AISC-20
-
Upload
deny-sitorus -
Category
Documents
-
view
80 -
download
0
description
Transcript of AISC-20
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 40 of 131 Design Columns for the lightest W10's and W12's section. Columns are to be sized for two options:Option I Continuous, Option II with Splices. Then prices are to be compared to select most economical option. Both explicit calculations or Column Design Tables may be used.
COLUMN B-2 LOAD TAKEOFF Dead load (psf) Live load (psf)
Penthouse Roof = 30 20 KLL= 4 Penthouse Floor = 100 80 Fy (ksi)= 50
Roof = 30 20
61 80 Bold Numbers are
61 80 Roof Live Loads
Tributary Areas (At):Width (ft) Length (ft)
At 1 = 36 30 1080At 2 = 18 15 270
At 3 = At 1 - At 2 = 810
Plan View At 1 (floors) : At 2 (penthouse floor) :
DL = 61 psf DL = 100 psf
LL = 80 psf LL = 80 psf
30 30
Penthouse At 3 (roof) :
DL = 30 psf
36 36 LL = 20 psf
Note: Live load reduction can be applied in accordance with ASCE 7-02 section 4.8.1
(see ASCE 7-02 Eq. 4-1)
Use the larger of:
L = reduced design live load value in psf L > 0.5*Lo (columns supporting one floor)
L > 0.4*Lo (columns supporting two or more floors)
if AI > 400 ft^2 live load reduction is allowed
AI (1) = 4320 >400 ft^2
AI (2) = 1080 >400 ft^2
L (2nd floor) = 38 psf > 32 psf, thus use = 38
L (3rd floor) = 38 psf > 32 psf, thus use = 38
L (penthouse floor) = 57 psf > 40 psf, thus use = 57
Red font indicates user input
3rd Floor =
2nd Floor =
L = Lo*(0.25+15/AI^0.5) ASCE 7-02 Eq. 4-1
Lo = unreduced live load in psf
AI = influence area
AI = Tributary area *KLL
Note: Roof Live loads are NOT allowed to be Reduced
At 1 At 3
At 2
PROJECT: STEEL BUILDING DESIGN CASE STUDY
SUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 41 of 131
COLUMN DESIGN
METHOD 1 - EXPLICIT CALCULATIONS
METHOD 2 - USE COLUMN DESIGN TABLES
CONTINUOUS - L =13 FEET
Notation:
Fcr - critical design force
Fy - specified yield strength, ksi
E - modulus of elasticity, ksi
K - effective length factor
l - Laterally unbraced length of member, in
r - governing radius of gyration about the axis of buckling, in
Begin Load Takeoff from roof and proceed downward:
From Ground floor to 2nd floor:
dead loads (psf) live loads (psf)
Pnth Roof 30 20
Pnth Floor 100 57
Roof 30 20
61 38
61 38
Pu (Pnth Roof) = 68 psf * A2 = 18 kipsPu (Pnth Floor) = 210 psf * A2 = 57 kips
Pu (Roof) = 68 psf * A3 = 55 kipsPu (3rd Floor) = 134 psf * A1 = 145 kipsPu (2nd Floor) = 134 psf * A1 = 145 kips
sum = 421 kips
PU = 421 kips
Note: Use column B2 for ALL Interior Columns.
