Arc Blast Flash

89
ARC FLASH / BLAST SAFETY

Transcript of Arc Blast Flash

Page 1: Arc Blast Flash

ARC FLASH / BLAST

SAFETY

Page 2: Arc Blast Flash

What is the best way to prevent thehazards of electricity?

Stop - Before ActionThink - Risks/HazardsOptions - LOTO-Tagout-

TryoutProtection - Proper PPE

Avoiding energizedcircuits is the Safest

Way!

Page 3: Arc Blast Flash

ELECTRICAL SAFETY

Why Electrical Safety Practicesand Procedures?

1. An estimated 30,000 non-fatal electrical shock accidents occur each year.

2. Over 600 people die from electrocution each year.

3. Electrocution remains the fourth (4th)highest cause of industrial fatalities.

4. Approximately 3000 reported flash burn incidents reported annually along with approximately 350 deaths.

Page 4: Arc Blast Flash

ELECTRICAL SAFETY

NFPA 70E – Standard for Electrical Safety in the Workplace

• Formally “Standard for Electrical Safety Requirements for Employee Workplaces”

• Begin 1976 by NFPA to assist

OSHA

Page 5: Arc Blast Flash

ELECTRICAL HAZARDS

• Shock

• Arc Flash & Arc Blast

• Fire Ignition

Page 6: Arc Blast Flash

Some arc flash injury statistics:Five to ten arc flash explosions occur in electrical equipment every day in the United States, according to statistics compiled by Cap-Schell, Inc., a Chicago-based research and consulting firm that specializes in preventing workplace injuries and deaths.

Injuries from arc flash events range from minor injuries to third degree burns and potential death due to the energy released.

Other injuries include blindness, hearing loss, nerve damage, and cardiac arrest.

The average cost of medical treatment for survivors of arc flash incidents is $ 1,500,000

Total costs including litigation can be $8M - $10M

Page 7: Arc Blast Flash

The Effects of Shock - Immediate

• Immediate– Muscle contraction– Vital organs (heart, lungs, etc)– Tingling– Pain– Breathing– Disorientation– Dizziness

Page 8: Arc Blast Flash

The Effects of Shock – Long Term

• Long Term– Memory Loss– Nervous Disorders– Chemical Imbalances– Damage to Vital Organs– Sometimes Fatal

Page 9: Arc Blast Flash

Injury Facts

Numerous workers are injured or killed each year while working on energized equipment.

Defining incident energy hazards raises awareness of the harm to humans that can result from an electric arc.

Injuries often include:• Severe skin burns• Hearing damage• Face and eye injuries• Blast pressure injuries

Page 10: Arc Blast Flash

Effects of AC Current

More than 3mA - Painful shocks which can cause indirect accidents

More than 10mA - Muscle contraction, “not able to let go”

More than 30mA - Lung paralysis, usually temporary

Page 11: Arc Blast Flash

Effects of AC Current

More than 50mA - Possible ventricular fibrillation

100mA to 4amp - Certain fatal ventricular

fibrillation

Over 4 amps - Severe burns, heart paralysis

Page 12: Arc Blast Flash

Resistance and the Body

The body has a natural defense system (Skin)

Why 50 volts? How can you raise

body resistance? The key to survival

is decrease our exposure.

Ohm’s Law for Electric current (amps), voltage and Body ResistanceThe typical body has a contact resistance of 500 ohms at the point of contact with the electrical source.The body has an internal resistance of approximately 100 ohms.There is another point of contact to ground of maybe 5000 ohms.

–120v / (500: + 100: + 5000:) = 21mA

–50v / (500: + 100: + 5000:) = 8.9 mA

It is around 10 mA that the “cannot let go” level is reached. Once lock up occurs, exposure time is increased and the possibility of electrocution may occur.

