Tundra Specialties series.280033.pdf · Tundra Specialties. Tundra Specialties
AND Energy Controls - Relay Specialties, Inc. · people can set them without consulting the...
Transcript of AND Energy Controls - Relay Specialties, Inc. · people can set them without consulting the...
Contractor shall furnish
and install Grasslin DTMV
Defrost Control
No Equal
Contractor shall specify
Talento 894 four channel
365 day program
No Equal
Contractor shall
furnish and install
Grasslin LightMaster
LM230-I-120
No Equal
Time AND
Energy Controls
imagination at work
Electromechanical Time ControlsElectronic Time ControlsIn-Wall TimersLighting ControlsPhoto ControlsDefrost TimersElectronic Temperature/Refrigeration ControlsCycle TimersHour MetersInterval TimersDefinite Purpose Contactors
Welcome to Grasslin... the Global Leader in Time and Energy Controls for OEMs, Distributors, Contractorsand Users of Time Controls.
Today, Grasslin is one of the world's leading time control producerswith a product range of approximately 2,000 timing devices.Grasslin's products have set the standards for quality and innova-tion in technology and design. Our three modern manufacturinglocations are ISO 9001 registered.
Grasslin products are sold in over 50 countries throughout theworld. They carry the UL and CE mark as well as numerous otherapprobations.
We look forward to serving your time control requirements withquality products and service second to none.
INNOVATION in applying new technology in small packages. Innovation in simplifying the setting and programming oftime controls. Innovation in flexibility of mounting and use. Innovation is the key to providing superior electro-mechanical and electronic time controls to meet the application needs of contractors, as well as industrial, com-mercial, institutional, residential, and agricultural users.
ENERGY SAVINGS is one of the major benefits Grasslin Time Controls offer. From extremely compact electro-mechanical 24-hour and 7-day time switches to innovative 365-day multi-channel programmable controls,Grasslin products meet the need for control of heating, cooling, and refrigeration systems; interior, outdoor ordisplay lighting; machinery and appliances, and many other applications.
MODERN DESIGN is exemplified by the compact size of Grasslin Time Controls. Look at the clean simple lines.Look at the easy-to-read dials. Look at the functional appearance. Look at the simplified programming. Over thelast ten years, Grasslin has set the standard in design, quality and performance.
USER FRIENDLY is not just a buzzword at Grasslin. From the flexibility of mounting and ease of wiring to the mini-mal single function programming keys on electronic units, at Grasslin the installing contractor is our #1 concern.
BROAD PRODUCT RANGE The right product for the job is available through the extensive selection of time control,hour meter, photo-electric control, and temperature control products offered.
SIMPLICITY Programming either the electromechanical or electronic time controls are intuitive and easy to under-stand. No double function keys and consistent programming logic between models simplify programming. Mostpeople can set them without consulting the instructions.
INSTALLATION FLEXIBILITY Compact design permits installation virtually anywhere; conserves control panelspace. Capability for flush panel, surface, or DIN rail mounting, plus availability of both indoor and outdoor enclo-sures for all models makes installation a breeze.
LightMaster
Time and Energy Controls for Changing Times
Intelligent Time Control Starts Here!
www.grasslin.com 201.825.9696 1
ContentsELECTROMECHANICAL TIME CONTROLS
24 Hour Electromechanical Time Switches
TimeMaster – GM Series......................................2
TimeMaster – GMX Series....................................3
Water Heater Timer .............................................4
MIL 72A, E............................................................5
FM/1.........................................................………12
7 Day Electromechanical Time Switches
TimeMaster – GM Series......................................2
TimeMaster – GMX Series....................................3
MIL 72A, E............................................................5
FM/1 ...........................................................……12
1 Hour Electromechanical Time Switch
TALENTO-121.....................................................26
12 Hour Electromechanical Time Switches
FM/1 S12hu .......................................................26
ELECTRONIC TIME CONTROLS
One Channel Electronic Time Switches
TimeMaster – GM Series......................................6
TimeMaster – GMX Series....................................7
Digi 20A, E ..........................................................8
Digi 42A, E ..........................................................8
TALENTO-471 (24-hr/7-day) .........................10-11
TALENTO-891 (365 day) .............................10-11
FM/1 digi 20 & 42...............................................13
Two Channel Electronic Time Switches
(24-hour, 7-day, and 365-day)
TimeMaster – GMX Series....................................7
Digi 42/2 ...............................................................9
TALENTO-472 (24-hr/7-day) .........................10-11
TALENTO-892 (365 day)...............................10-11
Four Channel Electronic Time Switches
TALENTO-894 (365 day)...............................10-11
Eight Channel Electronic Time Switch
SRS-3800 ..........................................................11
LightMaster – LM1, LM2 ........................................18-19
Photo Controls .......................................................20-21
DEFROST CONTROLS–COMMERCIAL
REFRIGERATION
FrostKing – DTMV..................................................22-23
FrostKing – DT140 Electronic..................................…23
ELECTRONIC TEMPERATURE/REFRIGERATION
CONTROLS
TC10 ...........................................................................24
TFC212........................................................................25
IN-WALL TIMERS
KLT – Spring-Wound ...................................................14
ET616 – Electronic Count Down .................................15
KM2 Electro-Mechanical 24-Hour/7-Day ....................16
ET724 Electronic 24-Hour/7-Day ................................17
HOUR METERS—AC, DC, VIBRATORY
UWZ ...........................................................................29
FWZ ...........................................................................28
GZ ...........................................................................27
RZ ...........................................................................27
RESIDENTIAL PLUG-IN TIMERS
Electro-Mechanical .....................................................30
Electronic ....................................................................31
DEFINITE PURPOSE CONTACTORS ..................33-34
ACCESSORIES ..........................................................32
MODEL CODE INDEX................................................39
REPLACEMENT CROSS REFERENCE ....................40
COMPETITIVE CROSS REFERENCE..................37-38
APPLICATION GUIDE...........................................35-36
ELECTROMECHANICAL TIME CONTROLS
www.grasslin.com 201.825.96962
GM1SW-”X”-MV 120, 208/240, 277V SPDT 30
GMDSW-”X”-MV 120, 208/240, 277V DPDT 30
GM1QW-”X”-MV 120, 208/240, 277V SPDT 30
GMDQW-”X”-MV 120, 208/240, 277V DPDT 30
GM1ST-”X”-MV 120, 208/240, 277V SPDT 30
GMDST-”X”-MV 120, 208/240, 277V DPDT 30
GM1QT-”X”-MV 120, 208/240, 277V SPDT 30
GMDQT-”X”-MV 120, 208/240, 277V DPDT 30
GM MultiVolt Series24 Hour, 7 DayThe GM MultiVolt Series Time Controls are universal, electromechanicaltime switches which can be field configured for various supply voltages.The voltage selection includes 120VAC, 208/240VAC or 277VAC – all with-in the same unit! Selecting the appropriate supply voltage is easily achievedby positioning “Jumpers” on the printed circuit board assembly to the cor-responding locations (refer to detailed operating instruction sheet). Themechanism is mounted in a NEMA indoor or outdoor enclosure and isdesigned to control lighting, heating, air conditioning, pumps, motors, orother general purpose electrical circuits in residential, commercial, indus-trial and agricultural facilities. All GM models are available as “MechanismOnly” (–M) for installation in other enclosures or control panels.
Features• 120, 208/240 or 277VAC
• 30A, 2 HP @ 240V switch
• Indoor or outdoor enclosure
• Captive trippers with intervalof 15 minutes on 24 hourmodel (2 hours on 7-daymodel)
• Easy to set clock face timer
• Optional clear cover allowsviewing timer clock face with-out opening cover
SPECIFIERS GUIDE
Furnish and install a Grasslin GM ___ MultiVolt Series 24 hour (7 day) time switch with captive trippers and quartz (synchronous) drive. Input voltage shall be 120, 208/240 or277VAC on all units and SPDT (DPDT) contacts shall be rated at 30A, 2 HP @ 240V. To set the starting time and to provide time indication, the unit shall have an authentic clockface with hour and minute hands. Enclosure to be NEMA 1 (NEMA 3R raintight). Time switch shall contain an OFF/AUTO/ON manual override.
For Carry-over: The time switch shall have a quartz drive with 7 day reserve carry-over.
Model Code Timer Voltage Switch Amps
SPECIFICATIONS
Switch Rating: SPDT and DPDT switch models
NOTE: If loads are connected to both NC and NO contacts, both contacts are derated to 67% of the above values.
Wiring Connections:Screw clamp terminals accommodate up to two #10AWG wires.
Environmental Ratings:Operating Temperature Range: –40°F to 130°F, Synchronous Units
–20°F to 130°F, Quartz UnitsOperating Humidity: 0 to 95% non-condensing
Enclosures:Indoor: Plastic, gray, NEMA 1 or metal, gray, NEMA 1Outdoor: Plastic, gray, NEMA 3R raintightDimensions: 10” x 6.5” x 3.75” deep
Shipping Weight: 2 lbs.
Model Code Timer Voltage Switch Amps
Enclosure Options, Substitute the Following for “X”:“I” = NEMA 1 Indoor Enclosure, “IC” = NEMA 1 Indoor Enclosure with Clear Cover,
“O” = NEMA 3R Outdoor Enclosure, “OC” = NEMA 3R Outdoor Enclosure with Clear Cover,“IM” = NEMA 1 Indoor Metal Enclosure, “M” = Mechanism Only - No Enclosure
ORDERING DATA
MULTIVOLT
File #E83486
NO Contacts30A General Purpose/Res@277V1 HP; 96ALR, 20AFL @ 120V2 HP; 72ALR, 12AFL @ 240V15A, 1800W Tungsten @ 125V5A, 1250W Tungsten @ 250V20A Ballast @ 120-277V1A Pilot Duty @ 120-240V20A Resistive @ 28VDC
NC Contacts15A General Purpose/Res@250V6A General Purpose/Res@277V1/4 HP @ 125V, 1/2 HP @ 250V3A, 750W Tungsten @ 125-250V3A Ballast @ 120-277V1A Pilot Duty @ 120-240V15A Resistive @ 28VDC
24 Hour, Battery Backup (7 Day Reserve) 7 Day, Battery Backup (7 Day Reserve)
24 Hour 7 Day
Hot
(H)
(N)
Neutral
120VAC
LOAD
GM1 Digi
T
NC NO COM
10”
61/2”
GM1 MV Typical Wiring:
www.grasslin.com 201.825.9696 3
ELECTROMECHANICAL TIME CONTROLS
File #E83486
GMX Series24 Hour, 7 Day
The GMX Series Time Controls are universal, electromechanical timeswitches. They are a low cost alternative for applications that do notrequire more than 21A or 2HP @240VAC. The unit is mounted in aNEMA indoor or outdoor enclosure and is designed to control light-ing, heating, air conditioning, pumps, motors, or other general pur-pose electrical circuits in residential, commercial, industrial and agri-cultural facilities.
SPECIFIERS GUIDE
Furnish and install a Grasslin GMX ___ 24 hour (7 day) time switch with captivetrippers and quartz (synchronous) drive. Input voltage shall be 120V (24V, 240V,277V) and SPDT (DPDT) contacts shall be rated at 21A, 2 HP @ 240VAC. To setthe starting time and to provide time indication, the unit shall have an authenticclock face with hour and minute hands. Enclosure to be NEMA 1 (NEMA 3Rraintight). Time switch shall contain an OFF/AUTO/ON manual override.
For Carry-over: The time switch shall have a quartz drive with 7 day minimumreserve carry-over.
SPECIFICATIONS
SPDT Switch Rating:
21A Resistive @ 250VAC
1HP @ 120VAC
2HP @ 240VAC
16FLA, 96LRA, 120VAC
12FLA, 72LRA, 240VAC
1350W Tungsten @ 240V
Environmental Ratings:
Operating Temperature Range:
–40°F to 180°F, Synchronous Units
–20°F to 140°F, Quartz Units
Operating Humidity: 0 to 95% non-condensing
Wiring Connections:
Screw terminals for up to #12AWG wire
Enclosures:
Indoor: Plastic, gray, NEMA 1 or metal, gray, NEMA 1
Outdoor: Plastic, gray, NEMA 3R raintight
GMXSW-”X”-120 120, 60Hz SPDT 21GMXSW-”X”-240 208/240V, 60Hz SPDT 21GMXSW-”X”-24 24V, 60Hz SPDT 21GMXSW-”X”-277 277V, 60Hz SPDT 21
GMXQW-”X”-120 120, 50/60Hz SPDT 21GMXQW-”X”-240 208/240V, 50/60Hz SPDT 21GMXQW-”X”-24 24V, 50/60Hz SPDT 21
GMXST-”X”-120 120, 60Hz SPDT 21
GMXST-”X”-240 208/240V, 60Hz SPDT 21GMXST-”X”-24 24V, 60Hz SPDT 21
GMXST-”X”-277 277V, 60Hz SPDT 21
GMXQT-”X”-120 120, 50/60Hz SPDT 21
GMXQT-”X”-240 208/240V, 50/60Hz SPDT 21GMXQT-”X”-24 24V, 50/60Hz SPDT 21
Model Code Timer Voltage Switch Amps Model Code Timer Voltage Switch Amps
Enclosure Options, Substitute the Following for “X”:“I” = NEMA 1 Indoor Enclosure, “IC” = NEMA 1 Indoor Enclosure with Clear Cover,
“O” = NEMA 3R Outdoor Enclosure, “OC” = NEMA 3R Outdoor Enclosure with Clear Cover,“IM” = NEMA 1 Indoor Metal Enclosure
ORDERING DATA
24 Hour, Battery Backup 7 Day, Battery Backup
24 Hour 7 Day
Features• 21A, 2 HP @ 240V switch
• Indoor or outdoor enclosure
• Captive trippers with interval of 15 minutes on 24 hour model (2 hours on7-day model)
• Easy to set clock face timer
• Optional clear cover allows viewing timer clock face without opening cover
T
TO 120V LINE
TIMER NCNOCOM
1 2 3 4 5
H
NTO LOAD
GMX Typical Wiring:
ELECTROMECHANICAL TIME CONTROLS
www.grasslin.com 201.825.96964
Water Heater Time ControlWH-4 (24-Hour) and WH-7 (7-Day/Skip a day) Models
Grasslin’s water heater time switch is an universal electromechanical controller foroperating residential, commercial, and industrial water heaters up to 7500 Wattscapacity running at 208/240VAC. The unit is mounted in a NEMA indoor or outdoorenclosure.
Features• Saves energy by shutting heaters OFF during “off-peak” periods
• Indoor or outdoor enclosure
• Captive trippers with interval of 15 minutes on 24 hour model (2 hours on7-day model)
• Easy to set clock face timer
• Manual Override
SPECIFIERS GUIDEFurnish and install a Grasslin WH ___ Water Heater Time Control with captivetrippers and quartz (synchronous) drive. Input voltage shall be 208/240VACon all models. Contacts shall be (DPDT) rated at 30A, 7500 Watts @ 240VAV.To set the starting time and to provide time indication, the unit shall have anauthentic clock face with hour and minute hands. Enclosure to be NEMA 1 or(NEMA 3R rain-tight). Time switch shall contain an OFF/AUTO/ON manualoverride.
SPECIFICATIONS
Input Voltage: 208/240VAC
Switch rating: DPDT Model; 7500 watts @ 240V / single phase; 12000watts @ 240V / 3 phase
Normally Open Contacts: 30A Resistive @ 277V
Normally Closed Contacts: 15A Resistive @ 250V
Note: If loads are connected to both NC and NO contacts, bothcontacts are de-rated to 67% of the above values.
Environmental Ratings: Ambient Temperature: -40º F to 130º FHumidity: 0-95% RH, Non-condensing
Wiring Connections:Screw clamp terminals for up to 2 AWG #10 wires per position.
File #E83486
L1
(L1)
L2
(L2)
240VAC
LOAD
T
NC NO COM NC2 COM2NO2
WH-4 24 hour DPDT 30A 208-240/60HzWH-7 24 hour, Skip-a-day, 7 day DPDT 30A 208-240/60Hz
Model Program Switch Amps Voltage/Frequency
ORDERING DATA
WH Typical Wiring:
www.grasslin.com 201.825.9696 5
ELECTROMECHANICAL TIME CONTROLS
STuZ–24 STuZH–24 QTuZH–24 24VAC SPDT 21A 15 min. ON 1/4 hr.STuZ–120 STuZH–120 QTuZH–120 120VAC SPDT 21A 15 min. ON 1/4 hr.STuZ–240 STuZH–240 QTuZH–240 208/240VAC SPDT 21A 15 min. ON 1/4 hr.
STuZH–277 277VAC SPDT 21A 15 min. ON 1/4 hr.
SWuZ–24 SWuZH–24 QWuZH–24 24VAC SPDT 21A 2 hr. ON 2 hr.SWuZ–120 SWuZH–120 QWuZH–120 120VAC SPDT 21A 2 hr. ON 2 hr.SWuZ–240 SWuZH–240 QWuZH–240 208/240VAC SPDT 21A 2 hr. ON 2 hr.
SWuZH–277 277VAC SPDT 21A 2 hr. ON 2 hr.
Optional Enclosures–See Page 25 **Quartz units also operate on DC voltages down to 12VDC
MIL 72 SeriesFor Panel Mounting24 Hour, 7 DayTime based control of lighting, ventilating, heating, cooling or otherelectrical loads in commercial and industrial applications. The MIL 72time switches are available with a 24-hour or 7-day program dial witha SPDT switch (form “C” contact). The MIL 72A series is intended forsurface mounting. The control is completely enclosed in a plastichousing and includes a terminal cover and sub-base for installationand hard wiring. The MIL 72E is intended for flush (panel) mounting.All units are supplied with a clear plastic cover.
