Appliance and Controller Electrical Installation Guide.
MHG Heating Ltd
Unit 4 Epsom Downs Metro Centre Waterfield Tadworth
Surrey KT20 5LR
Telephone 0845 6448802
Fax 0845 6448803 Email [email protected]
www.mhgheating.co.uk 01/01/12
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
2
Content
Appliances Page
ProCon 16 – 77 Wall Mounted Condensing Boilers (LMU64) 3
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager (LMU64) RVA47 Controlled to 01/01/2011
5
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager (LMU64) RVS43 Controlled from 01/01/2011
6
ProCon HT 150 -225 Floor Standing Condensing Boilers (LMU64) RVA47 Controlled to 01/01/2011
8
ProCon HT 150 -225 Floor Standing Condensing Boilers (LMU64) RVS43 Controlled from 01/01/2011
9
Boiler Controller Mounted Options
AGU2.511 BMS Run & Fault Output & 0-10V or 0-20mA Input Clip 11
AGU2.500 Heating Zone 2 Pump & Mixing Valve Clip 13
OCI420 LPB Cascade & System Controller Communication Clip 14
Cascade, System & Room Controls
RVA47 Cascade Manager Without Optional Housing 15
RVA47 Cascade Manager With Optional Housing 16
RVA63 Boiler and Zone Controller Without Optional Housing 18
RVA63 Boiler and Zone Controller With Optional Housing 20
RVA46 Zone Controller Without Optional Housing 23
RVA46 Zone Controller With Optional Housing 24
RVS63 Cascade and Zone Control Manager With/Without Housing 25
QAA73 Single Boiler Opentherm Room Unit 27
QAA70/50/10 PPS Cascade or System Controller Room Unit 28
QAA55 BSB Cascade or System Controller Room Unit 29
QAA75 BSB Cascade or System Controller Room Unit 30
QAA78 Wireless Cascade or System Controller Room Unit 31
Please note that this document is intended as a quick reference guide. Further detailed guidance should be sought from the respective boiler/controller technical manuals.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
3
ProCon 16 – 77 Wall Mounted Condensing Boilers. Boiler Wiring Terminals
Boiler Controller Mounted Terminals
Terminal Designation
Tag Terminal
#s Voltage
Screened Cable
(Earthed Screening) Description/Operation/Function
RU 1 & 2 (Not Polarity Sensitive)
< 25V Yes QAA73 Opentherm Room Unit or Link to enable second heating zone time switch.
(AGU2.500 Communication Clip required to control second heating zone pump/valve.) RT 3 & 4
(Not Polarity Sensitive) < 25V Yes Heating Volt Free Enable. (Via Time Switch/Room Thermostat/BMS)
AT 5 & 6 (Not Polarity Sensitive) < 25V Yes Outside Air Sensor. (QAC34)
(Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected)
BW 7 & 8 (Not Polarity Sensitive) < 25V Yes
Hot Water Sensor (QAZ36) or Volt Free Enable.
(Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used)
BW/K3 10 Perm Live 11 Neutral
12 Switched Live 230V -
Hot Water Charging Pump or 3 way Valve Output. (Max 1 Amp)
(Parameter alteration required if charging pump used with 16 & 31 and if 3 way valve used with 47 & 75.)
K2 13 Switched Live
14 Neutral 230V -
Models 16 & 31 External Heating Pump. (Max 1
Amp) Models 47 & 75 Internal Boiler Pump. (Max 1 Amp)
K1 16 Neutral
17 Switched Live 230V -
Models 16 & 31 Internal Boiler Pump. (Max 1 Amp) Models 47 & 75 External Heating Pump. (Max 1
Amp)
E 9, 15 &
18 - - Common Permanent Earth
N 19 230V - Permanent Neutral L 20 230V - Permanent Live (Max 5 Amp)
X10-03 - <25V Yes Safety Interlock Volt Free Enable (For use with ventilation interlocks/gas pressure switch etc.)
For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13/14 for additional guidance.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
4
Generic Single Boiler Hydraulic Configuration
For BMS Run and Fault indication terminal allocation refer to the section titled,
Boiler Controller Mounted Options.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
5
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager. RVA47 (Grey) Controlled. Produced to 01/01/2012
Additional Wiring Terminals (This terminal rail is in addition to the standard rail.)
