Analysis and Design of Two Way Slab With Beams

63
1 Prof. Dr. Qaisar Ali Reinforced Concrete Design – II Department of Civil Engineering, University of Engineering and Technology Peshawar Lecture-04 Analysis and Design of Two-way Slab System (Part-I: Two Way Slabs Supported on Stiff Beams Or Walls) By: Prof Dr. Qaisar Ali Civil Engineering Department UET Peshawar www.drqaisarali.com 1 Prof. Dr. Qaisar Ali Reinforced Concrete Design – II Department of Civil Engineering, University of Engineering and Technology Peshawar Topics Behavior Moment Coefficient Method Steps in Moment Coefficient Method Design Example 1 (Typical House with 2 Rooms and Verandah) Design Example 2 (100′ × 60′, 3-Storey Commercial Building) Practice Examples References 2

description

design of two way slab

Transcript of Analysis and Design of Two Way Slab With Beams

Page 1: Analysis and Design of Two Way Slab With Beams

1

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Lecture-04

Analysis and Design of Two-way Slab System

(Part-I: Two Way Slabs Supported on Stiff Beams Or Walls)

By: Prof Dr. Qaisar Ali

Civil Engineering Department

UET Peshawar

www.drqaisarali.com

1

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Topics

Behavior

Moment Coefficient Method

Steps in Moment Coefficient Method

Design Example 1 (Typical House with 2 Rooms and Verandah)

Design Example 2 (100′ × 60′, 3-Storey Commercial Building)

Practice Examples

References

2

Page 2: Analysis and Design of Two Way Slab With Beams

2

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab System (Long span/short span < 2)

3

25′ 25′ 25′ 25′

20′

20′

20′

Behavior

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

4

One-Way Behavior Two-Way Behavior

Behavior

Two-Way Bending of Two-Way Slabs

Page 3: Analysis and Design of Two Way Slab With Beams

3

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

5

Behavior

Two-Way Bending of Two-Way Slabs

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

6

Short Direction

Behavior

Short Direction Moments in Two-Way Slab

Page 4: Analysis and Design of Two Way Slab With Beams

4

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

7

Long Direction

Behavior

Long Direction Moments in Two-Way Slab

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

More Demand (Moment) in short direction due to size

of slab

Δcentral Strip = (5/384)wl4/EI

As these imaginary strips are part of monolithic slab, the deflection at

any point, of the two orthogonal slab strips must be same:

Δa = Δb

(5/384)wala4/EI = (5/384)wblb

4/EI

wa/wb = lb4/la

4 wa = wb (lb4/la

4)

Thus, larger share of load (Demand) is taken by the shorter direction.

8

Behavior

Page 5: Analysis and Design of Two Way Slab With Beams

5

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

The Moment Coefficient Method included for the first time in

1963 ACI Code is applicable to two-way slabs supported on

four sides of each slab panel by walls, steel beams relatively

deep, stiff, edge beams (h = 3hf).

Although, not included in 1977 and later versions of ACI code,

its continued use is permissible under the ACI 318-11 code

provision (13.5.1). Visit ACI 13.5.1.

9

Moment Coefficient Method

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moments:

Ma, neg = Ca, negwula2

Mb, neg = Cb, negwulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

2

Where Ca, Cb = Tabulated moment coefficients

wu = Ultimate uniform load, psf

la, lb = length of clear spans in short and long directions respectively.

10

Ma,neglb

la

Ma,neg

Ma,posMb,neg Mb,negMb,pos

Moment Coefficient Method

Page 6: Analysis and Design of Two Way Slab With Beams

6

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Cases

Depending on the support conditions, several cases are possible:

11

Moment Coefficient Method

4 spans @ 25′-0″

3 sp

ans @ 20

′-0″

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

12

Moment Coefficient Method

Cases

Depending on the support conditions, several cases are possible:

4 spans @ 25′-0″

3 spans @ 20

′-0″

Page 7: Analysis and Design of Two Way Slab With Beams

7

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

13

Moment Coefficient Method

Cases

Depending on the support conditions, several cases are possible:

4 spans @ 25′-0″

3 sp

ans @ 20

′-0″

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

14

Moment Coefficient Method

Cases

Depending on the support conditions, several cases are possible:

4 spans @ 25′-0″

3 spans @ 20

′-0″

Page 8: Analysis and Design of Two Way Slab With Beams

8

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

15

Moment Coefficient Method

Note: Horizontal sides of the figure represents longer side while vertical side

represents shorter side.

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

16

Moment Coefficient Method

Note: Horizontal sides of the figure represents longer side while vertical side

represents shorter side.

Page 9: Analysis and Design of Two Way Slab With Beams

9

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

17

Moment Coefficient Method

Note: Horizontal sides of the figure represents longer side while vertical side

represents shorter side.

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

18

Moment Coefficient Method

Note: Horizontal sides of the figure represents longer side while vertical side

represents shorter side.

Page 10: Analysis and Design of Two Way Slab With Beams

10

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

19

Moment Coefficient Method

Note: Horizontal sides of the figure represents longer side while vertical side

represents shorter side.

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

20

Moment Coefficient Method

Note: Horizontal sides of the figure represents longer side while vertical side

represents shorter side.

Page 11: Analysis and Design of Two Way Slab With Beams

11

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

21

Moment Coefficient Method

Note: Horizontal sides of the figure represents longer side while vertical side

represents shorter side.