Red font indicates user input
fPn - design compressive strength, kips
lc - width-thickness ratio
Ag - gross area of member, in2
3rd Floor
2nd Floor
Pu = [1.2*dead load + 1.6*live load]
Pu = [1.2*dead load + 1.6* roof live load]
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 42 of 131 COLUMN DESIGN From Ground floor to 2nd floor:
may not be the lightest. If this is the case, do explicit calculations and then try a section from the Table 1-25 LRFD. Use W8x24 as the smallest size (do not use W10’s or W12’s with a nominal
Analysis(Equation E2-1 LRFD p.16.1-27)
(Equation E2-2 LRFD p.16.1-27)
(Equation E2-3 LRFD p.16.1-27)
(Equation E2-4 LRFD p.16.1-27)
Fy = 50 ksiK = 1
Pu = 421 kips L = 13.00 ftE = 29000 ksi
Assume KL/r = 60 to start0.7930
Fcr = 38.4 ksi
Ag = 12.88
LRFD p.4-25Check W 12:
Select W12x53 KL/rx = 29.8
Ag = 15.6 KL/ry = 62.9ry = 2.48 in 0.83
rx/ry = 2.11 in Fcr = 37.4rx = 5.23 in 496.4
Section OK
LRFD p.4-26Check W 10:
Select W10x49 KL/rx = 35.9
Ag = 14.4 KL/ry = 61.4ry = 2.54 in 0.81
rx/ry = 1.71 in Fcr = 37.9rx = 4.35 in 464.5
Section OK
Red font indicates user input
Note: For small axial loads the smallest section from the column design Tables (Table 4-2 LRFD)
weight less than 24 lb/ft). If the column tables are used you only need to write down the section selected and its capacity.
fPn = 0.85 * Ag * Fcr
Fcr = (.658lc^2) * Fy when lc < 1.5
Fcr = (0.877 / lc2) * Fy when lc > 1.5
lc = (K * L/p * r) * (Fy / E)0.5
lc =
in2
in2
lc =
fPn = fPn > Pu ?
in2
lc =
fPn = fPn > Pu ?
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 43 of 131COLUMN DESIGN METHOD 1 - EXPLICIT CALCULATIONSMETHOD 2 - USE COLUMN DESIGN TABLESCONTINUOUS - L =13 FEETNotation:
Fcr - critical design force
Fy - specified yield strength, ksi
E - modulus of elasticity, ksi
K - effective length factor
l - Laterally unbraced length of member, in
r - governing radius of gyration about the axis of buckling, in
From Ground 2nd floor to 3rd floor:
dead loads (psf) live loads (psf)
Pnth Roof 30 20
Pnth Floor 100 57
Roof 30 20
61 38
- -
Pu (Pnth Roof) = 68 psf * A2 = 18 kipsPu (Pnth Floor) = 210 psf * A2 = 57 kips
Pu (Roof) = 68 psf * A3 = 55 kipsPu (3rd Floor) = 134 psf * A1 = 145 kips
sum = 275 kips
PU = 275 kips
Red font indicates user input
fPn - design compressive strength, kips
lc - width-thickness ratio
Ag - gross area of member, in2
3rd Floor
2nd Floor
Pu = [1.2*dead load + 1.6*live load]
Pu = [1.2*dead load + 1.6* roof live load]
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 44 of 131COLUMN DESIGN From Ground 2nd floor to 3rd floor:
may not be the lightest. If this is the case, do explicit calculations and then try a section from the Table 1-25 LRFD. Use W8x24 as the smallest size (do not use W10’s or W12’s with a nominal
Analysis(Equation E2-1 LRFD p.16.1-27)
(Equation E2-2 LRFD p.16.1-27)
(Equation E2-3 LRFD p.16.1-27)
(Equation E2-4 LRFD p.16.1-27)
Fy = 50 ksiK = 1
Pu = 275 kips L = 13.00 ftE = 29000 ksi
Assume KL/r = 60 to start0.7930
Fcr = 38.4 ksi
Ag = 8.43
LRFD p.4-25Check W 12:
Select W12x40 KL/rx = 30.4
Ag = 11.7 KL/ry = 80.4ry = 1.94 in 1.06
rx/ry = 2.64 in Fcr = 31.2rx = 5.13 in 309.9
Section OK
LRFD p.4-26Check W 10:
Select W10x39 KL/rx = 36.5
Ag = 11.5 KL/ry = 78.8ry = 1.98 in 1.04
rx/ry = 2.16 in Fcr = 31.8rx = 4.27 in 310.4
Section OK
Note: For small axial loads the smallest section from the column design Tables (Table 4-2 LRFD)
weight less than 24 lb/ft). If the column tables are used you only need to write down the section selected and its capacity.
fPn = 0.85 * Ag * Fcr
Fcr = (.658lc^2) * Fy when lc < 1.5
Fcr = (0.877 / lc2) * Fy when lc > 1.5
lc = (K * L/p * r) * (Fy / E)0.5
lc =
in2
in2
lc =
fPn = fPn > Pu ?
in2
lc =
fPn = fPn > Pu ?
