Appliance and Controller Electrical Installation Guide.

MHG Heating Ltd

Unit 4 Epsom Downs Metro Centre Waterfield Tadworth

Surrey KT20 5LR

Telephone 0845 6448802

Fax 0845 6448803 Email [email protected]

www.mhgheating.co.uk 01/01/12

Page 2: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

2

Content

Appliances Page

ProCon 16 – 77 Wall Mounted Condensing Boilers (LMU64) 3

ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager (LMU64) RVA47 Controlled to 01/01/2011

5

ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager (LMU64) RVS43 Controlled from 01/01/2011

6

ProCon HT 150 -225 Floor Standing Condensing Boilers (LMU64) RVA47 Controlled to 01/01/2011

8

ProCon HT 150 -225 Floor Standing Condensing Boilers (LMU64) RVS43 Controlled from 01/01/2011

9

Boiler Controller Mounted Options

AGU2.511 BMS Run & Fault Output & 0-10V or 0-20mA Input Clip 11

AGU2.500 Heating Zone 2 Pump & Mixing Valve Clip 13

OCI420 LPB Cascade & System Controller Communication Clip 14

Cascade, System & Room Controls

RVA47 Cascade Manager Without Optional Housing 15

RVA47 Cascade Manager With Optional Housing 16

RVA63 Boiler and Zone Controller Without Optional Housing 18

RVA63 Boiler and Zone Controller With Optional Housing 20

RVA46 Zone Controller Without Optional Housing 23

RVA46 Zone Controller With Optional Housing 24

RVS63 Cascade and Zone Control Manager With/Without Housing 25

QAA73 Single Boiler Opentherm Room Unit 27

QAA70/50/10 PPS Cascade or System Controller Room Unit 28

QAA55 BSB Cascade or System Controller Room Unit 29

QAA75 BSB Cascade or System Controller Room Unit 30

QAA78 Wireless Cascade or System Controller Room Unit 31

Please note that this document is intended as a quick reference guide. Further detailed guidance should be sought from the respective boiler/controller technical manuals.

Page 3: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

3

ProCon 16 – 77 Wall Mounted Condensing Boilers. Boiler Wiring Terminals

Boiler Controller Mounted Terminals

Terminal Designation

Tag Terminal

#s Voltage

Screened Cable

(Earthed Screening) Description/Operation/Function

RU 1 & 2 (Not Polarity Sensitive)

< 25V Yes QAA73 Opentherm Room Unit or Link to enable second heating zone time switch.

(AGU2.500 Communication Clip required to control second heating zone pump/valve.) RT 3 & 4

(Not Polarity Sensitive) < 25V Yes Heating Volt Free Enable. (Via Time Switch/Room Thermostat/BMS)

AT 5 & 6 (Not Polarity Sensitive) < 25V Yes Outside Air Sensor. (QAC34)

(Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected)

BW 7 & 8 (Not Polarity Sensitive) < 25V Yes

Hot Water Sensor (QAZ36) or Volt Free Enable.

(Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used)

BW/K3 10 Perm Live 11 Neutral

12 Switched Live 230V -

Hot Water Charging Pump or 3 way Valve Output. (Max 1 Amp)

(Parameter alteration required if charging pump used with 16 & 31 and if 3 way valve used with 47 & 75.)

K2 13 Switched Live

14 Neutral 230V -

Models 16 & 31 External Heating Pump. (Max 1

Amp) Models 47 & 75 Internal Boiler Pump. (Max 1 Amp)

K1 16 Neutral

17 Switched Live 230V -

Models 16 & 31 Internal Boiler Pump. (Max 1 Amp) Models 47 & 75 External Heating Pump. (Max 1

Amp)

E 9, 15 &

18 - - Common Permanent Earth

N 19 230V - Permanent Neutral L 20 230V - Permanent Live (Max 5 Amp)

X10-03 - <25V Yes Safety Interlock Volt Free Enable (For use with ventilation interlocks/gas pressure switch etc.)

For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13/14 for additional guidance.

