Ammonia Refrigerant Hazards
-
Upload
randall-bleijie -
Category
Documents
-
view
212 -
download
0
Transcript of Ammonia Refrigerant Hazards
-
7/31/2019 Ammonia Refrigerant Hazards
1/7
A single copy of this document is licensed to
On
This is an uncontrolled copy. Ensure use of themost current version of the document by searching
the Construction Information Service.
uninorth
30/06/2012
-
7/31/2019 Ammonia Refrigerant Hazards
2/7
Introduction
The phasing out of CFCs and HCFCs(chlorofluorocarbons andhydrochlorofluorocarbons), and uncertaintyabout the environmental acceptability of thenewer HFC (hydrofluorocarbon) refrigerants,has led to growing use of ammonia in airconditioning systems in buildings. Ammoniahas excellent refrigeration properties and a lowenvironmental impact. The high efficiency ofammonia-based refrigeration systems couldreduce the energy consumption and CO2
emissions of building cooling systems.However, ammonia is highly toxic and mildlyflammable which means that more demandingsafety measures are required than with themuch safer HFC refrigerants and older CFCsand HCFCs.
Until recently ammonia refrigerationsystems were mainly used for industrialapplications, especially in the food processingand brewing industries where the advantagesof higher efficiency offset the higher cost ofsafety and maintenance.
The environmental benefits of the use of
ammonia must be weighed against the highersafety risks. The Health and Safety Executive(HSE) is concerned[1]that deficiencies in theunderlying management of industrial ammoniasystems cause unnecessary incidents leading toinjury, deaths and sometimes widespreadevacuation of the vicinity. HSE is alsoconcerned that wider use of ammonia couldincrease the incidence of such occurrences.
Designers and consultants currently believethat a safe location for ammonia refrigerationsystems is in the open air on a building roof,
based on the premise that because ammonia
vapour is less dense than air it should dischargesafely skywards. This paper shows that this isan incorrect assumption which can lead tounsafe installations, and it gives preliminaryguidance on how to overcome this problem.
The hazards of ammonia:toxicity and flammability
Toxicity
Ammonia is highly toxic. However, itscharacteristic pungent odour makes it readily
detectable by smell at a concentration of
CI/SfB (57)(L7)
Ammonia refrigerantin buildings:
minimising the
hazardsD J G Butler* and D J Hall
*BRE Centre for Environmental EngineeringEnvirobods Ltd
IP 18/00
Ammonia is being
increasingly used as
refrigerant for building air
conditioning systems on
account of its lowenvironmental impact and
excellent refrigeration
properties. However,
ammonia is highly toxic
which means that greater
care is needed in its use.
This paper shows that the
design of safe ammonia
systems must also take
into account dispersal
mechanisms.
constructing the future
inform
ation
paper
-
7/31/2019 Ammonia Refrigerant Hazards
3/7
around 5 parts per million (ppm), well belowthe level for toxic effects, giving early warningof its presence and making inadvertent and
voluntary exposure to high concentrationsunlikely. Industrial experience is that exposure
to concentrations between 400 and 700 ppmcauses immediate eye and throat irritation, and
a level of 1700 ppm causes tissue damage andrepeated coughing which can prove fatal after30 minutes exposure. A significant fraction of
the general populace is far more sensitive thanthe working populace, and would show muchmore severe reactions to these levels ofexposure.
The HSEs occupational exposure standards(OESs) have been set to protect workers from
both long-term and short-term effects. The8-hour time-weighted average is 25 ppm and
the short-term limit measured over a10-minute reference period is 35 ppm. Thiscompares with an 8-hour time-weightedaverage of 1000 ppm for the majority of HCFCand HFC refrigerants.
Although HCFCs and HFCs have lowtoxicities they can also be dangerous. Becausethey are practically odourless and are heavierthan air, they can accumulate undetected inconfined spaces. High concentrations can resultin a risk of asphyxiation and other toxic effectsincluding narcosis and cardiac sensitivity.
Flammability
Ammonia is flammable in air at concentrationsbetween 16 and 27%, although ignition is moredifficult than for fuel gases.
