Analysis on the performance of distance relay during fault impedance near zone 1 reach for different...

16
Analysis on the Performance of Distance Relay during Fault Impedance near Zone 1 Reach for Different Load Power Factor Muhd Hafizi Idris Surya Hardi Syafruddin Hasan Mohd Zamri Hasan School of Electrical System Engineering & Faculty of Engineering Technology Universiti Malaysia Perlis

Transcript of Analysis on the performance of distance relay during fault impedance near zone 1 reach for different...

Page 1: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Analysis on the Performance of Distance Relay during Fault Impedance near Zone 1 Reach for

Different Load Power FactorMuhd Hafizi Idris

Surya HardiSyafruddin Hasan

Mohd Zamri HasanSchool of Electrical System Engineering

& Faculty of Engineering TechnologyUniversiti Malaysia Perlis

Page 2: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Introduction Transmission line must be protected from any type of fault

to maintain the reliability and security of power system. There are two types of relay used to protect transmission

line, which are main and backup protection relays. Typical relays used as main protection relay are distance and current differential relays.

Distance relay measures the apparent impedance from relay point until fault point and send the trip signal when computed impedance is less than set impedance [1].

For current differential relay, it will measure the differential current between local and remote phase currents. When a fault occurred at transmission line, differential current will be higher than set pickup current and relay will send trip signal to isolate the line [2].

Page 3: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Distance Relay Principles The inputs for distance protection relay are three phase

current and voltage phasors [3]. Three phase current phasors are taken from current

transformer (CT) while three phase voltage phasors are taken from voltage transformer (VT).

Basic distance protection scheme

Page 4: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Distance Relay Principles When a fault occurred at transmission line, distance relay

will first determine the type of fault using internal phase selection feature.

Then, it will use the correct algorithm to calculate the fault impedance [5].

Different fault impedance calculation algorithms

Where; A, B and C indicate faulty phases. G indicates ground fault. VA, VB and VC indicate voltage phasors IA, IB and IC indicate current phasors Z0 = line zero-sequence impedance Z1 = line positive-sequence impedance k0 = residual compensation factor where k0 = (Z0-Z1)/Z1. I0 = zero-sequence current.

Page 5: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Distance Relay Principles There are many types of distance relay characteristics such as

Plain, Mho, Offset Mho, Polarized Mho, Reactance, Quadrilateral, etc.

Each type of characteristic is dedicated for different application and transmission line configuration [6].

Mho characteristic is typically used to protect long transmission line where fault resistance, Rf do not has much effect on the accuracy of distance relay [7].

Mho Characteristic

Page 6: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Distance Relay Principles Distance relay segregates the connected transmission lines into

different zones of protection typically zone 1, zone 2, zone 3, zone 3 offset or zone 3 reverse, load area, power swing area etc.

These zones are coordinated in sequence starting from zone 1. The nearer the fault to relay terminal, the higher the fault current and

the smaller the fault impedance will be thus faster tripping signal is required to isolate the fault.

For zones more than zone 1, delayed tripping signals are set to act as backup for zone 1 and also when other dedicated protection relays/zones fail to isolate the fault [7].

The computed fault impedance by distance relay might be different from the actual impedance until fault point.

The factors which can give significant effects on impedance measurement are line mutual impedance, current transformer saturation, high fault resistance, source impedance ratio, line charging current, remote current contribution, FACTs devices operation, etc [8-13].

Page 7: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Simulation Model The model was developed using Matlab/Simulink software. The transmission line choose is a spur transmission line. The reactive component of the load was varied to change the

load power factor. Single line-to-ground fault was simulated at a point near zone 1

reach/boundary setting (80% of line length).

Transmission line, source, load, power factor calculation and measurement subsystem

The reactive component was

changed to vary the power factor

Page 8: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Simulation Model

Overall model of the project

Apparent impedance algorithm used is for single line-to-ground fault. Fault resistance and fault reactance will be transferred to the

workspace and plotted onto impedance diagram to determine the location of fault (inside or outside of zone 1).

Page 9: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Simulation Results & Discussions

To see the effects of power factor variation on distance relay performance for fault near zone 1 reach boundary, fault was simulated at 2 locations which are at :1) 38.5 km (measured fault impedance just outside the

zone 1 reach boundary) 2) 38 km (measured fault impedance just inside the

zone 1 reach boundary). For each fault location, power factor was varied

for three conditions which are power factor equal to 1, 0.9 and 0.8.

Page 10: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Simulation Results & Discussions

The load was changed from purely consuming active power (case 1) to consuming both active and inductive reactive powers (case 2 and 3).