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

hmin = perimeter/ 180 = 2(la + lb)/180

Calculate loads on slab

Calculate m = la/ lb

Decide about case of slab

Use table to pick moment coefficients

Calculate Moments and then design

Apply reinforcement requirements (smax = 2hf, ACI 13.3.2)

22

Steps in Moment Coefficient Method

Page 12: Analysis and Design of Two Way Slab With Beams

12

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

3D Model of the House

In this building we will design a two-way slab (for rooms), a one-way

slab, beam and column (for verandah)

23

Design Example 1(Typical House with 2 Rooms and Verandah)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Given Data:

Service Dead Load

4″ thick mud

2″ thick brick tile

Live Load = 40 psf

f′c = 3 ksi

fy = 40 ksi

24

Design Example 1(Typical House with 2 Rooms and Verandah)

Page 13: Analysis and Design of Two Way Slab With Beams

13

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Sizes

For two way slab system

hmin = perimeter / 180 = 2(la + lb)/180

hmin = 2 (12 +16) /180 = 0.311 ft = 3.73 inch

Assume 5 inch slab

For one way slab system

For 5″ slab, span length l is min. of:

l = ln+ hf = 8 + (5/12) = 8.42′

c/c distance between supports = 8.875′

Slab thickness (hf) = (8.42/20) × (0.4+��/100000)

= 4.04″ (min. by ACI)

Taking 5 in. slab

25

Design Example 1(Typical House with 2 Rooms and Verandah)

9′ Wide Verandah

ln = 8′

lc/c = (8 + (9/12) / 2 + 0.5) = 8.875′

9″ Brick Wall

Slab

h

A

A

Section AA

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Loads

5 inch Slab = 5/12 x 0.15 = 0.0625 ksf

4 inch mud = 4/12 x 0.12 = 0.04 ksf

2 inch tile = 2/12 x 0.12 = 0.02 ksf

Total DL = 0.1225 ksf

Factored DL = 1.2 x 0.1225 = 0.147 ksf

Factored LL = 1.6 x 0.04 = 0.064 ksf

Total Factored Load = 0.211 ksf

26

Design Example 1(Typical House with 2 Rooms and Verandah)

Page 14: Analysis and Design of Two Way Slab With Beams

14

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Analysis

This system consist of both one way and two way slabs. Rooms

(two way slabs) are continuous with verandah (one way slab).

A system where a two way slab is continuous with a one way slab

or vice versa is called a mixed slab system.

27

Design Example 1(Typical House with 2 Rooms and Verandah)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Analysis

The ACI approximate methods of analysis are not applicable to

such systems because:

In case of two way slabs, the moment coefficient tables are applicable

to two way slab system where a two way slab is continuous with a two

way slab.

In case of one ways slabs, the ACI approximate analysis is applicable

to one way slab system where a one way slab is continuous with a one

way slab.

28

Design Example 1(Typical House with 2 Rooms and Verandah)

Page 15: Analysis and Design of Two Way Slab With Beams

15

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Analysis

The best approach to analyze a mixed system is to use FE

software.

However, such a system can also be analyzed manually by making

certain approximations.

In the next slides, We will analyze this system using both of the

above mentioned methods.

29

Design Example 1(Typical House with 2 Rooms and Verandah)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Analysis using FE Software (SAFE)

30

Design Example 1(Typical House with 2 Rooms and Verandah)

Moments in Longer Direction in Two Way Slabs

Moments in Shorter Direction in Two Way Slabs & Moment in Verandah One Way Slab

Two Way Slab Moments (ft-kip/ft)(Rooms)

One Way Slab Moment (ft-kip/ft)(Verandah)

Ma,pos Mb,pos Ma,neg Mb,neg Mver (+ve)

1.58 1.17 2.10 1.67 1.10

Mb,pos Mb,posMb,neg Ma

,po

s

Ma

,po

s

Ma

,ne

g

Ma

,ne

g

Mv

er

(+v

e)

Mb,pos

Ma,p

os

Ma,n

eg

Mb,negMb,pos

Ma,n

eg

Ma,p

os

Mver

(+v

e)

Page 16: Analysis and Design of Two Way Slab With Beams

16

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Analysis using Manual Approach

For approximate manual analysis of two way slab of rooms, we

know that two way slabs of rooms are not only continuous along the

long direction but also continuous along the short direction with the

verandah slab. We assume that the verandah slab is a two way slab

instead of one way slab in order to calculate Mb,neg

Now, using Moment Coefficient Method for analysis.

31

Design Example 1(Typical House with 2 Rooms and Verandah)

Mb,pos

Ma,p

os

Ma,n

eg

Mb,negMb,pos

Ma,n

eg

Ma,p

os

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis

Case = 4

m = la/lb = 12/16 = 0.75

Ca,neg = 0.076

Cb,neg = 0.024

Ca,posDL = 0.043

Cb,posDL = 0.013

Ca,posLL = 0.052

Cb,posLL = 0.016

Design Example 1(Typical House with 2 Rooms and Verandah)

32

16′

12′

Mb,negMb,pos

Ma

,po

s

Case 4

Ma,n

eg

Page 17: Analysis and Design of Two Way Slab With Beams

17

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis

Case = 4

m = la/lb = 12/16 = 0.75

Ca,neg = 0.076

Cb,neg = 0.024

Ca,posDL = 0.043

Cb,posDL = 0.013

Ca,posLL = 0.052

Cb,posLL = 0.016

Design Example 1(Typical House with 2 Rooms and Verandah)

33

16′

12′

Mb,negMb,pos

Ma

,po

s

Case 4

Ma,n

eg

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Case = 4

m = la/lb = 12/16 = 0.75

Ca,neg = 0.076

Cb,neg = 0.024

Ca,posDL = 0.043

Cb,posDL = 0.013

Ca,posLL = 0.052

Cb,posLL = 0.016

Two-Way Slab Analysis

Design Example 1(Typical House with 2 Rooms and Verandah)

34

16′

12′

Mb,negMb,pos

Ma

,po

s

Case 4

Ma,n

eg

Page 18: Analysis and Design of Two Way Slab With Beams

18

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Case = 4

m = la/lb = 12/16 = 0.75

Ca,neg = 0.076

Cb,neg = 0.024

Ca,posDL = 0.043

Cb,posDL = 0.013

Ca,posLL = 0.052

Cb,posLL = 0.016

Two-Way Slab Analysis

Design Example 1(Typical House with 2 Rooms and Verandah)

35

16′

12′

Mb,negMb,pos

Ma

,po

s

Case 4

Ma,n

eg

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Case = 4

m = la/lb = 12/16 = 0.75

Ca,neg = 0.076

Cb,neg = 0.024

Ca,posDL = 0.043

Cb,posDL = 0.013

Ca,posLL = 0.052

Cb,posLL = 0.016

Two-Way Slab Analysis

Design Example 1(Typical House with 2 Rooms and Verandah)

36

16′

12′

Mb,negMb,pos

Ma

,po

s

Case 4

Ma,n

eg

Page 19: Analysis and Design of Two Way Slab With Beams

19

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Case = 4

m = la/lb = 12/16 = 0.75

Ca,neg = 0.076

Cb,neg = 0.024

Ca,posDL = 0.043

Cb,posDL = 0.013

Ca,posLL = 0.055

Cb,posLL = 0.016

Two-Way Slab Analysis

Design Example 1(Typical House with 2 Rooms and Verandah)