Page 4: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

4

Generic Single Boiler Hydraulic Configuration

For BMS Run and Fault indication terminal allocation refer to the section titled,

Boiler Controller Mounted Options.

Page 5: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

5

ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager. RVA47 (Grey) Controlled. Produced to 01/01/2012

Additional Wiring Terminals (This terminal rail is in addition to the standard rail.)

Terminal Designation

Tag Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

BW 230V - Hot Water Charging Pump Output. (Max 2 Amp) HK / ZB 230V - Heating Circuit Pump Output. (Max 2 Amp)

H1 < 25V Yes Enabling Input

Volt Free Enable or 0-10Volt or Operation Changeover (M = Ground & H1 = Positive)

RL < 25V Yes Return Sensor (QAD21) (M = Ground & B70/B4 Positive)

VL < 25V Yes Flow Sensor (QAD21) (M = Ground & B10 Positive)

BW < 25V Yes Hot Water Sensor (QAZ21) or Volt Free Enable.

(Via Time Switch/Calorifier Thermostat/BMS) (Parameter alteration required if Volt free enable used)

(M = Ground & B3 Positive)

AF < 25V Yes Outside Air Sensor. (QAC31/32) (620Ω Substitute Resistor = -10C)

(Mounted on North Facing Wall) (Parameter alteration required if outside air sensor not connected)

(M = Ground & B9 Positive)

RU < 25V Yes Room Unit QAA70/50/10 (M = Ground & A6 Positive)

LPB < 25V Yes LPB Cascade Communication. (Loom Mounted Plug.) (MB = Ground & DB = Data Bus)

Each boiler within the cascade including the master will have an OCI420 Communication Clip fitted.

The LPB communication wiring must be wired (X41) between each OCI420

Communication Clip in parallel.

Page 6: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

6

ProCon 75 & 77 Wall Mounted Condensing Boilers Cascade Manager. RVS43 Controlled. Produced from 01/01/2012

Additional Wiring Terminals Located on the RVS43 Controller.

Tag Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

L E N 230V - Permanent 230 Volt Power Supply From the

LMU X1:02. P 230V - Not Used in this configuration.

Q 230V - Safety Interlock

(SK1 & SK2) R 230V - HWS Pump or Valve Output 230 Volts Max 1 Amp (Q3) S 230V - Heating Circuit Pump Output 230 Volt Max 1 Amp (Q2)

T 230V - Heating Circuit Mixing Valve Output

(Y1 Valve Open. Y2 Valve Close) U 230V - Multifunctional Relay Output (QX1)

X30 < 25V Ribbon Display Panel

a < 25V Yes LPB Cascade Communication

For connection to OCI clips in master and cascade boilers. DB Data MB Ground

b < 25V Yes BSB Data Communication

b < 25V Yes QAA75 Room Unit Communication

CL+ Data CL- Ground G+ 12 Volt Power Supply f < 25V Yes Not Used in this configuration.

h < 25V Yes Hot Water Sensor or Volt Free Enable QAZ36 Parameter change required if using volt free enabling.

k < 25V Yes Outside Air Sensor QAD34

n < 25V Yes Volt Free Enable or 0-10 Volt Drive input

H1 +, M Ground p < 25V Yes Heating Circuit 1 Flow Senor. (Only used when a mixing valve is applied.) n < 25V Yes System Flow Senor QAZ36 n < 25V Yes System Return Sensor QAZ36

Page 7: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

7

Generic Multiple Boiler Hydraulic Configuration

For BMS Run and Fault indication terminal allocation refer to the section

titled, Boiler Controller Mounted Options.

Page 8: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

8

ProCon HT 150-225 Floor Standing Condensing Boilers.

RVA47 (Grey) Controlled. (Produced to 01/01/2011)

Boiler Wiring Terminals

External Flow and return sensors (QAD21) are required for Cascade Manager Units only. The sensors must be wired to the terminal detailed below.

These terminals are located on the top left of the boiler frame when viewed from the front.

(These terminals are pre-wired on Standalone FS units.)

