America’s Boiler Company - Burnham · PDF fileAmerica’s Boiler Company Contents...
Transcript of America’s Boiler Company - Burnham · PDF fileAmerica’s Boiler Company Contents...
Firetube Boilers and Accessories
America’s Boiler Company
�
�
ContentsPRODUCT PAGESeries 3 Packaged Firetube Boiler.................................................................................................................. 3Series 3 Shock Proof Boiler........................................................................................................................... 9Series 3 Packaged Firetube Boiler “Ohio Special”......................................................................................... 11Anticipated Efficiencies................................................................................................................................. 13Wetback vs. Hard Refractory Dryback Design.............................................................................................. 15Series 4S 4-Pass Wetback Scotch Boiler..................................................................................................... 17Low Nox Boiler............................................................................................................................................ 21Series 4F Forced Draft Firebox Boiler........................................................................................................... 23Series 4F-40 ................................................................................................................................................ 27Series 4F-45 ................................................................................................................................................ 29Series 4F-50 ................................................................................................................................................ 31Series 4F Forced Draft Firetube Boiler “Ohio Special” ................................................................................. 33Series 4N Natural Draft Firebox Boiler ......................................................................................................... 35Series 4NP Natural Draft Firebox Boiler ....................................................................................................... 43C Series Compact Package Boiler ................................................................................................................ 45Component Summary Information .............................................................................................................. 49Chemical Feed System ................................................................................................................................ 52Bypass and Shot Feed Systems .................................................................................................................. 54Boiler Feedwater System ............................................................................................................................ 56Condensate Return System ........................................................................................................................ 57Blowdown Heat Recovery System ............................................................................................................... 58Bottom Blowdown Tank .............................................................................................................................. 60Flash Separator ........................................................................................................................................... 62Bottom Blowdown Separator ...................................................................................................................... 64Conductivity Controller ............................................................................................................................... 66Water Softener Systems BS & BP ............................................................................................................... 68Horizontal and Integral Deaerators .............................................................................................................. 70Engineering and Application Data Index ...................................................................................................... 73
�
Series 3Packaged Firetube Boiler
� �
Series 3 - Packaged Firetube BoilerSave Thousands Of Dollars Over The Life Of Your BoilerLong-term energy and maintenance efficiencies are the focus of Burnham quality engineering. When choosing a boiler, it’s a good idea to select a product with these features in order to reduce enormous hidden costs down the road. Review our wetback versus dryback literature for cost savings.
Boiler Costs Is Not Jus A First Year PropositionWith any ordinary boiler, expenses such as fuel, maintenance, and repair costs can escalate as the years go on. Burnham packaged boilers are designed to diminish these significant expenditures.
Burnham’s High Life-Cycle EfficiencyWhile most competitive boilers can give fuel-to-steam efficiencies of 80% or over—when they’re new—how consistently can they be expected to maintain this level of operation? Burnham wetback boiler performance will not drop due to deteriorating rear refractory, leaking door baffles and seals, and heat-stressed rear tube sheet as can happen with some drybacks. Easy access is a necessity for those with heavy refractory, since they need frequent and expert maintenance.
The Burnham Wetback Saves Big Money On MaintenanceOver the life of a dryback, brittle refractory baffling and rear door gasketing will require continuous monitoring, maintenance, and replacement, costing thousands upon thousands of dollars. These built-in maintenance costs can eventually equal or exceed the original cost of the boiler. As refractory deteriorates, leaking hot gas causes boiler efficiency to drop until the condition is noticed and the repairs can be made. Expensive flue temperature alarms are offered with some drybacks to monitor this dangerous and costly potentiality. The rear door itself can become heat-distorted, requiring an expensive replacement. In addition, boiler downtime during repairs can mean crippling losses.
This waste of time and money is eliminated with the Burnham Wetback. The actively functional water jacket eliminates the need for: refractory wall, rear door, rear door inspection and sealing, door swing space, and flue temperature alarm. These costly maintenance headaches are gone, while boiler performance is increased. Burnham has only a small, inexpensive refractory area in the burner area, for burner mounting. The rear access door liner is a ceramic fiber insert that contains no refractory.
The furnace and rear turnaround area are cool running, fully wetbacked radiant heat transfer surfaces. They promote good internal water circulation and rapid heat absorption. There is no need for the forced internal circulation pumps often specified to cool the rear tube-sheets and drybacks.
The Burnham Wetback Is Built To LastTypical dryback boilers have a common rear tubesheet that expands and contracts at different rates adjacent to each tube pass, stressing tube ends and increasing the likelihood of leaks. Additionally, the heavy refractory used in some drybacks reflects intense heat to the rear tube ends and tube sheet, accelerating their deterioration. In attempts to stop leaking, the rear ends of tubes have sometimes been welded. Cleaning or tube replacement involves opening both the front and rear covers and resealing them when the job is done. Usually, if tubes have been welded at the ends, the welds must be burned out, the tube sheet repaired (or a new segment welded in) and the new tubes welded.
These costly expenditures are not an issue with the Burnham Scotch Marine: separate rear tube sheets from each pass to expand and contract at its own rate without tube-to-sheet stress. Tubes are rolled and flared in low-pressure units; and rolled, flared and beaded in high-pressure units. No welding of tubes is permitted, nor is it necessary. Any eventual tube replacement is simply a mechanical operation, no welding involved. The end result is less cost and less headache.
� �
Series 3 - Ratings and Data
Boiler Model
Shell Diam.
Gross Output Net Rating Heating Surface Firing Rate
Furn. Vol., Cu. Ft.
Water Content Approx. Wt. Dry, Lbs.
BHP MBH LBS/HR
Steam MBH
Steam Sq. Ft.
Water, MBH
Sq. Ft.
F.S.
Sq. Ft.
W.S.
Gas, MBH
Oil, GPH*
Lbs. Steam
Lbs. Water
15-30 PSI
150 PSI
�0 �8 �0 1,��9 1,�80 1,011 �,�11 1,16� �00 ��0 1,67� 1�/11 1�.8 1,760 �,18� �,700 �,�00
�0 �8 �0 1,67� 1,7�� 1,�90 �,�76 1,��6 ��0 �80 �,09� 1�/1� 17.1 �,�0� �.701 �,�00 �,700
60 �8 60 �,009 �,070 1,�60 6,�99 1,7�7 �00 ��� �,�00 18/17 19.� �,76� �,��� �,700 �,�00
70 �� 70 �,��� �,�1� 1,819 7,�80 �,0�7 ��0 �90 �,9�0 �1/�0 �7.8 �,�8� �,160 �,�00 6,�00
80 �� 80 �,678 �,760 �,079 8,66� �,��9 �00 ��� �,��8 ��/�� �0.� �,67� �,6�1 �,900 6,700
90 �� 90 �,01� �,10� �,��9 9,7�7 �,6�0 ��0 �00 �,766 �7/�� ��.0 �,060 �,1�� 6,�00 7,�00
100 �� 100 �,��8 �,��0 �,�99 10,8�0 �,911 �00 ��� �,18� �0/�8 ��.8 �,��� �,711 6,900 7,700
1�� 66 1�� �,18� �,�1� �,��8 1�,��� �,6�8 6�� 69� �,��0 �8/�� �1.9 �,�8� 6,67� 8,700 9,�00
1�0 66 1�0 �,0�1 �,17� �,898 16,��� �,�66 7�0 8�� 6,�76 ��/�� �7.7 6,660 7,9�7 9,700 10,600
17� 66 17� �,8�8 6,0�0 �,��8 18,9�0 �,09� 87� 970 7,��� ��/�9 ��.1 7,7�8 9,��� 10,900 11,600
�00 66 �00 6,69� 6,900 �,198 �1,6�8 �,8�� 1,000 1,110 8,�69 60/�6 �8.8 8,8�9 10,�19 1�,�00 1�,�00
��0 78 ��0 8,�69 8,6�� 6,�98 �7,07� 7,�77 1,��0 1,�60 10,�61 7�/70 86.6 11,17� 1�,98� 1�,�00 18,600
�00 78 �00 10,0�� 10,��0 7,797 ��,�89 8,7�� 1,�00 1,6�0 1�,�00 90/8� 99.1 1�,�1� 16,6�9 18,100 �1,�00
��0 90 ��0 11,716 1�,07� 9,096 �7,901 10,188 1,7�0 1,900 1�,6�� 10�/98 11�.� 1�,�9� 19,��0 �1,000 ��,700
�00 90 �00 1�,�90 1�,800 10,�96 ��,�17 11,6�� �,000 �,17� 16,7�8 1�0/11� 1��.7 16,76� ��,1�� ��,�00 �6,100
�00 10� �00 16,7�8 17,��0 1�,99� ��,1�7 1�,��� �,�00 �,71� �0,9�� 1�0/1�0 1��.0 18,�1� ��,788 �7,�00 �0,600
600 10� 600 �0,08� �0,700 1�,�9� 6�,9�7 17,�6� �,000 �,�60 ��,106 180/168 17�.� ��,1�8 �8,�81 �1,�00 ��,�00
700 10� 700 ��,��� ��,1�0 18,19� 7�,80� �0,�77 �,�00 �,80� �9,�19 �10/196 19�.8 ��,767 ��,00� ��,700 �9,700
800 108 800 �6,780 �7,600 �0,79� 86,6�� ��,�87 �,000 �,��9 ��,�7� ��0/��� �0�.� ��,9�� ��,76� ��,900 ��,900
900 11� 900 �0,1�8 ��,�17 ��,�00 97,61� N/A �,�00 �,90� �7,660 �69/��� �78 �0,89� N/A �7,800 �6,600
1000 1�� 1,000 ��,�76 ��,�00 ��,990 108,�9� N/A �,000 �,��0 �1,8�6 �00/�80 �09 ��,��7 N/A �1,600 10�,�00
Note: Dimensions and Data are Not for Construction Purposes and are Subject to Change without Notice
6 7
• Ready access to tubes through rugged front door and rear covers makes routine cleaning easier and less costly than with drybacks.
• Burner does not have to be disturbed.
• No inner air baffle door to contend with.
• No delicate expensive baffle tiles or door seals to replace.
• Unlike dryback boilers, securing the doors on a Burnham wetback boiler requires no specialized skills or expensive repair materials. It is a simple process which can be done with in-house personnel and performed with minimal downtime.
Front View
Rear View
• Large, fully waterbacked furnace tube assures complete combustion and heat absorption without flame impingement.
• Three gas passes extract maximum usable heat from the fuel while maintaining optimum flow for forced draft firing.
• Fully waterbacked reversing chamber effectively absorbs radiant heat into the water, keeping tube ends and rear of boiler cooler than those of hot-running drybacks.
6 7
What do all these features and specifications mean? More savings for you! Our Packaged Wetback Firetube boilers are designed for long-term efficiency and economical operation, making Burnham your cost-performance leader!
The Series 3 matches burner to boiler, providing a fuel-efficient, low-maintenance package. Maintenance costs can be further controlled in your boiler room with optional accessories. Such options include state-of-the-art annunciator systems, custom-designed to monitor all boiler and burner interlocks vital to your specific installation. They provide instant readouts of both normal and abnormal operating conditions. These features will pinpoint the cause of unscheduled shutdowns; reducing maintenance time and skill required.
• Forced-draft firing with oil (No. 2, 4, 5, or 6), gas or combination gas/oil
• Low or high pressure steam or water
• Highly efficient three-pass design
• Fully waterbacked primary heating surfaces
• Separate rear tube sheets for longer service life
• Wetback design allows easy front and rear access
• No expensive refractory or door replacement as with some drybacks.
It All Adds Up To Significant Cost-Performance Advantage.
8 9
Series 3 — Standard EquipmentBoiler:Three pass full wetback, packaged firetube type, constructed in accordance with requirements of the ASME Code Section IV for 30 psi and 125 psi water or 15 psi steam; Section I for higher pressure steam. All units are registered with the National Board.Boiler tubes are expanded and flared in low pressure boilers; expanded and beaded in high pressure boilers. Turbulator baffles are not used in tubes. Separate second and third pass rear tube sheets allow safe expansion and contraction.Waterbacked rear turnaround promotes rapid internal circulation and reduces gas temperatures at entrance to second pass, reducing tube end stress.Easy opening hinged, insulated front flue doors with lightweight closure provide full access to all tubes. A 16-inch diameter bolted rear access door with observation port provides access to the boiler furnace. Rear tube access is provided by removing light weight gasketed door(s) installed in the rear smokebox. No elaborate seals are used.A manhole is furnished as standard on water and low pressure steam boilers sizes 3-125 and larger; on high pressure steam boilers sizes 3-70 and larger.Handhole washouts are provided for easy inspection and cleaning of waterside surfaces.All steam boilers provided with a dry pan to ensure dry steam. A feedwater diffuser is provided on high pressure boilers. All water boilers are equipped with a dip tube at supply outlet and diffuser at return inlet.The round flanged vertical smoke outlet is equipped with a locking quadrant damper. All boilers are provided with an enameled steel jacket over 2 inches of fiberglass insulation, and lifting lugs.The boiler is mounted on a heavy duty structural steel base with extended skid and burner platform for protection of the burner during shipment and rigging.
Standard Trim and Controls:Steam: 157 pump control/low water cut-off with alarm contacts–piped with quick opening blowoff valve. Gauge glass set with hand-operated and try cocks. Steam pressure gauge—4 1/2 inch dial on sizes 100 hp and smaller, 6 inch dial on larger sizes. L404C manual reset high limit pressuretrol and appropriate firing rate control when required. Manual reset probe auxiliary low water cut-off.ASME side outlet safety valve(s). Water: 63M manual reset low water cut-off with 30 psi units, 150 low water cut-off with higher pressure units–piped with quick opening blowoff valve. Combination pressure/temperature gauge–3 1/2 inch dial on 100 hp and smaller. On larger sizes a 6 inch combination pressure/altitude gauge and 5 inch dial temperature gauge. L4006A operating aquastat and L4006E manual reset high limit aquastat and appropriate firing rate control when required.ASME side outlet safety valve(s).
Burner Equipment:Burner mounts to front head of boiler with no elaborate seals.Factory packaged units available with forced draft burners for all commonly used fuels–gas, all grades of oil–No. 2 through No. 6–and combination gas/oil. Choice of pressure or air atomizing burners for No. 2 oil–air atomizing on heavy oil. Gas burners are available for either natural or LP gas.Refer to burner data sheets for standard burner equipment and operating sequence.
Accessories and Optional Equipment:Accessories and optional equipment available at extra cost, including, but not limited to: • Solid-state annunciators • Alternate or additional water level controls or low water cut-offs • Built-in tankless heater coils—low-pressure boilers only • Motorized or pneumatic feed valves • Surface skimmers and blowoff valves • Bottom blowdown valves and drain valves • Feed stop and check valves • Sequence draft controls • Lead/lag sequencing systems • Boiler Feed systems • Low NOx burners • Deaerators • Water Softeners • Chemical Feed systems • Blowdown systems • Sample Coolers
©2009 Burnham Commercial - Lancaster, PAPhone: 1-888-791-3790
www.burnhamcommercial.com
8 9
Series 3Shock Proof Boiler
Eliminate any thermal shock concerns with a Series 3-SP Shock Proof hot water boiler package. Our low pressure, 15 psi steam boiler is equipped with a full capacity coil type
heat exchanger capable of 125 psi maximum water pressure.
10 11
Lancaster,PA17601Phone:888-791-�790
www.burnhamcommercial.com
Ratings and Data
Performancecriteriabasedon10psiboileroperatingpressureFlangesorientationmaybehorizontal,asillustrated,orvertical.Consultfactory.
Eliminate Thermal Shock…EliminateanythermalshockconcernswithourSeries�-SPShockProofhotwaterboilerpackage.ThisboilerdesignusesourreliableSeries�thatincorporatesahighsteamspacevolumethatcaneasilyaccommodatetheindustrieslargestfullcapacitycoil.TheSeries�wetbackdesignandlowvolumetricfurnacereleaserates allow easy firing and a prolonged boiler life. When properly commissionedandmaintained,yourshock-proofpackagedboilerwilllastformanyyears.
• Nosteamsidewatermakeup,nosteamside accessoriesarerequired.
• Thereisonlyoneinitialsteamsidewatertreatmentrequired. Sincethesteamsideissealed,expensivemaintenancehours, auxiliaryequipmentandchemicalsareeliminated.Acleansteam side will make your boiler run more efficiently.
• The hot system water flows only through the tubes of the heat exchangereliminatingthermalstressesandhotwatermaintenance issuesontheboilerside.
• Speciallydesignedheatexchangertubeswhicharehighlyresistant tocorrosionanderosion.
• Speciallyconstructedhead
• Flangedsupplyandreturn
• Coiltrimpackageincluded,consistsofinletandoutletpressure gauges,inletandoutletthermometersandcoilsidesafetyvalves.
• Equippedwithafullcapacitycoiltypeheatexchangerdesignedfor 1��psimaximumwaterpressure.
Model Number 3L125SP 3L150SP 3L200SP 3L250SP 3L300SP 3L350SP 3L400SP 3L500SP 3L600SP 3L800SP
Output @ Coil Nozzle, MBH, 4,184 5,021 6,695 8,369 10,043 11,716 13,390 16,738 20,085 26,780
GPM @ 20°F Delta T/180°F/200°F 420 503 670 840 1,008 1,180 1,340 1,680 2,015 2,755
Delta P thru coil at above flow rate, PSI 5 5 5 5 5 5 5 5 5 5
Head Flange Size, 150# ANSI 4” 4” 5” 6” 6” 6” 8” 8” 8” 8”
Shock Proof Benefits
Shock Proof Features
10 11
Theboilerismountedonaheavy-dutystructuralsteelbasewithextendedskidandburnerplatformforprotectionoftheburnerduringshipmentandrigging.
Standard Trim and Controls1�7pumpcontrol/lowwatercut-offwithalarm,contacts-pipedwithquickopeningblowoffvalve.Gaugeglasssetwithhandoperatedgaugeandtri-cocks.Steampressuregauge:�-1/�inchdialon100HP,6inchdialonlargersizes.L�0�Aoperatingpressuretrol,L�0�Cmanualresethighlimitpressuretrol and appropriate firing rate control when required. Manualresetprobeauxiliarylowwatercut-off.ASMEsideoutletsafetyvalve(s).
Series 3 Packaged Firetube Boiler — “Ohio Special” Three pass full wetback, packaged firetube, constructed in accordancewithrequirementsoftheASMEcode,sectionIVfor1�-psisteam;Section1forhigherpressuresteam.AllunitsareregisteredwiththeNationalBoard.
Boiler tubes are expanded and flared in low-pressure boilers; expandedandbeadedinhighpressureboilers.Separatesecondandthirdpassreartubesheetsallowsafeexpansionandcontraction.
Waterbacked rear turnaround promotes rapid internal circulationandreducesgastemperaturesatentrancetosecondpass,reducingtubeendstress.
Easy opening hinged, insulated front flue doors with bolted closureprovidefullaccesstoalltubes.A16-inchdiameterboltedrearaccessdoorwithobservationportprovidesaccesstotheboilerfurnace.Removinglightweightgasketeddoor(s)installedontherearsmokeboxprovidesreartubeaccess.Noelaboratesealsareused.AmanholeisfurnishedasstandardonallOhioSpecialBoilers,100through���hp.Handholewashoutsareprovidedforeasyinspectionandcleaningofwatersidesurfaces.
Allsteamboilersareprovidedwithadrypantoensuredrysteam.Afeedwaterdiffuserisprovidedonhigh-pressureboilers.
The round-flanged vertical smoke outlet is equipped with a lockingquadrantdamper.Allboilersareprovidedwithanenameled steel jacket over 2 inches of fiberglass insulation andliftinglugs.
Shell Diameter Ratings Gross Output - BHP Gross Output - MBH Gross Output - LBS/HR Net Rating - MBH Net Rating - Sq. Ft.
100X 125X 150X 175X 200X 225X
��100
�,��8�,��0�,�99
10,8�9
��1��
�,18��,�1��,��9
1�,��6
��1�0
�,0�1�,17��,898
16,���
��17�
�,8�86,0�7�,��8
18,9�1
���00
6,69�6,900�,198
�1,6�8
�����
7,���7,76��,8�8
��,�66
Safety Valve (15 PSIG) - LBS/HRSafety Valve (150 PSIG) - LBS/HR
�,��0�,906
�,�1��,88�
�,17��,8�8
6,0�76,8��
6,9007,811
7,76�8,787
Heating Surface - Sq. Ft. Fireside Waterside
��8�8�
��8�8�
��8�8�
��8�8�
��8�8�
��8�8�
Firetubes Number Diameter - Inches
�6�.�
�6�.�
�6�.�
�6�.�
�6�.�
�6�.�
Furnace Volume - Cu. Ft. Diameter - Inches
�0.���
�0.���
�0.���
�0.���
�0.���
�0.���
Firing Rate 100 BTU Gas - MBH 140 MBTU/Gal. Oil - GPH 150 MBTU/Gal. Oil - GPH
�,18��9.9�7.9
�,��0�7.���.9
6,�77��.8�1.8
7,�����.��8.8
8,�69�9.8��.8
9,�1�67.�6�.8
Ratings and Data
1� 1�
A - Base WidthB - Furnace CenterC - Overall High Pressure Supply Connection Overall Low Pressure Supply Connection
100X 125X 150X 175X 200X 225X
3833-5/16 76-5/8 76-5/8
3833-5/1676-5/8 76-5/8
3833-5/1676-5/8 76-5/8
3833-5/1676-5/8 76-5/8
3833-5/1676-5/8 76-5/8
38 33-5/1676-5/8 76-5/8
D - Width over TrimE - Width over JacketF - Base to N.W.L.G - Overall Length
69-1/459-1/459-3/4
190-1/2
69-1/459-1/459-3/4
190-1/2
69-1/459-1/459-3/4
190-1/2
69-1/459-1/459-3/4
192-1/2
69-1/459-1/459-3/4
192-1/2
69-1/459-1/459-3/4
194-1/2
H - Base LengthJ - Front to High Pressure Feed ConnectionK - Base ExtensionL - Flue Door Clearance
159-3/493-1/835-3/429-1/2
159-3/493-1/835-3/429-1/2
159-3/493-1/835-3/429-1/2
159-3/493-1/835-3/429-1/2
159-3/493-1/835-3/429-1/2
159-3/493-1/835-3/430-3/4
M - Tube Removal SpaceN - High Pressure Supply Size Low Pressure Supply Size P - Shell Length over Flue Outlet
1254” flg8” flg
154-3/4
1254” flg8” flg
154-3/4
1254” flg8” flg
154-3/4
1256” flg8” flg
156-3/4
1256” flg8” flg
156-3/4
1256” flg8” flg
158-3/4
Q - Front to SupplyR - High Pressure Supply to Manway Low Pressure Supply to ManwayS - Flue Outlet Flange Diameter
60-1/8333317
60-1/8333317
60-1/8333317
60-1/8333317
60-1/8333317
60-1/8333317
T - Flue Inside DiameterU - Outside Flange to CenterV - Floor to Flue Outlet Flange
13-3/88-1/2
74-3/8
13-3/88-1/2
74-3/8
13-3/88-1/2
74-3/8
15-1/29-1/2
74-3/8
15-1/29-1/2
74-3/8
17-1/29-1/2
74-3/8
W - Floor to High Pressure Feed ConnectionX - Feed Connection Size
43-5/161-1/4
43-5/161-1/4
43-5/161-1/4
43-5/161-1/2
43-5/161-1/2
43-5/161-1/2
Water Content LBS Gallons
5,536664
5,536664
5,536664
5,536664
5,536664
5,536664
Approximate Shipping Weight Low Pressure (Dry) - LBS Low Pressure (Wet, N.W.L) - LBS High Pressure (Dry) - LBS High Pressure (Wet, N.W.L.) - LBS
7,00012,4508,100
13,550
7,05012,4508,150
13,550
7,10012,5008,200
13,600
7,50012,9508,600
14,050
7,65013,0508,750
14,150
7,65013,0508,750
14,150
Dimensions (in inches)
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
1� 1�
Anticipated Efficiencies
BOILERSIZE
125% 50% 75% 100%10 # 125 # 10 # 125 # 10 # 125 # 10 # 125 #
100125150200
8�.�081.008�.008�.�0
78.�077.0078.0079.00
8�.�08�.008�.008�.�0
80.�079.0080.0080.�0
8�.�08�.008�.008�.�0
81.0079.�080.�081.00
8�.�08�.008�.008�.�0
81.0079.�080.�081.�0
250300350400500600
81.�08�.008�.�08�.008�.�08�.00
78.0078.�078.�078.0079.0079.�0
8�.008�.�08�.008�.008�.008�.00
79.�080.0080.�080.0081.0081.00
8�.008�.�08�.008�.008�.008�.�0
80.0080.�081.0080.�081.�08�.00
8�.008�.�08�.008�.008�.008�.�0
80.0080.�081.0080.�081.�08�.00
700800
1000
8�.008�.�08�.�0
79.�080.0080.00
8�.�08�.�08�.�0
81.�081.�081.�0
8�.�08�.�08�.�0
8�.008�.008�.00
8�.�08�.�08�.�0
8�.008�.008�.00
Natural Gas
BOILERSIZE
125% 50% 75% 100%10 # 125 # 10 # 125 # 10 # 125 # 10 # 125 #
100125150200
8�.�08�.008�.0086.00
81.�080.0081.008�.00
86.�08�.0086.0087.00
8�.�08�.008�.008�.00
86.�08�.�086.�087.00
8�.008�.�08�.�08�.�0
86.�08�.�086.�087.00
8�.008�.�08�.�08�.�0
250300350400500600
8�.008�.�08�.�08�.0086.0086.00
81.�081.�08�.0081.�08�.008�.�0
8�.�086.0086.�086.0087.0087.�0
8�.008�.�08�.008�.�08�.008�.�0
8�.�086.0086.�086.�087.�087.�0
8�.008�.�08�.�08�.008�.008�.00
8�.�086.0086.�086.�087.�087.�0
8�.008�.�08�.�08�.008�.008�.00
700800
1000
86.�087.0087.00
8�.�08�.008�.00
87.�088.0088.00
8�.�08�.008�.00
88.0088.0088.00
8�.�08�.�08�.�0
88.0088.0088.00
8�.�08�.�08�.�0
#2 Oil
1� 1�
ThERMAL EFFICIENCY Theeffectivenessoftheboilerasaheatexchanger.Itistheabilityoftheboilertoexchangeheatthroughtubesandfurnace,byradiation,conductionandconvection,tothetransfermedium(water).Afewofthefactorsaffectingthermalefficiency are heating surface, tube number and diameter, furnace tube length and diameter.
COMBuSTION EFFICIENCYThisisameasureoftheabilityoftheburnertoeffectivelyandcompletelyburnthefuel,coupledwiththethermalefficiency of the boiler. Burners requiring high amounts of excess air to provide flame stability will be less efficient. Combustion efficiency does not take into account heat loss to the surrounding air through the boiler jacket and piping.
FuEL TO STEAM EFFICIENCYSometimes referred to as overall efficiency. This is a ratio of heat output to heat input. This includes boiler jacket and pipinglossestothesurroundingenvironment.Itisthepercentofuseableheatinthesteam(orhotwater)comparedtothe heat input supplied by the burner. It is also defined as the combustion efficiency less boiler jacket and piping loss (radiation and convection losses). Since fuel-to-steam efficiency reflects the portion of actual usable heat supplied to thesystem,itismostusefulwhencomparingperformanceofsimilarequipment,orwhendoingfuelsavingsanalysis.
Ratingsmaybeexpressedinthefollowingunits:
BHP=BoilerHorsepower.OneBHPistheevaporationof��.�lbsof�1�°Fwaterperhourintodrysaturated steamatthesametemperature.
BTUhBHP= ��,�7�BTUh/BHP
BTU=BritishThermalUnits:thatquantityofheatrequiredtoraiseone(1)lb.ofwaterone (1)degreeontheFahrenheitscale.BTUh=BTU/hr.
MBH=1000BTUh
PPH=Poundsofsteamperhour
MBHPPH= 0.970�MBH/PPH
Gross Rating–Thefulloutputofaboileractuallyavailabletotheheatingorprocesssystemattheoutletnozzle. TheCommercialSteelBoilerIndustrycatalogsgrossoutputas80%ofinput.
Net Ratings–Thenetconnecteddesignloadthatcanbesuppliedwithheatbyaboilerofgivenoutput,allowing fornormalsystempipinglossesandpickupfromacoldstart.Sincesteamsystempipinglossesmaybe expectedtobelargerthanforwatersystems,andsteamboilersrequiregreaterheatinputfromacoldstart than water boilers before heat flows to the system, steam net ratings for automatic fired boilers are slightly lower in relation to gross output than water net ratings. Hand fired net water and steam ratings are equal andarelowerinrelationtogrossoutputinordertoprovideampleallowanceforrapidpickupfroma banked fire.
MBH net water=GrossMBHx0.87
MBH net steam=GrossMBHx0.776
Square Foot Ratings–Netratingsbasedonaheatemissionrateof��0BTUhpersquarefootofradiationfor steam,and1�0BTUhpersquarefootforwater.
Steam Net MBH Water net MBHSquare Feet Net Steam= Square Feet Net Water= 0.��MBH/sq.ft. 0.1�MBH/sq.ft.
BOILER RATINGS
1� 1�
Wetback Design vs. Hard Refractory Dryback DesignWhy is a Wetback design better?Burnham’sthree-passwetbackdesignhasarearwaterwall,whichseparatestheprimaryheatingsurfaceofthecombustionchamberfromthereartubesheet.Thewaterjacketeliminatestheneedforarefractorywallandreardoorswingspacebehindtheboiler,aswellascostlyrefractorymaintenance.
Therearwaterwalleliminatestheneedforgasketing,whichisvulnerabletothetemperaturegeneratedintherearoftheturnaroundarea.Awetbackdesignboilernotonly overcomes these expensive deficiencies, but it has great overall efficiency and virtually maintenance-free construction.
A Burnham boiler will cost you less over the lifetime of the boiler because it is better by design!
Some Points to Remember:Wetback Advantages• Wetback boilers have separate tube sheets between all major temperature changes.• The rear access door is constructed of lightweight ceramic fiber• Thereardoorsrequirenocool-downperiodandcanbeopenedimmediately• Nospaceconsumingarearequiredfortheswingdoor• The split rear flue doors are easily removed • Efficiency is readily maintainable because the design of the boiler promotes complete and even circulation of flue gases
Dryback Disadvantages• Fluegastemperaturedifferentialof1�00F-1600Fbetweenthesecondandthirdpassescreatesdamagingstresses onthesingletubesheet.Thecostofreardoorrefractoryreplacement(approximatelyeverythreeyears)will drasticallyincreaseoperatingcosts,aswellasthecostsassociatedwithyearlyreardoorgasketreplacement.• Openingandresealingthereardooristimeconsumingandrequiresa��-hourcooldownperiodpriortoopening• Theheavyrefractorymaysagonthedavitandmustberiggedbackintoplace.Heavyjacksorexpensiverigging mayberequiredjusttoopenandclosethereardoors• Exposing the refractory to hot flue gases can cause erosion and destroy the baffle; resulting in the uneven circulation of flue gases and lower efficiency• Rearrefractorywallsradiateunabsorbedheat,leadingtoexternalheatloss
16 17
WhAT IS FuEL-TO-STEAM EFFICIENCY AND IS IT IMPORTANT?Fuel-to-steam efficiency is very important because it is the only true measure of overall packaged boiler operational efficiency. True fuel-to-steam efficiency takes into account radiation and convection heat losses, which less reputable manufacturers may ignore. We suggest purchasing your boiler from a manufacturer who guarantees fuel-to-steam efficiency in the performance of your entire packaged boiler. Be wary of misleading efficiency terms, such as “thermal efficiency” or “combustion efficiency”. Contact your local Burnham Commercial sales representative for further defini-tion.
MAINTAINABLE EFFICIENCY VS. ATTAINABLE EFFICIENCYWhen looking at efficiency as criteria for purchasing a boiler, especially fuel-to-steam efficiency, the manufacturer’s design efficiency sets theoretical fuel costs while operation efficiency determines actual fuel costs. There is a differ-ence between attainable efficiency and maintainable efficiency. Correct burner adjustments are the key to maintain-able efficiency. It is a compromise between the optimum and the practical. Good burner tuning is achievable only with agoodburnerdesignandagoodburner/boilerpackage.
WILL A DRYBACK BOILER COST MORE TO OWN?The answer is simple…Yes! The high cost of maintenance is the biggest consideration in overall efficiency in a dry-backdesign.Considerthisexample:anaverage�00HPboileroperatingundernormalconditionswithaconserva-tivelifespanof��years.Oursurveyshaveshownthatduringthisboiler’slifetimethereardoorrefractorywouldbereplacedabout8times(roughlyeverythreeyears).Also,assumingtheboilerisopenedonlyonceayearforinspec-tion,regasketingofthereardoorwouldoccur��times.
Howmuchcheaperisthehardrefractorybackedboiler?So, somebody is offering a hard refractory backed boiler design for less money than a wetback design! While it may makeyourinitialcapitalinvestmentcostslookgreat,whatdoesitdotoyourpocketbookinthelongrun?Let’stakealook.... Averagecostforreplacingreardoorhardrefractory:$6,000 Averagecostofregasketingthereardoor:$�00
Applythesecoststotheaveragelifespanoftheboiler: $6,000X8=$�8,000 $�00X��=$1�,�00
Comparethecostsofreplacingthereardoorgasketofyourwetbackdesign: $�0X��=$7�0
Thedifferencebetweenthehardrefractorydrybackmaintenanceandthewetbackmaintenanceis $60,�00-$7�0=$�9,7�0.
Nowcomestheshockingpart...forthesameamountofmoneyspentindrybackmaintenance:
YOu COuLD hAVE PuRChASED A NEW BuRNRhAM WETBACK BOILER!
16 17
Series 4S4-Pass Wetback Scotch Boiler
18 19
4-Pass Wetback Scotch BoilerAmerica’s Boiler CompanyTheBurnhamCommercialSeries�Sfour-passwetbackscotchboilerwasdesignedusingour1�0+yearsofboilerexperienceandissoldandservicedthroughthelargestandmostexperiencednetworkofsalesrepresentativesinthe country. With a complete commercial product offering andunmatchedsalesandtechnicalsupport,it’snowonderwhyweareAmerica’sBoilerCompany!
Why Choose the Series 4S?• The design incorporates positive water flow circulation andmaximumheattransfertomaximizeratings.
• Thehandholeclean-outsareplacedforeaseof servicing.
• Theaccessdooris constructedofdurable, lightweightvacuumformed ceramic fiber—the door liner weighslessthan�0pounds!
• Allexternaltrimpipingis designedandinstalledin accordancewiththeASME Code and is certified by an independentinspectionagencyforcompliance.
• The fiberglass insulated steel jacket is finish painted withhighglossBurnhamblueenamel.
• Thefrontandrearfull-sizedhingedaccessdoorsare standardandsecuredwithnon-corrosivebrassnuts.
• TheULapprovedpackagedburnersaretrimmedand wiredtoassembledgastrains.
• Theheavysteelbaseprovidesadequatestability alongwithshippingandriggingprotection.
• It is completely packaged and ready for “same day” installation.• The�sq.ft./hprateddesigndoesnotuseturbulators orweldedtubeends.
• The multitude of QC checkpoints and stringent final inspectionassuresyouofaqualityproduct.
• Therearenoproprietarypartsorgasketsontheboiler trimortheburner.
Latest Design TechniquesTheSeries�Susestheverylatestdesigntechniquesandstandards.Itsfurnace,theworkhorseoftheboiler,isdesignedforlowvolumetricreleaseratesofnomorethan1�6,000btu/hr/cu.ft.Thelowerthereleaserates,the “easier” your boiler works. As your boiler works easier,lessstressisputuponthesteel,tubeends,refractory,etc.,resultinginalongerlastingboiler.Inadditiontolongevity,alargerfurnacemakesforeasein firing using any selected burner vendor. The Series �SisalsoeasilyconvertedtoalowNOxproductwhenneeded.
Higher EfficiencyTheBurnhamSeries�Sdesignproducesahigherefficiency due to the larger furnace and higher heat transfer design. To determine the efficiency of your next job,contactyourlocalBurnhamrepresentative.
4 Pass Wetback Scotch Boiler—To learn more about wetback versus dryback, please refer to our wetback literature
18 19
Dimensions and Ratings
Rating Data
Dimensions are approximate, see detailed drawings for more specific dimensions.
100 125 150 175 200 250 300 350 400 500 600 700 800
A 68 68 76 76 76 86 86 94 94 104 104 114 114B 84 85 93 93 93 103 103 111 111 121 121 131 131C 150 176 169 188 207 207 235 240 263 264 300 282 311
Boiler Size, HP 100 125 150 175 200 250 300 350 400 500 600 700 800
Shell Diameter 62 62 70 70 70 70 78 88 88 98 98 108 108
Gross Output, BHP 100 125 150 175 200 250 300 350 400 500 600 700 800
Gross Output, MBH 3348 4184 5021 5858 6695 8369 10,043 11,716 13,390 16,738 20,085 23.433 26,780
Gross Ouput, Lbs./Hr. 3450 4312.5 5175 6037.5 6900 8625 10,350 12,075 13,800 17,250 20,700 24,150 27,600
Heating Surface, FS Sq. Ft.Firing Rate - Gas Gas - MBH Oil - GPH (140 MBTU/Gal.)
500
418429.9
625
523037.4
750
627744.8
875
732352.3
1000
836959.8
1250
10,46174.7
1500
12,55389.7
1750
14,645104.6
2000
16,738119.6
2500
20,922149.4
3000
25,106179.3
3500
29,2912092
4000
33,475239.1
Furnace Volume - Cu. Ft.Heat Releases Rate BTU/Hr./Cu. Ft.
39
107,618
46
112,686
58
108,471
66
111,565
73
114,003
93
112,617
108
116,193
133
110,011
149
112,491
177
118,528
206
121,670
219
133,559
246
136,013
Water Content Flooded - Gal. NWL - Gal.
875779
1,115995
1,1871,019
1,3911,187
1,6061,367
1,7501,487
2,1101,786
2,6612,266
3,0452,601
3,5362,818
4,2563,405
4,7473,932
5,4314,507
Shipping Weight - Lbs. 15/30 psi 125/150 psi
8,0008,900
9,94010,400
10,50011,700
12,00013,200
13,20014,400
15,60019,000
18,30021,600
22,30021,600
24,50027,600
28,90032,300
33,20037,100
38,30045,100
42.50050,000
�0 �1
Lancaster,PA17601Phone:888-791-�790www.burnhamcommercial.com
Series 4S Standard Equipment
Boiler:Four-pass full wetback firetube type, constructed in accordancewithrequirementsoftheASMECode,SectionIVfor�0PSIand1��PSIwateror1�PSIsteam;SectionIforhigher-pressuresteam.AllunitsareregisteredwiththeNationalBoard.
Turbulator baffles are not used in tubes. Separate rear tube sheetsallowsafeexpansionandcontraction.
Waterbacked rear turnaround promotes rapid internal circulationandreducesgastemperaturesattheentrancetothesecondpass,reducingtubeendstress.
Easy opening hinged, insulated front flue doors with light weightnon-refractoryclosureprovidefullaccesstoalltubes.Alightweight16-inchdiameterboltedrearaccessdoorwithobservationportprovidesaccesstotheboilerfurnace.Reartubeaccessisprovidedbyremovinglightweightgasketeddoors(s)installedontherearsmokebox.Noelaboratesealsareused.
Amanholeisfurnishedasstandard.Handholewashoutsareprovidedforeasyinspectionandcleaningofwatersidesurfaces.
Allsteamboilersareprovidedwithadrypantoensuredrysteam.Afeedwaterdiffuserisprovidedonhigh-pressureboilers.Allwaterboilersareequippedwithadiptubeatsupplyoutletanddiffuseratreturninlet.
The round-flanged vertical smoke outlet is equipped with a quadrantdamper.Allboilersareprovidedwithanenameledsteel jacket installed over 2 inches of fiberglass insulation andliftinglugs.
Theboilerismountedonaheavy-dutystructuralsteelbasewithextendedskidandburnerplatformforprotectionoftheburnerduringshipmentandrigging.
Standard Trim and Controls: Steam:1�7pumpcontrol/lowwatercut-offwithalarmcontacts—piped with quick opening blowoff valve. Gauge glasssetwithhand-operatedgaugeandtrycocks.Steampressure gauge—4 ½-inch dial on sizes 125 HP and smaller, 6-inchdialonlargersizes.L�0�Aoperatingpressuretrol,L�0�Cmanualresethighlimitpressuretrolandappropriatefiring rate control when required. Manual reset probe auxiliarylowwatercut-off.ASMEsideoutletsafetyvalve(s).
Water: 6�Mmanualresetlowwatercut-offwith�0PSIunits,150M low water cut-off with higher-pressure units—piped withquickopeningblowoffvalve.Combinationpressure/temperature gauge—3 ½ inch dial on 125 HP and smaller. Onlargersizesa6-inchcombinationpressure/altitudegaugeand�-inchdialtemperaturegauge.L�006AoperatingaquastatandL�006Emanualresethighlimitaquastatandappropriate firing rate control when required. ASMEsideoutletreliefvalve(s).
Burner Equipment:Burnermountsdirectlytothefrontheadoftheboilerwithnoelaborateseals.
Factorypackagedunitsavailablewithforceddraftburnersfor all commonly used fuels—gas, all grades of oil—No. 2 through No. 6—a combination gas/oil. Choice of pressure or air atomizing burners for No. 2 oil—air-atomizing burners for No. 2 oil—air atomizing on heavy oil. Gas burners are availableforeithernaturalorLPgas.
Refertoburnerdatasheetsforstandardburnerequipmentandoperatingsequence.