37

16′

12′

Mb,negMb,pos

Ma

,po

s

Case 4

Ma,n

eg

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

38

Design Example 1(Typical House with 2 Rooms and Verandah)

Two-Way Slab Analysis

Calculating moments using ACI Coefficients:

Ma, neg = Ca, negwula2

Mb, neg = Cb, negwulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

2

Using above relations the moments calculated are:

Ca,neg = 0.076 Cb,neg = 0.024

Ca,posLL = 0.052 Cb,posLL = 0.016

Ca,posDL = 0.043 Cb,posDL = 0.013

wu, dl = 0.147 ksf, wu, ll = 0.064 ksf, wu = 0.211 ksf

Ma,neg = 2.31 ft-kip

Mb,neg = 1.29 ft-kip

Ma,pos = 1.39 ft-kip

Mb,pos = 0.76 ft-kip

16′

12′

Mb,negMb,pos

Ma

,po

s

Case 4

Ma,n

eg

Page 20: Analysis and Design of Two Way Slab With Beams

20

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

One Way Slab Analysis

For calculation of Mver (+ve) along the short direction in the verandah

slab, we will pick the coefficients of continuous one way slabs having

two spans.

Now, using ACI Approximate analysis procedure (ACI 8.33) for analysis.

39

Design Example 1(Typical House with 2 Rooms and Verandah)

Mver(

+v

e)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

40

Design Example 1(Typical House with 2 Rooms and Verandah)

One-Way Slab Analysis

For two span one way slab system, positive moment at midspan is given as

follows:

Mver (+ve) = wuln2/11

Mver (+ve) = 0.211 × (8)2/11

= 1.23 ft-k/ft

9′ Wide Verandah

ln = 8′

9″ Brick Wall

Wu = 0.211 ksf

h

1/11 1/11

1/91/9Simply Supported

Simply Supported

Page 21: Analysis and Design of Two Way Slab With Beams

21

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

41

Design Example 1(Typical House with 2 Rooms and Verandah)

Design of Two-Way Slab

Comparison of Analysis Results from FE Analysis and Manual Analysis

Analysis results from both approaches are almost similar.

Hence the intelligent use of manual analysis yields fairly reasonable results in most cases.

Analysis Type

Ma,neg Mb,neg Ma,pos Mb,pos Mver (+ve)

SAFE 2.10 1.67 1.58 1.17 1.10

Manual 2.31 1.3 1.39 0.76 1.23

NOTE: All values are in ft-kip units

Mb,pos

Ma,p

os

Ma,n

eg

Mb,negMb,pos

Ma,n

eg

Ma,p

os

Mver

(+v

e)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

42

Design Example 1(Typical House with 2 Rooms and Verandah)

Design of Two-Way Slab

First determining capacity of min. reinforcement:

As,min = 0.002bhf = 0.12 in2

Using #3 bars: Spacing for As,min = 0.12 in2 = (0.11/0.12) × 12 = 11″ c/c

However ACI max spacing for two way slab = 2h = 2(5) = 10″ or 18″ = 10″ c/c

Hence using #3 bars @ 10″ c/c

For #3 bars @ 10″ c/c: As,min = (0.11/10) × 12 = 0.132 in2

Capacity for As,min: a = (0.132 × 40)/(0.85 × 3 × 12) = 0.17″

ΦMn = ΦAsminfy(d – a/2) = 0.9 × 0.132 × 40(4 – (0.17/2)) = 18.60 in-kip

Therefore, for Mu values ≤ 18.60 in-k/ft, use As,min (#3 @ 10″ c/c) & for Mu

values > 18.6 in-kip/ft, calculate steel area using trial & error procedure.

Page 22: Analysis and Design of Two Way Slab With Beams

22

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

43

Design Example 1(Typical House with 2 Rooms and Verandah)

Design of Two-Way Slab

For Ma,neg = 2.31 ft-kip = 27.71 in-kip > 18.60 in-kip: As = 0.20 in2 (#3 @ 6.6″ c/c)

Using #3 @ 6″ c/c

For Mb,neg = 1.29 ft-kip = 15.56 in-kip < 18.60 in-kip: Using #3 @ 10 c/c

For Ma,pos = 1.39 ft-kip = 16.67 in-kip < 18.60 in-kip: Using #3 @ 10 c/c

For Mb,pos = 0.76 ft-kip = 9.02 in-kip < 18.60 in-kip: Using #3 @ 10″ c/c

16′

12′

Mb,negMb,pos

Ma,p

os

Case 4

Ma,n

eg

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

44

Design Example 1(Typical House with 2 Rooms and Verandah)

Design of Two-Way Slab

Reinforcement at Discontinuous Ends

Reinforcement at discontinuous ends in a two way slab is 1/3 of the positive

reinforcement.

Positive reinforcement at midspan in this case is #3 @ 10 c/c. Therefore

reinforcement at discontinuous end may be provided @ 30 c/c.

However, in field practice, the spacing of reinforcement at discontinuous ends

seldom exceeds 18 c/c. The same is provided here as well.

Supporting Bars

Supporting bars are provided to support negative reinforcement.

They are provided perpendicular to negative reinforcement, generally at spacing

of 18 c/c.