Terminal Designation
Tag Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
BW 230V - Hot Water Charging Pump Output. (Max 2 Amp) HK / ZB 230V - Heating Circuit Pump Output. (Max 2 Amp)
H1 < 25V Yes Enabling Input
Volt Free Enable or 0-10Volt or Operation Changeover (M = Ground & H1 = Positive)
RL < 25V Yes Return Sensor (QAD21) (M = Ground & B70/B4 Positive)
VL < 25V Yes Flow Sensor (QAD21) (M = Ground & B10 Positive)
BW < 25V Yes Hot Water Sensor (QAZ21) or Volt Free Enable.
(Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used)
(M = Ground & B3 Positive)
AF < 25V Yes Outside Air Sensor. (QAC31/32) (620Ω Substitute Resistor = -10C)
(Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected)
(M = Ground & B9 Positive)
RU < 25V Yes Room Unit QAA70/50/10 (M = Ground & A6 Positive)
LPB < 25V Yes LPB Cascade Communication. (Loom Mounted Plug.) (MB = Ground & DB = Data Bus)
Each boiler within the cascade including the master will have an OCI420 Communication Clip fitted.
The LPB communication wiring must be wired (X41) between each OCI420
Communication Clip in parallel.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
6
ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager. RVS43 Controlled. Produced from 01/01/2012
Additional Wiring Terminals Located on the RVS43 Controller.
Tag Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
L E N 230V - Permanent 230 Volt Power Supply From the
LMU X1:02. P 230V - Not Used in this configuration.
Q 230V - Safety Interlock
(SK1 & SK2) R 230V - HWS Pump or Valve Output 230 Volts Max 1 Amp (Q3) S 230V - Heating Circuit Pump Output 230 Volt Max 1 Amp (Q2)
T 230V - Heating Circuit Mixing Valve Output
(Y1 Valve Open. Y2 Valve Close) U 230V - Multifunctional Relay Output (QX1)
X30 < 25V Ribbon Display Panel
a < 25V Yes LPB Cascade Communication
For connection to OCI clips in master and cascade boilers. DB Data MB Ground
b < 25V Yes BSB Data Communication
b < 25V Yes QAA75 Room Unit Communication
CL+ Data CL- Ground G+ 12 Volt Power Supply f < 25V Yes Not Used in this configuration.
h < 25V Yes Hot Water Sensor or Volt Free Enable QAZ36 Parameter change required if using volt free enabling.
k < 25V Yes Outside Air Sensor QAD34
n < 25V Yes Volt Free Enable or 0-10 Volt Drive input
H1 +, M Ground p < 25V Yes Heating Circuit 1 Flow Senor. (Only used when a mixing valve is applied.) n < 25V Yes System Flow Senor QAZ36 n < 25V Yes System Return Sensor QAZ36
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
7
Generic Multiple Boiler Hydraulic Configuration
For BMS Run and Fault indication terminal allocation refer to the section
titled, Boiler Controller Mounted Options.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
8
ProCon HT 150-225 Floor Standing Condensing Boilers.
RVA47 (Grey) Controlled. (Produced to 01/01/2011)
Boiler Wiring Terminals
External Flow and return sensors (QAD21) are required for Cascade Manager Units only. The sensors must be wired to the terminal detailed below.
These terminals are located on the top left of the boiler frame when viewed from the front.
(These terminals are pre-wired on Standalone FS units.)
Module Controller Mounted Safety Interlock Terminals (X10:03)(Low Voltage<25V) If required each module can be connected to an external safety device. A relay must be used to ensure separation of the voltages generated by each module controller. (X10:03)
Terminal Designation
Tag Terminal
#s Voltage
Screened Cable
(Earthed Screening) Description/Operation/Function
RU A6 & MD (Not Polarity Sensitive)
< 25V Yes QAA70/50/10 PPS Room Unit
H1 H1 & M (Polarity Sensitive) <25V Yes
0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS
BW B3 & M (Not Polarity Sensitive) < 25V Yes
Hot Water Sensor (QAZ21) or Volt Free Enable. (Via Time Switch/Calorifier Thermostat/BMS)
(Parameter alteration required if Volt free enable used)
AF B9 & M (Not Polarity Sensitive) < 25V Yes Outside Air Sensor. (QAC31/32) or (620Ω Substitute Resistor = -10C)
(Mounted on North Facing Wall)(Parameter alteration required if outside air sensor not connected)
BUS DB & MB (Polarity Sensitive) < 25V Yes Boiler Communication to Slave Boilers.