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 45 of 131COLUMN DESIGN METHOD 1 - EXPLICIT CALCULATIONSMETHOD 2 - USE COLUMN DESIGN TABLESCONTINUOUS - L =13 FEETNotation:
Fcr - critical design force
Fy - specified yield strength, ksi
E - modulus of elasticity, ksi
K - effective length factor
l - Laterally unbraced length of member, in
r - governing radius of gyration about the axis of buckling, in
From 3rd floor to roof level:
dead loads (psf) live loads (psf)
Pnth Roof 30 20
Pnth Floor 100 57
Roof 30 20
- -
- -
Pu (Pnth Roof) = 68 psf * A2 = 18 kipsPu (Pnth Floor) = 210 psf * A2 = 57 kips
Pu (Roof) = 68 psf * A3 = 55 kips
sum = 130 kips
PU = 130 kips
Red font indicates user input
fPn - design compressive strength, kips
lc - width-thickness ratio
Ag - gross area of member, in2
3rd Floor
2nd Floor
Pu = [1.2*dead load + 1.6*live load]
Pu = [1.2*dead load + 1.6* roof live load]
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 46 of 131COLUMN DESIGN From 3rd floor to roof level:
may not be the lightest. If this is the case, do explicit calculations and then try a section from the Table 1-25 LRFD. Use W8x24 as the smallest size (do not use W10’s or W12’s with a nominal
Analysis(Equation E2-1 LRFD p.16.1-27)
(Equation E2-2 LRFD p.16.1-27)
(Equation E2-3 LRFD p.16.1-27)
(Equation E2-4 LRFD p.16.1-27)
Fy = 50 ksiK = 1
Pu = 130 kips L = 13.00 ftE = 29000 ksi
Assume KL/r = 60 to start0.7930
Fcr = 38.4 ksi
Ag = 3.99
LRFD p.4-25Check W 12:
Select W12x26 KL/rx = 30.2
Ag = 7.65 KL/ry = 103.3ry = 1.51 in 1.37
rx/ry = 3.42 in Fcr = 22.9rx = 5.17 in 149.0
Section OK
LRFD p.4-26Check W 10:
Select W10x30 KL/rx = 35.6
Ag = 8.84 KL/ry = 113.9ry = 1.37 in 1.51
rx/ry = 2.16 in Fcr = 19.4rx = 4.38 in 145.5
Section OK
Note: For small axial loads the smallest section from the column design Tables (Table 4-2 LRFD)
weight less than 24 lb/ft). If the column tables are used you only need to write down the section selected and its capacity.
fPn = 0.85 * Ag * Fcr
Fcr = (.658lc^2) * Fy when lc < 1.5
Fcr = (0.877 / lc2) * Fy when lc > 1.5
lc = (K * L/p * r) * (Fy / E)0.5
lc =
in2
in2
lc =
fPn = fPn > Pu ?
in2
lc =
fPn = fPn > Pu ?