Features• Synchronous drive or quartz drive with battery backup
• 21A SPDT switch
• Captive trippers with interval as low as 15 minutes
• With or without 3-way override
• Real clock face
• Surface, flush, or DIN rail mount
SPECIFICATIONS
Size: MIL 72A: 2.83” x 4.0” x 2.06”MIL 72E: 2.83” x 2.83” x 1.36”
Power Consumption: 1VASwitch: SPDT dry contacts, silver
cadmium oxide
Switch Rating: 21A 250V Resistive1350 Watts Tungsten1HP @ 120V2HP @ 240V16FLA, 96LRA–120VAC12FLA, 72LRA–240VAC
Minimum Switching Current:100ma, 20V
Ambient Temperature Range:–40°F to 180°F synchronous units–14°F to 131°F quartz units
Wiring Connections: ScrewTerminals Suitable for #10 to#24AWG
INSTALLATIONStand Alone: With indoor or outdoor
enclosurePanel: Surface, flush, or DIN rail
mounting
ORDERING DATA
Synchronous Quartz–7 Day Carry-Over** Switch Minimum EventWithout With 3 Way Input Rating On/Off On/OffOverride Override With 3 Way Override Voltage 250V Res. Time Time
IN OPTIONALENCLOSURESLISTED
®
UL FILE: E83486CSA FILE: LR52379
Complete Model Number = MIL 72A or E followed by suffix code and voltageExample: MIL 72A STuZ–24
MIL 72A–Surface MountMIL 72E–Flush Mount 7 DAY TIME CONTROL
MIL 72A–Surface MountMIL 72E–Flush Mount24 HOUR TIME CONTROL
SPECIFIERS GUIDEFurnish and install a Grasslin MIL 72____ 24 hour (7 day) time switch with 15min. (2 hour) interval captive trippers and quartz (synchronous) drive. Inputvoltage shall be 120V (24V, 240V, 277V) and SPDT switch contacts shall besilver cadmium oxide rated at 21A, resistive, 2HP @ 250VAC. To set the start-ing time and to provide time indication, the unit shall incorporate an authenticclock face. Installation for surface, (flush, DIN rail or within indoor or outdoorenclosure) mounting. Time switch shall contain an OFF/AUTO/ON override.
For Carry-over: The time controls shall have a quartz drive with 7 day reservecarry-over from a rechargeable battery.
3-way manualoverride switch
Off position with trippers pushed in(trippers pushed out will close contacts3 and 4 and turn load on)
I = permanent ON= automatic
0 = permanent OFF
MIL 72 Typical Wiring:
www.grasslin.com 201.825.96966
ELECTRONIC TIME CONTROLS
GMDdigi20-”X”-120 120V 50/60Hz 20 DPDT 30GMDdigi20-”X”-240 208/240V 50/60Hz 20 DPDT 30GMDdigi20-”X”-277 277V 50/60Hz 20 DPDT 30GM1digi42-”X”-120 120V 50/60Hz 42 SPDT 30GM1digi42-”X”-240 208/240V 50/60Hz 42 SPDT 30GMDdigi42-”X”-120 120V 50/60Hz 42 DPDT 30GMDdigi42-”X”-240 208/240V 50/60Hz 42 DPDT 30
GM digi Series24 Hour, 7 Day(GM Digi 42 models have automatic daylight time changeover and Holiday programming)
The GM Digi Series is a universal electronic time switch mounted in a NEMAindoor or outdoor enclosure. Intended for control of lighting, heating, air con-ditioning, pumps, motors, or other purpose general electrical circuits in resi-dential, commercial, industrial and agricultural facilities.
Features• 30A, 2 HP @ 240V switch
• Indoor or outdoor enclosure
• Rechargeable battery backup with 1-4weeks reserve carry-over
• Optional clear cover allows viewingtimer display without opening cover
• GM digi 42 models have holiday pro-gram and automatic daylight t imechangeover
SPECIFICATIONS
Switch Rating: SPDT and DPDT switch models
NOTE: If loads are connected to both NC and NO contacts, both con-tacts are derated to 67% of the above values.
Wiring Connections:Screw clamp terminals accommodate up to two #10AWG wires.
Environmental Ratings:Operating Temperature Range: –20°F to 131°F (–29°C to 55°C)Operating Humidity: 0 to 95% non-condensing
Programming:Up to 42 programs per channel: consist of one or more days of theweek, and an ON or OFF time. Shortest switching time 1 minute.
Enclosures:Indoor: Plastic, gray, NEMA 1 or metal, gray, NEMA 1Outdoor: Plastic, gray, NEMA 3R raintightDimensions: 10” x 6.5” x 3.75” deep
Shipping Weight: 2 lbs.
ORDERING DATA
File #E83486
NO Contacts30A General Purpose/Res@277V1 HP; 96ALR, 20AFL @ 120V2 HP; 72ALR, 12AFL @ 240V15A, 1800W Tungsten @ 125V5A, 1250W Tungsten @ 250V20A Ballast @ 120-277V1A Pilot Duty @ 120-240V20A Resistive @ 28VDC
NC Contacts15A General Purpose/Res@250V6A General Purpose/Res@277V1/4 HP @ 125V, 1/2 HP @ 250V3A, 750W Tungsten @ 125-250V3A Ballast @ 120-277V1A Pilot Duty @ 120-240V15A Resistive @ 28VDC
Model Code Timer Voltage Prog. Switch Amps
Enclosure Options, Substitute the Following for “X”:“I” = NEMA 1 Indoor Enclosure, “IC” = NEMA 1 Indoor Enclosure with Clear Cover,
“O” = NEMA 3R Outdoor Enclosure, “OC” = NEMA 3R Outdoor Enclosure with Clear Cover,“IM” = NEMA 1 Indoor Metal Enclosure, “M” = Mechanism Only - No Enclosure
One Channel, 24hr./7 day
C.E.C. CERTIFIED TITLE 24, PART 6
ON ALL DIGI 42 MODELS
SPECIFIERS GUIDEFurnish and install a Grasslin GM ___ electronic time switch. This one channel control shallhave 24 hour and 7 day programming and include block programs for different weekdayschedules. The LCD shall display time of day in AM/PM format and provide load status indi-cation. A daylight time adjustment key shall also be provided. The time switch will be pro-grammable to the minute and also offer a manual override for ON or OFF to the next sched-uled event or for permanent ON/AUTO/OFF.The SPDT (DPDT) relay output will be rated for30A, 2HP @ 240VAC. Carry-over shall be provided for a minimum of 7 days with a built-inrechargeable NiCad battery which need not be replaced. Enclosure to be NEMA 1 (NEMA3R raintight).
1 week reserve carryover
4 weeks reserve carryover
GM1 digi 20 SPDT 20 programsGMD digi 20 DPDT 20 programs
GM1 digi 42 SPDT 42 programsGMD digi 42 DPDT 42 programs
}
}
Hot
(H)
(N)
Neutral
120VAC
LOAD
GM1 Digi
T
NC NO COM
GM1 Digi Typical Wiring:
Two Channel
GMX2digi42-”X”-120 120V 50/60Hz 42 (2) SPDT 16GMX2digi42-”X”-240 208/240V 50/60Hz 42 (2) SPDT 16GMX2digi42-”X”-24 24V 50/60Hz 42 (2) SPDT 16
GMXdigi20-”X”-120 120V 50/60Hz 20 SPDT 16GMXdigi20-”X”-240 208/240V 50/60Hz 20 SPDT 16GMXdigi20-”X”-24 24V 50/60Hz 20 SPDT 16GMXdigi20-”X”-277 277V 50/60Hz 20 SPDT 16GMXdigi42-”X”-120 120V 50/60Hz† 42 SPDT 16GMXdigi42-”X”-240 208/240V 50/60Hz† 42 SPDT 16GMXdigi42-”X”-24 24V 50/60Hz† 42 SPDT 16
File #E83486
GMX digi Series24 Hour, 7 Day
The GMX Digi Series is a universal electronic time switchmounted in a NEMA indoor or outdoor enclosure. They are alow cost alternative for applications that do not require morethan 16A Intended for control of lighting, heating, air condi-tioning, pumps, motors, or other purpose general electricalcircuits in residential, commercial, industrial and agricultur-al facilities.
SPECIFICATIONS
SPDT Switch Rating:
16A Resistive @ 250VAC
1000W Tungsten @ 250VAC
Shortest Switching Time: 1 minute
Environmental Ratings:
Operating Temperature Range:
–20°F to 140°F
Operating Humidity: 0 to 95% non-condensing
Wiring Connections:
Screw terminals for up to #12AWG wire
Enclosures:
Indoor: Plastic, gray, NEMA 1 or metal, gray, NEMA 1
Outdoor: Plastic, gray, NEMA 3R raintight
ORDERING DATA
Model Code Timer Voltage Prog. Switch Amps
Note: 6V & 12VDC Models Available
Model Code Timer Voltage Prog. Switch Amps
Enclosure Options, Substitute the Following for “X”:“I” = NEMA 1 Indoor Enclosure, “IC” = NEMA 1 Indoor Enclosure with Clear Cover,
“O” = NEMA 3R Outdoor Enclosure, “OC” = NEMA 3R Outdoor Enclosure with Clear Cover,“IM” = NEMA 1 Indoor Metal Enclosure
C.E.C. CERTIFIEDTITLE 24, PART 6
ON ALL DIGI 42 MODELS
www.grasslin.com 201.825.9696 7
ELECTRONIC TIME CONTROLS
Features• A low cost alternative for applications that require only 16A switching
• 24 hour or 7 day programming with accuracy to the second
• Easy programming; minimal keys and programming steps
• Selectable blocks of weekdays or weekends for quick programming
• Rechargeable battery backup with 1~4 weeks reserve carry-over
• Manual override provides for either temporary or continuous ON or OFF state
• Replaces Intermatic, Tork, and Paragon time switches
• Indoor or outdoor enclosure
• Optional clear cover allows viewing timer display without opening cover
• GMX digi 42 models have holiday program and automatic daylight time changeover
SPECIFIERS GUIDEFurnish and install a Grasslin GMX digi ___ 120 (24, 240, 277) volt electronic time switch. This one (two) channel control shall have 24 hour and 7 day programming andinclude block programs for different weekday schedules. The LCD shall display time of day in AM/PM format and provide load status indication. A daylight time adjustmentkey shall also be provided. The time switch will be programmable to the minute and also offer a manual override for ON or OFF to the next scheduled event or for perma-nent ON/AUTO/OFF. The SPDT relay output will be rated for 16A @ 240VAC. Carry-over shall be provided for a minimum of 7 days with a built-in rechargeable NiCad bat-tery which need not be replaced. Enclosure to be NEMA 1 (NEMA 3R raintight).
T
TO 120V LINE
TIMER NCNOCOM
1 2 3 4 5
H
NTO LOAD
GMX Digi Typical Wiring:
ELECTRONIC TIME CONTROLS, 1 CHANNEL
www.grasslin.com 201.825.96968
Digi20A – 120 120V, 50/60Hz Surface or DIN Rail 20 140 SPDT, 16A, 250VDigi20A – 240 208/240V, 50/60Hz Surface or DIN Rail 20 140 SPDT, 16A, 250VDigi20A – 24 24V, 50/60Hz Surface or DIN Rail 20 140 SPDT, 16A, 250VDigi20A – 277 277V, 50/60Hz Surface or DIN Rail 20 140 SPDT, 16A, 250VDigi42A – 120 120V, 50/60Hz Surface or DIN Rail 42 294 SPDT, 16A, 250VDigi42A – 240 208/240V, 50/60Hz Surface or DIN Rail 42 294 SPDT, 16A, 250VDigi42A – 24 24V, 50/60Hz Surface or DIN Rail 42 294 SPDT, 16A, 250V
Digi20E – 120 120V, 50/60Hz Flush Panel 20 140 SPDT, 16A, 250VDigi20E – 240 208/240V, 50/60Hz Flush Panel 20 140 SPDT, 16A, 250VDigi20E – 24 24V, 50/60Hz Flush Panel 20 140 SPDT, 16A, 250VDigi20E – 277 277V, 50/60Hz Flush Panel 20 140 SPDT, 16A, 250VDigi42E – 120 120V, 50/60Hz Flush Panel 42 294 SPDT, 16A, 250VDigi42E – 240 208/240V, 50/60Hz Flush Panel 42 294 SPDT, 16A, 250VDigi42E – 24 24V, 50/60Hz Flush Panel 42 294 SPDT, 16A, 250V
ORDERING DATA
File #E83486
Digi 20, Digi 42 Series24 Hour, 7 Day
Time based control of lighting, ventilating, heating, cooling or other electricalloads in commercial and industrial applications. These one channel timeswitches are programmable for 24-hour or 7-day schedules. The Digi 42 offersan “8th day” or holiday schedule. The Digi 20A or Digi 42A are intended foreither surface or DIN rail mounting. Both models are completely enclosed in aplastic housing and includes a terminal cover and sub-base for installation andhard wiring. The Digi 20E or Digi 42E are intended for flush mounting. Bothmodels are supplied with a clear plastic snap-on dust cover.
Features• 24 hour or 7 day programming with accuracy to the second
• Easy programming; minimal keys and programming steps
• Unique “Circular Programming” with large keys is easier to use
• Selectable blocks of weekdays or weekends for quick programming on Digi 20, anycombination of days on Digi 42
• Holiday program on Digi 42 may be sched-uled a week in advance for one or moredays
• Rechargeable battery backup with 1-4weeks reserve carry-over
• Manual override provides for either tempo-rary or continuous ON or OFF state, withstatus displayed in large LCD
• Digi 42 models have automatic daylighttime changeover
• 24V models will operate on AC or DC
SPECIFICATIONS Digi 20 Digi 42Channels 1 1Programs 20 42Holiday Program No YesReserve Carryover; min. 1 week 2 weeksAutomatic Spring/Fall DaylightTime Changeover No Yes
TECHNICAL DATAOutput: 1 SPDT relay with dry contactsSwitching Capacity: 16A Resistive @ 277VAC
1000W Tungsten @ 240VACInput Draw: 4VAShortest Switching Time: 1 minuteAccuracy: Less than ±4 minutes per year deviationAmbient Temperature: 0°F to 140°F (–18°C to 60°C)Ambient Humidity: 0 to 95% RH, non-condensingSelectable AM/PM or 24 hr. (military) time LCD displayOne Key Daylight Time Changeover (automatic on Digi 42)Manual 3-Way Override: Temporary or permanent ON or
OFF status indication in LCD display.Wiring Connections: “A” Models: screw terminals for
#10 to #24 AWG wire“E” Models: 1/4” quick connects
Setpoint Maximum Weekly Relay OutputModel Code Timer Voltage Mounting Programs On/Off Events Resistive Rating
Digi 42A and E also available for 12VDC input.
Digi 42A
Digi 20E
For models in NEMA indoor or outdoor enclosures, see GMX Series, page 7 (24V models will operate on AC or DC)
C US
C.E.C. CERTIFIED TITLE 24, PART 6ON ALL DIGI 42 MODELS
Digi 42
COM NO NC
M
Hot Neutral
1
120VAC
2 4 5
LOAD
3
Digi 42 Typical Wiring:
SPECIFIERS GUIDEFurnish and install a Grasslin Digi 20 (Digi 42) ___ electronic time switch. This 1 channel control shall have 24 hour and 7 day programming and also offer 10 (21) ON and 10(21) OFF setpoint programs and include 4 block programs (allow selection of any combination of days) for different weekday schedules. The LCD shall display time of day inAM/PM or military time format and provide load status indication. A daylight time adjustment key shall also be provided. The time switch will be programmable to the minute andalso offer a manual override for ON or OFF to the next scheduled event or for permanent ON/OFF/Automatic. (The Digi 42 shall provide a 8th day or “Holiday” program which maybe activated to begin on a specific day up to a week in advance, and continue from 1 to 99 days, selectable by the user.) The SPDT relay output will be rated for 16A Resistive@ 277VAC. Reserve shall be provided for a minimum of 7 days with built-in rechargeable batteries which need not be replaced. The time switch shall be surface, DIN rail or flushmountable or shall be available with a NEMA 1 indoor or NEMA 3R outdoor enclosure.
www.grasslin.com 201.825.9696 9
ELECTRONIC TIME CONTROLS, 2 CHANNEL
Digi42/2 – 120 120V, 50/60Hz Flush or Surface 42 294 (2) SPDT, 16A, 250VACDigi42/2 – 240 240V, 50/60Hz Flush or Surface 42 294 (2) SPDT, 16A, 250VACDigi42/2 – 24 24V, 50/60Hz Flush or Surface 42 294 (2) SPDT, 16A, 250VAC
Digi 42/224 Hour, 7 Day
Time based control of 2-circuit lighting, ventilating, heating, coolingor other electrical loads in commercial and industrial applications.The Digi 42/2 time switches are programmable for 24-hour or 7-dayschedules as well as an “8th day” or holiday schedule. Each channelcan operate independently or combined.