(LPB DB Data & MB Ground)
BW N Neutral
Q3 Switched Live 230V - Hot Water Charging Pump or 3 way Valve Output. (Max 2 Amp)
HK 11 Switched Live
N Neutral 230V - Heating Pump Output (Max 2 Amp)
230V N Perm Neutral
L Perm Live 230V - Permanent 240 Volt Supply (Max 10 Amp)
VL B10 & M < 25V Yes System Flow Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor)
RL M & B70 < 25V Yes System Return Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor)
X10-03 - <25V Yes Safety Interlock Volt Free Enable (For use with ventilation interlocks/gas pressure switch etc.)
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
9
ProCon HT 150-225 Floor Standing Condensing Boilers.
RVS43 Controlled. (Produced from 01/01/2011)
Boiler Wiring Terminals
Module Controller Mounted Safety Interlock Terminals (X10:03)(Low Voltage<25V) If required each module can be connected to an external safety device. A relay must be used to ensure separation of the voltages generated by each module controller. (X10:03)
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
10
Generic Single HT Boiler Hydraulic Configuration
Generic Multiple HT Boiler Hydraulic Configuration (Indicting the location of the system mounted Flow and Return Sensors)
For Module BMS Run and Fault indication terminal allocation refer to the section titled,
Boiler Controller Mounted Option.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
11
Boiler Controller Mounted Options. AGU2.511 BMS Run & Fault 230V Outputs & 0-10Volt/0-20mA Input Clip.
Terminal Designation
Tag Terminal
#s Voltage Description/Operation/Function
Switched Output Power Input
X52-01
1 Live 2 Neutral
230V (Max)
Power Supply from X01-02 for switched live outputs. Power Supply from BMS can replace power supply
from X01-02 (<230V/0.5Amp)
Output 1R X52-02
1 Live 2 Neutral
230V (Max)
Programmable Output Available Options
Boiler Fault Output. Or Boiler Operating Output or SSOV.(Safety Shut Off Valve) (Max 1 Amp)
(Parameter amendment required)
Output 2R X52-03
1 Live 2 Neutral
230V (Max)
Programmable Output Available Options
Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp)
(Parameter amendment required)
Output 3R X52-03 3 Live
230V (Max)
Programmable Output Available Options
Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp)
(Parameter amendment required)
Control Input
X51-01
1 Control Input
2 Ground
0-10V Or
0-20mA
Programmable Control Input 0-10 Volt or 0-20mA
Flow Temperature or % Power Control (Parameter amendment required)
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
12
Boiler Controller Mounted Options. AGU2.500 Heating Zone 2 Pump/Mixing Valve/Sensor Clip.
Terminal Designation
Tag Terminal
#s Voltage Description/Operation/Function
Switched Output Power Input
X52-01
1 Live 2 Neutral
230V
Power Supply from X01-02 for switched live outputs.
Pump Output X52-02
1 Live 2 Neutral
230V
Heating Zone 2 Pump Outputs (Max 1 Amp)
Mixing Valve
X52-03
1 Close 2 Neutral 3 Open
230V
Heating Zone 2 Mixing Valve Outputs (Valve control is possible only when a zone flow sensor is connected)
(Max 1 Amp)
Flow Sensor Input
X51-01
1 & 2 (Not Polarity Sensitive)
<25V Heating Zone 2 Flow Sensor Inputs. (QAD36)
*H552 must be set to 66 to ensure correct operation of mixing zone clip.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
13
Generic Single Boiler (AGU2.500 Zoned) Hydraulic Configuration
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
14
Boiler Controller Mounted Options. OCI420 LPB Cascade Communication Clip. For use when control is provided via a RVA47 Cascade Manager or RVA63 Controller.
Terminal Designation
Tag Terminal #s Screened Cable Description/Operation/Function
LPB X41-01
1, DB LPB Data 2, MB LPB Ground
(Polarity Sensitive)
Yes LPB Control Communication From RVA47
Cascade Manager or RVA63 Boiler and zone controller.
