Report Nº SHES181001183471 Page 1 of 9
IEC62109-1:2010
ANNEX I
(Pictures of the EUT and Electrical Schemes)
Annex I
Report Nº SHES181001183471 Page 2 of 9
IEC62109-1:2010
1 PICTURES
Front of UP5000-M10342
Side of UP5000-M10342
Annex I
Report Nº SHES181001183471 Page 3 of 9
IEC62109-1:2010
Connection interface of UP5000-M10342
Internal
Annex I
Report Nº SHES181001183471 Page 4 of 9
IEC62109-1:2010
Front side of invert board
Back side of invert board
Annex I
Report Nº SHES181001183471 Page 5 of 9
IEC62109-1:2010
Front side of PV charge board
Back side of PV charge board
Annex I
Report Nº SHES181001183471 Page 6 of 9
IEC62109-1:2010
Front side of signal transfer board
Back side of signal transfer board
Annex I
Report Nº SHES181001183471 Page 7 of 9
IEC62109-1:2010
Front side of AC-DC board
Back side of AC-DC board
Annex I
Report Nº SHES181001183471 Page 8 of 9
IEC62109-1:2010
2 ELECTRICAL SCHEMES
AC-DC:
MCU drive
Q1
Q3
Q2
Q4
Full bridge rectifier circuit
Current sampling
Voltage sampling
C220Vacinput
Auxiliary power
transformerVoltage sampling
DCoutput
BAT+
BAT-Communication Interface
PWMsignal
Solar Charging:
BAT+
BAT-
PV+
PV-
MCU
Current sampling
Voltage sampling
Voltage sampling
drive
Auxiliary power supply and communication
interface
Annex I
Report Nº SHES181001183471 Page 9 of 9
IEC62109-1:2010
Inverter:
Drive circuit B
MCUAC OUT
Drive circuit
APWM
Push-pull circuit Rectifier bridge
Full bridge inverter circuit Filter
circuit
Switching circuit
AC IN
L
N
L
N
BAT+
BAT-
Current sampling
Voltage sampling
Voltage sampling
Auxiliary power supply
and communication
interface
Annex II
Report Nº SHES181001183471 Page 1 of 4
IEC 62109-2: 2011
ANNEX II
(Testing information)
Annex II
Report Nº SHES181001183471 Page 2 of 4
IEC 62109-2: 2011
1 TESTING CIRCUIT
Different equipment has been used to take measures as it shows in testing equipment list.
Current and voltage clamps have been connected to the inverter output for all the tests.
All the tests described in the following pages have used this specified test setup.
Annex II
Report Nº SHES181001183471 Page 3 of 4
IEC 62109-2: 2011
2 TESTING EQUIPMENT
Clause Measurement /
testing
Testing / measuring equipment / material used, (Equipment ID)
Range used Last
Calibration date
Calibration due date
4.3 Thermal testing Data Acquisition (34970A)
20~40channel, accuracy 0.1°C DCV:0.0002V ACV:0.0050V R: -0.0025KΩ DCC:0.0005 mA ACC:0.0640mA
2018/11/28 2019/11/27
4.4.4 Testing in single fault condition
Precision Power Analyzer (WT3000)
(ACC):0.0131mA (ACV): -0.004V (AC power): -0.006W (Frequency):0Hz (Power Factor):0.00122
2018/11/28 2019/11/27
4.5 Humidity preconditioning test
Programmable Temperature & Humidity Test Chamber (THS-D2C-100)
-20-100℃/10-98%RH 2018/5/28 2019/5/29
4.6 Backfeed voltage protection test
Precision Power Analyzer (WT3000)
(ACC):0.0131mA (ACV): -0.004V (AC power): -0.006W (Frequency):0Hz (Power Factor):0.00122
2018/11/28 2019/11/27
4.7.2 Electrical ratings test
Precision Power Analyzer (WT3000)
(ACC):0.0131mA (ACV): -0.004V (AC power): -0.006W (Frequency):0Hz (Power Factor):0.00122
2018/11/28 2019/11/27
7.3.6.3.4
Earth continuity
Earthing Resistance Tester
(GEO 416)
(3.0~60)A, (1~510/150)mΩ, (1~999.9)s, 50/60Hz
2018/11/8 2019/11/7
7.3.6.3.5
Cross-sectional protectice earthing conductor
Earthing Resistance Tester
(GEO 416)
(3.0~60)A, (1~510/150)mΩ, (1~999.9)s, 50/60Hz
2018/11/8 2019/11/7
7.3.7.4 Clearance distances
Vernier Caliper (0~200) mm
(EOI): +0.02mm 2018/11/29 2019/11/28
7.3.7.5 Creepage distances
Vernier Caliper (0~200) mm
(EOI): +0.02mm 2018/11/29 2019/11/28
7.5.1 Impulse voltage test
Impulse tester (GC-107)
0-7000V 2018/4/8 2019/4/7
Annex II
Report Nº SHES181001183471 Page 4 of 4
IEC 62109-2: 2011
7.5.2 Voltage test (dielectric strength test)
Puncture Tester (AT9220A)
(ACV): -0.006kV (DCV): -0.005kV (ACI):0.0049mA (DCI):0.0173mA (T):0.02S
2018/11/28 2019/11/27
7.5.4 Touch current measurement (Annex H)
Puncture Tester (AT9220A)
(ACV): -0.006kV (DCV): -0.005kV (ACI):0.0049mA (DCI):0.0173mA (T):0.02S
2018/11/28 2019/11/27
8.5 Wall mounting Stop Watch (694)
accuracy 0.01s 2018/4/16 2019/4/17
3 MEASUREMENT UNCERTAINTY
Voltage measurement uncertainty
±0,05 %
Current measurement uncertainty
±0,05 %
Frequency measurement uncertainty
±0,001 Hz
Time measurement uncertainty
±0.001s
Power measurement uncertainty
±0,5 %
Phase Angle ±0. 1º
Cosφ ±0,01%
Annex III
Report Nº SHES181001183471 Page 1 of 4
IEC 62109-2: 2011
ANNEX III
(GRAPHS OF TEMPERATURE TEST RESULTS)
Annex III
Report Nº SHES181001183471 Page 2 of 4
IEC 62109-2: 2011
3.1 TEMPERATURE TEST CONDITION
Condition. Test ambient
temperature(℃)
Input Output
(PF=1 default settings)
Voltage V.
Current A
Power W
Voltage V
Current A
Power W
AC-DC Charging
22.6℃ 170.4Va.c 12.28 2092 57.8 29.9 1728
DC-DC Discharging
23.4℃ 48.1 88.42 4216 219.3 18.1 3960
DC-DC charging
25.1℃ 79.8 62.92 5020 57.0 85.5 4878
Annex III
Report Nº SHES181001183471 Page 3 of 4
IEC 62109-2: 2011
3.2 TEMPERATURE TEST WAVEFORM
AC-DC Charging Input: 170Vac, Output: 57.8Vac, Test at 22.6°C
DC-DC Discharging Input: 48Vdc, Output: 219.3Vac, Test at 23.4°C
DC-DC charging Input: 79.8Vdc, Output: 57.0Vac, Test at 25.1°C