Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017...

24
Alliance Control Panel Installation Manual Models: AL-2017 AL-3017 g GE Security

Transcript of Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017...

Page 1: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

Alliance Control Panel

Installation ManualModels: AL-2017

AL-3017

g

GESecurity

Page 2: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

1AL-2017/AL-3017 Installation Manual

Contents

Introduction ............................................................................................................. 2

Installation................................................................................................................ 3

System Wiring .......................................................................................................... 5

Earth grounding ...................................................................................................................................... 5

System bus connection ........................................................................................................................... 5

Shielded cable routing ............................................................................................................................ 6

Auxiliary power supply connections ...................................................................................................... 6

PSTN wiring ........................................................................................................................................... 7

AL-2017/AL-3017 Wiring ....................................................................................... 8

Basic Programming ............................................................................................... 10

Programming Steps ............................................................................................... 12

Text words ............................................................................................................................................ 12

Time zones ............................................................................................................................................ 12

Areas ..................................................................................................................................................... 12

Alarm groups ........................................................................................................................................ 13

Remote arming stations (RAS) ............................................................................................................. 13

Data gathering panels (DGP) ............................................................................................................... 13

Zone (inputs) ........................................................................................................................................ 14

Communication options ....................................................................................................................... 15

New installer code ................................................................................................................................ 15

Relays (outputs) .................................................................................................................................... 16

Battery Capacity .................................................................................................... 17

Battery calculation worksheet example ................................................................................................ 18

Absolute maximum loads ..................................................................................................................... 18

Battery calculation worksheet .............................................................................................................. 19

FCC Compliance.................................................................................................... 20

UL Compliance ...................................................................................................... 20

Specifications .......................................................................................................... 22

© 2009 GE Security. All rights reserved. No part of this publication may be reproduced, transmitted, stored in a retrieval system, ortransmitted in any form, or by any means – electronic, photocopying, recording, or otherwise – without the prior written permission of GESecurity. GE Security reserves the right to change information without notice.

Page 3: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

2 AL-2017/AL-3017 Installation Manual

Introduction

This manual covers the information needed to install and set up the Alliance AL-2017/AL-3017 control panels including system wiringand basic programming steps. See the Alliance System Programming Manual for complete planning and programming details for theAlliance system, including a programming map and a system glossary.

Planning the systemIt is important to create a comprehensive system plan prior to installing the Alliance system. This plan should include a site map, acomponent and equipment list, a zone list, a type list, an area list, a region list and the number of users.

Memory expansion options for the AL-3017 (AL-2017 does not support memory expansion)AL-1830 memory expansion is a special option installed into the AL-3017 control panel to increase the memory capacity as detailedbelow:

AL-1830 1M memory expansionUsers 50 11,466

Door Groups 10 128Floor Groups 10 64

History:

Alarm System Events 100 1,000

Access Control Events 100 1,000

Page 4: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

3AL-2017/AL-3017 Installation Manual

InstallationEach Alliance system control panel is shipped with the following hardware:

• Two and three position terminal blocks that can be combined to provide a variety of terminal block configurations

• Clip-in and screw-in male/female standoffs

• Mounting screws

• Battery wires

CAUTION You must be free of static electricity before handling circuit boards. Wear a grounding strap or touch a baremetal surface to discharge static electricity.

To install the controller, do the following:

1. Mount the enclosureA suitable mounting location should include easy access for wiring, good lighting, suitable access to power and earth ground, and amplespace to work. The mounting surface should be flat and dry. We do not recommend mounting metal enclosures directly onto concretewalls. Check with local authorities to verify local codes regarding metal enclosure mounting.

Note: To maintain compliance with UL 365, UL 690, and UL 1610, the main control panel must be installed within a safe, vault,or Extent #1 stockroom.

All of the Alliance System enclosures contain four mounting holes located in the corners of the enclosures. Use appropriate mountinghardware to mount the enclosure to the mounting surface and the batteries to the enclosure as shown in Figure 2.

2. Install the standoffsBefore the control panel can be installed, the appropriate standoffs must be configured. Use male/female standoffs where threaded holesare aligned with the mounting holes on the control panel and use clip-in standoffs where square holes are aligned with the mounting holes(Figure 3).

3. Install the transformerMount the transformer in the enclosure using two 6/32 x 1/4” screws provided with the transformer. Install the rubber grommet into thetransformer shield and mount it to the enclosure using four 6/32 x 1/4” screws provided with the transformer.

4. Earth/chassis ground standoffsIt is important that proper grounding is provided to the enclosure. Use two male/female standoffs provided with the enclosure to secureboth the earth ground and enclosure ground wires. When securing the ground wires, use the internal tooth star washers provided with theenclosure between the standoff and the wire connector. All connections should be tight and make a good electrical connection.

5. Install the tamper switchAssemble the tamper switch assembly per the instructions provided with the tamper switch. Mount the switch assembly using the three 6/32 x 1/4” screws provided.

6. Install the control panel boardSlide the terminal blocks together as shown in Figure 1. Slide the blocks over the appropriate pins indicated on the board. Mount the boardusing four 6/32 x 1/4” screws along with internal star washers. To ensure proper ground, tighten screws securely. See Figure 3 for propermounting orientation.

7. FerritesTo be compliant with FCC Part 15B, ferrites must be installed on each of the AC wires (Figure 2). Refer to the instructions provided withthe ferrites for mounting details.

