[email protected] 27/10/2009 1 PHOS Cooling status (1-27 Oct) Brief History: 28 Sep start cool...
-
Upload
donald-sark -
Category
Documents
-
view
215 -
download
0
Transcript of [email protected] 27/10/2009 1 PHOS Cooling status (1-27 Oct) Brief History: 28 Sep start cool...
27/10/2009 1
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)Brief
History:28 Sep start cool down. Steps (by liquid) was:
+17, +5, -3, -10, -15, -20, -25, -30, -29.5°C.
2 interlocks happened and was fixed:– 1 Oct – alarm on ECV controller battery fail, fixed;– 19 Oct – alarm on low pump cover temperature threshold, fixed.
At the moment (27 Oct):Nominal PHOS stabilization temperature achieved.Temperature (by Pt100 sensors):
Cooling liquid (C6F14): -29.50 ± 0.06°C
PWO2: -25.00°C, PWO3: -24.40°C, PWO4: -25.02°C
FEE2: +15.41°C, FEE3: +16.31°C, FEE4: +10.16°C.
Humidity (by 3×PWO + 2×FEE sensors):PWO2: 42,46,23%, PWO3: 43,43,29%, PWO4: 64,38,26%
FEE2: 7,4%, FEE3: 12,16%, FEE4: 7,8%
Liquid level in receiver tank ~53 Liters.
27/10/2009 2
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct) PHOS temperatures (overview)
Nominal stabilization temperature achieved 21 Oct
cooling liquid(C6F14)
FEE2 FEE3
FEE4
PWO2
PWO3PWO4Interlock 1 Oct.
Interlock 19 Oct.
27/10/2009 3
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct) PHOS temperatures (details)
In constant FEE state ± 0.1°C PWO stability shown
cooling liquid(C6F14)
PWO2PWO3
PWO4
Stability of cooling liquid average (per control cycle)
temperature are: -29.50 ± 0.06°C
FEE switchon/off causetemperaturevariations
PWO3temperature0.5°C higher
then PWO2,PWO4 (why?)
Temperature difference between PWO and cooling liquid is
about 4.5°C
27/10/2009 4
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)Cooling liquid level ~53 L
Temperature effect + (possible) leak ~1 L/week (?)
+5°C
-3°C
-25°C
-10°C
-30°C-20°C
-15°C
Interlock 19 Oct by pump cover temperature
Interlock 1 Oct by ECV controller battery, +25°C
-5°C ~3 Litres of C6F14
filled 21 Oct
Now ~53.3 LitresNeed more time to eastimate leak
27/10/2009 5
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)PHOS-2 humidity
FEE2
PWO2
27/10/2009 6
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)PHOS-3 humidity
FEE3
PWO3
27/10/2009 7
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)PHOS-4 humidity
FEE4
PWO4
27/10/2009 8
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)Pump cover temperatures
Pump2
Pump1
Pumps works inround-robin order(8 hours per cycle)
to equalizeworking times
27/10/2009 9
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)Compressor cover temperatures
Comp.2
Compressors alsoworks in round-robin order (8hours per cycle)
to equalizeworking times
Comp.3
Comp.4
Comp.1
27/10/2009 10
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) Concept scheme (just to remind)
Evaporator (suction header)
Condenser (discharge header)4 Compressors
Freon R404Areceiver
Water condenser for
freon cooling
HeatExchanger
R404A C6F14
ElectricControlValve
ECVcontroller
2 Pumps
Receivertank 65L
C6F14
Cooling serveralidcscom252
LAN2
DCS serveralidcscom072phs_topprojectPVSS
LAN1
DIM
4 compressors, 2 pumps, 3 heaters, 2 valves,Electric Control Valve + controller, fan,3 pressure + 14 temperature sensors, liquidlevel sensor, thermo/oil/pressure relays,funless industrial computer, 10×I-7000 RS-485remote data acquisition modules, 6×ELMB cards,15 humidity + 96 temperature sensors in PWO,FEE
PHOSControl unit (ADC, DIO etc)
RS-485
Feedbacktemperature
sensor
27/10/2009 11
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) PHOS DCS servers scheme
PHOS cooling control - alidcscom252 (AliPhosCool program)PHOS cooling client - alidcscom074 (PVSS, phs_col project)PHOS cooling top GUI – alidcscom072 (PVSS, phs_top project)
27/10/2009 12
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) Cooling control server: alidcscom252
Cooling plant works as DIM server under controlof AliPhosCool program designed in VNIIEF,Sarov.RS-485 and CAN devices uses for data taking & control.
