© 2016 tekmar 670_A - 10/16
670_A10/16
Snow Melting Replaces: New
WiFi Snow Melting Control 670
Application Brochure
Application Page
Dedicated Boiler 2
Dedicated Boiler and Mixing Valve 4
Shared Boiler and Heat Exchanger 6
Shared Boiler and Mixing Valve with Optional Tandem Sensors 8
Shared Boiler and Injection Mixing 10
Modulating Steam Valve 12
Electric Cable 14
Multiple Zones with Multiple Boilers and Shared Mixing Valve 16
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
The WiFi Snow Melting Control 670 operates hydronic and electric heating equipment designed to melt snow and/or ice from roads and walkway surfaces. The control works with the tekmar Snow/Ice Sensor 090 or Snow Sensor 095 to automatically detect snow or ice and operates a single boiler, steam valve, or electric cable to supply heat to the slab. Boiler return protection is provided to non-condensing boilers using a mixing valve or variable speed injection mixing pump. The tekmar Connect mobile application allows for remote operation and monitoring of the snow melting system from anywhere in the world.
2 of 20© 2016 tekmar 670_A - 10/16
Dedicated Boiler A670-1 Mechanical
DescriptionThe WiFi Snow Melting Control 670 operates a boiler that is dedicated for the snow melting system. The system is piped in primary-secondary to allow constant flow rates through the low-mass boiler and filled with glycol to prevent freezing.• The system pump operates continuously when heating the slab during melting/idling/storm operation.• The boiler pump cycles on and off together with the boiler.• The slab temperature is controlled by modulating the boiler firing rate or cycling the boiler on and off.• The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.• Optional slab protection limits the temperature differential between the boiler supply and slab.
The system operation is dependent on sensor selection, as listed in the table below.
Application SettingsSetting Name Value
Application Mode Boiler
Sensor options Operation methods
Sensor Sensor Model(s)Auto Start/Auto Stop
Auto Start/Timed Stop
Manual Start/Timed Stop
Slab TemperatureControl
S1 Automatic Snow/Ice Sensor 090 or 094 • – • •
S2 Aerial Snow Sensor 095 – • • –
S3 Slab Sensor 072 or 073 – – • •
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073 – • • •
B1 = Modulating BoilerP1 = System PumpP2 = Boiler PumpS1 = Snow/Ice Sensor 090 or 094S2 = Snow Sensor 095S3 = Slab Sensor 072 or 073S4 = Outdoor Sensor 070S5 = Boiler Supply Sensor 082
Legend
S4
670
Snow/Ice Sensor Options
B1
P2
P1S5
S2
S1
S3
© 2016 tekmar 670_A - 10/163 of 20
T T–+
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
BrnSlab
BlkCom YelBluRed
SnowSensor
095
S4
B1
LN
P1
S5S1
S2 S3
Dedicated Boiler A670-1 Electrical
4 of 20© 2016 tekmar 670_A - 10/16
Dedicated Boiler and Mixing A670-2 Mechanical
Application SettingsSetting Name Value
Application Mode Boiler+Mix
B1 = Modulating BoilerM1 = Actuating Motor 741P1 = System PumpP2 = Boiler PumpS1 = Snow/Ice Sensor 090 or 094S2 = Snow Sensor 095S3 = Slab Sensor 072 or 073S4 = Outdoor Sensor 070S5 = Boiler Supply Sensor 082S6 = Mix Supply Sensor 082X1 = Transformer 009V1 = 3-Way Mixing Valve 710 through 714
Legend
670
Snow/Ice Sensor Options
S4
S5 S6P1P2 V1
M1B1
S1
S2
S3
DescriptionThe WiFi Snow Melting Control 670 operates a boiler and a mixing valve that is dedicated for the snow melting system. The boiler is piped in primary-secondary to the system to allow constant flow rates through the low-mass boiler. The entire system is filled with glycol to prevent freezing.• The system and boiler pumps operate continuously when heating the slab during melting/idling/storm operation.• The mixing valve position is adjusted to 100% open unless providing boiler return protection.• The slab temperature is controlled by modulating the boiler firing rate or cycling the boiler on and off.• The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.• Optional slab protection limits the temperature differential between the boiler supply and slab.