Figure 1. Terminal blocks

Page 5: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

4 AL-2017/AL-3017 Installation Manual

AL-2017/AL-3017Board

Figure 3. Layout diagrams

Figure 2. Enclosure

Optionalaccessoryboards

PSTN (PublicSwitchedTelephone Network)

120 VAC

24 VAC, 100VA

12 V battery,refer to Battery calculationworksheet for appropriatebattery type.

Chassisground

Enclosure mounting screws

Chassis groundconnection

Earthgroundconnection

Enclosure mountingscrew

Tamper switchaccess hole

Ferrites

Enclosure mountingscrew

Optional boardmounting holes

AL-2017/AL-3017mounting holes

AL-2017/AL-3017

AL-2017/AL-3017

Optionalboards

Optionalboards

Page 6: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

5AL-2017/AL-3017 Installation Manual

System WiringAll panel wiring should be kept well away from other wiring, avoiding parallel wire runs with other wires. Where parallel wires areunavoidable, keep wires a minimum of 2 inches apart, or in EMT. We recommend that Alliance system components that use direct wiretransformers be wired into a dedicated circuit breaker and those that use plug-in transformers be plugged into an unswitched outlet.

Earth groundWARNING Each control panel or device which mounts in a metal enclosure, must have its enclosure connected to earth

ground. Correct earth grounding procedure must be followed.

Earth grounding one enclosure containing several devicesAll devices designed for the system have chassis ground connections via metal studs to the metal enclosure. Take care that these metalstuds make good connection to the enclosure (beware of paint). The earth connections of every piece of equipment in the system can beused for connecting the shielding of shielded cables. If a device, such as a keypad, is placed in a plastic enclosure the earth lug of thisdevice does not have to be connected.

Earth grounding panels in a single buildingIf several enclosures or devices are connected to earth ground in one building, the safety earth ground of this building has to be checked bya licensed contractor.

Earth grounding panels in multiple buildingsIf the wiring extends to separated buildings, more than one common earth ground system will be used. Use isolater/repeaters to isolate thesystem bus. In this way the system is protected against variations in earth potential.

System bus connectionThe system bus (COMMS) is used to connect data gathering panels (DGP) to provide extra zones, and remote arming stations (RAS) to theAlliance system control panel. Remote devices can be up to 5,000 feet (1.5 km) from an Alliance system control panel. DGP and RASdevices must be connected via a 2-pair twisted, shielded data cable from the system bus connection (Belden 8723 is recommended). Theshield of the data cable should be connected to earth at the Alliance system control panel and should be left disconnected at any other end.We recommend that where the distance between the arming station and the nearest device is more than 328 feet (100 meters), a separatepower supply be used to power the arming station. To power the arming station, do not connect ‘+’ from the system bus. Connect ‘+’ ofthe local power supply to ‘+’ on the arming station and connect 0 volts from the power supply and 0 volts from the system bus to thearming station terminal marked ‘-’.

Note: The first and last devices on the system bus must be terminated. All other devices on the system bus must notbe terminated.

Figure 4. System bus connection

System bus

D-D+0V+12D-D+0V+12D-D+OV

12V Connection

Control panelRASDGP

Page 7: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

6 AL-2017/AL-3017 Installation Manual

Figure 5. Shielded cable routing

Figure 6. Auxiliary power supply connections

Shielded cable routingThe shielding of all shielded cables used in the system should only be connected at ONE side to one common earthing point in a building.If a shielded bus cable is routed via more than one plastic device, the shielding from incoming and out-going cable has to be connected.

Note: Metal chassis must be earth grounded. Splice shield drain wire at all juntions.

Auxiliary power supply connectionsIn systems in which expansion module power is not supplied by the main control panel or an AC-powered DGP with auxiliary outputs, aUL Listed power supply suitable for burglar alarm applications, such as the Altronix AL300ULX, must be utilized.

Note: Tie all 0V together. Do not connect the +12V together.

Cable shield drain wire

Shield drainwire ground

System bus

D-D+0V+12D-D+0V+12D-D+OV

Control panelRASDGP

Altronix AL300ULXauxiliary power supply

- +

D-D+0V+12D-D+0V+12D-D+OV

Control panelRASDGP

Page 8: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

7AL-2017/AL-3017 Installation Manual

PSTN wiring

Figure 7 shows how to wire the control panel to PSTN connection. This equipment complies with FCC Part 68 rules. US: GEIAL07B3-4000

Note: We recommend that the system be wired to a dedicated PSTN line.

Figure 7. PSTN Wiring Diagram

AL-2017/AL-3017control panel

Chassisground

Bx A

x B A

PSTNconnection

Tip Green

Ring Red

RJ31X

RJ45

RJ11/12

Premises phone

Premises (Tip)

Premises (Ring)

Note: A - To Pin 5 on RJ45 CableB - To Pin 4 on RJ45 CableAX - To Pin 1 on RJ45 CableBX - To Pin 8 on RJ45 Cable

Page 9: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

8 AL-2017/AL-3017 Installation Manual

Figure 8. Non-power and power limited wiring

AL-2017/AL-3017 WiringKeep non-power limited wiring away (1/4” minimum) from power limited wiring as shown in Figure 8. Disconnect the AC mains powervia a dedicated circuit breaker before servicing.

Figure 9. AL-2017/AL-3017 control panel components

Power limited wiring

Powerlimitedwiring

Non-powerlimitedwiring

Non-powerlimitedwiring

Optionalaccessoryboards

PSTNconnection

AL-2017/AL-3017

J18

J20

PSTN connection

Expansion

ACBattery

Aux. PowerSirensStrobe

Bell

L1

J1 J7

Kill

Comms/Tamper Zone (inputs)

RXTX

RXTX

Modem

Comms

Control panel wiring connectionsFigure 9 shows the AL-2017/AL-3017 control panel components and Figures 10 and 11 provide wiring connection details.

J1, to AL-1810/AL-1813 relay output moduleJ7, to AL-1206 zone expansion module

Page 10: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

9AL-2017/AL-3017 Installation Manual

Figure 11. Zone (inputs) wiring methods

Method 1 Method 2single zone dual zone

Note: Method 2, dual zone, is not acceptablefor UL 365, UL 609, and UL 1610 compliance.

