Alarm Messages A1

download Alarm Messages A1

of 74

Transcript of Alarm Messages A1

  • 8/6/2019 Alarm Messages A1

    1/74

    Alarm Message

    Reference Guide

    278558 Rev. A1

  • 8/6/2019 Alarm Messages A1

    2/74

    Use this publication as a source for complete and accurate information that helps you better operate or service

    Metso Automation equipment. Your comments and suggestions are welcome.

    Metso Automation, Inc.

    1180 Church Road

    Lansdale, PA 19446

    Attention: Manager, Technical Publications

    Copyright 2004 by Metso Automation MAX Controls Inc.

    Printed in the United States of America

    All rights reserved

  • 8/6/2019 Alarm Messages A1

    3/74

    Contents

    Preface ...............................................................................................................................................1

    Chapter 1 ........................................................................................................................................1-1

    Introduction....................................................................................................................................1-1

    maxDNA System Alarm Classes .......................................................................................................... 1-1Process Alarms......................................................................................................................1-1System Alarms ......................................................................................................................1-1

    Alarm Configuration ..............................................................................................................................1-2Configuring Alarm Priorities ................................................................................................1-2

    Viewing Alarm Messages ......................................................................................................................1-2Alarm Summary Display........................................................................................................................1-3

    Alarm Summary Menu Buttons ............................................................................................1-3Alarm List Display................................................................................................................1-4Acknowledging and Silencing Alarms...................................................................................................1-5Using Keyboard Buttons........................................................................................................................1-5

    Acknowledge and Silence.....................................................................................................1-5Defeat....................................................................................................................................1-5Restore ..................................................................................................................................1-6

    Defeating and Restoring Alarms............................................................................................................1-6Using maxVUE Runtime Display Buttons........ ........... ........... .......... ........... ........... .......... ........... .........1-6

    Chapter 2 ........................................................................................................................................2-1How to Interpret .............................................................................................................................2-1

    Process Alarms..............................................................................................................................2-1

    Control Block Alarms ............................................................................................................................2-1High Level Analog Input Alarms...........................................................................................................2-2Data Block Alarms.................................................................................................................................2-3

    Individual Alarm Cutouts .....................................................................................................2-3Troubleshooting Process Problems........................................................................................................2-4

    Logged Process Alarm Format: ............................................................................................2-5

    Chapter 3 ........................................................................................................................................3-1How to Interpret .............................................................................................................................3-1

  • 8/6/2019 Alarm Messages A1

    4/74

    maxSTATION Installation

    Reference Guide ...........................................................................................................................II -1

    Process Alarms .................................................................................................................................... II -1DPU4E/DPU4F Process Alarms ..........................................................................................................II -2DPU4E/DPU4F System Alarms...........................................................................................................II -3WorkStation Alarms.............................................................................................................................II -4Controller/Datapoint Alarms................................................................................................................II -8

    Part III .............................................................................................................................................III-1Alarm Message.............................................................................................................................III -1

    Reference Guide ..........................................................................................................................III -1

    System Alarms....................................................................................................................................III -1

  • 8/6/2019 Alarm Messages A1

    5/74

    Preface

    The Alarm Reference Message Guide contains listings of all the process

    and system related alarm messages you are likely to encounter in the

    operation of a maxDNA system.

    Part I of this publication introduces you to all the maxDNA alarm types,

    alarm-related displays and alarm message formats appearing on displays

    and on hard copy reports.

    Part II provides a complete alphabetized listing of all the maxDNA

    process alarm messages along with text explaining what they mean. Part

    III provides a similar listing for system alarms.

    This publication assumes you are familiar with the maxSTATION and

    the various display environments.

    For more information about related topics, refer to the following

    publications:

    Book Title Book Number

    maxSTATION Operator's Guide 278557

  • 8/6/2019 Alarm Messages A1

    6/74

  • 8/6/2019 Alarm Messages A1

    7/74

    Chapter 1

    Introduction

    maxDNA System Alarm Classes

    maxDNA System lets you view two classes of alarms:

    Process Alarms

    System Alarms

    Process Alarms

    Process alarms consist of alarm messages associated with the process

    itself. These consist of two types:

    Process Limit Alarms

    Process limit alarms are caused by values exceeding their

    assigned limits. Alarm information consists of time, point

    tagname and its long description, alarm text associated with the

    alarm, current value of the point, alarm limit value, and the units

    of measure for the point in alarm.

    Process Status Alarms

    Process status alarms are generated by points and programs atDPUs. Alarm information consists of time, point tagname and its

    long description, alarm type text and the alarm value.

    System Alarms

  • 8/6/2019 Alarm Messages A1

    8/74

    maxSTATION Installation

    tagname of the station reporting the alarm, the device reporting

    the fault, and the alarm text.

    DPU Bus Network Diagnostic Alarms

    This relates to two classes of alarms, DPU Bus related and

    maxNET network related. DPU Bus network diagnostic alarms

    are caused by cable breaks, token passing errors, failure of

    stations to respond, etc. maxNET Network alarms are caused by

    Frame Switch or hub failures, Ethernet card failures, Ethernet

    cable breaks, or a failed target maxSTATION.

    Alarm information consists of time, tagname for the DPU Bus

    reporting the alarm (e.g. DPUBUS1), name of the maxSTATION

    involved in the fault, and the alarm text.

    Alarm Configuration

    You may set up alarms and events to be detected when you create

    configurations using maxTOOLS. The system then automatically detects

    the alarms and events, processes them, and identifies them for display

    and acknowledgment, logging, analysis, and optional archiving.

    Configuring Alarm Priorities

    At time of configuration, you may give alarms one of six severity levels.(0 is the lowest prioritynot alarmed at alland 5 is the highest

    priority.) Alarm severities can be used in conjunction with a temporary

    filtering function that you may configure using maxVUE Runtime to

    further classify, filter, and sort alarms for a more meaningful presentation

    of alarm conditions on alarm-related displays. See "Alarm Summary

    Display" for a listing of other filtering categories.

    Viewing Alarm Messages

    You may view alarms from the following standard and custom

    maxSTATION displays:

  • 8/6/2019 Alarm Messages A1

    9/74

    Introduction

    Custom graphic displays

    Alarm Summary Display

    The Alarm Summary display shows filtered or unfiltered alarms from all

    maxDPUs and DBMs in the domain and the local LSS. By default, a

    single Alarm Summary page displays up to 20 alarms, however, the

    window may be configured to display from 1 to 40 alarms; display

    buttons let you page up and down through the full list. There is no limitto the number of pages. Older systems with only DBMs would have a

    limit of 5000 alarms per DBM.

    Click the Alarm Summary button on the Vertical Toolbar or on the

    Operator keyboard to access the display in a single keystroke. Each entry

    on the display lists the time, date, tagname, long description, value, limit,

    and acknowledge status of the alarm. Points may be selected in the

    summary for display swap or control action. When selected, the tagname

    of the selected point will appear on the Point Select button on the

    Horizontal Toolbar display.

    Note: By default, the Alarm Summary display lists all alarms without

    filtering. Use the Temporary Filter Setting Display to set up and control

    how alarms are seen on the actual Alarm Summary displays.

    You may filter alarms by type, the state of acknowledgment, and theseverity. See Publication 278599, maxSTATION Operator's Guide,

    "Filtering Alarms."

    Alarm Summary Menu Buttons

    The Alarm Summary Display includes six buttons at the bottom of the

    display that let you view alarms filtered by various categories that you

    select from the Temporary Filter Setting dialog box. See Publication

    278599, maxSTATION Operator's Guide, "Temporary Filter Setting."Table 1-1 relates the available filtering categories to maxDNA alarm

    classes as described at the beginning of this chapter. You may click the

    following buttons to display a filtered alarm list:

    Click This To View This Display

  • 8/6/2019 Alarm Messages A1

    10/74

    maxSTATION Installation

    Process diagnostic Display only process diagnostic alarms.

    Process control Display only process control alarms.

    Refer to the following Alarm Filtering Quick Reference Table for a

    listing of each filtering category that you may select, and the

    corresponding alarm classes and types that come under this category.

    These correspond to choices available under the Alarm Type field from

    the Temporary Filter Settings dialog window in maxVUE Runtime.

    Table 1-1. Alarm Filtering Quick Reference Table

    Filtering Category

    (from Alarm Type

    field)

    Alarm Class Alarm Types

    Process

    Diagnostic/Control

    Process Process Limit, Process Status

    Process/System

    Diagnostic

    System,

    Process

    System Diagnostic, Process Limit

    Alarm, Process Status Alarm

    System Diagnostic System Station Diagnostic, Highway

    Network Diagnostic

    Process Diagnostic Process Process Limit Alarm, Process

    Status Alarm

    Process Control Process Process Limit, Process Status

    All Process,

    System

    Process Limit, Process Status,

    Station Diagnostic HighwayNetwork

    Alarm List Display

    The Alarm List display shows the most recent acknowledged and

    unacknowledged alarms (with the highest severity). By default, the

    Alarm List displays up to 20 alarms, however, the window may be

    configured to display from 1 to 40 alarms; the alarms appear inside awindow at the lower part of the Vertical Toolbar.

    Because the Alarm List remains on the Vertical Toolbar display, you

    never lose sight of highest priority alarms. Unacknowledged alarms are

    displayed in their corresponding alarm severity color combination;

    k l d d l i hit t t bl k b k d

  • 8/6/2019 Alarm Messages A1

    11/74

    Introduction

    Acknowledging and Silencing Alarms

    With only a single keystroke, you may acknowledge alarms using the

    operator keyboard, the PC keyboard and from a variety of maxVUE

    Runtime Displays at the maxSTATION.