Cooling serveralidcscom252Special funless
industrial computer,located insidecooling plant
27/10/2009 13
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) Cooling top GUI server: alidcscom072
Cooling plant GUI works as DIM client under PVSS.It’s fully integrated into ALICE DCS structures.But (at the moment) shifter can only view cooling data.To control cooling, expert should login to alidcscom252.
27/10/2009 14
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) Stabilization algorithm
PHOS cooling stabilization algorithm based on compressorswitch on/off by feedback temperature sensor. So liquidtemperature is not constant, but average temperature percontrol cycle is stable (±0.1°C).
27/10/2009 15
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)Stabilization: control parameters
Control parameters:Tstab – wanted stabilization temperature of cooling liquidDelta – temperature corridor to switch compressors on/offNbMin – minimal number of compressors (when T < Tstab-Delta)NbMax – maximal number of compressors (when T > Tstab+Delta)
Monitor parameters:Taver – achieved average (per control cycle) temperature of liquidCaver – achieved period (in minutes) of control cycleNaver – achieved average (per control cycle) number of compressors
Tstab°C
Delta°C
NbMin NbMaxTaver°C
Caverminutes
Naver
+17 1 0 1 17.18 ± 0.13 3.09 ± 1.19 0.31 ± 0.08
+5 1 0 1 5.01 ± 0.01 6.11 ± 0.05 0.45 ± 0.02
+3 1 0 1 2.99 ± 0.01 6.25 ± 0.04 0.51 ± 0.02
-3 1.5 0 2 -2.94 ± 0.17 6.71 ± 1.50 0.79 ± 0.06
-4 1.5 0 2 -3.97 ± 0.03 7.10 ± 0.19 0.82 ± 0.04
-10 1 0 2 -9.99 ± 0.03 2.24 ± 0.11 1.16 ± 0.04
-15 1 1 3 -14.94 ± 0.19 7.44 ± 5.65 1.69 ± 0.24
-20 1 1 3 -20.31 ± 0.02 5.32 ± 0.30 2.55 ± 0.02
-25 1 2 4 -25.21 ± 0.09 4.81 ± 0.82 3.43 ± 0.12
-29.5 0.3 3 4 -29.50 ± 0.06 4.64 ± 2.74 3.74 ± 0.13
-30 0.2 3 4 -29.97 ± 0.05 6.43 ± 3.53 3.85 ± 0.09
Main control parameter is Tstab.Delta, NbMin, NbMaxdepends on Tstab.Parameters chosen to achieve stable
periodic control cycle (when possible).
Large Caver “sigma” means control cycle instability
(large variations of period)
Table shows used parameter values
27/10/2009 16
ALICE-PHOS
ALICE-PHOS
PHOS Cooling status (1-27 Oct)Stabilization: power problem
As shown in table and picture, at -30°C we are working near maximum of compressor’s power (~94% of max. power).This cause some instability of control cycle (see pic.).Remind that we have another (more powerful) cooling machine in b.167. At the moment this machine is not ready for operation, so we should plan this item for the next year.
Control cycle period is not stable enough
27/10/2009 17
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) Safety: Alarms and Interlocks
PHOS cooling plant have 3 outcome Interlocks:1. Hardware (normal opened relay) – signal in case of
cooling system power off or control computer hang2. Software (DIM service) – signal in case of alarms, i.e.
dangerous conditions (some parameter out of threshold)3. Network (DIM service) – shows that cooling server
(alidcscom252) still alive
Software alarm produce interlocks by 35 conditions.Interlock mean that cooling plant halted because it
could not continue safe operation.
Important note:Cooling system alarms protect cooling plant against
damage, but not PHOS PWO & FEE.PHOS protection is job for higher DCS level (PVSS,
phs_top project).
27/10/2009 18
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) Safety: Alarms and Interlocks
Software alarms : 35 conditions
Each alarm conditionhave:1) Flag
(enable/disable)
2) Timeout(milliseconds)
3) Threshold(optional parameter)
Positive timeout produce temporary device blockingNegative timeout produce Interlock, i.e. fatal alarm and system HALT
Interlock requireshifter’s commandto Reset
27/10/2009 19
ALICE-PHOS
ALICE-PHOS
PHOS Cooling System status (1-27 Oct) Problems and discussions
1. Leak ~1 L per week in PHOS-4, ~8 month of work (without liquid filling). More liquid should be purchased next year (~60 liters ?).
2. Cooling system’s Control Parameters and Alarms tuning should be done after period of test operation (partly done).
3. It’s not quit clear how L3 magnetic field influent to temperature sensors in PWO. Should be tested.
4. Phs_top (PVSS) actions on cooling plant interlocks is still under discussion and should be modified (maybe).
5. Detail documentation (manuals) should be written for “cooling experts”.
6. For next year new cooling machine (more powerful) should be assembled and connected.