4.7K

NCOpen = Alarmor Trouble

NOClosed = Alarm

Zoneinput C

4.7K

NCOpen = Tamperor Trouble

NCOpen = Alarm

Zoneinput C

4.7K

NOClosed = Tamper

EXT

24 VAC, AL-1290 transformer kit

+

-

+

+

+

-

-

-

SW +

SW -

AC

BATT

AUX. POWER

INT

STRB

COMMS

TAMPER

BELL (relay output)

Note: Do not short circuit. Use ferriteson AC input wires.

Note: Total AUX POWER output 300mA,including +12 on COMMS.

Note: Alarm output 1 Amp total.* Siren output must be programmed forDC output if a bell is connected to theseterminals instead.A 1k resistor must be installed across theexternal siren outputs.

Note: The first and last device on thesystem bus (COMMS) must be terminated.

Ademco *AB12M.

≈≈

Note: These are dry contacts.NEG = NCPOS = NO

Note: Refer to Battery CalculationWorksheet for appropriate battery type.

Figure 10. AL-2017/AL-3017 control panel wiring connections

S +

S -

S +

S -

+

-

NEG

C

POS

8 ohm 15 watt

MPI - 35 or EQ

1K

Strobe

+12

OV

D +

D -

T

C

Alliance keypador other(BUS)(LAN)(COMM) Device

Zones (inputs)

1 C 2 3 C 4 5 C 6 7 C 8

Note: No switched auxiliary output forthe AL-2017.

Page 11: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

10 AL-2017/AL-3017 Installation Manual

Basic ProgrammingWhen you have finished installing the control panel, you can clear the panel memory, apply power and start programming.

Clear panel memoryBefore programming, the panel memory needs to be cleared. To clear the memory, do the following:

1. Remove all power to the panel (AC and battery).

2. Short the KILL jumper (Figure 9).

3. Wait 30 seconds.

4. Open the KILL jumper.

The panel memory is now cleared and restored to factory defaults.

Power up the panelOn initial power-up, the panel’s LEDs (Figure 9) should indicate:

L1 Slow flashing (micro processer is running)

Comms Tx Rapid flashing (Comms bus activity)

Comms Rx Rapid flashing (if RAS 1 is connected and functioning)

The master LCD arming station (RAS 1) should have all area LEDs lit (armed). After the RAS prompt, press MENU, then press CLEAR.If there is a system condition (such as low battery), it will be indicated on the top line of the RAS display.

If the master RAS powers up, but no LEDs lit (on) and there is not LCD display, then no power has been applied to the RAS. If the RASpowers up with all LEDs flashing and the display shows System Fault, then the system bus cabling may be faulty, or the RAS address hasbeen incorrectly set (RAS 1 address should be all DIP switches set to OFF).

Access programming menus

To disarm the system, enter 1122 (the default Manager PIN code), press OFF,and enter 0 (select all areas).

To enter the system menu, press MENU, enter 1278 (default Installer PIN), andpress ENTER.

To access installer programming, enter 19 (installer programming menu), andpress ENTER.

To choose the advanced menu option, press MENU. To choose the simplemenu option, press ENTER.

Note: The simple menu option will limit access to a number of options in the Installer Programming Menu. We recommend thatyou always choose the advanced menu option.

00:00 01/01/2003Code:

0-Exit ENTER-Down, *Up0-Exit, Menu:

Simple/Advanced Menu*-Advanced

Installer Programming0-Exit, Menu:

Page 12: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

11AL-2017/AL-3017 Installation Manual

27. Reserved menu

28. To remote devices

29. Computer connection

30. Printer

31. Battery testing

32. Custom LCD message

33. Program next service

34. Program system event flags

35. Program macro logic

36. Reserved menu

37. Reserved menu

38. Reserved menu

39. Reserved menu

40. Reserved menu

41. Reserved menu

42. Reporting class database

43. Test calls

44. Reserved menu

45. Reserved menu

46. Reserved menu

47. Reserved menu

48. Reserved menu

49. Class database

50. Channel mapping

51. Engineer reset

52. Voice reporting

Installer programming menu

1. Zone database

2. Area database

3. RAS database

4. DGP database

5. Alarm groups

6. Timers

7. System options

8. Auto reset

9. Communication options

10. Program text

11. Version number

12. LED test

13. Time zones

14. Reset to default

15. Alarm group restrictions

16. Event to outputs

17. Auto arm/disarm

18. Areas assign to vaults

19. Area linking

20. System codes

21. Zone shunts

22. Time zone to follow output

23. Poll errors

24. Download to remote devices

25. Display card

26. Reserved menu

Default the panelThis option resets all programming to the factory default. All programming will be erased and all options will have the standard values. Todefault the panel, do the following:

1. Press MENU, enter 1278, and press ENTER to access the system menu.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 14 and press ENTER to access the default option.

4. Enter 99 and press ENTER.

The panel is now defaulted.

Change the time/date settingsTo set the time and date, do the following:

1. Disarm the system.

2. Press MENU, enter 1278, and press ENTER to access the System menu.

3. Enter 15 and press ENTER to access the time and date menu.

4. Enter 2 and press ENTER to set the time and date.

5. Enter the hour and press ENTER.Note: The Alliance System uses a 24-hour format. For example, noon would be entered as 12 andmidnight would be entered as 24.

6. Enter the minutes and press ENTER.

7. Enter the seconds and press ENTER.

8. Enter the day of the month and press ENTER.

9. Enter the month and press ENTER.10. Enter the year (last two digits) and press ENTER.

For further details on time and date setting options, see the Alliance System User’s Guide.

See the Alliance System Programming Manual for a complete programming map.

Page 13: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

12 AL-2017/AL-3017 Installation Manual

Programming StepsThe following programming steps are meant as an overview. For more information on each programming area, see the Alliance SystemProgramming Manual.

Text wordsProgram any needed text words that are not included in the word library. See the Alliance System Programming Manual to view the wordlibrary.

1 Press MENU, enter 1278, and press ENTER to access the system menu.

2 Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3 Enter 10 and press ENTER to access program text.