    Using Keyboard Buttons

    The four alarm keys, colored yellow on the maxDNA operator keyboard,control alarms. Two of these keys, and , also

    appear on the standard Horizontal and Vertical Toolbar display. Use

    these keys as follows: to temporarily stop alarms from occurring,

    , restore their function (remove defeat), ,

    acknowledge them, , and silence the audible annunciator,

    .

    The Acknowledge, Silence, Defeat and Restore keys work in maxDNArelease versions 3 and 4 but are restricted to the selected point and the

    selected point must have a Point Control pop-up on the screen.

    Acknowledge and Silence

    Press the key to acknowledge the highest priority

    unacknowledged alarm; this is the top alarm displayed in the alarm list

    display on the Vertical Toolbar display. This key has the same effect asthe Ack button on the Alarm List display. On the PC keyboard, the

    equivalent key is .See the next section.

    When a new alarm is detected, the maxSTATION can sound an audible

    alarm in addition to posting the new alarm in the appropriate location in

    the alarm list.The key lets you quiet the alarm with a single

    keystroke and has the same effect as the Silence button on the Vertical

    Toolbar display. See "Using maxVUE Runtime Display Buttons". On

    the PC keyboard, the equivalent key is

    The key only silences an audible alarm; the

    key both silences and acknowledges the top most alarm on the list.

    Defeat

  • 8/6/2019 Alarm Messages A1

    12/74

    maxSTATION Installation

    Restore

    Restores all alarms on the currently selected block so that it can alarmagain. On the PC keyboard, the equivalent key is . See next

    section.

    Defeating and Restoring Alarms

    You may temporarily defeat Control and Data Block alarms withoutchanging their triggering criteria. This permits individual process loops

    and other control actions to be switched off during operating periods

    when the alarm would be of no use. An example of this would be

    nuisance alarms that occur during startup or changes to part of the

    system. When normal operation resumes, the alarm features of that

    function can be restored.

    The Defeat capability eliminates clutter in alarm summaries and

    operating views, simplifying the operator's view of the process. To besure operators do not overlook defeated alarms, the word defeated

    appears in every faceplate, which displays that loop or controls action.

    Note: You may only defeat process-related points; alarms related to

    system hardware points cannot be defeated.

    Using maxVUE Runtime Display Buttons

    From maxVUE Runtime displays, you may acknowledge and silence

    alarms from the standard Vertical and Horizontal Toolbars, Alarm

    Summary Display, Alarm List Display, and from Point Control pop-ups

    and digital Detail Displays. Refer to the following table:

    Button Location Description

    Ack Point Data Pop-up,

    Point Detail Display

    Acknowledge Alarm condition

    of the current point.

    Ack Page Alarm Summary Acknowledges all alarms in

    the currently displayed page.

  • 8/6/2019 Alarm Messages A1

    13/74

    Introduction

    the Alarm List window and

    the Alarm Summary display.

    **Silence Vertical Toolbar Silence an audible signaloriginating in a

    maxSTATION equipped with

    a sound board and speakers.

    The audible signal indicates

    that an alarm has occurred for

    a point assigned to a pre-

    defined hierarchical group.

    * If an audible alarm is equipped, this action will silence the audible alarm.** The Silence key only silences an audible alarm;the Acknowledge key both

    silences and acknowledges the top most alarm on the list. maxSTATIONs notequipped with sound boards and speakers may be configured to silence alarms

    occurring at a maxSTATION playing the sound.

    Note: Because and buttons, and the Alarm

    List window appear on the standard Vertical and Horizontal Toolbars,

    you may place these elements on every screen view in the system, ifdesired.

    You may select individual alarms on the Alarm Summary display by

    pointing to an alarm and clicking the left mouse button. In response, the

    system displays the point tag name at the bottom of the display. Once

    selected, the point can be acknowledged via the Ack point button.

    Additionally, the Point Data, Control and Detail buttons will apply to the

    selected point.

  • 8/6/2019 Alarm Messages A1

    14/74

  • 8/6/2019 Alarm Messages A1

    15/74

    Chapter 2

    How to Interpret

    Process Alarms

    A process alarm indicates that some portion of the process has gone

    beyond its specified limits. When a point goes into alarm, the system

    adds its tagname to the Alarm List and Alarm Summary displays, and

    indicates the alarm condition on appropriate point-related pop-updisplays.

    Each of the standard maxDNA functional blocks stored in the DPU

    database has many alarm states and control conditions built into them,

    which are set during the configuration process. This permits alarming

    capability and an interlocking capability with other user-ready and user-

    defined blocks.

    Control Block Alarms

    Control Blocks, stored in the DPU (DPU4A and earlier), can contain up

    to 16 independently adjustable alarms, which permit alarming and

    interlock capabilities not only within the specific block originating the

    alarm but also in other computational blocks. The PID Control Block, for

    example, will alarm and set triggers (Alarm/Mode Word bits) forinterlock upon the following six conditions:

    Process Variable HI Setpoint LO

    Process Variable LO Deviation HI

  • 8/6/2019 Alarm Messages A1

    16/74

  • 8/6/2019 Alarm Messages A1

    17/74

    How to Interpret Proc ess Alarms

    Analog input alarms can help discriminate between reaching an

    operational and safety alarm condition and the failure of an input device,

    such as a field sensor/transducer or the loss of an I/O module or channel.

    Data Block Alarms

    The DPU 248 Data Blocks each have the same eight input alarms listed

    for the High Level Analog Inputs. This allows the same alarms to be

    applied to other inputs by linking them to a Data Block. In addition, Data

    Blocks can each be used to perform any of the following alarm options:

    Open thermocouple detection.

    HI and LO alarm condition.

    HI-HI and LO-LO alarms expressed either as an absolute value

    or as a delta from the HI or LO alarm value.

    Rate-of-change alarms and rate-of-change clamps placed on

    inputs or outputs to detect unacceptable slew rates or to limit signal

    slew rates.

    Adjustable hysteresis (% value) deadband for value-related

    alarms (HI, LO, HI-HI etc.) to prevent nuisance alarms as a variable

    hovers around an alarm trip value.

    Time Delay settings to suppress transient swings into alarm but

    not sustained alarm conditions.

    Alarms built into each Data Block can be set up to trigger:

    On single threshold crossing or on repetitive deltas.

    Upon return to normal.

    If acknowledged, but situation remains uncorrected for too long

    a time period.

    Alarms can also automatically acknowledge when they return to normal

    before being acknowledged by the operator. These options enable the

    i l b l di i hil

  • 8/6/2019 Alarm Messages A1

    18/74

    maxSTATION Installation

    HI alarms, rising/falling, or all alarms. Cutout can be due to process

    value changes or system hardware conditions. For example, during

    known disruptive operations (start up or shut down), selective alarms canbe temporarily disabled to avoid masking more important real alarms.

    Yet you will be kept aware of other conditions of that same bypassed

    point, such as an open thermocouple.

    These alarm cutouts are independent of the Alarm Defeat/Restore

    mechanism, and can be triggered either by operator command, by a

    discrete signal, or induced by a program.

    Any event, threshold of analog value, lapse of time, condition, state,sequence step (or completion) or command either within or outside of

    maxDNA can be used to trigger an alarm cutout.

    A single event or logic result of several conditions or events (boolean

    expression) can impact the alarm of a single Data Block, or any

    combination of Blocks. Each Data Block can have its own independent

    triggering circumstance.

    Troubleshooting Process Problems

    Process limit alarms and process status alarms appear together on the

    Alarm Summary display mixed in with system alarm messages. The

    format of displayed process alarms is somewhat different from the format

    for station alarms and DPU Bus network alarms. (Refer to Chapter 3,

    "How to Interpret System Alarms" for a description of system alarm

    formats.)

    Process limit alarms have the following format:

    Message TextTime Date Tagname Description

    Alarm Text Alarm

    Value

    Limit

    HH:MM:SS MM:DD:YY Up to 16

    characters

    Up to 32

    characters

    Variable Character Lengths

  • 8/6/2019 Alarm Messages A1

    19/74

    How to Interpret Proc ess Alarms

    Process status alarms have the following format:

    Message TextTime Date Tagname Description

    Alarm Text Alarm

    Value

    Limit

    HH:MM:SS MM:DD:YY Up to 16

    characters

    Up to 32

    characters

    Variable Character Lengths

    Note: The Limits field does not apply to

    status alarms.

    Displayed process limit alarms and process status alarms are also

    somewhat different from each other. Process limit alarms report:

    Time the alarm occurred.

    Tagname of associated point.

    Name of point and alarm message text under the Description

    field.

    Alarm type.

    Current value of the point.

    Alarm limit value.

    Units of measure for the point.

    The process status alarms format is similar to the process limit alarms

    format as outlined above; however, because status alarms are associated

    with digital type points, the Summary Display Limits field does not

    apply and is not used.

    Process alarm messages also appear in a hardcopy version that uses a

    format somewhat different from the Alarm Summary Display format.

    Because the printed format can accommodate 133 characters per line,printed text may contain additional information. Refer to the following

    figure to learn how to recognize logged process alarms:

    Logged Process Alarm Format:

    date/ time severity type alm/clr tagname description value long

  • 8/6/2019 Alarm Messages A1

    20/74

    maxSTATION Installation

    Severity

    Alarm severity ranging from 0 to 5; the severity number appears in a

    three-character field surrounded by asterisks: *5*

    Type

    When a process alarm is logged, the characterspa appear in this two-

    character wide field.

    Note: The format for process alarms and edit actions is the same. An Edit

    Action occurs when an operator takes some action involving a point,

    such as a mode change or a configuration. When a Edit Action is logged,the characters ea appear.

    Tagname

    Tagname of associated point; the tagname is created when you

    configure a point using maxTOOLS.