Page 23: Analysis and Design of Two Way Slab With Beams

23

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

45

Design Example 1(Typical House with 2 Rooms and Verandah)

Design of One-Way Slab

Main Reinforcement:

Mver (+ve) = 14.73 in-kip

As,min = 0.002bhf = 0.002(12)(5) = 0.12 in2

Using #3 bars, spacing = (0.11/0.12) × 12 = 11″ c/c

For one-way slabs, max spacing by ACI = 3h = 3(5) = 15″ or 18″ = 15″ c/c

For #3 bars @ 15″ c/c, As = (0.11/15) × 12 = 0.09 in2. Hence using As,min = 0.12 in2

a = (0.12 × 40)/(0.85 × 3 × 12) = 0.16″

ΦMn = ΦAsminfy(d – a/2) = 0.9 × 0.12 × 40(4 – (0.16/2)) = 16.94 in-kip > Mver (+ve)

Therefore, using #3 @ 11″ c/c

However, for facilitating field work, we will use #3 @ 10″ c/c

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

46

Design Example 1(Typical House with 2 Rooms and Verandah)

Design of One-Way Slab

Shrinkage Reinforcement:

Ast = 0.002bhf = 0.12 in2 (#3 @ 11″ c/c)

However, for facilitating field work, we will use #3 @ 10″ c/c

Page 24: Analysis and Design of Two Way Slab With Beams

24

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

47

Verandah Beam Design

Step 01: Sizes

Let depth of beam = 18″

ln + depth of beam = 15.875′ + (18/12) = 17.375′

c/c distance between beam supports

= 16.375 + (4.5/12) = 16.75′

Therefore l = 16.75′

Depth (h) = (16.75/18.5) × (0.4 + 40000/100000) × 12

= 8.69″ (Minimum requirement of ACI 9.5.2.2).

Take h = 1.5′ = 18″

d = h – 3 = 15″

b = 12″

Design Example 1(Typical House with 2 Rooms and Verandah)

Verandah Beam

16.375 16.375

ln = 16.375 – 0.5(12/12) = 15.875 ln = 16.375 – 0.5(12/12) = 15.875

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

48

Verandah Beam Design

Step 02: Loads

Load on beam will be equal to

Factored load on beam from slab + factored

self weight of beam web

Factored load on slab = 0. 211 ksf

Load on beam from slab = 0. 211 ksf x 5 =

1.055 k/ft

Factored Self load of beam web =

= 1.2 x (13 × 12/144) × 0.15 = 0.195 k/ft

Total load on beam = 1.055 + 0.195

= 1.25 k/ft

5′

Design Example 1(Typical House with 2 Rooms and Verandah)

ln = 8′

9″ Brick Wall

8/2 = 4′

12″ Column

4′ + 1′ = 5′

Page 25: Analysis and Design of Two Way Slab With Beams

25

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

49

Verandah Beam

Design

Step 03: Analysis

Using ACI Moment

Coefficients for analysis

of verandah beam

Design Example 1(Typical House with 2 Rooms and Verandah)

16.375

ln = 16.375 – 0.5(12/12) = 15.875 ln = 16.375 – 0.5(12/12) = 15.87516.375

16.375

ln = 15.875 ln = 15.875

9.92 k

11.41 k

Vu(ext) = 8.34 k

Vu(int) = 9.61 k

343.66 in-kip 343.66 in-kip

420.03 in-kip

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Beam Design

Flexure Design:

Shear Design:

Smax is min. of: (1) Avfy/(50bw) = 14.67″ (2) d/2 =7.5″ (3) 24″ c/c (4) Avfy/ 0.75√(fc′)bw = 17.85″

50

Design Example 1(Typical House with 2 Rooms and Verandah)

Mu

(in-kip)d

(in.)b

(in.)As

(in2)Asmin

(in2)Asmax

(in2)As

(governing)Bar

used# of bars

343.66 (+) 15 28.75 (beff) 0.64 0.90 3.654 0.90 #4 5

#5 3

420.03 (-) 15 12 0.81 0.90 3.654 0.90 #4 5

#4 + #5 2 + 2

Location Vu (@ d)(kip)

ΦVc = Φ2 �′�bwd (kips) ΦVc > Vu, Hence

providing minimum reinforcement.

smax,

ACI

S taken(#3 2-legged)

Exterior 8.34 14.78 7.5″ 7.5″

Interior 9.61 14.78 7.5″ 7.5″

Page 26: Analysis and Design of Two Way Slab With Beams

26

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

51

Design Example 1(Typical House with 2 Rooms and Verandah)

Column Design

Sizes:

Column size = 12″ × 12″

Loads:

Pu = 11.41 × 2 = 22.82 kip

Verandah Column

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

52

Design Example 1(Typical House with 2 Rooms and Verandah)

Column Design

Main Reinforcement Design:

Nominal strength (ΦPn) of axially loaded column is:

ΦPn = 0.80Φ {0.85fc′ (Ag – Ast) + Astfy} {for tied column, ACI 10.3.6}

Let Ast = 1% of Ag (Ast is the main steel reinforcement area)

ΦPn = 0.80 × 0.65 × {0.85 × 3 × (144 – 0.01 × 144) + 0.01 × 144 × 40}

= 218.98 kip > Pu = 22.82 kip, O.K.

Ast =0.01 × 144 =1.44 in2

Using 3/4″ Φ (#6) with bar area Ab = 0.44 in2

No. of bars = 1.44/0.44 = 3.27 ≈ 4 bars

Use 4 #6 bars (or 8 #4 bars) and #3 ties @ 9″ c/c

Page 27: Analysis and Design of Two Way Slab With Beams

27

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

53

Design Example 1(Typical House with 2 Rooms and Verandah)

Drafting Details for

Slabs

Panel Depth (in) Mark Bottom Reinforcement Mark Top reinforcement

S1 5"M1 #3 @ 10" c/c

MT1 #3 @ 10" c/c Continuous EndMT1 #3 @ 18" c/c Non Continuous End

M2 #3 @ 10" c/cMT2 #3 @ 6" c/c Continuous EndMT2 #3 @ 18" c/c Non Continuous End

S2 5"M1 #3 @ 10" c/c MT2 #3 @ 6" c/c Continuous EndM2 #3 @ 10" c/c MT2 #3 @ 18" c/c Non Continuous End

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

54

Design Example 1(Typical House with 2 Rooms and Verandah)

Drafting Details for Slabs

Page 28: Analysis and Design of Two Way Slab With Beams

28

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

55

Design Example 1(Typical House with 2 Rooms and Verandah)

Drafting Details for Verandah Beam

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

56

Design Example 1(Typical House with 2 Rooms and Verandah)

Drafting Details for Verandah Column

OR

Page 29: Analysis and Design of Two Way Slab With Beams

29

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

A 100′ 60′, 3-storey commercial building is to be designed. The grids of

column plan are fixed by the architect.

In this example, the slab of one of the floors of this 3-storey building will

be designed.