(Parameter amendment required)
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
15
RVA47 Cascade Manager. Manager Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation
Tag Terminal
#s Voltage
Screened Cable
(Earthed Screening) Description/Operation/Function
H1 6 (Polarity Sensitive) <25V Yes
0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS
(M terminal used to create circuit)
B70/B4
5 (Not Polarity Sensitive) <25V Yes System Return Sensor (QAD21)
(To be positioned on boiler side of system Low Loss Header)
B3 4 (Not Polarity Sensitive) <25V Yes
Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS
(Parameter alteration required if Volt Free Enable Used)
M M <25V Yes Ground Connection for all Sensors/Inputs
B10 2 (Not Polarity Sensitive) <25V Yes System Flow Sensor (QAD21)
(To be positioned on system side of system Low Loss Header) B9 1
(Not Polarity Sensitive) <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)
MD M (Not Polarity Sensitive) <25V Yes QAA70/50/10 Room Unit (PPS Ground)
A6 - (Not Polarity Sensitive) <25V Yes QAA70/50/10 Room Unit (PPS Data)
MB M (Polarity Sensitive) <25V Yes Boiler Communication (LPB Ground connected in parallel to
boiler mounted OCI420 Clips)
DB - (Polarity Sensitive) <25V Yes Boiler Communication (LPB Data connected in parallel to
boiler mounted OCI420 Clips))
Q3 3 230V - Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)
Q1 2 230V - Heating Pump Output (Max 2 Amp)
F1 F 230V - Power Input for Heating and Hot Water Pump
Outputs (To be linked to Live Input)
L L 230V - Permanent Live (Max 6 Amp) N N 230V - Permanent Neutral
For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
16
RVA47 Cascade Manager. Manager Wiring Terminals.(Housing) (Housing designed for use with additional RVA46 Zone controller)
(RVA 46 Zone Controller wiring Information detailed later in document.)
Terminal Designation
Tag Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
DB <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clips))
MB <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clips)
A6 <25V Yes QAA70/50/10 Room Unit (PPS Data) MD <25V Yes QAA70/50/10 Room Unit (PPS Ground)
B9 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)
M <25V Yes Ground Connection for all Sensors/Inputs
B10 <25V Yes System Flow Sensor (QAD21) (To be positioned on system side of system Low Loss Header)
B3 <25V Yes Hot Water Sensor (QAZ21)/Volt Free Enable via
Calorifier Thermostat/BMS (Parameter alteration required if Volt Free Enable Used)
B70/B4
<25V Yes System Return Sensor (QAD21) (To be positioned on boiler side of system Low Loss Header)
H1 <25V Yes 0-10 Volt Input via BMS/Volt Free Enable via Room
Thermostat/BMS
Q1 230V - Heating Pump Output (Max 2 Amp) Q3 230V - Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp) N 230V - Permanent Neutral PE - - Permanent Earth L 230V - Permanent Live (Max 6 Amp)
(All ‘M’ Terminals are Internally Linked)
For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
17
Generic Multiple Boiler RVA47 Controlled Hydraulic Configuration
Heating Zone
RVA47 Cascade Controller
Outside Air Sensor QAC32
QAA70/50/10
Zone Pump
Flow Sensor QAD21
Hot Water Primary Pump
Hot Water Sensor QAZ21
Return Sensor QAD21
Up to 12 ProCon Boilers In Cascade
LPB Communication to each boiler via an OCI clip module.