    Alm/clr

    When an unacknowledged process alarm is logged, the characters alm

    appear in this three-character wide field. If the alarm is acknowledged

    or otherwise clears, the characters clrappear. If the line applies to an

    edit action, the field is blank.

    Description

    Process Alarm message text, such as HiHi LoLo; Range High; and so

    forth.

    When this field applies to an edit action, the message text describes an

    attribute that was edited.

    Value Limit

    When this field applies to a process alarm, it reports the current value

    of the point and the alarm limit value.

    When this field applies to an edit action, it reports that the limit was

    changed; the new limit value along with the previous value limit

    appear in this field.

  • 8/6/2019 Alarm Messages A1

    21/74

    How to Interpret Proc ess Alarms

    You may invoke these displays in maxVUE Runtime by selecting the

    appropriate button on the main menu Horizontal and Vertical Toolbars.

    See Publication 278599, maxSTATIONOperator's Guide.

  • 8/6/2019 Alarm Messages A1

    22/74

  • 8/6/2019 Alarm Messages A1

    23/74

    Chapter 3

    How to Interpret

    System Alarms

    System and Network Alarms

    System diagnostic status alarms inform you of maxDNA system

    hardware and software problems. Problems detected within a specific

    module or station are classified as diagnostic failures. Problems withcommunications are referred to as highway network alarms. DPU Bus

    network alarms are further divided between DPU Bus network and

    maxNET network communications problems. maxVUE Runtime System

    Status displays show both alarm types.

    System alarms appear along with process alarms on the Alarm Summary

    Display and on the Alarm List. The format of displayed system alarms is

    somewhat different from the format for process alarms; refer to the

    previous chapter for a description of process alarm formats.

    System alarms have the following format:

    Time Date Tagname Text

    Subsystem Name Message TextHH:MM:SS MM:DD:YY Up to 16

    charactersVariable Character Length

    On the display, the subsystem reporting the fault and the message text

    appear together under the Description field. The three fields to the right

    of this field Type, Value, Limit apply to Process alarms.

    System alarm messages also appear in a hardcopy version that uses a

    format somewhat different from the Alarm Summary display format

  • 8/6/2019 Alarm Messages A1

    24/74

    H t I t t S t Al

  • 8/6/2019 Alarm Messages A1

    25/74

    How to Interpret System Alarms

    actual physical device. This makes it easier to pinpoint the location of the

    maxSTATION, DPU, I/O module, or DPU Bus reporting the problem.

    If you have a particularly large configuration consisting of multiple DPU

    Buses and many stations configured with each DPU Bus, system status

    displays may also help you to pinpoint the location of a system problem.

    System status displays are a collection of screens used to diagnose

    problems in your system. These consist of:

    System Status Display

    DPU Bus Map Display

    DPU Bus Statistics Display

    DPU Bus Station Status Display

    Refer to Publication 278599, maxSTATION Operator's Guide, for more

    information about these displays.

  • 8/6/2019 Alarm Messages A1

    26/74

  • 8/6/2019 Alarm Messages A1

    27/74

    Part II

    Alarm Message

    Reference Guide

    Process Alarms

    Part II consists of an alphabetic listing of all maxDNA Process Alarm

    messages. The following pages contain the actual message text

    (appearing here in all upper case characters), the point or points which

    can generate the alarm, and a description of what each process alarm

    message means.

    Process alarm message text for any given point appears in three versions:

    16-character text used in alarm log

    12-character text used in Alarm Summary displays

    12-character text used in Detail pop-ups

    All three versions are listed for each process alarm message entry.

    Note: Points for which an alarm message is applicable include some

    Control Blocks, which are no longer supported by maxDNA, but were

    supported by the Models 582 and 585 Operator Stations. Those points

    are identified using ** in the table.

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    28/74

    maxSTATION Installation

    DPU4E/DPU4F Process Alarms

    Process alarms in a maxDPU are generated by three types of atomic

    blocks: ATAG, DTAG and ALMREP. ATAG and DTAG will generate

    specific alarm text strings for the alarm summary display and events.

    These texts are shown below. Names in capital letters below are

    attributes of ATAG and DTAG.

    Alarm Clear Value = (TMSG attribute value) DTAG

    TMSG is set to TRTXT or FLSTXT based on the value

    of OUT in the DTAG. A clear alarm occurs when the

    DTAG output value changes to the non-alarm state.

    Alarm Digital Value = (TMSG attribute value) DTAG

    TMSG is set to TRTXT or FLSTXT based on the value

    of OUT in the DTAG.

    Return to Normal DTAG, ATAG

    Return to Normal behavior must be selected in the

    ALMBEHAVE attribute. A return to normal alarm

    occurs when the alarm condition of an acknowledged

    alarm clears.

    AlarmRising =ACTUALRATE Lim=LIMRATE ATAG

    LIMRATE attribute must be non-zero for a rising or

    falling alarm to occur.

    AlarmFalling =ACTUALRATE Lim=LIMRATE ATAG

    LowAlarm Limit =LIMLO Value =OUT ATAG

    HighAlarm Limit =LIMHI Value =OUT ATAG

    LoLoAlarm Limit =LIMLOLO Value =OUT ATAG

    HiHiAlarm Limit =LIMHIHI Value =OUT ATAG

    Workstation Alarms

  • 8/6/2019 Alarm Messages A1

    29/74

    Workstation Alarms

    DPU4E/DPU4F System Alarms

    The maxDPU produces several system alarms. ATAG can produce an

    open circuit alarm when referenced to a TC. The base DPU atomic

    blocks will produce the others.

    TC input# ADDR nnn Open Circuit ATAG

    Input# is the TC input referenced by the ATAG.

    nnn is the address of the TC card. This alarm is

    generated by ATAG but actually occurs due to a break in

    the wiring for a TC input.

    Standby DPU has Failed BACKUP

    This occurs in DPU4E only and is somewhat misleading.

    This alarm is generated in the active DPU that has just

    taken over due to a takeover request or failure of the

    (previously) active DPU.

    Primary/Secondary DPU Takeover BACKUP

    DPU4F only. This alarm is generated when the inactive

    DPU changes it state to active due to a takeover or a

    failure of the (previously) active DPU.

    Normal Queue Overrun QUEOVRN

    The normal time class typically executes every 500 ms

    in a DPU. If it cannot complete execution of all of the

    normal time class atomic blocks in the configured time

    period, this alarm is generated. While this alarm should

    be very rare, it indicates a fairly serious condition. TheDPU is overloaded to the point where it cannot perform

    control and monitoring functions in a timely manner.

    Prompt attention should be given to the size of the

    configuration and to the allocation of atomic blocks to

    the critical, high and normal time classes. For example,

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    30/74

    maxSTATION Installation

    DPU4F set to 10 MB operation when connected to a 100

    MB port will generate a NetErr alarm.

    DPU Battery Problem BATALARM

    DPU4E only. Generated when the battery voltage is

    determined to be too low to sustain DPU operation long

    enough to write the configuration to flash memory.

    DPU CPU Fan Problem FANALARM

    DPU4E only. The CPU fan has stopped or slowed to thepoint where it is no longer effective. The fan should be

    replaced.

    WorkStation Alarms

    A number of programs in the workstation can produce alarms. The name

    of the originating program is shown on the right. The text on the left will

    appear in the Text field on the alarm summary display. All workstation

    alarms are of type System.

    [IP address] DPU is Not Responding Healthlog

    Healthlog cannot establish communication with theDPU.

    [IP address] Status: SBP_E_TIMEOUT Healthlog

    Healthlog has lost communication with a DPU.

    ALM DLL COULD NOT READname RealTimeGateway

    The RealTimeGateway alarm dll could not establish

    communication with a DBM (name). Alarms from this

    DBM will not be displayed.

    ALM Primary and Secondary Printer Error LSS

    Workstation Alarms

  • 8/6/2019 Alarm Messages A1

    31/74

    o stat o a s

    The primary network printer is not available. Data

    (loggers, reports) should be re-directed to the secondary

    printer.

    ALM Secondary Printer Error LSS

    The secondary network printer is not available. If the

    primary printer should fail, the secondary will not be

    there to takeover.

    ALM Reports sizen MB exceeds limit ofm MB LSS

    The size of generated report files on the hard disk has

    exceeded the amount specified in the MCS registry (Max

    Generated Rpts MB). Generated reports are saved in the

    c:\Custom\Reports\Generated folder.

    ALM Archive sizen MB exceeds limit ofm MB LSS

    The size of archived report files on the hard disk has

    exceeded the amount specified in the MCS registry (MaxArchive Megabytes). Archived reports are saved in the

    c:\Custom\Reports\Archive folder.

    ALM Event sizen MB exceeds limit ofm MB LSS

    The size of event databases on the hard disk has

    exceeded the amount specified in the MCS registry (Max

    Event Megabytes). Event MDBs are saved in thec:\Custom\Database\System\Events folder.

    ALM Spool sizen MB exceeds limit ofm MB LSS

    The size of the files in the spool folder the hard disk has

    exceeded the amount specified in the MCS registry (Max

    Spooling Megabytes). Spool files are saved in the

    c:\WinNT\System32\Spool\Printers folder.

    ALM Total sizen MB exceeds limit ofm MB LSS

    The size of the report, event and spool files on the hard disk has

    exceeded the amount specified in the MCS registry (Max Total

    Megabytes)

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    32/74

    Dead Man Timer Timed Out LSS

    Only applies to a program that starts up an LSS dead

    man timer service. That program is responsible forupdating the dead man timer. If it does not do so in a

    timely fashion, the above alarm is generated.

    Disable Time Sync To DBM RealTimeGateway

    DISK WRITE FAILED: DATA LOST ! maxSTORIAN

    This alarm will occur if the disk is full and has not yet

    been trimmed.