57

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Given Data:

Material Properties:

f′c = 3 ksi, fy = 40 ksi

Sizes:

Slab thickness = 7″

Columns = 14″ 14″

Beams = 14″ 20″

Loads:

S.D.L = Nil

Self Weight = 0.15 x (7/12) = 0.0875 ksf

L.L = 144 psf = 0.144 ksf ; wu = 0.336 ksf

58

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Page 30: Analysis and Design of Two Way Slab With Beams

30

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Complete analysis of the slab is done by analyzing four panels

59

Panel I Panel I

Panel I Panel I

Panel II Panel II

Panel III Panel III

Panel III Panel III

Panel IV Panel IV

4 spans @ 25′-0″

3 sp

ans @

20′-0″

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-I)

Case = 4

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.071

Cb,neg = 0.029

Ca,posDL = 0.039

Cb,posDL = 0.016

Ca,posLL = 0.048

Cb,posLL = 0.020

Case 4la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,neg

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

60

Page 31: Analysis and Design of Two Way Slab With Beams

31

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-I)

Case = 4

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.071

Cb,neg = 0.029

Ca,posDL = 0.039

Cb,posDL = 0.016

Ca,posLL = 0.048

Cb,posLL = 0.020

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

61

Case 4la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,neg

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-I)

Case = 4

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.071

Cb,neg = 0.029

Ca,posDL = 0.039

Cb,posDL = 0.016

Ca,posLL = 0.048

Cb,posLL = 0.020

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

62

Case 4la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,neg

Page 32: Analysis and Design of Two Way Slab With Beams

32

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-I)

Case = 4

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.071

Cb,neg = 0.029

Ca,posDL = 0.039

Cb,posDL = 0.016

Ca,posLL = 0.048

Cb,posLL = 0.020

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

63

Case 4la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,neg

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-I)

Case = 4

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.071

Cb,neg = 0.029

Ca,posDL = 0.039

Cb,posDL = 0.016

Ca,posLL = 0.048

Cb,posLL = 0.020

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

64

Case 4la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,neg

Page 33: Analysis and Design of Two Way Slab With Beams

33

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-I)

Case = 4

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.071

Cb,neg = 0.029

Ca,posDL = 0.039

Cb,posDL = 0.016

Ca,posLL = 0.048

Cb,posLL = 0.020

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

65

Case 4la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,neg

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

66

Two-Way Slab Analysis (Panel-I)

Calculating moments using ACI Coefficients:

Ma, neg = Ca, negwula2

Mb, neg = Cb, negwulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

2

Using above relations the moments calculated are:

Ca,neg = 0.071 Cb,neg = 0.029

Ca,posLL = 0.048 Cb,posLL = 0.020

Ca,posDL = 0.039 Cb,posDL = 0.016

wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

Ma,neg = 8.44 ft-k (101.2 in-k)

Mb,neg = 5.52 ft-k (66.2 in-k)

Ma,pos = 5.37 ft-k (64.4 in-k)

Mb,pos = 3.57 ft-k (42.8 in-k)

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Case 4la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,neg

Page 34: Analysis and Design of Two Way Slab With Beams

34

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-II)

Case = 9

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.075

Cb,neg = 0.017

Ca,posDL = 0.029

Cb,posDL = 0.010

Ca,posLL = 0.042

Cb,posLL = 0.017

Case 9la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

67

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-II)

Case = 9

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.075

Cb,neg = 0.017

Ca,posDL = 0.029

Cb,posDL = 0.010

Ca,posLL = 0.042

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

68

Case 9la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 35: Analysis and Design of Two Way Slab With Beams

35

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-II)

Case = 9

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.075

Cb,neg = 0.017

Ca,posDL = 0.029

Cb,posDL = 0.010

Ca,posLL = 0.042

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

69

Case 9la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-II)

Case = 9

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.075

Cb,neg = 0.017

Ca,posDL = 0.029

Cb,posDL = 0.010

Ca,posLL = 0.042

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

70

Case 9la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 36: Analysis and Design of Two Way Slab With Beams

36

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-II)

Case = 9

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.075

Cb,neg = 0.017

Ca,posDL = 0.029

Cb,posDL = 0.010

Ca,posLL = 0.042

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

71

Case 9la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-II)

Case = 9

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.075

Cb,neg = 0.017

Ca,posDL = 0.029

Cb,posDL = 0.010

Ca,posLL = 0.042

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

72

Case 9la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 37: Analysis and Design of Two Way Slab With Beams

37

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

73

Two-Way Slab Analysis (Panel-II)

Calculating moments using ACI Coefficients:

Ma, neg = Ca, negwula2

Mb, neg = Cb, negwulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

2

Using above relations the moments calculated are:

Ca,neg = 0.075 Cb,neg = 0.017

Ca,posLL = 0.042 Cb,posLL = 0.017

Ca,posDL = 0.029 Cb,posDL = 0.010

wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

Ma,neg = 8.91 ft-k (106.9 in-k)

Mb,neg = 3.24 ft-k (38.8 in-k)

Ma,pos = 4.51 ft-k (54.1 in-k)

Mb,pos = 2.82 ft-k (33.8 in-k)

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Case 9la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-III)

Case = 8

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.055

Cb,neg = 0.041

Ca,posDL = 0.032

Cb,posDL = 0.015

Ca,posLL = 0.044

Cb,posLL = 0.019

Case 8la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

74

Page 38: Analysis and Design of Two Way Slab With Beams

38

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-III)

Case = 8

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.055

Cb,neg = 0.041

Ca,posDL = 0.032

Cb,posDL = 0.015

Ca,posLL = 0.044

Cb,posLL = 0.019

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

75

Case 8la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-III)

Case = 8

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.055

Cb,neg = 0.041

Ca,posDL = 0.032

Cb,posDL = 0.015

Ca,posLL = 0.044

Cb,posLL = 0.019

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

76

Case 8la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 39: Analysis and Design of Two Way Slab With Beams

39

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-III)

Case = 8

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.055

Cb,neg = 0.041

Ca,posDL = 0.032

Cb,posDL = 0.015

Ca,posLL = 0.044

Cb,posLL = 0.019

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

77

Case 8la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-III)

Case = 8

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.055

Cb,neg = 0.041

Ca,posDL = 0.032

Cb,posDL = 0.015

Ca,posLL = 0.044

Cb,posLL = 0.019

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

78

Case 8la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 40: Analysis and Design of Two Way Slab With Beams

40

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-III)