The system operation is dependent on sensor selection, as listed in the table below.
Sensor options Operation methods
Sensor Sensor Model(s)Auto Start/Auto Stop
Auto Start/Timed Stop
Manual Start/Timed Stop
Slab TemperatureControl
S1 Automatic Snow/Ice Sensor 090 or 094 • – • •
S2 Aerial Snow Sensor 095 – • • –
S3 Slab Sensor 072 or 073 – – • •
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073 – • • •
© 2016 tekmar 670_A - 10/165 of 20
Com
Close
Open
T T–+
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
BrnSlab
BlkCom YelBluRed
SnowSensor
095
S1
S2 S3
M1
V1
X1
LN
S4
S5
P2 P1
S6
Dedicated Boiler and Mixing A670-2 Electrical
6 of 20© 2016 tekmar 670_A - 10/16
Shared Boiler and Heat Exchanger A670-3 Mechanical
Application SettingsSetting Name Value
Application Mode PWM Zone
Boiler Type Enable
A1 = Normally Closed Freeze Protection AquastatB1 = Boiler EnableHX = Heat ExchangerP1 = System PumpP2 = On/Off Heat Exchanger PumpS1 = Snow/Ice Sensor 090 or 094S2 = Snow Sensor 095S3 = Slab Sensor 072 or 073S4 = Outdoor Sensor 070
Legend
670
Snow/Ice Sensor Options
S4
P2
A1
P1
S1
S2
S3
HX
DescriptionThe WiFi Snow Melting Control 670 operates a snow melting zone warmed from a heat source that is shared with other loads in a building. A heat exchanger isolates the glycol-filled snow melting system loop from the water-filled main heating system.• The system pump operates continuously when heating the slab during melting/idling/storm operation.• The slab temperature is controlled by cycling the heat exchanger pump and the boiler enable on and off.• The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.• A normally-closed aquastat protects the heat exchanger from freezing by shutting off power to the system pump.
The system operation is dependent on sensor selection, as listed in the table below.Sensor options Operation methods
Sensor Sensor Model(s)Auto Start/Auto Stop
Auto Start/Timed Stop
Manual Start/Timed Stop
Slab TemperatureControl
S1 Automatic Snow/Ice Sensor 090 or 094 • – • •
S2 Aerial Snow Sensor 095 – • • –
S3 Slab Sensor 072 or 073 – – • •
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073 – • • •
© 2016 tekmar 670_A - 10/167 of 20
BrnSlab
BlkCom YelBluRed
SnowSensor
095
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
S1
S3S2
S4
LN
B1
P2
A1
P1
Shared Boiler and Heat Exchanger A670-3 Electrical
8 of 20© 2016 tekmar 670_A - 10/16
Shared Boiler and Mixing Valve with Optional Tandem Sensors A670-4 Mechanical
670 Application SettingsSetting Name Value
Application Mode Mixing
Mixing Type Floating
Boiler Type Enable
Optional 654 Application SettingsSetting Name Value
Application Mode 090
A1 = Normally Closed Freeze Protection AquastatB1 = Boiler EnableHX = Heat ExchangerM1 = Actuating Motor 741P1 = System PumpP2 = Heat Exchanger PumpS1a, S1b = Snow/Ice Sensor 090 or 094S4 = Outdoor Sensor 070S5 = Boiler Return Sensor 082S6 = Mix Supply Sensor 082V1 = 3-Way Mixing Valve 710 through 714X1 = Transformer 009
Legend
670 Optional654S4
S5
P2 P1S6
V1HX
M1S1a
S1bA1
DescriptionThe WiFi Snow Melting Control 670 operates a snow melting zone warmed from a heat source that is shared with other loads in a building. The system uses a mixing valve to regulate the water temperature and a heat exchanger isolates the glycol-filled snow melting system loop from the water-filled main heating system. The 670 is paired with a Snow Melting Control 654 to provide Tandem Snow/Ice Detection using a Snow/Ice Sensor 090 or 094. Tandem sensors double the detection area to provide increased reliability and redundancy in case of sensor failure. • The system pump operates continuously when heating the slab during melting/idling/storm operation.• The slab temperature is controlled by adjusting the mixing valve position.• When the mixing valve is open, the heat exchanger pump and the boiler enable are on.• The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.• A normally-closed aquastat protects the heat exchanger from freezing by shutting off power to the system pump.• Either snow/ice sensor will start the melting operation if snow or ice is detected. Both sensors must be dry in order to
stop melting.