Module Controller Mounted Safety Interlock Terminals (X10:03)(Low Voltage<25V) If required each module can be connected to an external safety device. A relay must be used to ensure separation of the voltages generated by each module controller. (X10:03)

Terminal Designation

Tag Terminal

#s Voltage

Screened Cable

(Earthed Screening) Description/Operation/Function

RU A6 & MD (Not Polarity Sensitive)

< 25V Yes QAA70/50/10 PPS Room Unit

H1 H1 & M (Polarity Sensitive) <25V Yes

0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS

BW B3 & M (Not Polarity Sensitive) < 25V Yes

Hot Water Sensor (QAZ21) or Volt Free Enable. (Via Time Switch/Calorifier Thermostat/BMS)

(Parameter alteration required if Volt free enable used)

AF B9 & M (Not Polarity Sensitive) < 25V Yes Outside Air Sensor. (QAC31/32) or (620Ω Substitute Resistor = -10C)

(Mounted on North Facing Wall)(Parameter alteration required if outside air sensor not connected)

BUS DB & MB (Polarity Sensitive) < 25V Yes Boiler Communication to Slave Boilers.

(LPB DB Data & MB Ground)

BW N Neutral

Q3 Switched Live 230V - Hot Water Charging Pump or 3 way Valve Output. (Max 2 Amp)

HK 11 Switched Live

N Neutral 230V - Heating Pump Output (Max 2 Amp)

230V N Perm Neutral

L Perm Live 230V - Permanent 240 Volt Supply (Max 10 Amp)

VL B10 & M < 25V Yes System Flow Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor)

RL M & B70 < 25V Yes System Return Sensor (QAZ21/QAD21) (Standalone boilers have an internal sensor. Cascade manager boilers required an externally mounted sensor)

X10-03 - <25V Yes Safety Interlock Volt Free Enable (For use with ventilation interlocks/gas pressure switch etc.)

Page 9: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

9

ProCon HT 150-225 Floor Standing Condensing Boilers.

RVS43 Controlled. (Produced from 01/01/2011)

Boiler Wiring Terminals

Module Controller Mounted Safety Interlock Terminals (X10:03)(Low Voltage<25V) If required each module can be connected to an external safety device. A relay must be used to ensure separation of the voltages generated by each module controller. (X10:03)

Page 10: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

10

Generic Single HT Boiler Hydraulic Configuration

Generic Multiple HT Boiler Hydraulic Configuration (Indicting the location of the system mounted Flow and Return Sensors)

For Module BMS Run and Fault indication terminal allocation refer to the section titled,

Boiler Controller Mounted Option.

Page 11: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

11

Boiler Controller Mounted Options. AGU2.511 BMS Run & Fault 230V Outputs & 0-10Volt/0-20mA Input Clip.

Terminal Designation

Tag Terminal

#s Voltage Description/Operation/Function

Switched Output Power Input

X52-01

1 Live 2 Neutral

230V (Max)

Power Supply from X01-02 for switched live outputs. Power Supply from BMS can replace power supply

from X01-02 (<230V/0.5Amp)

Output 1R X52-02

1 Live 2 Neutral

230V (Max)

Programmable Output Available Options

Boiler Fault Output. Or Boiler Operating Output or SSOV.(Safety Shut Off Valve) (Max 1 Amp)

(Parameter amendment required)

Output 2R X52-03

1 Live 2 Neutral

230V (Max)

Programmable Output Available Options

Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp)

(Parameter amendment required)

Output 3R X52-03 3 Live

230V (Max)

Programmable Output Available Options

Boiler Fault Output. Or Boiler Operating Output or SSOV (Max 1 Amp)

(Parameter amendment required)

Control Input

X51-01

1 Control Input

2 Ground

0-10V Or

0-20mA

Programmable Control Input 0-10 Volt or 0-20mA

Flow Temperature or % Power Control (Parameter amendment required)

Page 12: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

12

Boiler Controller Mounted Options. AGU2.500 Heating Zone 2 Pump/Mixing Valve/Sensor Clip.

