Akumal Mod. j - Submittal

18
Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones Inlet 90 84 94 86 82 80 77 68 90 78 30 Performance Corrections Elevation (ft) 0 Airstream Temp.(F) 70 Air Density (ft3) 0.075 Drive Loss (%) 4.1 Inlet Conditions Standard Outlet Conditions Standard Model: SWB-224-50 Backward Inclined Centrifugal Utility Fan Actual Performance Requested Volume (CFM) 10,580 Actual Volume (CFM) 10,580 External SP (in. wg) 0.3 Total SP (in. wg) 0.3 OV (ft/min) 3,206 Fan RPM 1260 Operating Power (hp) 4.12 Tip Speed (ft/min) 8,081 Static Eff. (%) 13 FEG 80 Fan Configuration Quantity 1 Arrangement 10 Rotation CW Discharge Position TH Drive Type Belt Dimensional Weight w/o Acc's (lb) 554 Weight w/ Acc's (lb) 558 Max T Motor Frame Size 256 Motor Motor Mounted Yes Size (hp) 5 V/C/P 230/60/3 Enclosure ODP Motor RPM 1725 Windings 1 NEC FLA* (Amps) 15.2 Motor Pulley Type Adjustable Notes: All dimensions shown are in units of in. *FLA - based on tables 150 or 148 of National Electrical Code 2002. Actual motor FLA may vary, for sizing thermal overload, consult factory. LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 5 ft - dBA levels are not licensed by AMCA International Sones - calculated using AMCA 301 at 5 ft 9/11/2014 Printed Date: AKUMAL MOD. J Job: IK-J01 Mark: CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 1 of 18

description

zdcxv

Transcript of Akumal Mod. j - Submittal

  • Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 90 84 94 86 82 80 77 68 90 78 30

    Performance Corrections

    Elevation (ft) 0

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 4.1

    Inlet Conditions Standard

    Outlet Conditions Standard

    Model: SWB-224-50

    Backward Inclined Centrifugal Utility Fan

    Actual Performance

    Requested Volume (CFM) 10,580

    Actual Volume (CFM) 10,580

    External SP (in. wg) 0.3

    Total SP (in. wg) 0.3

    OV (ft/min) 3,206

    Fan RPM 1260

    Operating Power (hp) 4.12

    Tip Speed (ft/min) 8,081

    Static Eff. (%) 13

    FEG 80

    Fan Configuration

    Quantity 1

    Arrangement 10

    Rotation CW

    Discharge Position TH

    Drive Type Belt

    Dimensional

    Weight w/o Acc's (lb) 554

    Weight w/ Acc's (lb) 558

    Max T Motor Frame Size 256

    Motor

    Motor Mounted Yes

    Size (hp) 5

    V/C/P 230/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 15.2

    Motor Pulley Type Adjustable

    Notes:All dimensions shown are in units of in.

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J01Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 1 of 18

    camper1Resaltado
  • Model: SWB-224-50

    Backward Inclined Centrifugal Utility Fan

    Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with

    prepunched mounting holes - Adjustable motor plate - Corrosion resistant

    fasteners - Steel components are phosphatized and coated

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    Steel Scroll Housing

    Steel Wheel Construction

    Steel Inlet Cone

    Switch, NEMA-1, Toggle, Junction Box Mounted & Wired

    No Weatherhood--Unit for Indoor Use Only

    Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire

    Fan

    Unit Warranty: 1 Yr (Standard)

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J01Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 2 of 18

  • NOT DRAWN TO SCALECONNECTIONS

    INLET OUTLET

    25.88INLET

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    19

    26

    HO

    USIN

    G

    CE

    NTER

    LIN

    E

    END VIEW

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    0.634 Holes

    FAN FOOTPRINT

    SHAFT

    CENTERLINE

    *SIDE VIEW IS VIEWED FROM DRIVE SIDE

    SIDE VIEW

    41.50

    25.88

    19.00

    12.0034.50

    46.50

    2.50

    15.56

    15.56

    9.25

    26.75

    17.75

    40.63

    31.50

    26.25

    57.75

    33.63

    SWB-224-50 Backward Inclined Centrifugal Utility Fan

    Notes: All dimensions shown are in units of in.