© 2016 tekmar 670_A - 10/169 of 20
Com
Close
Open
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
SlabBrn
+ModtN4Aux Ht R C
BretOut/
Com–BlkYel Blu Red Sup
No Power
X1
LN
S1aS1bS4
B1
P2 P1
A1
S6
S5
M1
V1
Shared Boiler and Mixing Valve with Optional Tandem Sensors A670-4 Electrical
654 670
10 of 20© 2016 tekmar 670_A - 10/16
Shared Boiler and Mixing Injection Pump A670-5 Mechanical
Application SettingsSetting Name Value
Application Mode Mixing
Mixing Type Injection
Boiler Type Enable
A1 = Normally Closed Freeze Protection AquastatB1 = Boiler EnableHX = Heat ExchangerP1 = System PumpP2 = Heat Exchanger PumpP3 = Variable Speed Injection Mixing PumpS1 = Snow/Ice Sensor 090 or 094S2 = Snow Sensor 095S3 = Slab Sensor 072 or 073S4 = Outdoor Sensor 070S5 = Boiler Return Sensor 082S6 = Mix Supply Sensor 082V1 = Globe Valve
Legend
Sensor options Operation methods
Sensor Sensor Model(s)Auto Start/Auto Stop
Auto Start/Timed Stop
Manual Start/Timed Stop
Slab TemperatureControl
S1 Automatic Snow/Ice Sensor 090 or 094 • – • •
S2 Aerial Snow Sensor 095 – • • –
S3 Slab Sensor 072 or 073 – – • •
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073 – • • •
670
Snow/Ice Sensor Options
S4
S5
P2 P1 S6P3HX
S1
S2
S3A1
V1
DescriptionThe WiFi Snow Melting Control 670 operates a snow melting zone warmed from a heat source that is shared with other loads in a building. The system uses a variable speed injection pump to regulate the water temperature and a heat exchanger isolates the glycol-filled snow melting system loop from the water-filled main heating system.• The system pump operates continuously when heating the slab during melting/idling/storm operation.• The slab temperature is controlled by adjusting the speed of the variable speed injection pump.• When the variable speed injection pump is on, the heat exchanger pump and the boiler enable are on.• The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.• A normally-closed aquastat protects the heat exchanger from freezing by shutting off power to the system pump.
The system operation is dependent on sensor selection, as listed in the table below.
© 2016 tekmar 670_A - 10/1611 of 20
Shared Boiler and Mixing Injection Pump A670-5 Electrical
BrnSlab
BlkCom YelBluRed
SnowSensor
095
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
LN
S1
S2 S3
S4
B1
P2 P1
A1
S5
S6
P3
12 of 20© 2016 tekmar 670_A - 10/16
Modulating Steam Valve A670-6 Mechanical
Application SettingsSetting Name Value
Application Mode Mixing
Mixing Type 0-10 V or 4-20 mA
Boiler Type Enable
B1 = Boiler EnableHX = Steam-to-Glycol Heat ExchangerM1 = Modulating Steam ValveP1 = System PumpS1 = Snow/Ice Sensor 090 or 094S2 = Snow Sensor 095S3 = Slab Sensor 072 or 073S4 = Outdoor Sensor 070S5 = Mix Supply Sensor 082
Legend
670
Snow/Ice Sensor Options
S4
S5P1HX
M1
S1
S2
S3
DescriptionThe WiFi Snow Melting Control 670 operates a modulating steam valve and a steam-to-water heat exchanger to heat a glycol-filled snow melting system.• The system pump operates continuously when heating the slab during melting/idling/storm operation.• The slab temperature is controlled by adjusting the modulating steam valve position.• The boiler relay is closed while the modulating steam valve is open. This provides a signal to fire the steam boiler.• The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.