Page 13: Arc Blast Flash
Page 14: Arc Blast Flash

Two types of burns from Shock

Surface Burns• Caused by entrance and exit of

electrical currents through the body

• Can be caused by a very small amount of current

• 1st degree to 3rd degree

Page 15: Arc Blast Flash

Two types of burns from Shock

Internal Tissue Burns• Caused by current flowing through organs

of the body• Caused by currents in excess of 1.5 amps• 3rd degree• Internal organs• Typically fatal

Page 16: Arc Blast Flash
Page 17: Arc Blast Flash

One Type of Burn from Arc Flash

Surface Burns• Caused by exposure to the arc flash • Can cause more surface burns if the initial

arc flash ignites other material such as clothing

• 1st degree to 3rd degree• It has and may cause death!!!!!!

Page 18: Arc Blast Flash

ELECTRICAL SAFETY

How to prevent Shock?

1. Place Circuits in an Electrically Safe Working Conditions by Locking out and tagging out all sources

Chapter 1, Section 120.2(D) of NFPA 70E- 2004

2. Verifying that no electrical energy is present

Chapter 1, Section 120.2(D) of NFPA 70E- 2004

Page 19: Arc Blast Flash

AF Incident

480 Volt System 22,6000 Amp

Symmetrical Fault Motor Controller

Enclosure 6-Cycle Arcing Fault (0.1

sec)

Page 20: Arc Blast Flash

Exposure to Danger• The National Electric Code protects individuals

from shock hazards under normal conditions.

• It is not designed to protect us from abnormal conditions.

• We need additional policies to protect from abnormal conditions.

Page 21: Arc Blast Flash

Conditions

• Normal Conditions– Panel Covers In Place.– Equipment plugged in normally.– Normal, designed protection in place.

Page 22: Arc Blast Flash

Conditions

• Abnormal Conditions– Panel covers removed.– Equipment temporarily wired.– Normal designed

• protection such as guards, limits switches, etc., not in place.

Page 23: Arc Blast Flash

Protection from Abnormal Conditions

• The Company– NFPA 70 E– OSHA– Electrical Safety– Procedures Manual– Electrical Safety– Training

Page 24: Arc Blast Flash

Protection from Abnormal Conditions

• You– The first line of defense– Only you can truly keep you safe– Implement Safety Procedures Outlined in

Safety Manual– Only you can ensure that you go home at

night

Page 25: Arc Blast Flash

Old School

• Electricians have always recognized the shock hazards of electricity. They are taught:

• To consider circuits to be energized• To insulate and protect our selves• Stand to one side if you suspect an arc flash/blast

Page 26: Arc Blast Flash

New School

• Arc Flash and Blast hazards were not formally studied until 1993 (IEEE 1584 began study)

• Electricians have not experienced arc flash and blasts to the same frequency as electrical shock.

• We have not been trained how to avoid and minimize arc flash and blasts in the past.

• The Electrical Energized Work Practices outlined in NFPA 70E incorporates measures to help avoid or minimize damage from arc flash.

Page 27: Arc Blast Flash

What is an Arc Flash?

NFPA 70E says an arc flash hazard is:

A dangerous condition associated with the release of energy caused by an electric arc

A hazard beyond shock and electrocution

Page 28: Arc Blast Flash

Bolted and Arcing Fault Characteristics

• Arcing fault incident energy released is:– Greater at higher bolted fault current levels– Reduced by dynamic impedance (air)– And increased by the time duration of the arc

• The most controllable factor in reducing the incident energy is time

• Current flow in a 480V arcing fault is approximately half that of the bolted fault current (impedance of air)

• Fuses or circuit breakers are the first line of defense in reducing arcing fault incident energy

• Calculating arc fault incident energy is a very complex engineering task

Page 29: Arc Blast Flash

Causes of Bolted and Arcing Faults

• What causes these types of faults?– Bolted faults (low impedance and high current)

• Commonly caused by– Improper connections after maintenance

– Installation errors

– Arcing faults (high impedance, lower current)• Commonly caused by

– Careless cover or device removal

– Foreign object (tool) dropped into equipment

– Misalignment of moving contacts (parts failure)