4 Enter the text word number (custom text word numbers start at 900) and press ENTER.

5 Using the number keys, enter the required letter. Press the ENTER key to advance to the next letter. Press the MENU to advance tothe next word. Press the CLEAR key to exit this menu option.

Time zonesProgram time zones to allow certain automatic functions, such as Auto Arm or only allow certain users access during predetermined timeperiods.

1. Press MENU, enter 1278, and press ENTER to access the system menu.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 13 and press ENTER to access time zone programming.

4. Enter the time zone number and press ENTER.

5. Enter the start time hour and press ENTER.

6. Enter the start time minute and press ENTER.

7. Enter the end time hour and press ENTER.

8. Enter the end time minute and press ENTER. The start and end times will display on the top line of the keypad display.

9. Press ENTER to advance to the day field.

10. Enter 1 through 7 (Sunday through Saturday) or 8 (holiday) for each day needed for this time zone and press ENTER.Repeat steps 5 through 10 for each access time needed for this time zone (four available).

AreasProgram areas to configure individual areas, or partitions, as autonomous systems, or as parts of a single larger system.

1. Press MENU, enter 1278, and press ENTER to access the system menu.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 2 and press ENTER to access the area database programming.

4. Enter the number of the area to be configured and press ENTER.

5. Program the area name numeric code by selecting one of the default names from the word library or from text words added in textword programming and press ENTER.

6. Enter the exit time for this area and press ENTER.7. Enter the entry time for this area and press ENTER.

8. Enter the event flags and press [ENTER].9. Enter the out-of-hours time zone, if required, and press ENTER.

10. Enter the area disarmed time (used in conjuction with the alarm group restriction) and press ENTER.11. Select the central station the area will report to and press ENTER.

12. Select audio listen-in, if required, and press ENTER.

13. Select exit fault report, if required, and press ENTER.

14. Select A & B alarm verification reporting, if required, and press ENTER.

15. Select disable arming if all inputs are bypassed, if required, and press ENTER.

Repeat steps 1 through 12 for all areas in the system.

Page 14: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

13AL-2017/AL-3017 Installation Manual

Alarm groups1. Press MENU, enter 1278, and press ENTER to access the system programming.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 5 and press ENTER to access alarm group programmaning.

4. Enter the alarm group number to be programmed and press ENTER.

Note: Care should be taken when programming this function because it can be linked to users, doors, and remote armingstations. A review of alarm groups in the Alliance System Programming Manual is advised before programming this feature.

Remote arming stations (RAS)Program RAS to establish communication (polling) with the main control panel. Before a RAS can be programmed, it must be installedand the DIP switch address on the RAS must be set as shown in the RAS installation instructions.

1. Press MENU, enter 1278, and press ENTER to access system programming.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 3 and press ENTER to access RAS database programming.

4. Enter the address number of the first RAS to be polled and press ENTER. Repeat for all RAS to be polled and press ENTER againafter all RAS have been polled.

5. Enter the address number of the first RAS to be configured and press ENTER.

6. Enter the alarm group number for the RAS and press ENTER.

7. Enter the menu alarm group number for the RAS and press ENTER.

8. Enter the door event flag for the RAS, if required, and press ENTER.

9. Enter the output controller assignment for the RAS and press ENTER.

10. Select Yes, if polling an LCD keypad, and press ENTER.

11. Select Yes, if toggles area status is required, and press ENTER.

12. Select Yes, if enter key opens door only is required, and press ENTER.

13. Select Yes, if door event flag on alarm code is required, and press ENTER.14. Select Yes, if display shunted zone on LCD is required, and press ENTER.

15. Select Yes, if arm/disarm using one key is required, and press ENTER.16. Select Yes, if card auto disarm is required, and press ENTER.

17. Select Yes, if card always arms/disarms is required, and press ENTER.

18. Select Yes, if reset from RAS without code is required, and press ENTER.

19. Select Yes, if alarm group restrictions to disarm only is required, and press ENTER.20. Select Yes, if entry/exit buzzers is required, and press ENTER.21. Select Yes, if time lockout is required, and press ENTER.

22. Select Yes, if cards arm after 3 badges is required, and press ENTER.

Repeat steps 4 through 21 for each RAS to be configured.

Data gathering panels (DGP)

Program DGPs to establish communication (polling) with the main control panel. Before a DGP can be programmed, the DGP must beinstalled and the DIP switch address on the DGP must be set as shown in the DGP installation instructions.

1. Press MENU, enter 1278, and press Enter to access system programming.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 4 and press ENTER to access DGP programming.

4. Enter the address number of the first DGP to be polled and press ENTER. Repeat for all DGP to be polled and press ENTER againwhen all DGP have been polled.

5. Enter the address number of the first DGP to be configured and press ENTER.

6. Enter 0 for standard DGP, 1 for a 4-door controller DGP, or 2 for a 4-elevator controller DGP and press ENTER.

Repeat steps 4 and 5 for all DGP to be configured.

Page 15: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

14 AL-2017/AL-3017 Installation Manual

Zones (inputs)Program zones to determine how the zone will function in given circumstances. There are over 50 types of zones. Refer to the AllianceSystem Programming Manual for more detailed information.

1. Press MENU, enter 1278, and press ENTER to access system programming.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 1 and press ENTER to access the zone programming.

4. Enter the zone number and press ENTER to access programming details and press ENTER again to move to between programmingoptions.

Zone AssignmentsAll DGPs, zones (inputs) and relays (outputs) are numbered according to a set formula. This formula determines the number/location ofDGPs, zones, and relays.