    Dongle will expire inn days LSS

    The parallel port dongle will expire shortly and

    maxVUE will no longer run. This alarm is associated

    with test dongles.

    ILLEGAL ALARM SORT FOR DBM RealTimeGateway

    The DBM does not support the Sev/Time sort order. An

    alarm request for this sort order will cause the

    RealTimeGateway to issue an alarm. Alarms from the

    DBM will not be displayed.

    The maxLINKS program can also generated alarms if it has been

    configured to do so. It will issue analog and digital alarms as shown

    below where name is the tagname of a maxLINKS service/point.

    Name = Val=> LimitH =LimVal maxLINKS

    Name = Val=> LimitHH =LimVal maxLINKS

    Name = Val

  • 8/6/2019 Alarm Messages A1

    33/74

    An alarm provider such as maxMERGEDPUALM, LSS,

    or RealTimeGateway could not be read. Alarms from

    this provider will not appear on the alarm summary

    display.

    MERGE RCV BAD ALARM FROMprovider maxMERGEALM

    Indicates that unknown data was received from an alarm

    provider. This is not a serious problem since the alarm

    data will be retrieved on the next read. However,

    repeated occurrences of this alarm indicate some

    workstation problem (possibly low memory?).

    Net Err: Station Lost Comm withDBMon Net A/B Realtimegateway

    Generated by the DBMcomm plugin in the

    RealTimeGateway when communication is lost with a

    DBM on the A or B network.

    NetErr:name NetAstatus maxTransport

    Text for this alarm could also indicate net B. name is the

    workstation name. Status can display: CommLost,

    CommRegained, CommOk. If the status sticks at

    CommLost, no communication is occurring on the

    failed network.

    POINTS WITH LOWERED PRIORITY maxSTORIAN

    maxSTORIAN cannot keep up with all of the data that it

    is receiving and will shed load.

    Station: Log In: [IP] RemoteServe

    A user has logged in remotely from the listed IP address.

    Station: Log Out [IP] RemoteServe

    A remote user has logged out.

    UNCONNECTED POINTS maxSTORIAN

    MaxSTORIAN cannot access one or more points that it

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    34/74

    Controller/Datapoint Alarms

    ALM INT'LOCK ALM INRLOCK ALARM INLK

    Point(s) which generate this alarm: ReversingMotor Controller (Cntrl Block)

    Meaning: One of the Interlock inputsconfigured as an Alarm Interlock has becometrue. The motor will be turned off. This alarmmay cause the algorithm to go to the'stopping' state.

    ALARM INTERLOC ALM INTERLOC ALM INTERLOC

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary Control ModuleExCEL.

    BACKED OVER BACKED OVER SEC ACTIVE

    Point(s) which generate this alarm: Backup(Control Block)

    Meaning: Control has been transferred to thesecondary DPU of a backup pair.

    BACKUP BACKUP BACKUP

    Point(s) which generate this alarm:**Receives (Control Blocks)

    Meaning: This block is now receiving datafrom the backup DPU of a backup pair,becauseof a transfer of control in that pair.

    BOTH LIMITS BOTH LIMITS BOTH LIMIT

    Point(s) which generate this alarm:Valve/Breaker Controller (Control Block)

    Meaning: Both limit inputs have become true.

    CLOSED CLOSED CLOSED

    Workstation Alarms

  • 8/6/2019 Alarm Messages A1

    35/74

    COMM FAILED COMM FAILED COMM FAIL

    Point(s) which generate this alarm:**Receives (Control Blocks)

    Meaning: No data received from other station.

    CONF ERROR CONF ERROR CONF ERROR

    Point(s) which generate this alarm: All DataBlocks

    Meaning: An illegal value has been enteredinto one of the editable fields of a DataBlock.

    DEV HIHI DEV HIHI DV HL

    Point(s) which generate this alarm: **RealAlarm (Control Block)

    Meaning: The deviation has exceeded the

    configured HIHI limit.

    DEV LIMIT DEV LIMIT DV

    Point(s) which generate this alarm: PID(Control Block)

    Meaning: 'Generic' alarm raised if the PIDalgorithm has raised a deviation limit alarm

    but the condition cleared before it was logged.

    DEV LOLO DEV LOLO DV HL

    Point(s) which generate this alarm: **RealAlarm (Control Block)

    Meaning: The deviation has exceeded theconfigured LOLO limit.

    DEVIATION DEVIATION DV

    Point(s) which generate this alarm: **DataAcquisition (Control Block)

    Meaning: The L3 limit is exceeded by any pair

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    36/74

    Meaning: Deviation between process variableand set point has exceeded the configured highalarm limit.

    DEVIATION LO DEV LOW DV

    Point(s) which generate this alarm: PID(Control Block)

    Meaning: Deviation between process variableand set point has exceeded the configured lowalarm limit.

    DEV HIGH DEV HIGH DV

    Point(s) which generate this alarm: **EventCounter (Control Block)

    Meaning: Output minus the specified deviationvalue has exceeded the configured deviationhigh alarm limit.

    DEV LOW DEV LOW DV

    Point(s) which generate this alarm: **EventCounter (Control Block)

    Meaning: Output minus the specified deviationvalue has exceeded the configured deviation lowalarm limit.

    DIGITAL ALRM DIGITAL ALRM ALARM

    Point(s) which generate this alarm: Alldigital Data Blocks

    Meaning: A digital data block has gone intoalarm.

    DIGITAL INP DIGITAL INP ALARM

    Point(s) which generate this alarm: DigitalStatus/Alarm (Control Block)

    Meaning: The output bit of the point hasbecome true and the algorithm is configured toalarm.

    Workstation Alarms

  • 8/6/2019 Alarm Messages A1

    37/74

    block attempted to access a step which ishigher than allowed based on the number ofslots in the chain; or the control block wastrying to find the first 'off' step but eithercould not find it or its number was greaterthan 255.

    DISCREP+TIM DISCREP+TIME DISC + TIME

    Point(s) which generate this alarm:Sequencer, Ramp Gen (Control Blocks)

    Meaning: A discrepancy alarm has occurred,

    and the time in a particular step has exceededthe allowed time.

    DV HL DV HL DV

    Point(s) which generate this alarm: **RealAlarm (Control Block)

    Meaning: 'Generic' alarm raised if the Real

    Alarm algorithm has raised a deviation limitalarm but the condition cleared before it waslogged.

    DV RATE DV RATE DV R

    Point(s) which generate this alarm: **RealAlarm (Control Block)

    Meaning: Input 1 rate of change has exceeded

    the configured limit.

    FAIL FAIL FAIL

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary ControlModule ExCEL.

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    38/74

    FAILED FAILED FAILED

    Point(s) which generate this alarm: Backup(Control Block)

    Meaning: Control has been transferred to thebackup DPU of a backup pair; this controlblock is no longer in control.

    FALLING FALLING FALLING

    Point(s) which generate this alarm: AnalogData Blocks

    Meaning: The output of the Data Block isdecreasing at a rate faster than theconfigured Rate-of-Change limit.

    HIGH ALARM HIGH ALARM ALARM HIGH

    Point(s) which generate this alarm: AnalogData Blocks, Analog Input Buffers

    Meaning: Input value is greater than or equalto the configured high alarm limit.

    HIHI ALARM HIHI ALARM HIHI ALARM

    Point(s) which generate this alarm: AnalogData Blocks

    Meaning: Input value is greater than or equal

    to the configured high alarm limit.

    INP 1 INP 1 INP

    Point(s) which generate this alarm: AnalogControl Blocks

    Meaning: Input 1 of this block is in alarm;see the input's Detail Popup to observe theexact alarm condition.

    INP 2 INP 2 INP

    Point(s) which generate this alarm: AnalogControl Blocks

  • 8/6/2019 Alarm Messages A1

    39/74

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    40/74

    Meaning: 'Generic' alarm raised if thecontrol block has raised an input alarm butthe condition cleared before it was logged.

    I1 LIMIT I1 LIMIT INP

    Point(s) which generate this alarm: Selectand 8-Pos Switch Control Blocks

    Meaning: 'Generic' alarm indicating that the

    control block has raised an input alarm forinput 1 but the condition cleared before itwas logged.

    I2 LIMIT I2 LIMIT INP

    Point(s) which generate this alarm: Select

    and 8-Pos Switch Control Blocks

    Meaning: 'Generic' alarm indicating that the

    control block has raised an input alarm for

    input 2 but the condition cleared before it

    was logged.

    INSTR HIGH INSTR HIGH INST HIGH

    Point(s) which generate this alarm: AnalogData Blocks, Analog Input Buffers

    Meaning: Hardware failure alarm indicatingthat the input is greater than 5.5V on a 1V-5V

    input.

    INSTR LOW INSTR LOW INST LOW

    Point(s) which generate this alarm: AnalogData Blocks, Analog Input Buffers

    Meaning: Hardware failure alarm indicatingthat the input is less than 0.5V on a 1V-5Vinput.

    LEFT LIMIT LEFT LIMIT LEFT LIMIT

  • 8/6/2019 Alarm Messages A1

    41/74

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    42/74

    NOT CLOSED NOT CLOSED NOT CLOSED

    Point(s) which generate this alarm:

    Valve/Breaker Controller (Control Block)

    Meaning: The 'closed' feedback input has notgone true within the specified time limit.

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary ControlModule ExCEL.

    NOT OPEN NOT OPEN NOT OPEN

    Point(s) which generate this alarm:Valve/Breaker Controller (Control Block)

    Meaning: The 'open' feedback input has not

    gone true within the specified time limit.

    NOT OFF NOT OFF NOT OFF

    Point(s) which generate this alarm: ReversingMotor Controller (Cntrl Block)

    Meaning: Within 2 seconds of the start/stopinput going false the motor forward (or motor

    reverse) input has not gone false; or the runfeedback input has not gone false within theconfigured time limit during the stopsequence.