Current ammonia safety standards,
codes and other guidance
Current UK safety codes and standards on thesafety of ammonia refrigeration systemsinclude:q
BS 4434:1995 Safety and environmental aspectsin the design, construction and installation ofrefrigerating appliances and systems[2]
q Health and Safety Executive Guidance NotePM81 Safe management of ammoniarefrigeration systems[1]
q Institute of Refrigeration Safety code forcompression systems utilising ammonia[3]
A European CEN standard is in preparation(prEN 378) which will eventually replaceBS 4434:1995. Although these documents give
detailed guidance on the design, installation,commissioning, maintenance and operation ofammonia refrigeration systems, none of themgives guidance on the discharge and dispersionof ammonia.
Accidental releases of ammonia
There is little published information on thecauses and frequency of ammonia dischargesfrom refrigeration plant, or on the rates ofdischarge. The rate of discharge is important asit will strongly influence both the behaviour of
an ammonia leak and the ambientconcentrations that it produces. A small leakfrom a leaking seal or gland may be in the orderof grams per second or lower. A catastrophicrelease, caused by a fractured or severed pipeor from a pressure relief device, could result inmost of the machine charge being released in a
very short time, perhaps at a rate of a 0.1 to1 kg/s. The total discharge is determined by
the machine charge, which depends on thecooling capacity of the machine and its design.
Table 1 gives details of some recently installedammonia chillers in air conditioned buildingsin the UK. Specific refrigerant charge varies
between 0.055 and 0.45 kg/kW of nominalcooling capacity. Clearly chiller selection is aneffective way of minimising the quantity ofammonia used and the consequential hazardsof accidental release.
A crucial feature of ammonia discharges isthe ambient density of the dischargedammonia. Ammonia vapour has a density
between 0.6 and 0.7 that of air (depending onits discharge temperature), so that a cloud ofreleased ammonia will be positively buoyant.Liquid ammonia releases behave differentlyand when released from a part of the plant
which is at high pressure can produce flashingclouds of boiling liquid droplets and vapour.
The cooling effect of the continuouslyevaporating droplets cools the cloud so that itbecomes denser than air. Very large dischargesfrom industrial plant, which sometimes contain
tonnage quantities of ammonia, can therefore
2
Table 1 Ammonia charge of some recently
installed ammonia chillers for air conditioning in
UK buildings
Nominal cooling Ammonia charge Specific charge
duty (kW) (kg) (kg/kW)
250 17 0.068
175 48 0.270
316 30 0.095
1000 55 0.055
200 48 0.240
550 250* 0.450
730 49 0.067
* The high charge was due to this chiller being a
thermosyphon chiller with a flooded shell and tube
evaporator
-
7/31/2019 Ammonia Refrigerant Hazards
4/7
be very dangerous. The hazard from themajority of the building systems detailed in
Table 1, which generally have total chargesbelow 60 kg, would be less. Some liquidreleases produce less flashing and can lead torelatively stable pools of liquid ammonia on theground. The high latent heat of ammonia can
mean that the ground cannot supply sufficientheat for rapid evaporation. Sudden input ofheat, such as by spraying with water to clear
the discharge (see Containment of accidentalspillage and leakage of liquid ammonia), wouldcause violent boiling and formation of vapourclouds. The high latent heat of ammonia canalso result in liquid pools remaining in largeplant after refrigerant recovery and evacuation,creating a safety hazard for maintenancepersonnel.
Gas concentration in dispersing
plumes
Earlier wind tunnel experiments[4] have shownthat the highest gas concentration (C) in adispersing plume is given by
C= 9V/ux2 (1)
where Vis the gas discharge rate,uis the wind speed, andxis the distance along the plume fromits source.
This gives the highest likely concentration at agiven distance. In practice such exposure
would be intermittent as plume motion at short
ranges is usually unsteady. No account is takenof plume buoyancy or the influence of thesurroundings (including buildings) on wind
behaviour. Figure 1 shows curves for a range ofplume concentrations plotted as a function ofammonia release rate and distance from therelease, assuming a wind speed of 2 m/s. It is
clear that quite high gas concentrations (abovethe level for toxic effects) are possible atsignificant distances from the point ofdischarge. It should be emphasised thatFigure 1 shows worst-case short-termconcentrations. Practical experiments withammonia discharges are necessary todetermine more typical concentrations.
Dispersing plume behaviour
It is crucial to understand that the buoyancy ofa discharging gas is not sufficient alone todetermine whether the resulting plume rises orfalls.
The plume buoyancy is determined by thedimensionless buoyancy flux
F/u3L (2)
where Fis the flux of buoyancy defined as
F= (V/) g(/) (3)
where Vis the volume discharge of ammonia,Lis the scale of the release (in this case
the height of the building), is the density difference between
the discharged ammonia and ambientdensity , andgis gravitational acceleration.
High values of the dimensionless buoyancy flux(Equation 2) above about 0.10.3, mean that
the plume will have a positive buoyancy. A
positively buoyant discharge (for exampleammonia vapour) will rise, and a negativelybuoyant discharge (for example a heavier-than-air cold ammonia droplet and vapourcloud) will fall. Conversely low values for thedimensionless buoyancy flux, below about0.002, mean that the plume will have neutral
buoyancy and will neither rise nor fall,regardless of the discharge buoyancy. These
values have been determined from previousBRE work on fire plumes discharging from
warehouses (D J Hall et al, 1995, unpublished).
It is clear from these equations that thedimensionless buoyancy flux is proportional to
3
Figure 1 Approximate distances to a given predicted ammonia
concentration in dispersing plumes (wind speed = 2 m/s)(Note: 1 mg/m3 1.43 ppm)
0.00
50.00
100.00
150.00
200.00
250.00
0 0.2 0.4 0.6 0.8 1
Ammonia release rate (kg/s)
Distance(m
)
Plumecon
centrat
ion=1
00(mg
/m3)
10
30
300
1000
3000
-
7/31/2019 Ammonia Refrigerant Hazards
5/7
the rate of gas discharge and its densitydifference from ambient as well as to the scaleof the dispersion pattern. (For discharges from
building roofs the dispersion scale is taken asthe height of the building.) The dimensionlessbuoyancy flux is also very strongly dependenton wind speed (as u3), so that the highest
levels of the dimensionless buoyancy flux occurat low wind speeds and reduce rapidly withincreasing wind speed.
From the range of possible ammonia releaserates estimated earlier, the range of values of
the dimensionless buoyancy flux that mayoccur in practice can be calculated. Figure 2shows plots of the values of ammonia releaserate and wind speed that give rise to specific
values of the dimensionless buoyancy flux, forpositively buoyant discharges (for exampleammonia vapour). The approximate divisions
between negligible, partial and pronouncedplume buoyancy effects are shown by dashedlines. Also shown are values of the 98thpercentile (20 m/s) and typical annual mean(3 m/s) wind speeds in open country at 10 mheight. In urban areas wind speeds aregenerally reduced significantly below these
values. The scale Lhas been taken as theheight of a typical building, 10 m.
Figure 2 shows that smaller release rates athigher wind speeds show negligible plume
buoyancy effects, while the larger release ratesat lower wind speeds will show verypronounced plume buoyancy effects. Althoughnot shown here, the equivalent effects occur forheavier-than-air releases: the larger releaserates at lower wind speeds will showpronounced slumping of the plume, while theplume will have a neutral buoyancy withsmaller release rates at higher wind speeds.
Wind tunnel visualisations of gas
discharges
The flow patterns of negatively and positivelybuoyant ammonia discharges around buildingshave been investigated using a small-scalemodel (representing a rectangular building of
height 20 m) inside BREs dispersion windtunnel at BRE Cardington.
Figure 3 shows dispersion of neutrallybuoyant discharges from the building roof andan upwind ground level source close to the
building. It can be seen that both dischargeplumes spread over the entire downwind faceof the building. Clearly both locations would beunsuitable for neutrally buoyant ammoniadischarges, as would be the case with smallerdischarges at high wind speeds.
Figure 4 shows flow visualisations ofpositively buoyant discharges from the samelocations. In both cases there was pronouncedplume rise, but when the discharge was atground level the rising plume was spread overall sides of the building, making such a locationhighly dangerous in the event of ammoniadischarges.