– Dirt contamination or dielectric breakdown

– Entry of foreign body (rodent, snake, squirrel, human)

Page 30: Arc Blast Flash

Insulation Failures

• Loose Connections– Animals– Poorly maintained equipment– Equipment failures– Inadvertent contact

Page 31: Arc Blast Flash

Two Types of Major Electrical Faults Can Occur

• Bolted faults– Low impedance and high current– Energy is contained by the conductor (bus or cable)– Cleared quickly by circuit breakers or fuses– Arcing is confined within the circuit breaker or fuse– Usually no damage to equipment– Relatively low safety risk to personnel

• Arcing faults– High impedance (air) results in lower current– Persist longer and propagate– High release of heat and blast energy– Are very destructive and dangerous to personnel

Page 32: Arc Blast Flash

Electric Arcs Produce:

• The intense heat from arc causes the sudden expansion of air that results in a blast with very strong air pressure (Lightning is a natural arc).

Page 33: Arc Blast Flash
Page 34: Arc Blast Flash

Electric Arcs Produce:

• Electric arcs produce the highest temperatures on earth –up to 35,000 degrees Fahrenheit (4 x temp of the sun)!

Page 35: Arc Blast Flash

AF Incident

Page 36: Arc Blast Flash

AF Incident

Page 37: Arc Blast Flash

AF Incident

Page 38: Arc Blast Flash

AF Incident

Page 39: Arc Blast Flash

AF Incident

Page 40: Arc Blast Flash

Developments Leading to NFPA 70E-2004

Large Hydro in Pacific NW

6.9 kV Swgr

Racking in Breaker

AF occurred

One worker injured

5+ years

$10+ million

Page 41: Arc Blast Flash

Electric Arcs Effects:

• All known materials are vaporized at this temperature. (Copper expands 67,000 times, Water 1670 times).

Page 42: Arc Blast Flash

Developments Leading to NFPA 70E-2004

Page 43: Arc Blast Flash

Electric Arcs Effects:

• Arcs in enclosures, such as a Motor Control Centers (MCCs) or switchgear, magnify blast and energy transmitted as the blast is forced to the open side of the enclosure.

Page 44: Arc Blast Flash

Electric Arcs Effects:

• Arcs spray droplets of molten metal at high-speed pressure. Blast shrapnel can penetrate the body.

Page 45: Arc Blast Flash

AF Incident

Page 46: Arc Blast Flash

Electric Arcs Effects:

• Blast pressure waves have thrown workers across rooms and knocked them off ladders. Pressure on the chest can be higher than 2000 lbs/ sq. ft.

Page 47: Arc Blast Flash

Electric Arcs Effects:

• Clothing can be ignited several feet away. Clothed areas can be burned more severely than exposed skin.

Page 48: Arc Blast Flash

Electric Arcs Effects:

• Hearing loss from sound blast. The sound can have a magnitude as high as 140 dB at a distance of 2 feet from the arc.

Page 49: Arc Blast Flash

Electric Arcs Effects:

• Energy released is a function of:• system voltage• fault current magnitude• fault duration

Page 50: Arc Blast Flash

Results of an Arc Flash

• Other non-human consequences

• Downtime• Lost revenue• Loss of product• Equipment damage• Regulatory impact• OSHA citation and fines

Page 51: Arc Blast Flash

How to protect against Shock and Arc Flash/Blast?

Chapter 1, Section 130 of NFPA-70E20041. Justification for Live Work

2. Work Permits Secured if Applicable

3. Approach Boundaries Established

a) Shock Protection

b) Limited Boundary

c) Restricted Boundary

d) Prohibited Boundary

4. Flash Protection –– ONE BOUNDARY

Page 52: Arc Blast Flash

Electrical Arc Facts

• Arc is electric current passing through air– Shock potential from contact with arc

• Temperature of arc plasma center is greater than 5000°F (some say much higher)– Radiated heat burns

• Pressure wave generated from arc– Impact to hearing, etc– Gaseous copper is 44,000 times solid– Molten metal expelled from equipment at high speed

• Arc fault results from something wrong or out of place

Page 53: Arc Blast Flash

Arcing Short Circuit

Page 54: Arc Blast Flash

Flash protection boundary

Limited approach boundary

Limited space

Restricted approach boundary

Restricted space

Any point on an exposed, energized electrical conductor or circuit part

Prohibited spaceProhibited approach boundary

Flash protection boundary:

An approach limit at a distance from exposed live parts within which a person could receive a second degree burn if an electric arc flash were to occur.