The effect of changing the load type was power factor was changed from unity power factor to 0.9 and 0.8 lagging power factors.

It can be seen that, the lower the power factor for lagging conditions, the lower the value of measured fault resistance, R, fault reactance, X and fault impedance, Z.

R-G fault at 38.5 km

Lagging pf

Page 11: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Simulation Results & Discussions

It can be concluded that, when power factor becoming lower in lagging conditions, the impedance measured will be lower thus the impedance will be over-reached when the actual fault impedance is just outside the reach boundary.

This condition will change the relay decision from sending the tripping signal at a delayed time (zone 2) to sending the tripping signal at instantaneous time (zone 1) which is not desired.

zoomed

Measured fault impedance locus for all three cases when fault occurred at 38.5 km from

local substation

Over-reached

Lagging pf

Page 12: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Simulation Results & Discussions

The load was changed from purely consuming active power (case 1) to consuming both active and capacitive reactive powers (case 2 and 3).

The effect of changing the load type was power factor was changed from unity power factor to 0.9 and 0.8 leading power factors.

It can be seen that, the lower the power factor for leading conditions, the higher the value of measured fault resistance, R, fault reactance, X and fault impedance, Z.

R-G fault at 38 km

Leading pf

Page 13: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Simulation Results & Discussions

It can be concluded that, when power factor becoming lower in leading conditions, the impedance measured will be higher thus the impedance will be under-reached when the actual fault impedance is just inside the reach boundary.

This condition will change the relay decision from sending the tripping signal at instantaneous time (zone 1) to sending the tripping signal at a delayed time (zone 2) which is not desired.

zoomed

Measured fault impedance locus for all three cases when fault occurred at 38 km from local

substation

Under-reached

Leading pf

Page 14: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Conclusions It can be concluded that for lower power factor in lagging

condition, it will make the distance relay to be over-reached when actual fault impedance is just outside the reach boundary of zone 1.

While for lower power factor in leading condition, it will make the distance relay to be under-reached when actual fault impedance is just inside the reach boundary of zone 1.

Both situations affect the performance of distance relay in making decision to send the tripping signal because the actual fault impedance at the line will be seen differently by the relay as shown by the measured fault impedance.

Thus, it can be said that the distance relay will be mal-operated for faults near zone 1 reach setting when power factor less than unity for either lagging or leading conditions.

Page 15: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

References[1] “Modern Distance Protection Functions and Applications”, Working Group B5.15, CIGRE Publication, October

2008. [2] Chris Werstiuk , “The Relay Testing Handbook, End-to-End Testing”, 7th Edition, Valence Electrical Training

Services LLC, 2010. [3] Muhd Hafizi Idris, Surya Hardi, Mohd Zamri Hasan, “Teaching Distance Relay Using Matlab/Simulink Graphical

User Interface”, Procedia Engineering, Volume 53, Pages 264–270, 2013. [4] T. S. Sidhu, D. S. Ghotra, and M. S. Sachdev, "A Fast Distance Relay Using Adaptive Data Window Filters",

IEEE/PES Summer Meeting, July 2000, pp. 1407-1412. [5] Takuya Utsumi, Tomomichi Nakatsuka, Hideyuki Takani, Hidenari Amoh, “Faulted Phase Selection Function based

upon Impedance Comparison in a Distance Protection Relay”, International Conference on Advanced Power System Automation and Protection, 2011.

[6] “Network Protection & Automation Guide: Protective Relays, Measurement & Control”, Alstom Grid, 2011. [7] C. Russell Mason, “The Art & Science of Protective Relaying”, General Electric. [8] Fernando Calero, “Mutual Impedance in Parallel Lines – Protective Relaying and Fault Location Considerations”,

34th Annual Western Protective Relay Conference, October 2007. [9] Joe Mooney, “Distance Element Performance Under Conditions of CT Saturation”, Texas A&M Conference for

Protective Relay Engineers, 2008. [10] M. E. Erezzaghi and P. A. Crossley, “The Effect Of High Resistance Faults On A Distance Relay”, IEEE Xplore,

2003. [11] Yiyan Xue, Dale Finney and Bin Le, “Charging Current in Long Lines and High-Voltage Cables – Protection

Application Considerations”, 67th Annual Georgia Tech Protective Relaying Conference, Atlanta, Georgia, 2013. [12] Walter A. Elmore, “Protective Relaying: Theory and Applications”, CRC Press, 2003. [13] A. Elmitwally, “Effect of FACT Devices on Distance Relay”, The Online Journal on Power and Energy Engineering

(OJPEE), Vol. 2, No. 2.

Page 16: Analysis on the performance of distance relay during fault impedance near zone 1 reach for different load power factor

Thank You