Component Control Capability of RVA47
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
18
RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation (Low Voltage Terminals)
Tag Terminal
#s Voltage
Screened Cable
(Earthed Screening) Description/Operation/Function
MD - (Not Polarity Sensitive) <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Ground)
A7 - (Not Polarity Sensitive) <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Data)
B12 3 (Not Polarity Sensitive) <25V Yes Zone 2 Flow Sensor (QAD21/26)
(To be positioned on Zone side of 3 way mixing valve) M M
(Not Polarity Sensitive) <25V Yes Ground Connection for all Sensors/Inputs
B8 1 (Not Polarity Sensitive) <25V Yes Flue Gas Sensor (Not Used)
B31/H2/ B41
4 (Polarity Sensitive) <25V Yes Volt Free Enable via Room Thermostat/BMS
B1 3 (Not Polarity Sensitive) <25V Yes Zone 1 Flow Sensor (QAD21/26)
(To be positioned on Zone side of 3 way mixing valve)
H1 6 (Polarity Sensitive) <25V Yes
0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS
B2 5 (Not Polarity Sensitive) <25V Yes Boiler Sensor (Not Used)
B3 4 (Not Polarity Sensitive) <25V Yes
Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS
(Parameter alteration required if Volt Free Enable Used)
B9 1 (Not Polarity Sensitive) <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C)
(Mounted on North Facing Wall)
MD M (Not Polarity Sensitive) <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Ground)
A6 - (Not Polarity Sensitive) <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Data)
MB M (Polarity Sensitive) <25V Yes Boiler Communication (LPB Ground connected in parallel to
boiler mounted OCI420 Clip or RVA47 Manager)
DB - (Polarity Sensitive) <25V Yes Boiler Communication (LPB Data connected in parallel to
boiler mounted OCI420 Clip or RVA47 Manager) For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420
Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
19
RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation (230 Volt Terminals)
Tag Terminal
#s Voltage Description/Operation/Function
Y6 - 230V Zone 2 Mixing Valve Closing Output (Max 2 Amp) Y5 - 230V Zone 2 Mixing Valve Opening Output (Max 2 Amp)
F3 - 230V Power Input for Zone 2 Valve Outputs (To be linked to Live Input)
Q6 3 230V Zone 2 Pump Output (Max 2 Amp) Q2 2 230V Zone 1 Pump Output (Max 2 Amp)
F6 F 230V Power Input for Zone Pumps Output (To be linked to Live Input)
Y2 3 230V Zone 1 Mixing Valve Closing Output (Max 2 Amp) Y1 2 230V Zone 1 Mixing Valve Opening Output (Max 2 Amp)
F2 F 230V Power Input for Zone 1 Valve Outputs (To be linked to Live Input)
Q3/Y3
3 230V Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)
F1 F 230V Power Input for Hot Water Pump/Valve Output (To be linked to Live Input)
K5 4 230V Burner Enable Output Stage 2 (Not Used) F5 F 230V Power Input Burner Enable Stage 2 (Not Used) K4 2 230V Burner Enable Stage 1 (Not Used) F4 F 230V Power Input Burner Enable Stage 1 (Not Used) L L 230V Permanent Live (Max 6 Amp) N N 230V Permanent Neutral
For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
20
RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing)
Terminal Designation (Low Voltage Terminals)
Tag Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
DB <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager)
M <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager)
A6 <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Data) M <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Ground)
B9 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)
M <25V Yes Ground Connection for all Sensors/Inputs
B3 <25V Yes Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier
Thermostat/BMS (Parameter alteration required if Volt Free Enable Used)
B2 <25V Yes Boiler Sensor (Not Used)
H1 <25V Yes 0-10 Volt Input via BMS/Volt Free Enable via Room
Thermostat/BMS B7 - - Not Used with RVA63
B1 <25V Yes Zone 1 Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve)
B31/H2/ B41
<25V Yes Volt Free Enable via Room Thermostat/BMS
B8 <25V Yes Flue Gas Sensor (Not Used)
B12 <25V Yes Zone 2 Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve)