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J01Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 3 of 18

  • Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 92 89 92 89 83 81 77 71 91 79 31

    Performance Corrections

    Elevation (ft) 0

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 4.1

    Inlet Conditions Standard

    Outlet Conditions Standard

    Model: SWB-222-50

    Backward Inclined Centrifugal Utility Fan

    Actual Performance

    Requested Volume (CFM) 9,100

    Actual Volume (CFM) 9,100

    External SP (in. wg) 0.3

    Total SP (in. wg) 0.3

    OV (ft/min) 3,358

    Fan RPM 1493

    Operating Power (hp) 3.98

    Tip Speed (ft/min) 8,697

    Static Eff. (%) 11

    FEG 75

    Fan Configuration

    Quantity 1

    Arrangement 10

    Rotation CW

    Discharge Position TH

    Drive Type Belt

    Dimensional

    Weight w/o Acc's (lb) 436

    Weight w/ Acc's (lb) 440

    Max T Motor Frame Size 215

    Motor

    Motor Mounted Yes

    Size (hp) 5

    V/C/P 230/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 15.2

    Motor Pulley Type Adjustable

    Notes:All dimensions shown are in units of in.

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J02Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 4 of 18

    camper1Resaltado
  • Model: SWB-222-50

    Backward Inclined Centrifugal Utility Fan

    Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with

    prepunched mounting holes - Adjustable motor plate - Corrosion resistant

    fasteners - Steel components are phosphatized and coated

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    Steel Scroll Housing

    Steel Wheel Construction

    Steel Inlet Cone

    Switch, NEMA-1, Toggle, Junction Box Mounted & Wired

    No Weatherhood--Unit for Indoor Use Only

    Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire

    Fan

    Unit Warranty: 1 Yr (Standard)

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J02Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 5 of 18

  • NOT DRAWN TO SCALECONNECTIONS

    INLET OUTLET

    23

    INLET

    HO

    USIN

    G

    CE

    NTER

    LIN

    E

    17

    23.5

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    END VIEW

    HO

    USIN

    G

    CE

    NTE

    RLIN

    E

    0.63

    4 Holes

    FAN FOOTPRINT

    SHAFT

    CENTERLINE

    *SIDE VIEW IS VIEWED FROM DRIVE SIDE

    SIDE VIEW

    39.63

    23.00

    17.00

    11.0032.50

    43.50

    2.50

    14.13

    14.13

    8.13

    26.00

    16.25

    36.88

    28.75

    23.75

    52.5

    30.50

    SWB-222-50 Backward Inclined Centrifugal Utility Fan

    Notes: All dimensions shown are in units of in.

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J02Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 6 of 18

  • Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 88 85 88 83 79 77 72 66 86 74 24

    Performance Corrections

    Elevation (ft) 0

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 4.6

    Inlet Conditions Standard

    Outlet Conditions Standard

    Model: SWB-222-30

    Backward Inclined Centrifugal Utility Fan

    Actual Performance

    Requested Volume (CFM) 7,583

    Actual Volume (CFM) 7,583

    External SP (in. wg) 0.35

    Total SP (in. wg) 0.35

    OV (ft/min) 2,798

    Fan RPM 1264

    Operating Power (hp) 2.49

    Tip Speed (ft/min) 7,361

    Static Eff. (%) 18

    FEG 75

    Fan Configuration

    Quantity 1

    Arrangement 10

    Rotation CW

    Discharge Position TH

    Drive Type Belt

    Dimensional

    Weight w/o Acc's (lb) 414

    Weight w/ Acc's (lb) 418

    Max T Motor Frame Size 215

    Motor

    Motor Mounted Yes

    Size (hp) 3

    V/C/P 230/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 9.6

    Motor Pulley Type Adjustable

    Notes:All dimensions shown are in units of in.

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J03Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 7 of 18

    camper1Resaltado
  • Model: SWB-222-30

    Backward Inclined Centrifugal Utility Fan

    Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with

    prepunched mounting holes - Adjustable motor plate - Corrosion resistant

    fasteners - Steel components are phosphatized and coated

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    Steel Scroll Housing

    Steel Wheel Construction

    Steel Inlet Cone

    Switch, NEMA-1, Toggle, Junction Box Mounted & Wired

    No Weatherhood--Unit for Indoor Use Only

    Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire

    Fan

    Unit Warranty: 1 Yr (Standard)

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J03Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 8 of 18

  • NOT DRAWN TO SCALECONNECTIONS

    INLET OUTLET

    23

    INLET

    HO

    USIN

    G

    CE

    NTER

    LIN

    E

    17

    23.5

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    END VIEW

    HO

    USIN

    G

    CE

    NTE

    RLIN

    E

    0.63

    4 Holes

    FAN FOOTPRINT

    SHAFT

    CENTERLINE

    *SIDE VIEW IS VIEWED FROM DRIVE SIDE

    SIDE VIEW

    39.63

    23.00

    17.00

    11.0032.50

    43.50

    2.50

    14.13

    14.13

    8.13

    26.00

    16.25

    36.88

    28.75

    23.75

    52.5

    30.50

    SWB-222-30 Backward Inclined Centrifugal Utility Fan

    Notes: All dimensions shown are in units of in.