Zones and relays allocated to each DGP:Control panel 1-16 DGP 8 129-144

DGP 1 17-32 DGP 9 145-160

DGP 2 33-48 DGP 10 161-176

DGP 3 49-64 DGP 11 177-192

DGP 4 65-80 DGP 12 193-208

DGP 5 81-96 DGP 13 209-224

DGP 6 97-112 DGP 14 225-240

DGP 7 113-128 DGP 15 241-255

Either 8 or 16 zones can be connected to the control panel to expand the control panel to 24 or 32 zones. A standard DGP has 4 or 8 zones,some can be expanded in increments of 8 to contain up to 32 zones. Expanding the number of zones connected to the control panel or aDGP to more than 16 zones by using the AL-1206 is the same as combining two DGP addresses. To maintain consistent numbering, theadditional zones are taken from the next DGP address so you can not include the next DGP address for polling.

Example: An AL-2017/AL-3017 control panel has one AL-1206 (8-zone input expander) connected to J7. There is also an AL-1205 (8-zone standard DGP) connected to the System bus. In this case the zone numbering, and DGP addressing, would be:

AL-2017/AL-3017 control panel AL-1206 (standard zone expander) AL-1205 (standard DGP)

Zones 1-16 allocated Zones 17-32 allocated Zones 33-48 allocated

for this address for DGP 1 address for DGP 2 address

*unused zones must be disabled *unused zones must be disabled

To program the system for this configuration:

1. Set the address DIP switch on the AL-1205 for DGP 2 (Refer to the AL-1205 Installation Instructions for further details).

2. In installer programming go to option 4, (DGP Database). Poll DGP 2 and set DGP Type to standard. Do not poll DGP 1because the allocated zone inputs for DGP 1 have been taken by the AL-1206.

3. In installer programming go to option 1, (Zone Database). Select the proper zone type, area, and central station. Zonenumbers 25-32 must be set for zone type 0 Disabled as these zones are not used.

Page 16: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

15AL-2017/AL-3017 Installation Manual

Communication optionsProgram communication options to set up the telephone numbers and communication formats for central station reporting. Reportingoptions can be set for both system and area reporting.

PBX number (public branched exchange)

Use this option when connection to the PSTN (public switch telephone network) is made via a PBX by dialing a number sequence. Forexample, you must dial 9 to get an ouside line. This feature should not be used if dial tone detection is required, as dial tone detection doesnot occur during this dial sequence. If dial tone detection is required, the PBX number can be entered in the central station phone number.

1. Press MENU, enter 1278, and press ENTER to access system programming.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 9 and press ENTER to program communications options.

4. If a 2-second pause P is required prior to dialing, press MENU, MENU, enter the dialing sequence required to gain access to theoutside telephone line, and press ENTER.

5. To clear a telephone number that has been previously entered, press MENU, MENU. A P will appear on the lower line of the keypaddisplay and the previously entered telephone number will appear on the top line of the keypad display. Press ENTER and thetelephone number will be cleared.

Note: Do not enter a “T” (wait for dial tone) since the dial tone detection does not occur during the PBX dialing string.

MSN number (Microsoft Network)For ISDN dialers, program a MSN number. This number is sent to the ISDN network on dialing, o a computer, or central station. To entera MSN number, use the same method as used for the PBX number.

Note: The MSN number can not contain a 2-second dial pause “P” or wait for dial tone “T”.

Dial tone detection

This option enables or disables dial tone detection and also allows country specific dial tone detections. For operation in the USA, werecommend that CTR21 be used. Dial tone detection will take place at the beginning of the central station dialing string when a T isdetected in the dialing string. For example, in the number 9T1234567, dial tone detection will occur before the digit 9 is dialed and againbefore the 1 is dialed.

Enter the dial tone type to be detected:

0 = Disabled (no dial tone detection takes place, the panel will dial after a 2-second delay)

1 = CTR21

2 = Netherlands

3 = UK

4 = Other

New installer codeTo delete, display, or create a user, do the following:

1. Press MENU, enter 1278, and press ENTER to access system programming.

2. Enter 14 and press ENTER to access the users programming.

3. Enter 3 (create user) and press ENTER.4. Enter 50 (Installer) and press ENTER.

5. Press MENU to list the available alarm groups that can be assigned.

6. Press MENU again to scroll through the list.

7. Press ENTER three times (to scroll through unneeded options) and press MENU.

8. Enter the new code (up to 10 digits) and press ENTER.

9. Press ENTER three times (to scroll through unneeded options).

10. Enter 0 and press ENTER to exit. The installer PIN code is now changed.

Page 17: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

16 AL-2017/AL-3017 Installation Manual

Relays (outputs)Output controllers are used to expand the number of relays (outputs) on a DGP or control panel. Each output controller expands theoutputs by eight. A DGP can have two output controllers connected, increasing the outputs to a maximum of 16 per DGP. An AllianceSystem can have up to 32 output controllers, which allows a system maximum of 255 outputs.

If there are more than two output controllers connected to the main control panel, resulting in more than 16 outputs, the output numbers areduplicated on DGP 1. When this is done, one of two options can be used:

1. The outputs on DGP 1 are not used.

or2. Both outputs are activated together.

Example: If the main control panel has three output controllers and DGP 1 has one output controller, when output 17 isactive, the first output on the third output controller connected to the control panel and the first output on theoutput controller that is connected to DGP 1 are both activated.

Output numbers are always the same as the first 16 zone numbers on the DGP they are connected to. If a DGP address does not existbecause the previous DGP has an expanded number of zones, the output numbers of that DGP address cannot be used. The output numberscan be used if output controllers are connected to the control panel that corresponds to those output numbers.

Example: DGP 1 has 32 zones: 17-48DGP 1 outputs (max 16): 17-32(DGP 2 outputs 33-48 are not used)DGP 3 has 32 zones: 49-80DGP 3 outputs: 49-64(DGP 4 outputs 65-80 are not used)

Strobe and siren outputsThe internal strobe output is always treated as output 2. The internal siren speaker output on the control panel is always treated as output15 and the external siren speaker output on the control panel is always treated as output 16. On DGPs with siren speaker outputs, the last ofthe 16 output numbers associated with that DGP address is the siren output. For example, on DGP 3 the siren speader output is output 64.