Terminal Designation

Tag Terminal

#s Voltage Description/Operation/Function

Switched Output Power Input

X52-01

1 Live 2 Neutral

230V

Power Supply from X01-02 for switched live outputs.

Pump Output X52-02

1 Live 2 Neutral

230V

Heating Zone 2 Pump Outputs (Max 1 Amp)

Mixing Valve

X52-03

1 Close 2 Neutral 3 Open

230V

Heating Zone 2 Mixing Valve Outputs (Valve control is possible only when a zone flow sensor is connected)

(Max 1 Amp)

Flow Sensor Input

X51-01

1 & 2 (Not Polarity Sensitive)

<25V Heating Zone 2 Flow Sensor Inputs. (QAD36)

*H552 must be set to 66 to ensure correct operation of mixing zone clip.

Page 13: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

13

Generic Single Boiler (AGU2.500 Zoned) Hydraulic Configuration

Page 14: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

14

Boiler Controller Mounted Options. OCI420 LPB Cascade Communication Clip. For use when control is provided via a RVA47 Cascade Manager or RVA63 Controller.

Terminal Designation

Tag Terminal #s Screened Cable Description/Operation/Function

LPB X41-01

1, DB LPB Data 2, MB LPB Ground

(Polarity Sensitive)

Yes LPB Control Communication From RVA47

Cascade Manager or RVA63 Boiler and zone controller.

(Parameter amendment required)

Page 15: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

15

RVA47 Cascade Manager. Manager Wiring Terminals.(Rear of controller)(Housing available)

Terminal Designation

Tag Terminal

#s Voltage

Screened Cable

(Earthed Screening) Description/Operation/Function

H1 6 (Polarity Sensitive) <25V Yes

0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS

(M terminal used to create circuit)

B70/B4

5 (Not Polarity Sensitive) <25V Yes System Return Sensor (QAD21)

(To be positioned on boiler side of system Low Loss Header)

B3 4 (Not Polarity Sensitive) <25V Yes

Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS

(Parameter alteration required if Volt Free Enable Used)

M M <25V Yes Ground Connection for all Sensors/Inputs

B10 2 (Not Polarity Sensitive) <25V Yes System Flow Sensor (QAD21)

(To be positioned on system side of system Low Loss Header) B9 1

(Not Polarity Sensitive) <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)

MD M (Not Polarity Sensitive) <25V Yes QAA70/50/10 Room Unit (PPS Ground)

A6 - (Not Polarity Sensitive) <25V Yes QAA70/50/10 Room Unit (PPS Data)

MB M (Polarity Sensitive) <25V Yes Boiler Communication (LPB Ground connected in parallel to

boiler mounted OCI420 Clips)

DB - (Polarity Sensitive) <25V Yes Boiler Communication (LPB Data connected in parallel to

boiler mounted OCI420 Clips))

Q3 3 230V - Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)

Q1 2 230V - Heating Pump Output (Max 2 Amp)

F1 F 230V - Power Input for Heating and Hot Water Pump

Outputs (To be linked to Live Input)

L L 230V - Permanent Live (Max 6 Amp) N N 230V - Permanent Neutral

For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.

Page 16: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

16

RVA47 Cascade Manager. Manager Wiring Terminals.(Housing) (Housing designed for use with additional RVA46 Zone controller)

(RVA 46 Zone Controller wiring Information detailed later in document.)

Terminal Designation

Tag Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

DB <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clips))

MB <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clips)

A6 <25V Yes QAA70/50/10 Room Unit (PPS Data) MD <25V Yes QAA70/50/10 Room Unit (PPS Ground)

B9 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)

M <25V Yes Ground Connection for all Sensors/Inputs

B10 <25V Yes System Flow Sensor (QAD21) (To be positioned on system side of system Low Loss Header)

B3 <25V Yes Hot Water Sensor (QAZ21)/Volt Free Enable via

Calorifier Thermostat/BMS (Parameter alteration required if Volt Free Enable Used)

B70/B4

<25V Yes System Return Sensor (QAD21) (To be positioned on boiler side of system Low Loss Header)

H1 <25V Yes 0-10 Volt Input via BMS/Volt Free Enable via Room

Thermostat/BMS

Q1 230V - Heating Pump Output (Max 2 Amp) Q3 230V - Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp) N 230V - Permanent Neutral PE - - Permanent Earth L 230V - Permanent Live (Max 6 Amp)

(All ‘M’ Terminals are Internally Linked)

For cascade control via a RVA47 cascade manager each boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.

Page 17: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

17

Generic Multiple Boiler RVA47 Controlled Hydraulic Configuration

Heating Zone

RVA47 Cascade Controller

Outside Air Sensor QAC32

QAA70/50/10

Zone Pump

Flow Sensor QAD21

Hot Water Primary Pump

Hot Water Sensor QAZ21

Return Sensor QAD21

Up to 12 ProCon Boilers In Cascade

LPB Communication to each boiler via an OCI clip module.

Component Control Capability of RVA47

Page 18: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

18

RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(Housing available)

Terminal Designation (Low Voltage Terminals)

Tag Terminal

#s Voltage

Screened Cable

(Earthed Screening) Description/Operation/Function

MD - (Not Polarity Sensitive) <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Ground)

A7 - (Not Polarity Sensitive) <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Data)

B12 3 (Not Polarity Sensitive) <25V Yes Zone 2 Flow Sensor (QAD21/26)

(To be positioned on Zone side of 3 way mixing valve) M M

(Not Polarity Sensitive) <25V Yes Ground Connection for all Sensors/Inputs

B8 1 (Not Polarity Sensitive) <25V Yes Flue Gas Sensor (Not Used)

B31/H2/ B41

4 (Polarity Sensitive) <25V Yes Volt Free Enable via Room Thermostat/BMS

B1 3 (Not Polarity Sensitive) <25V Yes Zone 1 Flow Sensor (QAD21/26)

(To be positioned on Zone side of 3 way mixing valve)

H1 6 (Polarity Sensitive) <25V Yes

0-10 Volt Input via BMS/Volt Free Enable via Room Thermostat/BMS

B2 5 (Not Polarity Sensitive) <25V Yes Boiler Sensor (Not Used)

B3 4 (Not Polarity Sensitive) <25V Yes

Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier Thermostat/BMS

(Parameter alteration required if Volt Free Enable Used)

B9 1 (Not Polarity Sensitive) <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C)

(Mounted on North Facing Wall)

MD M (Not Polarity Sensitive) <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Ground)

A6 - (Not Polarity Sensitive) <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Data)

MB M (Polarity Sensitive) <25V Yes Boiler Communication (LPB Ground connected in parallel to

boiler mounted OCI420 Clip or RVA47 Manager)

DB - (Polarity Sensitive) <25V Yes Boiler Communication (LPB Data connected in parallel to

boiler mounted OCI420 Clip or RVA47 Manager) For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420

Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page.

Page 19: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

19

RVA63 Boiler and Zone Controller. Manager Wiring Terminals.(Rear of controller)(Housing available)

Terminal Designation (230 Volt Terminals)

Tag Terminal

#s Voltage Description/Operation/Function

Y6 - 230V Zone 2 Mixing Valve Closing Output (Max 2 Amp) Y5 - 230V Zone 2 Mixing Valve Opening Output (Max 2 Amp)

F3 - 230V Power Input for Zone 2 Valve Outputs (To be linked to Live Input)

Q6 3 230V Zone 2 Pump Output (Max 2 Amp) Q2 2 230V Zone 1 Pump Output (Max 2 Amp)

F6 F 230V Power Input for Zone Pumps Output (To be linked to Live Input)

Y2 3 230V Zone 1 Mixing Valve Closing Output (Max 2 Amp) Y1 2 230V Zone 1 Mixing Valve Opening Output (Max 2 Amp)

F2 F 230V Power Input for Zone 1 Valve Outputs (To be linked to Live Input)

Q3/Y3

3 230V Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)

F1 F 230V Power Input for Hot Water Pump/Valve Output (To be linked to Live Input)

K5 4 230V Burner Enable Output Stage 2 (Not Used) F5 F 230V Power Input Burner Enable Stage 2 (Not Used) K4 2 230V Burner Enable Stage 1 (Not Used) F4 F 230V Power Input Burner Enable Stage 1 (Not Used) L L 230V Permanent Live (Max 6 Amp) N N 230V Permanent Neutral

For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420 Clip. Refer to Page 13 for additional guidance.