The system operation is dependent on sensor selection, as listed in the table below.
Sensor options Operation methods
Sensor Sensor Model(s)Auto Start/Auto Stop
Auto Start/Timed Stop
Manual Start/Timed Stop
Slab TemperatureControl
S1 Automatic Snow/Ice Sensor 090 or 094 • – • •
S2 Aerial Snow Sensor 095 – • • –
S3 Slab Sensor 072 or 073 – – • •
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073 – • • •
© 2016 tekmar 670_A - 10/1613 of 20
Modulating Steam Valve A670-6 Electrical
+ –
BrnSlab
BlkCom YelBluRed
SnowSensor
095
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
LN
S1
S2 S3
S4
B1
P1
S5
M1
14 of 20© 2016 tekmar 670_A - 10/16
Electric Cable A680-7 Mechanical
Application SettingsSetting Name Value
Application Mode Electric
670
E1 = 115 or 230 V (ac) Electric Power SupplyH1 = Electric Heating CableR1 = Electric Relay ContactorS1 = Snow/Ice Sensor 090 or 094S2 = Snow Sensor 095S3 = Slab Sensor 072 or 073S4 = Outdoor Sensor 070
Legend
Snow/Ice Sensor Options
S4
E1 R1
H1
S1
S2
S3
DescriptionThe WiFi Snow Melting Control 670 operates an electric cable snow melting system.• The electric contactor is cycled on and off based on the slab load.
The system operation is dependent on sensor selection, as listed in the table below.
Sensor options Operation methods
Sensor Sensor Model(s)Auto Start/Auto Stop
Auto Start/Timed Stop
Manual Start/Timed Stop
Slab TemperatureControl
S1 Automatic Snow/Ice Sensor 090 or 094 • – • •
S2 Aerial Snow Sensor 095 – • • –
S3 Slab Sensor 072 or 073 – – • •
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073 – • • •
© 2016 tekmar 670_A - 10/1615 of 20
Electric Cable A670-7 Electrical
R W
BrnSlab
BlkCom YelBluRed
SnowSensor
095
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
LN
S1
S2 S3
S4
R1
16 of 20© 2016 tekmar 670_A - 10/16
Multiple Zones with Multiple Boilers and Shared Mixing Valve A670-8 Mechanical
400
V1
B1
423 & 346
444
B2 M1
S4
S5S6
tN4 Mix 1 Bus
DescriptionThe system has two snow melting zones heated by two boilers. The water temperature is regulated by a shared mixing valve for the two snow melting zones. The boilers and mixing valve are operated by a Universal Reset Module 423, Power Manager 346 and Mixing Expansion Module 444. Each snow melting zone is operated by a WiFi Snow Melting Control 670.• The slab target is determined by the melting/idling/storm setpoint and by the measured outdoor air temperature.• The zone pump cycles on/off when heating the slab during melting/idling/storm operation.• When the zone is heated, the 670 communicates to the 423 and 444 to operate the mixing valve and fire the boilers.• The 423 and 444 close the mixing valve to provide boiler return protection when the boiler supply temperature falls below
the 423 boiler minimum setting.
The system operation is dependent on sensor selection, as listed in the table below.Sensor options Operation methods
Sensor Sensor Model(s)Auto Start/Auto Stop
Auto Start/Timed Stop
Manual Start/Timed Stop
Slab TemperatureControl
S1 Automatic Snow/Ice Sensor 090 or 094 • – • •
S2 Aerial Snow Sensor 095 – • • –
S3 Slab Sensor 072 or 073 – – • •
S2+S3 Aerial Snow Sensor 095 and Slab Sensor 072/073 – • • •
© 2016 tekmar 670_A - 10/1617 of 20
A670-8 Mechanical
B1, B2 = Modulating BoilersM1 = Actuator Motor 741P1 = Zone 1 PumpP2 = Zone 2 PumpS1a = Zone 1 Snow/Ice Sensor 090 or 094S1b = Zone 2 Snow/Ice Sensor 090 or 094S2a = Zone 1 Snow Sensor 095S2b = Zone 2 Snow Sensor 095
S3a = Zone 1 Slab Sensor 072 or 073S3b = Zone 2 Slab Sensor 072 or 073S4 = Outdoor Sensor 070S5 = 423 Boiler Supply Sensor 082S6 = 444 Mix Supply Sensor 082V1 = 3-Way Mixing Valve 710 through 714X1 = Transformer 009
Legend
670 Application SettingsSetting Name Value
Application Mode PWM Zone
Outdoor Sensor tekmarNet
Boiler Type Control
400
S1a S1b
S2a S2b
S3a S3b
P1 P2
670 670
tN4 Mix 1 Bus
Zone #1 Zone #2
Zone #1 Snow/Ice Sensor Options
Zone #2 Snow/Ice Sensor Options
18 of 20© 2016 tekmar 670_A - 10/16
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up50 51 52 53
Stage1/ Stage 2/ Boil Enbl Setp Enbl
75 76 77 78
Demand DemandDHW Setpoint
54 55
DHW Primary
10 Amax79 80 81 82
NPump NPump
tN4Made in Canada
8 VA 1 VA
Boil Sens Sup / RetH7010A
Off / DHW SensorOff / tekmar StagerBoilers On-Off / ModOff / Rotation
Meets Class B: CanadianICES & FCC Part 15
PoweredOutputs24 V (ac)
Universal Reset Module 423
Item
Menu
tektra 1006-01
Demands: 20 - 260 V (ac)Relay Rating: 115 V (ac) 5 A
71 72 73 74DHW 24 V (ac)
/
57 58 59 60 6156
C
C
tN4Mod2 (dc)Mod1 (dc)
6564
C3C1+ –
C
+ – tN4
62 63
C2 tN4 tN4
66 67
DHW ComBoiler
68 69
Boil Com
70
Out
Do not apply power
Test
1 2 3
Vlv R
No Power
Mixing Expansion Module 444Variable Speed / Floating Action / Modulating
Made in CanadaSignal wiring
must be rated atleast 300V / 90°CCu
t for
mA
outp
ut
5R
6R
41tN4
7Mod
+
8Com
9Mix
Power ClsOpnSysPmp
2C
3R
No Power
Date
Cod
e
1
tektra 1019-01
1
Power Manager 346
For product literature:www.tekmarcontrols.com
Boiler Bus 0 Demand Power
Aux Pump 1
Aux Pump 2
Aux Pump 3
tN4
Bus 1 Demand
Bus 2 Demand
Bus 3 Demand
Meets Class B: CanadianICES & FCC Part 15
Caution! Disconnect AllPower before Opening
24 V (ac) Fuse: T2.5 A 250 V
H701
1A
Relay Power27 28
NLAux Pump 229 30
NPmpAux Pump 331 32
NPmp
For product instructions, see brochureInput Power: 115 V (ac) ±10% 60 Hz, 12 AAll Loads Using Input Power: 11.5 ARelay Ratings: 115 V (ac) 5 ARelay Power: 115 V (ac) ±10% 60 Hz, 10 ADemands: 20 to 260 V (ac) 2 VA
Supply wires 90°C/105°CSee manual
Boil Bus 0
16 17Demand
Bus 3 Bus 2
18Dem DemDem
19
Bus 1
20 21Demand
227
tN4
5 6
tN4 C C
2Boil 0
11
tN4
9 102C C
15
tN4
13 143
ComAuxPmp1
4
RR R R
3
AuxPmp2
8
AuxPmp3
12Limited power available, see wiring brochure
Room Occ
Room UnOcc
0Boil
1
2
3 1
3
11
9
7
5
12
10
8
6
4
2Sch
edul
eM
embe
r
Input Power23 24
NLAux Pump 125 26
NPmp
RC
Com
Open
Close
Multiple Zones with Multiple Boilers and Shared Mixing Valve A670-8 Electrical
B1, B2 = Modulating BoilersM1 = Actuator Motor 741P1 = Zone 1 PumpP2 = Zone 2 PumpS1a = Zone 1 Snow/Ice Sensor 090 or 094S1b = Zone 2 Snow/Ice Sensor 090 or 094S2a = Zone 1 Snow Sensor 095S2b = Zone 2 Snow Sensor 095
