- Application A 260-1s3.supplyhouse.com/product_files/260-wiring guide.pdf · The designer must...
Transcript of - Application A 260-1s3.supplyhouse.com/product_files/260-wiring guide.pdf · The designer must...
1 of 8
- ApplicationBoiler Control 260
A 260-1
03/09
Copyright ©2009 A 260-1 03/09
Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance withcode requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safetyand limit devices must be added.
P1
M MMT3 T2 T1
OutdoorSensor (S2) 070
BoilerSensor
(S1) 082
Z1Z2Z3
Class 2Transformer
120 V (ac) 24 V (ac)
260Mechanical
NL
Zone ValveMotor EndSwitches
U1
S1
S2Boiler
260
1 2 4 6 8 10 11Boiler
Demand L N
3Power
5 9Boil
Do not apply power
13 14 15 16 17 18Com
Sw
UnO ComBoil Out
12IndrDHW
Demand
7
P1 N
DHW
Pmp/VlvBoiler
10A 10A10A
24 V (ac)
120 V (ac)
Class 2Transformer
CR
P1
Z1
Z2
Z3
Electrical
P1 = Boiler PumpS1 = Boiler Sensor 082S2 = Outdoor Sensor 070T1, ..., T3 = ThermostatsU1 = tekmar Timer 033 (optional)Z1, ..., Z3 = Zone Valve Motor End Switches
OffInstaller
Advanced DHW during UnOcc
DHW Pump Off
DHW PriorityDHW Valve
= Not Used
= Required
= Optional
Product design, software and literature are Copyright © 2009 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
tekmar Control Systems Ltd., Canadatekmar Control Systems, Inc., U.S.A.Head Office: 5100 Silver Star RoadVernon, B.C. Canada V1B 3K4Tel. (250) 545-7749 Fax. (250) 545-0650Web Site: www.tekmarcontrols.com
Control Systems
System Operation
All specifications are subject to change without notice.2 of 8
A 260-1 03/09
Printed in Canada. A 260-1 03/09.
The Boiler Control 260 provides partial or full outdoor reset to three (or more) boiler zones. The boiler is operated at the temperaturerequired in order to satisfy the load.
Heat Source Details The heat source can be either a high mass or low mass non-condensing or low temperature boiler.
Piping Details Thermostat controlled zone valves are piped into the boiler loop. The boiler pump (P1) provides circulation through thesezones when heat is required.
Boiler Demand When heat is required in the boiler zones, the zone valve end switches send a Boiler Demand to the 260. The 260 turnson the boiler pump (P1). The boiler supply water temperature is based on the Characterized Heating Curve settings. The boiler is firedto satisfy the required boiler supply water temperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply watertemperature to at least the BOIL MIN setting.
All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260.
3 of 8
- ApplicationBoiler Control 260
A 260-2
03/09
Copyright ©2009 A 260-2 03/09
Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance withcode requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safetyand limit devices must be added.
Mechanical
DHWTank
MM MM
OutdoorSensor (S2) 070
P1BoilerSensor
(S1) 082
A2
A1
T3 T2 T1
Z1Z2Z3
Class 2Transformer
120 V (ac) 24 V (ac)
260
V1
V1
Electrical
A1 = DHW AquastatA2 = DHW High Limit AquastatP1 = Boiler PumpS1 = Boiler Sensor 082S2 = Outdoor Sensor 070T1, ..., T3 = ThermostatsU1 = tekmar Timer 033 (optional)V1 = DHW ValveZ1, ..., Z3 = Zone Valve Motor End Switches
Zone ValveMotor EndSwitches
Boiler
S1
S2U1
24 V (ac)
120 V (ac)
Class 2Transformer
NL
CR
P1
A1
A2
Z1
Z2
Z3
260
1 2 4 6 8 10 11Boiler
Demand L N
3Power
5 9Boil
Do not apply power
13 14 15 16 17 18Com
SwUnO ComBoil Out
12IndrDHW
Demand
7
P1 NDHW
Pmp/VlvBoiler
10A 10A10A
M= Required
= Optional
= Not Used
DHW Pump OffOffInstaller
Advanced DHW during UnOcc
DHW PriorityDHW Valve
Product design, software and literature are Copyright © 2009 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
tekmar Control Systems Ltd., Canadatekmar Control Systems, Inc., U.S.A.Head Office: 5100 Silver Star RoadVernon, B.C. Canada V1B 3K4Tel. (250) 545-7749 Fax. (250) 545-0650Web Site: www.tekmarcontrols.com
Control Systems
System Operation
All specifications are subject to change without notice.4 of 8
A 260-2 03/09
Printed in Canada. A 260-2 03/09.
The Boiler Control 260 provides partial outdoor reset to three (or more) boiler zones. The 260 also controls the supply of heat to anindirect fired Domestic Hot Water (DHW) tank. The boiler is operated at the temperature required in order to satisfy the loads.
Heat Source Details The heat source can be either a high mass or low mass non-condensing boiler.
Piping Details Thermostat controlled zone valves are piped into the boiler loop. The boiler pump (P1) provides circulation through thesezones when heat is required. Heat is supplied to the DHW tank through a DHW valve (V1).
DHW Demand When the DHW aquastat (A1) calls for heat, the 260 turns on the boiler pump (P1), opens the DHW valve (V1), andraises the boiler water temperature to at least 180°F (82°C).
Boiler Demand When heat is required in the boiler zones, the zone valve end switches send a Boiler Demand to the 260. The 260 turnson the boiler pump (P1). The boiler supply water temperature is based on the Characterized Heating Curve settings. The boiler is firedto satisfy the required boiler supply water temperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply watertemperature to at least the BOIL MIN setting.
All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260.
5 of 8
- ApplicationBoiler Control 260
A 260-3
03/09
Copyright ©2009 A 260-3 03/09
Mechanical
M MM
OutdoorSensor (S2) 070
DHWTank
Class 2Transformer
120 V (ac) 24 V (ac)
BoilerSensor
(S1) 082P1
P2
A2
A1
T1T2T3
Z1Z2Z3
260
Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance withcode requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safetyand limit devices must be added.
Electrical
A1 = DHW AquastatA2 = DHW High Limit AquastatP1 = Boiler PumpP2 = DHW PumpS1 = Boiler Sensor 082S2 = Outdoor Sensor 070T1, ..., T3 = ThermostatsU1 = tekmar Timer 033 (optional)Z1, ..., Z3 = Zone Valve Motor End Switches
Zone ValveMotor EndSwitches
Boiler
260
1 2 4 6 8 10 11Boiler
Demand L N
3Power
5 9Boil
Do not apply power
13 14 15 16 17 18Com
SwUnO ComBoil Out
12IndrDHW
Demand
7
P1 NDHW
Pmp/VlvBoiler
10A 10A10A
U1
S1
S2
24 V (ac)
120 V (ac)
Class 2Transformer
NL
CR
P2
P1A2
Z1
Z2
Z3
A1
= Required
= Optional
= Not Used
OffInstaller
Advanced DHW during UnOcc
DHW Pump Off
DHW PriorityDHW Valve
tekmar Control Systems Ltd., Canadatekmar Control Systems, Inc., U.S.A.Head Office: 5100 Silver Star RoadVernon, B.C. Canada V1B 3K4Tel. (250) 545-7749 Fax. (250) 545-0650Web Site: www.tekmarcontrols.com
Control Systems
System Operation
All specifications are subject to change without notice.6 of 8
A 260-3 03/09
Product design, software and literature are Copyright © 2009 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc. Printed in Canada. A 260-3 03/09.
The Boiler Control 260 provides partial or full reset to three (or more) boiler zones. The 260 also controls the supply of heat to an indirectfired Domestic Hot Water (DHW) tank. The boiler is operated at the temperature required in order to satisfy the loads.
Heat Source Details The heat source can be either a high mass or low mass non-condensing or low temperature boiler. If using a lowtemperature boiler, refer to section C3 of the Data Brochure for additional information.
Piping Details Thermostat controlled zone valves are piped into the boiler loop. The boiler pump (P1) provides circulation through thesezones when heat is required. Heat is supplied to the DHW tank through a DHW pump (P2).
DHW Demand When the DHW aquastat (A1) calls for heat, the 260 turns on the DHW pump (P2) and raises the boiler water tempera-ture to at least 180°F (82°C). The control can provide DHW priority (refer to section C2 of the Data Brochure) by turning off the boilerpump (P1). Once the DHW demand is removed, the 260 performs a DHW Post Purge and possibly a Mixing Purge.
Boiler Demand When heat is required in the boiler zones, the zone valve end switches send a Boiler Demand to the 260. The 260 turnson the boiler pump (P1). The boiler supply water temperature is based on the Characterized Heating Curve settings. The boiler is firedto satisfy the required boiler supply water temperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply watertemperature to at least the BOIL MIN setting.
All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260.
7 of 8
- ApplicationBoiler Control 260
A 260-4
03/09
Copyright ©2009 A 260-4 03/09
Note: This is only a concept drawing. The designer must determine whether this application will work in his system and must ensure compliance withcode requirements. Necessary auxiliary equipment, isolation relays (for loads greater than the specified tekmar internal relay ratings), and other safetyand limit devices must be added.
Mechanical
BoilerSensor
(S1) 082
OutdoorSensor (S2) 070
DHWTank
A1
A2
P1Z2Z1 Z3
R1 R2 R3
T1 T2 T3
Class 2Transformer
120 V (ac) 24 V (ac)
260
Electrical
A1 = DHW AquastatA2 = DHW High Limit AquastatP1 = DHW PumpR1, ..., R3 = Relay 003S1 = Boiler Sensor 082S2 = Outdoor Sensor 070T1, ..., T3 = ThermostatsU1 = tekmar Timer 033 (optional)Z1, ..., Z3 = Zone Pumps
Boiler
260
1 2 4 6 8 10 11Boiler
Demand L N
3Power
5 9Boil
Do not apply power
13 14 15 16 17 18Com
SwUnO ComBoil Out
12IndrDHW
Demand
7
P1 NDHW
Pmp/VlvBoiler
10A 10A10A
24 V (ac)
120 V (ac)
Class 2Transformer
A2
P1
A1
= Required
= Optional
= Not Used
NL
U1
S1
S2
R1
R2
R3
Z1
Z2
Z3
T3
T2
T1
CR
34
65
7
218
34
65
7
218
34
65
7
218
Return
OffInstaller
Advanced DHW during UnOcc
DHW Pump Off
DHW PriorityDHW Valve
tekmar Control Systems Ltd., Canadatekmar Control Systems, Inc., U.S.A.Head Office: 5100 Silver Star RoadVernon, B.C. Canada V1B 3K4Tel. (250) 545-7749 Fax. (250) 545-0650Web Site: www.tekmarcontrols.com
Control Systems
System Operation
All specifications are subject to change without notice.8 of 8
A 260-4 03/09
Product design, software and literature are Copyright © 2009 by:tekmar Control Systems Ltd. and tekmar Control Systems, Inc. Printed in Canada. A 260-4 03/09.
The Boiler Control 260 provides partial or full reset to three (or more) boiler zones. The 260 also controls the supply of heat to an indirectfired Domestic Hot Water (DHW) tank. The boiler is operated at the required temperature in order to satisfy the loads.
Heat Source Details The heat source can be either a high mass or low mass non-condensing or low temperature boiler. If using a lowtemperature boiler, refer to section C3 of the Data Brochure for additional information.
Piping Details Thermostat controlled zone pumps are piped into the boiler loop. Heat is supplied to the DHW tank through a DHWpump (P1).
DHW Demand When the DHW aquastat (A1) calls for heat, the 260 turns on the DHW pump (P1) and raises the boiler water tempera-ture to at least 180°F (82°C). The control can provide DHW priority (refer to section C2 of the Data Brochure) by turning off the Boil P1contact and not allowing any of the boiler zones to operate. Once the DHW demand is removed, the 260 performs a DHW Post Purgeand possibly a Mixing Purge.
Boiler Demand When heat is required in the boiler zones, the zone pump relays send a Boiler Demand to the 260. The boiler supplywater temperature is based on the Characterized Heating Curve settings. The boiler is fired to satisfy the required boiler supply watertemperature. Whenever the boiler is fired, the 260 aims to increase the boiler supply water temperature to at least the BOIL MIN setting.
All control functions and specifications are listed in the Product Catalog I 000 and Data Brochure D 260.