Page 20: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

20

RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing)

Terminal Designation (Low Voltage Terminals)

Tag Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

DB <25V Yes Boiler Communication (LPB Ground connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager)

M <25V Yes Boiler Communication (LPB Data connected in parallel to boiler mounted OCI420 Clip or RVA47 Manager)

A6 <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Data) M <25V Yes Zone 1 QAA70/50/10 Room Unit (PPS Ground)

B9 <25V Yes Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)

M <25V Yes Ground Connection for all Sensors/Inputs

B3 <25V Yes Hot Water Sensor (QAZ21)/Volt Free Enable via Calorifier

Thermostat/BMS (Parameter alteration required if Volt Free Enable Used)

B2 <25V Yes Boiler Sensor (Not Used)

H1 <25V Yes 0-10 Volt Input via BMS/Volt Free Enable via Room

Thermostat/BMS B7 - - Not Used with RVA63

B1 <25V Yes Zone 1 Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve)

B31/H2/ B41

<25V Yes Volt Free Enable via Room Thermostat/BMS

B8 <25V Yes Flue Gas Sensor (Not Used)

B12 <25V Yes Zone 2 Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve)

B4 - - Not Used with RVA63 M <25V Yes Ground Connection for all Sensors/Inputs M <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Ground) A7 <25V Yes Zone 2 QAA70/50/10 Room Unit (PPS Data)

(All ‘M’ Terminals are Internally Linked) For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420

Clip. Refer to Page 13 for additional guidance. 230 Volt Terminals shown on following page.

Page 21: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

21

RVA63 Boiler and Zone Controller. Manager Wiring Terminals. (Housing)

Terminal Designation (230 Volt Terminals)

Tag Voltage Description/Operation/Function K6 - Not Used with RVA63 Y6 230V Zone 2 Mixing Valve Closing Output (Max 2 Amp) Y5 230V Zone 2 Mixing Valve Opening Output (Max 2 Amp) N 230V Permanent Neutral

Q6 230V Zone 2 Pump Output (Max 2 Amp) Q2 230V Zone 1 Pump Output (Max 2 Amp) N 230V Permanent Neutral Y2 230V Zone 1 Mixing Valve Closing Output (Max 2 Amp) Y1 230V Zone 1 Mixing Valve Opening Output (Max 2 Amp)

Q3/Y3

230V Hot Water Charging Pump/3 Way Valve Output (Max 2 Amp)

PE - Permanent Earth N 230V Permanent Neutral L1 230V Permanent Live (Max 6 Amp) K5 230V Burner Enable Output Stage 2 (Not Used) F5 230V Power Input Burner Enable Stage 2 (Not Used) K4 230V Burner Enable Stage 1 (Not Used)

For zone control via a RVA63 zone controller the boiler must be fitted with an OCI420

Clip. Refer to Page 13 for additional guidance.

Page 22: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

22

Generic Single Boiler RVA63 Controlled Hydraulic Configuration

Heating Zone 1 Heating Zone 2

Component Control Capability of RVA63

RVA63 ControllerOutside Air Sensor QAC32

RVA47 Cascade Controller

QAA70/50/10 QAA70/50/10

Zone 1 PumpZone 2 Pump

Mixing Valve

Mixing Valve

Zone 1 Flow Sensor QAD26

Zone 2 Flow SensorQAD26

Single Boiler Control with OCI420 Clip

Hot Water Primary Pump

Hot Water Sensor QAZ21

LPB Communication to each boiler via OCI Clip Modules

LPB

Page 23: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

23

RVA46 Zone Controller. Controller Wiring Terminals.(Rear of controller)(Housing available)

Terminal Designation

Tag Terminal

#s Voltage

Screened Cable

(Earthed Screening) Description/Operation/Function

H1 6 (Not Polarity Sensitive) <25V Yes Volt Free Enable via Room Thermostat/BMS

M M <25V Yes Ground Connection for all Sensors/Inputs

B1 2 (Not Polarity Sensitive) <25V Yes Zone Flow Sensor (QAD21)

(To be positioned on Zone side of 3 way mixing valve) B9 1

(Not Polarity Sensitive) <25V Yes Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall) (Not required if using RVA47 O/S Sensor)

MD M (Not Polarity Sensitive) <25V Yes Zone QAA70/50/10 Room Unit (PPS Ground)

A6 - (Not Polarity Sensitive) <25V Yes Zone QAA70/50/10 Room Unit (PPS Data)

MB M (Polarity Sensitive) <25V Yes RVA47/63 Communication (LPB Ground connected in parallel to

RVA47 Manager or RVA63 Zone controller)

DB - (Polarity Sensitive) <25V Yes RVA47/63 Communication (LPB Data connected in parallel to RVA47

Manager or RVA63 Zone controller)

Y2 3 230V - Mixing Valve Closing Output (Max 2 Amp) Y1 2 230V - Mixing Valve Opening Output (Max 2 Amp)

F2 1 230V - Power Input for Zone Valve Outputs (To be linked to Live Input)

Q2 2 230V - Zone Pump Output (Max 2 Amp)

F6 F 230V - Power Input for Zone Pump Output (To be linked to Live Input)

L L 230V - Permanent Live (Max 6 Amp) N N 230V - Permanent Neutral

Page 24: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

24

RVA46 Zone Controller. Controller Wiring Terminals.(Housing) (Housing designed for use with primary RVA47 Cascade Manager.)

(RVA 47 Cascade Manager wiring Information detailed earlier in document.)

Terminal Designation

Tag Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

A6 <25V Yes Zone QAA70/50/10 Room Unit (PPS Data) MD <25V Yes Zone QAA70/50/10 Room Unit (PPS Ground)

B9 <25V Yes Zone Outside Air Sensor (QAC31/32) or (620Ω Substitute Resistor = -10C) (Mounted on North Facing Wall)(Not required if using RVA47 O/S Sensor)

M <25V Yes Ground Connection for all Sensors/Inputs

B1 <25V Yes Zone Flow Sensor (QAD21) (To be positioned on Zone side of 3 way mixing valve)

H1 <25V Yes Volt Free Enable via Room Thermostat/BMS

Q2 240V - Zone Pump Output (Max 2 Amp) Y1 240V - Mixing Valve Opening Output (Max 2 Amp) Y2 240V - Mixing Valve Closing Output (Max 2 Amp)

(All ‘M’ Terminals are Internally Linked)

Page 25: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

25

RVS63 Cascade and Zone Controller. Wiring Terminals Located on the RVS63 Controller. (Housing Available)

Page 26: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

26

Terminal Legend. Tag Terminal #s Voltage Screened Cable

(Earthed Screening) Description/Operation/Function Z QX4, QX4, FX4, EX2 230 Volts NA Multifunctional 4 Relay Output U QX3, ‡, N 230 Volts NA Multifunctional 3 Relay Output U QX2, ‡, N 230 Volts NA Multifunctional 2 Relay Output

T Y6, ‡, N, Y5 230 Volts NA Heating Circuit 2 Mixing Valve

Output Y5 Open, Y6 Close S Q6, ‡, N 230 Volts NA Heating Circuit 2 Pump Output U QX1, ‡, N 230 Volts NA Multifunctional 1 Relay Output

T Y2, ‡, N Y1 230 Volts NA Heating Circuit 1 Mixing Valve

Output Y1 Open, Y2 Close S Q2, ‡, N 230 Volts NA Heating Circuit 1 Pump Output R Q3, ‡, N 230 Volts NA HWS Circuit Pump, Valve Output Q SK2, SK1 230 Volts NA External Safety Interlock Circuit P 4, S3, T2, T1, , L1 230 Volts NA **Burner Outputs Not Used** ~ S3 230 Volts NA **Burner Outputs Not Used** ~ L1 230 Volts NA Permanent Live Output ~ N, E, L 230 Volts NA Permanent Supply Input

Tag Terminal #s Voltage Screened Cable

(Earthed Screening) Description/Operation/Function n M, UX >24 Volts Yes 0-10 Volt Output **Not Used** n M, BX4 >24 Volts Yes Multifunctional 4 Sensor Input n M, BX3 >24 Volts Yes Multifunctional 3 Sensor Input

n M, H3 >24 Volts Yes Volt Free Enable or 0-10 Volt Input

Heating Zone 2

p M, B12 >24 Volts Yes Heating Circuit 2 Flow Sensor

QAD/Z36 n M, BX2 >24 Volts Yes Boiler Return Sensor QAD/Z36#

n M, BX1 >24 Volts Yes System Flow Sensor QAD/Z36#

p M, B1 >24 Volts Yes Heating Circuit 1 Flow Sensor

QAD/Z36

n M, H1 >24 Volts Yes Volt Free Enable or 0-10 Volt Input

Heating Zone 1 k M, B9 >24 Volts Yes Outside Air Sensor QAC34

h M, B3 >24 Volts Yes HWS Sensor QAZ36 or Volt Free

Enable f M, B2 >24 Volts Yes Boiler Sensor **Not Used** G+ QAA75 Power Supply 12 Volts

b CL-, CL+ >24 Volts Yes Heating Circuit 1 QAA55/75

-Ground, + Data

b CL-, CL+ >24 Volts Yes Heating Circuit 2 QAA55/75

-Ground, + Data b CL-, CL+ >24 Volts Yes BSB Comms to second RVS

a MB,DB >24 Volts Yes Boiler Communication Connection (OCI420 Clips mounted in Boilers

Wiring in Parallel) X30 ~ >24 Volts Yes Display Panel Connection X60 ~ >24 Volts Yes Connection for QAA78 Sender

# Parameter alterations may be required to configure these terminals.

Page 27: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

27

QAA73 Single Boiler Opentherm Room Units Room Unit Mounting Plate Wiring Terminals

Terminal Designation

Terminal #s

Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

1 & 2 (Not Polarity Sensitive) <25V Yes

Opentherm communication to Single Boiler Installation

3 & 4 - - Not Used 5 & 6 - - Not Used

Page 28: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

28

QAA70/50/10 PPS Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals

Terminal Designation

Terminal #s

Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

D1 & D2 (Not Polarity Sensitive) <25V Yes

PPS communication to RVA47/46/63 Controlled Installation

D 3 & D4 (Not Polarity Sensitive) <25V Yes

Tamperproof QAW44 Remote Sensor or Volt Free Enable

D5 & D6 - - Not Used

Page 29: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

29

QAA55 BSB Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals

Terminal Designation

Terminal #s

Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

1 <25V Yes BSB Data CL+ 2 <25V Yes BSB Ground CL-

Page 30: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

30

QAA75 BSB Cascade or System Controller Room Units Room Unit Mounting Plate Wiring Terminals

Terminal Designation

Terminal #s

Voltage Screened

Cable (Earthed Screening)

Description/Operation/Function

1 <25V Yes BSB Data CL+ 2 <25V Yes BSB Ground CL- 3 <25V Yes Power Supply DC 12V G+

Page 31: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

31

QAA78 Wireless Cascade or System Controller Room Units Room Unit Mounting Plate and Receiver Module Mount the receiver module outside of the boiler/housing and connect the ribbon cable to X60 on the controller

Mount the cradle and insert the batteries into the rear of the QAA78 room unit.

**Follow synchronising instructions supplied with the QAA78 room unit.**

Page 32: Appliance And Controller Electrical Installation Guide 010112

MHG Heating Ltd ©

MHG Heating Ltd Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey KT20 5LR Telephone 08456 448802 Fax 08456 448803 Email [email protected] Web www.mhgheating.co.uk

01/01/12

32

NOTES