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    IK-J03Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 9 of 18

  • Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 90 83 93 85 81 79 74 68 88 77 28

    Performance Corrections

    Elevation (ft) 0

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 3.9

    Inlet Conditions Standard

    Outlet Conditions Standard

    Model: SWB-224-75

    Backward Inclined Centrifugal Utility Fan

    Actual Performance

    Requested Volume (CFM) 9,578

    Actual Volume (CFM) 9,578

    External SP (in. wg) 1.5

    Total SP (in. wg) 1.5

    OV (ft/min) 2,902

    Fan RPM 1287

    Operating Power (hp) 5.08

    Tip Speed (ft/min) 8,257

    Static Eff. (%) 46

    FEG 80

    Fan Configuration

    Quantity 1

    Arrangement 10

    Rotation CW

    Discharge Position TH

    Drive Type Belt

    Dimensional

    Weight w/o Acc's (lb) 591

    Weight w/ Acc's (lb) 595

    Max T Motor Frame Size 256

    Motor

    Motor Mounted Yes

    Size (hp) 7 1/2

    V/C/P 230/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 22

    Motor Pulley Type Adjustable

    Notes:All dimensions shown are in units of in.

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J02Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 10 of 18

    camper1Resaltado
  • Model: SWB-224-75

    Backward Inclined Centrifugal Utility Fan

    Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with

    prepunched mounting holes - Adjustable motor plate - Corrosion resistant

    fasteners - Steel components are phosphatized and coated

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    Steel Scroll Housing

    Steel Wheel Construction

    Steel Inlet Cone

    Switch, NEMA-1, Toggle, Junction Box Mounted & Wired

    No Weatherhood--Unit for Indoor Use Only

    Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire

    Fan

    Unit Warranty: 1 Yr (Standard)

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J02Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 11 of 18

  • NOT DRAWN TO SCALECONNECTIONS

    INLET OUTLET

    25.88INLET

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    19

    26

    HO

    USIN

    G

    CE

    NTER

    LIN

    E

    END VIEW

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    0.634 Holes

    FAN FOOTPRINT

    SHAFT

    CENTERLINE

    *SIDE VIEW IS VIEWED FROM DRIVE SIDE

    SIDE VIEW

    41.50

    25.88

    19.00

    12.0034.50

    46.50

    2.50

    15.56

    15.56

    9.25

    26.75

    17.75

    40.63

    31.50

    26.25

    57.75

    33.63

    SWB-224-75 Backward Inclined Centrifugal Utility Fan

    Notes: All dimensions shown are in units of in.

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J02Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 12 of 18

  • Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 90 87 90 87 82 79 74 70 88 77 27

    Performance Corrections

    Elevation (ft) 0

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 4.0

    Inlet Conditions Standard

    Outlet Conditions Standard

    Model: SWB-222-50

    Backward Inclined Centrifugal Utility Fan

    Actual Performance

    Requested Volume (CFM) 7,982

    Actual Volume (CFM) 7,982

    External SP (in. wg) 1.5

    Total SP (in. wg) 1.5

    OV (ft/min) 2,945

    Fan RPM 1471

    Operating Power (hp) 4.37

    Tip Speed (ft/min) 8,566

    Static Eff. (%) 45

    FEG 75

    Fan Configuration

    Quantity 1

    Arrangement 10

    Rotation CW

    Discharge Position TH

    Drive Type Belt

    Dimensional

    Weight w/o Acc's (lb) 436

    Weight w/ Acc's (lb) 440

    Max T Motor Frame Size 215

    Motor

    Motor Mounted Yes

    Size (hp) 5

    V/C/P 230/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 15.2

    Motor Pulley Type Adjustable

    Notes:All dimensions shown are in units of in.