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary Control

    Module ExCEL.

    NOT OPEN/CLOSED NOT OP/CL NOT OP/CL

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Workstation Alarms

  • 8/6/2019 Alarm Messages A1

    43/74

    Meaning: Both 'open' and 'closed' feedbackinputs are false.

    NOT READY NOT READY NOT READY

    Point(s) which generate this alarm: ReversingMotor Controller (Cntrl Block)

    Meaning: The 'motor ready' input goes falsewhile the motor is running, or during startup.

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary ControlModule ExCEL.

    NOT START NOT START NOT START

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary ControlModule ExCEL.

    OPEN T/C OPEN T/C OPEN TC

    Point(s) which generate this alarm: AnalogData Blocks

    Meaning: Hardware failure alarm indicating an

    open thermocouple.

    OUT INPUT OUT INPUT DV

    Point(s) which generate this alarm: **DemandLimit Regulator (Control Block)

    Meaning: Generic alarm indicating that thepoint has generated either an output > inputalarm or an output < input alarm, but the

    condition cleared before it was logged.OUTPUT

  • 8/6/2019 Alarm Messages A1

    44/74

    Meaning: Difference between the input to and

    the output of the algorithm has exceeded the

    configured limit value.

    POS'N TIMOUT POS'N TMOUT POS TIME

    Point(s) which generate this alarm:Positioner (Control Block)

    Meaning: The motor has been started and themaximum positioning time has been exceeded.

    POS+BOTH LIM POS+BOTH LMS POS BOTH

    Point(s) which generate this alarm:Positioner (Control Block)

    Meaning: Maximum position time has beenexceeded and both limits are true.

    POS+L LIMIT POS+LEFT LM POS LEFT

    Point(s) which generate this alarm:Positioner (Control Block)

    Meaning: Maximum position time has beenexceeded and the left limit is true.

    POS+R LIMIT POS+RIGHT LM POS RIGHT

    Point(s) which generate this alarm:Positioner (Control Block)

    Meaning: Maximum position time has beenexceeded and the right limit is true.

    PV HIGH HIGH PV HIHI PV HL

    Point(s) which generate this alarm: **Real

    Alarm (Control Block)

    Meaning: The process input value has exceededthe configured HIHI limit.

    PV LOW LOW PV LOLO PV HL

  • 8/6/2019 Alarm Messages A1

    45/74

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    46/74

    Meaning: Analog input I2 is greater than theconfigured HI alarm value.

    PV I2 LOW PV I2 LOW PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I2 is less than theconfigured LO alarm value.

    PV I3 HIGH PV I3 HIGH PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I3 is greater than theconfigured HI alarm value.

    PV I3 LOW PV I3 LOW PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I3 is less than theconfigured LO alarm value.

    PV I4 HIGH PV I4 HIGH PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I4 is greater than theconfigured HI alarm value.

    PV I4 LOW PV I4 LOW PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I4 is less than the

    configured LO alarm value.

    PV I5 HIGH PV I5 HIGH PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Workstation Alarms

  • 8/6/2019 Alarm Messages A1

    47/74

    Meaning: Analog input I5 is less than theconfigured LO alarm value.

    PV I6 HIGH PV I6 HIGH PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I6 is greater than theconfigured HI alarm value.

    PV I6 LOW PV I6 LOW PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I6 is less than theconfigured LO alarm value.

    PV I7 HIGH PV I7 HIGH PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I7 is greater than theconfigured HI alarm value.

    PV I7 LOW PV I7 LOW PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I7 is less than theconfigured LO alarm value.

    PV I8 HIGH PV I8 HIGH PV

    Point(s) which generate this alarm:Overrides, 8 Pos Switch (Control Blocks)

    Meaning: Analog input I8 is greater than theconfigured HI alarm value.

    PV I8 LOW PV I8 LOW PV

    Point(s) which generate this alarm:O id 8 P S it h (C t l Bl k )

    maxSTATION Installation

  • 8/6/2019 Alarm Messages A1

    48/74

    Meaning: 'Generic' alarm indicating that thepoint has generated a PV limit alarm but thecondition cleared before it was logged.

    RANGE HIGH RANGE HIGH OVERRANGE

    Point(s) which generate this alarm: DataBlocks, Analog Input Buffers

    Meaning: The input to the data block isgreater than the configured range high limit.

    RANGE LOW RANGE LOW UNDERRANGE

    Point(s) which generate this alarm: DataBlocks, Analog Input Buffers

    Meaning: The input to the data block is lessthan the configured range low limit.

    RIGHT LIMIT RIGHT LIMIT RIGHT LIMIT

    Point(s) which generate this alarm:Positioner (Control Block)

    Meaning: The right limit input has becometrue while the motor is running in the reversedirection.

    RISING RISING RISING

    Point(s) which generate this alarm: Analog

    Data Blocks

    Meaning: The output of the data block isincreasing at a rate faster than theconfigured Rate-of-Change limit.

    RUNBACK RUNBACK DV

    Point(s) which generate this alarm: Hard

    Runback (Control Block)

    Meaning: The logic input calling for arunback has become true and the output of theblock is being decreased; or the limitassociated with the logic input calling forth b k h b d d

    Workstation Alarms

  • 8/6/2019 Alarm Messages A1

    49/74

    block is being decreased to the limitassociated with the logic input calling forthe rundown.

    RUN'G NO F/R RUN NO MF/MR RUN NO FF

    Point(s) which generate this alarm: ReversingMotor Controller (Cntrl Block)

    Meaning: Either the motor forward input or

    the motor reverse input goes false whilemotor is running.

    RUNN'G NO RF RUNN NO RF RUN NO RF

    Point(s) which generate this alarm: ReversingMotor Controller (Cntrl Block)

    Meaning: The motor running feedback input

    goes false while the motor is running.

    RUNUP RUNUP DV

    Point(s) which generate this alarm: DemandLimit Regulator (Control Block)

    Meaning: The logic input calling for a runuphas become true and the output of the block isbeing increased to the limit associated withthe logic input calling for the runup.

    SEC'Y FAIL SEC FAIL SEC FAIL

    Point(s) which generate this alarm:**Receives (Control Blocks)

    Meaning: No data being received from theother station; the last value that wasreceived came from the secondary DPU of abackup pair.

    SEC'Y NO RDY SEC NOT RDY NOT READY

    Point(s) which generate this alarm: Backup(Control Block)

    maxSTATION Installation

    i O f h l k i

  • 8/6/2019 Alarm Messages A1

    50/74

    Meaning: One of the Interlock inputsconfigured as a Sequence Interlock has becometrue. The motor will be turned off only if itis not already in the Running Forward or

    Running Reverse states. This alarm may causethe algorithm to go to the stopping state.

    SEQUENC INTERLOC SEQ INTERLOC SEQ INTERLOC

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary ControlModule ExCEL.

    SETPT CLAMP SETPT CLAMP SP

    Point(s) which generate this alarm: PIDControl Block

    Meaning: 'Generic' alarm indicating that thepoint has generated a setpoint clamp alarm butthe condition cleared before it was logged.

    SETPT HI SETPT HI SP

    Point(s) which generate this alarm: PIDControl Block

    Meaning: The setpoint is greater than thevalue configured in K5.

    SETPT LO SETPT LO SP

    Point(s) which generate this alarm: PIDControl Block

    Meaning: The setpoint is less than the valueconfigured in K4.

    START START START

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Workstation Alarms

    M i g Th f db k i t h t g

  • 8/6/2019 Alarm Messages A1

    51/74

    Meaning: The run feedback input has not gonetrue within the configured time limit duringthe starting sequence of the motor.

    START NO F/R ST NO MF/MR START NO FF

    Point(s) which generate this alarm: ReversingMotor Controller (Cntrl Block)

    Meaning: The motor forward (or motor reverse)input has not gone true within 2 seconds ofthe start sequence of the motor.

    TIME EXCEED TIME EXCEED TIME XCD

    Point(s) which generate this alarm:Sequencer, Ramp Gen (Control Block)

    Meaning: The configured time to move to thenext step of the ramp or sequence has been

    exceeded.

    TRIP TRIP TRIP

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary ControlModule ExCEL.

    UNAVAIL FLD DEV UA FIELD DEV UA FIELD DEV

    Point(s) which generate this alarm: BinaryControl (Control Block)

    Meaning: User-defined in Binary ControlModule ExCEL.

  • 8/6/2019 Alarm Messages A1

    52/74

    P III

  • 8/6/2019 Alarm Messages A1

    53/74

    Part III

    Alarm Message

    Reference Guide

    System Alarms

    Part III consists of an alphabetic listing of all maxDNA System Alarm

    messages. The following pages contain the actual message text (appearing

    here in all upper case characters), how the alarm impacts the DPU, the

    reporting device and a description of what each system alarm messagemeans.

  • 8/6/2019 Alarm Messages A1

    54/74

    Alarm Message Reference Guide System Alarms

  • 8/6/2019 Alarm Messages A1

    55/74

    Alarm Text Type CausesDPU

    Failover

    ActivatesDPU

    OfflineContact

    DPUAlarm

    Severity

    ReportingDevice

    Description

    AP CANNOT COMMUNICATE ON

    NETWORK A

    APPL An Applications Processor has lost communications with

    a Real-Time Processor on Network A. Real-Time

    Processors regularly broadcast their status on both control

    room networks. All Graphics Processors will receive all

    Real-Time Processor broadcasts, even if the Graphics

    Processor and Real-Time Processor are in different

    domains. When a Graphics Processor ceases to receive a

    broadcasts from a Real-Time Processor on this network, itgenerates this alarm. This situation may be caused by any

    number of failures, such as a bad Ethernet card A in the

    Applications Processor, a bad cable, a bad Ethernet card A

    in the Real-Time Processor, or a failed Real-Time

    Processor.