Safety guidelines
The requirements of BS 4434:1995[2], theInstitute of Refrigeration Safety Codes[3] andHSE PM81[1], as well as the generalrequirements of the Health and Safety at Worketc Act, should always be complied with. Evenso, the work described in this paper shows thatadditional consideration needs to be given to
the location of ammonia plant and possibleammonia discharges.
Minimise ammonia charge
The hazards of ammonia discharges can beminimised by restricting the amount of
ammonia charge in any single chiller. Carefulchiller design can lead to very low ammoniaspecific charges, and values of around 0.05 kgper kW nominal cooling capacity are possible
with current commercially available chillersusing plate heat exchangers. Note that it is notrecommended to use ammonia in directexpansion (dx) air cooler systems in which therefrigerant-containing parts of the system may
be located in occupied parts of the building (seealso BS 4434:1995[2]).
Location of ammonia chillersThe safest location for ammonia chillers is in aspecial plant room (complying with the safetyrequirements of BS 4434:1995[2] and theInstitute of Refrigeration Safety Codes[3]). The
4
Figure 2 Effect of wind speed and discharge rate on plume buoyancy for
positively buoyant ammonia releases
0.001
0.01
0.1
1
10
100
0.1 1 10 100
Wind speed (m/s)
Ammoniadischargerate(kg/s)
Buo
yanc
yflu
x=10
0
10
1
0.1
0.01
0.00
010.00
1
Typical UK meanwind speed
Typical 98%ile
UK wind speed
Discharge behavesas neutrally buoyantplume
Discharge behaves
as positively buoyantplume
-
7/31/2019 Ammonia Refrigerant Hazards
6/7
siting of ammonia chillers out of doors, eitherat ground level or on a building roof, wouldresult in any accidental release or leakage ofammonia dispersing in an unpredictablemanner, depending on the rate of dischargeand prevailing local wind conditions.
The advantages of locating ammonia chillersin special plant rooms is that liquid spills can
be contained and that external discharge ratesof ammonia can be controlled. Discharge could
be through a fan-assisted stack with highvelocity efflux. Specific guidance on stackdesign is given elsewhere (for exampleASHRAE HandbookFundamentals[5]).
An alternative to a special plant room for
smaller systems is a container or box with itsown ventilation system and ammonia vapourdetectors. If designed and built correctly thisshould offer safety comparable to aconventional special plant room but withsignificantly lower cost and weight.
Pressure relief valve discharge locations
It is fairly common for pressure relief valvedischarge pipes to terminate with a 90 elbow
to prevent ingress of water and dirt. However,this results in a horizontal discharge and
therefore destroys much of the verticalmomentum which assists the rise of thedischarging plume. An improved arrangementhas been suggested by Stoecker[6]where therelief valve discharges into a mixing box where
the ammonia is diluted with fresh air and thendischarged through a vertical fan-assistedstack. However, this makes little difference toconcentrations beyond a few metres from thedischarge point and it is better overall to retaina high velocity vertical discharge of ammoniafrom an elevated nozzle as this maximises theplume rise.
The design of the stack or elevated nozzlemust prevent water and dirt ingress. Guidanceon this is contained in the ASHRAEHandbookFundamentals[5].
Containment of accidental spillage and
leakage of liquid ammonia
Liquid ammonia releases tend to remain in theliquid phase for a long time, owing to the highlatent heat of ammonia and insufficient heatnormally being available in the air or through
the ground surface to cause rapid evaporation.This results in low rates of evaporation ofammonia, which is advantageous in avoidinghigh concentrations around the building. Thefire brigade, who tend to be summoned to deal
with large ammonia releases, are trained todrench the area of the spillage with water. Thisis actually potentially dangerous as the water
provides sufficient additional heat to causeliquid ammonia to boil violently and createhazardous droplet and vapour clouds with a farhigher effective rate of discharge. All plant, butespecially when it is located out of doors,
5
Figure 4 Flow visualisations of positively buoyant
discharges from the roof and upwind ground level
sources
Figure 3 Flow visualisations of neutrally buoyant
discharges from the roof and upwind ground level
sources
-
7/31/2019 Ammonia Refrigerant Hazards
7/7
should be surrounded by an insulated bund tocontain any liquid spills and reduceevaporation rates . Liquid ammonia should also
be prevented from entering roof-top drains orventilation inlets. Clearly it is safer for the plantto be contained in a special plant room, or boxfor smaller systems.
