  • Installation instructions for

    Matching Resistance to TD 50/76

    No. TD142

    Acc.

    Date 29-11-10

    EC 10001 Page 1(1)

    1) Remove the cover.

    2) WTI is prepared for afterwards assembly of the "Matching Resistance", in hole left of

    the terminal block marked TD 50/76:

    a) Remove lock-nut, nut and washer from the "Matching Resistance" shaft.

    b) Put the shaft, from below, through the hole and turn the stop-pin in the smaller hole.

    c) Remount washer, nut and lock-nut.

    d) Connect the cables to the terminal 5-5 on the terminal block (i.e. parallel with the

    existing cables).

    e) Adjust the cables position along the terminal block.

    3) Check that the resistance over 5-5 is adjustable between 1-1.8 Ohm for TD 76 or

    0-1.7 Ohm for TD50.

    Locknut

    Nut

    Washer

    Qualitrol LLC. An ISO 9001 system certified company. Information subject to change without notice.

    Phone +46 8447 5460 Fax +46 8604 6810 Email [email protected]