Accessories and Optional Equipment:Accessoriesandoptionalequipmentavailableatextracost,including,butnotlimitedto:• Alternateoradditionalwaterlevelcontrolsorlowwatercut-offs• Built-in tankless heater coils—low-pressure boilers only• Motorizedorpneumaticfeedvalves• Surfaceskimmersandblowoffvalves• Bottomblowdownvalvesanddrainvalves• Feedstopandcheckvalves• Sequencedraftcontrols• Lead/lagsequencingsystems• BoilerFeedsystems• LowNOxburners• Deaerators• Water Softeners• ChemicalFeedsystems• Blowdownsystems• SampleCoolers
�0 �1
Low NOx
�� ��
Lancaster,PA17601Phone:888-791-�790www.burnhamcommercial.com
America’s Boiler CompanyBurnhamCommercialhasbeendesigningandproducingboilersfor1�0+years,andwesellandservicethroughthelargestandmostexperiencednetworkofsalesrepresentativesinthecountry.Ourrepresentativesarecapableofprovidingtechnicalassistance,competentpricing,start-up,andlongtermservicing.It’snowonderweareAmerica’sBoilerCompany!
Low NOx NeedsBeingAmerica’sBoilerCompany,weknowwhatburnervendorsarelookingforinboilerdesignswhenit comes to reduced NOx combustion levels—large furnaces, high heat transfer, and low draft losses:
• Largefurnacesmeanlowvolumetricreleaserates.• High heat transfer for the most efficient boiler for yourapplication.• Lessburnermotorhorsepowersolessenergyis usedtooperateyourboiler.
CombiningthesethreefeaturescontributetoanideallowNOxpackageapplication.
Our firebox design provides the largest furnace possible in a firetube, and our scotchboilershavesomeofthelargestfurnacesavailable in our market—meaning we can meet all yourLowNOxneeds.
Important Design ConsiderationsOurprovendesignsusetheverylatestlowNOxtechniquesandstandards.Ourfurnace,theworkhorseoftheboiler,isdesignedforlowvolumetricheatrelease.Thelowerthereleaserates,the “easier” your boiler works. As your boiler works easier,lessstressisputuponthesteel,tubeends,refractory,etc.,resultinginalongerlastingboiler.Inadditiontolongevity,alargerboilermakesforeaseinfiring using any selected burner vendor.
Smallerfurnacesareextremelysusceptibletoerraticflame patterns. Deformed flame patterns cause unevenheatdistribution,unevenabsorptionandlocalizedhotspots,whichcanleadtooverheatingandoverstressing.OurselectionsgivethecustomerthechoiceofanyofthemajorlowNOxburnermanufacturers.Becausewehavesomanyprovenproductdesignselectionstochoosefrom,wecancustom fit any of our products to your boiler room. Burnham Commercial can offer you firebox, three-
pass or four-pass wetback scotch. We are theonlymanufacturerwhocanoffertheir packages complete with flue gas recirculationpiping,whennecessary.Thateliminatesextradesignresponsibilityand
field installation costs.
Proven Product ApplicationsUnlikeanyothermanufacturer,everyBurnham
CommercialLowNOxpackageisdesignapplicationapprovedbyourownEngineeringDepartmentandourburnervendors’EngineeringandApplicationsDesignGroups.Our1�0+yearssuccessfultrackrecordassuresyouthatourproducts,andourvendorselection,arethebestavailable.
Low NOx
�� ��
Series 4FForced Draft Firebox Boiler
�� ��
Series 4F Forced Draft Firebox Boiler
The Versatile BoilerTheBurnhamCommercial�Fforceddraftsteelfirebox boiler is a consistent sales leader in the heatingindustry.Itscompactandconstructivedesignsavesoninstallation,operation,andmaintenance.
4F Saves on InstallationThe 4F is a compact boiler that fits where other designsofsimilarcapacitycannot.Availablefor1�psisteamand�0or60psiwater*,the�Fcanserveperfectlyastheheartofalmostanysystem. As a factory assembled, forced-draft fired boiler,thispackagedunitdoesnotrequireatall,expensiveventstackorexcessivejobsitetimeandlabor.
4F Saves in Operation• The furnace surrounds the flame with highly efficient waterbacked primary heatabsorbingsurfaces.Thislarge combustion chamber is easy to fire andaccommodatesmanyforced-draft burners without flame impingement or other critical firing problems.
• Forced draft firing makes the 4F inherently more efficient than boilers using outmoded atmospheric burnersandgivesyouafeaturethatatmospheric unitscannotoffer:theoptionofburninggasoroil.
• A dual fired burner allows you to burn the more economicalfuelorthemostreadilyavailablefuel at the flip of a switch and affords you leverage in negotiatingfuelprices.
• The�Fisaneconomicalheatsource,whetherused singlyorinmultiples.Infact,�F’swithmodulating burners may be sequenced to operate in a step-fired systemmorecosteffectivelythanalargenumberof spacesaverboilerswhenongoingmaintenancecosts areconsidered.
4F Saves on Maintenance• Superiordesignmakesthe�Feasytocleanand maintain — requiring no special tools, materials, or skills.
• Opening the front flue door allows firetubes to be brushedoutquickly,unlikethewatertubesusedin someboilerswhichcanbevirtuallyimpossibleto clean.
• Elaborateorexpensiveproprietarysealsarenot requiredtore-closethedoorsaswithsomeboilers.
• Asawetbackboiler,thereisnodelicateorexpensive rearrefractorytomaintain.
*60-psiwaterboiler-consultfactoryforavailablesizes.
�� ��
Series 4F — Models 63 - 675
Dimensions (in Inches)
*3” and 4” are IPS female thread, 6” and larger are flanged. 150# bolt pattern. Specifications, Dimensions Data Subject to Change without Notice
4F Boiler Models 63 78 92 107 127 154 180 209 240 277 311 345 360 450 563 675
A - Boiler Width 31 31 31 31 36-3/8 36-3/8 36-3/8 36-3/8 45-1/8 45-1/8 45-1/8 45-1/8 52-3/4 52-3/4 56-1/2 56-1/2
B - Boiler Length 32 39 45-1/2 52-1/2 44-1/2 53 61 70 57 65 72-1/2 80 80-3/4 93-1/4 104-3/8 122-1/4
C - Boiler Height 55-1/4 55-1/4 55-1/4 55-1/4 63-5/8 63-5/8 63-5/8 63-5/8 70-5/8 70-5/8 70-5/8 70-5/8 82-7/16 82-7/16 85-3/16 85-3/16
D - Base Width 33-1/4 33-1/4 33-1/4 33-1/4 38-5/8 38-5/8 38-5/8 38-5/8 47-3/8 47-3/8 47-3/8 47-3/8 53-1/8 53-1/8 57 57
E - Base Length 47-1/2 54-1/2 65 72 64 72-1/2 80-1/2 92-1/2 79-1/2 87-1/2 95 102-1/2 107-1/2 124 135-1/8 153
F - Base Extension 15-1/2 15-1/2 19-1/2 19-1/2 19-1/2 19-1/2 19-1/2 22-1/2 22-1/2 22-1/2 22-1/2 22-1/2 26-3/4 30-3/4 30-3/4 30-3/4
G - Front Smoke Box Height 27-5/16 27-5/16 27-5/16 27-5/16 29-7/16 29-7/16 29-7/16 29-7/16 35-1/8 35-1/8 35-1/8 35-1/8 38-1/2 38-1/2 41-9/16 41-9/16
H - Front Smoke Box Depth 5-1/2 5-1/2 5-1/2 5-1/2 6-1/2 6-1/2 6-1/2 6-1/2 7-1/2 7-1/2 7-1/2 7-1/2 6-1/2 6-1/2 7-1/2 7-1/2
J - Supply Location 13 13 13 13 16 16 16 16 19 19 19 19 28 28 28 28
*K - Supply Size 4 4 4 4 6 6 6 6 6 8 8 8 8 10 10 10
*L - Return Size - Steam 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4
M - Return Location 6-1/2 6-1/2 6-1/2 6-1/2 7 7 7 7 7 7 7 7 7-3/8 7-3/8 7-3/8 7-3/8
N - Top Vent Collar Dia. 7 7 7 7 10 10 10 10 12 12 12 12 — — — —
P - Rear Vent Collar Dia. — — — — — — — — — — — — 14 14 18 18
Q - Rear Vent Collar Height 38 38 38 38 46-1/2 46-1/2 46-1/2 46-1/2 52 52 52 52 58-13/16 58-13/16 59-5/8 59-5/8
R - Smoke Box Depth 9 9 9 9 12 12 12 12 14 14 14 14 16 16 20 20
T - Top Vent Collar Height 42-1/2 42-1/2 42-1/2 42-1/2 52-1/2 52-1/2 52-1/2 52-1/2 59-1/4 59-1/4 59-1/4 59-1/4 66-5/16 66-5/16 69-1/8 69-1/8
U - Tube Pull Space 32 39 45-1/2 52-1/2 44-1/2 53 61 70 57 65 72-1/2 80 81-1/2 94 105 123
V - Supply Fitting Height 1-1/2 1-1/2 1-1/2 1-1/2 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-1/4 3-3/8 3-3/8 3-7/16 3-7/16
W - Normal Water Line Height 43-3/4 43-3/4 43-3/4 43-3/4 51-1/2 51-1/2 51-1/2 51-1/2 58 58 58 58 69-3/16 69-3/16 72 72
�6 �7
The Complete Boiler Room Supplier
Dimensions (in Inches)
*4” are IPS female thread, 6” and larger are flanged. 150# bolt pattern. Specifications, Dimensions Data Subject to Change without Notice
4F Boiler Models 827 993 1157 1323 1654 1985 2315 2645 3075
A - Boiler Width 64 64 70 70 76 82 82 82 96
B - Boiler Length 106-1/4 129 116-1/2 136 130-1/2 128 148 163 163
C - Boiler Height 95-3/16 95-3/16 106-3/4 106-3/4 122-3/8 142-3/8 142-3/8 142-3/8 151-1/2
D - Base Width 61 61 67 67 73 79 79 79 93
E - Base Length 138-1/4 161 158-1/2 178 172-1/2 170 190 205 213
F - Base Extension 30 30 40 40 40 40 40 40 48
G - Front Smoke Box Height 29-1/8 29-1/8 33-11/16 33-11/16 41-7/8 55-1/8 55-1/8 55-1/8 69-3/4
H - Front Smoke Box Depth 12-3/4 12-3/4 13-1/2 13-1/2 14-1/2 15-1/2 15-1/2 15-1/2 16-1/2
J - Supply Location 22 22 22 22 22 22 22 22 68
*K - Supply Size 8 8 8 8 10 12 12 12 12
*L - Return Size - Steam 4 4 4 6 6 6 6 6 6
Return Size - Water 6 6 6 8 8 8 8 8 8
M - Return Location 10-1/4 10-1/4 11-1/8 11-1/8 11-1/8 11-1/2 11-1/2 11-1/2 10-1/2
N - Rear Smoke Box Depth 19-3/8 19-3/8 19-3/8 19-3/8 21-3/8 23-3/8 23-3/8 23-3/8 23-3/8
P - Rear Vent Collar Dia. 20 20 22 22 24 28 28 28 30
Q - Rear Vent Collar Height 66-3/16 66-3/16 76-13/16 76-13/16 90-11/16 106-5/16 106-5/16 106-5/16 110-1/2
R - Top Vent Collar Width 22 22 26 26 28 34 34 34 44
S - Top Vent Collar Depth 16 16 16 16 18 20 20 20 20
T - Top Vent Collar Height 76-1/8 76-1/8 87-3/ 87-3/4 102-5/8 120-1/4 120-1/4 120-1/4 123-15/16
U - Tube Pull Space 108 131 118-1/2 138 132-1/2 130 150 165 165
W - Normal Water Line Height 78-1/4 78-1/4 89-3/4 89-3/4 104-1/2 118-1/2 118-1/2 118-1/2 126
©�008BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
Series 4F — Models 827 - 3075
�6 �7
The Complete Boiler Room Supplier
4F - 40 Boiler Models 63 78 92 107 127 154 180 209 240 277 311 345 360A 450A 563A 675A
Gross Output MBH BHP Lbs. Stm/Hr
52715.7543
65319.5673
77023.0794
89626.8923
1,06331.8
1,096
1,28938.5
1,328
1,50645.0
1,553
1,74952.2
1,803
2,00960.9
2,070
2,31869.2
2,389
2,60377.8
2,683
2,88786.2
2,975
3,01590.1
3,108
3,770112.63,885
4,720141.04,864
5,657169.05,832
Net Rating - Steam MBH Sq. Ft.
4091,705
5072,115
5982,490
6952,895
8253,445
1,0004,165
1,1694,870
1,3575,655
1,5596,495
1,7997,495
2,0208,415
2,2409,335
2,3409,750
2,92612,190
3,66315,265
4,39018,295
Net Rating - Water MBH 458 568 670 780 925 1,121 1,310 1,522 1,748 2,017 2,265 2,512 2,623 3,280 4,106 4,922
Firing Rate - Gas MBHFiring Rate - Light Oil GPH* Heavy Oil GPH*
6594.7—
8165.8—
9636.9—
11208.0—
13299.5—
1,61111.5—
1,88313.5—
2,18615.6—
2,51117.9—
2,89820.7—
3,25423.2—
3,60925.8—
3,76926.925.1
4,71333.731.4
5,90042.139.3
7,07150.547.1
Heating Surface Sq. Ft. Fireside Waterside
5963
7378
8692
101107
120127
145154
168180
194209
224240
257277
289311
320345
360398
450497
563622
675746
Furnace Volume Cu. Ft. 8.8 10.7 12.6 14.6 18.3 21.9 25.3 29.1 34.7 39.7 44.4 49.1 58.9 68.0 89.3 104.7
Heat Release MBH/Cu. Ft. 74.9 76.3 76.4 76.7 72.6 73.6 74.4 75.1 72.4 73.0 73.3 73.5 64.0 69.3 66.1 67.5
Water Content Gal. Steam Water
6590
81112
94132
110153
133168
145196
172232
198268
214288
245329
274369
302408
470569
551666
663881
788951
Approx. Dry Weight Lbs. 1,700 1,900 2,100 2,600 2,700 3,100 3,300 3,600 4,200 4,400 5,300 5,600 6,710 8,700 9,300 10,400
Approx. Full Weight Lbs. Steam Water
2,2402,450
2,5702,835
3,0903,195
3,5103,870
3,8004,095
4,3004,735
4,7305,235
5,2505,830
5,9806,595
6,4357,140
7,5758,365
8,1108,995
10,61511,495
13,29014,255
14,82515,975
16,97018,325
Ratings and Data
Ratings based on 4 square feet of heating surface per boiler horsepower* Light oil—140,000 BTU/GAL ** Heavy oil,—150,000 BTU/GAL
Series 4F-40Forced Draft Firebox Generator
Coil Number*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
Rated Capacity — Gallons Heated40° to 140°F Boiler Water Temp.
108°FGPM
180°FGPH
212°FGPH
INA-210 All sizes 3.5 210 325
INA-300 All except 4F-63 5.0 300 466
INA-360 All sizes 6.0 360 560
INA-450 All except 4F-63 7.5 450 700INA-600 4F-154 and larger, also 4F-107 10.0 600 933INA-750 4F-154 and larger, also 4F-107 12.5 750 1,165INA-900 4F-92 and larger 15.0 900 1,400INA-1125 4F-154 and larger 18.7 1,125 1,750INA-1350 4F-277 and larger, also 4F-209 22.5 1,350 2,100INA-1500 4F-345 and larger 25.0 1,500 2,330
Instantaneous hot Water heating Coils
*Twocoilsofanysizeorcombinationofsizesmaybeinstalledin�F-11�7andlarger
�8 �9
Series 4F-40 Standard Equipment
Boiler:TheboilersareathreepassdesignconstructedandstampedinaccordancewithASMESectionIVoftheASMECodefor1�psigsteamor�0psigwateronanysize boiler or 60 psig water on sizes 4FW63 through 4FW993. They are the sealed forced draft firing design with skid base and floor insulation. The flue outlet is atopoutletonsizes�F6�through�F���andarearoutletonsizes�F��0andlarger.Optionaloutletsareavailableonallsizes.Theboilercomescompletewithagas tight front flue cleanout door, rear observation port onsizes�F6�through�F���,orrearaccessdoorandobservationportonsizes�F��0andlargerandliftinglugsonsizes�F1�7andlarger.Optionalaccessdoorsandliftinglugsareavailableforallsizes.
Jacket: Rectangular type 1” fiberglass insulated jacket on sizes 4F63 through 4F345, 2” fiberglass insulated rectangular jacket on sizes 4F450 through 4F675 and 2” fiberglass wraparoundjacketonsizes�F8�7andlarger.
Steam Trim:Thefollowingtrimisshopmountedandwired:MM1�7combination pump control and LWCO with alarm contactsandquickopeningblowoffvalves,probetype manual reset auxiliary LWCO, L404A operating pressuretrol,L�0�Cmanualresethighlimitpressuretroland appropriate firing rate control when required.
The following trim is shipped loose for field mounting: 3 ½” steam pressure gauge (on models 4FL63 through 4F675), 6” steam pressure gauge (on models 4F827 andlarger),ASMEsideoutletsafetyvalve(s)andgaugeglassset.
Water Trim:Thefollowingtrimsareshopmountedandwired:probe type LWCO (on 30 psig models 4FW63 through 4FW675) or MM63M manual reset LWCO with quick opening blowoff valve (on 30 psig models 4FW827 and larger) or probe type LWCO (on 60 psi models 4FW63 through 4FW675) or MM150M manual reset LWCO withquickopeningblowoffvalve(onall60psiboilerson models 4FW827 and larger) or L4006A operating aquastat,L�006Emanualresethighlimitaquastatandappropriate firing rate control when required.
The following trims are shipped loose for field mounting: 3 ½” theraltimeter (on models 4FW63 through 4FW675) or 5” thermometer and 6” pressure/altitude gauge (on models 4FW827 and larger) and loose ASME side outlet reliefvalve(s).
Burner: Asselectedforthefueltobeburned,mountedandwired.Refertoburnerdatasheetsfordetailsofburnerequipment.Burnersavailableforgas,No.�oil,No.�oil,No.�oil,No.6oil,combinationgas/No.�oil,gas/No.�oil,gas/No.�oil,gas/No.6oil,combinationgas/No.�oil,gas/No.�oil,gas/No.�oil,andgas/No.6oil.
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
�8 �9
4F - 45 Boiler Models 63 78 92 107 127 154 180 209 240 277 311 345 360A 450A 563A 675A
Gross Output MBH BHP Lbs. Stm/Hr
46914
483
57917.3597
68320.4704
79723.8821
94428.2973
1,14534.2
1,180
1,33940.0
1,380
1,55346.4
1,601
1,78453.3
1,839
2,06261.6
2,125
2,31369.1
2,384
2,56876.7
2,646
2,67880.0
2,760
3,348100.03,450
4,251127.04,380
5,055151.05,210
Net Rating - Steam MBH Sq. Ft.
3641,515
4491,870
5302,210
6182,575
7333,055
8893,705
1,0394,340
1,2055,020
1,3845,765
1,6006,665
1,7957,480
1,9938,305
2,0788,660
2,59810,825
3,29913,745
3,92316,345
Net Rating - Water MBH 403 504 594 693 821 996 1,165 1,351 1,552 1,794 2,012 2,234 2,350 2,913 3,698 4,398
Firing Rate - Gas MBHFiring Rate - Light Oil GPH Heavy Oil GPH
5864.2—
7245.2—
8546.1—
9967.1—
1,1808.4—
1,43110.2—
1,67412.0—
1,94113.9—
2,23015.9—
2,57818.4—
2,89120.7—
3,21022.9—
3,34823.922.3
4,18529.927.9
5,31438.035.4
6,31945.142.1
Heating Surface Sq. Ft. Fireside Waterside
5963
7378
8692
101107
120127
145154
168180
194209
224240
257277
289311
320345
360398
450497
563622
675746
Furnace Volume Cu. Ft. 8.8 10.7 12.6 14.6 18.3 21.9 25.3 29.1 34.7 39.7 44.4 49.1 58.9 68.0 89.3 104.7
Heat Release MBH/Cu. Ft. 66.6 67.7 67.8 68.2 64.5 65.3 66.2 66.7 64.3 64.9 65.1 65.4 56.8 61.5 59.5 60.4
Water Content Gal. Steam Water
6590
81112
94132
110153
133168
145196
172232
198268
214288
245329
274369
302408
470569
551666
663801
788951
Approx. Dry Weight Lbs. 1,700 1,900 2,100 2,600 2,700 3,100 3,300 3,600 4,200 4,600 5,300 5,600 6,900 8,700 9,300 10,400
Approx. Full Weight Lbs. Steam Water
2,2402,450
2,5702,835
3,0903,195
3,5103,870
3,8004,095
4,3004,735
4,7305,235
5,2505,830
5,9806,595
6,4357,140
7,5758,365
8,1108,995
10,61511,495
13,29014,255
14,82515,975
16,97018,325
Ratings and Data
Ratings based on 4.5 square feet of heating surface per boiler horsepower
Series 4F-45Forced Draft Firebox Generator
4F - 45 Boiler Models 360A-3 450-A 563A-3 675A-3 827 993 1157 1323 1654 1985 2315
Gross Output MBH BHP Lbs. Stm/Hr
2,95388.2
3,044
3,445102.93,550
4,188125.14,316
4,924147.15,075
6,126183.06,315
7,388220.77,617
8,606257.18,872
9,842294.0
10,146
12,302367.5
12,682
14,766441.1
15,223
17,220514.4
17,753
Net Rating - Steam MBH Sq. Ft.