S3a = Zone 1 Slab Sensor 072 or 073S3b = Zone 2 Slab Sensor 072 or 073S4 = Outdoor Sensor 070S5 = 423 Boiler Supply Sensor 082S6 = 444 Mix Supply Sensor 082V1 = 3-Way Mixing Valve 710 through 714X1 = Transformer 009
Legend
S4S5
S6
B2
B1
L N
X1
M1 V1
© 2016 tekmar 670_A - 10/1619 of 20
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up
20Mod Boiler 19
WiFi Snow Melting Control 670Boiler & Mixing / Electric
Power 115 V (ac) ±10%, 60 Hz, 20 VARelays 230 V (ac) 5 A 1/3 hpVar. Pump 230 V (ac) 2.4 A
1084-01Designed and assembled in Canada
Date
Cod
eH
2055
A
1 kΩ max 1 kΩ max
Opn3
Var
2
–Mix V/mA1
+Pwr4
MixCls5
Blu8
Yel9
Brn/10
SlabMan
11
MeltC
12Blk/7
ComRed6
Boiler 121
Stage 1Boiler 1Stage 2
HeatRelay
SystemPump–
22
+
23 24 25Do Not Apply Power
Mix15
SupCom16
Boil17
Out18
Com14
tN413 282726
Power29
L
30
N
For product literature:Pour la documentation du produit:Para la literatura del producto:tekmarControls.com
Disconnect all power before opening.WARNING
Coupez l'alimentation avant l'ouverture.ATTENTION
Desconecte la electricidad antes de abrir.ADVERTENCIA
Signal wiring must be rated at least 300 V.Le câblage du signal doit être d'une capacité d'au moins 300 V.Cableado de señal debe tener unacalificación mínima de 300 V.
Contains WiFi transceiver:FCC ID: Z64-CC3100M0DR1, IC: 4511-CC3100M0DR1Meets Class B: FCC Part 15B, ICES-003
Manual Melt
Time Left- - : - - hrs
Outdoor32 °F
Settings Status
System is Melting
Stop
10:30 AM
Warming Up50 51 52 53
Stage1/ Stage 2/ Boil Enbl Setp Enbl
75 76 77 78
Demand DemandDHW Setpoint
54 55
DHW Primary
10 Amax79 80 81 82
NPump NPump
tN4Made in Canada
8 VA 1 VA
Boil Sens Sup / Ret
H7010A
Off / DHW SensorOff / tekmar StagerBoilers On-Off / ModOff / Rotation
Meets Class B: CanadianICES & FCC Part 15
PoweredOutputs24 V (ac)
Universal Reset Module 423
Item
Menu
tektra 1006-01
Demands: 20 - 260 V (ac)Relay Rating: 115 V (ac) 5 A
71 72 73 74DHW 24 V (ac)
/
57 58 59 60 6156
C
C
tN4Mod2 (dc)Mod1 (dc)
6564
C3C1+ –
C
+ – tN4
62 63
C2 tN4 tN4
66 67
DHW ComBoiler
68 69
Boil Com
70
Out
Do not apply power
Test
1 2 3
Vlv R
No Power
Mixing Expansion Module 444Variable Speed / Floating Action / Modulating
Made in CanadaSignal wiring
must be rated atleast 300V / 90°CCu
t for
mA
outp
ut
5R
6R
41tN4
7Mod
+
8Com
9Mix
Power ClsOpnSysPmp
2C
3R
No Power
Date
Cod
e
1
tektra 1019-01
1
Power Manager 346
For product literature:www.tekmarcontrols.com
Boiler Bus 0 Demand Power
Aux Pump 1
Aux Pump 2
Aux Pump 3
tN4
Bus 1 Demand
Bus 2 Demand
Bus 3 Demand
Meets Class B: CanadianICES & FCC Part 15
Caution! Disconnect AllPower before Opening
24 V (ac) Fuse: T2.5 A 250 V
H701
1A
Relay Power27 28
NLAux Pump 229 30
NPmpAux Pump 331 32
NPmp
For product instructions, see brochureInput Power: 115 V (ac) ±10% 60 Hz, 12 AAll Loads Using Input Power: 11.5 ARelay Ratings: 115 V (ac) 5 ARelay Power: 115 V (ac) ±10% 60 Hz, 10 ADemands: 20 to 260 V (ac) 2 VA
Supply wires 90°C/105°CSee manual
Boil Bus 0
16 17Demand
Bus 3 Bus 2
18Dem DemDem
19
Bus 1
20 21Demand
227
tN4
5 6
tN4 C C
2Boil 0
11
tN4
9 102C C
15
tN4
13 143
ComAuxPmp1
4
RR R R
3
AuxPmp2
8
AuxPmp3
12Limited power available, see wiring brochure
Room Occ
Room UnOcc
0Boil
1
2
3 1
3
11
9
7
5
12
10
8
6
4
2Sch
edul
eM
embe
r
Input Power23 24
NLAux Pump 125 26
NPmp
RC
Com
Open
Close
A670-8 Electrical670 Application SettingsSetting Name Value
Application Mode PWM Zone
Outdoor Sensor tekmarNet
Boiler Type Control
S1a
S1b
P1
P2
L
L
N
N
670_A - 10/16 20 of 20 © 2016 tekmar
Tel: (250) 545-7749 • Fax: (250) 984-0815 tekmarControls.com