DGP Siren output number DGP Siren output numberDGP 1 32 DGP 9 160

DGP 2 48 DGP 10 176

DGP 3 64 DGP 11 192

DGP 4 80 DGP 12 208

DGP 5 96 DGP 13 224

DGP 6 112 DGP 14 240

DGP 7 128 DGP 15 -

DGP 8 144

To enable the siren speaker output, the output number representing the siren output must be assigned to the required siren event flagnumber. The siren event flag numbers are programmed in installer programming option 2 (Area database).

Output control groupsOutput control group numbers identify a group of eight outputs controlled by the control panel, a DGP, or a RAS. When an output controlgroup is assigned to a RAS, the open collector output (OUT) terminal follows the first output of the output control group.

Programming steps1. Press MENU, enter 1278, and press ENTER to access system programming.

2. Enter 19 and press ENTER to access installer programming. Press MENU (advanced menu).

3. Enter 16 and press ENTER to access event to output programming.

4. Enter the output number to be programmed and press ENTER.

5. Enter the event flag number needed to trigger the output and press ENTER.

6. Enter the time zone assigned to the output and press ENTER.

7. Press MENU to toggle between Output active or Inactive during time zone and press ENTER.

8. Press MENU to toggle between Output is inverted or Noninverted and press ENTER.

Page 18: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

17AL-2017/AL-3017 Installation Manual

Battery CapacityThe battery capacity calculations must be performed separately for each part of the system that has a separate AC supply and standbybattery. Use the following steps to determine the correct battery capacities for your system:

1. Determine the exact configuration of your system.

2. A separate battery calculation worksheet should be used for each part of the system that has a separate power supply and standbybattery. In the top row of the worksheet, list the primary component (control panel or expansion module) that is powered by thestandby battery. Expansion modules include zone expander modules, relay modules, keypads and card readers.

3. On each worksheet, add rows for all expansion modules or other devices that are powered by the primary component on thatworksheet.

4. On each worksheet, add rows for any type of notification appliance that is connected to corresponding circuits on the primarycomponent. Also include rows for auxiliary power circuits that have attached devices.

Starting with the first worksheet:5. On the row for the primary component, in the total standby current column, enter the current listed for that device. For the control

panel worksheet, this value is 200mA.

6. On the same worksheet, in any following expansion module rows, enter the operating current for the module in the standby currentcolumn. On all of the expansion module rows, multiply the value in the standby current column by the attached quantity of modulesof that type. Enter the result in the same row, in the total standby current column. If any row contains AL-1191 or AL-1193 cardreaders, enter 80mA in the active current column for that row. Multiply any value in the active current column by the number ofattached card readers, and enter the result in the same row, in the total active current column.

7. On the same worksheet, in each notification appliance row, enter the alarm current drawn by a single device in the alarm current perdevice column. On all of the notification appliance rows multiply the value in the alarm current per device column by the number ofdevices used on that circuit. Enter the result in the same row, in the total alarm current column.

8. On the same worksheet, in rows listing devices that are attached to auxiliary power terminals of the primary component, enter theoperating current for each device in the standby current per device column. On all of these rows, multiply the value in the standbycurrent per device column by the number of devices attached to that auxiliary power circuit. Enter the result in the same row, in thetotal standby current column.

9. Repeat steps 5 through 8 for every worksheet.

10. At the bottom of each worksheet, total the values in the total standby current column, the total alarm current column, and the totalactive current column.

Perform the following calculations for each worksheet:

11. Transfer the totaled value at the bottom of the total standby current column to the first blank in formula 1. Enter the required numberof hours in standby in the corresponding blank, and perform the indicated calculation. The result is the standby Amp-hours yoursystem requires. The value for required number of hours in standby varies by locale. Check with the proper authority havingjurisdiction to determine your requirements.

12. Transfer the totaled value at the bottom of the total alarm current column to the first blank in formula 2. Enter the required number ofminutes in alarm in the corresponding blank, and perform the indicated calculation. The result is the alarm Amp-hours your systemrequires. The value for required number of minutes in alarm varies by locale. Check with the proper authority having jurisdiction todetermine your requirements.

13. Transfer the totaled value at the bottom of the total active current column to the first blank in formula 3. To calculate the requirednumber of seconds active value, multiply the number of times a card is typically passed by a card reader each hour times the numberof card readers, times 5 seconds. For a medium traffic area, 12 accesses per hour is a commonly used value (i.e. 5 seconds peraccess).

14. Carry the calculated values from the preceeding three steps to the corresponding blanks in formula 4. Perform the calculation to findthe minimum battery capacity requirement for your system.

15. Due to the natural aging effects on batteries over time, temperature cycles, and varying levels of discharge, a derating factor is appliedto compensate for these variables. Please consult the battery manufacturer data sheets for the appropriate derating factor. Formula 5shows how to apply a typical derating factor of 1.15 to the minimum battery capacity requirement to determine the actual batterycapacity requirement. The batteries selected for the control panel and for any separately powered expansion modules, must have acapacity rating that is equal to or greater than the actual battery capacity requirement.

Note: This system may require two batteries. Each battery must individually meet the actual battery capacity requirement. Donot mix batteries of different types.

Page 19: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

18 AL-2017/AL-3017 Installation Manual

The following tables list the maximum continuous loads that can be supported by two 17.2 Ah batteries or one 17.2 Ah battery. If the totalstandby current exceeds those listed in the tables, you do not meet 24/72-hour standby requirements. Other battery sizes are possible, buttwo 17.2 Ah batteries are the maximum battery size supported. If your standby time is different, the battery calculation worksheet can beused to calculate the total standby battery power required. If the answer exceeds the battery size you have chosen, then appropriatebatteries must be installed or the system configuration must be adjusted to meet the battery power requirements.