Conclusion
The phasing out of CFC and HCFCrefrigerants and environmental concerns aboutHFC-based alternatives mean that ammoniarefrigeration plant will be increasingly specifiedfor building air conditioning applications.However, ammonia is highly toxic and issuessuch as location of the plant and safetymeasures require careful consideration. Inparticular it has been shown that the dispersalof accidental releases of ammonia is notproperly understood by the industry, andcurrent practice could lead to hazardousconcentrations of ammonia around the
building which could enter any buildingopening. The safest location for ammonia plantis in purpose-built plant rooms, or boxes forsmaller plant, complying with the relevantstandards and codes (for example BS 4434:1995[2] and the Institute of Refrigeration SafetyCodes[3]). Any accidental release should be
vented vertically above the roof in a controlledmanner, so that it cannot be entrained back to
the building. This may require the use of fan-assisted stacks.
Despite its toxicity ammonia is an excellentrefrigerant, and industry experience has shown
that accidents are rare if plant is designed,installed and maintained strictly in accordance
with existing codes and standards. BREsresearch has shown that it is also necessary toconsider the dispersion of ammonia tominimise the risk of it reaching building
occupants or people on the ground. Furtherwork is needed to determine actual rates ofammonia discharge so that the degree ofhazard from ammonia leaks and discharges can
be more accurately assessed.
Acknowledgements
This work was carried out by BRE withfunding from the DETR ConstructionSponsorship Directorate. The views expressedin this paper are those of the authors and notnecessarily those of the Secretary of State for
the Environment, Transport and the Regions.
References
[1] Health and Safety Executive. Safe management of
ammonia refrigeration systems. Guidance Note PM81.
London, HSE, 1995.
[2] British Standards Institution. Safety and
environmental aspects in the design, construction and
installation of refrigerating appliances and systems. British
StandardBS 4434:1995. London, BSI, 1995.
[3] Institute of Refrigeration.Safety code for
compression systems utilising ammonia. Part 1: Design
and construction. Part 2: Commissioning, inspection and
maintenance. Carshalton, Surrey, Institute of
Refrigeration, 1990.
[4] Wilson D J. Flow patterns over flat roofed buildings
and application to exhaust stack design. ASHRAE
Transactions, 1979, 85 284295.
[5] American Society of Heating, Refrigerating and
Air-Conditioning Engineers (ASHRAE). ASHRAE
Handbook 1997. Fundamentals. Chapter 15. Airflow
around buildings. Atlanta, ASHRAE, 1997.
[6] Stoecker W F.Expanded applications for ammonia:
coping with releases to the atmosphere. CFCs: Todays
Options Tomorrows Solutions. CFC Technology
Conferences, US National Institute of Standards and
Technology, Gaithersburg, Maryland, 2728 September
1989. ASHRAE, 1989.
Further reading
BRE Digest358 CFCs in buildings
BRE Information PapersIP1/94 Minimising refrigerant emissions from air
conditioning systems in buildings
IP16/95 Safety and environmental requirements of new
refrigerants
IP6/98 Performance of air-conditioning systems with
alternative refrigerants
6
BRE is the UKs leading centre of expertise on building and
construction, and the prevention and control of fire. For informationon BRE and its services, or for technical advice, contact:
BRE, Garston, Watford, WD2 7JR
Tel: 01923 664000
Fax: 01923 664098
email: [email protected]
website:www.bre.co.uk
BRE publishes a wide range of information on all
aspects of the built environment.Details of all BRE publications and the Professional
Development Package (the subscription service that
supplies Digests, Good Building Guides, Good Repair
Guides and Information Papers as they are published),
can be obtained from CRC Ltd publi shers for BRE
or from the BRE website.
CRC Ltd, 151 Rosebery Avenue,
London, EC1R 4GBTel: 020 7505 6622
Fax: 020 7505 6606
email: [email protected]
website: www.constructionplus.co.uk
Requests to copy any part of this
publication should be made to:CRC Ltd, PO Box 202,
Watford, Herts, WD2 7QG
Copyright BRE 2000
July 2000
ISBN 1 86081 419 0
constructing the future