Installation instructions for
Matching Resistance to TD 50/76
No. TD142
Acc.
Date 29-11-10
EC 10001 Page 1(1)
1) Remove the cover.
2) WTI is prepared for afterwards assembly of the "Matching Resistance", in hole left of
the terminal block marked TD 50/76:
a) Remove lock-nut, nut and washer from the "Matching Resistance" shaft.
b) Put the shaft, from below, through the hole and turn the stop-pin in the smaller hole.
c) Remount washer, nut and lock-nut.
d) Connect the cables to the terminal 5-5 on the terminal block (i.e. parallel with the
existing cables).
e) Adjust the cables position along the terminal block.
3) Check that the resistance over 5-5 is adjustable between 1-1.8 Ohm for TD 76 or
0-1.7 Ohm for TD50.
Locknut
Nut
Washer
Qualitrol LLC. An ISO 9001 system certified company. Information subject to change without notice.