Case = 8

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.055

Cb,neg = 0.041

Ca,posDL = 0.032

Cb,posDL = 0.015

Ca,posLL = 0.044

Cb,posLL = 0.019

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

79

Case 8la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

80

Two-Way Slab Analysis (Panel-III)

Calculating moments using ACI Coefficients:

Ma, neg = Ca, negwula2

Mb, neg = Cb, negwulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

2

Using above relations the moments calculated are:

Ca,neg = 0.055 Cb,neg = 0.041

Ca,posLL = 0.044 Cb,posLL = 0.019

Ca,posDL = 0.032 Cb,posDL = 0.015

wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

Ma,neg = 6.54 ft-k (78.4 in-k)

Mb,neg = 7.80 ft-k (93.6 in-k)

Ma,pos = 4.78 ft-k (57.4 in-k)

Mb,pos = 3.38 ft-k (40.5 in-k)

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Case 8la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 41: Analysis and Design of Two Way Slab With Beams

41

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-IV)

Case = 2

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.065

Cb,neg = 0.027

Ca,posDL = 0.026

Cb,posDL = 0.011

Ca,posLL = 0.041

Cb,posLL = 0.017

Case 2la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

81

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-IV)

Case = 2

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.065

Cb,neg = 0.027

Ca,posDL = 0.026

Cb,posDL = 0.011

Ca,posLL = 0.041

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

82

Case 2la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 42: Analysis and Design of Two Way Slab With Beams

42

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-IV)

Case = 2

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.065

Cb,neg = 0.027

Ca,posDL = 0.026

Cb,posDL = 0.011

Ca,posLL = 0.041

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

83

Case 2la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-IV)

Case = 2

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.065

Cb,neg = 0.027

Ca,posDL = 0.026

Cb,posDL = 0.011

Ca,posLL = 0.041

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

84

Case 2la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 43: Analysis and Design of Two Way Slab With Beams

43

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-IV)

Case = 2

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.065

Cb,neg = 0.027

Ca,posDL = 0.026

Cb,posDL = 0.011

Ca,posLL = 0.041

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

85

Case 2la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Two-Way Slab Analysis (Panel-IV)

Case = 2

m = la/lb = 18.83/23.83 = 0.78 ≈ 0.80

Ca,neg = 0.065

Cb,neg = 0.027

Ca,posDL = 0.026

Cb,posDL = 0.011

Ca,posLL = 0.041

Cb,posLL = 0.017

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

86

Case 2la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Page 44: Analysis and Design of Two Way Slab With Beams

44

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

87

Two-Way Slab Analysis (Panel-IV)

Calculating moments using ACI Coefficients:

Ma, neg = Ca, negwula2

Mb, neg = Cb, negwulb2

Ma, pos, (dl + ll) = M a, pos, dl + M a, pos, ll = Ca, pos, dl × wu, dl × la2 + Ca, pos, ll × wu, ll × la

2

Mb, pos, (dl + ll) = Mb, pos, dl + Mb, pos, ll = Cb, pos, dl × wu, dl × lb2 + Cb, pos, ll × wu, ll × lb

2

Using above relations the moments calculated are:

Ca,neg = 0.065 Cb,neg = 0.027

Ca,posLL = 0.041 Cb,posLL = 0.017

Ca,posDL = 0.026 Cb,posDL = 0.011

wu, dl = 0.105 ksf, wu, ll = 0.2304 ksf, wu = 0.336 ksf

Ma,neg = 7.72 ft-k (92.7 in-k)

Mb,neg = 5.14 ft-k (61.6 in-k)

Ma,pos = 4.31 ft-k (51.8 in-k)

Mb,pos = 2.88 ft-k (34.5 in-k)

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Case 2la = 18.83′

lb = 23.83′

Ma

,ne

gM

a,p

os

Mb,posMb,negMb,neg

Ma

,ne

g

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

88

Analysis Results (All values are in ft-kip)

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

8.42

4 spans @ 25′-0″

3 spans @ 2

0′-0″

5.375.523.57

8.91

8.91

3.244.51

2.82

6.54

7.80 7.804.783.38

7.72

7.72

5.145.144.31

2.881.50

1.79

1.19 1.19 Mneg at Non-

Continuous End =

1/3 of Mpos

NOTE: White: Longer Direction Moments, Yellow: Shorter Direction Moments

Page 45: Analysis and Design of Two Way Slab With Beams

45

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

89

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Slab Design

First determining the capacity of min. reinforcement:

As,min = 0.002bhf = 0.002 × 12 × 7 = 0.17 in2

For #4 bars, spacing = (0.20/0.17) × 12 = 14.2 c/c.

ACI max spacing for two-ways slabs = 2h = 2(7) = 14 or 18

Using #4 @ 12 c/c

For the 12 spacing: As = (0.20/12) × 12 = 0.20 in2. Hence As,min = 0.20 in2

Capacity for As,min: a = (0.20 × 40)/(0.85 × 3 × 12) = 0.26

ΦMn = ΦAsminfy(d – a/2) = {0.9 × 0.20 × 40(6 – (0.26/2))}/12 = 3.52 ft-kip

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

90

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Slab Design

Positive Moments in Long Direction:

3.57 ft-kip/ft

3.38 ft-kip/ft

2.82 ft-kip/ft

2.88 ft-kip/ft

Since all the above moments values are almost equal to or less than

3.52 ft-kip/ft. Therefore using #4 @ 12 c/c for all positive moments in

short direction.

Page 46: Analysis and Design of Two Way Slab With Beams

46

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

91

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Slab Design

Positive Moments in Short Direction:

5.37 ft-kip/ft

4.51 ft-kip/ft

4.78 ft-kip/ft

4.31 ft-kip/ft

Using trial and success method for determining As for 5.37 ft-kip/ft:

Assume a = 0.2d= 0.2(6) = 1.2, As = (5.37 × 12)/{0.9 × 40(6 – (1.2/2))} = 0.33 in2

Now, a = (0.33 × 40)/(0.85 × 3 × 12) = 0.43, As = 0.31 in2

For #4 bars, spacing = (0.20/0.31) × 12 = 7.7

As all the above moments are almost same, we will use #4 @ 7 c/c for all above

moments.

