APS Underground Distribution Cable Replacement Project
Scott GudemanManager Const Projects and Support Svcs
September 27, 2012
![Page 2: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/2.jpg)
2
Agenda
• UG Distribution Cable Historical Overview• Cable Replacement Program• Replace Vs. Repair• Where We Are Today• Future Direction
![Page 3: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/3.jpg)
UG Distribution Cable Historical Overview
![Page 4: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/4.jpg)
4
Background
• APS began installing direct buried underground primary distribution cable in the 1950’s and continued until the mid 1980’s.
• The majority of direct buried underground primary cable in the APS distribution system is a 165-180 mil XLPE, non-jacketed type cable.
![Page 5: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/5.jpg)
5
Cable Failures
• In the mid-1980’s, we started to experience a steady increase in direct buried underground cable failures.
• There were 0.3 failures for every circuit mile of underground cable, accounting for 24% of the Company’s overall SAIFI rating.
![Page 6: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/6.jpg)
6
Cause of the Failures
• The direct buried XLPE primary cable had reached the end of its useful life. Although manufacturer’s projected a 30-year life expectancy; we were realizing 16 years.
• Contributing factors to cable failures were installation practices, mechanical failures, water trees, accessory failures, manufacturing defects, corrosion, or system overload.
• As a result, APS began to install 220 mil, TRXLPE, Jacketed UG cable in conduit in 1986 and fully transitioned to full conduit primary and secondary system in 1988.
![Page 7: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/7.jpg)
Cable Replacement Project
![Page 8: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/8.jpg)
8
Cable Replacement Project
• The Underground Distribution Cable Replacement Project began in 1992 with the goal of replacing all direct buried underground cable in the APS System.
• It has continued since then with the same objective, yet with changing funding levels and business drivers to achieve that goal.
![Page 9: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/9.jpg)
9
Cable Replacement Plan Business Drivers
The Business Drivers used to determine which cable runs to replace:
• Customer Satisfaction• Critical Customers and Key Accounts• Operating Demands and Priorities• Number of Faults per Run• Reliability (SAIFI)• Cost Containment
![Page 10: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/10.jpg)
11
Replacement Approaches
Utilize a combination of quick response and planned tactics:
– Accelerated Replacement (AR) 1-1/0A– Quick Hitters (QH) 3-1/0A– 750A and 1/0A Planned Replacement Work– Corroded Neutral Planned Replacement Work– Locate and Repairs– Service/Secondary Replacement
![Page 11: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/11.jpg)
12
Quick Response Cable Replacement – AR’s and QH’s
Three Phase 3-1/0A CableSingle Phase 1/0A Cable
– <= 500’– Not in major street– Not in private easement– Use blanket permit with municipalities– Contract out all excavation and conduit installation– APS crews install and terminate wire– Typically a 7 working day turnaround on jobs with guards
![Page 12: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/12.jpg)
13
Planned Feeder Cable Replacement - 750A
750kCmil Feeder Cable
– Jobs are scoped, designed, routed and permits acquired
– Budget status determines when job is released for construction
– A limited number of jobs are on the shelf so that we can react quickly
– Contract all excavation and conduit installation– APS crews install and terminate wire
![Page 13: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/13.jpg)
14
Planned Cable Replacement – Corroded Neutral Cable
1/0A or 3-1/0 in Northern Regions
• Concentric Neutral on DB cable has sacrificed itself due to corrosive soil conditions
• Jobs to replace multiple runs prioritized by Districts• Jobs are scoped, designed, routed and permits acquired• Budget status determines when job is released for
construction• A limited number of jobs are on the shelf so that we can
react quickly• Contract all excavation and conduit installation• APS crews install and terminate wire
![Page 14: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/14.jpg)
15
Locate & Repair
Single Phase or Three Phase Circuits
– >500’– In major street– In private easement– Needs a permit to replace– Other complications such as limited access
![Page 15: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/15.jpg)
16
Service/Secondary Cable Replacement
Includes both service and secondary direct buried low voltage (<600 volts) cable runs
• Added emphasis in 2011 to replace rather than repair service/secondary faults
• Typically, no guards since we can put a service kit on the house
• All work is completed by a contractor. They excavate, install conduit and conductor, and re-landscape
![Page 16: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/16.jpg)
Replace Vs. Repair
![Page 17: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/17.jpg)
18
Replace Vs. Repair Primary Cable
• Philosophy is a balanced approach between Replace and Repair
• Mean time between faults accelerates with each failure
– 2nd Time Fault Recurrence – 3.58 years– 3rd Time Fault Recurrence – 2.13 years– 4th Time Fault Recurrence – 1.21 years– 5th Time Fault Recurrence – 1.40 years– 6th Time Fault Recurrence – 0.56 years
![Page 18: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/18.jpg)
19
Replace Vs. Repair Primary Cable
• Average cost for Repairs (2011)– $3,800 for 1/0A– $5,800 for 750A
• Average Replacement Cost (2011) per work order– $10,190 for 1/0A– $60,108 for 750A
• Can replace 1/0A for less than the cost to repair it three times.
![Page 19: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/19.jpg)
Where We Are Today
![Page 20: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/20.jpg)
21
How Much Direct Buried Cable Was Installed?
• It was estimated that we installed about 5,000 trench miles of direct buried underground primary cable
• We have replaced approximately 2,300 trench miles through July 2012
![Page 21: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/21.jpg)
22
Cable Replacement Year to DateMetro Primary Cable Replacement Summary
Project Year Trench Miles Replaced Total Expenditures88 thru 91 289.57
1992 117.92 $22,922,839 1993 121.26 $27,888,119 1994 180.78 $27,568,844 1995 138.33 $23,578,462 1996 127.70 $19,597,170 1997 148.50 $19,662,976 1998 155.59 $18,866,000 1999 132.83 $16,815,172 2000 130.76 $17,857,885 2001 127.79 $18,476,340 2002 114.71 $16,507,908 2003 75.91 $8,014,052 2004 66.16 $10,448,000 2005 64.18 $11,068,871 2006 55.68 $12,345,972 2007 54.36 $13,940,602 2008 44.12 $15,031,960 2009 30.83 $14,601,760 2010 47.23 $13,120,202 2011 49.21 $16,316,439 2012 25.65 $11,563,707
Total 2,299.07 $356,193,280
* 2012 = Jan - Jul
![Page 22: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/22.jpg)
23
Estimated Direct Buried Cable Remaining Trench Miles (Aug 2012)
Division 1-1/0A 3-1/0A 3-750A Total
Metro 1444 133 55 1632
NE 288 111 3 402
NW 360 54 4 418
SE 93 25 3 121
SW 135 14 2 151
Total 2320 337 67 2724
![Page 23: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/23.jpg)
Future Direction
![Page 24: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/24.jpg)
25
Going Forward
The Cable Replacement Program will focus on:
• Replacing all of the direct buried 750A feeder cable in the next 4-5 years
• Replacing all identified corroded neutral primary cable (estimated 67 trench miles) in next 7-8 years
• Continue with AR and QH program
![Page 25: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/25.jpg)
26
Going Forward
• Continue the balanced approach to replace and repair both primary and secondary/service
• Advocate funding cable replacement at the same levels as 2012– Primary - $22M– Svc/Sec - $3.5M
![Page 26: APS Underground Distribution Cable Replacement Project Scott Gudeman Manager Const Projects and Support Svcs September 27, 2012.](https://reader035.fdocuments.in/reader035/viewer/2022070306/551957d2550346b5698b4646/html5/thumbnails/26.jpg)
Questions?