350
CFM
350
CFM
325
CFM
325
CFM
325
CFM
325
CFM
297
CFM
220
CFM
220
CFM
220
CFM
220
CFM
170
CFM
170
CFM
170
CFM
170
CFM
200
CFM
325
CFM
325
CFM
325
CFM
325
CFM
300
CFM
300
CFM
100
CFM
235
CFM
300
CFM
250
CFM
365
CFM
365
CFM
350
CFM
350
CFM
350
CFM
350
CFM
445
CFM
445
CFM
240
CFM
550
CFM
550
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
325
CFM
297
CFM
297
CFM
297
CFM
297
CFM
AC-CC-1
AC-1W-1
VRF-4B
CO
CO
CO
1-1/4" COND.
DRAIN LINE
VRF-6A
VRF-6B
CO
MITSUBISHI AE-200 CENTRAL CONTROL
PANEL AND RELATED SUB-PANEL-
FINAL LOCATION TO BE COORDINATED
WITH OWNER IN THE FIELD
(120V/1PH EA. PANEL)
T
T
T
T
AC-10
T
T
AC-34
T
T
T
AC-38
AC-29
AC-31
NEW 10x12
NEW 6x12
AC-9
T
T
T
AC-7A
T
AC-7A
REFRIGERANT PIPING - RISE
EXPOSED TO POINT ABOVE
CEILING-EXTEND AND CONN.
TO RESPECTIVE BRANCH
CONTROLLER (BC) - PROVIDE
GALV. SHEETMETAL COVER
OVER EXPOSED PIPING AND
PAINT TO MATCH BUILDING- (TYP)
AC-CC-2
1156
CFM
1156
CFM
1156
CFM
1156
CFM
1156
CFM
1156
CFM
5"Ø
4"Ø
16-1/2" x 7-3/4" BRICK VENT
W/ FULL SIZE PLENUM
INJECTOR FAN WITH FILTER
FRAME AND 1" WASHABLE
FILTER - FANS SHALL BE
SOLERPALAU SERIES
TD-SILENT,125XS, 80 CFM,
.3" EXT. S.P., 50W,
120V/1PH.60HZ, OR
APPROVED EQUIVALENT-
INTERLOCK TO OPERATE
ANYTIME CASSETTE UNIT
OPERATES
5"Ø
4"Ø
INJECTOR FAN WITH FILTER
FRAME AND 1" WASHABLE
FILTER - FANS SHALL BE
SOLERPALAU SERIES
TD-SILENT,125XS, 40 CFM,
.3" EXT. S.P., 50W,
120V/1PH.60HZ, OR
APPROVED EQUIVALENT-
INTERLOCK TO OPERATE
ANYTIME CASSETTE UNIT
OPERATES
2020-110
03.31.2020
SHEET TITLE :
MCKEE JOB # :
CHECKED BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a n
d
I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
3
61
04
(3
34
) 8
34
-9
93
3
- M
onday, A
pril 27, 2020 7:33:28 A
M
- Z
:\M
ckee\20-37 S
tevenson M
iddle S
chool H
VA
C\20-37 M
ech P
lans B
.dw
g
T. ZGOUVAS
REVISED DATE:
REVISED DATE:
REVISED DATE:
HV
AC
IM
PR
OV
EM
EN
TS
TO
ST
EV
EN
SO
N M
ID
DLE
S
CH
OO
L
FO
R T
HE
JA
CK
SO
N C
OU
NT
Y B
OE
ST
EV
EN
SO
N, A
LA
BA
MA
DRAWN BY :C. WARD
MONTGOMERY, AL. 36104800 S McDONOUGH STREET
334.263.4406
ZGOUVAS, EIRING & ASSOCIATESCONSULTING ENGINEERS
THE INFORMATION CONTAINED IN THIS DRAWING IS COPYRIGHTED MATERIAL AND SHALL NOT BE REPRODUCED, DIGITIZED, OR REVISED, IN WHOLE OR IN PART, WITHOUT THE WRITTEN CONSENT OF ZGOUVAS, EIRING AND ASSOCIATESZEA PROJECT NUMBER 20-37
4-25-2020
4-25-2020
M6
HVAC PLAN - PART "B"
SCALE: 1/8" = 1'-0"
N
E
S
W
KEY PLAN
NOT TO SCALE
N
E
S
W
"A"
"B"
HVAC PLAN
PART "B"
8'
1/8" = 1'-0
0 8 16 FT
GRAPHIC SCALE
FLOOR PLAN - PART "B" -
ELECTRICAL
E2.2
2020-110
02.04.2020
SHEET TITLE :
MCKEE JOB # :
CHECKED BY :
DATE:
SHEET NO. :
M c K
E
E
a
n
d
A
S
S
O
C
I A
T
E
S
A R
C
H
I T
E
C
T
U
R
E
a n d I N
T
E
R
I O
R
D
E
S
I G
N
63
1 S
OU
TH
H
UL
L S
TR
EE
T M
ON
TG
OM
ER
Y , A
LA
BA
MA
36
10
4 (33
4) 8
34
-99
33
- T
ue
sd
ay, A
pril 2
8, 2
02
0 8
:1
8:1
7 A
M
- N
:\2
02
0\2
0-0
43
S
TE
NS
ON
M
S H
VA
C\D
ra
win
gs\e
le
c\E
2.2
.d
wg
K.R.G.
REVISED DATE:
REVISED DATE:
REVISED DATE:
HV
AC
IM
PR
OV
EM
EN
TS
TO
ST
EV
EN
SO
N M
ID
DLE
S
CH
OO
L
FO
R T
HE
JA
CK
SO
N C
OU
NT
Y B
OE
ST
EV
EN
SO
N, A
LA
BA
MA
DRAWN BY :J. TILLERY
3102 Highway 14
Gunn & Associates, P.C.Consulting Engineers
Millbrook, AL 360541200 Providence Park, Suite 200
Birmingham, AL 35242GA#20-043Tel: 334.285.1273
04-28-2020
PART "A"
PART "B"
NO SCALEKEY PLAN
SCALE: 1/8"=1'-0" FLOOR PLAN PART "B" - ELECTRICAL1
E2.1
PART "A"PART "B"
PART "A"PART "B"
SHEET NOTES: GENERAL NOTES:
04-28-2020