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 47 of 131COLUMN DESIGN
From roof level to penthouse:
dead loads (psf) live loads (psf)
Pnth Roof 30 20
Pnth Floor - -
Roof - -
- -
- -
Pu (Pnth Roof) = 68 psf * A2 = 18 kips
sum = 18 kips
PU = 18 kips
Red font indicates user input
3rd Floor
2nd Floor
Pu = [1.2*dead load + 1.6*live load]
Pu = [1.2*dead load + 1.6* roof live load]
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 48 of 131COLUMN DESIGN
From roof level to penthouse:
may not be the lightest. If this is the case, do explicit calculations and then try a section from the Table 1-25 LRFD. Use W8x24 as the smallest size (do not use W10’s or W12’s with a nominal
Analysis(Equation E2-1 LRFD p.16.1-27)
(Equation E2-2 LRFD p.16.1-27)
(Equation E2-3 LRFD p.16.1-27)
(Equation E2-4 LRFD p.16.1-27)
Fy = 50 ksiK = 1
Pu = 18 kips L = 13.00 ftE = 29000 ksi
Assume KL/r = 60 to start0.7930
Fcr = 38.4 ksi
Ag = 0.56
LRFD p.4-25Check W 12:
Select W8x24 KL/rx = 45.6
Ag = 7.08 KL/ry = 96.9ry = 1.61 in 1.28
rx/ry = 2.12 in Fcr = 25.2rx = 3.42 in 151.5
Section OKLRFD p.4-26Check W 10:
Select W8x24 KL/rx = 45.6
Ag = 7.08 KL/ry = 96.9ry = 1.61 in 1.28
rx/ry = 2.12 in Fcr = 25.2rx = 3.42 in 151.5
Section OK
Note: For small axial loads the smallest section from the column design Tables (Table 4-2 LRFD)
weight less than 24 lb/ft). If the column tables are used you only need to write down the section selected and its capacity.
fPn = 0.85 * Ag * Fcr
Fcr = (.658lc^2) * Fy when lc < 1.5
Fcr = (0.877 / lc2) * Fy when lc > 1.5
lc = (K * L/p * r) * (Fy / E)0.5
lc =
in2
in2
lc =
fPn = fPn > Pu ?
in2
lc =
fPn = fPn > Pu ?
Lab Note: When beams and girders are framed to columns with simple shear connections, the columns are usually designed as concentrically loaded members.
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 49 of 131COLUMN DESIGN SPLICED vs CONTINOUS
Steel Prices per ton = $1,600
500
W10's
AnalysisContinous:Member Length (ft) Weight (tons) CostW10x49 52 1.274 $2,038
Wt. / ft (lb)= 49Total cost = $2,038
All columns spliced:Member Length (ft) Weight (tons) CostW10x49 13 0.3185 $510
Wt. / ft (lb)= 49W10x39 13 0.2535 $406
Wt. / ft (lb)= 39W10x30 13 0.195 $312
Wt. / ft (lb)= 30W8x24 13 0.156 $250
Wt. / ft (lb)= 243 splice = 0.75 $1,200
Total cost = $2,677
TOTAL COST = $2,038.40
Answer:Continuous columns are more economical
b -- indicates general value according to Modern Steel Construction. April 2000.
Wt of additional splice (lb)b =
PROJECT: STEEL BUILDING DESIGN CASE STUDYSUBJECT: INTERIOR COLUMN DESIGN (underneath penthouse) SHEET 50 of 131COLUMN DESIGN SPLICED vs CONTINOUS
Steel Prices per ton = $1,600
500
W12's
AnalysisContinous:Member Length (ft) Weight (tons) CostW12x53 52 1.378 $2,205
Wt. / ft (lb)= 53Total cost = $2,205
All columns spliced:Member Length (ft) Weight (tons) CostW12x53 13 0.3445 $551
Wt. / ft (lb)= 53W12x40 13 0.26 $416
Wt. / ft (lb)= 40W12x26 13 0.169 $270
Wt. / ft (lb)= 26W8x24 13 0.156 $250
Wt. / ft (lb)= 243 splice = 0.75 $1,200
Total cost = $2,687
TOTAL COST = $2,204.80
Answer:Continuous columns are more economical
Use : W10's sections Continuous columns are more economical
Total cost = $2,038.40
b - indicates general value according to Modern Steel Construction, April 2000
Wt of additional splice (lb)b =