B4 - - Not Used with RVA63 M <25V Yes Ground Connection for all Sensors/Inputs M <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Ground) A7 <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Data)
(All ‘M’ Terminals are Internally Linked) For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420
Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
21
RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing)
Terminal Designation (230 Volt Terminals)
Tag Voltage Description/Operation/Function K6 - Not Used with RVA63 Y6 230V Zone 2 Mixing Valve Closing Output (Max 2 Amp) Y5 230V Zone 2 Mixing Valve Opening Output (Max 2 Amp) N 230V Permanent Neutral
Q6 230V Zone 2 Pump Output (Max 2 Amp) Q2 230V Zone 1 Pump Output (Max 2 Amp) N 230V Permanent Neutral Y2 230V Zone 1 Mixing Valve Closing Output (Max 2 Amp) Y1 230V Zone 1 Mixing Valve Opening Output (Max 2 Amp)
Q3/Y3
230V Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)
PE - Permanent Earth N 230V Permanent Neutral L1 230V Permanent Live (Max 6 Amp) K5 230V Burner Enable Output Stage 2 (Not Used) F5 230V Power Input Burner Enable Stage 2 (Not Used) K4 230V Burner Enable Stage 1 (Not Used)
For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420
Clip. Refer to Page 13 for additional guidance.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
22
Generic Single Boiler RVA63 Controlled Hydraulic Configuration
Heating Zone 1 Heating Zone 2
Component Control Capability of RVA63
RVA63 ControllerOutside Air Sensor QAC32
RVA47 Cascade Controller
QAA70/50/10 QAA70/50/10
Zone 1 PumpZone 2 Pump
Mixing Valve
Mixing Valve
Zone 1 Flow Sensor QAD26
Zone 2 Flow SensorQAD26
Single Boiler Control with OCI420 Clip
Hot Water Primary Pump
Hot Water Sensor QAZ21
LPB Communication to each boiler via OCI Clip Modules
LPB
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
23
RVA46 Zone Controller. Controller Wiring Terminals.(Rear of controller)(Housing available)
Terminal Designation
Tag Terminal
#s Voltage
Screened Cable
(Earthed Screening) Description/Operation/Function
H1 6 (Not Polarity Sensitive) <25V Yes Volt Free Enable via Room Thermostat/BMS
M M <25V Yes Ground Connection for all Sensors/Inputs
B1 2 (Not Polarity Sensitive) <25V Yes Zone Flow Sensor (QAD21)
(To be positioned on Zone side of 3 way mixing valve) B9 1
(Not Polarity Sensitive) <25V Yes Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall) (Not required if using RVA47 O/S Sensor)
MD M (Not Polarity Sensitive) <25V Yes Zone QAA70/50/10 Room Unit (PPS Ground)
A6 - (Not Polarity Sensitive) <25V Yes Zone QAA70/50/10 Room Unit (PPS Data)
MB M (Polarity Sensitive) <25V Yes RVA47/63 Communication (LPB Ground connected in parallel to
RVA47 Manager or RVA63 Zone controller)
DB - (Polarity Sensitive) <25V Yes RVA47/63 Communication (LPB Data connected in parallel to RVA47
Manager or RVA63 Zone controller)
Y2 3 230V - Mixing Valve Closing Output (Max 2 Amp) Y1 2 230V - Mixing Valve Opening Output (Max 2 Amp)
F2 1 230V - Power Input for Zone Valve Outputs (To be linked to Live Input)
Q2 2 230V - Zone Pump Output (Max 2 Amp)
F6 F 230V - Power Input for Zone Pump Output (To be linked to Live Input)
L L 230V - Permanent Live (Max 6 Amp) N N 230V - Permanent Neutral
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
24
RVA46 Zone Controller. Controller Wiring Terminals.(Housing) (Housing designed for use with primary RVA47 Cascade Manager.)
(RVA 47 Cascade Manager wiring Information detailed earlier in document.)
Terminal Designation
Tag Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
A6 <25V Yes Zone QAA70/50/10 Room Unit (PPS Data) MD <25V Yes Zone QAA70/50/10 Room Unit (PPS Ground)
B9 <25V Yes Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)(Not required if using RVA47 O/S Sensor)
M <25V Yes Ground Connection for all Sensors/Inputs
B1 <25V Yes Zone Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve)
H1 <25V Yes Volt Free Enable via Room Thermostat/BMS
Q2 240V - Zone Pump Output (Max 2 Amp) Y1 240V - Mixing Valve Opening Output (Max 2 Amp) Y2 240V - Mixing Valve Closing Output (Max 2 Amp)
(All ‘M’ Terminals are Internally Linked)
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
25