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J03Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 13 of 18

    camper1Resaltado
  • Model: SWB-222-50

    Backward Inclined Centrifugal Utility Fan

    Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with

    prepunched mounting holes - Adjustable motor plate - Corrosion resistant

    fasteners - Steel components are phosphatized and coated

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    Steel Scroll Housing

    Steel Wheel Construction

    Steel Inlet Cone

    Switch, NEMA-1, Toggle, Junction Box Mounted & Wired

    No Weatherhood--Unit for Indoor Use Only

    Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire

    Fan

    Unit Warranty: 1 Yr (Standard)

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J03Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 14 of 18

  • NOT DRAWN TO SCALECONNECTIONS

    INLET OUTLET

    23

    INLET

    HO

    USIN

    G

    CE

    NTER

    LIN

    E

    17

    23.5

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    END VIEW

    HO

    USIN

    G

    CE

    NTE

    RLIN

    E

    0.63

    4 Holes

    FAN FOOTPRINT

    SHAFT

    CENTERLINE

    *SIDE VIEW IS VIEWED FROM DRIVE SIDE

    SIDE VIEW

    39.63

    23.00

    17.00

    11.0032.50

    43.50

    2.50

    14.13

    14.13

    8.13

    26.00

    16.25

    36.88

    28.75

    23.75

    52.5

    30.50

    SWB-222-50 Backward Inclined Centrifugal Utility Fan

    Notes: All dimensions shown are in units of in.

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J03Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 15 of 18

  • Sound Power by Octave BandSound

    Data62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones

    Inlet 92 88 94 90 84 82 77 72 92 80 33

    Performance Corrections

    Elevation (ft) 0

    Airstream Temp.(F) 70

    Air Density (ft3) 0.075

    Drive Loss (%) 3.7

    Inlet Conditions Standard

    Outlet Conditions Standard

    Model: SWB-224-75

    Backward Inclined Centrifugal Utility Fan

    Actual Performance

    Requested Volume (CFM) 11,145

    Actual Volume (CFM) 11,145

    External SP (in. wg) 2

    Total SP (in. wg) 2

    OV (ft/min) 3,377

    Fan RPM 1495

    Operating Power (hp) 7.92

    Tip Speed (ft/min) 9,587

    Static Eff. (%) 46

    FEG 80

    Fan Configuration

    Quantity 1

    Arrangement 10

    Rotation CW

    Discharge Position TH

    Drive Type Belt

    Dimensional

    Weight w/o Acc's (lb) 602

    Weight w/ Acc's (lb) 606

    Max T Motor Frame Size 256

    Motor

    Motor Mounted Yes

    Size (hp) 7 1/2

    V/C/P 230/60/3

    Enclosure ODP

    Motor RPM 1725

    Windings 1

    NEC FLA* (Amps) 22

    Motor Pulley Type Adjustable

    Notes:All dimensions shown are in units of in.

    *FLA - based on tables 150 or 148 of National Electrical

    Code 2002. Actual motor FLA may vary, for sizing thermal

    overload, consult factory.

    LwA - A weighted sound power level, based on ANSI S1.4

    dBA - A weighted sound pressure level, based on 11.5 dB

    attenuation per Octave band at 5 ft - dBA levels are not

    licensed by AMCA International

    Sones - calculated using AMCA 301 at 5 ft

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J04Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 16 of 18

    camper1Resaltado
  • Model: SWB-224-75

    Backward Inclined Centrifugal Utility Fan

    Standard Construction Features:HOUSING: Steel housing with Lock-seam construction - Unit support angles with

    prepunched mounting holes - Adjustable motor plate - Corrosion resistant

    fasteners - Steel components are phosphatized and coated

    Options & Accessories:NEMA Premium Efficient Motor - meets NEMA Table 12-12

    Steel Scroll Housing

    Steel Wheel Construction

    Steel Inlet Cone

    Switch, NEMA-1, Toggle, Junction Box Mounted & Wired

    No Weatherhood--Unit for Indoor Use Only

    Coated with Permatector, Concrete Gray-RAL 7023, Standard Coating on Entire

    Fan

    Unit Warranty: 1 Yr (Standard)

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J04Mark:

    CAPS 4.15.1512 C:\Users\camper1\Documents\CAPS\AKUMAL MOD. J.gfcj Page 17 of 18

  • NOT DRAWN TO SCALECONNECTIONS

    INLET OUTLET

    25.88INLET

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    19

    26

    HO

    USIN

    G

    CE

    NTER

    LIN

    E

    END VIEW

    HO

    US

    ING

    CE

    NTE

    RLIN

    E

    0.634 Holes

    FAN FOOTPRINT

    SHAFT

    CENTERLINE

    *SIDE VIEW IS VIEWED FROM DRIVE SIDE

    SIDE VIEW

    41.50

    25.88

    19.00

    12.0034.50

    46.50

    2.50

    15.56

    15.56

    9.25

    26.75

    17.75

    40.63

    31.50

    26.25

    57.75

    33.63

    SWB-224-75 Backward Inclined Centrifugal Utility Fan

    Notes: All dimensions shown are in units of in.

    9/11/2014Printed Date: AKUMAL MOD. JJob:

    EK-J04Mark: