Akumal Mod. j - Submittal
description
Transcript of Akumal Mod. j - Submittal
-
Sound Power by Octave BandSound
Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 90 84 94 86 82 80 77 68 90 78 30
Performance Corrections
Elevation (ft) 0
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 4.1
Inlet Conditions Standard
Outlet Conditions Standard
Model: SWB-224-50
Backward Inclined Centrifugal Utility Fan
Actual Performance
Requested Volume (CFM) 10,580
Actual Volume (CFM) 10,580
External SP (in. wg) 0.3
Total SP (in. wg) 0.3
OV (ft/min) 3,206
Fan RPM 1260
Operating Power (hp) 4.12
Tip Speed (ft/min) 8,081
Static Eff. (%) 13
FEG 80
Fan Configuration
Quantity 1
Arrangement 10
Rotation CW
Discharge Position TH
Drive Type Belt
Dimensional
Weight w/o Acc's (lb) 554
Weight w/ Acc's (lb) 558
Max T Motor Frame Size 256
Motor
Motor Mounted Yes
Size (hp) 5
V/C/P 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 15.2
Motor Pulley Type Adjustable
Notes:All dimensions shown are in units of in.
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J01Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 1 of 18
camper1Resaltado -
Model: SWB-224-50
Backward Inclined Centrifugal Utility Fan
Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with
prepunched mounting holes - Adjustable motor plate - Corrosion resistant
fasteners - Steel components are phosphatized and coated
Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12
Steel Scroll Housing
Steel Wheel Construction
Steel Inlet Cone
Switch, NEMA-1, Toggle, Junction Box Mounted & Wired
No Weatherhood--Unit for Indoor Use Only
Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire
Fan
Unit Warranty: 1 Yr (Standard)
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J01Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 2 of 18
-
NOT DRAWN TO SCALECONNECTIONS
INLET OUTLET
25.88INLET
HO
US
ING
CE
NTE
RLIN
E
19
26
HO
USIN
G
CE
NTER
LIN
E
END VIEW
HO
US
ING
CE
NTE
RLIN
E
0.634 Holes
FAN FOOTPRINT
SHAFT
CENTERLINE
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
SIDE VIEW
41.50
25.88
19.00
12.0034.50
46.50
2.50
15.56
15.56
9.25
26.75
17.75
40.63
31.50
26.25
57.75
33.63
SWB-224-50 Backward Inclined Centrifugal Utility Fan
Notes: All dimensions shown are in units of in.
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J01Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 3 of 18
-
Sound Power by Octave BandSound
Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 92 89 92 89 83 81 77 71 91 79 31
Performance Corrections
Elevation (ft) 0
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 4.1
Inlet Conditions Standard
Outlet Conditions Standard
Model: SWB-222-50
Backward Inclined Centrifugal Utility Fan
Actual Performance
Requested Volume (CFM) 9,100
Actual Volume (CFM) 9,100
External SP (in. wg) 0.3
Total SP (in. wg) 0.3
OV (ft/min) 3,358
Fan RPM 1493
Operating Power (hp) 3.98
Tip Speed (ft/min) 8,697
Static Eff. (%) 11
FEG 75
Fan Configuration
Quantity 1
Arrangement 10
Rotation CW
Discharge Position TH
Drive Type Belt
Dimensional
Weight w/o Acc's (lb) 436
Weight w/ Acc's (lb) 440
Max T Motor Frame Size 215
Motor
Motor Mounted Yes
Size (hp) 5
V/C/P 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 15.2
Motor Pulley Type Adjustable
Notes:All dimensions shown are in units of in.
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J02Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 4 of 18
camper1Resaltado -
Model: SWB-222-50
Backward Inclined Centrifugal Utility Fan
Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with
prepunched mounting holes - Adjustable motor plate - Corrosion resistant
fasteners - Steel components are phosphatized and coated
Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12
Steel Scroll Housing
Steel Wheel Construction
Steel Inlet Cone
Switch, NEMA-1, Toggle, Junction Box Mounted & Wired
No Weatherhood--Unit for Indoor Use Only
Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire
Fan
Unit Warranty: 1 Yr (Standard)
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J02Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 5 of 18
-
NOT DRAWN TO SCALECONNECTIONS
INLET OUTLET
23
INLET
HO
USIN
G
CE
NTER
LIN
E
17
23.5
HO
US
ING
CE
NTE
RLIN
E
END VIEW
HO
USIN
G
CE
NTE
RLIN
E
0.63
4 Holes
FAN FOOTPRINT
SHAFT
CENTERLINE
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
SIDE VIEW
39.63
23.00
17.00
11.0032.50
43.50
2.50
14.13
14.13
8.13
26.00
16.25
36.88
28.75
23.75
52.5
30.50
SWB-222-50 Backward Inclined Centrifugal Utility Fan
Notes: All dimensions shown are in units of in.
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J02Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 6 of 18
-
Sound Power by Octave BandSound
Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 88 85 88 83 79 77 72 66 86 74 24
Performance Corrections
Elevation (ft) 0
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 4.6
Inlet Conditions Standard
Outlet Conditions Standard
Model: SWB-222-30
Backward Inclined Centrifugal Utility Fan
Actual Performance
Requested Volume (CFM) 7,583
Actual Volume (CFM) 7,583
External SP (in. wg) 0.35
Total SP (in. wg) 0.35
OV (ft/min) 2,798
Fan RPM 1264
Operating Power (hp) 2.49
Tip Speed (ft/min) 7,361
Static Eff. (%) 18
FEG 75
Fan Configuration
Quantity 1
Arrangement 10
Rotation CW
Discharge Position TH
Drive Type Belt
Dimensional
Weight w/o Acc's (lb) 414
Weight w/ Acc's (lb) 418
Max T Motor Frame Size 215
Motor
Motor Mounted Yes
Size (hp) 3
V/C/P 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 9.6
Motor Pulley Type Adjustable
Notes:All dimensions shown are in units of in.
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J03Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 7 of 18
camper1Resaltado -
Model: SWB-222-30
Backward Inclined Centrifugal Utility Fan
Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with
prepunched mounting holes - Adjustable motor plate - Corrosion resistant
fasteners - Steel components are phosphatized and coated
Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12
Steel Scroll Housing
Steel Wheel Construction
Steel Inlet Cone
Switch, NEMA-1, Toggle, Junction Box Mounted & Wired
No Weatherhood--Unit for Indoor Use Only
Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire
Fan
Unit Warranty: 1 Yr (Standard)
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J03Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 8 of 18
-
NOT DRAWN TO SCALECONNECTIONS
INLET OUTLET
23
INLET
HO
USIN
G
CE
NTER
LIN
E
17
23.5
HO
US
ING
CE
NTE
RLIN
E
END VIEW
HO
USIN
G
CE
NTE
RLIN
E
0.63
4 Holes
FAN FOOTPRINT
SHAFT
CENTERLINE
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
SIDE VIEW
39.63
23.00
17.00
11.0032.50
43.50
2.50
14.13
14.13
8.13
26.00
16.25
36.88
28.75
23.75
52.5
30.50
SWB-222-30 Backward Inclined Centrifugal Utility Fan
Notes: All dimensions shown are in units of in.
9/11/2014Printed Date: AKUMAL MOD. JJob:
IK-J03Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 9 of 18
-
Sound Power by Octave BandSound
Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 90 83 93 85 81 79 74 68 88 77 28
Performance Corrections
Elevation (ft) 0
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 3.9
Inlet Conditions Standard
Outlet Conditions Standard
Model: SWB-224-75
Backward Inclined Centrifugal Utility Fan
Actual Performance
Requested Volume (CFM) 9,578
Actual Volume (CFM) 9,578
External SP (in. wg) 1.5
Total SP (in. wg) 1.5
OV (ft/min) 2,902
Fan RPM 1287
Operating Power (hp) 5.08
Tip Speed (ft/min) 8,257
Static Eff. (%) 46
FEG 80
Fan Configuration
Quantity 1
Arrangement 10
Rotation CW
Discharge Position TH
Drive Type Belt
Dimensional
Weight w/o Acc's (lb) 591
Weight w/ Acc's (lb) 595
Max T Motor Frame Size 256
Motor
Motor Mounted Yes
Size (hp) 7 1/2
V/C/P 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 22
Motor Pulley Type Adjustable
Notes:All dimensions shown are in units of in.
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J02Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 10 of 18
camper1Resaltado -
Model: SWB-224-75
Backward Inclined Centrifugal Utility Fan
Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with
prepunched mounting holes - Adjustable motor plate - Corrosion resistant
fasteners - Steel components are phosphatized and coated
Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12
Steel Scroll Housing
Steel Wheel Construction
Steel Inlet Cone
Switch, NEMA-1, Toggle, Junction Box Mounted & Wired
No Weatherhood--Unit for Indoor Use Only
Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire
Fan
Unit Warranty: 1 Yr (Standard)
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J02Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 11 of 18
-
NOT DRAWN TO SCALECONNECTIONS
INLET OUTLET
25.88INLET
HO
US
ING
CE
NTE
RLIN
E
19
26
HO
USIN
G
CE
NTER
LIN
E
END VIEW
HO
US
ING
CE
NTE
RLIN
E
0.634 Holes
FAN FOOTPRINT
SHAFT
CENTERLINE
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
SIDE VIEW
41.50
25.88
19.00
12.0034.50
46.50
2.50
15.56
15.56
9.25
26.75
17.75
40.63
31.50
26.25
57.75
33.63
SWB-224-75 Backward Inclined Centrifugal Utility Fan
Notes: All dimensions shown are in units of in.