(NFPA 70E)

Page 55: Arc Blast Flash

Arc Flash Boundary

Page 56: Arc Blast Flash
Page 57: Arc Blast Flash

Approach Boundaries

Limited Approach Boundaryentered only by qualified persons or unqualified persons that have been advised and are escorted by a qualified person

Restricted Approach Boundaryentered only by qualified persons required to use shock protection techniques and PPE

Prohibited Approach Boundaryentered only by qualified persons requiring same protection as if direct contact with live part

Flash Protection Boundary linear distance to prevent any more than 2nd degree burns from a potential arc-flash (Typically 4 feet)

Page 58: Arc Blast Flash

Section 110.16 of the2002 NEC® Requires Arc

FlashHazard Labels

Page 59: Arc Blast Flash

Arc Flash Labeling Required by NEC

• 110.16 Flash Protection. Switchboards, panelboards, industrial control panels, and motor control centers in other than dwelling occupancies, that are likely to require examination, adjustment, servicing, or maintenance while energized, shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.

Page 60: Arc Blast Flash

Arc Flash Labeling Required by NEC

FPN No. 1: NFPA 70E-2000, Electrical Safety Requirements for Employee Workplaces, provides assistance in determining severity of potential exposure, planning safe work practices, and selecting personal protective equipment.

FPN No. 2: ANSI Z535.4-1998, Product Safety Signs and Labels, provides guidelines for the design of safety signs and labels for application to products.

Reprinted from NEC® 2002

Page 61: Arc Blast Flash
Page 62: Arc Blast Flash

Arc Flash and Shock Hazard Appropriate PPE Required

Page 63: Arc Blast Flash
Page 64: Arc Blast Flash
Page 65: Arc Blast Flash

48 inch Flash Hazard Boundary7.4 cal/cm2 Flash Hazard at 18 inchesHRC 2 PPE Level, FR Clothes, Shield, Hard Hat, Leather

Gloves, Leather Shoes, Hearing Protection480 VAC Shock Hazard when Cover is removed42 inch Limited Approach12 inch Restricted Approach - 500 V Class 00 Gloves1 inch Prohibited Approach - 500 V Class 00 Gloves

Courtesy E.I. du Pont de Nemours & Co.

Arc Flash and Shock Hazard Appropriate PPE Required

Page 66: Arc Blast Flash

Minimize Risk with Good Safety Practices

Page 67: Arc Blast Flash

Arc Flash and Shock Hazard Appropriate PPE Required

24 inch Flash Hazard Boundary3 cal/cm2 Flash Hazard at 18 inchesHRC 1 PPE Level, FR Pants & Shirt – 4 cal/cm2

480 VAC Shock Hazard when Cover is removed42 inch Limited Approach12 inch Restricted Approach - 500 V Class 00 Gloves1 inch Prohibited Approach - 500 V Class 00 Gloves

Courtesy E.I. du Pont de Nemours & Co.