Required batteries Maximum continuous load for 24/72-hour standby with 15-minute alarm and 1 active card read/5 minutes

24-hour 72-hour

Maximum total Maximum auxiliary plus system bus power Maximum total Maximum auxiliary

Two 17.2 Ah 750mA 500mA 325mA 100mA

Maximum Total Maximum auxiliary plus system bus power

One 17.2 Ah 500mA 300mA _ _

Absolute maximum loads

1. __________mA X .001Amp/mA X _____________ hours: ________________ Ah standby Amp-hours

2. __________mA X .001Amp/mA X ____________ minutes X .0167 hours/min _____________ Ah alarm Amp-hours

3. __________mA X .001Amp/mA X ____________ seconds X .000278 hours/sec ___________ Ah active Amp-hours

4. Standby Amp-hours + Alarm Amp-hours + Active Amp-hours = Minimum battery power required

______________ + ______________ + ______________ = _______________Ah

5. Minimum battery power required X Battery capacity derating coefficient = Total standby battery required

__________________________ X _____________________________ = _____________________Ah1.15

225 72 16.2

1000 15 .2505

80 12960 .288

16.2 .2505 .288 16.74

16.74 19.2

Note: Based on 1 card activation of 15 seconds every 5 minutes for 72 hours.

Battery calculation worksheet example

Total standbycurrent

Conversionfactor

Conversionfactor

Conversionfactor

Required number ofhours in standby

Required number ofminutes in alarm

Required number ofseconds active

Conversionfactor

Total alarmcurrent

Conversionfactor

Total activecurrent

Page 20: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

19AL-2017/AL-3017 Installation Manual

Alliance Standby Total standby Alarm current Total alarm Active Total active components current current per device current current current

AL-2017 200mA Aux power 300mA Ext siren 1000mA Int siren 1000mA Strobe 1000mA AL-3017 200mA Aux power 300mA Ext siren 1000mA Int siren 1000mA Strobe 1000mA Comms bus 1000mA AL-11XX 120mA AL-1170 45mA AL-1191 25mA 80mA AL-1193 25mA 80mA AL-1205 75mA Aux power 250mA Siren 1000mA AL-1206 25mA AL-1210 53mA AL-1220 53mA AL-1255/56/65 275mA Aux power 1000mA Siren 1000mA AL-1801 80mA AL-1810 100mA AL-1811 200mA AL-1830 5mA AL-1832 15mATotal current requirements

Calculations:

1. ______________mA X .001Amp/mA X __________________ hours: ________________ Ah standby Amp-hours

2. ___________mA X .001Amp/mA X ____________ minutes X .0167 hours/min _____________ Ah alarm Amp-hours

3. ___________mA X .001Amp/mA X ____________ seconds X .000278 hours/sec ___________ Ah Active Amp-Hours

4. Standby Amp-hours + Alarm Amp-hours + Active Amp-hours = Minimum battery power required

________________ + ______________ + ______________ = _______________Ah

5. Minimum battery power required X Battery capacity derating coefficient = Total standby battery required

___________________________ X ____________________________ = _____________________Ah1.15

Battery calculation worksheet

Total standbycurrent

Conversionfactor

Conversionfactor

Conversionfactor

Required number ofhours in standby

Required number ofminutes in alarm

Required number ofseconds active

Conversionfactor

Total alarmcurrent

Conversionfactor

Total activecurrent

Page 21: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

20 AL-2017/AL-3017 Installation Manual

FCC CompliancePart 15 notificationThis device complies with part 15 of the FCC rules. Operation is subject to the following three conditions:

(1) This device may not cause harmful interference.

(2) This device must accept any interference received, including interference that may cause undesired operation.

(3) Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate theequipment.

Note In order to maintain compliance with FCC Class B rules, shielded cable must be used (Belden 8723 or equivalent).

Part 68 notificationThis equipment complies with Part 68 of the FCC rules and the requirements adopted by the ACTA. On the inside of the door of theenclosure of this equipment is a label that contains, among other information, a product identifier in the format US:AAAEQ##TXXXX. Ifrequested, this number must be provided to the telephone company.

The REN is used to determine the number of devices that may be connected to a telephone line. Excessive RENs on a telephone line mayresult in the devices not ringing in response to an incoming call. In most but not all areas, the sum of RENs should not exceed five (5.0).To be certain of the number of devices that may be connected to a line, as determined by the total RENs, contact the local telephonecompany. For products approved after July 23, 2001, the REN for this product is part of the product identifier that has the formatUS:AAAEQ##TXXXX. the digits represented by ## are the REN without a decimal point (e.g., 03 is a REN of 0.3). For earlier products,the REN is separately shown on the label.

If this equipment causes harm to the telephone network, the telephone company will notify you in advance that temporary discontinuanceof service my be required. But if advance notice isn’t practical, the telephone company will notify the customer as soon as possible. Also,you will be adviced of your right to file a complaint with the FCC if you believe it is necessary.

The telephone company may make changes in its facilities, equipment, operations, or procedures that could affect the operation of theequipment. If this happens the telephone company will provide advance notice in order for you to make necessary modifications tomaintain uninterrupted service.

If trouble is experienced with this equipment, for repair or warrenty information, please contact GE Interlogix technical support at 800648-7424. If the equipment is causing harm to the telephone network, the telphone company may request that you disconnect the equip-ment until the problem is solved.

This equipment must have the ability to seize the line in the event of an emergency. Do not connect this equipment to a party line serviceas line seizure is not possible.

Automatic dialersWhen programming emergency numbers and (or) making test call to emergency numbers:1. Remain on the line and briefly explain to the dispatcher the reason for the call.2. Perform such activities in the off-peak hours, such as early morning or late evenings.