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

92

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Slab Design

Negative Moments at Non-Continuous Ends in Short & Long Directions:

1.19 ft-kip/ft

1.79 ft-kip/ft

1.50 ft-kip/ft

Since, all the above moments are

less than 3.52 ft-kip/ft, therefore using

#4 @ 12 c/c

Page 47: Analysis and Design of Two Way Slab With Beams

47

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

93

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Slab Design

Negative Moments at Continuous Ends in Short Direction:

8.42 ft-kip/ft

8.91 ft-kip/ft

7.72 ft-kip/ft

6.54 ft-kip/ft

Using trial and success method:

For 8.91 ft-kip/ft: As = 0.52 in2

Using #4 bars, spacing = 4.5 c/c

As all above moments are almost same, we will use #4 @ 4.5 c/c

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

94

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Slab Design

Negative Moments at Continuous Ends in Long Direction:

5.52 ft-kip/ft

3.24 ft-kip/ft

7.80 ft-kip/ft

5.14 ft-kip/ft

Reinforcement:

7. 80 ft-kip/ft is almost equal to 8.91 ft-kip/ft:

Therefore using #4 bars @ 4.5 c/c

7. 80 ft-kip/ft is almost equal to 8.91 ft-kip/ft:

Therefore using #4 bars @ 7 c/c

Page 48: Analysis and Design of Two Way Slab With Beams

48

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Slab Reinforcement Details

95

A

BBB

C

C

A

C CB

A

A

BA

C

C

A

A B

A

A= #4 @ 12″B = #4 @ 7″C = #4 @ 4.5″

4 spans @ 25′-0″

3 sp

ans @

20

′-0″

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

NOTE: White: Longer Direction Moments, Yellow: Shorter Direction Moments

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

96

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Load Transfer from Slab to the Beam

Review of Load transfer to Beam from One-Way Slabs

• In case of one-way slab system the entire slab load is transferred in short direction.

• Load transfer in short direction = (Wu × l / 2 × 1) + (Wu × l / 2 × 1)

• Load transfer in long direction = Wu × l / 2 × 0

l/2

l/2

l/2 l/2

Page 49: Analysis and Design of Two Way Slab With Beams

49

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

97

Load transfer from Slab to Beam

Load Transfer to Beam from Two-Way Slab

• In case of two way slab system, entire slab load is NOT transferred in shorter direction.

• Load transfer in shorter direction = (Wu × l / 2 × Wa ) + (Wu × l / 2 × Wa )

Longer Direction

4 spans @ 25′-0″

3 s

pa

ns @

20′-0

Sh

orte

r Dire

ctio

n

Panel I Panel I

Panel I Panel I

Panel II Panel II

Panel III Panel III

Panel III Panel III

Panel IV Panel IV

This value will NOT be 1 in this case, It is specified by ACI Table• Load transfer in longer direction = (Wu × l / 2 × Wb ) + (Wu × l / 2 × Wb )

Wb = 1 - Wa

ACI Table for Wa values

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

98

Load transfer from Slab to Beam

Load Transfer to Beam from Two-Way Slab

4 spans @ 25′-0″

3 sp

an

s @ 2

0′-0

Panel I Panel I

Panel I Panel I

Panel II Panel II

Panel III Panel III

Panel III Panel III

Panel IV Panel IV

Load Transfer from Slab to Beam B1

• Load is transferred to B1 from Panel-I and Panel-II in

short direction

= Wu × l / 2 × Wa,Panel-I + Wu × l / 2 × Wa,Panel-II

= 0.336 × 20/2 × 0.71 + 0.336 × 20/2 × 0.83

= 5.17 k/ft

(For Wa Values, refer to the tables on next slides)• Wu = 0.336 ksf

• Wa,Panel-I = 0.71

• Wa,Panel-II = 0.83

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Page 50: Analysis and Design of Two Way Slab With Beams

50

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

99

Load transfer from Slab to Beam

Load Transfer to Beam from Two-Way Slab (For Beam B1)

Sh

orte

r Dire

ction

20′

Wu = 0.336 ksf

Sh

orte

r Dire

ctio

n

20′

Wu = 0.336 ksf

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

100

Load transfer from Slab to Beam

Load Transfer to Beam from Two-Way Slab

4 spans @ 25′-0″

3 sp

an

s @ 2

0′-0

Panel I Panel I

Panel I Panel I

Panel II Panel II

Panel III Panel III

Panel III Panel III

Panel IV Panel IV

Load Transfer from Slab to Beam B2

• Load is transferred to B2 from Panel-I and Panel-III in

long direction

= Wu × l / 2 × Wb,Panel-I + Wu × l / 2 × Wb,Panel-III

= 0.336 × 25/2 × (1 - 0.71) + 0.336 × 25/2 × (1 - 0.55)

= 3.11 k/ft

(For Wa values, refer to the tables on next slide)• Wu = 0.336 ksf

• Wb,Panel-I = (1 – Wa,Panel-I) = 1 - 0.71 = 0.29

• Wb,Panel-III = (1 – Wa,Panel-III) = 1 - 0.55 = 0.45

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Page 51: Analysis and Design of Two Way Slab With Beams

51

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

101

Load transfer from Slab to Beam (For Beam B2)

Load Transfer to Beam from Two-Way Slab

= 0.336 × 25/2 × (1 - 0.71) + 0.336 × 25/2 ×

(1 - 0.55)

= 3.11 k/ft

Sh

orte

r Dire

ction

20′

Wu = 0.336 ksf

Sh

orte

r Dire

ctio

n

20′

Wu = 0.336 ksf

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

102

Table: Load on beam in Panel I, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.71 - 2.39

B2 25 10 0.71 - 2.39

B3 20 12.5 - 0.29 1.22

B4 20 12.5 - 0.29 1.22

Panel I

4 spans @ 25′-0″

3 spans @ 20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Page 52: Analysis and Design of Two Way Slab With Beams

52

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Table: Load on beam in Panel I, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.71 - 2.39

B2 25 10 0.71 - 2.39

B3 20 12.5 - 0.29 1.22

B4 20 12.5 - 0.29 1.22

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

B1

B1

B2

B2

B3 B3 B3 B4B4

4 spans @ 25′-0″

3 sp

ans @

20

′-0″

Panel I

103

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Panel I

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

104

4 spans @ 25′-0″

3 spans @ 20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Table: Load on beam in Panel II, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.83 - 2.78