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J02Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 12 of 18
-
Sound Power by Octave BandSound
Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 90 87 90 87 82 79 74 70 88 77 27
Performance Corrections
Elevation (ft) 0
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 4.0
Inlet Conditions Standard
Outlet Conditions Standard
Model: SWB-222-50
Backward Inclined Centrifugal Utility Fan
Actual Performance
Requested Volume (CFM) 7,982
Actual Volume (CFM) 7,982
External SP (in. wg) 1.5
Total SP (in. wg) 1.5
OV (ft/min) 2,945
Fan RPM 1471
Operating Power (hp) 4.37
Tip Speed (ft/min) 8,566
Static Eff. (%) 45
FEG 75
Fan Configuration
Quantity 1
Arrangement 10
Rotation CW
Discharge Position TH
Drive Type Belt
Dimensional
Weight w/o Acc's (lb) 436
Weight w/ Acc's (lb) 440
Max T Motor Frame Size 215
Motor
Motor Mounted Yes
Size (hp) 5
V/C/P 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 15.2
Motor Pulley Type Adjustable
Notes:All dimensions shown are in units of in.
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J03Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 13 of 18
camper1Resaltado -
Model: SWB-222-50
Backward Inclined Centrifugal Utility Fan
Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with
prepunched mounting holes - Adjustable motor plate - Corrosion resistant
fasteners - Steel components are phosphatized and coated
Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12
Steel Scroll Housing
Steel Wheel Construction
Steel Inlet Cone
Switch, NEMA-1, Toggle, Junction Box Mounted & Wired
No Weatherhood--Unit for Indoor Use Only
Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire
Fan
Unit Warranty: 1 Yr (Standard)
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J03Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 14 of 18
-
NOT DRAWN TO SCALECONNECTIONS
INLET OUTLET
23
INLET
HO
USIN
G
CE
NTER
LIN
E
17
23.5
HO
US
ING
CE
NTE
RLIN
E
END VIEW
HO
USIN
G
CE
NTE
RLIN
E
0.63
4 Holes
FAN FOOTPRINT
SHAFT
CENTERLINE
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
SIDE VIEW
39.63
23.00
17.00
11.0032.50
43.50
2.50
14.13
14.13
8.13
26.00
16.25
36.88
28.75
23.75
52.5
30.50
SWB-222-50 Backward Inclined Centrifugal Utility Fan
Notes: All dimensions shown are in units of in.
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J03Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 15 of 18
-
Sound Power by Octave BandSound
Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 92 88 94 90 84 82 77 72 92 80 33
Performance Corrections
Elevation (ft) 0
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 3.7
Inlet Conditions Standard
Outlet Conditions Standard
Model: SWB-224-75
Backward Inclined Centrifugal Utility Fan
Actual Performance
Requested Volume (CFM) 11,145
Actual Volume (CFM) 11,145
External SP (in. wg) 2
Total SP (in. wg) 2
OV (ft/min) 3,377
Fan RPM 1495
Operating Power (hp) 7.92
Tip Speed (ft/min) 9,587
Static Eff. (%) 46
FEG 80
Fan Configuration
Quantity 1
Arrangement 10
Rotation CW
Discharge Position TH
Drive Type Belt
Dimensional
Weight w/o Acc's (lb) 602
Weight w/ Acc's (lb) 606
Max T Motor Frame Size 256
Motor
Motor Mounted Yes
Size (hp) 7 1/2
V/C/P 230/60/3
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 22
Motor Pulley Type Adjustable
Notes:All dimensions shown are in units of in.
*FLA - based on tables 150 or 148 of National Electrical
Code 2002. Actual motor FLA may vary, for sizing thermal
overload, consult factory.
LwA - A weighted sound power level, based on ANSI S1.4
dBA - A weighted sound pressure level, based on 11.5 dB
attenuation per Octave band at 5 ft - dBA levels are not
licensed by AMCA International
Sones - calculated using AMCA 301 at 5 ft
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J04Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 16 of 18
camper1Resaltado -
Model: SWB-224-75
Backward Inclined Centrifugal Utility Fan
Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with
prepunched mounting holes - Adjustable motor plate - Corrosion resistant
fasteners - Steel components are phosphatized and coated
Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12
Steel Scroll Housing
Steel Wheel Construction
Steel Inlet Cone
Switch, NEMA-1, Toggle, Junction Box Mounted & Wired
No Weatherhood--Unit for Indoor Use Only
Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire
Fan
Unit Warranty: 1 Yr (Standard)
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J04Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 17 of 18
-
NOT DRAWN TO SCALECONNECTIONS
INLET OUTLET
25.88INLET
HO
US
ING
CE
NTE
RLIN
E
19
26
HO
USIN
G
CE
NTER
LIN
E
END VIEW
HO
US
ING
CE
NTE
RLIN
E
0.634 Holes
FAN FOOTPRINT
SHAFT
CENTERLINE
*SIDE VIEW IS VIEWED FROM DRIVE SIDE
SIDE VIEW
41.50
25.88
19.00
12.0034.50
46.50
2.50
15.56
15.56
9.25
26.75
17.75
40.63
31.50
26.25
57.75
33.63
SWB-224-75 Backward Inclined Centrifugal Utility Fan
Notes: All dimensions shown are in units of in.
9/11/2014Printed Date: AKUMAL MOD. JJob:
EK-J04Mark:
CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 18 of 18