2,2929,550
2,67311,140
3,25013,540
3,82115,920
4,75419,810
5,73323,890
6,88528,690
7,87332,805
9,54639,775
11,45847,740
13,36355,680
Net Rating - Water MBH 2,569 2,997 3,644 4,284 5,330 6,428 7,487 8,563 10,703 12,846 14,981
Firing Rate - Gas MBHFiring Rate - Light Oil GPH Heavy Oil GPH
3,69126.424.6
4,30630.828.7
5,23537.434.9
6,15544.041.0
7,65854.751.0
9,23566.061.6
10,75876.871.7
12,30387.982.0
15,378110.0102.7
18,458132.0123.2
21,525154.0143.7
Heating Surface Sq. Ft. Fireside Waterside
397429
463500
563608
662715
827893
9931,072
1,1571,250
1,3231,429
1,6541,786
1,9852,143
2,3152,500
Furnace Volume Cu. Ft. 58.9 68.0 89.3 104.7 115.6 139.2 160.7 186.5 234.0 301.6 348.6
Heat Release MBH/Cu. Ft. 62.7 63.3 58.6 58.8 66.2 66.3 66.9 66.0 65.7 61.2 61.7
Water Content Gal. Steam Water
421519
492676
602740
712875
7611,003
9251,220
1,0501,330
1,2271,554
1,4431,826
1,7202,147
1,9792,473
Approx. Dry Weight Lbs. 6,900 8,800 9,300 12,400 13,200 14,800 18,300 19,200 23,000 28,000 34,500Approx. Full Weight Lbs. Steam Water
10,40511,225
12,90014,430
14,31515,465
16,93018,290
18,97020,325
22,50024,950
27,04028,675
29,41532,140
35,01038,200
42,32045,870
50,97055,085
�0 �1
Series 4F Standard Equipment
Boiler:TheboilersareathreepassdesignconstructedandstampedinaccordancewithASMESectionIVoftheASMECodefor1�psigsteamor�0psigwateronanysize boiler or 60 psig water on sizes 4FW63 through 4FW993. They are the sealed forced draft firing design with skid base and floor insulation. The flue outlet is atopoutletonsizes�F6�through�F���andarearoutletonsizes�F��0andlarger.Optionaloutletsareavailableonallsizes.Theboilercomescompletewithagas tight front flue cleanout door, rear observation port onsizes�F6�through�F���,orrearaccessdoorandobservationportonsizes�F��0andlargerandliftinglugsonsizes�F1�7andlarger.Optionalaccessdoorsandliftinglugsareavailableforallsizes.
Jacket: Rectangular type 1” fiberglass insulated jacket on sizes 4F63 through 4F345, 2” fiberglass insulated rectangular jacket on sizes 4F450 through 4F675 and 2” fiberglass wraparoundjacketonsizes�F8�7andlarger.
Steam Trim:Thefollowingtrimisshopmountedandwired:MM1�7combination pump control and LWCO with alarm contactsandquickopeningblowoffvalves,probetype manual reset auxiliary LWCO, L404A operating pressuretrol,L�0�Cmanualresethighlimitpressuretroland appropriate firing rate control when required.
The following trim is shipped loose for field mounting: 3 ½” steam pressure gauge (on models 4FL63 through
4F675), 6” steam pressure gauge (on models 4F827 andlarger),ASMEsideoutletsafetyvalve(s)andgaugeglassset.
Water Trim:Thefollowingtrimsareshopmountedandwired:probe type LWCO (on 30 psig models 4FW63 through 4FW675) or MM63M manual reset LWCO with quick opening blowoff valve (on 30 psig models 4FW827 and larger) or probe type LWCO (on 60 psi models 4FW63 through 4FW675) or MM150M manual reset LWCO withquickopeningblowoffvalve(onall60psiboilerson models 4FW827 and larger) or L4006A operating aquastat,L�006Emanualresethighlimitaquastatandappropriate firing rate control when required.
The following trims are shipped loose for field mounting: 3 ½” theraltimeter (on models 4FW63 through 4FW675) or 5” thermometer and 6” pressure/altitude gauge (on models 4FW827 and larger) and loose ASME side outlet reliefvalve(s).
Burner: Asselectedforthefueltobeburned,mountedandwired.Refertoburnerdatasheetsfordetailsofburnerequipment.Burnersavailableforgas,No.�oil,No.�oil,No.�oil,No.6oil,combinationgas/No.�oil,gas/No.�oil,gas/No.�oil,gas/No.6oil,combinationgas/No.�oil,gas/No.�oil,gas/No.�oil,andgas/No.6oil.
Coil Number*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
Rated Capacity — Gallons Heated40° to 140°F Boiler Water Temp.
108°FGPM
180°FGPH
212°FGPH
INA-210 All sizes 3.5 210 325
INA-300 All except 4F-63 5.0 300 466
INA-360 All sizes 6.0 360 560
INA-450 All except 4F-63 7.5 450 700
INA-600 4F-154 and larger, also 4F-107 10.0 600 933
INA-750 4F-154 and larger, also 4F-107 12.5 750 1,165
INA-900 4F-92 and larger 15.0 900 1,400
INA-1125 4F-154 and larger 18.7 1,125 1,750
INA-1350 4F-277 and larger, also 4F-209 22.5 1,350 2,100
INA-1500 4F-345 and larger 25.0 1,500 2,330
Instantaneous hot Water heating Coils
*Twocoilsofanysizeorcombinationofsizesmaybeinstalledin�F-11�7andlarger
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
�0 �1
*Twocoilsofanysizeorcombinationofsizesmaybeinstalledin�F-11�7andlarger
4F - 50 Boiler Models 63 78 92 107 127 154 180 209 240 277 311 345 360A 450A 563A 675A
Gross Output MBH BHP Lbs. Stm/Hr
42212.6435
52215.6538
61618.4635
71621.4738
85025.4876
1,03130.8
1,063
1,20536.0
1,242
1,40041.8
1,442
1,60748.0
1,656
1,85555.4
1,911
2,08262.2
2,146
2,31069.0
2,381
2,41072.0
2,484
3,01590.0
3,108
3,770112.63,885
4,520135.04,660
Net Rating - Steam MBH Sq. Ft.
3271,365
4051,690
4781,990
5562,315
6602,750
8003,335
9353,895
1,0864,525
1,2475,195
1,4395,995
1,6166,735
1,7937,470
1,8707,790
2,3409,750
2,92612,190
3,50814,615
Net Rating - Water MBH 367 454 536 623 740 897 1,048 1,218 1,398 1,614 1,811 2,010 2,097 2,623 3,280 3,932
Firing Rate - Gas MBHFiring Rate - Light Oil GPH Heavy Oil GPH
5283.8—
6534.7—
7705.5—
8956.4—
1,0637.6—
1,2899.2—
1,50610.8—
1,75012.5—
2,00914.4—
2,31916.6—
2,60318.6—
2,88820.6—
3,01321.520.1
3,76927.025.2
4,71333.631.4
5,65040.437.7
Heating Surface Sq. Ft. Fireside Waterside
5963
7378
8692
101107
120127
145154
168180
194209
224240
257277
289311
320345
360398
450497
563622
675746
Furnace Volume Cu. Ft. 8.8 10.7 12.6 14.6 18.3 21.9 25.3 29.1 34.7 39.7 44.4 49.1 58.9 68.0 89.3 104.7
Heat Release MBH/Cu. Ft. 60.0 61.0 61.1 61.3 58.1 58.8 59.5 60.1 57.9 58.4 58.6 58.8 51.2 55.4 52.8 53.9
Water Content Gal. Steam Water
6590
81112
94132
110153
133168
145196
172232
198268
214288
245329
274369
302408
470569
537666
683801
788951
Approx. Dry Weight Lbs. 1,700 1,900 2,100 2,600 2,700 3,100 3,300 3,600 4,200 4,400 5,300 5,600 6,700 8,700 9,300 10,400
Approx. Full Weight Lbs. Steam Water
2,2402,450
2,5702,835
3,0903,195
3,5103,870
3,8004,095
4,3004,735
4,7305,235
5,2505,830
5,9806,595
6,4357,140
7,5758,365
8,1108,995
10,61511,495
13,29014,255
14,82515,975
16,97018,325
Ratings and Data
Ratings based on 5 square feet of heating surface per boiler horsepower
Series 4F-50Forced Draft Firebox Generator
4F - 50 Boiler Models 360A-3 450-A 563A-3 675A-3 827 993 1157 1323 1654 1985 2315 2645 3075
Gross Output MBH BHP Lbs. Stm/Hr
2,65879.4
2,739
3,10092.6
3,195
3,769112.63,885
4,432132.44,568
5,537165.05,706
6,648199.06,852
7,746231.07,983
8,857265.09,129
11,074331.0
11,413
13,290397.0
13,697
15,499463.0015,974
17,708529.0
18,252
20,587615.0
21,217
Net Rating - Steam MBH Sq. Ft.
2,0638,596
2,40610,025
2,92512,188
3,43914,329
4,29917,910
5,16121,505
6,01425,060
6,87728,655
8,59835,825
10,31842,995
12,03350,140
13,74857,285
15,97666,525
Net Rating - Water MBH 2,312 2,697 3,279 3,856 4,817 5,784 6,739 7,706 9,634 11,562 13,484 15,406 17,911
Firing Rate - Gas MBHFiring Rate - Light Oil GPH Heavy Oil GPH
3,32323.722.2
3,87527.725.8
4,71133.731.4
5,54039.636.9
6,92149.946.6
8,31060.056.0
9,68370.065.3
11,07180.074.7
13,84399.092.4
16,613119.0110.7
19,374139.0129.3
22,135158.0148.0
25,734184.0172.0
Heating Surface Sq. Ft. Fireside Waterside
397429
463500
563608
662715
827893
9931,072
1,1571,250
1,3231,429
1,6541,786
1,9852,143
2,3152,500
2,6452,857
3,0753,321
Furnace Volume Cu. Ft. 58.9 68.0 89.3 104.7 115.6 139.2 160.7 186.5 234.0 301.6 348.6 383.8 505.6
Heat Release MBH/Cu. Ft. 56.4 57.0 52.8 52.9 59.9 59.7 60.3 59.4 59.2 55.1 55.6 63.5 50.9
Water Content Gal. Steam Water
421519
492676
602740
712875
7611,003
9251,220
1,0501,330
1,2271,554
1,4431,826
1,7202,147
1,9792,473
2,1732,718
2,8143,665
Approx. Dry Weight Lbs. 6,900 8,800 11,000 12,400 14,800 18,300 19,200 19,800 23,000 28,000 34,500 38,200 49,000Approx. Full Weight Lbs. Steam Water
10,45011,225
12,90014,430
14,31515,465
16,93018,290
18,97020,325
22,50024,950
27,04029,375
29,41532,140
35,01038,200
42,32045,870
50,97055,085
56,29060,820
72,43079,510
�� ��
Series 4F Standard EquipmentBoiler:TheboilersareathreepassdesignconstructedandstampedinaccordancewithASMESectionIVoftheASMECodefor1�psigsteamor�0psigwateronanysize boiler or 60 psig water on sizes 4FW63 through 4FW993. They are the sealed forced draft firing design with skid base and floor insulation. The flue outlet is atopoutletonsizes�F6�through�F���andarearoutletonsizes�F��0andlarger.Optionaloutletsareavailableonallsizes.Theboilercomescompletewithagas tight front flue cleanout door, rear observation port onsizes�F6�through�F���,orrearaccessdoorandobservationportonsizes�F��0andlargerandliftinglugsonsizes�F1�7andlarger.Optionalaccessdoorsandliftinglugsareavailableforallsizes.
Jacket: Rectangular type 1” fiberglass insulated jacket on sizes 4F63 through 4F345, 2” fiberglass insulated rectangular jacket on sizes 4F450 through 4F675 and 2” fiberglass wraparoundjacketonsizes�F8�7andlarger.
Steam Trim:Thefollowingtrimisshopmountedandwired:MM1�7combination pump control and LWCO with alarm contactsandquickopeningblowoffvalves,probetype manual reset auxiliary LWCO, L404A operating pressuretrol,L�0�Cmanualresethighlimitpressuretroland appropriate firing rate control when required. The following trim is shipped loose for field mounting:
3 ½” steam pressure gauge (on models 4FL63 through 4F675), 6” steam pressure gauge (on models 4F827 andlarger),ASMEsideoutletsafetyvalve(s)andgaugeglassset.
Water Trim:Thefollowingtrimsareshopmountedandwired:probe type LWCO (on 30 psig models 4FW63 through 4FW675) or MM63M manual reset LWCO with quick opening blowoff valve (on 30 psig models 4FW827 and larger) or probe type LWCO (on 60 psi models 4FW63 through 4FW675) or MM150M manual reset LWCO withquickopeningblowoffvalve(onall60psiboilerson models 4FW827 and larger) or L4006A operating aquastat,L�006Emanualresethighlimitaquastatandappropriate firing rate control when required.
The following trims are shipped loose for field mounting: 3 ½” theraltimeter (on models 4FW63 through 4FW675) or 5” thermometer and 6” pressure/altitude gauge (on models 4FW827 and larger) and loose ASME side outlet reliefvalve(s).
Burner: Asselectedforthefueltobeburned,mountedandwired.Refertoburnerdatasheetsfordetailsofburnerequipment.Burnersavailableforgas,No.�oil,No.�oil,No.�oil,No.6oil,combinationgas/No.�oil,gas/No.�oil,gas/No.�oil,gas/No.6oil,combinationgas/No.�oil,gas/No.�oil,gas/No.�oil,andgas/No.6oil.
Coil Number*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
Rated Capacity — Gallons Heated40° to 140°F Boiler Water Temp.
108°FGPM
180°FGPH
212°FGPH
INA-210 All sizes 3.5 210 325
INA-300 All except 4F-63 5.0 300 466
INA-360 All sizes 6.0 360 560
INA-450 All except 4F-63 7.5 450 700
INA-600 4F-154 and larger, also 4F-107 10.0 600 933
INA-750 4F-154 and larger, also 4F-107 12.5 750 1,165
INA-900 4F-92 and larger 15.0 900 1,400
INA-1125 4F-154 and larger 18.7 1,125 1,750
INA-1350 4F-277 and larger, also 4F-209 22.5 1,350 2,100
INA-1500 4F-345 and larger 25.0 1,500 2,330
Instantaneous hot Water heating Coils
*Twocoilsofanysizeorcombinationofsizesmaybeinstalledin�F-11�7andlarger
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
�� ��
• Three pass full wetback, packaged firetube type, constructedinaccordancewithrequirementsofthe ASMEBoilerandPressureVesselCode,SectionIV for1�-psisteam.Allunitsareregisteredwiththe NationalBoard.
•Sealed forced draft firing design.
•Boiler tubes are expanded and flared. Separate secondandthirdpassreartubesheetsallowsafe expansionandcontraction.
•Waterback rear turnaround promotes rapid internal circulationandreducesgastemperaturesatentrance tosecondpass,reducingtubeandstress.
•Easy opening, insulated front flue doors with bolted closureprovidefullaccesstoalltubes.A16-inch diameterboltedrearaccessdoorwithobservationport providesaccesstotheboilerfurnace.
•Handholewashoutsareprovidedforeasyinspection andcleaningofwatersidesurfaces.
•Allsteamboilersprovidedwithadrypantoensure drysteam.
Series 4F Forced Draft Firetube Boiler“Ohio Special”
Series 4F Ohio Special Boiler Features:
•Theroundhorizontalsmokeoutletisstandard.Vertical smokeboxoutletandquadrantdampersareoptional.
•Allboilersareprovidedwithanenameledsteeljacket over 2 inches of fiberglass insulation and lifting lugs.
•Theboilerismountedonaheavy-dutysteelbasewith extendedskidandburnerplatformforprotectionofthe burnerduringshipmentandrigging.
�� ��
• 1�7combinationpumpcontrol
• LWCO with alarm contacts
• quickopeningblowoffvalves
• Gaugeglassset
4F360-OS Boiler Model 4F360-OS
Gross Output MBH BHP Lb. Stm./Hr.
3,01590.1
3,108
Net Rating - Steam MBH Sq. Ft.
2,3409,750
Net Rating - Water MBH 2,623
Firing Rate Gas - MBH Oil - GPH Light Oil (140,000 BTU/Gal.) Heavy Oil (150,000 BTU/Gal.)
3,769—
26.925.1
Heating Surface - Sq. Ft. Fireside Waterside
358396
Furnace Volume Cu. Ft. 58.9
Heat Release MBH/Cu. Ft. 64
Water Content - Gal. Steam Flooded
470569
Approx. Dry Weight - Lbs. 6,710
Approx. Full Weight - Lbs. Steam Flooded
10,61511,495
Ratings and Data4F360-OS Boiler Model
A - Boiler Width 52-1/4
B - Boiler Length 80-3/4
C - Boiler Height 82-3/8
D - Base Width 53-1/8
E - Base Length 107-1/2
F - Base Extension 26-3/4
G - Front Smoke Box Height 36-3/4
H - Front Smoke Box Depth 6-1/2
J - Supply Location 26
K - Supply Size - Flanged 8
L - Return Size - Threaded 4
M - Return Location 7-3/8
N - Smoke Box Depth - Rear Vent 8
P - Vent Collar Diameter 14
Q - Rear Vent Collar Height 58-3/4
R - Smoke Box Depth - Top Vent 16
T - Top Vent Collar Height 66-1/4
U - Tube Pull Space 81
V - Supply Fitting Height 3-1/2
W - Normal Water Line Height 69-1/4
Dimensions (in Inches)
Standard Trim and Controls• Steam pressure gauge — 3 ½
• L�0�operatingpressuretrol
• L�0�Cmanualresethighlimitpressuretroland appropriate firing rate control when required. Manual reset probe auxiliary LWCO.
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
�� ��
Series 4NNatural Draft Firebox Boiler
�6 �7
Series 4N Natural Draft Firebox Boiler
Ratings for Oil, Gas or Stoker Firing4N Boiler Models 63 78 92 107 127 154 180 209 240 277 311 345 397
Gross Output MBH BHP Lbs.Stm./Hr.
2457.3253
2998.9308
34810.4359
40312.0415
52215.6538
62618.7645
72421.6746
87026.0897
99629.8
1,027
1,14234.1
1,177
1,27838.2
1,317
1,41442.2
1,457
21,6065
2,226
Net Rating Steam MBH Sq. Ft.
190790
232970
2701,125
3131,305
4051,690
4862,025
5622,340
6752,815
7733,220
8873,695
9924,235
1,0984,570
1,6676,990
Net Rating Water MBH 213 260 303 351 454 545 630 757 867 994 1,112 1,230 1,878
Firing Rate - Gas MBH Light Oil (140,000 BTU/Gal.) Heavy Oil (150,000 BTU/Gal.)
3062.2—
3742.7—
4353.1—
5043.6—
6534.7—
7835.6—
9056.5—
1,0887.8—
1,2458.9—
1,42810.2—
1,59811.4—
1,76812.6—
2,70019.318.0
Coal (Stoker) Lbs./Hr. 25 31 36 41 54 64 74 89 102 117 131 145 222
Heating Surface Sq. Ft. Fireside Waterside
4547
5557
6467
7477
96100
115120
133139
153160
183193
210221
235247
260274
397429
Furnace Volume Cu. Ft. * 8.8 10.7 12.6 14.6 18.3 21.9 25.3 29.1 34.7 39.7 44.4 49.1 58.9
Heat Release MBH/Cu. Ft. 34.8 35.0 34.5 34.5 35.7 35.8 35.8 37.4 35.9 36.0 36.0 36.0 45.8
Water Content Gals. Steam Water
6792
83114
96134
113156
133168
149200
171231
197267
209283
239323
267362
295401
421520
Approx. Dry Weight Lbs. 1,500 1,700 1,900 2,200 2,500 2,800 3,100 3,400 3,900 4,300 4,900 5,200 6,500
Approx. Weight Full Lbs. Steam Water
2,0552,265
2,3902,650
2,7003,020
3,1403,500
3,6053,895
4,0404,465
4,5255,025
5,0405,620
5,6356,250
6,2856,985
7,1207,910
7,6508,535
10,00510,830
4N Boiler Models 463 563 662 827 993 1157 1323 1654 1985 2315 2645 3075
Gross Output MBH BHP Lbs.Stm./Hr.
2,51975
2,596
3,06392
3,156
3,601108
3,712
4,499134
4,636
5,402161
5,567
6,294188
6,484
7,197215
7,417
8,998269
9,273
10,798323
11,129
12,594376
12,979
14,389430
14,829
16,738500
17,250
Net Rating Steam MBH Sq. Ft.
1,9568,150
2,3789,910
2,79611,650
3,49314,555
4,19417,475
4,88720,360
5,58823,280
6,98629,110
8,38434,930
9,77840,740
11,17246,550
12,98954,120
Net Rating Water MBH 2,190 2,663 3,131 3,912 4,697 5,473 6,258 7,824 9,390 10,951 12,512 14,554
Firing Rate - Gas MBH Light Oil (140,000 BTU/Gal.) Heavy Oil (150,000 BTU/Gal.)
3,14922.521.0
3,82927.325.5
4,50132.130.0
5,62440.237.5
6,75348.245.0
7,86856.252.5
8,99664.360.0
11,24880.375.0
13,49896.490.0
15,743112.5104.9
17,986128.5120.0
20,923149.5139.5
Coal (Stoker) Lbs./Hr. 258 314 369 461 554 646 738 923 1,108 1,292 1,476 1,717
Heating Surface Sq. Ft. Fireside Waterside
463500
563608
662715
827893
9931,072
1,1571,250
1,3231,429
1,6541,786
1,9852,143
2,3152,500
2,6452,857
3,0753,321
Furnace Volume Cu. Ft. * 68.0 89.3 104.7 115.6 139.2 160.7 186.5 234.0 301.6 348.6 383.8 505.6
Heat Release MBH/Cu. Ft. 46.3 42.9 43.0 48.7 48.5 49.0 48.2 48.1 44.8 45.2 46.9 41.4
Water Content Gals. Steam Water
492607
602740
712875
7611,003
9251,220
1,0501,330
1,2271,554
1,4431,826
1,7202,147
1,9792,473
2,1732,718
2,8143,665
Approx. Dry Weight Lbs. 8,000 8,500 10,100 12,300 13,300 16,600 18,600 21,700 26,500 32,800 37,500 48,200
Approx. Weight Full Lbs. Steam Water
12,10013,055
13,51514,665
16,03017,390
18,63020,645
21,00523,455
25,34027,675
28,81531,540
33,71036,900
40,81544,370
49,27053,385
55,59060,120
71,63078,710
All models have 3 inch diameter tubes—except 3075 has 2-1/2 inch tubes*=deosnotincludebasevolume
�6 �7
Series 4N — Models 63 - 662
Dimensions (Inches)
*Oil, Gas, Stoker Only - See note below rating table for hand-fired boilers.**4” is IPS female thread, 6” and larger are flangedSpecifications, dimensions data subject to change without notice.
4N Boiler Models 63 78 92 107 127 154 180 209 240 277 311 345 397 463 563 662
A - Boiler Width 30-1/4 30-1/4 30-1/4 30-1/4 35-7/8 35-7/8 35-7/8 35-7/8 44-5/8 44-5/8 44-5/8 44-5/8 52-1/4 52-1/4 56 56
B - Boiler Length 30 37 43-1/2 50-1/2 42-1/2 51 59 68 55 63 70-1/2 78 76-3/4 89-1/4 100-3/8 118-1/4
C - Boiler Height 52-1/8 52-1/8 52-1/8 52-1/8 60-1/2 60-1/2 60-1/2 60-1/2 67-1/2 67-1/2 67-1/2 67-1/2 79-1/4 79-1/4 82 82
D - Base Width 29-3/4 29-3/4 29-3/4 29-3/4 35-1/8 35-1/8 35-1/8 35-1/8 43-7/8 43-7/8 43-7/8 43-7/8 50-1/8 50-1/8 54 54
E - Base Length 30-1/2 37-1/2 44 51 43 51-1/2 59-1/2 68-1/2 55-1/2 63-1/2 71 78-1/2 78-1/8 90-5/8 101-3/4 119-5/8
*F - Base Height 15 15 15 15 18 18 18 18 18 18 18 18 18 18 18 18
G - Front Smoke Box Height 22-3/4 22-3/4 22-3/4 22-3/4 24-7/8 24-7/8 24-7/8 24-7/8 30-5/8 30-5/8 30-5/8 30-5/8 33-5/8 33-5/8 36-3/4 36-3/4
H - Front Smoke Box Depth 6-1/2 6-1/2 6-1/2 6-1/2 7-1/2 7-1/2 7-1/2 7-1/2 8-1/2 8-1/2 8-1/2 8-1/4 8-1/4 8-1/4 9-3/4 9-3/4
J - Supply Location 12 12 12 12 15 15 15 15 18 18 18 18 26 26 26 26
**K - Supply Size 4 4 4 4 6 6 6 6 6 8 8 8 8 10 10 10
L - Return Size 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4
M - Return Location 3-1/2 3-1/2 3-1/2 3-1/2 4 4 4 4 4 4 4 4 4-3/8 4-3/8 4-3/8 4-3/8
N - Smoke Box Depth - Top Rear
816-1/2
816-1/2
816-1/2
816-1/2
920-1/2
920-1/2
920-1/2
920-1/2
1022-1/2
1022-1/2
1022-1/2
1022-1/2
1616
1616
1616
1616
P - Vent Collar Diameter 14 14 14 14 18 18 18 18 20 20 20 20 20 24 26 28
Q - Rear Vent Collar Height 33-7/8 33-7/8 33-7/8 33-7/8 40 40 40 40 46 46 46 46 51-1/2 51-1/2 52-3/8 52-3/8
R - Smoke Box Collar Width Top Vent — — — — — — — — — — — — 35-1/4 35-1/4 42-1/2 42-1/2
S - Smoke Box Collar Depth Top Vent — — — — — — — — — — — — 10 13 12 13
T - Top Vent Collar Height 41-7/8 41-7/8 41-7/8 41-7/8 49-1/8 49-1/8 49-1/8 49-1/8 57 57 57 57 64 64 66-7/8 66-7/8
U - Tube Pull Space 32 39 45-1/2 52-1/2 44-1/2 53 61 70 57 65 72-1/2 80 81 94 105 23
V - Supply Fitting Height 1-5/8 1-5/8 1-5/8 1-5/8 3-3/8 3-3/8 3-3/8 3-3/8 3-3/8 3-3/8 3-3/8 3-3/8 3-1/2 3-1/2 3-5/8 3-5/8
W - Normal Water Line Height 40-3/4 40-3/4 40-3/4 40-3/4 48-1/2 48-1/2 48-1/2 48-1/2 55 55 55 55 66-3/16 66-3/16 69 69
�8 �9
The Complete Boiler Room SupplierThe Complete Boiler Room SupplierSeries 4N — Models 827 - 3075
Dimensions (Inches)
*Oil, Gas, Stoker Only - See note below rating table for hand-fired boilers.**4” is IPS female thread, 6” and larger are flangedSpecifications, dimensions data subject to change without notice.
4N Boiler Models 827 993 1157 1323 1654 1985 2315 2645 3075
A - Boiler Width 64 64 70 70 76 82 82 82 96
B - Boiler Length 106-1/4 129 116-1/2 136 130-1/2 128 148 162 163
*C - Boiler Height 91 91 102-1/2 102-1/2 118-1/8 138-1/8 138-1/8 138-1/8 148
D - Base Width 61-1/2 61-1/2 67-1/2 67-1/2 73-1/2 79-1/2 79-1/2 79-1/2 93-1/2
E - Base Length 107-1/4 130 117-1/2 137 131-1/2 129 149 164 164
F - Base Height 18 18 18 18 18 18 18 18 18
G - Front Smoke Box Door Height 29-5/16 29-5/16 35-7/16 35-7/16 40-3/8 52-1/8 52-1/8 52-1/8 65-7/8
H - Front Smoke Box Depth 12-3/4 12-3/4 13-3/4 13-3/4 14-3/4 15-3/4 15-3/4 15-3/4 16-1/2
J - Supply Location 22 22 22 22 22 22 22 22 68
**K - Supply Size 8 8 8 8 10 12 12 12 12
**L - Return Size - Steam 4 4 4 6 6 6 6 6 6
**L - Return Size - Water 6 6 6 8 8 8 8 8 8
M - Return Location 6 6 6-7/8 6-7/8 6-7/8 7-1/4 7-1/4 7-1/4 7
N - Smoke Box Depth Rear 20-3/4 20-3/4 22-3/4 22-3/4 22-3/4 24-3/4 24-3/4 24-3/4 26
P - Rear Vent Collar Diameter 28 32 32 35 38 44 44 44 46
Q - Rear Vent Collar Height 71-1/2 71-1/2 81-1/2 81-1/2 94-5/8 110-5/8 110-5/8 110-5/8 119
R - Top Vent Collar Width 48 48 51 51 55 72 72 72 84
S - Top Vent Collar Depth 14 17 16 19 16 18 18 18 22
T - Top Vent Collar Height 87-3/4 87-3/4 99-1/4 99-1/4 113-7/8 132-7/8 132-7/8 132-7/8 142
U - Tube Pull Space 108 131 118-1/2 138 132-1/2 130 150 165 165
W - Normal Water Line Height 74 74 85-1/2 85-1/2 100-1/4 114-1/4 114-1/4 114-1/4 122-1/2
�8 �9
The Complete Boiler Room SupplierThe Complete Boiler Room Supplier Series 4N Ratings
4N Boiler Models 63 78 92 107 127 154 180 209 240 277 311 345
Net Rating - Steam or Water MBHNet Rating - Steam Sq. Ft.Net Rating - Water Sq. Ft.
158660
1,055
192800
1,280
225935
1,500
2591,0801,725
3371,4052,245
4041,6852,695
4681,9503,120
5382,2403,590
6492,7004,330
7443,1004,960
8313,4605,540
9223,8406,150
Heating Surface - Sq. Ft. Fireside Waterside
4547
5557
6467
7477
96100
115120
133139
153160
183193
210221
235247
260274
Grate Area Sq. Ft. 4.0 5.1 6.1 7.2 7.2 8.8 10.3 12.0 12.6 12.6 13.4 14.5
Furnace Volume Cu. Ft. 8.8 10.7 12.6 14.6 18.3 21.9 25.3 29.1 34.7 39.7 44.4 49.1
Heat Release MBH/Cu. Ft. 39.9 40.1 39.2 39.2 40.5 41.0 41.1 42.9 41.2 41.3 41.0 41.0
Water Content - Gals. Steam Water
6792
83114
96134
113156
133168
149200
171231
197267
209283
239323
267362
295401
Approx. Dry Weight - Lbs. 1,900 2,200 2,500 2,900 3,200 3,700 4,100 4,600 5,150 5,550 6,250 6,650
Approx. Full Weight - Lbs. Steam Water
2,4552,665
2,9003,160
3,3103,630
3,8604,220
4,3254,615
4,9205,905
5,5556,055
6,2406,820
6,8957,510
7,5458,245
8,4609,250
9,1009,985
4N Boiler Models 397 463 563 662 827 993 1157 1323 1654 1985 2315 2645
Net Rating - Steam or Water MBHNet Rating - Steam Sq. Ft.Net Rating - Water Sq. Ft.
1,4085,8659,391
1,7247,185
11,500
2,1889,115
14,595
2,57210,71517,155
3,21413,39021,435
3,85916,08025,740
4,49618,73029,990
5,14121,42034,290
6,42726,78042,870
7,71332,13551,445
8,99637,48560,005
10,27842,82568,555
Heating Surface - Sq. Ft. Fireside Waterside
397429
463500
563608
662715
827893
9931,072
1,1571,250
1,3231,429
1,6541,786
1,9852,143
2,3152,500
2,6452,857
Grate Area Sq. Ft. 16.4 18.1 20.5 22.5 25.6 28.4 30.9 33.2 37.4 41.2 44.7 48.0
Furnace Volume Cu. Ft. 58.9 68.0 89.3 104.7 115.6 139.2 160.7 186.5 234.0 301.6 348.6 383.8
Heat Release MBH/Cu. Ft. 52.3 53.0 49.1 49.2 55.6 55.5 56.0 55.1 55.0 51.2 51.6 53.6
Water Content - Gals. Steam Water
421520
492607
602740
712875
7611,003
9251,220
1,0501,330
1,2271,554
1,4431,826
1,7202,147
1,9792,473
2,1732,718
Approx. Dry Weight - Lbs. 8,150 9,800 10,550 12,350 14,850 16,150 19,700 21,900 25,450 30,600 37,250 42,300
Approx. Full Weight - Lbs. Steam Water
11,64512,470
13,91014,865
15,56516,715
18,28019,640
21,19023,200
23,84526,295
28,48030,715
32,13234,860
37,45040,640
44,93548,490
53,74057,855
60,40064,920
Grates for hand firing are not supplied by Burnham CommercialSelectboileronnetratingtomatchbuildingheatlossorinstalledradiation.Seeadditionalnoteregardingheatvalueofcoalonbackpage
•Compact, efficient three-pass firebox design •Applications firing solid fuel, gas or oil
•1�psisteam,�0psiwater
• Ample firebox assures non-critical combustion, high efficiency
Ratings for hand Firing
�0 �1
The Complete Boiler Room SupplierSeries 4N — Biomass/Wood RatingsModel 4NP-68
Boiler ModelGross Ratings
Firing Rate Lbs./Hr.
Fireside Heat-ing Surface
Sq. Ft.
Furnace Volume Cu. Ft.
Water Content-GallonsDry Weight
Lbs.MBH HP Steam Lbs./Hr. Water Steam
4NP625-68 3,077 92 3,171 653 625 148.5 941 764 16,211
4NP925-68 4,554 136 4,693 967 925 186.6 1,195 1,006 19,675
4NP1250-68 6,153 184 6,342 1,306 1,250 238.0 1,486 1,888 24,562
4NP1538-68 7,571 226 7,803 1,607 1,538 315.7 1,789 1,450 27,390
4NP1850-68 9,107 272 9,386 1,934 1,850 407.7 2,118 1,681 32,595
4NP2153-68 10,599 317 10,923 2,250 2,153 471.9 2,609 2,056 39,030
4NP2500-68 12,307 368 12,684 2,613 2,500 521.3 2,820 2,209 40,190
4NP3075-68 15,138 452 15,601 3,214 3,075 500.4 3,406 2,586 46,370
4NP3690-68 18,165 543 18,721 3,857 3,690 574.1 3,842 2,901 55,000
4NP4305-68 21,193 633 21,842 4,499 4,305 716.2 4,465 3,381 61,996
Boiler ModelGross Ratings
Firing Rate Lbs./Hr.
Fireside Heating Surface Sq. Ft.
Furnace Volume Cu. Ft.
Water Content-Gallons
MBH HP Steam Lbs./Hr. Water Steam
4NL/W63-68 222 6.6 228 47 47 8.8 2,265 2,055
4NL/W78-68 271 8.1 279 57 55 10.7 2,650 2,390
4NL/W92-68 315 9.4 325 67 64 12.6 3,020 2,700
4NL/W107-68 364 10.9 375 77 74 14.6 3,500 3,140
4NL/W127-68 473 14.1 487 100 96 18.3 2,895 3,605
4NL/W154-68 566 16.9 583 120 115 21.9 4,465 4,040
4NL/W180-68 655 19.6 675 139 133 25.3 5,025 4,525
4NL/W209-68 753 22.5 776 160 153 29.1 5,620 5,040
4NL/W240-68 901 26.9 928 191 183 34.7 6,250 5,635
4NL/W277-68 1,034 30.9 1,065 219 210 39.7 6,985 6,285
4NL/W311-68 1,157 34.6 1,192 246 235 44.4 7,910 7,120
4NL/W345-68 1,280 38.2 1,319 272 260 49.1 8,535 7,650
4NL/W397-68 1,954 58.4 2,014 415 397 58.9 10,830 10,005
4NL/W463-68 2,279 68.1 2,349 484 463 68.0 13,055 12,100
4NL/W563-68 2,772 82.8 2,856 588 563 89.3 14,665 13,515
4NL/W662-68 3,259 97.4 3,359 692 662 104.7 17,390 16,030
4NL/W827-68 4,071 121.6 4,196 864 827 115.6 20,645 18,630
4NL/W993-68 4,888 146.0 5,038 1,038 993 139.2 23,455 21,005
4NL/W1157-68 5,696 170.1 5,870 1,209 1,157 160.7 27,675 25,340
4NL/W1323-68 6,513 194.6 6,712 1,383 1,323 186.5 31,540 28,815
4NL/W1654-68 8,142 243.2 8,392 1,729 1,654 234.0 36,900 33,710
4NL/W1985-68 9,772 291.9 10,071 2,075 1,985 301.6 44,370 40,815
4NL/W2315-68 11,396 340.4 11,745 2,420 2,315 348.6 53,385 49,270
4NL/W2645-68 13,021 389.0 13,419 2,764 2,645 383.8 60,120 55,590
4NL/W3075-68 10,215 305.1 10,528 2,169 2,075 505.6 78,710 71,630
Model 4NL/W-68
NOTES:1. Boiler model suffix “68” indicates 6.8 SQ.FT.F.S.H.S./HP2. Firing rate based on biomass/wood fuel at 6000 BTU/LB and 78.5% operating efficiency�.Furnacevolumeismeasuredfromthebottomoftheboilermudleg
�0 �1
hand Fired Boilers — Rating Adjustment for heating Value of CoalHand fired ratings are based on coal having a heat value of1�,000btuperpound.Forcoaloflesserheatvalueperpound,multiplythenetloadbythefactorshowninthetablebeforeselectingboilersize:
Standard EquipmentBoiler: Three-passboilerconstructedandstampedinaccordancewithSectionIVoftheASMEBoilerandPressureVesselCodefor1�psisteamand�0psiwaterwithseparatebase,rearsmokeoutlet(topoutletavailable when specified), gas tight front flue cleanout door,rearobservationport6�Athrough���A,rearaccessdoorwithobservationport�97Aandlarger,liftinglugs1�7Aandlarger.
Jacket: Wrap-around type, with fiberglass insulation—installed.
Steam Trim:Steampressuregauge(�-1/�inch6�Athrough66�A;6inch8�7andlarger),gaugeglasssetformountingonboilerwith6�Athrough���A,castironwatercolumnwithgaugeglasssetandtricocks�97Aandlarger,andASMEsafetyvalve(s).Trimnotinstalled.
Water Trim:Theraltimeter(�-1/�inch)6�Athrough66�A,pressure/altitudegauge(6inch)andthermometer,(6inch)8�7andlarger,ASMEreliefvavle(s).Trimnotinstalled.
Additional EquipmentOil & Gas Fired Boilers-Burneropeninginfronthead(baserefractoryorcombustionequipmentisnotsuppliedbyBurnhamCommercial).
Stoker Fired Boilers - Firedoor(s)infronthead;hingedflue door, all sizes; ashpit door in base (Stoker not suppliedbyBurnhamCommercial).
Hand Fired Boilers - Same as stoker fired (Grate sets notsuppliedbyBurnhamCommercial).
Coil Number*For Use in the Following Boiler Sizes
Subject to Capacity Limitation of Boiler
Rated Capacity—Gallons Heated40° to 140°F
Boiler Water Temp.
108°FGPM
180°FGPH
212°FGPH
INA-210 All sizes 3.5 210 325
INA-300 All except 4N-63A 5.0 300 466
INA-360 All sizes 6.0 360 560
INA-450 All except 4N-63A 7.5 450 700
INA-600 4N-154A and larger, also 4N-107A 10.0 600 933
INA-750 4N-154A and larger, also 4N-107A 12.5 750 1165
INA-900 4N-92A and larger 15.0 900 1400
INA-1125 4N-154A and larger 18.7 1125 1750
INA-1350 4N-277AS and larger, also 4N-209A 22.5 1350 2100
INA-1500 4N-345A and larger 25.0 1500 2330
Instantaneous hot Water heating Coils
Heat Value of Coal - BTU/Lb. Factor12,500 1.0412,000 1.0811,500 1.1311,000 1.1810,500 1.2410,000 1.309,500 1.379,000 1.44
Series 4N Natural Draft Firebox Boiler
*Twocoilsofanysizeorcombinationofsizesmaybeinstalledin�N-11�7andlarger
�� ��
Lancaster,PA17601Phone:888-791-�790www.burnhamcommercial.com
Series 4N Natural Draft Firebox Boiler
�� ��All specifications, dimensions and data subject to change without notice. Dimensions shown are measured in inches.
4NP Boiler Models 625 925 1250 1538 1850 2153 2500 3075 3690 4305
A - Boiler Length 1�1 1�� 16� 16� 169 177 19� 191 �1� ���
B - Boiler Supply Height 9� 10� 11� 1�7 1�� 1�1 1�1 1�1 1�1 1�1
C - Base Length at Mudleg 1�� 1�6 1�� 1�� 1�� 1�1 166 161 18� �1�
D - Boiler Width at Mudleg 6� 68 7� 80 86 9� 9� 10� 10� 110
E - Firebox Width �8 �� 60 66 7� 78 78 90 90 96
F - Firebox Length 11� 1�� 1�9 1�0 1�0 1�8 1�� 1�8 171 �00
G - Firebox Height �0 �� �6 �� 66 66 66 �� �� ��
H - Supply Location 6� 71 7� 7� 77 79 87 86 98 11�
J - Supply Nozzle Size (300lb. Flg.) � 6 6 6 8 8 8 8 10 10
K - Return Connection Location �1-1/� �1-1/� �1-1/� �1-1/� �1-1/� �1-1/� �1-1/� �1-1/� �1-1/� �1-1/�
M - Return Connection Size 1-1/� 1-1/� 1-1/� � � �-1/� � � � �
N - Front Smokebox Depth 10 10 1� 1� 1� 1� 1� 16 16 16
P - Tube Removal Space 117 1�8 1�� 1�� 1�1 1�9 1�� 1�7 170 199
Q - Rear Flue Outlet Diameter �7 �� �9 �� �� �� �8 �8 �8 �1
R - Base to Flue Centerline 67-�/� 7�-1/� 81-1�/16 91-�/8 109-9/16 11�-9/16 11�-9/16 107-7/16 107-7/16 107-7/16
S - Normal Water Line 76-1/� 8�-7/8 9�-�/16 10�-1/� 1�1-1/� 1��-1�/16 1��-1�/16 1��-�/8 1��-�/8 1��-�/8
AA - Width Over Columns 81 87 9� 99 10� 111 111 1�� 1�� 1��
BB - Front and Rear Column Location 17 17 17 17 17 17 17 17 17 17
CC - Middle Column Location �6 �� �� �� �� 61 69 6� 78 8�
Approximate Dry Weight (Lbs.) 16,�11 19,67� ��,�6� �7,�90 ��,�9� �9,0�0 �0,190 �6,�70 ��,000 61,996
Approximate Weight, Full (Lbs.) ��,�7� �8,0�� ��,��8 �9,�69 �6,�98 �6,1�6 �8,�91 67,911 79,16� 90,160
Series 4NP Natural Draft Firebox Boiler
�� ��
The Complete Boiler Room SupplierThe Complete Boiler Room Supplier
BOILER MODEL
GROSS RATINGS NET RATINGS MAX. FIRING RATE - SINGLE FUEL
HEAT-ING
SUR-FACE
SQ. FT.FURNACE VOLUME. CU. FT.
WATER CONTENT GALLONS (STEAM)
MBH HPLBS. STM./HR.
STEAM MBH
SQ. FT. STEAM
GAS MBH
#2 OIL GPH
#6 OILGPH
#LBS/HR.
COAL*
FIRE SIDE
�NP6��-6� �,��8 100 �,��0 �,�98 10,8�� �,18� �0.� �7.9 ��8* 6�� 1�8.� 76�
�NP9��-6� �,0�1 1�0 �,17� �,896 16,��� 6,�76 ��.� �1.8 �9�* 9�� 186.6 1,006
�NP1��0-6� 6,69� �00 6,900 �,19� �1,6�6 8,�69 60.6 ��.8 6�6* 1,��0 ��8.0 1,188
�NP1��8-6� 8,�69 ��0 8,6�� 6,�9� �7,0�8 10,�61 7�.8 69.7 8�0* 1,��8 �1�.7 1,��0
�NP18�0-6� 10,0�� �00 10,��0 7,79� ��,�71 1�,��� 91.0 8�.7 98�* 1,8�0 �07.7 1,681
�NP�1��-6� 11,716 ��0 1�,07� 9,09� �7,88� 1�,6�� 106.1 97.6 11�8* �,1�� �71.9 �,0�6
�NP��00-6� 1�,�90 �00 1�,800 10,�91 ��,�96 16,7�8 1�1.� 111.6 1�1�* �,�00 ��1.� �,�09
�NP�07�-6� 16,7�8 �00 17,��0 1�,989 ��,1�1 �0,9�� 1�1.6 1�9.� 1,6�0* �,07� �00.�� �,�86
�NP�690-6� �0,08� 600 �0,700 1�,�86 6�,9�� ��,106 181.9 167.� 1,968* �,690 �7�.0� �,901
�NP��0�-6� ��,��� 700 ��,1�0 18,18� 7�,767 �9,�91 �1�.� 19�.� �,�96* �,�0� 716.�� �,�81
�NP6��-�0 �,18� 1�� �,�1� �,��7 1�,��9 �,��0 �7.9 ��.9 �8�** 6�� 1�8.� 76�
�NP9��-�0 6,19� 18� 6,�8� �,806 �0,0�� 7,7�1 �6.1 �1.6 �17** 9�� 186.6 1,006
�NP1��0-�0 8,�69 ��0 8,6�� 6,�9� �7,0�8 10,�61 7�.8 69.7 �6�** 1,��0 ��8.0 1,188
�NP1��8-�0 10,0�� �00 10,��0 7,79� ��,�71 1�,��� 91.0 8�.7 676** 1,��8 �1�.7 1.��0
�NP18�0-�0 1�,�86 �70 1�,76� 9,61� �0,0�0 1�,�8� 11�.� 10�.� 8��** 1,8�0 �07.7 1,681
�NP�1��-�0 1�,�9� ��0 1�,8�� 11,170 �6,��� 17,99� 1�0.� 119.9 969** �,1�� �71.9 �,0�6
�NP��00-�0 16,7�8 �00 17,��0 1�,989 ��,1�1 �0,9�� 1�1.6 1�9.� 1,1�7** �,�00 ��1.� �,�09
�NP�07�-�0 �0,08� 600 �0,700 1�,�86 6�,9�� ��,106 181.9 167.� 1,���** �,07� �00.�� �,�86
�NP�690-�0 ��,��� 700 ��,1�0 18,18� 7�,767 �9,�91 �1�.� 19�.� 1,�77** �,690 �7�.0� �,901
�NP��0�-�0 �8,��� 8�0 �9,��� ��,080 9�,001 ��,�68 ��7.7 ��7.1 191�** �,�0� 716.�� �,�81
Lancaster,PA17601888-791-�790www.burnhamcommercial.com
NOTES:1. Boiler model suffix “62” indicates 6.15 sq. ft. F.S.H.S. /HP and “50” indicates 5 sq. ft. F.S.H.S./HP�. Firingratebasedon: Natural gas @ 1000 BTU/cu. ft. and 80% heat transfer efficiency #2 oil @ 138 MBH/gal. and 80% heat transfer efficiency #6 oil @ 150 MBH/gal. and 80% heat transfer efficiency * 100% coal input @ 13,000 BTU/pound and 78.5% heat transfer efficiency (6.15 rating) ** Coalinput@1�,000BTU/poundlimitedto70%ofinputinordertodevelop�sq.ft.rating.�. Furnacevolumeismeasuredfromthebottomoftheboilermudleg(nodeductionforbridgewall)�. ApproximatedryweightincludesHcolumnsandbasecasing.
Series 4NP
�� ��
The Complete Boiler Room SupplierThe Complete Boiler Room Supplier
C SeriesCompact Package Boiler
�6 �7
C Series Compact Packaged Boiler
America’s Boiler CompanyTheBurnhamCommercialCSeriescompactpackagedboilerwasdesignedusingour1�0+yearsofboilerexperienceandissoldandservicedthroughthelargestandmostexperiencednetworkofsalesrepresentativesinthe country. With a complete commercial product offering andunmatchedsalesandtechnicalsupport,it’snowonderwhyweareAmerica’sBoilerCompany!
Packaged Boilers That Can Actually Fit Through A Door!TheCSeriesFiretubeboilerisfullypackagedanddesigned to provide maximum cost and energy efficiency. The C Series boiler fits through any standard 36” x 80” doorway,eliminatingtheneedforanycostlybuildingalterations or difficult site assemblies. This convenient size allows for easier and less expensive retrofit or upgrade of anexistingboilerroom.
Aforced-draftunit,theCSeriesavoidstheexpenseofatallstackandismuchmoreeconomicaltooperateandinstallthan atmospheric-fired boilers. The forced draft creates a morecontrolledcombustion,andamorethoroughmixtureof fuel and air is acheived resulting in optimum efficiency.
Otherdesignfeatureshelpmaintainthisdurabilityandeconomy over the years. While the original efficiency of someotherboilerscandecreasewhenouterwrappersdevelopairleaksandtubescannotbecleanedthoroughly,theCSeriesovercomestheseproblems.BuilttoASMEstandards,itsoutershellofheavyweldedsteelboilerplate
andextraheavytubesheetsassurethecontinuedairtightconditions necessary for efficient combustion. Opening the front flue door allows convenient access to the firetubes. By brushing out all of the firetubes, the original efficiency of the boilerisrestoredinamatterofminutes.AlltubeendsarerolledinaccordancewiththeASMEcodeandareinspectedforhydraulictightnessbyanindependentinsuranceinspector,priortoshipping.
Theseinstallation,operationandmaintenancefeaturesadduptorealsavingsforyou.Factorytestingassuresyouthattheboilerwilldeliverclean,quietandreliableheatfromthedayit’sinstalled.
FRONT REAR
�6 �7
Efficiencies and Features
C Series FeaturesBoiler:Three-pass firetube type, constructed with heavy steel, in ac-cordancewithrequirementsoftheASMECode.AllunitsareregisteredwiththeNationalBoard.
Water cooled sidewalls in the rear turnaround promote rapid internalcirculationandreducegastemperaturesattheen-trancetothesecondpass,reducingtubeendstress.Alltubeends are rolled and flared.
Easy-opening insulated front and rear flue doors with light weightnon-refractoryclosureprovidefullaccesstoalltubes.Noelaboratesealsareused.TheCSeriesoversizedfurnaceeasilyaccommodatesanyburner.
Washouts are provided for easy inspection and cleaning of watersidesurfaces.
Allsteamboilersareprovidedwithadrypantoensuredrysteam.Afeedwaterdiffuserisprovidedonsteamboilers.Allwaterboilersareequippedwithadiptubeatsupplyoutletanddiffuseratreturninlet.
Theroundverticalsmokeoutlethasroomforanoptionalquadrantdamper.Allboilersareprovidedwithliftingholesand
an enameled steel jacket installed over fiberglass insulation.Theboilerismountedonaheavy-dutystructuralsteelbasewithextendedskidandburnerplatformforprotectionoftheburnerduringshipmentandrigging.
Standard Trim and Controls: Steam:1�7pumpcontrol/lowwatercut-offwithalarmcon-tacts—piped with quick opening blowoff valve. Gauge glass setwithhand-operatedgaugeandtrycocks.Steampressuregauge—4 ½-inch dial. L404A operating pressuretrol, L404C manual reset high limit pressuretrol and appropriate firing rate controlwhenrequired.Manualresetprobeauxiliarylowwatercut-off.ASMEsideoutletsafetyvalve(s).
Water:63M manual reset low water cut-off—piped with quick openingblowoffvalve.Combinationpressure/temperaturegauge—3 ½ inch dial. L4006A operating aquastat and L4006E manual reset high limit aquastat and appropriate firing rate controlwhenrequired.ASMEsideoutletreliefvalve(s).
C Series Anticipated EfficienciesNATURAL GAS
Boiler HP
25% 50% 75% 100%
10 psig 180°F Water 10 psig 180°F Water 10 psig 180°F Water 10 psig 180°F Water20 8�.� 8�.� 8�.� 8�.� 8�.� 8�.8 8�.6 8�.1
30 8�.7 8�.7 8�.8 8�.� 8�.� 8�.9 8�.7 8�.1
40 8�.9 8�.8 8�.9 8�.� 8�.� 8�.9 8�.7 8�.1
50 8�.1 86.0 8�.1 8�.7 8�.7 8�.1 8�.0 8�.�
60 8�.� 86.1 8�.� 8�.9 8�.0 8�.� 8�.� 8�.8
70 8�.� 86.1 8�.� 8�.8 8�.9 8�.� 8�.� 8�.7
80 8�.� 86.� 8�.� 8�.9 8�.9 8�.� 8�.� 8�.7
90 8�.6 86.� 8�.6 86.1 8�.� 8�.7 8�.8 8�.�
100 8�.7 86.� 8�.8 86.� 8�.6 86.0 8�.� 8�.6
#2 OIL
Boiler HP25% 50% 75% 100%
10 psig 180°F Water 10 psig 180°F Water 10 psig 180°F Water 10 psig 180°F Water20 86.0 88.� 86.� 87.9 86.0 87.� 8�.� 86.9
30 86.7 88.6 86.7 88.� 86.� 87.8 8�.8 87.�
40 86.8 88.7 86.8 88.� 86.� 87.9 8�.9 87.�
50 87.� 89.0 87.1 88.6 86.8 88.� 86.� 87.7
60 87.� 89.� 87.� 88.9 87.1 88.6 86.7 88.1
70 87.� 89.� 87.� 88.9 87.1 88.� 86.6 88.0
80 87.� 89.� 87.� 88.9 87.1 88.� 86.7 88.0
90 87.8 89.� 87.8 89.� 87.6 89.0 87.� 88.6
100 88.0 89.7 88.0 89.6 87.9 89.� 87.6 89.0
�8 �9
C-Series Ratings & Dimensions
C Series Ratings
BHP A B C
Gross OutputMBH
Gross OutputLbs/Hr
Net RatingWaterMBH
Net RatingSteamMBH
Sq Ft NetSteam
Firing RateMBH - Gas
Firing RateGPH -#2 Oil
20 �0 66-�/8 7�-�/8 670 690 �8� ��0 �,166 816 �.7
30 �0 66-�/8 8�-�/8 1,00� 1,0�� 87� 780 �,��9 1,��� 8.�
40 ��-1/� 7�-7/8 90-1/8 1,��9 1,�80 1,16� 1,0�0 �,��� 1,6�� 11.�
50 ��-1/� 7�-�/8 100-�/8 1,67� 1,7�� 1,��� 1,�99 �,�1� �,0�1 1�.�
60 ��-1/� 7�-�/8 11�-1/8 �,009 �,070 1,7�7 1,��9 6,�97 �,��9 17.1
70 ��-1/� 78-1/� 11�-�/8 �,009 �,�1� �,0�8 1,819 7,�80 �,8�8 19.9
80 ��-1/� 78-1/� 1��-1/8 �,678 �,760 �,��9 �,079 8,66� �,�66 ��.8
90 ��-1/� 78-1/� 1��-1/8 �,01� �,10� �,6�0 �,��9 9,7�6 �,67� ��.6
100 ��-1/� 78-1/� 1��-1/8 �,��8 �,��0 �,911 �,�99 10,8�9 �,08� �8.�
A
OVERALL
WIDTH
B
MAX.
HEIGHT
PLAN VIEW
SIDE VIEWFRONT VIEW
C
OVER SKID
©�00�BurnhamCommercialLancaster,PA1760�Phone:888-791-�790www.burnhamcommercial.com
�8 �9
Component Summary InformationA boiler is not only a significant plant expenditure, but it is the most important element of any mechanical heating/process system. The continued reliability of the boiler is heavily dependent upon the quality and chemistry of the water within the system. Burnham Commercial features a complete line of boiler room accessory products designed to match the performance needs of your Burnham Commercial boiler. Proper use and installation of this equipment can significantly improve system efficiency and boiler longevity.
Burnham Deaerator SystemsaredesignedtoprotectyourBurnhamboilerandsteamsystemfromthecorrosioncausedbythepresenceofnon-condensablegases.Asolutionofoxygeninwaterisverycorrosivetometalswidelyusedinstemsystems.Useofdeaeratorsystemspayforthemselvesinfewerdowntimehours,lesschemicaladditivesandreducedmaintenancetotheentiresteamsystem.
Burnham Water Softener Systemsaredesignedtoproduceconditionedwatertoreducethemin-eralswhichproducedetrimentalscaleformationontheheattransfersurfacesintheboiler.Useofawatersoftenerreducestheneedforotherchemicalscalecontroladditives.
Burnham Chemical Feed Systemsenabletreatmentofboilerfeedwaterwithchemicalsthatprotectagainstboilerscalingandcorrosion.Amountandtypeofchemicaltreatmentwillvarydependingupontheindividualapplication.
Burnham Boiler Feedwater Systemsaredesignedtoefficientlystoreandreturnhotcondensateincombinationwithmake-upwatertoautomaticallymeetboilerwaterdemands.Useofboilerfeedwatersystemscanaccountforsignificantfuelsavingsandlowertotalchemicaltreatmentcosts.
Burnham Condensate Return Systemsarecompletesystemsdesignedtoincreasetheenergy/watersavingcircuitforsteamheatingorprocesssystemsandminimizedifficultiesfromboilerencrustationbyrecyclingpreviously-treatedsystemwater.
Burnham Blow Down Systemsaredesignedtoeliminatemineralbuild-upfromdissolvedsolidsthatwouldcausescaleandboilercorrosion.Theyareavailableintwobasictypes:BottomBlowDowndesignedforforcefulremovalofbottomresidueandSurfaceBlowDown/HeatRecoverywhichisanongoingprocessthatremovesdissolvedsolidsfromthetoplevelofwaterintheboilerwhileprovidingaheatrecoveryfunctionaswell.
�0 �1
Typical Steam System Layout
Water Softener System
Boiler Feedwater System
Boiler
Deaerator System Bottom Blow Down
Surface Blow Down/Heat Recovery System
Chemical Feed System
Condensate Return System
Surge System
�0 �1
Boiler Accessories
�� ��
Continuous Run & On-Off Boiler Feedwater Pump Applications• Equipmenttodosechemicalstotreatboiler feedwater.
• Introduceschemicalstotheboilerorboiler feedwaterpiping.
•Vertical�0gallonpolyethylenetankonstandwith lid(othersizetanksandtankmaterialsavailable).
•5/8” piston pump, adjustable from 0 to 6.2 gallons perhour(GPH)(othersizeandcapacityofpiston anddiaphragmpumpsavailable).
•Pistonpumpto1000psig(variousstainlesssteel headsavailableasanoption).
•Modularconfigurationtomeetcustomer requirementsincludes:tankwithlidonstand, pistonpump,factorsuctionpipingandagitator ContinuousRunonly:controlpaneland make-upwatermeter.
•Canbecustomconfiguredtomeetcustomer requirements.
•Morethanonepumpmaybemountedundera �0gallontank.
•1/�HP,totallyenclosednon-ventilated(TENV), 11�/1/60voltmotorstandard(�0hertzandmany othermotoroptionsavailable).
•Factorysuctionpipingincludes:strainerand safetyreliefvalve.
Chemical Feed System
•Agitator:angleorclampmounted,1/�HPTENV, 11�/1/60voltmotorstandard(�0hertzandmany othermotoroptionsavailable).
•Pumpcontrolviamake-upwatermetersignalto panel-mountedtimer.
•ContinuousRun-NEMA1�controlpanel includes:mixerandpumpswitches,motorrelays, fuses,terminalstripandtimer.
•On-Off- Controlpanelandwatermeteravailable asoptions.
�� ��
Chemical Feed System(Continuous Run & On-off Boiler Feedwater Pump Applications)
Capacity in Gallons Wall
Dimensions
Part Number Tank and Lid onlyA B C D
30 1/8” 18 30 12 49 103 030
55 1/8” 22 34 17 60 305 050
100 1/4” 28 42 18 70 310 0100
150 1/4” 31 47 18 75 315 0150
200 1/4” 36 48 20 77 320 0200
275 1/4” 42 48 20 77 327 0275
360 1/4” 48 48 20 77 336 0360
500 5/16” 54 60 20 89 350 0500
Specifications
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
�� ��
Bypass and Shot Feed SystemsFor applications requiring bulk feeding of chemicals to a pressure system
Bypass Chemical Feeders•Bypasschemicalfeedersinclude:tank,gauge glass,controlandsamplevalvesandfunnel.
•Usedinapplicationswhereacontinuoussupply ofchemicalisneededinaclosedlooporlow makeupsystem.
• Flowadjustmentsofchemicalsaremade manually with the flow regulator.
Shot Feeders•Shotfeedersinclude:tank,samplevalveand funnel.
•Usedtoaddaslugofchemicalsintoalow makeuporclosedloopsystems.
•Shotfeedersareconstructedofsteelandhave aratedworkingpressureof1��psig.
�� ��
Bypass and Shot Feed SystemsBypass Feeder
Item Description Qty.
1 Tank 1
2 Funnel 1
3 Petcocks 2
4 1” Pipe Nipple 2
5 1” Valve 2
6 Gauge Valve 2
7 Sight Glass 1
8 Glass Guards 2
9 1” x 3/8” Reducer Bushing 1
10 3’8” Pipe Nipple 3
11 3’8” Union 1
12 Flow Control Valve 1
13 3/8” valve 1
14 1/2” Coupling 3
15 1” Coupling 2
Dimensions in Inches
Tank Size(gallons)
A(Dia.)
B(Lht.)
1 6 10
1-1/2 6 12
2 8 10
2-1/2 8 12
5 10 15
10 10 29
18 14 32
25 18 28
Item Description Qty.
1 Tank 1
2 Funnel 1
3 1/2” Pipe Nipple 4
4 1” x 1/2” Reducer Bushing 1
5 Petcocks 2
6 1/2” Valve 2
7 1/2” Tee 1
8 1/2” Coupling 4
NOTE:�gallonandlargerfeedershave1�"legs.Alldimensionsareapproximate
3/4 Gallon
Dimensions in Inches
Tank Size(gallons)
A(Dia.)
B(Lht.)
1 6 10
1-1/2 6 12
2 8 10
2-1/2 8 12
5 10 15
10 10 29
18 14 32
25 18 28
Item Description Qty.
1 Tank 1
2 Funnel 1
3 1” Pipe Nipple 3
4 Petcocks 2
5 1” Valve 2
6 1/2” Coupling 3
7 1” Coupling 2
NOTE: 1.Alldimensionsareapproximate�.Alldimensionsareininches
1 - 25 Gallon
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790
www.burnhamcommercial.com
�6 �7
Boiler Feedwater System Features• Completesystemincluding:vessel,pump(s), stand,trim,andcontrolpanel
• Actsasareservoirforcondensatereturn, make-upwater,andboilerfeedwater
• Horizontal,stand-mounted,atmospheric configuration. Vessel unbolts from stand for easeofreplacementandinstallations
• Dishedhead,factorypressuretested,non-code stampedvessel–standard.ASME,SectionVIII Codestampedvessels,corrosionresistant vesselsavailable
• Modelrange:��gallonthrough1,�8�gallon
Boiler Feedwater Systems
• Water storage to full overflow: 15 minutes
• Factorypipedpumpre-circulation
• Oversizepumpsuctionlines
• Additionalopeningforfutureapplications
• Auxiliaryreliefvent(s)
• Can be custom configured to meet customerrequirements
• Factoryinsulationandjacketingavailable
• Optiontopre-heatboilerfeedwater
BhFS
BhTS
�6 �7
Condensate Return System Features• Manymotorandvoltageoptions available.
• Manytrim,electricalandcontrolpanel optionsavailable.
• Modular configuration to meet customer requirementsincludes:tank,pump(s), float control/alternator, control panel andtrimoptions.
• Pumpoptions: -17�0RPM-1/�HP/1.�GPMat 10psigthrough�HP/7�GPMat�0psig -���0RPM-1/�HP/1.�GPMat 10psigthrough10HP/1�0GPMat60psig
• Inexpensive/efficient mechanism for the capture and return of condensed steam. Unitsmaybeconvertedtoactasasmallboilerfeedwaterunits.
• “NO OPTION/QUICK SHIP” units available (15 to 21 gallon cast iron tank, 10 and 16 gallon steel tank, simplex or duplex, single phase with float switch, NO ALTERNATOR; 6 gallon cast iron
• Availableineitherrectangularsteeltank(16-�0gallon)orrectangularcastirontank(1�-110gallon).
Condensate Return System
�8 �9
Flash Economizer•Reducesdissolvedsolidsfromthetoplevelof waterintheboiler.
•Recoversheatfromsurfaceblowdowntoheat boilerfeedormake-upwater.
•ASMESectionVIIIcode-stampedflash separatorandcoil.
• Separatorissizedtoaccommodateagiven percentsurfaceblowdown/flowratefromboiler operatingpressuretoagivenventpsig.
• Coilissizedtoaccommodatemake-upflowrate atbetween8and18psigpressuredrop.
• ModelRange:HR-�9(�GPMblowdown/9 GPMmake-up)throughHR-�01�0(�0GPM blowdown/1�0GPMmake-up).
• Completesystemconfiguredtoinclude: flashseparatormountedaboveandflanged toastainlesssteelorcoppercoilonstainless steelstandwithtrap,ballvalve,gaugeglass, safetyvalve,�thermometersandfactorypiping.
• Stainlesssteelstrikingplatestandard.
• Flashseparatorflangedtocoilsectionforeaseor removalforcleaning.
Blowdown heat Recovery System
• Openingstofacilitatecleaningand inspectionstandard.
• Optionsincludemultipleboilermanifoldand mountingofconductivitycontroller.
�8 �9
Blowdown heat Recovery System(Flash Economizer)
Model
Blowdown Capacity
GPM
Make-upCapacity
GPMPressure
Drop* A B C D E F G H
HR-39 3 9 9 psi 97 50 36 10 1 2-1/2 1 1
HR-315 3 15 9 psi 96 44 44-1/4 8 1 2-1/2 1 3/4
HR-612 6 12 8 psi 111 53 46 12 1-1/2 3 1 1-1/4
HR-630 6 30 10 psi 110 49 50 10 1-1/2 3 1 3/4
HR-1020 10 20 13 psi 106 50 44 16 1-1/2 4 2 1-1/2
HR-1050 10 50 10 psi 100 44 42 16 1-1/2 4 2 1-1/4
HR-2040 20 40 18 psi 140 67 62 18 1-1/2 6 2 2
HR-20100 20 100 10 psi 140 67 62 18 1-1/2 6 2 1-1/2
HR-3060 30 60 15 psi 172 76 85 18 1-1/2 6-8 2 1-1/2
HR-30150 30 150 18 psi 132-1/2 67 53-1/4 24 1-1/2 6-8 2 2-1/2
Specifications
*Acrosswatercoilatmaximumflow
Constructed in accordance with ASME Code, Secion VIII, Division 1, for MAWP of 150 PSIG. Hydrostatictestedat���PSIG.SafetyReliefValvesetat1�0PSIG.
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
60 61
•Eliminateprecipitatedsolidsfromthebottom oftheboiler.
•Coolsblowdownto1�0°Forbelowbefore dumpingtodrainbystoringoneentireblowdown inareservoirandusingittocoolthenext blowdown.
•ASMESectionVIIIcode-stampedtank.
•Sizedeithertoaccommodateonecomplete boilerblowdownortosatisfyNewJersey regulations.
•ModelRange: 18” diameter x 24” height through 72” diameter x 92” height
•Modularconfigurationtomeetcustomer requirementsincludes:tank,legs,gaugeglass andpressuregauge.
•Canbecustomconfiguredtomeetcustomer requirements.
•Stainlesssteelstrikingplatestandard.
Bottom Blowdown Tank
•Openingstofacilitatecleaningandinspection standard.
•Safetyvalveandthermometermaybeincluded asoptions.
60 61
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
•ClosedorPressureType-ABlowdownTanksubjected tothemaximumsteamboilerpressuremustbe constructedforsuchpressureandstampedwitheither NewJersey,NationalBoardorASMEStandard.
• When the blowdown from any steam boiler is disposed inasewerorotherinterconnectedsystem,aBlowdown Tankmustbeplacedbetweentheboilerandthesewer orsystem.
•TheminimummetalthicknessofBlowdownTanks, whetherpressureoratmospheric,mustnotbeless than 5/16”.
•AtmosphericorVentedType-Theoutletfromthe BlowdownTankshallbetwicetheareaoftheboiler blowdownpipeandmadetoextendinternallywithin 6” from the bottom of the tank.
•Aventpipe,atleasttwicethediametertotheinlet, shallleadtotheoutsideatmosphere.
•Ventsshallbeasdirectaspossibletotheoutsideofthe atmosphereanddischargeatapointnotlessthan sevenfeetabovetheadjacentwalkwayorareas withoutavalveorotherpossibleobstructionsuchasa waterpocket.
•General-AllBlowdownTanks,whetheroftheclosed orventedtypeshouldbeofthefollowingdimensions inrelationtotheboilerrating,andmusthaveapproved openingsforcleaningandinspections:
Boiler Pressure
PSIG
Blow-off Line Pipe
SizeVent Pipe
SizeOutlet
Pipe SizeDiameter of Tank
Heightof Tank
100
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
2-1/2”3”
3-1/2”4”5”6”
3”3”4”5”6”6”
20”24”30”42”48”54”
3’6”4’0”4’2”4’0”4’6”6’0”
1�0
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
3”3-1/2”
4”5”6”8”
�3-1/2”
4”5”6”8”
20”24”36”42”54”60”
3’6”5’0”5’0”5’0”5’6”6’0”
�00
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
3”4”5”6”8”8”
3”4”5”6”8”8”
20”30”36”42”48”60”
4’3”4’6”5’0”6’0”7’3”7’0”
��0
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
3-1/2”4”5”6”8”
10”
3”4”5”6”8”
10”
24”30”42”48”54”60”
4’0”4’6”4’6”5’0”7’0”7’2”
�00
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
3-1/2”5”6”8”8”
10”
3-1/2”5”6”8”8”
10”
24”30”42”48”60”66”
4’6”5’6”5’0”5’6”6’3”7’8”
��0
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
4”5”6”8”
10”10”
4”5”6”8”8”
10”
24”30”42”48”60”72”
5’0”5’6”5’6”6’2”
6’10”7’0”
�00
3/4”1”
1-1/4”1-1/2”
2”2-1/2”
4”5”6”8”
10”10”
4”5”6”8”8”
10”
24”30”42”48”66”72”
5’6”6’0”6’0”6’4”6’0”8’0”
Boiler Rating HP Cu. Ft. Minimum Size Tank Gallons
�-�0 �.� 18” diameter x 24” �6.�
�1-�0 7.7 24” diameter x 30” �9
�1-100 1�.7 30” diameter x 36” 110
101-�00 �1.6 36” diameter x 36” 160
�01-�00 ��.8 36” diameter x 42” 18�
�01-800 �9.� 42” diameter x 48” �88
801-1000 6�.0 48” diameter x 60” �70
New Jersey Regulations for Blowdown Tanks
6� 6�
•Reducessteampressureorventsprocesssteam directlytoatmosphere.
•Eliminatesmoisturefromprocesssteam (cyclonicspinningmechanismpermitstheuse ofsmallertankstocompletelyseparateflash steamfromcondensate).
•ASME Section VIII “UE” stamped separator standarduptomodelBFS-16-�6.
•ASME Section VIII “U” stamped separator standardformodelsBFS-16-�6andabove.
•Sized to accommodate a given #/hour flow rate ofsteamfromagivensourcepsigtoagiven ventpsig.
•ModelRange: 6” diameter x 34” high through 36” diameter x 108” high.
•Modularconfigurationtomeetcustomer requirementsincludesaflashseparatorandthe followingoptions:trap,checkvalve,ballvalve, safetyreliefvalveandgaugeglass.
Flash Separator
•Canbecustomconfiguredtomeetcustomer requirements.
•Stainlesssteelstrikingplatestandard.
6� 6�
#/Hour Condensate
#/Hour Flash Steam100 500 700 1,000 2,000 3,000 4,000 8,000 12,000 18,000 21,000 25,000 35,000
100,000Height
DiameterDrainVent
108�0��
108�0��
108�0�
�-1/�
108�0��
108�0���
108�0��
108�0�6
108�0�8
108�0�010
108�0�
1�
108�0�
1�
108�6�
16
108�6�
18
90,000Height
DiameterDrainVent
96�0��
96�0��
96�0�
�-1/�
96�0��
96�0��
96�0��
96�0�6
96�0�8
96�0�
10
96�0�
1�
96�0�
1�
96�6�
16
96�6�
18
80,000Height
DiameterDrainVent
96����
96����
96���
�-1/�
96����
96����
96����
96���6
96���8
96���
10
96���
1�
96�0�
1�
96�6�
16
96�6�
18
70,000Height
DiameterDrainVent
7�����
7�����
7����
�-1/�
7�����
7�����
7�����
7����6
7����8
7����
10
7����
1�
7��0�
1�
7��6�
16
7��6�
18
60,000Height
DiameterDrainVent
�6����
�6����
�6���
�-1/�
�6����
�6����
�6����
�6���6
�6���8
�6���
10
�6���
1�
�6�0�
1�
�6�6�
16
50,000Height
DiameterDrainVent
7��0��
7��0��
7��0�
�-1/�
7��0��
7��0��
7��0��
7��0�6
7��0�8
7��0�
10
7����
1�
7��0�
1�
7��6�
16
40,000Height
DiameterDrainVent
�6�0��
�6�0��
�6�0�
�-1/�
�6�0��
�6�0��
�6�0��
�6�0�6
�6�0�8
�6�0�
10
�6���
1�
�6�0�
1�
30,000Height
DiameterDrainVent
�618��
�618��
�618�
�-1/�
�618��
�618��
�618��
�618�6
�618�8
�6�0�
10
�6��
�-1/�1�
20,000Height
DiameterDrainVent
�61�
�-1/��
�61�
�-1/��
�61�
�-1/��-1/�
�616
�-1/��
�616
�-1/��
�616
�-1/��
�616
�-1/�6
�616
�-1/�8
�6�0�
10
10,000Height
DiameterDrainVent
��1���
��1���
��1��
�-1/�
��1���
��1���
��1���
��1��6
��16
1-1/�8
5,000Height
DiameterDrainVent
��10
1-1/��
��10
1-1/��
��10
1-1/��-1/�
��10
1-1/��
��1�
1-1/��
��1�
1-1/��
��1�
1-1/�6
3,000Height
DiameterDrainVent
��10
1-1/��
��10
1-1/��
��10
1-1/��-1/�
��10
1-1/��
��1�
1-1/��
2,000Height
DiameterDrainVent
��8
1-1/��
��8
1-1/��
��81
�-1/�
��101�
1,000Height
DiameterDrainVent
��61�
��81�
��81
�-1/�
500Height
DiameterDrainVent
��61�
��61�
Pressure To... Pressure From...
800 700 600 500 400 300 200 100 75 50 25700600�00
�.��.�7.9
�.7�.� �.9
�00�00�00
10.81�.118.0
8.�11.91�.8
6.09.�
1�.�
�.�6.7
10.9�.77.9 �.�
100�0�0
��.1�6.9�9.0
�1.0��.9�7.0
18.8��.7��.9
16.��0.���.6
1�.�17.619.9
10.�1�.�16.7
6.010.�1�.8
�.67.1
�.��.1 �.6
1�7
0.0
�1.1��.6��.�
�9.��0.7��.�
�7.1�8.6�0.�
��.8�6.��8.�
��.���.8��.6
19.0�0.7��.�
1�.�16.918.7
9.611.�1�.�
7.69.�
11.9
�.�7.09.0
1.8�.7�.8
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
Follow the “Pressure From...” down vertically on the chart at left to the “Pressure To...”.
Example: 75 PSIG condensate flashed to low pressure heatingsystemat1�PSIGgives7.6% condensate flashed into system.
After determining the percent of flash from the chart above, determine the size of Flash Separator from the chart below.
Example: Referring back to the chart above, you have a 7.6% flash, If you have 30,000 #/hour condensate at 75PSIG, 2,280 #/hour steam (30,000 x .076). Locate 30,000 in the left column below, go across to 2,280 #/hour flash steam column (3,000). You would use a 56” high x 18” diameter Flash Separator with a 3” draft and 5” vent.
I Inlet-SpecifyinlettomatchyourreturnlineorblowofflineH �� �6 7� 96 108
Dia. 6 8 10 1� 16 18 �0 �� �0 �6D 1 1-1/� 1-1/� � �-1/� � � �V � �-1/� � � � 6 8 10 1� 1� 16 18
PL �/16 �/8
Dimension Chart Model BFS
*Flash Separators over 18” diameter, cleanout will be 2” NPT coupling.
6� 6�
•Eliminateprecipitatedsolidsfromthebottom oftheboiler.
•Coolsblowdownto1�0°Forbelowbefore dumpingtodrainbyintroducingcoolingwater viaanaftercooler.
•ASME Section VIII “UE” stamped separator. (“U” stamp available as option)
•Sizedtoaccommodateflowbasedonboiler blowdownlinesizeandboileroperatingpressure.
•ModelRange: 14” diameter x 22” through 56” in height forstandardboilers
(10” diameter x 14” high option available for boilers under 1000 #/hour)
•Modularconfigurationtomeetcustomer requirementsincludes:separator,legs (orwallbracket),aftercooler,temperature regulatingvalveandthermometer
•Canbecustomconfiguredtomeetcustomer requirements.
Bottom Blowdown Separator
•Stainlesssteelstrikingplatestandardand internalsteelrestrictorplatesstandard.
•Multipleseparatorswithmanifoldforhigh pressureapplicationsavailable.
6� 6�
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
Blowdown Valve Size Separator * 1” 1¼” 1½” 2” 2½” 3”Dimensions H I D V H I D V H I D V H I D V H I D V H I D V Boiler Operating Pressure
0-1� 1� 1 � 2½ �0 1¼ � � �0 1½ � � �0 � � � �� 2½ � 6 �� � 6 �16-�0 �0 1 � 2½ �0 1¼ � � �� 1½ � � �� � � � �� 2½ � 6 �� � 6 �
�1-100 �0 1 � 2½ �� 1¼ � � �� 1½ � � �� � � � �� 2½ 6 6 �� � 8 6101-1�� �� 1 � � �� 1¼ � � �� 1½ � � �� � � � �6 2½ 6 6 — — — —1�6-1�0 �� 1 � � �� 1¼ � � �� 1½ � � �6 � � 6 �6 2½ 6 6 — — — —1�1-17� �� 1 � � �� 1¼ � � �� 1½ � � �6 � � 6 �6 2½ 6 8 — — — —176-�00 �� 1 � � �� 1¼ � � �6 1½ � � �6 � 6 6 �6 2½ 6 8 — — — —�01-��� �� 1 � � �6 1¼ � � �6 1½ � � �6 � 6 6 �6 2½ 8 8 — — — —
**��6-�00 �6 1 � � �6 1¼ � � �6 1½ � 6 �6 � 6 6 �6 2½ 8 8 — — — —
Chart A — Boiler Blowdown Separators
*Minature Boilers: ½” - 1” Blowdown Valve up to 1000 #/hr. Blowdown use 14” high, 1” Inlet, 2” Drain, 2½” Vent. ** 251 - 300 PSIG required. U Symbol Construction and Stamping. See price sheet for adder.
Chart B — Cooling Water Line and Valve SizeSeparator Inlet Size 1” 1¼” 1½” 2” 2½” 3”Cooling Water Pressure (PSI) 40# 60# 80# 40# 60# 80# 40# 60# 80# 40# 60# 80# 40# 60# 80# 40# 60# 80# Boiler Operating Pressure
0-�0 ½ ½ ½ 1 1 ¾ 1¼ 1 1 1¼ 1¼ 1¼ 1½ 1½ 1¼ � � �
Usefor�0-70°FCooling Water Temperature
�1-100 1 ¾ ¾ 1 1 1 1¼ 1¼ 1 1½ 1¼ 1¼ � � � 2½ 2½ �101-1�� 1 ¾ ¾ 1¼ 1 1 1¼ 1¼ 1¼ � 1½ 1¼ � � � 2½ 2½ 2½1�6-17� 1 1 1 1¼ 1¼ 1 1¼ 1¼ 1¼ � � 1½ 2½ � � 2½ 2½ 2½176-��� 1 1 1 1¼ 1¼ 1¼ 1½ 1¼ 1¼ � � � 2½ � � � 2½ 2½��6-��0 1¼ 1¼ 1 1¼ 1¼ 1¼ 1½ 1¼ 1¼ � � � 2½ � � � 2½ 2½��1-�00 1¼ 1¼ 1 1¼ 1¼ 1¼ 1½ 1¼ 1¼ � � � 2½ 2½ � � � 2½
0-�0 ¾ ½ ½ 1 1 1 1 1 1 1¼ 1¼ 1¼ � 1½ 1½ 2½ � �
Usefor71-80°FCooling Water Temperature
�1-100 1 ¾ ¾ 1¼ 1 1 1¼ 1¼ 1¼ � 1½ 1¼ � � � 2½ 2½ �101-1�� 1 1 ¾ 1¼ 1¼ 1 1¼ 1¼ 1¼ � � 1½ 2½ � � 2½ 2½ 2½1�6-17� 1 1 1 1¼ 1¼ 1¼ 1¼ 1¼ 1¼ � � � 2½ � � � 2½ 2½176-��� 1 1 1 1¼ 1¼ 1¼ 1¼ 1¼ 1¼ � � � 2½ 2½ � � � 2½��6-��0 1¼ 1¼ 1 1¼ 1¼ 1¼ 1¼ 1¼ 1¼ 2½ � � 2½ 2½ � � � 2½��1-�00 1¼ 1¼ 1¼ 1½ 1¼ 1 1½ 1½ 1½ 2½ � � 2½ 2½ 2½ � � 2½
66 67
Surface Blowdown Solid State Intermittent Sampling
•Controlsboilertotaldissolvedsolids(TDS)using conductivitymeasurementandautomaticsurface blowdownviaintermittentsampling.
•Adjustableintervaltimer(1/�-�hours) periodicallyopensanelectricvalvetosample boilerwaterconductivity.
• Ifthesampleisbelowthemicromhossetpoint onthepotentiometer,blowdownisnotrequired andthevalvewillclose.Ifthesampleisabove themicromhossetpointonthepotentiometer, blowdownisrequired,andthevalvewill remainopen.
•Adjustablesampledurationtimer(1�-10 minutes)againsamplestodetermineif sampleisbelowthemicromhossetpoint onthepotentiometertopermitthevalvetoclose.
•Completesystemincludes:enclosure, potentiometer,twotimersandLEDlights.
•Valveassembliespurchasedseparatelyinclude: solenoidormotor-operatedfactory-pipedvalve withprobe,teeassemblyandorificekit.
Conductivity Controller
•1�0VAC,�0/60HZ,1�amp
•Solidstateelectronics
•NEMA�Xenclosure
66 67
Conductivity Controller(Surface blowdown solid state intermittent sampling)
Conductivity Range 0-7,000Microsiemens/cm.
Sample Timers Interval:1�Minutesto�Hours/Duration:�0Secondsto10Minutes
Display LED Indicators:Power,BlowdownandConductivityCalibration
Accuracy +/-�00Microsiemens
Drift Lessthan0.��%PerMonth
Input Power 11�VAC,�0/60HZ,10Amps
Output/Control 115 VAC, 50/60 HZ, 10 Amps. Maximum Combined Load / Pre-wired for 2 or 4 Wire Blowdown Valve
Environment Ambient Temperature:�0°Fto1�0°F(�°Cto60°C)Humidity:1-100%R.H.Non-condensing
Enclosure Nema 4X Weatherproof. See through Door with Padlockable Hasp. (3) 7/8” Diameter Holes Provided for 1/2” Conduit Connections: Blowdown Valve, AC Power, Probe and Optional Electrical Device.
Dimensions H. 10” x W. 8” x D. 4” (25 x 20 x 10 cm)
Net Weight 5.89 Lbs. (2.67 Kgs.) / 7.43 Lbs (3.48 Kgs.) - With Flow through Plumbing Assembly
Note: Specifications subject to change without prior notice.
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
68 69
•Exchanges"soft"sodiumionsfor"hard"calcium andmagnesiumions.
• BS-Modelrange: �0-�/�throughBS-1�00-�,twinorsingle (�0,000grainat8GPMthrough1,�00,000 grainat�80GPM).• BP-Modelrange: �0-�/�throughBP-600-�,twinorsingle (�0,000grainat8GPMthrough600,000 grainat��0GPM).
•Available in alternating "twin" configuration with flow meter and VIP computer demand controller or "single" configuration with time clock regeneration.Alternatingtwinsystemmaybe runinparalleltwinmode.•Modular configuration to meet customer requirementsforalternatingsystemincludes: resintanks,resin,gravel,brinetank,control valve, blocking valves, flow meter and VIP computerdemandcontroller.
•VIPcomputerdemandcontrollerstandard.
•BS-Resintanks: Steel"polybond"linedandprimed,pressure- testedto100psig,non-codestamped (codestampedresintanksavailable).
• BP-Resintanks: fiberglass reinforced polyester, pressure-tested, non-codestamped(codestampedresintanks NOTavailable).
Water Softener SystemsBS & BP
Steel Tanks Electronic Demand Controller Features
•Providedwithindustrystandard�0,000grainper cubicfootresin.
•Fleckcontrolvalvestandard.
•BS-Skidmounting(pre-piped/pre-wired) availableasoption.
• BP-SkidmountingNOTavailable.
68 69
Twin Drawing Number
Single Drawing Number
Model Type
Model Number
Cap. MaxGrains (1,000) Cu. Ft.
per Tank
Continuous Peak Drain Flow Max
Tank Dimensions Salt
Cap.Lbs.
Regeneration
Max. Min.GPM Flow
PSI Drop
GPM Flow
PSI Drop Resin Brine
Max.Lbs.
Min.Lbs.
900225-1 900252-1 32Z BS-30-.75 30 20 1 8 4 12 7 2 10 x 52 18 x 38 400 15 6
900225-3 900252-3 62A BS-60-1 60 40 2 17 15 24 20 3 12 x 52 18 x 38 400 30 12
900225-4 900252-4 92A BS-90-1 90 60 3 21 15 29 25 5 14 x 66 18 x 38 400 45 18
900226-1 900253-1 92B BS-90-1.5 90 60 3 24 9 36 16 5 14 x 66 18 x 38 400 45 18
900226-2 900253-2 122B BS-120-1.5 120 80 4 32 12 48 22 7 18 x 66 21 x 43 450 60 24
900226-3 900253-3 152B BS-150-1.5 150 100 5 40 13 58 25 7 18 x 66 21 x 43 450 75 30
900226-4 900253-4 182B BS-180-1.5 180 120 6 42 15 59 25 10 18 x 66 27 x 51 1000 90 36
900226-5 900253-5 212B BS-210-1.5 210 140 7 45 15 60 25 10 24 x 66 27 x 51 1000 105 42
900226-6 900253-6 242B BS-240-1.5 240 160 8 45 15 60 25 10 24 x 66 27 x 51 1000 120 48
900226-7 900253-7 272B BS-270-1.5 270 180 9 45 15 60 25 10 24 x 66 27 x 51 1000 135 54
900226-8 900253-8 302B BS-300-1.5 300 200 10 45 15 60 25 15 24 x 66 27 x 51 1000 150 60
900227-1 900254-1 122C BS-120-2 120 80 4 32 7 48 12 15 18 x 66 27 x 51 450 60 24
900227-2 900254-2 152C BS-150-2 150 100 5 40 6 60 11 15 18 x 66 27 x 51 450 75 30
900227-3 900254-3 182C BS-180-2 180 120 6 48 9 72 15 15 18 x 66 27 x 51 1000 90 36
900227-4 900254-4 212C BS-210-2 210 140 7 58 8 84 15 15 24 x 66 27 x 51 1000 105 42
900227-5 900254-5 242C BS-240-2 240 160 8 64 11 96 20 15 24 x 66 27 x 51 1000 120 48
900227-6 900254-6 272C BS-270-2 270 180 9 72 13 108 25 15 24 x 66 27 x 51 1000 135 54
900227-7 900254-7 302C BS-300-2 300 200 10 78 15 108 25 15 24 x 66 27 x 51 1000 150 60
900227-8 900254-8 452C BS-450-2 450 300 15 87 15 118 25 20 30 x 66 32 x 51 1500 225 90
900227-9 900254-9 602C BS-600-2 600 400 20 94 15 125 25 25 36 x 71 42 x 51 2500 300 120
900228-1 900255-1 602E BS-600-3 600 400 20 160 15 240 25 30 36 x 71 42 x 51 2500 300 120
900228-2 900255-2 902E BS-900-3 900 600 30 200 15 270 25 40 42 x 71 42 x 51 2500 450 180
900228-3 900225-3 1202E BS-1200-3 1200 800 40 210 15 280 25 50 48 x 71 52 x 60 4500 600 240NOTE: Some flow rates are shown at a rate less than the standard 15 PSI drop for continuous and 25 PSI drop for decreased softening capacity as these flows are exceeded.
NOTE: Some flow rates are shown at a rate less than the standard 15 PSI drop for continuous and 25 PSI drop for decreased softening capacity as these flows are exceeded.
Twin Drawing Number
Single Drawing Number
Model Type
Model Number
Cap. MaxGrains (1,000)
Cu. Ft.per
Tank
Continuous PeakDrain Flow Max
Tank DimensionsSalt Cap.Lbs.
Regeneration
Max. Min.GPM Flow
PSI Drop
GPM Flow
PSI Drop Resin Brine
Max.Lbs.
Min.Lbs.
900245-1 900232-1 31Z BP-30-.75 30 20 1 8 4 12 7 2 9 x 48 18 x 38 400 15 6
900245-3 900232-3 61A BP-60-1 60 40 2 16 10 24 20 3 12 x 52 18 x 38 400 30 12
900245-4 900232-4 91A BP-90-1 90 60 3 21 15 29 25 5 14 x 65 18 x 38 400 45 18
900246-1 900233-1 91B BP-90-1.5 90 60 3 24 9 36 16 5 14 x 65 18 x 38 400 45 18
900246-2 900233-2 121B BP-120-1.5 120 80 4 32 11 48 20 7 17 x 58 21 x 43 450 60 24
900246-3 900233-3 151B BP-150-1.5 150 100 5 36 15 52 25 7 17 x 72 21 x 43 450 75 30
900246-4 900233-4 181B BP-180-1.5 180 120 6 38 15 56 25 7 17 x 72 27 x 51 1000 90 36
900246-5 900233-5 211B BP-210-1.5 210 140 7 45 15 60 25 15 24 x 71 27 x 51 1000 105 42
900246-6 900233-6 241B BP-240-1.5 240 160 8 45 15 60 25 15 24 x 71 27 x 51 1000 120 48
900246-7 900233-7 271B BP-270-1.5 270 180 9 45 15 60 25 15 24 x 71 27 x 51 1000 135 54
900246-8 900233-8 301B BP-300-1.5 300 200 10 45 15 60 25 15 24 x 71 27 x 51 1000 150 60
900247-1 900234-1 121C BP-120-2 120 80 4 32 6 48 10 7 17 x 58 21 x 43 450 60 24
900247-2 900234-2 151C BP-150-2 150 100 5 40 10 60 16 7 17 x 72 21 x 43 450 75 30
900247-3 900234-3 181C BP-180-2 180 120 6 48 9 72 23 7 17 x 72 27 x 51 1000 90 36
900247-4 900234-4 211C BP-210-2 210 140 7 56 8 84 15 15 24 x 71 27 x 51 1000 105 42
900247-5 900234-5 241C BP-240-2 240 160 8 64 11 96 20 15 24 x 71 27 x 51 1000 120 48
900247-6 900234-6 271C BP-270-2 270 180 9 72 13 108 25 15 24 x 71 27 x 51 1000 135 54
900247-7 900234-7 301C BP-300-2 300 200 10 78 15 108 25 15 24 x 71 27 x 51 1000 150 60
900247-8 900234-8 451C BP-450-2 450 300 15 87 15 118 25 20 30 x 72 32 x 51 1500 225 90
900247-9 900234-9 601C BP-600-2 600 400 20 94 15 125 25 25 36 x 72 42 x 51 2500 300 120
900248-1 900235-1 601E BP-600-3 600 400 20 160 14 240 24 25 36 x 72 42 x 51 2500 300 120
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
70 71
horizontal and Integral DeaeratorsThespraytypedeaeratorisratedforoxygenremovalto.00�cc/I(7PPB)andCO�tozeromeasurableacrossitsentireoperating range. With its all stainless steel spring-loaded spray valve and second stage steam scrubber, the spray typedeaeratorisagoodchoiceforalldeaeratorapplications.Unitsareavailablewithacompleterangeofboilerfeedpumps and control options making them a total deaerator package with minimal amount of field assembly.
horizontal Tank Design Integral Tank Design
Performance Features•Oxygenremovalto.00�cc/I(7PPB)•CO�removalto0%measurable•Reducechemicalcosts•Reduceboilerandsystemcorrosion• Improve boiler efficiency•Pre-heatboilerfeedwater•Quickequipmentpaybackcomparedtochemical oxygenremoval
Construction Features•ConstructedtoASMESectionVIII,Division1for �0PSIG•Easilyaccessiblemanway•Standardtenminutedeaeratorstorage• Internalventcondenserforminimumsteamloss•Self-adjustingspring-loadedstainlesssteelsprayvalve• Structuralsteelstand/pumpplatform•Two-stagedeaeration•Availableascompletelypackagedunitincludingpumps andcontrolpanel
70 71
horizontal and Integral Deaerators
Highwaterlevelcontrol
Lowwaterlevelcontrol
Make-upwatercontrol
Vacuumbreaker
Temperaturegauge
Pressuregauge
Overflow trap
Vent
horizontal Tank Design Integral Tank Design
Pumpsuction
Pumpbypass
Chemicalport
Drain
Sampleport
Hightemperaturecondensatereturn
Gaugeglass
Manwayaccessopening
9
16
15
14
13
12
11
10
1
8
7
6
5
4
3
2
©�006BurnhamCommercial-Lancaster,PAPhone:1-888-791-�790www.burnhamcommercial.com
7� 7�
Engineering & Application Data
7� 7�
ENG-�
7� 7�
ENG-�
7� 7�
76 77
76 77
78 79
78 79
80 81
80 81
8� 8�
8� 8�
8� 8�
8� 8�
86 87
86 87
88 89
88 89
90 91
90 91
9� 9�
9� 9�
PRICES AND TERMS OF PAYMENTA. Prices quoted are firm for no more then 30 days from the date of quotation
subject to any conditions stated in Seller’s quotation or in an order submittedby Buyer and expressly accepted in writing by Seller. Seller will not be boundby any price sheet or quote other then a price quote signed by an authorizedrepresentative of Seller.
B. Prices on orders accepted by Seller are firm, to the extent stated in theaccepted order, subject to the following:1. The purchase order must provide for shipment within six months of the
date of purchase order.2. Any shipment made more then six months after such a date is subject to a
price adjustment, at Seller’s sole discretion, to the Seller’s price in effect atthe time of shipment, which will not exceed 125% of the price on theacknowledged purchase order.
3. Any shipment more then 12 months after the date of purchase order will beinvoiced at Seller’s price in effect at the time of shipment.
C. On orders having a total price of less then $100,000 payment will be due “netin 30 days” from date of shipment, unless otherwise specifically agreed bySeller. On orders having a total purchase prices of $100,000 or more termsare 10% with order, 45% upon Seller’s receipt of Buyer’s approval of drawings,45% within 30 days after shipment and 5% at the start-up of the products orwithin 90 days of shipment, which ever occurs sooner.
D. The price of parts, components and other items not manufactured by Seller issubject to adjustments by Seller to reflect price changes by Seller’s suppliers.
E. Orders accepted by Seller are subject to credit investigation and approval. IfBuyer’s financial condition at any time does not justify the terms specified,Seller may require payment in advance of shipment or, if shipment has beenmade, recover shipment from the carrier. A service charge of 1-1/2% permonth will be added to all accounts 30 days past due.
F. Any tax or governmental change now or hereafter levied upon the production,sale, use or shipment of products ordered or sold will be charged to and paidby the Buyer, unless the Buyer has provided Seller with a tax exemptioncertification acceptable to the applicable taxing authorities. Such taxes are notcovered in the selling price unless expressly stated on the quotation form.
SECURITY INTERESTSNot withstanding transfer of title to Buyer, the Seller retains and the Buyerhereby grants to the Seller a purchase money security interest in all productssold, and Buyer hereby irrevocably appoints Seller as its attorney-in-fact toexecute and deliver, in Buyer’s name, any such financing statement of otherdocuments as may be necessary under the Uniform Commercial Code or otherapplicable laws governing the items sold herein to perfect Seller’s interest therein.
Buyer will obtain and maintain insurance against the loss or damage naming Selleras an additional insured in an amount sufficient to protect Seller’s interest in allproducts until the purchase price has been paid in full.
CHANGES, ORDERS AND CANCELLATIONSeller may adjust the selling price to cover any requested change in specificationor other terms after the receipt of the Buyer’s order. Orders accepted byBurnham Commercial shall not be canceled by the Buyer except at BurnhamCommercial’s sole discretion. In the event of any cancellation, BurnhamCommercial reserves the right to impose a cancellation charge sufficient to coverall losses and out-of-pocket costs incurred by Seller in connection to such order,including materials and labor charges and cancellation charges from vendors, plusa cancellation charge of 20% of the original face amount of the order tocompensate the Seller for its loss in profit.
RETURNED GOODSProducts may not be returned for refund or credit until after Seller has agreed toaccept them. Inspection by a Seller representative may be required before returnauthorization is granted. A minimum restocking and handling charge of 25% (pluscost of any missing parts or components and inbound freight) will apply to allsuch returned products. All transportation charges for such products must be paidby Buyer.
TRANSPORTATION TERMS AND CLAIMSUnless otherwise stated on Seller’s quotation form, all process are F.O.B Seller’sshipping point. Delivery to the initial carrier shall constitute delivery to the Buyer.Seller’s responsibility ceases and title the goods passes, subject to Seller’ssecurity interests upon delivery in good order to such carrier, and all products areshipped at the Buyer’s risk. The Buyer agrees to examine all deliveries carefullybefore signing transportation receipts. If products are visibly damaged the Buyershall require that written confirmation of damage be noted on the carrier’sdelivery receipt and confirmed by the driver for the carrier. If damage isdiscovered after unpacking, the carrier shall be notified at once so that aninspection can be made and the claimed damage substantiated by the carrier.
FORCE MAJEURE AND STORAGEA. Seller shall not be liable for any delay or failure in the delivery or shipment of
products or for any damages suffered by reason of such delay or failuredirectly or indirectly, due to fire, flood, other weather conditions, accident,riots, war, embargo, labor stoppages, inadequate transportation facilities,shortage of materials or supplies, regulation by government authority or anycause beyond the Seller’s control.
B. Seller reserves the right to allocate available production among its customersin any fair and reasonable manner that it determines is necessary ordesirable.
C. If delivery is delayed due to any cause beyond the Seller’s control, Buyershall reimburse Seller for any added costs. Without limiting the foregoing,product on which manufacturer or delivery is delayed due to cause may beplaced in storage by Seller, for the Buyers account and risk, and regularcharges therefore and expense in connection therewith shall be paid by theBuyer. If, in Seller’s opinion, it is unable to obtain or continue such storage,the Buyer will, on request, provide or arrange for suitable storage facilities andassume all costs and risks in connection therewith.
SHORTAGES, VARIANCES AND WEIGHTSNo claims for variance from or shortages in orders will be considered unlesspresent within 30 days after receipt of products. Any shipping weights are givenor estimated are approximate, for the Buyer’s convenience only, and notguaranteed by Seller.
LIMITS OF LIABILITYAny action by Buyer on this contract, must be commenced within one year afterthe cause of action accrues. Actions on Seller’s Warranties shall be limited asprovided therein. Seller shall in no event have any liability for any liquidated
TERMS AND CONDITIONS OF SALE FOR BURNHAM COMMERCIAL STEEL BOILERSdamages, consequential damages or penalties, whether on account of lost profits,or otherwise, unless specifically agree in writing signed by an authorizedrepresentative of Seller.
PRODUCT CHANGESSeller reserves the right to make changes in products of any kind without priornotice, and to deliver revised designs or models of products against any order.Seller shall have no responsibility whatsoever with respect to changes made bythe manufacturer of products sold but not manufactured by it.
PATENTSProducts manufactured and sold by Seller may be used by the Buyer pursuant tosuch patent rights as Seller may own or enjoy. Seller shall not liable for any usesuch products may be put as part of any system, mechanism or process coveredby patent rights of others.
TESTSAny tests requested by the Buyer to determine the performance of productscovered by Seller’s quotation, must utilize procedures acceptable to Seller and theBuyer is responsible for costs thereof. Whenever an order includes start-up orservice agreement, Seller shall not be obliged to provide start-up or other serviceas long as payment to Seller is default.
CONFLICTING PROVISIONS OFFERED BY BUYERAny terms and conditions of Buyer’s purchase order which are different, from, inaddition to inconsistent with the terms and conditions contained herein, are herebyobjected to, and will not be binding on Seller in any manner whatsoever unlessaccepted by Seller in writing. Seller shall ship products referred to in this documentonly on the condition that the terms and conditions of sale set forth hereon shallbe binding on the Buyer.
APPLICABLE LAWAny order or contracts received by Seller from Buyer shall be governed by,construed and enforced by the laws of the Commonwealth of Pennsylvania.
COMPLETE AGREEMENTThe complete agreement between Seller and Buyer is contained herein and anyspecifications signed by the Seller, and no additional or different terms orconditions stated by Buyer shall be binding unless agreed to by Seller in writing.Neither course of dealings, not usage of trade shall be relevant to supplement orexplain any terms used in this Agreement, and this Agreement may be modifiedonly by a writing signed by both Seller and Buyer. The failure of Seller to insistupon strict performance of any of the terms and conditions stated herein shall notbe considered as a continuing waiver of any such terms and conditions or any ofSeller’s other rights.
CHANGES IN TERMSThese terms and conditions of sale are subject to change by Seller from time totime without prior notice.
LIMITED WARRANTYSubject to the terms and conditions herein, Seller warrants to the original owner atthe original installation site that products manufactured by Seller (“Products”)comply, at the time of manufacture, with recognized hydronics industry regulatoryagency standards and requirements therein effect and will be free from defects inmaterials and workmanship for a period of 12 months after the date of start-up or18 months after the date of shipment, whichever shall be less (the “WarrantyPeriod”)
REMEDYA. The sole remedy for breach of this warranty is expressly limited to the repair
or replacement of any part found to be defective under conditions of normaluse within the Warranty Period. Installation is not included.
B. Warranty – The owner must notify the original installer of the Product andSeller (Attention: Burnham Commercial, PO Box 3939, Lancaster, PA 17604) inwriting, within the Warranty Period, providing a detailed description of allclaimed defects. Transportation to a factory or other designated facility forrepairs or any products or alleged defective shall, in all events, be theresponsibility and at the cost of the owner.
EXCLUSIONSSeller shall have no liability for:A. Incidental, special or consequential damages, such as loss of the use of
products, facilities or production, inconvenience, loss of time or labor expenseinvolved in the repairing or replacing of the alleged defective product.
B. The performance of any Product under conditions varying materially fromthose under such Products is usually tested under industry standards as ofthe shipment time.
C. Any damage to the Product due to abrasion, erosion, corrosion, deterioration,abnormal temperatures or the influence of foreign matter or energy.
D. The design or operation of owner’s plant or equipment or of any facility orsystem of which any Product may be made a part.
E. The suitability of any Product for any particular application.F. Any failure resulting from misuse, modification, not authorized by Seller in
writing, improper installation or lack of proper maintenance.G. Equipment furnished by the owner, either mounted or unmounted, or when
contracted for by owner to be installed or handled.
Seller’s liability under this warranty shall not in any case exceed the amount paidfor the Product found defective.
THIRD-PARTY WARRANTIESFor goods or components not manufactured by Seller, the warranty obligations orSeller shall, in all respects, conform and be limited to the warranty actuallyextended to Seller by its vendors.
SEVERABILITYTo the extent that any provisions of this warranty would be void or prohibited underapplicable law, such provisions shall be limited in effect to the minimum extentnecessary to render the remaining provisions hereof enforceable.
NO OTHER WARRANTIESSeller makes no implied warranty of merchantability or fitness for a particularpurpose, or other warranties with respect to any products or services except asexpressly set forth in this limited warranty.
LIMITED WARRANTY
Form No. PL8146561001 - 4/04