B3 20 12.5 - 0.17 0.714

B4 20 12.5 - 0.17 0.714

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Panel II

Page 53: Analysis and Design of Two Way Slab With Beams

53

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Table: Load on beam in Panel II, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.83 - 2.78

B3 20 12.5 - 0.17 0.714

B4 20 12.5 - 0.17 0.714

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

B1

B1

B2

B2

B3 B3 B3 B4B4

Panel II

4 spans @ 25′-0″

3 sp

ans @

20

′-0″

105

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Panel II

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

106

4 spans @ 25′-0″

3 spans @ 20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Table: Load on beam in Panel III, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.55 - 1.84

B2 25 10 0.55 - 1.84

B3 20 12.5 - 0.45 1.89

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Panel III

Page 54: Analysis and Design of Two Way Slab With Beams

54

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Table: Load on beam in Panel III, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.55 - 1.84

B2 25 10 0.55 - 1.84

B3 20 12.5 - 0.45 1.89

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

B1

B1

B2

B2

B3 B3 B3 B4B4

Panel III

4 spans @ 25′-0″

3 sp

ans @

20

′-0″

107

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Panel III

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

108

4 spans @ 25′-0″

3 spans @ 20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Table: Load on beam in Panel IV, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.71 - 2.39

B3 20 12.5 - 0.29 1.22

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Panel IV

Page 55: Analysis and Design of Two Way Slab With Beams

55

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Table: Load on beam in Panel IV, usingCoefficients

(wu = 0.336 ksf)

BeamLength

(ft)

Width (bs) of slab panel

supported by beam

Wa Wb

Load due to slab, Wwubs

(k/ft)

B1 25 10 0.71 - 2.39

B3 20 12.5 - 0.29 1.22

Moment Coefficient Method: Example 2

Load On Beams from coefficient tables

B1

B1

B2

B2

B3 B3 B3 B4B4

Panel IV

4 spans @ 25′-0″

3 sp

ans @

20

′-0″

109

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Panel IV

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams

110

2.39 k/ft

1.22 k/ft

2.39 k/ft

1.22 k/ft

2.77 k/ft

2.77 k/ft

0.71 k/ft 0.71 k/ft

1.84 k/ft

1.89 k/ft

1.84 k/ft

1.89 k/ft

2.39 k/ft

1.22 k/ft

2.39 k/ft

1.22 k/ft

4 spans @ 25′-0″

3 spans @ 20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Page 56: Analysis and Design of Two Way Slab With Beams

56

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams

111

5.16 k/ft

1.22 k/ft

2.39 k/ft

3.11 k/ft

5.16 k/ft

0.71 k/ft 1.93 k/ft

4.23 k/ft

1.84 k/ft

3.11 k/ft

4.23 k/ft

1.93 k/ft

4 spans @ 25′-0″

3 sp

ans @

20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams

112

Self weight of beam

= 1.2 × (14 ×

13/144) × 0.15

= 0.23 kip/ft

Adding this with the

calculated loads on

beams:

14

20

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

5.16 k/ft

1.22 k/ft

2.39 k/ft

3.11 k/ft

5.16 k/ft

0.71 k/ft 1.93 k/ft

4.23 k/ft

1.84 k/ft

3.11 k/ft

4.23 k/ft

1.93 k/ft

4 spans @ 25′-0″

3 spans @ 20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Page 57: Analysis and Design of Two Way Slab With Beams

57

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Example 2

Load On Beams (including self-weight)

113

1.45 k/ft

2.62 k/ft

5.39 k/ft

0.94 k/ft

3.34 k/ft

2.07 k/ft

2.16 k/ft

4.46 k/ft

4 spans @ 25′-0″

3 sp

ans @

20

′-0″

B1

B1

B2

B2

B3 B3 B3 B4B4

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

114

lnln ln

Simplesupport

Integral withsupport

wu

Spandrelsupport

NegativeMoment

x wuln2

1/24 1/10* 1/11 1/11 1/10* 0

*1/9 (2 spans)

* 1/11(on both faces of other interior supports)

Columnsupport

1/16

PositiveMomentx

1/14 1/16 1/11

wuln2

Note: For simply supported slab, M = wul2/8, where l = span length (ACI 8.9).

* 1/12 (for all spans with ln < 10 ft)

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Page 58: Analysis and Design of Two Way Slab With Beams

58

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

115

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Analysis of Beams

Interior Beam B1

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

116

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Analysis of Beams

Exterior Beam B2

Page 59: Analysis and Design of Two Way Slab With Beams

59

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

117

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Analysis of Beams

Interior Beam B3

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Analysis of Beams

Exterior Beam B4

118

Design Example 2(100′ × 60′, 3-Storey Commercial Building)

Page 60: Analysis and Design of Two Way Slab With Beams

60

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

119

Pictures of a Multi-StoreyCommercial Building

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

120

Pictures of a Multi-StoreyCommercial Building

Page 61: Analysis and Design of Two Way Slab With Beams

61

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Different Stages of Building Construction

121

Phases of Construction

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Home Work

Design the given slab system

122

Panel I Panel I

Panel I Panel I

Panel II Panel II

Panel III Panel III

Panel III Panel III

Panel IV Panel IV

4 spans @ 25′-0″

3 spans @ 20

′-0″

Slab thickness = 6″

SDL = 40 psf

LL = 60 psf

fc′ =3 ksi

fy = 40 ksi

Practice Examples

Page 62: Analysis and Design of Two Way Slab With Beams

62

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

Moment Coefficient Method: Home Work

Design the given slab system

123

Panel I Panel I

Panel I Panel I

Panel II Panel II

Panel III Panel III

Panel III Panel III

Panel IV Panel IV

4 spans @ 20′-0″

3 sp

ans @

15′-0″

Slab thickness = 6″

SDL = 40 psf

LL = 60 psf

fc′ =3 ksi

fy = 40 ksi

Practice Examples

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

CRSI Design Handbook

ACI 318

Design of Concrete Structures 13th Ed. by Nilson, Darwin and

Dolan.

124

References

Page 63: Analysis and Design of Two Way Slab With Beams

63

Prof. Dr. Qaisar Ali Reinforced Concrete Design – II

Department of Civil Engineering, University of Engineering and Technology Peshawar

The End

125