Features• 24 hour or 7 day programming with resolution to the minute and accuracy to the
second
• Large keys ease programming
• Unique circular programming pattern and minimal steps simplify programming
• Automatic Daylight Time changeover in spring and fall eliminates need to man-ually change the time
• Holiday, or “8th day” program may be scheduled a week in advance for one ormore days
• Each channel may be programmed separately, or both together
• Automatically recharged NiCad battery maintains program and display for twoweeks or more
• Manual override for each channel provides for either temporary or continuousON or OFF state, with status displayed in large LCD
SPECIFICATIONSOutput Switches: Two SPDT relays with dry contacts
Switch Capacity: 16A General Purpose, 125-250VAC
1000W Tungsten, 250V
500W Tungsten, 125V
N.O. Contact: 1HP, 240VAC; 1/2HP, 120VAC
Pilot Duty: 720VA, 120-240VAC
N.C. Contact: 3/4HP, 240VAC; 1/3HP, 120VAC
Pilot Duty: 360VA, 120-240VAC
Input Power: 4.4VA
Shortest Switching Time: 1 minute
Accuracy: Less than ±4 minutes per year deviation
Ambient Temperature: 0°F to 140°F (–18°C to 60°C)
Ambient Humidity: 0 to 95% RH, non-condensing
Selectable AM/PM or 24 hr. (military) time display
Selectable completely automatic or one key manual daylight timechangeover
Manual 3-Way Override: Temporary or permanent ON or OFF; statusindication in LCD display
Wiring Connections: Screw terminals #12 to #24AWG
Size: 2.83” x 2.83” square face, x 2.28” deep
UL and Canadian UL Recognized: File E83486
ORDERING DATA
C
Setpoint Maximum Weekly Relay OutputModel Code Timer Voltage Mounting* Programs On/Off Events General Purpose Rating
*For DIN rail mounting, order: MB-DIN Rail Mounting Base
File #E83486
C.E.C. CERTIFIED TITLE 24, PART 6
ON ALL DIGI 42 MODELS
(L1) (L2)
240VAC
LOAD
GMD Digi
T
NC NO COM NC2 COM2NO2
Digi 42/2 Typical Wiring:
SPECIFIERS GUIDEFurnish and install a Grasslin Digi 42/2 electronic time switch. This two channel control shall have 24 hour and 7 day programming and also offer 21 ON and 21 OFF setpointprograms and allow selection of any combination of days for different weekday schedules. The LCD shall display time of day in AM/PM or military time format and provideload status indication. Selectable automatic or manual daylight time changeover shall be provided. In automatic mode, the time switch shall automatically advance the timeby 1 hour at 2AM on the first Sunday of April, and set back the time 1 hour at 2AM on the last Sunday of October. The time switch shall be programmable to the minute andalso offer a manual override for ON or OFF to the next scheduled event or for permanent ON/OFF/Auto. A 8th day or “Holiday” program shall be provided which may be acti-vated to begin on a specific day up to a week in advance, and continue from 1 to 99 days, selectable by the user. The SPDT relay outputs will be rated for 16A GeneralPurpose, 1HP at 240V, and 16A General Purpose, 1/2HP at 120V as well as pilot duty of 720VA. Reserve shall be provided for a minimum of 14 days with a built-in recharge-able battery which need not be replaced. The time switch shall be surface or flush panel mountable with a DIN rail mounting base optional, or shall be available with a NEMA1 indoor or NEMA 3R outdoor enclosure.
ELECTRONIC TIME CONTROLS, 1, 2 & 4 CH.
www.grasslin.com 201.825.969610
talento400 & 800 Series24-Hour, 7-Day, 365-DayElectronic Time Controls
Features• 1, 2 & 4 channels
• Automatic leap year and daylight savings adjustment
• “Pulse” and “Cycle” programming
• Lithium battery backup for clock
• EEPROM Non-Volatile program memory
• Astronomical function
talento 894
talento 471
MON
•TUE
•W
ED•THU•FRI•
SAT
•SU
N •
7DAY
JAN • FEB•
MA
R•
APR
•M
AY•JUN•JUL•AUG•
SEP
•O
CT•
NOV •DEC•
365DAY
(in optionalenclosure)
C US
The talento series electronic time switches provide time-of-day control for light-ing, heating, air conditioning, pumps, motors or general electrical circuits. The“400” series are 24-hour/7-day controls, while the “800” series units offer 365-day programming with holiday capability through the year 2095.
All models offer automatic leap year and daylight savings adjustment. Thesefeatures are activated when the user enters the current date and respective daylight savings time change-over dates. Fromthat point on, daylight change-over dates will never have to be entered again.
A LCD indicates the load status, time-of-day, weekday and on the “800” series, the date. The units can be surface mounted,mounted to a standard DIN rail or within a Grasslin enclosure for stand-alone installations. Enclosure options include indooror outdoor plastic (with solid or clear cover) or indoor metallic.
In addition to the conventional On/Off programming format, these units offer pulse and cycle functions. A pulse is simply anon or off event with a duration of one or more seconds. The cycle function provides for a repeating on event within a selec-table total cycle. Both the on duration and the total cycle duration are independently programmable in minutes or seconds.In addition, the cycle function can be set to repeat indefinitely or to occur within a time and/or date range.
“On”
“Total”
On
Off
Cycle Programming
The “On” and “Total” time are independently pro-grammable in minutes or seconds
Start Time End Time
Remote PC ProgrammingThe talento 800 series can be programmed from a PC utilizing the optionaltalento dialog set. The set includes Windows®-based software, the taxxihand-held programmer, CD Rom, interconnect cable and instructions.
The software contains a schedule of fixed and floating holidays that can beselected, as required, for the particular application. Floating holidays willautomatically repeat on the correct date, year after year. Thus, all fixed andfloating holidays need only be programmed once. In addition, an astronomical programis included which will automatically adjust the program schedule to follow the changingsunrise and sunset times.
Once the programming is completed on the PC, it is transferred to the taxxi hand pro-grammer from which programs are downloaded into one or more installed talento 800series time controls. The taxxi can store up to four independent programs and can alsoupload a program from the talento into a PC for review or editing. taxxi
Remote PC Programming
www.grasslin.com 201.825.9696 11
ELECTRONIC TIME CONTROLS, 1, 2, 4 & 8 CH.
Features• Eight channel electronic time switch
• 7 day programming
• 2 ON and 2 OFF settings per day
• On-Off-Auto Override for each channel
• Holiday “OFF” provision
• Indoor/Outdoor enclosure w/clear door
• Battery backup for 1 month
• 10 Amp, SPDT switching
SPECIFICATIONS
Input: 120V 50/60 Hz, 12VA power drawOutput Switches: 6 SPDT, 2 SPST (NO)Switching Capacity: 10A Resistive, 120-240VACShortest Switching Time: 1 minuteAmbient Temperature: 14°F to 122°F (–10°C to 50°C)Ambient Humidity: 0 to 95% RH, non-condensingManual 3-way Override: Auto-On-Off“ON” or “OFF” status indicator for each channelWiring Connections: Screw terminals, 12-24AWGSize: 8.38 (213mm) x 7.08” (180mm) x 4.5” (114mm)
SRS 38008 CHANNEL, 7 DayTime of day ON/OFF control of 8 circuits of HVAC systems, zoneheating, industrial processes, alarm systems, lighting, fans, pumpsor other loads in commercial, industrial, institutional, and agricul-tural facilities. A simple and effective energy management systemfor small and mid-sized office buildings, schools, banks, malls, andgovernment buildings.
Specifications & Features 471 472 891 892 894
Power Supply 24VAC/DC, 120VAC, 240VACSwitch Rating 16A @ 250VACSwitch Output Isolated SPDT (1 per channel)Channels 1 2 1 2 4Battery Backup Lithium, 3 Years Lithium, 6 YearsMinimum Switching Interval 1 SecondSwitch Program 24-Hour, 7-Day 24-Hour, 7-Day, 365-DayProgram Capacity 30 40 400 Operating Modes Auto., Temporary On, Temporary Off, Fixed On, Fixed OffPulse Programming YesCycle Programming YesDaylight Savings Time Change-over Manual or AutomaticLCD Display Time, Day, Output Status Time, Day, Date, Output Status
SPECIFIERS GUIDE800 Series
The contractor shall furnish and install a Grasslin talento 894, 4 channel (892, 2 channel / 891, 1 channel) electronic time switch. Each channel shall be independent-ly programmable. A total of 400 events shall be provided. The time switch shall offer daily, weekly or annual programming capability with up to 99 separate holiday peri-ods of any duration and priority. Three types of switching commands shall be provided; on/off, pulse and cycle. Automatic or user selectable daylight savings timechange-over shall be incorporated through the year 2095. An optional Windows®-based software program shall be available for remote programming capability. It shallprovide full graphic indication of the switching schedule. It shall also include a database of fixed and floating holidays. Floating holidays will automatically repeat eachyear on the correct date. An astronomical program shall be included which will automatically adjust the switch event schedule according to the changing sunrise andsunset times. A LCD shall be provided to indicate the current time, date, switch contact status and program schedule. A replaceable lithium battery shall be provided tomaintain the current time and date in the event of a power failure for up to six (6) years; the switch program shall be stored in non-volatile (EEPROM) memory. The SPDTswitch contacts shall be rated for 16A at 250VAC. Time switch supply voltage shall be 24VAC/DC or 120VAC or 240VAC. The time switch shall be capable of surface orDIN rail mounting or it can be provided in an indoor or outdoor (NEMA 1 or 3R) enclosure. It shall be UL, C-UL recognized, and UL/C-UL listed in optional enclosure.
400 Series
The contractor shall furnish and install a Grasslin talento 472, 2 channel (471, 1 channel) electronic time switch. Each channel shall be independently programmable. Atotal of 40 (30, 471) events shall be provided. The time switch shall offer daily or weekly programming. Three types of switching commands shall be provided; on/off, pulseand cycle. Automatic or user selectable daylight savings time change-over shall be incorporated through the year 2095. A LCD shall be provided to indicate the currenttime, day, switch contact status and program schedule. A lithium battery shall be provided to maintain the current time and date in the event of a power failure for up tothree (3) years; the switch program shall be stored in non-volatile (EEPROM) memory. The SPDT switch contacts shall be rated for 16A at 250 VAC. Time switch supply volt-age shall be 24VAC/DC or 120VAC, or 240VAC. The time switch shall be capable of surface or DIN rail mounting or it can be provided in an indoor or outdoor (NEMA 1 or3R) enclosure. It shall be UL, C-UL recognized, and UL/C-UL listed in optional enclosure.
OEM ELECTROMECHANICAL TIMER MODULES
www.grasslin.com 201.825.969612
KM2 STuH 24 hr. 20 minutes 20 minutes SPDT 21A Res.KM2 SWuH 7 day 2 hr. 20 minutes 2 hr. 20 minutes SPDT 21A Res.
FM/1 STuZ (synchronous) 24 hr. No 15 minutes 15 minutes SPDT 21A Res.FM/1 SWuZ (synchronous) 7 day No 2 hours 2 hours SPDT 21A Res.
FM/1 QTuZ (quartz) 24 hr. 7 day 15 minutes 15 minutes SPDT 21A Res.FM/1 QWuZ (quartz) 7 day 7 day 2 hours 2 hours SPDT 21A Res.
†For 3-way override switch: Add “H” Available with 24V, 120V, 240V, 277VAC input For Enclosure Options–See Page 25 Quartz also available with 12V, 30V, 60V, or 120VDC input
KM2 Series24 Hour, 7 DayThe KM/2 series modules are designed to fit into tight locations. It offers up to 21Aswitching designed for control of heating, ventilating, air conditioning, refrigeration,lighting, security, circulating pumps, spas or any electrical load requiring 24-hour or7- day scheduling.
OPERATING FEATURES Switch Output
Switch Program Program On/Off Every Minimum On/Off Time Type Rating
SPECIFICATIONS:Size: 1.67” x 2.64” x 1.67”Power Consumption: 1VASwitch Rating: SPDT
Resistive: 21A @ 250VMotor: 1HP @ 125VAC
2HP @ 250VACInductive: 8A @ 250VACTungsten: 1350W
Wiring Connections: 1/4” quick-connects
The FM/1 series modules are designed to be placedinside a machine control panel, circuit board, or otherequipment. It offers up to 21A switching designed forcontrol of heating, ventilating, air conditioning, refriger-ation, lighting, security, circulating pumps, spas or anyelectrical load requiring 24-hour or 7-day scheduling.
SPECIFICATIONS:Size: 2.36” x 2.36” x 1.25”
Supply Voltage: 24, 120, 240VAC
Power Consumption: 1VA
Switch Rating: SPDT
Resistive: 21A
Tungsten: 1350W
Inductive: 1HP @ 120VAC
2HP @ 240VAC
Wiring Connections: 1/4” quick-connects
INSTALLATION:Stand Alone: With indoor or out-door enclosure
Panel: Surface mounting
Switch Program Minimum Switch OutputProgram Carry-Over On/Off Every On/Off Time Type Rating
KM 2 STuH
UL FILE:E83486
CSA FILE:LR52379
UL FILE:E83486
CSA FILE:LR52379
FM/1 Series 24 Hour, 7 Day
ORDERING DATA†
ORDERING DATA
Features• Authentic clock face
• 21A SPDT switch
• Captive Trippers
• 1/4” quick terminals
Features• Very small and compact, fits anywhere
• On/Auto/Off manual switch standard
• Captive trippers for easy programming
• 1/4” quick terminals
FM/1 Typical Wiring:
KM/2 TypicalWiring:
www.grasslin.com 201.825.9696 13
OEM ELECTRONIC TIMER MODULES
FM/1 digi 20–120 120V 50/60Hz 24 hr./7 day 20 140 No 1 week SPDT 16AFM/1 digi 20–240 240V 50/60Hz 24 hr./7 day 20 140 No 1 week SPDT 16AFM/1 digi 20–24 24V 50/60Hz 24 hr./7 day 20 140 No 1 week SPDT 16AFM/1 digi 20–277 277V 50/60Hz 24 hr./7 day 20 140 No 1 week SPDT 16A
FM/1 digi 42–120 120V 50/60Hz 24 hr./7 day 42 294 Yes 2 weeks SPDT 16AFM/1 digi 42–240 240V 50/60Hz 24 hr./7 day 42 294 Yes 2 weeks SPDT 16AFM/1 digi 42–24 24V 50/60Hz 24 hr./7 day 42 294 Yes 2 weeks SPDT 16A
FM/1 digi 2024 Hour, 7 Day
FM/1 digi 4224 Hour, 7 DayThe FM/1 digi 42 is a compact electronic 24 hour/7 day time switch module,with heavy duty relay contacts for switching low or line voltage loads.Applicable for time of day control of pumps, fans, heaters, HVAC control cir-cuits, lighting, machinery and many other types of commercial, industrial, andagricultural equipment. All digi 42 models offer holiday programming andautomatic daylight savings time changeover. All models feature large keys withunique “circular programming” for easy programming, a large LCD displayand battery backup.
SPECIFICATIONS
Switch Rating: SPDT16A Resistive @ 277VAC1000W Tungsten @ 240VAC
Input Draw: 4VAInput Frequency: 50/60HzShortest Switching Time: 1 minuteAmbient Temperature: 0°F to 140°F (–18°C to 60°C)Ambient Humidity: 0 to 95% RH, non-condensingWiring Connections: 1/4” quick connectsUL and Canadian UL File E 83486
SPECIFICATIONS
Switch Rating: SPDT16A Resistive @ 277VAC1000W Tungsten @ 240VAC
Input Draw: 4VAInput Frequency: 50/60HzShortest Switching Time: 1 minuteAmbient Temperature: 0°F to 140°F (–18°C to 60°C)Ambient Humidity: 0 to 95% RH, non-condensingWiring Connections: 1/4” quick connectsUL and Canadian UL File E 83486
Switch Max. Weekly Holiday ReserveModel Input Voltage Program Programs On/Off Events Program Carryover Relay Output
FM/1 digi 42 also available for 12VDC input, 24V models are AC/DC.
C
C
ORDERING DATA
C.E.C. CERTIFIED TITLE 24, PART 6
ON ALL DIGI 42 MODELS
Features• 20 programs, up to 140 events
per week
• Easy to program with large keys
• 16 Amp @ 277V SPDT switching
• Capacitor backup with 5 day car-ryover
• Manual overridev
Features• A u t o m a t i c D a y l i g h t
Savings Time Changeover
• 42 programs, up to 294events per week
• Holiday programming
• 16 Amp @ 277V SPDTswitching
• Rechargeable bat terybackup with carryover ofover 4 weeks
The FM/1 digi 20 is a compact electronic 24 hour/ 7 daytime switch module with heavy duty relay contacts forswitching low or line voltage loads. Applicable for time ofday control of pumps, fans, heaters, HVAC control circuits,lighting, machinery and many other types of commercial,industrial, and agricultural equipment. The FM/1 digi 20features large keys with unique “circular pattern” for easyprogramming, an easy-to-read LCD display and capacitorbackup to retain program memory during power outages.
SPECIFIERS GUIDEFurnish and install a Grasslin FM/1 digi 20-___ electronic time switch.This one circuit control shall have 24 hour and 7 day programmingand also offer 10 ON and 10 OFF setpoints and include 4 block pro-grams for different weekday schedules. The LCD shall display time ofday in AM/PM or military time format and provide load status indica-tion. A daylight time adjustment key shall also be provided. The timeswitch will be programmable to the minute and also offer a manualoverride for ON or OFF to the next scheduled event or for permanentON/OFF/Automatic. The SPDT relay output will be rated for 16A @277VAC. Carryover shall be provided for a minimum of 5 days with abuilt-in rechargeable capacitor which need not be replaced.
SPECIFIERS GUIDEFurnish and install a Grasslin FM/1 digi 42-___ electronic time switch.Thisone circuit control shall have 24 hour and 7 day programming and alsooffer 21 ON and 21 OFF setpoints and days selectable in any combina-tion. It shall have a “8th day” or Holiday program which can be scheduledup to a week in advance to be effective from 1 to 99 days. The LCD shalldisplay time of day in AM/PM or military time format and provide load sta-tus indication. A daylight time adjustment key shall also be provided. Thetime switch will be programmable to the minute and also offer a manualoverride for ON or OFF to the next scheduled event or for permanentON/OFF/Automatic. The SPDT relay output will be rated for 16A @277VAC. Carryover shall be provided for a minimum of 14 days with a built-in rechargeable NiCad battery which need not be replaced.