    APPLICATIONS PROCESSOR SWITCHED

    SERVERS

    APPL The Applications Processor has either lost Control Room

    Network communications with its current Real-Time

    Processor or has determined that a different Real-Time

    Processor in the same domain has a better data highway

    status. This is a one shot alarm and does not persist.

    AP CANNOT COMMUNICATE ON

    NETWORK B

    APPL An Applications Processor has lost communications with a

    Real-Time Processor on Network B. Real-Time

    Processors regularly broadcast their status on both control

    room networks. All Graphics Processors will receive all

    Real-Time Processor broadcasts, even if the Graphics

    Processor and Real-Time Processor are in different

    domains. When a Graphics Processor ceases to receive a

    broadcast from a Real-Time Processor on this network, it

    generates this alarm. This situation may be caused by any

    number of failures, such as a bad Ethernet card B in the

    Applications Processor, a bad cable, a bad Ethernet card B

    in the Real-Time Processor, or a failed Real-Time

    Processor.

    Metso Automation, Inc. 278558

    III-3

    Alarm Message Referenc e Guide System Alarms

  • 8/6/2019 Alarm Messages A1

    56/74

    Alarm Text Type CausesDPU

    Failover

    ActivatesDPU

    OfflineContact

    DPUAlarm

    Severity

    ReportingDevice

    Description

    BACKUP LINK CRC/FRAMEERROR NO NO 11 QUE There was a communications error (either a cyclic

    redundancy check failed, or there was a frame error) in the

    high-speed backup link between a backup pair of DPUs.

    BACKUP LINK QUEUE OVERFLOW NO NO 13 QUE The inactive DPU of a backup pair is not keeping up with

    information coming over the backup link.

    BACKUP LINK TIMEOUT NO NO 04 QUE The active DPU of a pair of backup DPUs is reporting that

    the inactive DPU didnt respond to a query within the

    timeout period.

    BATTERY #1 WEAK NO NO 02 IOP Battery #1 weak on DPU motherboard (model 555-2) or

    battery weak for CMOS on the CPU board (models PSF

    and PDP).

    BATTERY #2 WEAK NO NO 03 IOP Battery #2 weak on DPU motherboard. (model 555-2) or

    battery pack weak on motherboard (models PSF and

    PDP).

    BUFFER OVERFLOW DHWn One of the highway processor's communications buffers is

    not being emptied by the DBRT in the RTP. Will

    probably require that the Real-Time Processor be reset.

    BUFFER OVERFLOW YES NO 37 DHW The DPUs highway processors communications buffers

    are not being emptied by the CP. Will require that the

    DPU be reset.

    Metso Automation, Inc. 278558

    III-4

  • 8/6/2019 Alarm Messages A1

    57/74

  • 8/6/2019 Alarm Messages A1

    58/74

    Alarm Message Reference Guide System Alarms

    Alarm Text Type CausesActivates DPU Reporting Description

  • 8/6/2019 Alarm Messages A1

    59/74

    ypDPUFailover

    DPUOffline

    Contact

    AlarmSeverity

    p gDevice

    p

    PARTITION which the events are stored.

    CPU FAILURE DHWn The highway processor's periodic diagnostic test of its

    CPU detected a fault.

    CPU FAILURE YES NO 48 DHW The highway processors periodic diagnostic test of its

    CPU detected a fault.

    CURRENT RTP IS NOT A PREFERRED

    SELECTION

    APPL GP A Graphics or Applications Processor is currently

    using a Real-Time Processor as a data server and that

    Real-Time Processor is not on its preferred server list.

    This alarm will persist until the station starts using a

    preferred Real-Time Processor as its current server.

    The switch to non-preferred server can happen either

    as a result of failure of all preferred servers, or manual

    switch via the RTP Selection Display.

    CURRENT YEAR IS OUT OF CONFIGURED

    RANGE

    RTP The time configuration file which has been produced

    and installed by the Configuration Builder is not

    correct; thus, this Real-Time Processor will roll back

    to its previous configuration. See the Install log file

    which is built by the Configuration Builder.

    DAQD OR IOP DEADMAN TIMER TIMED

    OUT

    YES YES 18 IOP IOP timed out (periodic tasks not being scheduled).

    Millisecond interrupts have stopped.

    DATA POINT RECEIVES IN LINKFAIL YES NO 25 IOP Data block receive in Linkfail condition; data is not

    being received by Data Block.

    DEADMAN TIMER NOT REFRESHED DHWn This highway processor is reporting that its own

    deadman timeout circuitry has not been refreshed.

    DH NEVER RECEIVED CP RESPONSE YES NO F0 DHW The highway CPU requested data from the CP in order to

    respond to a highway request; but, after a timeout period,the CP had not responded.

    DMA TIMEOUT ON NETWORK SCSI

    OPERATION

    RTP There is a fault in the SCSI bus of this WorkStation: a

    DMA operation was not completed within the required

    timeout period. The most likely reason for this error is that

    some Graphics Processors in this WorkStation have the

    same SCSI ID (look at CONFIG.INI in the \VUE

    subdirectory to see). There may also be a hardware fault

    such as a lose SCSI connector, a defective SCSI cable, etc.

    Metso Automation, Inc. 278558

    III-7

    Alarm Message Referenc e Guide System Alarms

    Alarm Text Type CausesActivates DPU Reporting Description

  • 8/6/2019 Alarm Messages A1

    60/74

    ypDPUFailover

    DPUOffline

    Contact

    AlarmSeverity

    p gDevice

    p

    DPU BACKUP PAIR IS RUNNING ON

    SECONDARY

    NO NO 07 SLOT In a DPU backup pair, the Secondary is currently active.

    After you determine that the Primary DPU is able to take

    control, you can transfer control back via the pushbutton

    on that DPU.

    DPU EVENT QUEUE FLUSHED RTP The event queue of a DPU has been emptied; this event

    was received from that DPU.

    DPU EVENT QUEUE OVERFLOWED RTP The event queue of a DPU has not been emptied fast

    enough by one or more Real-Time Processors; thus some

    older events in the queue have been overwritten by newerevents, and the older ones will not be collected by those

    Real-Time Processors.

    DPU FAILURE: ILLEGAL RETURN THRU 0 YES YES FE SLOT An internal failure has occurred in the DPU; this is a fatal

    error.

    DPU FAILURE: SRAM CHECKSUM ERROR YES YES FF SLOT There is a checksum error in the static RAM (the RAM

    which contains the operating system) of this DPU. This is

    a fatal error (reported by model 555-2 only).

    DPU IS OFFLINE NO NO 07 IOP The DPU is presently offline, so it is no longer updating

    any process/control outputs. Check the state of the DPU

    keylock and Interaction Page 9 to get the DPU back

    online.

    Alarm Text Type CausesDPUFailover

    ActivatesDPUOfflineContact

    DPUAlarmSeverity

    ReportingDevice

    Description

    DPU PROCESSOR FAN FAILURE NO NO 04 SLOT The cooling fan mounted on the CP of the PDP DPU hasfailed. Replace or repair the fan immediately to avoid

    overheating.

    DRAM CODE CHECKSUM ERROR YES YES FD SLOT The CP background diagnostics has detected an incorrect

    checksum in the program logic stored in dynamic RAM

    (DRAM); the DPU will have to be reset.

    Metso Automation, Inc. 278558 III-8

    Alarm Message Reference Guide System Alarms

    Alarm Text Type CausesActivates DPU Reporting Description

  • 8/6/2019 Alarm Messages A1

    61/74

    DPUFailover

    DPUOffline

    Contact

    AlarmSeverity

    Device

    DUPLICATE HIGHWAY STATION

    NUMBERS

    YES NO 46 DHW The highway processor received a message in which the

    highway address of the sender was the same as its address.

    DUPLICATE HIGHWAY STATION

    NUMBERS

    DHWn The highway processor received a message in which the

    highway address of the sender was the same as its address.

    ECC CORRECTED A ONE-BIT ERROR NO NO 11 DHW ECC logic detected and corrected a single-bit DRAM

    error (reported by model 555-2 only).

    EVENT BARREL OVERFLOW RTP The event barrel of a Real-Time Processor has not been

    emptied fast enough by its client Applications Processor;

    thus, some older events which had been stored in the

    barrel will be lost.

    EVENT DISK I/O ACCESS ERROR RTP This alarm indicates a problem occurred when the events

    subsystem tried to access the hard drive of the Real-Time

    Processor. If this alarm persists, then there might be a

    problem with the hard drive.

    EVENT QUEUE DATA LOSS QUE Event Queue overflow; dequeue rate is insufficient.

    EVENT QUEUE HAS BEEN RESET YES NO E2 QUE Event Queue reset.

    EVENTS BUFFER NEARLY FULL APPL The CURRENT volume is not mounted on the opticaldrive, or the CURRENT volume is full and needs to be

    closed out and replaced. The Event History buffer has

    been storing data and is nearly full.

    EVENTS DATA LOSS EMINENT APPL Same as above message, but this is a second-level warning

    for the Event History buffer.

    Alarm Text Type CausesDPU

    Failover

    ActivatesDPU

    OfflineContact

    DPUAlarm

    Severity

    ReportingDevice

    Description

    EVENTS DATA LOST APPL Same as above, but Event History data has now been lost

    and cannot be recovered.