UL Compliance StatementUL ListingsUL 264, Standard for Access Control System Units

UL 365, Standard for Police Station Connected Burglar Alarm Units and Systems

UL 609, Standard for Local Burglar Alarm Units and Systems

UL 1610, Standard for Central-Station Burglar-Alarm Units

UL 1635, Standard for Digital Alarm Communicator System Units

To maintain compliance with UL365, UL609, and UL1610:Mercantile Premises Alarm Systems1. Zone types 22, 28, 29, and 30 (Auto Reset) can not be used.

2. Force arming is not allowed (see the Alliance System Programming Manual).

3. Siren time should be programmed for no less than 15 minutes (see the Alliance System Programming Manual).

4. Siren delay time must be set to 0 seconds (see the Alliance System Programming Manual).

5. Total combined entry/exit time can not exceed 60 seconds (see the Alliance System Programming Manual).

Page 22: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

21AL-2017/AL-3017 Installation Manual

6. Alarm sounding device must be powered by the control unit and the siren test must be programmed “YES” (see the Alliance SystemProgramming Manual).

7. Safe and vault supervision circuits must be programmed for 24-hour operation (see the Alliance System Programming Manual).

8. The system must be programmed for 24-hour test reports to be sent to the control station (see the Alliance System ProgrammingManual).

9. Dual zone operation is not permitted.

10. Reporting to central station 2, 3, and 4 must be set to “NO” (see the Alliance System Programming Manual).

11. Display shunted zones on LCD keypad must be set to “YES” (see the Alliance System Programming Manual).

12. Resets from RAS without code must be set to “NO” (see the Alliance System Programming Manual).

13. AC fail delay time must not exceed 240 minutes (see the Alliance System Programming Manual).

14. System tamper activates siren and strobe must be set to “YES” (see the Alliance System Programming Manual).

15. Latching system alarms must be set to “YES” (see the Alliance System Programming Manual).

16. Siren types must be set to “1” (see the Alliance System Programming Manual).

17. Enable PSTN line monitor must be set to “YES” (see the Alliance System Programming Manual).

18. Sirens only after fail to report must be set to “NO” (see the Alliance System Programming Manual).

Mercantile safe and vaultIn addition to the above requirements, Mercantile Safe and Vault Alarm Systems must comply with the following:1. Alarm sounding device output must be mechanically and electrically protected (see hook-up label).

Bank safe and vaultIn addition to the above requirements, Bank Safe and Vault Alarm Systems must comply with the following:1. This equipment must be installed within a complete vault, a complete safe, or an extent number 1 stockroom.

2. The system must be programmed to inhibit disarming the system during closed hours (see the Alliance System ProgrammingManual).

Note: For Bank Safe and Vault applications, both the internal and external alarm sounding devices must be the UL ListedAdemco, Model AB12M.For Mercantile Premise and Mercantile Safe and Vault applications, the alarm sounding devices must be a UL Listed BurglarAlarm bell or siren such as the Moose, Model MPI35.

Note: The maximum AUX Power output including comms bus power (max total):24-Hour 72-Hour

AL-2017 500mA 100mAAL-3017 500mA 100mA

Page 23: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

22 AL-2017/AL-3017 Installation Manual

Part Terminal Description Min Typ MaxJ17 AC Input 16.5* 24** VAC

2.1 A

BATT Battery connection 9 12 14 VDCBattery charge 1 ABattery AH rating 24 AH

J14, J10 AUX.POWER Auxiliary power output 9 13.8 14 VDCCOMMS System bus power output 300 mA

J13 EXT SIREN Alarm outputs 9 13.8 14 VDC

* AL-1692 ** AL-1690, AL-1691

The following list contains the values to be used for EOL resistors. Both the resistance and the voltage over the zone are shown. Thevoltage will differ for other power supply voltages measured.

To get the current power supply voltage, measure the voltage over the zone when it is open. The EOL resistor used is based on the settingfor the EOL resistor code as programmed in the system options (see the Alliance System Programming Manual).

EOL code 0 (10 kOhm resistors)

Status Rzone (kOhms) Vzone (V)

Active zone 6.4 8.01 - 0

Normal zone 7.1 - 14.2 8.34 - 10.42

Active zone >18.1 11.01 - 13.8

EOL code 1 (4.7 kOhm resistors)

Status Rzone (kOhms) Vzone (V)

Active zone 1.02 < 2.4 4.69 - 0

Normal zone 3.3 - 5.2 5.72 - 7.28

Active zone >7.2 8.34 - 13.8

EOL code 2 (2 kOhm resistors)

Status Rzone (kOhms) Vzone (V)

Active zone 1.5 3.4 - 0

Normal zone 3.0 - 1.6 3.5 - 5.1

Active zone 3.1 5.5 - 13.8

External terminals specifications

Values for end-of-line resistors

Current consumption 200 mA nominal

End-of-line (EOL) resistors 10.0 kΩ, 5%, 0.25W

4.7 kΩ, 5 %, 0.25W

2.0 kΩ, 5%, 0.25WEnclosure dimensions (L x W x D) 21” (533mm) x 14.5” (368mm) x 4.5” (114mm)Operating temperature 32 °F to 122 °F (0 °C to 50 °C)Humidity 95% non-condensingListings UL 294 - the Standard for Access Control System Units

UL 365 - the Standard for Police Station Connected Burglar AlarmUnits and SystemsUL 609 - the Standard for Local Burglar Alarm Units and SystemsUL 1610 - the Standard for Central-Station Burglar-Alarm UnitsUL 1635 - the Standard for Digital Alarm Communictor SystemUnits

Specifications

Note: Do not mix EOLs on the same panel.

Control panel (no accessories) specifications

Page 24: Alliance Control Panel Installation Manualstatic.interlogix.com/library/1052109 B AL-2017 3017...Access Control Events 100 1,000 AL-2017/AL-3017 Installation Manual 3 Installation

GESecurity12345 SW Leveton Dr.Tualatin, OR 97062503-885-5700

Tech Support888-437-3287FaxBack: 800-483-2495www.GESecurity.com1052109 B 03/09