FM/1 Digi20 & 42 Typical Wiring:
2.12” 54mm
2.44
”62
mm
2.36” 60mm
IN-WALL TIMERS
www.grasslin.com 201.825.969614
0-5 Minutes KLT-5M KLT-5MH0-15 Minutes KLT-15M KLT-15MH0-30 Minutes KLT-30M KLT-30MH0-60 Minutes KLT-60M KLT-60MH
0-2 Hours KLT-2H KLT-2HH0-4 Hours KLT-4H KLT-4HH0-6 Hours KLT-6H KLT-6HH0-12 Hours KLT-12H KLT-12HH
Example: KLT-30M-W Add “-W” to above for white knob & plateExample: KLT-30MH-A Add “-A” to above for aluminum plate & plastic knob
Time Cycle No-Hold Models with IVORY Knob & Plate Hold Models with IVORY Knob & Plate
KLT SeriesSpring Wound Interval/Countdown Time Switch
KLT can be wired into new or existing standard wall box as a replacement toa toggle switch. It provides temporary timed power to loads such as lighting,heat lamps, exhaust fans, heaters, air conditioners, pumps, and other equip-ment. Spring operated interval/countdown timer. Completely mechanical;does not require input power. Automatically turns OFF the load at end of thetime interval, saving energy and extending equipment life. May be used inEnergy Management Systems as an override to temporarily turn loads ON thathave been turned OFF by the system.
SPECIFICATIONS:
SPST Switch Contact Ratings (50/60Hz):20A@125VAC (Resistive/Inductive)1HP@125VAC (Inductive)7A@125VAC (Tungsten)10A@250VAC (Resistive/Inductive)10A@277VAC (Resistive/Inductive)
Wiring Connections: Screw TerminalsOperating Temperature: –20°F to 185°FN.O. and N.C. Terminals
ORDERING DATA
LISTED
®
File #E83486
SPECIFIERS GUIDEFurnish and install a Grasslin ___ mechanical spring wound timer which requires noelectricity to operate the timing mechanism. The time switch must be capable of fit-ting a standard 2-1/2” deep single or multigang wallbox and a decorator wallplate orstandard toggle switch wallplate. Knob and scaleplate shall be available in ivory(white) or with an aluminum wallplate and plastic knob. The device must also becapable of flush panel mounting. The SPST switch shall close when manually acti-vated and automatically open at the end of the time interval (units with “Hold” optionwill remain permanently closed if the hold mode is selected). Normally closed ver-sions shall open when manually activated and automatically close at the end of thetime interval. The switch contact shall be rated 20A (inductive).
Features• Timing ranges from 5 minutes to 12 hours
• Heavy Duty 20A@125VAC SPST (N.O. and N.C.)
• SPST 20A, 2HP switch
• Decorator style dial plate fits both standard and decoratorwallplates
• Aluminum wallplate available
• Fits in single or multigang wallboxes
• May be flush panel mounted
• Normally open and closed standard connection (except 5 min.)
www.grasslin.com 201.825.9696 15
IN-WALL TIMERS
ET 616ElectronicInterval/Countdown Timer
The ET 616 is a wall mounted Electronic Time Switch which automat-ically turns lights or other loads OFF after a preset time period. Whenused for control of lights in a conference room, rest room, or similartemporary use room, it functions like a standard light switch, turningthe lights ON when the button is pressed, and OFF when pressedagain. If left ON, it will automatically turn OFF after a time period set-table from 5 minute to 12 hours via tamper-proof dip switches. It isalso suitable for the control of tanning beds, fans, heaters, chemicalpumps, laboratory apparatus, and other applications requiring a pre-set ON time and automatic shutoff.
SPECIFICATIONS:
Input: 120V or 277VAC 50/60 Hz
Switch Rating:
1000W Tungsten, 800W Ballast Switch Rating
@ 120VAC
1500W Tungsten, 1200W Ballast Switch
Rating @ 277VAC
Operating Temperature:
0° to 100°F (–18° to 38°C)
Operating Humidity:
0-95% RH Non-Condensing
Faceplate Color: White
Timing Accuracy: Less Than 1% Deviation
Wiring Connections: 6” Leadwires
1000 W (Tung.) @ 120VET616 120 or 277 VAC 5, 15, 30, 60 Min. 800W (Bal.) @ 120V
50/60 Hz 3, 6, 9, 12 Hr. 1500W (Tung.) @ 277V1200W(Bal.) @ 277V
Model Voltage Timing Interval Switch Rating
ORDERING DATA
SPECIFIERS GUIDEFurnish and install a Grasslin Model ET616 Electronic Interval Timer. The timer shall fit a standard 2-1/2” deep single or multigang wall box and decorator style wall plate.It shall be capable of being powered by 120 or 277 volts. The unit shall offer preset time intervals of 5, 15, 30 or 60-minutes and 3, 6, 9 or 12-hours set with “DIP” switch-es. Operation shall be via a single push button located on the front of the time switch. The push button shall operate as a standard on/off switch as well as to initiate theselected countdown interval. The time switch shall incorporate a “scroll-up” or “scroll-down” feature that allows the preset time to be adjusted up or down in 1-minute (minutesettings) or 10-minute (hour settings) increments. The timer shall provide a “beep” and “flash” mode to indicate the last minute of operation. If activated, the unit shall flashonce at the one-minute mark or beep once every 5 seconds from the one-minute mark to the shutdown point. The unit shall provide a reset feature, activated by pressingthe push button once during the last minute of operation, to reinitiate the selected countdown interval. The time switch shall incorporate a backlighted LCD to display thecountdown time. The unit shall contain a capacitor to retain the switch position during a power failure for up to 10 hours.
Features• Operates on 120V or 277VAC
• Mounts in standard wallbox
• Single button ON/OFF operation
• Backlighted LCD display
• Preset time adjustments; 5, 15, 30, 60 minutes, 3, 6, 9, 12 hours
• Switch holds position during a power failure (on or off), restarts at preset time when poweris restored
• UL and cUL Listed
Red
120V Hot
Neutral
Bla
ck
Gre
en/Y
ello
w
Gre
en
Load
ET616 Typical Wiring(120VAC):
IN-WALL TIMERS
www.grasslin.com 201.825.969616
24 Hour 7 Day Wallplate Configuration Switch
KM2 ST-1G KM2 SW-1G 1 Gang SPSTKM2 STu-1G KM2 SWu-1G 1 Gang, 3 Way SPDTKM2 ST-2G KM2 SW-2G 2 Gang, Toggle SPSTKM2 STu-2G — 2 Gang Toggle, 3 Way SPDTKM2 ST-3G KM2 SW-3G 3 Gang, Toggle SPSTKM2 ST-4G KM2 SW-4G 4 Gang, Toggle SPSTKM2 ST-2D KM2 SW-2D 2 Gang, Decorator SPSTKM2 ST-3D KM2 SW-3D 3 Gang, Decorator SPSTKM2 ST-2R KM2 SW-2R 2 Gang, Receptacle SPSTKM2 STST-2G KM2 SWSW-2G 2 Gang, Dual Timers (2) SPST
ORDERING DATA
File #E83486
KM2 In-Wall Timer24 Hour, 7 Day
Replaces standard wall switch (toggle) to provide automatic control ofoutdoor or indoor lighting, fans, pumps, office machines, and other typesof circuits. Captive trippers are easy to set, can’t be lost. 72 trippers pro-vide up to 36 ON/OFF events in 24 hour period. Three way, OFF/AUTO/ONoverride switch provides continuous ON or OFF positions. UL Listed. Easywiring and installation.
SPECIFICATIONS
Switch Rating:20A @ 120VAC, 60Hz2400W Resistive8A Inductive1HP @ 120VAC1350W Tungsten
Environmental Ratings:Operating Temperature Range:
–40°F to 180°F (–40°C to 85°C)Operating Humidity: 0 to 95% non-condensing
Wiring Connections:(3) #14AWG color coded lead wires
Hot – BlackSwitched – RedNeutral – White
SPECIFIERS GUIDEFurnish and install a Grasslin KM2 ST24 hour (SW, 7 day) “In-Wall” timeswitch with 20 minute (2-1/3 hr.) intervalcaptive trippers. Input voltage shall be120V and SPST (SPDT) contacts shallbe rated at 20A, 1HP @ 120VAC. Timeswitch shall contain an OFF/AUTO/ONmanual switch.
Features• Captive trippers with 20 minute switching interval
(2-1/3 hr. for 7 day)
• SPST 20A, 1HP @ 120V switch
• Replaces standard wall switches
• Multiple plates available
• Reliable synchronous timer motor
• Easy wiring and installation
HOT (BLACK) LOAD (RED)LOAD
NEUTRAL (WHITE)
KM2 Typical Wiring:
2-gang/toggle2-gang/decoratorDual Timer(2-gang with 2 KM2’s)
4-gang/toggle
ET724 ElectronicIn-Wall Timer24 Hour, 7 Day
Replaces standard wall switch (toggle) to provide automatic control of out-door or indoor lighting, fans, pumps, office machines, and other types ofcircuits. The unit can be programmed for 7-ON and 7-OFF events daily orweekly. AUTO and Manual Modes are clearly displayed along the time ofday. The ET724 is designed to be mounted in a standard decorator plate fora sleek modern look.
www.grasslin.com 201.825.9696 17
IN-WALL TIMERS
Model Code UPC No. 614573 Description Wallplate Configuration Switch
ET724 05757 Electronic 24-hr./7-day (White Only) 1 Gang Decorator (Not Included) SPST
ORDERING DATA
SPECIFICATIONS
Input: 120VAC, 60 Hz
Switch Rating:
20A Ballast Switch Rating @ 120VAC
20A Inductive Switch Rating @ 120VAC
2400W Resistive
1HP Motor
Operating Temperature:
32° to 122°F (0° to 50°C)
Faceplate Color: White
Timing Accuracy: Less Than 1% Deviation
Wiring Connections: 6” Leadwires
SPECIFIERS GUIDEFurnish and install a Grasslin model ET724 elec-tronic in-wall 7 day time control. The timer shall fitinto a standard 2-1/2” deep single or multigang wallbox and decorator style wallplate. It shall not pro-trude from the wall more than 1/8” and have a cap-tive cover plate over the programming keys. Theunit shall be capable of switching a 20 amp ballastor general purpose load or 1 HP motor and haveseven independently programmable events. Thebattery backup will be a rechargeable NiMh typethat does not require replacement.
Features• Sleek profile
• Easy to program
• Single push-button control
• Mounts in standard wallbox
• Built-in rechargeable battery neverneeds replacement
• LCD display
• Flush mounted design
• Non-volatile memory
• Captive cover plate
• UL Listed and CSA Approved
ET724 Typical Wiring:
Profile
ELECTRONIC PHOTO-ELECTRIC SWITCHES
www.grasslin.com 201.825.969618
PC SeriesPhoto-electric Switches
The PC and LM series are one or two channel electronic lighting controls.Theyare provided with a waterproof light level sensor that can be remotely mount-ed up to 330 feet away. For large installations, up to 10 units (20 channels)can be connected to a single sensor. The integral light sensitivity adjustmentprovides a wide range of settings, making these units applicable for control ofindoor and outdoor lighting as well as automatic awnings or shades. The PC1and PC2 operate strictly via a light level adjustment. The PC2 unit has an inde-pendent light level setting for each channel. Either unit can be connected inseries with any Grasslin Time Switch to provide time-of-day control.
SPECIFICATIONS:
Input Voltage: Separate models available for120V or 277VAC; 50/60 Hz
Resistive Rating:1 Channel: 16A @ 250VAC2 Channel: 10A @ 250VAC
Ballast Rating: 12A @ 120VAC, 8A @ 277VAC
Output Relay: SPDT “dry” contacts for each channel
Power Consumption: 2.5VA
Temperature Range:Control Unit –4°F to 131°F (–20°C to 55°C)Sensor –22°F to 158°F (–30°C to 70°C)
Humidity Range:Control Unit 0 to 95% RH non-condensingSensor 0 to 100% RH
Weight: 8.5 oz.
Mounting: Surface & DIN rail (NEMA 1 & 3R enclosures available)
Light Sensitivity Adj.: .2 to 50 Foot Candles(10 to 1000 F.C. w/ optional sensor)
Time Delay BeforeSwitching Adjustable, 0 to 100 sec.
Time Switch Accuracy: ± 2.5 seconds per day @ 68°F (20°C)
LightMaster
PC1-120 120V 1 Surface or DIN RailPC1-240 240V 1 Surface or DIN RailPC1-277 277V 1 Surface or DIN Rail
PC2-120 120V 2 Surface or DIN RailPC2-240 240V 2 Surface or DIN RailPC2-277 277V 2 Surface or DIN Rail
LM1-”X”-120 120V 1LM1-”X”-277 277V 1
LM2-”X”-120 120V 2LM2-”X”-277 277V 2
Model Code Voltage Channels Mounting
Enclosure Options Substitute the Following for “X”:
“I” = NEMA 1 Indoor Enclosure“IC” = NEMA 1 Indoor Enclosure
with Clear Cover“O” = NEMA 3R Outdoor
Enclosure“OC” = NEMA 3R Outdoor Enclosure
with Clear Cover
ORDERING DATA
C.E.C. CERTIFIED TITLE 24,PART 6
ON ALL MODELS
In Optional Enclosure
C US
10”
61/2”
SPECIFIERS GUIDEFurnish and install a Grasslin, Model PC1, single (PC2, two) channel photo-electricswitch. The controller shall provide an integral light sensitivity adjustment, selectablefrom 0.2 to 1000 footcandles for low or high light level control (two channel units shallhave independent adjustments for each channel). A LED indication of relay status shallbe provided. The unit shall be provided with a remotely mounted light level sensor, inweather proof housing, capable of being located up to 300 feet from the control. TheSPDT switch contact(s) shall be rated 16A @ 250VAC. The controller shall be surface,DIN rail or enclosure mounted.
Features• Single or two channel
• 16A switch rating
• Dual level control for dim or bright light
• Remote sensor
Jumper required between 9 and 10
3-4 and 6-7 closes on light level decreasing below setpoint
3 4 51 2 6 7 8 9 10 11
NOINPUT
CH 1 CH 2
NC NO NC
SENSOR
M~
{
PC Series Typical Wiring:
www.grasslin.com 201.825.9696 19
ELECTRONIC PHOTO-ELECTRIC/TIME SWITCHES
PC Digi Series24 Hour and 7 Day CombinationPhoto-electric & Time Switches
The PC Digi and LM Digi series are one or twochannel electronic lighting controls and timeswitch combination.They are provided with awaterproof light level sensor that can be remote-ly mounted up to 330 feet away. For large installations, up to 10 units (20 chan-nels) can be connected to a single sensor. The integral light sensitivity adjust-ment provides a wide range of settings, making these units applicable for controlof indoor and outdoor lighting as well as automatic awnings or shades. The PC“Digi” models incorporate an integral one or two channel electronic timer withautomatic “Day Light Savings Time” changeover.
SPECIFICATIONS:Input Voltage: Separate models available for
120V or 277VAC; 50/60 Hz
Resistive Rating:1 Channel: 16A @ 250VAC2 Channel: 10A @ 250VAC
Ballast Rating: 12A @ 120VAC, 8A @ 277VAC
Output Relay: SPDT “dry” contacts for each channel
Power Consumption: 2.5VA
Battery Backup: 3 years (“digi” units)
Temperature Range:Control Unit –4°F to 131°F (–20°C to 55°C)Sensor –22°F to 158°F (–30°C to 70°C)
Humidity Range:Control Unit 0 to 95% RH non-condensingSensor 0 to 100% RH
Weight: 8.5 oz.
Mounting: Surface & DIN rail (NEMA 1 & 3R enclosures available)
Light Sensitivity Adj.: .2 to 50 Foot Candles(10 to 1000 F.C. w/ optional sensor)
Time Delay BeforeSwitching Adjustable, 0 to 100 sec.
Time Switch Accuracy: ± 2.5 seconds per day @ 68°F (20°C)
LightMaster
PC1-digi 20-120 120V 1 Surface or DIN RailPC1-digi 20-277 277V 1 Surface or DIN Rail
PC2-digi 30-120 120V 2 Surface or DIN RailPC2-digi 30-277 277V 2 Surface or DIN Rail
LM1-digi 20-”X”-120 120V 1LM1-digi 20-”X”-277 277V 1
LM2-digi 30-”X”-120 120V 2LM2-digi 30-”X”-277 277V 2
Model Code Voltage Channels Mounting
Enclosure Options Substitute the Following for “X”:
“I” = NEMA 1 Indoor Enclosure“IC” = NEMA 1 Indoor Enclosure
with Clear Cover“O” = NEMA 3R Outdoor
Enclosure“OC” = NEMA 3R Outdoor Enclosure
with Clear Cover
ORDERING DATA
C.E.C. CERTIFIED TITLE 24, PART 6
ON ALL MODELS
In Optional Enclosure
C US
Features• Single or two channel
• 16A switch rating
• Battery backup
• Dual level control for dim or bright light
• Remote sensor
• Automatic Daylight Savings time changeover
SPECIFIERS GUIDEFurnish and install a Grasslin, Model PC1-digi 20, single (PC2-digi 30, two)channel combination photo-electric/time switch. The time/day will be storedin the event of a power failure by a Lithium battery. The program scheduleshall be stored in EEPROM. The controller shall provide an integral lightsensitivity adjustment, selectable from 0.2 to 1000 foot-candles for low orhigh light level control. A LCD display shall provide indication of the time,day and status of each channel. A LED shall be provided to indicate photo-electric output.The unit shall be provided with a remotely mounted light levelsensor, in weather proof housing, capable of being located up to 300 feetfrom the control. The SPDT switch contact(s) shall be rated 16A @ 250VAC.The controller shall be surface, DIN rail or enclosure mounted.
PHOTO CONTROLS
www.grasslin.com 201.825.969620
Conduit MountingSeriesThese units are designed to provide “dusk-to-dawn” lighting control.The dome and base are ultrasonically welded for added strength andweather resistance (CM, CMS, CMP). The CMM Series features a gas-keted heavy duty die-cast zinc housing. The units are easy to adjust viaa “slide” selector. They are available in non-swivel, swivel, “pencil”swivel, and metallic versions. All units incorporate a built-in time delayfunction designed to eliminate nuisance switching.