    ExCEL STACK CHECK ERROR NO NO 04 PFI As of the execution of a check command, the ExCEL

    processor's stack was not empty (the check command tests

    the state of the stack to permit debug of an ExCEL

    ro ram which is causin the alarm "User Stack no em t

    Metso Automation, Inc. 278558

    III-9

    Alarm Message Referenc e Guide System Alarms

    Alarm Text Type CausesDPU

    ActivatesDPU

    DPUAl

    ReportingD i

    Description

  • 8/6/2019 Alarm Messages A1

    62/74

    DPUFailover

    DPUOffline

    Contact

    AlarmSeverity

    Device

    at Restart" to be reported by PFI).

    GENERIC SCSI I/O ERROR RTP There is a fault in the SCSI bus of this WorkStation. This

    can be caused by either hardware, software, or a processor

    which is temporarily too busy.

    GLOBAL IGAP COMPLETED Highway

    Comm

    HWYn An IGAP (Initialize Go-Ahead Pointers) was completed

    on this highway.

    GP BECAME ACTIVE RTP The Real-Time Processor annunciates that the attached

    Graphics Processor has become active.

    GP HAS SWITCHED SERVERS APPL The Graphics Processor has either lost Control Room

    Network communications with its current Real-Time

    Processor or has determined that a different Real-Time

    Processor in the same domain has a better data highway

    status. This is a one shot alarm and does not persist.

    HDI CARD(S) MISSING AND CARD(S)

    TIMEOUT

    RTP An HDI card has failed during normal operation. This may

    be a temporary condition due to this station's being

    IGAP'd out; if not, then the Real-Time Processor will have

    to be reset.

    HIGHWAY STATION # DISCREPANCY NO NO 04 DHW This highway processor is reporting that the periodic

    check of its highway address is failing.

    HIGHWAY STATION # DISCREPANCY DHWn This highway processor is reporting that the periodic

    check of its highway address is failing.

    Alarm Text Type CausesDPU

    Failover

    ActivatesDPU

    OfflineContact

    DPUAlarm

    Severity

    ReportingDevice

    Description

    HWYn TIMED OUT OR COMMUNICATION

    CEASED

    RTP This highway processor either stopped refreshing its

    deadman timer, or it failed to perform the periodic

    highway query issued by DBRT. Will probably require the

    Real-Time Processor to be reset.

    Metso Automation, Inc. 278558 III-10

    Alarm Message Reference Guide System Alarms

    Alarm Text Type CausesDPU

    ActivatesDPU

    DPUAl

    ReportingD i

    Description

  • 8/6/2019 Alarm Messages A1

    63/74

    DPUFailover

    DPUOffline

    Contact

    AlarmSeverity

    Device

    I/O BUS ACCESS ERROR YES NO B0 PFI The DPUs programmed functions interpreter is unable to

    communicate with one or more modules on the I/O bus.

    ILLEGAL ALGORITHM CODE YES NO 40 SLOT A control block contains an algorithm code which is not

    part of the standard algorithm set.

    ILLEGAL BUFFER POINTER VALUE YES NO 30 DHW The highway processor does a periodic check of the buffer

    pointers of its communication buffers; this alarm indicates

    that one or more pointers were outside the allowed range.

    Will require that the DPU be reset.

    ILLEGAL BUFFER POINTER VALUE DHWn The highway processor does a periodic check of the bufferpointers of its communication buffers; this alarm indicates

    that one or more pointers were outside the allowed range.

    Will require the Real-Time Processor to be reset.

    ILLEGAL OR NO APPLICATION OBJECT YES NO 17 PFI The application program area of the DPU is either empty

    because the DPU needs to be reloaded, or there is illegal

    object code in that program area.

    IOM CYCLE EXCEEDED 1 MSEC YES YES E8 QUE The IOM is unable to complete its scheduled processing

    each millisecond. This condition occurs if either the IOM

    stops running or if it is configured with too many digital

    terminal boards (16 in model PSF SFP, 25 in model PDP).

    LOSS OF COMM WITH A GRAPHICS

    PROCESSOR

    RTP This Real-Time Processor could no longer communicate

    with one of its client Graphics Processors. The RTP's

    timesync function generates this alarm if each GP does not

    periodically issue time sync requests. This can be an

    Ethernet communications problem, or a failure of a

    Graphics Processor. This is a one-shot alarm and does not

    persist.

    Alarm Text Type CausesDPUFailover

    ActivatesDPUOfflineContact

    DPUAlarmSeverity

    ReportingDevice

    Description

    LOSS OF COMM WITH AN APPLICATIONS

    PROC

    RTP This Real-Time Processor could no longer communicate

    with its client A lications Processor. The RTP's time

    Metso Automation, Inc. 278558

    III-11

  • 8/6/2019 Alarm Messages A1

    64/74

    Alarm Message Reference Guide System Alarms

    Alarm Text Type CausesActivates DPU Reporting Description

  • 8/6/2019 Alarm Messages A1

    65/74

    Alarm Text Type CausesDPU

    Failover

    ActivatesDPU

    OfflineContact

    DPUAlarm

    Severity

    ReportingDevice

    Description

    MODEM JABBERHALT RELAY

    ACTIVATED

    DHWn The highway modem logic deactivated the relays which

    connect the modem's receiver/transmitter to the data

    highway. This action will be taken if the highway processor

    will not cease transmitting.

    NO CLEAR-TO-SEND AFTER

    REQUEST-TO-SEND

    NO NO 12 DHW The highway processor wanted to transmit, but its modem

    would not activate CTS to permit transmission to begin.

    NO CLEAR-TO-SEND AFTER

    REQUEST-TO-SEND

    DHWn The highway processor wanted to transmit, but its modem

    would not activate CTS to permit transmission to begin.NO TIME CONF DATA FOR CURRENT

    YEAR

    RTP The time configuration file which has been produced and

    installed by the Configuration Builder is not correct; thus,

    this Real-Time Processor will roll back to its previous

    configuration. See the Install log file which is built by the

    Configuration Builder.

    NON-MASTER STN INITIATED A TOKEN

    PASS

    Highway

    Comm

    HWYn This system monitor detected that another station initiated a

    token pass which was out of sequence. This may be

    reported if there is a recovery from stallout.

    OPTICAL DISK MOUNT REQUEST APPL A request for either Process History data or Event History

    data has resulted in a request to mount an unmounted

    WORM volume.

    OPTICAL DISK REQUIRES ATTENTION APPL The optical disk which is currently being written to is either

    full or there are write errors.

    OTP FREE LIST EMPTY RTP There is no space left in the outstanding transaction packet

    pool of memory. This alarm could be indicative of a

    software operational problem within the Real-Time

    Processor, but it could also occur as a side-effect of a SCSI

    communication problem. The Real-Time Processor will

    probably need to be rebooted.

    Metso Automation, Inc. 278558

    III-13

    Alarm Message Referenc e Guide System Alarms

    Alarm Text Type CausesActivates DPU Reporting Description

  • 8/6/2019 Alarm Messages A1

    66/74

    Alarm Text Type CausesDPU

    Failover

    ActivatesDPU

    OfflineContact

    DPUAlarm

    Severity

    ReportingDevice

    Description

    PARALLEL I/O MODULE / DATA PT CONF.

    ERR

    YES CONFIG.

    DEP.

    B0 IOP There is a discrepancy between the parallel I/O module

    assignments called for in this DPU's configuration and the

    actual modules which are present. The module address is

    displayed on Interaction Page 10 with a red background.

    POINT TRANSFER DATABASE ERROR RTP There is a problem with the point transfer database file

    which has been produced and installed by the

    Configuration Builder; thus, this Real-Time Processor will

    roll back to its previous configuration. See the Installlog file which is built by the Configuration Builder.

    PRINTER 1 NEEDS ATTENTION

    PRINTER 2 NEEDS ATTENTION

    PRINTER 3 NEEDS ATTENTION

    PRINTER 4 NEEDS ATTENTION

    PRINTER 5 NEEDS ATTENTION

    PRINTER 6 NEEDS ATTENTION

    PRINTER 7 NEEDS ATTENTION

    PRINTER 8 NEEDS ATTENTION

    APPL A printer fault has been detected on the reported printer.

    PROCESS HISTORY BUFFER NEARLY

    FULL

    APPL The CURRENT volume is not mounted on the optical

    drive, or the CURRENT volume is full and needs to be

    closed out and replaced. The Process History buffer has

    been storing data and is nearly full.

    PROCESS HISTORY DATA LOSS EMINENT APPL Same as above message, but this is a second-level warning

    for the Process History buffer.

    PROCESS HISTORY DATA LOST APPL Same as above, but Process History data has now been

    lost and cannot be recovered.

    PROCESSOR BOARD LOCAL RAM ERROR YES NO 44 DHW DPU highway CPU local RAM read/write error found by

    the on-line diagnostics.

    PROCESSOR BOARD PROM CHECKSUM

    ERROR

    YES NO 45 DHW PROM checksum error found by on-line diagnostics.

    Metso Automation, Inc. 278558 III-14

    Alarm Message Reference Guide System Alarms

    Alarm Text Type CausesDPU

    ActivatesDPU

    DPUAlarm

    ReportingDevice

    Description

  • 8/6/2019 Alarm Messages A1

    67/74

    Failover Offline

    Contact

    Severity

    PROCESSOR EXECUTED ILLEGAL

    INSTRUCTION

    YES NO 35 DHW The highway processor executed an instruction reserved

    for a fault condition. Will require that the DPU be reset.

    PROCESSOR EXECUTED ILLEGAL

    INSTRUCTION

    DHWn The highway processor executed an instruction reserved

    for a fault condition. Will probably require the Real-Time

    Processor be reset.

    PROCESSOR RESTART - RESET OR

    RELOAD

    NO NO 10 IOP,SLOT,

    DHW,PFI

    DPU has been reset, or reload has been completed.