RVS63 Cascade and Zone Controller. Wiring Terminals Located on the RVS63 Controller. (Housing Available)
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
26
Terminal Legend. Tag Terminal #s Voltage Screened Cable
(Earthed Screening) Description/Operation/Function Z QX4, QX4, FX4, EX2 230 Volts NA Multifunctional 4 Relay Output U QX3, ‡, N 230 Volts NA Multifunctional 3 Relay Output U QX2, ‡, N 230 Volts NA Multifunctional 2 Relay Output
T Y6, ‡, N, Y5 230 Volts NA Heating Circuit 2 Mixing Valve
Output Y5 Open, Y6 Close S Q6, ‡, N 230 Volts NA Heating Circuit 2 Pump Output U QX1, ‡, N 230 Volts NA Multifunctional 1 Relay Output
T Y2, ‡, N Y1 230 Volts NA Heating Circuit 1 Mixing Valve
Output Y1 Open, Y2 Close S Q2, ‡, N 230 Volts NA Heating Circuit 1 Pump Output R Q3, ‡, N 230 Volts NA HWS Circuit Pump, Valve Output Q SK2, SK1 230 Volts NA External Safety Interlock Circuit P 4, S3, T2, T1, , L1 230 Volts NA **Burner Outputs Not Used** ~ S3 230 Volts NA **Burner Outputs Not Used** ~ L1 230 Volts NA Permanent Live Output ~ N, E, L 230 Volts NA Permanent Supply Input
Tag Terminal #s Voltage Screened Cable
(Earthed Screening) Description/Operation/Function n M, UX >24 Volts Yes 0-10 Volt Output **Not Used** n M, BX4 >24 Volts Yes Multifunctional 4 Sensor Input n M, BX3 >24 Volts Yes Multifunctional 3 Sensor Input
n M, H3 >24 Volts Yes Volt Free Enable or 0-10 Volt Input
Heating Zone 2
p M, B12 >24 Volts Yes Heating Circuit 2 Flow Sensor
QAD/Z36 n M, BX2 >24 Volts Yes Boiler Return Sensor QAD/Z36#
n M, BX1 >24 Volts Yes System Flow Sensor QAD/Z36#
p M, B1 >24 Volts Yes Heating Circuit 1 Flow Sensor
QAD/Z36
n M, H1 >24 Volts Yes Volt Free Enable or 0-10 Volt Input
Heating Zone 1 k M, B9 >24 Volts Yes Outside Air Sensor QAC34
h M, B3 >24 Volts Yes HWS Sensor QAZ36 or Volt Free
Enable f M, B2 >24 Volts Yes Boiler Sensor **Not Used** G+ QAA75 Power Supply 12 Volts
b CL-, CL+ >24 Volts Yes Heating Circuit 1 QAA55/75
-Ground, + Data
b CL-, CL+ >24 Volts Yes Heating Circuit 2 QAA55/75
-Ground, + Data b CL-, CL+ >24 Volts Yes BSB Comms to second RVS
a MB,DB >24 Volts Yes Boiler Communication Connection (OCI420 Clips mounted in Boilers
Wiring in Parallel) X30 ~ >24 Volts Yes Display Panel Connection X60 ~ >24 Volts Yes Connection for QAA78 Sender
# Parameter alterations may be required to configure these terminals.
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
27
QAA73 Single Boiler Opentherm Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation
Terminal #s
Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
1 & 2 (Not Polarity Sensitive) <25V Yes
Opentherm communication to Single Boiler Installation
3 & 4 - - Not Used 5 & 6 - - Not Used
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
28
QAA70/50/10 PPS Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation
Terminal #s
Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
D1 & D2 (Not Polarity Sensitive) <25V Yes
PPS communication to RVA47/46/63 Controlled Installation
D 3 & D4 (Not Polarity Sensitive) <25V Yes
Tamperproof QAW44 Remote Sensor or Volt Free Enable
D5 & D6 - - Not Used
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
29
QAA55 BSB Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation
Terminal #s
Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
1 <25V Yes BSB Data CL+ 2 <25V Yes BSB Ground CL-
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
30
QAA75 BSB Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals
Terminal Designation
Terminal #s
Voltage Screened
Cable (Earthed Screening)
Description/Operation/Function
1 <25V Yes BSB Data CL+ 2 <25V Yes BSB Ground CL- 3 <25V Yes Power Supply DC 12V G+
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12
31
QAA78 Wireless Cascade or System Controller Room Units Room Unit Mounting Plate and Receiver Module Mount the receiver module outside of the boiler/housing and connect the ribbon cable to X60 on the controller
Mount the cradle and insert the batteries into the rear of the QAA78 room unit.
**Follow synchronising instructions supplied with the QAA78 room unit.**
MHG Heating Ltd ©
MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk
01/01/12