SPECIFICATIONS:Cell: Cadmium Sulphide
Cell Size: 1/2” – CM, CMS, CMP
1” – CMM
Temperature Range: –40°F to 140°F
Activation:
Turn-on: .75 to 2.5FC – CM, CMS, CMP
1.5 to 5.5FC – CMM
Turn-off: Approximately 3 times turn-on
CM, CMS, CMP, CMM
For voltages and switch ratings, see chart below.
LISTED
®
LISTED
®
CM Series
CMS Series
CMP Series
CMM SeriesSpec Grade
5 year warranty
CM-120 CMS-120 CMP-120 120 2000W 1800VA
CM-287 CMS-287 CMP-287 208-277 2000W 1800VA
CM-127 CMM-1127 120/277 2000W 1800VA
Models Voltage RatingStandard Metallic Swivel “Pencil” 50/60 Hz Tungsten Ballast
ORDERING DATA
SPECIFIERS GUIDEFurnish and install a Grasslin CM__ Series photo control. Switch rating shall be 2000W Tungsten, 1800VA Ballast at ____ volts (50/60Hz). The unit shall be suitable for out-door installation via 1/2” conduit mounting. Temperature range shall be –40°F to 140°F. A built-in time delay shall be incorporated to prevent nuisance switching. The SPSTnormally closed switch shall provide fail “on” operation. Turn-on shall be at .75 to 2.5FC (1.5 to 5.5FC for CMM Series) and turn-off shall be at approximately 3 times turn-on.
Features• 1/2” conduit mounting
• SPST, normally closed switch
• Built-in time delay
PhotoelectricSwitch
Line (Black)
120V Models
Neutral (White)
(Red)
Load
PhotoelectricSwitchFor 277VAC:
L1 - LineL2 - Neutral
L1
L2240V
208-277V Models
(White)
(Red)
Load
Line
Neutral
PhotoelectricSwitch
120VAC
(Red)(Black)
(Blue) (White)
120/277V Models
Line
Neutral
PhotoelectricSwitch
277VAC
(Red)(Black)
(White) (Blue)
Typical Wiring:
www.grasslin.com 201.825.9696 21
PHOTO CONTROLS
Button Type SeriesThese units are designed to provide “dusk-to-dawn” lighting control. Theseems (BT Series) are ultrasonically welded for added strength and weatherresistance. The BT-120 and 287 mount through 11/16~13/16” hole with 3/4”threaded stem. The BTW-120 mounts into standard outdoor junction boxwith stainless steel plate and gasket (included). The TL Series features lock-ing type prongs that meet ANSI C136.10-1988 and uses standard gap typeor MOV surge arrestor..
Turn-Lock Mounting Series
SPECIFICATIONS:“BT” Series “TL” Series
Cell: Cadmium Sulphide Cadmium Sulphide
Cell Size: 1/2” 1/2” or 1”
Temperature Range: –40°F to 140°F –40°F to 140°F
Activation:
Turn-on: 3 to 5FC 1FC, Avg.
Turn-off: Approx. 3x turn-on 3x turn-on, avg.
For voltages and switch ratings, see charts below.
LISTED
®
BT Series
BTW
BT-120 120 1500W 1200VA 1/2” DelayBT-287 208-277 1500W 1200VA 1/2” DelayBTW-120 120 1500W 1200VA 1/2” DelayTLD-1185 105-285 1200-2850W 1800-2800VA 1” DelayTLD-1480* 480 1000W 1800VA 1” DelayTLD-120 105-130 1200W 1800VA 1/2” DelayTLD-287 208-277 2080-2770W 2100-2800VA 1/2” DelayRCB Receptacle w/Bracket
Standard Rating ResponseModel Voltage 50/60 Hz Tungsten Ballast Cell Size Time
ORDERING DATA
*Not UL/CSA
TL Series
LISTED
®
Features• Flush mounting
• SPST, normally closed switch
• Built-in time delay
Features• Low profile design with locking-type prongs
• SPST, normally closed switch
• Built-in time delay
SPECIFIERS GUIDEFurnish and install a Grasslin ____ Series photo control. Switch rating shall be ____Tungsten, ____ Ballast at ____ volts. The unit shall be suitable for outdoor installationand temperature ranges of –40°F to 140°F. Mounting shall be via locking type prongs(through 11/16” - 13/16” hole or flush in outdoor junction box). A built-in time delay shallbe incorporated to prevent nuisance switching (response time shall be instant). TheSPST normally closed switch shall provide fail “on” operation. Turn-on shall be at ____FC. Turn-off shall be approximately 3 times turn-on.
DEFROST CONTROLS
www.grasslin.com 201.825.969622
Multi-Voltage
Defrost Timer–DTMVTime/Temperature/Pressure TerminatedThe DTMV is tailor made for the after-market in that one unit replaces all com-petitive models. It’s also available in different mounting configurations making itideal for OEM applications. The DTMV is applicable to air defrost (compressorshutdown) and in electric or hot gas defrost systems where the defrost is termi-nated by the timer or when the coil is frost free, as sensed by a temperature orpressure switch, even though the programmed defrost termination time has notbeen reached. The time termination functions as a fail-safe and will terminate thedefrost if the temperature or pressure switch fails to do so.
SPECIFICATIONS
Switch Rating:30A Resistive @ 208-250VAC2HP @ 208-250VAC; 1HP @ 125VAC690VA pilot duty @ 125-250VAC“F” Terminal: 10A Resistive @ 208-250VAC
1HP @ 208-250VAC;1/2HP @ 125VAC
(Terminal 1-3 rating reduced to 20A when “F”terminal used)
Wiring Connections: Screw clamp terminals accommodate up to two #8 AWG wires.
Environmental Ratings:Operating Temperature Range: –40°F to 131°F (–40°C to 55°C)Operating Humidity: 0 to 95% non-condensing
Dimensions: 10” x 6.5” x 3.75” deepShipping Weight: 2 lbs.
File #E83486
10”
61/2”
Features• Universal Replacement DTMV replaces over 40 competitive models
• Multi-Voltage field adjustable for 120, or 208/240VAC
• Mounts in existing enclosures
• Standard wiring
• Defrost times settable on quarter hour with captive trippers
• NEMA 3R outdoor enclosure
• 30 Amp, 2HP Rating
• Electromechanical or electronic timer module
• Optional clear cover allows viewing timer clock face without opening cover
• LED indications for defrost and refrigeration cycles
• Space saving panel mount version available with 1/4” standoffs
• Defrost cycles are programmed independently
• “Real-time” clock for quick, easy and accurate setting
SPECIFIERS GUIDEFurnish and install a Grasslin DTMV defrost control which is fieldadjustable for 120V or 240V operation and shall have defrost initiationtimes settable to the quarter hour via captive trippers at 15 minuteintervals. The defrost timer shall be housed in a NEMA 3R indoor/out-door plastic enclosure.The relay output will be rated for 30A Resistive,2HP @ 250VAC. Defrost termination to be by time (and by a remotetemperature or pressure switch).
THERMOSTAT
COMPRESSOROR
SOLENOID VALVEOR
CONTACTOR COIL
FANMOTOR
DEFROSTHEATER
L1
L2
TIMER
TIMERRELEASE
RELAY
TERMINATIONTHERMOSTATW/FAN DELAY
F 3 1 2 4 XN
HI-LO PRESSURE SW.
LINE
COMPRESSOROR
SOLENOID VALVEOR
CONTACTOR COIL
DEFROSTHEATER
L1
L2
TIMER
TIMERRELEASE
RELAY
F 3 1-N 2 4 X
LINE
THERMOSTAT
DTMV Time/Time–Electric or Air Defrost Wiring Diagram DTMV Time/Temperature–Electric Defrost Wiring Diagram
NOTE: Fan motor may be connected to “F” terminal instead of “4” terminal if desired.
The only one you need!
www.grasslin.com 201.825.9696 23
DEFROST CONTROLS
StandardDTMV 120V, 208/240V, 60Hz Synchronous No 1 to 24 15-180 min. 15 minutes
Quartz Battery BackupDTQMV 120V, 208/240V, 50/60Hz Quartz 7 day 1 to 24 15-180 min. 15 minutes
ElectronicDT 140 digi 20-120 120V, 50/60Hz Electronic 7 day 1 to 8 1-180 min. 1 minuteDT 140 digi 20-240 208/240V, 50/60Hz Electronic 7 day 1 to 8 1-180 min. 1 minute
Defrost MinimumFrequency Defrost Duration
Model Voltage Timer Carryover No./Day Duration Interval
ORDERING DATA
Time Initiated, Remote Temperature, Pressure, or Time Terminated
Add “-M” for Mechanism only. Add “-P” for Panel Mount (Less Enclosure). Add “-B” for Bracket Mount
Mounts in existing enclosures.
No need to change wiring.
Universal ReplacementTime Initiated,
Remote Temperature, Pressure or Time TerminatedPARAGON PRECISION
8141-00 6141-008143-00 6143-008145-00 6145-008041-00 6041-008043-00 6043-008045-00 6045-008046-008047-00 6047-008141-20 6141-208143-20 6143-208145-20 6145-208041-20 6041-208043-20 6043-208045-20 6045-208046-208047-20 6047-208245-20 6245-208243-20 6243-208247-20 6247-20
DTMV=
8043 / S1 Pos. B
8045 / S1 Pos. A
8047 / S1 Pos. B
8041 / S1 Pos. A8141 / S1 Pos. A
8143 / S1 Pos. B
8243 / S1 Pos. B8245 / S1 Pos. A
8247 / S1 Pos. B
N 1 XN 1 3 4 2 2
F 3 1 4 2 N NOCONN.
NOCONN.
NOCONN.
N 1 3 2 4 Xp pF 3 1-N 2 4 Xp p1 N 3 4 2 X
F 3 1-N 2 4 X
3 2 4
RETROFITTED WITHFrostKing DTMV
Defrost Timer
GRASSLIN CONTROLS CORPORATION31 Industrial Ave. • Mahwah, NJ 07430Tel.: 201-825-9696 • Fax: 201-825-8694
www.grasslin.com
160-
0037
Retrofit Conversion Kit
Universal Replacement LabelsInsulator and Standoffs
Bracket Mount
(High ImpactMaterial)
TC-10 SeriesThe TC-10 is an ideal replacement for applications that use the combination of anelectro-mechanical thermostat and a defrost timer. The TC-10 incorporates a 4-position DIP switch to enable the user to change temperature range, differentialtemperature, and defrost interval times and/or defrost duration times. It providesaccurate temperature control and automatic (Off-Cycle) defrost management. TheTC-10 has two built-in diagnostic functions which provide a warning and alarmsignal should the Condenser be blocked or the Refrigeration System Fail. The TC-10 can be powered directly from a 120 or 240VAC source.
SPECIFICATIONS
Model identification number: GE-TC-10-D(U)
Temperature range: -/- 1-9°C or 30-48°F-/- 4-9°C or 25-48°F
Voltage: 120/240VAC 60Hz
Accuracy: > 1.0°C
Resolution: 1°C
Max. allowable ambient temperature: 65°C or 149°F
Max. allowable storage temperature: 75°C or 167°F
Material casing: Black fire-retaradant Cycoloy
Material lens: Clear Polycarbonate
Material temperature selection knob: Nylon
Length thermistor wire: 1.5 or 2.5 mtr +/- 5%
LED indicator light colors: Green, Yellow, and Red
ELECTRONIC TEMPERATURE/REFRIGERATION CONTROLS
www.grasslin.com 201.825.969624
Black Cycoloy (fireretardant) housing Inner protection plate
Nylon temperatureselection knob
Outer fascia
Access to dip switch
Agency Approvals
FUNCTIONAL PROPERTIES AND VALUES
Minimum compressor rest time: 3 minutes
Defrost intervals: 3 hours or 4 hours
Defrost duration: 10 minutes or 15 minutes
Default setting: None
Differential: 3°C or 4°F
RSF time out: 72 hours
High temperature alarm set point: 90°C or 194°F
TFC-212 SeriesThe TFC-212 has been specifically designed for applications where the userneeds to alter the defrost interval/duration and fan delay function. In addi-tion this unit has an internal alarm buzzer and a connection for an externalalarm device. The TFC-212 is ideal for coolers and freezer applications dueto it’s low temperature characteristics. It can control set points between -22°F to 77°F. The unit comes standard with 4 output relays (i.e.Compressor Relay, Fan Relay, Alarm Relay, and Electric Heater or SolenoidRelay). The average temperature can also be displayed simply by pushingthe two right hand side buttons simultaneously.
www.grasslin.com 201.825.9696 25
ELECTRONIC TEMPERATURE/REFRIGERATION CONTROLS
SPECIFICATIONS
Model identification number: GE - TC - 212 - AA - LT
Temperature range: -/- 15-25°C./ 5-77°F-/- 30-25°C / -22-77°F
Voltage: 12 Volt AC
Accuracy: < 0.5°C
Resolution: 0.1°C
Max. allowable ambient temperature: 65°C or 149°F
Max. allowable storage temperature: 75°C or 167°F
Display: L.E.D.
Display color: Green
Material casing: Black cycoloy
Material lens: Green polycarbonate
Material buttons: Soft anti-slip plastic rubber
Length thermistor wire: 1.5 or 2.5 mtr +/- 5 %
Transformer: 240 or 120 Volt, 12 Volt / 210 mA
Agency Approvals
PROGRAMMABLE PARAMETERSUS Upper set point -30 to 25°C / -22 to 77°F (LT)LS Lower set point -30 to 25°C/ -22 to 77°F (LT)DIF Differential 1 to 99°Ca1 Calibration sensor 1 +/- 9.9°CCA2 Calibration sensor 2 +/- 9.9°CD1 Display speed 1 to 8D2 Display stability 1 to 255DP Decimal point 0 or 1RT Minimum rest time 1 to 30 minutesDE Defrost intervals 1 to 199 hoursDD Defrost duration 1 to 199 minutesDEF Display during defrost 1, 2 or 3DT Max. temp. in appliance +/- 42°C/108 to - 44°FSp2 Set point evaporator sensor +/- 42°CFP Fan stop 0 or 1FD Fan delay 0 to 60 minutesCT RSF failure time elapse 1 to 255 hoursLL Low temperature alarm +/- 99°CHL High temperature alarm +/- 99°CAD Alarm delay 0 to 255 minutesb1 Alarm duration 0 to 120 minutesb2 Alarm intervals 0 to 255 minutes
Thermistors
Transformer powers unit
CYCLE TIMERS
www.grasslin.com 201.825.969626
talento 121One Hour Repeat Cycle Time SwitchThe talento 121 is a synchronous motor driven electromechanical one hour time switch intendedas a low cost repeat cycle timer for industrial processes and other applications. It provides con-tinuous on and off cycling of a load in a pattern which will repeat every hour. Captive trippersallow setting up to 24 on and 24 off times in 1.25 minute increments over a one hour period. Itmay be used in conjunction with a GRASSLIN 24 hour or 7 day time switch to provide repeat cycletimed switching only during selected periods of the day or week. It may be surface or DIN railmounted within panels, or may be mounted in a GRASSLIN indoor or outdoor enclosure.
SPECIFICATIONS
Size: 2.13” x 3.31” x 2.56” deepSwitch Output: SPDT isolated contacts
16A Resistive @ 125/250VAC4A Inductive @ 125/250VAC1350W Tungsten @ 240V
Shortest Switching Time: 1.25 MinutesOperating Temperature: –13°F to 130°FOperating Humidity: 0 to 95%
RH non-condensingWiring Connections: Screw terminals for up to
#12AWG wire
talento 121 120V or 240V No One Hour 1.25 minutes SPDT 16A Res.
FM/1 S 12H 24V, 120V, 240V No 12-Hour 7.5 minutes SPDT 21A Res.
MinimumModel Voltage Carryover Switch Program ON/OFF Time Switch Output
ORDERING DATA
SPECIFICATIONS:Size: 2.36” x 2.36” x 1.25”
Supply Voltage: 24, 120, 240VAC
Power Consumption: 1VA
Switch Rating: SPDT
Resistive: 21A
Tungsten: 1350W
Inductive: 1HP @ 120VAC
2HP @ 240VAC
Wiring Connections: 1/4” quick-connects
INSTALLATION:Stand Alone: With indoor oroutdoor enclosure
Panel: Surface mounting
UL FILE:E83486
CSA FILE:LR52379
FM/1 S 12H12 Hour Repeat Cycle Time SwitchThe FM/1 S 12H is a synchronous motor driven electromechanical 12 hour time switchintended as a low cost repeat cycle timer for industrial processes and other applications.It provides continuous on and off cycling in a pattern which will repeat every 12 hours.Captive trippers allow setting up to 48 ON and 48 OFF times in 7.5 minute increments overa 12 hour period.
Features• 1.25 minute resolution
• Up to 24 ON/OFF times per hour
• Captive trippers
• SPDT 16A switch
• Surface or DIN rail mounting
Features• 12 hour cycle
• 7.5 minute resolution
• Captive trippers
• SPDT 21A switch
• Flush, surface or DIN rail mounting
Talento 121 Typical Wiring:
www.grasslin.com 201.825.9696 27
DC HOUR METERS
GZ 41GZ 40A GZ 40B
• Bezel: 2.12” x 1.25”(54 x 32mm)
• Capacity: 99.999.9hours
• Digits: 6 – 0.125 highnumeralsHours: white on blackTenths: red on white
• Voltage: 10-80VDC• Power Consumption:
.03W @ 12VDC
.70W @ 48VDC
• Temperature: –22° to150°F (–30° to 65°C)Special Model Temp:–40° to 185°F(–40° to 85°C)
• Vibration Resistance:10 to 75Hz @ 1-8g’s
• Termination: 1/4”spade terminals
• Protected From:reverse polarity,inductive switch
• Weight: 2oz
• SAE Bezel: 2.31” dia.(59mm)
• Capacity: 99.999.9hours
• Digits: 6 – 0.125 highnumeralsHours: white on blackTenths: red on white
• Voltage: 4-40VDC and10-80VDC
• Power Consumption:.03W @ 12VDC.70W @ 48VDC
• Temperature: –22° to150°F (–30° to 65°C)Special Model Temp:–40° to 185°F(–40° to 85°C)
• Vibration Resistance:10 to 75Hz @ 1-8g’s
• Termination: 1/4”spade terminals
• Protected From:reverse polarity,inductive switch
• Weight: 2oz
• 3-Hole Bezel: 2.80”dia. (72mm)
• Totally sealed case• Capacity: 99.999.9
hours• Digits: 6 – 0.125 high
numeralsHours: white on blackTenths: red on white
• Voltage: 4-40VDC and10-80VDC
• Power Consumption:.03W @ 12VDC.70W @ 48VDC
• Temperature: –22° to150°F (–30° to 65°C)Special Model Temp:–40° to 185°F(–40° to 85°C)
• Vibration Resistance:10 to 75Hz @ 1-8g’s
• Termination: 1/4”spade terminals
• Protected From:reverse polarity,inductive switch
• Weight: 2oz
GZ 52A/B The Hour Meter WithoutElectrical Connection
The RZ hour meter records therunning time of machines,vehicles, etc. which vibrateduring operation.
The automatic mechanism inthis meter converts vibrationsinto energy which drives thehour meter and minute sweephand. It is so sensitive, it iscapable of operating from theslight vibration of a moving car.
LEGEND RZ52/RZ60
RZ52 = Model referenceD = Rubber mounting assemblyh = Horizontal installationv = Vertical installation
RZ60 = With adapter ring for 60mm diameter cut-out
ORDERING EXAMPLE:
RZ 52hVibratory hour meter for horizontal installation
Bezel: 2.28” round (58mm)
GZ Series
RZ Series
Dimensions in inches (mm)
GZ 40B 3-Hole Bezel
GZ 40A SAE Bezel
Dimensions in inches (mm)
GZ52A GZ52BOperating Voltage 8-30VDC 8-30VDCCurrent Consumption <3mA @12VDC <3mA @12VDCAccuracy ±0.5sec/day@20°C ±0.5sec/day@20°CMechanical Movement 2-Phase Step Motor 2-Phase Step MotorDisplay 6 Digits (99999.9 Hours) 6 Digits (99999.9 Hours)Operation Indicator LED LEDBezel Metal (Chrome) Circular Black (Plastic) CircularElectrical Connection 1/4” Quick Connectors 1/4” Quick ConnectorsPolarity Protection Diode DiodeMounting Flush (screw adj.) Flush (screw adj.)Operating Temperature –40°C - 85°C –40 C - 85°CStorage Temperature –40°C - 90°C –40 C - 90°CEnvironmental Rating IP 65 IP 65Shock Resistance DIN EN60068-2-27 DIN EN60068-2-27Vibration Resistance DIN EN60068-2-64 DIN EN60068-2-64Approvals CE CE
AC HOUR METERS
www.grasslin.com 201.825.969628
FWZ 36 FWZ 53 FWZ 55
Flush panel mount withwatertight/dusttight sealedbezels–non-resetable
UL FILE: E86119 CSA FILE: LR44080
FWZ 72Black Polycarbonate
FWZ 72BBlue-Silver on ColorlessFrosted Polycarbonate
All models also available with 1/4” spade terminals without screw clamp.
FWZ Series
• Bezel: 1.42” x 0.95”(36 x 24mm)
• Capacity: 99.999.99hours
• Digits: 7• Voltage: 24, 120, 240, 50
or 60Hz models• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)• Termination: Combination
1/4” spade and screwclamp. Rear access
screw terminalsavailable (model “K”)
• Weight: 1.2oz• Flush panel retainer
mounted with wirespring clip retainer
• Panel Opening: 1.36” x0.90” rectangular (34.5x 23mm)
Ordering Information
FWZ36 – voltage/freq.*Rear access screw
terminals
• Bezel: 2.83” round (72mm)3-hole
• Capacity: 99.999.99 hours• Digits: 7 – 0.16” high
numerals• Voltage: 24, 120, 240, 50
or 60Hz models• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)
• Termination: Combination1/4” spade and screwclamp. Rear accessscrew terminals avail-able (model “K”)
• Weight: 1.8oz• Flush panel mounted with
(3) 0.185” holes for #8screws
• Panel Opening: 1.75”round (44.5mm) or 1.50”x 1.00” rectangular (38 x25mm)
Ordering Information
FWZ72 – voltage/freq.FWZ72B – voltage/freq.FWZ72K* – voltage/freq.*Rear access screw
terminals
• Bezel: 1.42” x 0.95”(36 x 24mm)
• Capacity: 99.999.99hours
• Digits: 7• Voltage: 24, 120, 240, 50
or 60Hz models• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)• Termination: Combination
1/4” spade and screwclamp. Rear access
screw terminalsavailable (model “K”)
• Weight: 1.2oz• Flush panel retainer
mounted with wirespring clip retainer
• Panel Opening: 1.36” x0.90” rectangular (34.5x 23mm)
Ordering Information
FWZ36 – voltage/freq.*Rear access screw
terminals
• Bezel: 2.36” x 1.36”(60 x 34.5mm)
• Capacity: 99.999.99hours
• Digits: 7 – 0.16” highnumerals
• Voltage: 24, 120, 240, 50or 60Hz models
• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)• Termination: Combination
1/4” spade and screwclamp. Rear access
screw terminalsavailable (model “K”)
• Weight: 1.8oz• Flush panel retainer
mounted with slip-onplastic retainingbracket
• Panel Opening: 2.06” x1.08” rectangular (52 x27.5mm)
Ordering Information
FWZ55 – voltage/freq.FWZ55K* – voltage/freq.*Rear access screw
terminals
Dimensions in inches (mm)
Dimensions in inches (mm)
Dimensions in inches (mm) Dimensions in inches (mm)
www.grasslin.com 201.825.9696 29
AC HOUR METERS
UWZ48
SurfaceMount
UWZ48AEnclosedSurfaceMount
UWZ 48EFlush Mount
UWZ48VDIN RailMount
For within panels or indoor
mounting–non-resetable
UL FILE: E86119
CSA FILE: LR44080
All models are light grey
color with white numerals on
black background. Tenths and
hundreths numerals are
yellow. An orange dial
adjacent to the hundreths
digit provides running
indication.
UWZ52E
Flush Mount
UWZ Series
• Bezel: 1.89” x 1.89” (48 x48mm) • Capacity: 99,999.99hours• Mounting: Surface• Digits: 7 – 0.16” high • Voltage: 24, 120, 240, 50or 60Hz• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)• Termination: Screw Lugs• Weight: 2.5oz.
Surface mounted type.The UWZ 48 unit withplug-in base whereterminal protection is notnecessary. The socketbase is easy to installand connect. The meteris simply plugged into thebase and secured by onescrew.
Ord. Info.: UWZ 48 –voltage/freq.
• Bezel: 2.28” round(58mm) • Capacity: 99,999.99hours• Mounting: Flush• Digits: 7 – 0.16” highnumerals• Voltage: 24, 120, 240, 50or 60Hz• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)• Termination: Combination
1/4” spade and screwclamp
• Weight: 2.1oz.Flush mounted withbracket. The UWZ 52Ewith round face isfastened with a plasticslip-on retaining bracket.For larger cutouts up to a60mm diameter, a slip-on65mm ø bezel isavailable.
Ord. Info.: UWZ 52E –voltage/freq.
• Bezel: 1.89” x 1.89”(48 x 48mm) • Capacity: 99,999.99hours• Mounting: Surface• Digits: 7 – 0.16” high • Voltage: 24, 120, 240, 50or 60Hz• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)• Termination: Screw Lugs• Weight: 2.5oz.
Wall mounted type. Usedin conjunction with aterminal cover for addedsafety, the UWZ 48A issurface mounted.Installation merelyrequires fixing the base towall or panel with twoscrews, wiring the base,and plugging in the meterwith the terminal cover.
Ord. Info.: UWZ 48A –voltage/freq.
• Bezel: 1.89” x 1.89”(48 x 48mm) • Capacity: 99,999.99hours• Mounting: Flush• Digits: 7 – 0.16” highnumerals• Voltage: 24, 120, 240, 50or 60Hz• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)• Termination: Combination
1/4” spade and screwclamp
• Weight: 2.1oz.
Flush mounted withbracket. The UWZ 48Eunit fits into a 1.79 x1.79in. (45.5 x 45.5mm)cut-out. The thickness ofthe panel for flushmounting can be up to0.35in. (9mm). The unit issecured in position by aplastic slip-on retainingbracket. Also fits squareor round openings for72mm meters withoptional 72mm bezel.
Ord. Info.: UWZ 48E –voltage/freq.
• Bezel: 1.89” x 1.89”(48 x 48mm) • Capacity: 99,999.99hours• Mounting: DIN Rail• Digits: 7 – 0.16” highnumerals• Voltage: 24, 120, 240, 50or 60Hz• Power Consumption: 1VA• Temperature: –40° to
160°F (–40° to 72°C)
• Termination:Combination 1/4”spade and screwclamp
• Weight: 2.5oz.DIN rail mounting. Aspecial snap-on socketbase enables the unit tobe quickly and simplyfitted on DIN rail.
Ord. Info.: UWZ 48V –voltage/freq.
Dimensions in inches (mm) Dimensions in inches (mm)
Dimensions in inches (mm)Dimensions in inches (mm) Dimensions in inches (mm)
PanelC
utout 2.0”(50.5m
m)
ELECTRO-MECHANICAL RESIDENTIAL TIMERS
www.grasslin.com 201.825.969630
T25 Plug-in Timer
SPECIFICATIONS:Input Voltage: 120VACSwitch Rating: 15A @ 125VAC
Tungsten: 1250W, TV-41/3HP
Polarized 2-conductor plug and receptacle
SPECIFICATIONS:
Voltage: 110-120VAC
Switch Rating: 15A Resistive
Ambient TemperatureRange: 14°F to 122°FGrounded 3-conductor plugand receptacle
T35 Plug-In Timer
T25 24 hour No 15 minutes 15 minutesT35 24 hour No 15 minutes 15 minutesT100 24 hour No 15 minutes 15 minutesT240 24 hour No 15 minutes 15 minutes
OPERATING FEATURES
Model Switch Program Reserve Program On/Off Every Shortest Switching Time
ORDERING DATA
Features• 24 hour electromechanical plug-in timer
• Captive trippers
• Programming resolution of 15 minutes
• Easy to program
• Manual override
T100 Plug-in Timer
SPECIFICATIONS:
Voltage: 110-120VAC
Switch Rating: 15A Resistive, 1800W
Ambient Temperature Range:14°F to 131°FGrounded 3-conductor plug andreceptacle
SPECIFICATIONS:
Voltage: 240VAC, 60Hz
Switch Rating: 20A Resistive
Ambient Temperature Range: 14°F to 122°FGrounded 3-conductor plug and receptacle
Features• 24 hour electromechanical plug-in timer
• Captive trippers
• Programming resolution of 15 minutes
• Heavy Duty 20A, 4800W
• Manual override
Features• Heavy Duty 20A, 4800W
• Manual override
• 24 hour electromechanical plug-in timer
• Captive trippers
• Programming resolution of 15 minutes
• Precise Movement
• Manual override
Features• 24 hour electromechanical plug-in timer
• Captive trippers
• Programming resolution of 15 minutes
• Easy to program
• Manual override
T240 Plug-in Timer
www.grasslin.com 201.825.9696 31
ELECTRONIC RESIDENTIAL TIMERS
CP924 Plug-in Timer
SPECIFICATIONS:Input Voltage: 120VACSwitch Rating: 15A Res. @ 120VACTime Base: Quartz StabilizedAmbient Temperature Range: 14°F to 122°FPrograms: 12 (6 on; 6 off)
T25/2E 24 hour/7 day Yes 1 minute 1 minuteTH-868 24 hour/7 day Yes 1 minute 1 minuteCP924 24 hour/7 day Yes 1 minute 1 minute
OPERATING FEATURES
Model Switch Program Reserve Program On/Off Every Shortest Switching Time
ORDERING DATA
Features• 24 hour and 7 day electronic plug-in timer• 12 programs• Built-in battery for reserve carry-over• Manual switch• One minute interval• Programming resolution of 1 minute
SPECIFICATIONS:
Voltage: 120VAC, 60Hz
Switch Rating: 15A Res.@ 120VAC, 1800W3-prong grounded plug and recepticle
Ambient Temperature Range: 14°F to 122°FPrograms: 12 (6 on; 6 off)
Features• 24 hour and 7 day electronic
plug-in timer
• 12 programs
• Built-in battery for reservecarry-over
• Manual switch
• One minute interval
• Programming resolution of 1minute
T25/2E Plug-in Timer
SPECIFICATIONS:
Input Voltage: 120VAC 60Hz
Switch Rating: 15A Res.@ 120VAC, 1800W
2-prong polarized plug and receptacle
Ambient Temperature Range: 14°F to 122°F
Programs: 16 (8 on; 8 off)
Features• 24-Hour and 7-Day
Electronic Plug-In timer
• Large LCD display andkeys
• 16 programs (8 on, 8 off)
• One minute interval
• AA size battery (+100 hours carryover)
• Manual override button
• Countdown Timer Function(up to 10 hours)
• Convenient receptacle onside (maintains low profile)
TH-868 Plug-in Timer
ACCESSORIES
www.grasslin.com 201.825.969632
E110 Metal IndoorEnclosureSteel NEMA 1 enclosure.Size: 5-1/8” x 7-7/8” x 3”;Grey painted finish.
E200 PlasticOutdoorEnclosurePlastic NEMA 3R raintight enclosurewith hinged door and latch.Provisions for mounting ANYGrasslin time control. Five combina-tion 1/2”-3/4” knockouts: In bottom,sides and back.Exterior Size: 6.5” x10” x 3.75” deep. Interior Size: 4.75”x 7.75” x 3” deep. Dark grey plasticfinish.
E150 PlasticIndoor EnclosurePlastic NEMA 1 enclosure with hinged door and latch.Provisions for mounting ANY Grasslin time control. Fivecombination 1/2”-3/4” knockouts: In bottom, sides andback. Exterior Size: 6.5” x 10” x 3.75” deep. Interior Size:4.75” x 7.75” x 3” deep. Pale grey plastic finish.
E150C and E200C same as E150/200except with clear see-thru cover
DIN RAILSDIN-4 4” Metal RailDIN-12 12” Metal RailMOUNTING BASESMB-DIN DIN Rail Mounting SubbaseMB-FMPC Printed Circuit Board Base for FM/1REPLACEMENT BATTERIESBAT-16/32 Battery for digi 16, digi 32BAT-14/56 Battery for digi 14, digi 56BAT-127 Battery for digi 127-4, 9RBAT-128 Battery for digi 128
CLEAR SEE-THROUGH/DUST COVERSDC-72 Clear Cover for MIL 72, MIL 2002, MIL 2008,
digi XX-72 ModelsDC-FME Clear Cover for FM/1 All ModelsDC-KM Clear Cover for KM/2 Series
TRIPPERST-2008-1 One Hour Trippers for MIL 2008; 1 ea., Green and RedT-2008-1/2 One Half Hour Trippers for MIL 2008; 1 ea., Green and
Red
HOUR METER ACCESSORIESBEZ-55G 55mm Sq. Bezel Adapter, Grey, UWZ 48EBEZ-55B 55mm Sq. Bezel Adapter, Black, UWZ 48EBEZ-72 72mm Sq. Bezel Adapter, Grey, UWZ 48EBEZ-72P 72mm Sq. Bezel Adapter w/pins for 3-Hole Pattern, Grey,
UWZ 48EMB-48V Mounting Base for UWZ 48VMP-RZ60 60mm Steel Mounting Bracket, RZ SeriesG55 Gasket for FWZ55 ModelsG72 Gasket for FWZ72 Models
GRASSLIN 4 IN. SCREWDRIVER
Miscellaneous Accessories
55mm Bezel for UWZ 48E
Ord. Info.:BEZ-55G GreyBEZ-55B Black
72mm Bezel for UWZ 48E
Ord. Info.:BEZ-72 Grey
72mm Bezel w/3 pins forround 3-bolt hole openingsfor UWZ 48E
Ord. Info.:BEZ-72P Grey
60mm steel mountingbracket for RZ Series
Ord. Info.: MP-RZ60
www.grasslin.com 201.825.9696 33
GE DEFINITE PURPOSE CONTACTORS
Outstanding performance meets all pertinent standards: UL Recognized Component, CSA, CE and ARI 780 – insuring long servicelife and suitable for HVAC/R, and other electrical applications. All ratings meet 6x, 5x, 4x locked rotor (Amp) rating at 240, 480 and600V respectively. Tested for endurance per ARI 780, all contactors meet or exceed for 500,000 mechanical and 200,000 electri-cal operations.
120 30 120 100 80 1 + Shunt
2
125 35 150 125 100 1 + Shunt
2
130 40 180 150 120 1 + Shunt
2
180 150 120 135 50 1 + Shunt
210 175 140 2
40 50 240 200 160 2
Resistive Locked Rotor Amps, Single Phase, 50/60Hz
Full Load Amps Amps Per Pole 240/277V 480V 600V Poles
CR453C Electrical Ratings
Resistive Three Phase, 50/60Hz Single PhaseFull Load Amps Per 204V 480V 600V HP, 50/60Hz
Amps Pole HP LRA HP LRA HP LRA 120V 240V Poles
225 35 7.5 150 10 125 10 100 2 3 3
230 40 10 180 15 150 15 120 2 5 3
240 50 10 240 20 200 20 160 3 7.5 3
CR453A Electrical Ratings
GE DEFINITE PURPOSE CONTACTORS
www.grasslin.com 201.825.969634
Full Load Resistive Locked Rotor Amps, Three Phase, 50/60HzAmps Amps Per Pole 240V 480V 600V Poles
250 62 300 250 200 3
260 75 360 300 240 3
275 90 450 375 300 3
290 90 540 450 360 3
2120 120 720 600 480 3
2150 150 900 750 600 3
CR353 Electrical Ratings
Full LoadCatalog UPC No. Coil Volt Amps ResistiveNumber 0783166 (60Hz) (Inductive) Amps/Pole
Compact 1 - Pole (Standard Type)CR453CA1AAA 60826 110-120 20 30CR453CA1BAA 60827 208-240 20 30 CR453CA1HAA 60829 24 20 30 CR453CC1AAA 60850 110-120 30 40 CR453CC1BAA 60851 208-240 30 40 CR453CC1HAA 60853 24 30 40
Compact 1-1/2 - Pole [w/Shunt] (Standard Type)CR453CA3AAA 60834 110-120 20 30 CR453CA3BAA 60835 208-240 20 30 CR453CA3HAA 60837 24 20 30CR453CB3AAA 60846 110-120 25 35 CR453CB3BAA 60847 208-240 25 35 CR453CB3HAA 60849 24 25 35 CR453CC3AAA 60858 110-120 30 40 CR453CC3BAA 60859 208-240 30 40 CR453CC3HAA 60861 24 30 40 CR453CD3AAA 60870 110-120 35 50 CR453CD3BAA 60871 208-240 35 50 CR453CD3HAA 60873 24 35 50
Compact 1 - Pole (Standard Type)CR453CA2AAA 60830 110-120 20 30 CR453CA2BAA 60831 208-240 20 30 CR453CA2HAA 60833 24 20 30 CR453CB2AAA 60842 110-120 25 35 CR453CB2BAA 60843 208-240 25 35 CR453CB2HAA 60845 24 25 35 CR453CC2AAA 60854 110-120 30 40CR453CC2BAA 60855 208-240 30 40 CR453CC2HAA 60857 24 30 40 CR453CE2ABB 60926 110-120 40 50 CR453CE2BBB 60927 208-240 40 50 CR453CE2HBB 60929 24 40 50
2 - Pole (Standard Type)CR453AB2AAA 61115 110-120 25 35CR453AB2BAA 61123 208-240 25 35CR453AB2DAA 61136 550-600 25 35
Full LoadCatalog UPC No. Coil Volt Amps ResistiveNumber 0783166 (60Hz) (Inductive) Amps/Pole
3 - Pole (Standard Type)CR453AB3AAA 61162 110-120 25 35CR453AB3BAA 61179 208-240 25 35CR453AB3HAA 61216 24 25 35CR453AC3AAA 61290 110-120 30 40CR453AC3BAA 61305 208-240 30 40CR453AC3HAA 61347 24 30 40CR453AD3ABB 61422 110-120 40 50CR453AD3BBB 61442 208-240 40 50CR453AD3HBB 61486 24 40 50
3 - Pole High Amperage (Standard Type)CR353FE3BA1 40665 110-120 50 62CR353FE3BB1 40673 208-240 50 62CR353FE3BH1 40680 24 50 62CR353FF3BA1 40704 110-120 60 75CR353FF3BB1 40711 208-240 60 75CR353FF3BH1 40715 24 60 75CR353EG3BA1 40594 110-120 75 90CR353EG3BB1 40604 208-240 75 90CR353EG3BH1 60414 24 75 90CR353EH3BA1 40631 110-120 90 90CR353EH3BB1 40640 208-240 90 90CR353EH3BH1 40647 24 90 90CR353GJ3AA1 40723 115-120 120 120CR353GJ3AB1 40728 230-240 120 120CR353GK3AA1 40734 115-120 150 150CR353GK3AB1 40737 230-240 150 150
4 - Pole High Amperage (Standard Type)CR353AC4AA1 40331 110-120 30 40CR353AC4AB1 40333 208-240 30 40CR353AC4AH1 40339 24 30 40CR353AD4BA1 40429 110-120 40 50CR353AD4BB1 40433 208-240 40 50CR353AD4BH1 40439 24 40 50
ORDERING DATA
www.grasslin.com 201.825.9696 35
APPLICATION GUIDE
GMX digi 20 7 1 24 hr./7 day 20 140 Manual 5 day ✔ ✔ SPDT 16A I or O
GMX digi 42 7 1 24 hr./7 day 42 294 ✔ Automatic 7 day ✔ ✔ SPDT 16A I or O
GMX2 digi 42 7 2 24 hr./7 day 42 588 ✔ Automatic 7 day ✔ ✔ 2 SPDT 16A I or O
GM1 digi 20 6 1 24 hr./7 day 20 140 Manual 5 day ✔ ✔ SPDT 30A I or O
GM1 digi 42 6 1 24 hr./7 day 42 294 ✔ Automatic 7 day ✔ ✔ SPDT 30A I or O
GMD digi 20 6 1 24 hr./7 day 20 140 Manual 7 day ✔ ✔ DPDT 30A I or O
GMD digi 42 6 1 24 hr./7 day 42 294 ✔ Automatic 7 day ✔ ✔ DPDT 30A I or O
Digi 20A 8 1 24 hr./7 day 20 140 Manual 5 day ✔ ✔ SPDT 16A S, D
Digi 20E 8 1 24 hr./7 day 20 140 Manual 5 day ✔ ✔ SPDT 16A F
Digi 42A 8 1 24 hr./7 day 42 294 ✔ Automatic 7 day ✔ ✔ SPDT 16A S, D
Digi 42E 8 1 24 hr./7 day 42 294 ✔ Automatic 7 day ✔ ✔ SPDT 16A F
Digi 42/2 9 2 24 hr./7 day 42 588 ✔ Automatic 7 day ✔ ✔ 2 SPDT 16A S, F*
talento 471 10 1 24-hr/7-day 30 210 Auto 3-yrs ✔ ✔ ✔ SPDT 16A S,D,I,O
talento 472 10 2 24-hr/7-day 40 560 Auto 3-yrs ✔ ✔ ✔ 2-SPDT 16A S,D,I,O
talento 891 10 1 24hr/7day/365day 400 2800 ✔ Auto 6-yrs ✔ ✔ ✔ SPDT 16A S,D,I,O
talento 892 10 2 24hr/7day/365day 400 5600 ✔ Auto 6-yrs ✔ ✔ ✔ 2-SPDT 16A S,D,I,O
talento 894 10 4 24hr/7day/365day 400 11,200 ✔ Auto 6-yrs ✔ ✔ ✔ 4-SPDT 16A S,D,I,O
FM/1 digi 20 13 1 24 hr./7 day 20 140 Manual 5 day ✔ ✔ SPDT 16A S
FM/1 digi 42 13 1 24 hr./7 day 42 294 ✔ Automatic 7 day ✔ ✔ SPDT 16A S
PC1-digi 20† 18 1 24 hr./7 day 16 112 Manual 7 day ✔ ✔ SPDT 16A S,D,I,O
PC2-digi 30† 18 2 24 hr./7 day 32 224 Manual 7 day ✔ ✔ SPDT 16A S,D,I,O
†With photo-electric controls
Mounting
Ratin
gSwitc
h
TypeMom
enta
ry
Contact
Manual
Overri
de
Daylig
ht
Savin
gs Tim
e
Change
Batte
ry
Backu
p
Holiday
Max. O
n/Off
Events
/Wk.
Number
of
Progra
ms
No. Chan
nels
Page
No.
Switch
Progra
m
Mainta
in
Contact
Model
1. Programs: A program consists of a time, one or more days of the week, and an on or off event.Example: “5:00p.m./ Mon., Tue., Wed., Thur., Fri./ Off” is one program.
2. Daylight Savings Time: Manual = Time change accomplished with single press of ±1 hr. key.Auto = Automatically changes time.
3. Mounting: S = Surface D = DIN RailF = Flush I or O = Available in either indoor or outdoor enclosure*Optional DIN Mounting base available—See accessories**Optional Flush Mountingkit available—See accessories
4. Enclosures: Indoor and outdoor enclosures are available for all time controls.
5. Standard Voltages: 24VAC/DC, 120V and 208/240V, all models are 50/60Hz.
Electronic Time Control Features
How to Select The Correct Time Switch for Your Application• 24 Hour Switch Program: If the same schedule repeats itself every day of the week.• 7 Day Switch Program: If a different schedule is required for different days of the week, or if it is desired to “skip” certain days.• Reserve Carry-Over: If it is desirable that the time switch retain the correct time of day during a power outage.• Surface Mounting: If the time switch is to be installed inside an enclosure; or if class 2 wiring is used and it is mounted to a wall
or other surface.• Flush Mounting: If the time switch is installed through a panel opening so that the face is on the outside of the panel.• DIN Rail Mounting: If it is to be mounted to a DIN rail within an enclosure or panel.
NOTES ON ELECTRONIC TIME CONTROL FEATURES
APPLICATION GUIDE
www.grasslin.com 201.825.969636
GMX-ST 3 24 hr. 15 min. 48 Captive ✔ SPDT 21A Indoor or Outdoor Encl.GMX-SW 3 7 day 2 hr. 42 Captive ✔ SPDT 21A Indoor or Outdoor Encl.GMX-QT 3 24 hr. 15 min. 48 Captive ✔ SPDT 21A 7 days Indoor or Outdoor Encl.GMX-QW 3 7 day 2 hr. 42 Captive ✔ SPDT 21A 7days Indoor or Outdoor Encl.GM1-ST-MV 2 24 hr. 15 min. 48 Captive ✔ SPDT 30A Indoor or Outdoor Encl.GM1-SW-MV 2 7 day 2 hr. 42 Captive ✔ SPDT 30A Indoor or Outdoor Encl.GM1-QT-MV 2 24 hr. 15 min. 48 Captive ✔ SPDT 30A 7 days Indoor or Outdoor Encl.GM1-QW-MV 2 7 day 2 hr. 42 Captive ✔ SPDT 30A 7 days Indoor or Outdoor Encl.GMD-ST-MV 2 24 hr. 15 min. 48 Captive ✔ DPDT 30A Indoor or Outdoor Encl.GMD-SW-MV 2 7 day 2 hr. 42 Captive ✔ DPDT 30A Indoor or Outdoor Encl.GMD-QT-MV 2 24 hr. 15 min. 48 Captive ✔ DPDT 30A 7 days Indoor or Outdoor Encl.GMD-QW-MV 2 7 day 2 hr. 42 Captive ✔ DPDT 30A 7 days Indoor or Outdoor Encl.
MIL 72A STuZ 5 24 hr. 15 min. 48 Captive SPDT 21A ✔ ✔
MIL 72A STuZH 5 24 hr. 15 min. 48 Captive ✔ SPDT 21A ✔ ✔
MIL 72A QTuZ 5 24 hr. 15 min. 48 Captive SPDT 21A 7 days ✔ ✔
MIL 72A QTuZH 5 24 hr. 15 min. 48 Captive ✔ SPDT 21A 7 days ✔ ✔
MIL 72E STuZ 5 24 hr. 15 min. 48 Captive SPDT 21A ✔
MIL 72E STuZH 5 24 hr. 15 min. 48 Captive ✔ SPDT 21A ✔
MIL 72E QTuZ 5 24 hr. 15 min. 48 Captive SPDT 21A 7 days ✔
MIL 72E QTuZH 5 24 hr. 15 min. 48 Captive ✔ SPDT 21A 7 days ✔
MIL 72A SWuZ 5 7 day 2 hr. 42 Captive SPDT 21A ✔ ✔
MIL 72A SWuZH 5 7 day 2 hr. 42 Captive ✔ SPDT 21A ✔ ✔
MIL 72A QWuZ 5 7 day 2 hr. 42 Captive SPDT 21A 7 days ✔ ✔
MIL 72A QWuZH 5 7 day 2 hr. 42 Captive ✔ SPDT 21A 7 days ✔ ✔
MIL 72E SWuZ 5 7 day 2 hr. 42 Captive SPDT 21A ✔
MIL 72E SWuZH 5 7 day 2 hr. 42 Captive ✔ SPDT 21A ✔
MIL 72E QWuZ 5 7 day 2 hr. 42 Captive SPDT 21A 7 days ✔
MIL 72E QWuZH 5 7 day 2 hr. 42 Captive ✔ SPDT 21A 7 days ✔
FM/1 STuZ 12 24 hr. 15 min. 48 Captive SPDT 21A ✔
FM/1 STuZH 12 24 hr. 15 min. 48 Captive ✔ SPDT 21A ✔
FM/1 QTuZ 12 24 hr. 15 min. 48 Captive SPDT 21A 7 days ✔
FM/1 QTuZH 12 24 hr. 15 min. 48 Captive ✔ SPDT 21A 7 days ✔
FM/1 SWuZ 12 7 day 2 hr. 42 Captive SPDT 21A ✔
FM/1 SWuZH 12 7 day 2 hr. 42 Captive ✔ SPDT 21A ✔
FM/1 QWuZ 12 7 day 2 hr. 42 Captive SPDT 21A 7 days ✔
FM/1 QWuZH 12 7 day 2 hr. 42 Captive ✔ SPDT 21A 7 days ✔
KM2 STuH 16 24 hr. 20 min. 36 Captive ✔ SPDT 21A ✔
KM2 ST-1G 16 24 hr. 20 min. 36 Captive ✔ SPST 20A In-Wall
DIN R
ail
Mounting
Flush
Pan
el
Mounting
Surface
Mounting
Batte
ry
Backu
pSwitc
h
TypeMan
ual
Overri
de
Trip
per
TypeMax
. On/O
ff
Events
Min. O
n/Off
TimeSwitc
h
Progra
m
Page
No.
Ratin
gModel
Electromechanical Time Control Features
NOTES:1. Enclosures: Indoor and outdoor enclosures are available for all time controls.2. Standard Voltages: 24VAC/DC, 120VAC, 240VAC 60Hz – Many models also available in 50Hz.
Multivolt units will operate on 120VAC, 208/240VAC, 277VAC.Quartz drive, battery backup models are all 50/60Hz and also operate on DC voltages: 12V, 30V, etc.
www.grasslin.com 201.825.9696 37
COMPETITIVE CROSS REFERENCE
24 Hour Time Switches
Grasslin Intermatic Tork ParagonT101 1101 P101
GMX ST-I-120 T101(B) 8001 1015-00RST1906T101P 1101-N P101P
GMX ST-O-120 T101(B) 8001-N 42011-00T1905-R
GMX2P40 T104 1104 4004-20P104
T101 1101 P101T101(B) 1102 4001-00
T102 8001 4002-71GM1 ST-I-MV T102(B) 8004 4005-00
T105 1015-00RST185T1905T1906T101P 1101-N P101PT101R 1102-N 4011-00(P)
T101(B) 8001-N 42011-00T102P 8004-N 24011-20
GM1 ST-O-MV T102RT102(B)T106R
T1905RT1906R
T101 1101 P103T102 1102 P104
GMD ST-I-MV T103 1103 4003-00T104 1104 4004-71T105 1015-00RST103 1101-N P103P
T103P 1102-N P104PT103R 1103-N 4011-00(P)
GMD ST-O-MV T104 1104-N 4013-00T104P 8002N 4014-71T104R 8042N 42013-00
42013-20
Electronic Time SwitchesSingle Channel 24 Hour
Grasslin Paragon Intermatic Tork
GMX digi 20-I-120 EC4000/120V - E120GMX digi 20-OC-120 EC4000PC/120V - -GMX digi 20-I-240 EC4000/208-277V - E120-2GM1 digi 20-I-120 EC4004/120V ET100C E101GM1 digi 20-OC-120 EC4004PC/120V - -GM1 digi 20-I-240 EC4004/208-277V ET101C E101-2GMD digi 20-OC-120 EC4005PC/120, 208-240V ET103C -GMD digi 20-OC-240 EC4005PC/120, 208-240V ET103C E103
1 and 2 Channel 24 Hour / 7 DayGMX digi 20-I-24 EC7000/24V - -GMX digi 20-I-120 EC7000/120V ET715C EW120GMX digi 20-I-240 EC7000/208-277V ET715C EW120-2/-3GMX digi 20-OC-120 EC7000PC/120V - -GM1 digi 20-I-120 EC7004/120V ET171C EW101GM1 digi 20-I-240 EC7004/208-277V ET171C EW101-2GMD digi 20-OC-120 EC7005PC/120,208-240V ET173C EW103GMD digi 20-OC-240 EC7005PC/120,208-240V ET173C EW103-2/-3GMX digi 42-I-120 EC71/30S/120 ET715C DIN101ADigi 20A-120 - - DIN100Digi 42A-24 EC71D/30S/24Digi 42A-120 EC71D/30S/120 - -Digi 42A-240 EC71D/30S/240 - -Digi 42/2-120 - - DIN200
One, Two, Four & Eight Channel Electronic
GMX 891-I-120 EC71/18S/120 ET70115C DTS100Atalento 891-120 EC71D/18S/120 - -talento 891-24 EC71D/18S/24 - DTS100A-24GMX 892-I-24 EC72/24 ET70215CR24 DTS200A-24GMX 892-I-120 EC72/120 ET70215C DTS200Atalento 892-24 EC72D/24 - -talento 892-120 EC72D/120 - -GMX 894-I-24 EC74/50S/24V ET70415CR24 DZS400A-24GMX 894-I-120 EC74/50S/120V ET70415CR DZS400Atalento 894-24 EC74/120D/24V - -talento 894-120 EC74/120D/120V - -SRS 3800 EC77/120, 240 - -All talento 800 series units are available with or without an enclosure
7 Day Electromechanical Time SwitchesGrasslin Intermatic Tork Paragon
T171 7100 P101-ST172 7102 1015-00RS
T171B 7120 1015-00RSBT172B 7122 42011-00
GM1 SW-I-MV T175 W100 42011-20T176 W120 4005-00S
T1975 8001 4005-00SBT1976 8004 4006-71ST2005 8007T2006 8008
T173 7200 4003-00ST174 7202 4003-00S
T1871BR 7220 4004-71ST1872BR 7222 4013-SS0
GMD SW-O-MV T7801B W200 4014-71ST7802B W202 P103-S
W220 P103-PSW222 P104-S8042N P104-PS
42013-0042013-207008-007008-71
GMXSW-4 Pole T7401/2B W400A/402A 7007
Universal Replacement Defrost Timers
Grasslin Paragon Precision
8041-00 6041-008141-00 6141-008143-00 6143-008145-00 6145-008041-00 6041-008043-00 6043-008045-00 6045-008046-00 -8047-00 6047-008141-20 6141-208143-20 6143-208145-20 6145-208041-20 6041-208043-20 6043-208045-20 6045-208046-20 -8047-20 6047-208245-20 6245-208243-20 6243-208247-20 6247-20
Competitive model numbers are provided as a general reference and do not imply exact equals as some features may vary.
DTMV
COMPETITIVE CROSS REFERENCE
www.grasslin.com 201.825.969638
Spring Wound Interval Timers
Photo Controls
Grasslin Paragon Intermatic Tork RhodesKLT5M - FD5M A505M -KLT5M-W - - A505MW -KLT5MH - FG5MH - -KLT5MH-W - - - -KLT5M-A SWP5M FF5M - 9304MKLT5MH-A - FF5MH - 9304MHKLT15M SWPD15M FD15M A515M 9315MIKLT15M-W SWPD15M-W - A515MW 9315MHKLT15MH SWPD15MH FD15MH A515MH 9315MHIKLT15MH-W SWPD15MH-W - A515MHW 9315MHWKLT15MC - - - -KLT15MC-W - - - -KLT15M-A SWP15M FF15M - 9315MHKLT15MH-A SWP15MH FF15MH - -KLT15MC-A - - - -KLT30M SWPD30M FD30M A530M 9330MIKLT30M-W SWPD30M-W - A530MW 9330MWKLT30MH SWPD30MH FD30MH A530MH 9330MHIKLT30MH-W SWPD30MH-W - A530MHW -KLT30MC - - - -KLT30MC-W - - - -KLT30M-A SWP30M FF30M - 9330MKLT30MH-A SWP30MH FF30MH - 9330MHKLT30MC-A - - - 90011KLT60M SWPD60M FD60M A560M 9360MIKLT60M-W SWPD60M-W - A560MW 9360MWKLT60MH SWPD60MH FD60MH A560MH 9360MHI
KLT60MH-W SWPD60MH-W - A560MHW -KLT60M-A SWP60M FF60M - 9360MKLT60MH-A SWP60MH FF60MH - 9360MHKLT2H - - A502H -KLT2H-W - - A502HW -KLT2HH - - A502HH -KLT2HH-W - - A502HHW -KLT2H-A SWP2H - - 9302HKLT2HH-A SWP2HH - - 9302HHKLT4H - - A504H -KLT4H-W - - A504HW -KLT4HH - - A504HH -KLT4HH-W - - A504HHW -KLT4H-A SWP4H - - 9304HKLT4HH-A SWP4HH - - 9304HHKLT6H SWPD6H FD6H A506H 9306HIKLT6H-W - - A505HW -KLT6HH - FD6HH A506HH -KLT6HH-W - - A506HHW -KLT6H-A SWP6H FF6H - 9306HKLT6HH-A SWP6HH FF5HH - 9306HHKLT12H SWPD12H FD12H A512H 9312HIKLT12H-W SWPD12H-W - A512HW 9312HWKLT12HH SWPD12HH FD12HH A512HH 9312HHIKLT12HH-W SWPD12HH-W - A512HHW 9312HHWKLT12H-A SWP12H FF12H - 9312HKLT12HH-A SWP12HH FF12HH - 9312HH
GRASSLIN PARAGON INTERMATIC TORK ALR FISHER PIERCE PRECISIONCM-120 CW201-00 K4121 2000 PT-15 FT-15 T-15CM-287 CW201-71 K4124 2000-2 PT-168 FT-168 T-168CM-127 CW201-70 - 2000-7 PT-20 - -CMS-120 CW201S-00 K4221 2001 SPT-15 SFT-15 ST-15CMS-287 - K4224 2002 SPT-168 SFT-168 ST-168CMP-120 PN201-00 - 2021 TL-115 FL-115 ET-15CMP-287 - - 2022 TL-1168 - ET-168CMM-1120 CW201-00 - 2101 AT-15 - -CMM-1287 CW201-71 - 2104 AT-168 - -CMM-1127 CW201-70 - 2107 AT-20 - -BT-120 LB201-00 K4021 3000 AA-105 FA-105 A-105BT-287 LB201-71 K4022, 4, 33 3002 AA-1068 FA-1068 A-1068BTW-120 LB201W-00 K4321 3010 AA-105W FA-105W A-105WTLD-1120 TL201-00 LC4521 5001S - NFP-120 LM-2275TLDV-1120 - - 5001M M-120 NFP-120E -TLD-1287 TL201-71 K4524 5004S BF-208 FP-208-277 LM-58275TLDV-1287 - - 5004M M-208-277 NFP-277E -TLD-1185 TL201-70 - 5007S BF-PV - P-26275TLDV-1185 - - 5007M M-PV - -TLD-1480 - K4535 5008S* M480 - P7275TLDV-1480 - K4535 5008M* M-480 NFP-480 LM-7275MOVTLD-120 - LC4521 5021S LC-120 NFP-120 P-2275TLDV-120 - - 5021M BF-120 - LM-2275MOVTLD-287 TL201-71 LC4523 5024S LC-208-277 NFP-208-277 P-68275TLDV-287 - - 5024M BF-208-277 - LM-68275MOVTLI-1120 - K1221 2005 - 7760 8660TLI-1185 - - 2007 - 7790 8690TLI-1480 - - 2008* - 7794 8694RG - - 2223 AM-1-A-NB S476-81 603RB - - 2224 AM-1-A S476-81 -RCB TB201-99 K122 2421 AM-2-A S-476-71 M-2ASC SC201-99 K4500 5500 SC-10 NS1038-1 JP-275
Grasslin Paragon Intermatic Tork Rhodes
MINUTE INTERVALS HOUR INTERVALS
www.grasslin.com 201.825.9696 39
Model Code Index
BAT-127 ...................................................32BAT-128 ...................................................32BAT-14/56.................................................32BAT-16/32.................................................32BEZ-55 Black ...........................................32BEZ-55 Gray ............................................32BEZ-72 .....................................................32BEZ-72P ...................................................30BT-120 .....................................................21BT-287 .....................................................21BTW-120...................................................21CM-120 ...................................................20CM-127 ...................................................20CM-287 ...................................................20CMM-1120 ..............................................20CMM-1127 .............................................20.CMP-120 .................................................20CMP-287 .................................................20CMS-120...................................................20CMS-287...................................................20CP924.......................................................31CR353.......................................................34CR453.......................................................33DC-FME....................................................32DC-KM2 ..................................................32DIGI20A ....................................................8DIGI20E......................................................8DIGI42/2 ...................................................9DIGI42A ....................................................8DIGI42E......................................................8DIN-12......................................................32DIN-4........................................................32DTMV.......................................................22DTQMV....................................................22DT140-digi20 ..........................................22E110..........................................................32E150..........................................................32E150C.......................................................32E200..........................................................32E200C.......................................................32ET616 ......................................................15ET724 ......................................................17FM/1 Digi20 ............................................13FM/1 Digi42 ............................................13FM/1 QTuZ...............................................12FM/1 QWuZ ............................................12FM/1 S 12H .............................................26FM/1 STuZ ...............................................12FM/1 SWuZ .............................................12FWZ 36.....................................................28FWZ 53.....................................................28FWZ 55.....................................................28
FWZ 55K...................................................28FWZ 72.....................................................28FWZ 72B...................................................28G-55..........................................................30GZ-55........................................................27GZ-72........................................................27GM1-digi20 ...............................................6GM1-digi42 ...............................................6GM1QT .....................................................2GM1QW.....................................................2GM1ST........................................................2GM1SW......................................................2GMD-digi20 ..............................................6GMD-digi42 ..............................................6GMDQT......................................................2GMDQW ....................................................2GMDST.......................................................2GMDSW ....................................................2GMX-digi20 ..............................................7GMX-digi42 ..............................................7GMX121...................................................26GMX2-digi42 ............................................9GMX2P40.................................................34GMX471...................................................10GMX472...................................................10GMX891...................................................10GMX892...................................................10GMX894...................................................10GMXQT......................................................3GMXQW ....................................................3GMXST.......................................................3GMXSW ....................................................3GZ40A .....................................................27GZ40B.......................................................27GZ41.........................................................27GZ52A/B...................................................27KLT12H ...................................................14KLT15M....................................................14KLT2H .....................................................14KLT30M....................................................14KLT4H .....................................................14KLT5M......................................................14KLT60M....................................................14KLT6H .....................................................14KM2 STuH ...............................................16KM2 SWuH...............................................16KM2ST-1G ...............................................16KM2ST-2D ...............................................16KM2ST-2G ...............................................16KM2ST-2R.................................................16KM2ST-3D ...............................................16KM2ST-3G ...............................................16
KM2ST-4G ...............................................16KM2STST-2G ...........................................16KM2STU-1G ............................................16KM2STU-2G ............................................16LM1 .........................................................18LM1-digi20...............................................19LM2 .........................................................18LM2-digi30...............................................19MB-48Y.....................................................30MB-DIN ...................................................32MB-FMPC ................................................32MIL72AQTUZH ..........................................5MIL72AQWUZH .......................................5MIL72ASTUZ..............................................5MIL72ASTUZH ..........................................5MIL72ASWUZ ...........................................5MIL72ASWUZH..........................................5PC1...........................................................18PC1-digi20................................................19PC2...........................................................18PC2-digi30................................................19RCB...........................................................21RZ 52 .......................................................27RZ 60 .......................................................27SC ...........................................................20.SRS3800....................................................11T100 ........................................................30T240 ........................................................30T25 ..........................................................30T25/2E .....................................................31T35 ..........................................................30TALENTO-121 .........................................26TALENTO-471 .........................................10TALENTO-472 .........................................10TALENTO-891 .........................................10TALENTO-892 .........................................10TALENTO-894 .........................................10TAXXI-DIALOG-SET.................................10TH-868 ....................................................31TLD-1185..................................................21TLD-120....................................................21TLD-1480..................................................21TLD-287....................................................21UWZ 48 ....................................................29UWZ 48A..................................................29UWZ 48E ..................................................29UWZ 48V ................................................29UWZ 52E ..................................................29WH-4..........................................................4WH-7..........................................................4
Model Code Page Model Code Page Model Code Page
REPLACEMENT CROSS REFERENCE
www.grasslin.com 201.825.969640
It’s Time
To Switch!
Discontinued Time SwitchesThe following time switches, which were discontinued, are shown below with their replacements. Inall cases, the size and physical configuration of the replacement is identical, and in most cases themounting holes are the same.
Discontinued Models RecommendedModel - Voltage Replacement
Discontinued Models RecommendedModel - Voltage Replacement
Electromechanical Single Pole
MIL 2008 SFTu-120 MIL 72A STuZH-120MIL 2008 SFTu-240 MIL 72A STuZH-240MIL 2008 SFTu-24 MIL 72A STuZH-24MIL 2008 SFWu-120 MIL 72A SWuZH-120MIL 2008 SFWu-240 MIL 72A SWuZH-240MIL 2008 SFWu-24 MIL 72A SWuZH-24MIL 2008 QFRTu-120 MIL 72A QTuZH-120MIL 2008 QFRTu-240 MIL 72A QTuZH-240MIL 2008 QFRTu-24 MIL 72A QTuZH-24MIL 2008 QFRWu-120 MIL 72A QWuZH-120MIL 2008 QFRWu-240 MIL 72A QWuZH-240MIL 2008 QFRWu-24 MIL 72A QWuZH-24V86 S1hu talento 121
Electromechanical ElectronicDouble Pole Double Pole
MIL 2008 SDT2u-120 Digi 42/2-120MIL 2008 SDT2u-240 Digi 42/2-240MIL 2008 SDT2u-24 Digi 42/2-24MIL 2008 SDW2u-120 Digi 42/2-120MIL 2008 SDW2u-240 Digi 42/2-240MIL 2008 SDW2u-24 Digi 42/2-24MIL 2008 QDRT2u-120 Digi 42/2-120MIL 2008 QDRT2u-240 Digi 42/2-240MIL 2008 QDRT2u-24 Digi 42/2-24MIL 2008 QDRW2u-120 Digi 42/2-120MIL 2008 QDRW2u-240 Digi 42/2-240MIL 2008 QDRW2u-24 Digi 42/2-24
For Electromechanical replacement, GMD Series may be used.
Electronic Two Channel
Digi 32-72/2-120 Digi 42/2-120Digi 32-72/2-240 Digi 42/2-240Digi 32-72/2-24 Digi 42/2-24Digi 56-72/2-120 Digi 42/2-120Digi 56-72/2-240 Digi 42/2-240Digi 56-72/2-24 Digi 42/2-24Digi 322-45/2Y-120V talento 892-24VDigi 322-45/2Y-24V talento 892-120VGMX2 digi 32-I-120 GMX2 digi 42-I-120GMX2 digi 32-I-240 GMX2 digi 42-I-240GMX2 digi 32-I-24 GMX2 digi 42-I-24GMX2 digi 32-O-120 GMX2 digi 42-O-120GMX2 digi 32-O-240 GMX2 digi 42-O-240GMX2 digi 32-O-24 GMX2 digi 42-O-24
Electronic One Channel
Digi 14-72/1-120 Digi 20A-120Digi 14-72/1-240 Digi 20A-240Digi 14-72/1-24 Digi 20A-24Digi 16-72/1-120 Digi 20A-120Digi 16-72/1-240 Digi 20A-240Digi 16-72/1-24 Digi 20A-24Digi 56-72/1-120 Digi 42A-120Digi 56-72/1-240 Digi 42A-240Digi 56-72/1-24 Digi 42A-24Digi 322-45/1Y-120V talento 891-120VDigi 322-45/1Y-240V talento 891-240VDigi 322-45/1Y-24V talento 891-24VFM/1 digi 16-12DC FM/1 digi 42-12DCFM/1 digi 16-120 FM/1 digi 20-120FM/1 digi 16-240 FM/1 digi 20-240FM/1 digi 16-24 FM/1 digi 20-24GM1 digi 16-I-120 GM1 digi 20-I-120GM1 digi 16-I-240 GM1 digi 20-I-240GM1 digi 16-O-120 GM1 digi 20-O-120GM1 digi 16-O-240 GM1 digi 20-O-240GMD digi 16-I-120 GMD digi 20-I-120GMD digi 16-I-240 GMD digi 20-I-240GMD digi 16-O-120 GMD digi 20-O-120GMD digi 16-O-240 GMD digi 20-O-240GMX digi 16-I-120 GMX digi 20-I-120GMX digi 16-I-240 GMX digi 20-I-240GMX digi 16-O-120 GMX digi 20-O-120GMX digi 16-O-240 GMX digi 20-O-240MIL 72A digi 16-120 Digi 20A-120MIL 72A digi 16-240 Digi 20A-240MIL 72A digi 16-24 Digi 20A-24MIL 72E digi 16-120 Digi 20E-120MIL 72E digi 16-240 Digi 20E-240MIL 72E digi 16-24 Digi 20E-24
Electronic Multi-Channel
Digi 127 (4 channel) Digi 322-45/4Digi 127-9 (9 channel) SRS-3800 (8 Channel)Digi 128 (4 channel) Digi 322-45/4Digi 322-45/4-120V talento 894-120VDigi 322-45/4Y-120V talento 894-120VDigi 322-45/4Y-240V talento 894-240VDigi 322-45/4Y-24V talento 894-24V
Grasslin Time Controls are available from HVAC, Refrigeration, Electrical, and Industrial ControlsWholesalers and Distributors throughout the US and Canada. If your distributor does not stockGrasslin controls, please ask him to special order for you, or call us at 1-800-272-1115 for the loca-tion of the nearest Grasslin stocking distributor. Normal Grasslin lead time on shipment of orders is 1-2 days after receipt of the order.
For technical questions or to obtain detailed literature on a product, FAX us at 1-201-825-8694, orfor immediate service, call 1-800-272-1115 between 8 a.m. and 5 p.m. Eastern Time.
Visit Our Web Site: www.grasslin.com
GE GRASSLIN GmbH & Co. KG, a General Electric Company, is ISO 9001 certified, which is
evidence that the highest standards of quality control and the capability to provide excellent
products and services are present in all Grasslin facilities.
WarrantyGrasslin Controls Corp. products are warranted to be free from defects in workmanship or material under normal use and serv-ice for a period of one year from date of purchase by the installer or user. Grasslin’s Warranty is to the original purchaser only,but is extended to you by the Distributor or OEM from whom you purchased.
Grasslin’s obligation under this Warranty is limited to replacing with a new or repaired unit to the original purchaser. The unitmust be returned, and replacements obtained from the Distributor or OEM from whom it was purchased.
This Warranty will not apply if, in the judgement of Grasslin Controls Corp., damage or failure has resulted from accident, alter-ation, misuse, abuse or operation in an incorrect power supply.
Under no circumstances shall Grasslin Controls Corp. be liable to purchaser or any third party for any loss of profits or otherdirect or indirect costs, expenses, losses or consequential damages arising out of or as a result of any defects in or failure ofGrasslin Products or any part or parts thereof.
THIS WARRANTY IS IN LIEU OF ANY OTHER WARRANTY, EITHER EXPRESSED OR IMPLIED, AS TO DESCRIPTION, QUAL-ITY, MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE OR USE, OR ANY OTHER MATTER.
Grasslin reserves the right to change or modify the design or specifications of products at any time without notice or obligation.
©2004 Grasslin Controls Corp.
Specifications and other information in this catalog are subject tochange without notice.
Printed in USA 065 01.04
GRASSLIN CONTROLS CORPORATIONA GE Industrial Systems Company31 Industrial Ave. • Mahwah, New Jersey 07430Tel.: 201-825-9696 • Fax: 201-825-8694www.grasslin.com