    PROM CHECKSUM FAILURE DHWn The highway processor detected an error in its periodic

    on-line test of the checksum of its software PROM.REAL-TIME CLOCK CHIP ON 1

    STDB

    FAILED

    YES NO 28 IOP Either a) the real-time clock hardware has failed; or b)

    there was an error in the reception of the IRIG-B time

    sync signal.

    RECOVERY FROM STALLOUT

    ATTEMPTED ON HWY

    YES NO 27 DHW A highway stallout (no highway activity for 500

    microseconds) condition was detected; this station

    recovered by restarting the token.

    RECOVERY FROM STALLOUT

    ATTEMPTED ON HWY

    DHWn A highway stallout (no highway activity for 500

    microseconds) condition was detected; this station

    recovered by restarting the token.

    RESET (any) This station has been reset.

    RTP CANNOT COMMUNICATE ON

    NETWORK A

    RTP The Real-Time Processor failed to successfully initialize

    the NIC adapter card for Network A on start-up, or it

    cannot communicate with an Applications Processor on

    Network A. Communication failures can be caused by any

    number of failures, such as a bad Ethernet card A in the

    Real-Time Processor, a bad cable, a bad Ethernet card A

    in the Applications Processors or a failed Applications

    Processors.

    Metso Automation, Inc. 278558 III-15

    Alarm Message Referenc e Guide System Alarms

    Alarm Text Type CausesDPU

    ActivatesDPU

    DPUAlarm

    ReportingDevice

    Description

  • 8/6/2019 Alarm Messages A1

    68/74

    Failover Offline

    Contact

    Severity

    RTP CANNOT COMMUNICATE ON

    NETWORK B

    RTP The Real-Time Processor failed to successfully initialize

    the NIC adapter card for Network B on start-up, or it

    cannot communicate with an Applications Processor on

    Network B. Communication failures can be caused by any

    number of failures, such as a bad Ethernet card B in the

    Real-Time Processor, a bad cable, a bad Ethernet card B in

    the Applications Processors or a failed Applications

    Processors.

    RTP DATABASE LOAD FAILURE RTP One or more configuration database files, which have beenproduced and installed by the Configuration Builder, are

    not correct; thus, this Real-Time Processor will roll back

    to its previous configuration. See the Install log file which

    is built by the Configuration Builder.

    RTP TREND DATABASE LOAD FAILURE RTP The trend database files, which have been produced and

    installed by the Configuration Builder, are not correct;

    thus, this Real-Time Processor will roll back to its

    previous configuration. See the Install log file which is

    built by the Configuration Builder.RTP TREND SCAN FAILURE RTP Trend scanning was disrupted, usually because of severe

    highway communication problems.

    SCAN NOT COMPLETED IN TIME

    ALLOWED

    RTP Trend scanning was not completed in its allotted time,

    usually because the highway token rate is momentarily

    below the level needed to permit timely completion of all

    tasks, or because of hardware problems which prevent

    highway communications.

    SCSI BUS COMMUNICATIONS ERROR RTP There was an error in the operation of the SCSI bus which

    runs among the Real-Time Processor and its clients (the

    Applications and Graphics processors).

    Metso Automation, Inc. 278558 III-16

    Alarm Message Reference Guide System Alarms

    Alarm Text Type CausesDPU

    ActivatesDPU

    DPUAlarm

    ReportingDevice

    Description

  • 8/6/2019 Alarm Messages A1

    69/74

    Failover Offline

    Contact

    Severity

    SCSI NETWORK CONFIGURATION ERROR RTP The Real-Time Processor's database of hardware devices

    does not match the names and addresses of the SCSI

    client(s) which are currently connected to that device.

    SERIAL I/O COMMUNICATIONS ERROR NO NO 08 DHW The highway serial I/O chip is generating interrupts

    which, in the CPU's opinion, are garbage.

    SERIAL I/O COMMUNICATIONS ERROR DHWn The highway serial I/O chip is generating interrupts

    which, in the CPU's opinion, are garbage.

    SERIAL I/O DATA POINT ERROR YES NO 50 IOP Data has not been resent within the timeout period.

    SERIAL PORT 1 COMMUNICATIONERROR

    SERIAL PORT 2 COMMUNICATION

    ERROR

    NO NO 1213

    PFI An ExCEL program is communicating to an externaldevice through a serial port. Either the ExCEL program

    cannot keep up with the incoming data stream, or the

    ExCEL program is transmitting too fast for the selected

    port and baud rate. You should check the RTS/CTS and

    XON/XOFF interlocks, as well as the ExCEL program

    running state.

    SLOT #16 PARALLEL I/O MODULE

    TROUBLE

    SLOT #nn PARALLEL I/O MODULE

    TROUBLE

    SLOT #nn PARALLEL I/O MODULE

    TROUBLE

    YES NO D1

    B1-BF

    C1-D0

    SLOT Any slot which is driving an Output Driver module will

    report this alarm if the Output Driver reports an output

    fault. D1 is used for slot 16; B1 to BF are used for slots 1

    to 15; C1 to D0 are used for slots 17 to 32.

    SOE AND DIGITAL INPUT DATA LOSS YES NO E0 IOP Digital input barrel overflow caused by excessive input

    state change activity. The SOE barrel has 3000 entries,

    and is emptied at the rate of 5000 entries per second, so

    the excessive activity would have to continue for an

    extended period of time.

    STACK OVERFLOW OR UNDERFLOW YES NO 38 DHW Stack underflow detected in local RAM.

    Metso Automation, Inc. 278558 III-17

    Alarm Message Referenc e Guide System Alarms

    Alarm Text Type CausesDPU

    ActivatesDPU

    DPUAl

    ReportingD i

    Description

  • 8/6/2019 Alarm Messages A1

    70/74

    DPU

    Failover

    DPU

    OfflineContact

    Alarm

    Severity

    Device

    STATION BECAME INACTIVE Highway

    Comm

    HWYn The named highway station became inactive; normally

    reported after an IGAP caused the removal of that device

    from the system map.

    (name)

    STATION DIDN'T RESPOND TO A QUERY Highway

    Comm

    HWYn A data highway query was made of a station, and that

    station did not respond, perhaps because it failed.(name)

    STATION HAS SWITCHED RTP SERVER APPL GP A Graphics or Applications Processor has switched to a

    new Real-Time Processor server either due to automatic

    failover or manual request via the RTP Selection Display.This is a one-shot alarm and does not persist.

    STATION IS NO LONGER IGAP'D - RE-

    IGAP

    Highway

    Comm

    HWYn A station on this data highway is not IGAP'd, probably

    because it was reset after the last IGAP command (a station

    always comes up unIGAP'd).

    STATION MISSED AN IGAP COMMAND Highway

    Comm

    HWYn After an IGAP, a station did not correctly perform the

    IGAP operation (consisting of trying each address after its

    own until it finds a station, and then always giving the

    token to that station).

    (name)

    STATION PRESENT BUT NOTCONFIGURED

    RTP The Real-Time Processor has detected the presence of aSCSI device which is not defined in the RTPs hardware

    database, or the SCSI device is not configured properly to

    match the database information.

    STN BECAME ACTIVE FOR THE FIRST

    TIME

    Highway

    Comm

    HWYn A station on HWYn became active for the first time; it will

    be added to the highway map maintained by each token

    monitor.

    STN DIDN'T USE CORRECT LOW LOOP

    ADDRESS

    Highway

    Comm

    HWYn The named station did not use the correct low-loop address

    when passing the token from the high-traffic loop to the

    low loop.

    (name)

    STN IS MASTER WHILE THIS STN IS

    MASTER

    Highway

    Comm

    HWYn This station has the token, and therefore is the master at the

    present moment. This station then detects that another

    station is attempting to transmit (illegally).

    (name)

    STN RCVR PROBLEM / MONITOR MISSED

    TOKEN

    Highway

    Comm

    HWYn A station appeared to have missed the token pass, maybe

    because this station had a receiver problem and did not

    hear the token being passed.

    (name)

    Metso Automation, Inc. 278558 III-18

    Alarm Message Reference Guide System Alarms

    Alarm Text Type CausesDPUF il

    ActivatesDPUOffli

    DPUAlarmS it

    ReportingDevice

    Description

  • 8/6/2019 Alarm Messages A1

    71/74

    Failover Offline

    Contact

    Severity

    STN SKIPPED A STN ON SRCH FOR NEXT

    STN

    Highway

    Comm

    HWYn During an IGAP procedure, a station was searching for

    stations with addresses greater than its own; during that

    search, that station appeared to have skipped a station.

    TASK OVERRUN YES NO 27 IOP Task overrun counters are non-zero: the CP couldnt keep

    up with scheduled periodic tasks (control blocks, data

    blocks, and analog input buffers).

    THIS STATION STALLED OUT THE

    HIGHWAY

    NO NO 13 DHW When this station had the token, it attempted to pass it on,

    but it got no response; so, it dropped the token to force a

    stallout, thus permitting a system monitor to restart tokenpassing.

    THIS STATION STALLED OUT THE

    HIGHWAY

    DHWn When this station had the token, it attempted to pass it on,

    but it got no response; so, it dropped the token to force a

    stallout, thus permitting a system monitor to restart token

    passing.

    TIME CONFIGURATION FILE LOAD

    FAILURE

    RTP The time configuration file which describes timezone,

    standard or daylight savings, etc. was read correctly, but

    when the file was to be used by this Real-Time Processor,

    there was an error in the file. This Real-Time Processorwill 'roll back' to its previous configuration. See the Install

    log file which is built by the Configuration Builder.

    TIME CONFIGURATION FILE READ

    ERROR

    RTP The time configuration file which describes time zone,

    standard or daylight savings, etc. was not read correctly by

    this Real-Time Processor. This Real-Time Processor will

    roll back to its previous configuration. See the Install

    log file which is built by the Configurati