Page 68: Arc Blast Flash
Page 69: Arc Blast Flash

NFPA 70E: Safety in WorkplaceOSHA 1910.333 (a) (1) & NFPA 70E 130.1

Qualified electrical workers shall not be asked to work on equipment that is “hot” or “live” except for two demonstrable reasons :

1. De-energizing introduces additional or increased hazards: a) cutting ventilation to a hazardous location

b) emergency alarm systems

or

2. Infeasible due to equipment design or operational limitations:a) voltage testing for diagnostics

b) start up testing

Page 70: Arc Blast Flash

Safety-Related Work Practices

1910-333 Selection & use of work practices

(a) General. Safety-related work practices shall be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contact, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards

Page 71: Arc Blast Flash

Safety-Related Work Practices

1910-335 Safe guards for personnel protection

(a)(2)(B)(ii) Protective shields, protective barriers, or insulating materials shall be used to protect each employee from shock, burns, or other electrically related injuries while that employee is working near exposed energized parts which might be accidentally contacted or where dangerous electric heating or arcing might occur.

Page 72: Arc Blast Flash

Arc Flash Incident

Page 73: Arc Blast Flash

Background

May 2003

Troubleshooting energized outdoor switchgear

Three workers, all wearing polyester blend clothing

Voltage = 13,200V

A company security camera filmed the entire accident

Page 74: Arc Blast Flash

AF Incident

The next scene shows a ball of flame totally engulfing the three workers

Page 75: Arc Blast Flash

AF Incident

The worker who was standing in front of the equipment on the left hand side is engulfed in flames.

The worker laying in the cell is propelled outward in a ball of flames.

Page 76: Arc Blast Flash

Injuries

3rd worker not burned but suffered neurological damage from the blast.

Note: He weighed approximately 300 lbs. and was thrown almost 12 feet backwards.

Currently OSHA has $148,000 in penalties pending for serious and willful violations.

Page 77: Arc Blast Flash

Injuries

Two workers 2nd and 3rd degree burns over 60% of the body.

Synthetic hair nets and hardhat suspension burned into scalp.

One burn victim in drug induced come for 6 weeks while burns being scrubbed.

Page 78: Arc Blast Flash

AF Incident

The worker who was at the bottom of the compartment is crawling away from the equipment with his clothing on fire.

The worker on the right lands on his back with his feet in the air.

The worker on the left is running away.

Page 79: Arc Blast Flash

AF Incident

State of shock.

Panic after the Arc Flash and Arc Blast.

Page 80: Arc Blast Flash

AF Incident

The worker on fire is frantically tearing his coveralls from his body.

As he is doing this, we can see the workpants he is wearing underneath his coveralls are on fire.

Page 81: Arc Blast Flash

Who’s Responsible for Safety?

The “Employer” is responsible for• OSHA requirements• Electrical Safety Program• Safety Policies and Procedures• Safety Training and Retraining

The “Employee” is responsible for• Implementing procedures• [NFPA 70E-110.3(B)]

The “Owner” and Contractors are both responsible

• To coordinate and document hazards and safety procedures• Contractors on site and visa versa

[NFPA 70E-110.3(B)]

Page 82: Arc Blast Flash

Response to an Electrical Accident

Personnel that are Trained in CPR should be identified and available when work near or on energized parts is being performed

Page 83: Arc Blast Flash

Response to an Electrical Accident

The first step must be to

“TURN THE POWER OFF”

Page 84: Arc Blast Flash

What an Arcing Fault looks like:

Page 85: Arc Blast Flash

Steps to Take if an Electrical Accident Happens

• Remove the Immediate Hazard:– turn Off the Power

• Remember that Speed is Essential

• Extinguish flames

• Call for Help (911)

• Begin CPR & First Aid

Page 86: Arc Blast Flash

Steps to Take if an Electrical Accident Happens

• First Aid– Cool the burn with water– Do not attempt to remove burned clothing– Elevate burned limbs– Handle the victim with care– Treat for shock

– Maintain body temperature– Do not give anything by mouth

Page 87: Arc Blast Flash

CPR

Personnel that work near or on energized parts should be trained in CPR.

Page 88: Arc Blast Flash

What is the best way to prevent thehazards of electricity?

Stop - Before ActionThink - Risks/HazardsOptions - LOTO-Tagout-

TryoutProtection - Proper PPE

Avoiding energizedcircuits is the Safest

Way!

Page 89: Arc Blast Flash

The EndGillis safety services, llc©