All specifications are subject to change without notice
Specifications
The following are the recommended specifications for the WiFi Snow Melting Control 670.• The control shall communicate with the Internet Cloud to provide remote starting, stopping and monitoring through an Android
or Apple iOS mobile application or through a web browser.• The control shall have the ability to use a snow/ice sensor in order to automatically detect snow or ice and begin operation
of the system. The system shall continue to run until the sensor is dry or the control is manually stopped.• The control shall communicate with an Internet weather service to determine the local snow fall forecast and automatically
pre-heat the slab for an adjustable timed duration.• The control shall have the ability to be manually started with an adjustable running time that counts down and automatically
stops the system.• The control shall not operate the system to provide heat to the snow melting zones when it enters into either a Warm Weather
Shut Down (WWSD) or a Cold Weather Cut Off (CWCO) mode.• The system water temperature shall be based on the outdoor temperature and feedback from sensors located in the snow
melting slabs.• The control shall have the option to mix the supply water temperature using a mixing valve with a floating action, 0-10 V (dc)
or a 4-20 mA actuator motor, or using a variable-speed injection mixing pump.• The control shall have an adjustable minimum return water temperature setting to help prevent condensation of flue gases
and subsequent corrosion and blockage of the boiler’s heat exchanger and chimney.• The control shall have the ability to limit the amount of cool water being returned to the boiler through the mixing device in
order to prevent low boiler operating temperatures and flue gas condensation.• The control shall have the ability to directly control the supply temperature of a modulating boiler, a one or two-stage boiler,
or to send a boiler enable signal to another boiler operating control to allow for a staging control to be connected.• The control shall have the option of an automatic differential calculation for the operation of one or two boiler stages in order
to prevent short cycling.• The control shall use proportional, integral and derivative (PID) logic when modulating or staging boiler stages.• The control shall have the option to limit the heat up rate of the slab to help prevent cracking the concrete.• The control shall have two separate lockable access levels to limit the number of adjustments available to various users.• The control shall have a manual override that allows each output to be manually turned on or off.• The control shall continuously monitor its temperature sensors and provide an error message upon a control or sensor failure.• The control shall record and display boiler and pump running hours and minimum and maximum temperatures depending
on the access level that has been selected.• During extended periods of inactivity, the pumps and valves that are operated by the control shall be periodically exercised
to prevent seizure during long idle periods.
This Application Brochure is not intended to provide full installation instructions and safety information. In order to avoid property damage or injury, please refer to the complete installation manual and product safety information provided with the product.